Roberts Gorden 150, 175, 250, 200, 400 User Manual

...
Page 1
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
®
Combat
UHA-Series
Tubular Unit Heaters
(Standard Range)
Installation, Operation
& Service Manual
Models UHA[S]
150, 175, 200, 225
Fire Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
250, 300, 350, 400
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Quality in Any Language™
© Copyright 2007 Roberts-Gordon, LLC
Roberts-Gordon, LLC
1250 William Street P. O . Box 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com
P/N 111101NA 10 / 0 7 R e v. D
Page 2
Page 3
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility .....................................2
2.1 Wall Tag ....................................................................... 2
2.2 Corrosive Chemicals....................................................2
2.3 National Standards and Applicable Codes .................. 2
SECTION 3: Critical Considerations .....................................3
3.1 Basic Information.........................................................3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances .................3
3.4 Clearances to Combustibles ........................................3
3.5 Ventilation .................................................................... 3
3.6 Gas Supply ..................................................................3
3.7 Electrical Supply .......................................................... 3
3.8 Vent..............................................................................3
3.9 Separated Combustion Installation..............................3
SECTION 4: National Standards and Applicable Codes .....5
4.1 Gas Codes................................................................... 5
4.2 Aircraft Hangars ...........................................................5
4.3 Parking Structures and Repair Garages......................5
4.4 Electrical ...................................................................... 5
4.5 Venting.........................................................................5
4.6 High Altitude ................................................................ 5
SECTION 5: Major Components ............................................ 6
5.1 General........................................................................ 6
5.2 Suspension..................................................................6
SECTION 6: Venting................................................................ 7
6.1 Venting.........................................................................7
6.2 Vent Installation ...........................................................7
6.3 Unvented Operation.....................................................8
6.4 Horizontal Venting........................................................ 8
6.5 Vertical Venting............................................................8
6.6 Length Requirements ..................................................8
6.7 Vent Material................................................................9
SECTION 7: Air Supply......................................................... 13
7.1 Separated Combustion Installation............................. 13
7.2 Unvented Installation .................................................. 13
7.3 Building Ventilation .....................................................13
7.4 Outside Combustion Air Supply.................................. 13
SECTION 8: Gas Piping........................................................14
8.1 Connections............................................................... 14
SECTION 9: Wiring................................................................15
9.1 Positioning Thermostats ............................................ 15
9.2 Low Voltage Thermostat with One Heater ................. 15
9.3 UHA(S) Series Internal Wiring Diagram .................... 16
9.4 UHA(S) Series Ladder Wiring Diagram ..................... 17
9.5 Electrical Connection to the Heater ........................... 18
SECTION 10: Operation and Maintenance.......................... 19
10.1 Pre-Start-Up Checks ................................................ 19
10.2 Begin Start-Up ......................................................... 19
10.3 Complete the Start-Up .............................................21
SECTION 11: User Instructions............................................22
11.1 User Instructions .......................................................22
11.2 Heater Operation ......................................................22
11.3 Common User Controls.............................................22
11.4 Lighting Instructions ..................................................22
11.5 Simple Troubleshooting.............................................22
SECTION 12: Servicing.........................................................24
12.1 Servicing Instructions...............................................24
12.2 Burner Maintenance.................................................24
12.3 Fan/Motor Assembly Maintenance...........................24
12.4 Heat Exchanger Maintenance..................................24
12.5 Gas Valve Maintenance ...........................................24
12.6 Combustion Fan.......................................................24
12.7 Venting and Air Intake Pipe ......................................24
12.8 Maintenance Checklist .............................................25
SECTION 13: Troubleshooting .............................................27
13.1 General ....................................................................27
13.2 Troubleshooting For Automatic Ignition Burner
Systems...................................................................28
13.3 Troubleshooting for Flame Supervision System .......29
13.4 Troubleshooting for Gas Valves................................30
13.5 Troubleshooting for Combustion Fan........................30
SECTION 14: Replacement Parts .........................................31
14.1 Gas Valve .................................................................31
14.2 Burner Compartment ...............................................32
14.3 Ignition Electrode and Flame Probe.........................33
14.4 Combustion Fan Vertical Installation ........................34
14.5 Pressure Switch........................................................35
14.6 Ignition Control .........................................................36
14.7 Axial Fan/Guard/Motor Assembly.............................36
14.8 Limit Switches ..........................................................36
SECTION 15: Specifications.................................................37
15.1 Standard (Models 150 - 400) UHA(S) Series
Dimension Data .........................................................37
15.2 General Technical Data Table (All Models) ..............38
15.3 Technical Data Table (All Models) ............................38
SECTION 16: The ROBERTS GORDON® COMBAT
UHA-Series Warranty.....................................39
®
© 2007
Roberts-Gordon, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon, LLC.
Printed in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Installation Clearances and Clearances to
Combustibles.............................................................4
Figure 2: Suspension Methods ................................................. 6
Figure 3: Vent and Roof Detail .................................................. 9
Figure 4: Standard Vented Heater - Vertical and
Horizontal Vent Termination ...................................... 9
Figure 5: Standard Vented Heater - Common Vertical Vent
Termination.............................................................. 10
Figure 6: Separated Combustion Heater - Vertical and
Horizontal Vent Termination .................................... 11
Figure 7: Concentric Vent Box ................................................ 11
Figure 8: Concentric Vertical and Horizontal Vent
Termination - Separated Combustion Heater........... 12
Figure 9: Gas Connection....................................................... 14
Figure 10: Automatic Burner Control Sequence...................... 20
Figure 11: Gas Valve for Models UHA(S) 150 - 400................20
Figure 12: LED Diagnostic Codes...........................................22
Page 6
Page 7
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. Heaters are not approved for residential installation. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation. Thin sheet metal parts, including the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. Before installation, check that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible.
SECTION 1: HEATER SAFETY
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
1
Page 8
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
2.2 Corrosive Chemicals
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a Local
Do not use heater in an area containing corrosive chemicals.
Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the
Avoid the use of corrosive chemicals to ensure a longer life of the burner, heat exchanger and other parts.
Failure to follow these instructions can result in property damage.
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
CAUTION
• To never use heater as support for a ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for combustion, ventilation and distribution in accordance with local codes.
2.1 Wall Tag
A laminated wall tag is included with the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater.
A copy of the wall tag (P/N 91040031) is illustrated on the back cover.
Know your model number. Model number is found on the heater and in the Installation, Operation and Service Manual.
See Page 9, Figure 3 through Page
14, Figure 9.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen ele­ments (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA(S) heaters have automatic ignition burners for ON/OFF operation only.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with horizontal discharge.
• May be mounted on a shelf of non-combustible material.
• May be suspended from above (See Page 6, Figure 2) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table
on Page 37, Section 15.1. Drop rods must be a minimum of 3/8" diameter mild steel. Four suspension points (3/8" nuts) are located on top of the heater.
• Must be installed in a manner which allows access to all serviceable components. See Page 4, Figure 1 for details.
SECTION 3: CRITICAL CONSIDERATIONS
3.7 Electrical Supply
A permanent 120 V 60 Hz 1 Ø electrical supply is required for the main electrical power. The heater also requires suitable controls in accordance with Section 9.
3.8 Vent
Choose heater orientation to allow for the proper location of the vent. Each heater must be fitted with a correctly sized sealed vent system.
If vented horizontally, no other appliance may be connected to the vent.
See Page 7, Section 6.
3.9 Separated Combustion Installation
For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.
Separated combustion units may not be common vented.
See Page 7, Section 6.
3.3 Minimum Required Installation Clearances
Clearances around the heater and vent must be as indicated
on Page 4, Figure 1; Page 9, Figure 3
through Page 12, Figure 8 to ensure access for
servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
1. If clearances to combustibles are not indicated,
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national codes.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight.
3
Page 10
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
Figure 1: Installation Clearances and Clearances to Combustibles
Installation Clearances
Roof Terminal
(Optional separated
combustion concentric
venting shown.)
Top
Wall
Terminal
24" for adequate air flow access axial fan.
20' (6.0 m) - 30' (9.1 m)
Max. Mounting Height*
10'
(3 m)
* Recommended mounting height varies with heater input.
Clearances to Combustibles
6"**
(15 cm)
Clearance to Vent: 2" (5 cm) Heaters may be mounted at a higher level if destratification fans are installed.
Note: Venting directly from top of heater not applicable
**31" (79 cm) minimum is necessary for servicing.
on Models 150 - 400.
The heater must always be installed at least 6' (2 m) above the floor. The vent pipe must have clearance from combustibles by 2" (5 cm). If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.
6"
(15 cm)
31" (79 cm)
3"
4
Page 11
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
• In accordance with the Standard for Parking Structures NFPA 88A, heaters must be located a minimum of 18" (50 cm) below the floor-ceiling assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision, heaters must not be installed less than 8' (2.4 m) above the floor.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.6 High Altitude
These heaters are approved for installations up to 2000' (610 m) (US), 4500' (1370 m) (Canada) without modification. Consult factory if US installation is above 2000' (610 m) or Canadian installation is above 4500' (1370 m).
5
Page 12
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8" Threaded Rod
Nut
Washer
Riv Nut
Washer
3/8"
Threaded
Rod
Nut
Unistrut
Channel Nut
SECTION 5: MAJOR COMPONENTS
5.1 General
Heaters are designed for installation above 6' (1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.
5.2 Suspension
WARNING
Crush Hazard
Use 3/8" threaded rod minimum.
Failure of the supports can result in death, injury or property damage.
For typical suspension, See Page 6, Figure 2.
Figure 2: Suspension Methods
Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.
6
Support Points
Page 13
SECTION 6: VENTING
6.1 Venting
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code. Any portion of vent pipe passing through a combustible wall must have an listed thimble to conform with the above codes.
The heater may be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes
and
Page 8, Section 6.3 for further information.
Unvented operation also requires compliance with the clearances to combustibles given
on Page 4,
Figure 1.
The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.
Vent terminal must be beyond any combustible overhang.
Secure all joints with corrosion resistant #8 x 3/8" sheet metal screws.
For single wall venting, pressure sensitive aluminum tape or silicone sealant must be used to seal all joints.
Aluminum tape shall have a minimum temperature rating of 400° F (204° C) and meet SMACNA AFTS­100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).
6.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.
NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.
6.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
SECTION 6: VENTING
mechanical air supply inlet to any building. The vent shall not terminate within 3' (.9 m) of a
window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
6.2 Vent Installation
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
For vented units, the vent must terminate outside of the building.
Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed Figure 8. The joints between the vent terminal and the roof or wall must be properly sealed. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.
For vent termination See Page 9, Figure 3 through Page 12, Figure 8.
6.2.1 Standard Vented Heaters (Models UHA 150 - 400)
The vent must be fitted with a low resistance terminal. Figure 4. Standard vented heaters do not allow outdoor air intake for combustion air.
on Page 9, Figure 3 through Page 12,
See Page 9, Figure 3 through Page 9,
7
Page 14
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
6.2.2 Separated Combustion Heaters (Models UHAS 150 - 400)
The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals.
See Page 12, Figure 8. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof.
6.3 Unvented Operation
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
For unvented operation in commercial installations, sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).
WA RN IN G: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
6.4 Horizontal Venting
Horizontally vented heaters must be individually vented.
Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3 m). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. For vents pitched up toward the vent terminal, place the condensation drain within 5' (1.5 m) of the heater.
In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.
Instead of an insulated vent terminal, a listed thimble (with 2" air gap) may be used with a 4" vent cap (P/N
90502102).
6.5 Vertical Venting
Vertically vented heaters can be common vented (up to 4 heaters). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. Vent from the rear of the heater cabinet then run the vent vertically and use a condensate drain at the bottom of the vertical vent. Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3 m).
For 4'' (10 cm), an approved vent cap (P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap (P/N 90502103) must be used.
For common vertical venting of more than two heaters,
See Page 10, Figure 5.
A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.
6.6 Length Requirements
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. The entire vent should be insulated with foil faced fiberglass insulation (1/2" thick, 1-1/2# density minimum).
Maximum Vent Lengths Table
Model UHA(S)
150 - 400
40 ft (12.2 m) 1 35 ft (10.7 m) 2
30 ft (9.1 m) 3 25 ft (7.6 m) 4 20 ft (6.1 m) 5
# of Elbows
8
Page 15
SECTION 6: VENTING
6.7 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to
Page 7, Section
6.2.
If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent manufacturer's clearance from vent material is maintained. Seal annular space of the type B-1 vent as well as all joints in the remaining vent.
Figure 3: Vent and Roof Detail
Vent
Terminal
Roof
2" Air Gap to
Combustible Material
Flashing
or Rain Collar
Listed Thimble
Vent
Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination
Vent Terminal
Flashing (By Others)
Listed
Thimble
(2" Clearance)
4" Dia.Vent
Vertical
Option
Model Vent Diameter Part Number
UHA 150 - 400 4" (10 cm) 90502102
90° Bend
Horizontal
Option
Vent
Condensate
Trap to Drain
(Optional)
Listed Thimble (2" Clearance)
Flashing (By Others)
12" (31 cm) Minimum
Vent Terminal
Note: Vent supports not shown.
9
Page 16
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Figure 5: Standard Vented Heater - Common Vertical Vent Termination
Type "B" vent cap (7" or 8") may be used. (These are not available
SIDE VIEW
from Roberts-Gordon.)
Type "B" Vent Pipe
TOP VIEW
18" (46 cm)
Min.
The last section of vent pipe passing through the roof or wall may be Type "B" vent pipe. All other vent materials in the building must be single wall vent pipe.
4" (10 cm)
Single Wall Pipe
"D"
Roof
Flashing
Roof
Approved
Thimble
(If Applicable)
Single Wall Pipe
"D" Area must equal sum
of open area of
individual vents.
4" (10 cm)
Single Wall Pipe
10
Page 17
Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent Termination
12" (31 cm)
Minimum from air inlet to vent
termination (may be horizontal
or vertical clearance).
SECTION 6: VENTING
Air Intake*
90° Bend
Model Vent Diameter Terminal P/N
UHAS 150 - 400 4" (10 cm) 90502102
Model *Air Intake Diameter Terminal P/N
UHAS 150 - 250 4" (10 cm) 90502102 UHAS 300 - 400 5" (13 cm) 90502105
Figure 7: Concentric Vent Box
Vertical
Option
Vent
Horizontal
Option
Air Intake
Vent
Condensate
Trap to Drain
(Optional)
Listed Thimble through
Combustible Wall
12" (31 cm) Minimum from air inlet to vent termination (may be horizontal or vertical clearance).
Air Intake Termination
Vent Termination
12" (31 cm) Minimum from wall to vent termination.
Note: Vent supports not shown
4" (10 cm) or 5" (13 cm)
Seal joint between single wall and Type B vent with silicone sealant.
Toward Heater
4" (10 cm) Single Wall Vent Pipe (By Others)
One Piece Double Wall Type B-1 Vent Pipe (By Others)
Concentric
Use 3 sheetmetal screws equally spaced around joint.
Use 3 sheetmetal screws equally
Vent Box
spaced around collar.
Toward Outside
6" (15 cm) or 8" (20 cm) Single Wall Inlet Air Pipe (By Others)
11
Page 18
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Figure 8: Concentric Vertical and Horizontal Vent Termination
4" Type B-1
UHA 150-250: 6" Dia. Single Wall UHA 300-400: 8" Dia. Single Wall
Concentric Vent Box
Air Intake*
Vent
Vertical
Option
10' (3 m)
Maximum
Combustion Air Terminal
Vent
Air Intake*
Vent Terminal with Baffle Plate
Storm Collar (By Others) (Attach with 3 sheet metal screws.)
Flashing (By Others)
Condensate Trap to Drain (Optional)
Horizontal Option
- Separated Combustion Heater
6" (16 cm)
Minimum
12" (31 cm)
Maximum
4"
Type
B-1
Vent
Vent Terminal with Baffle Plate
Vent
Description Part Number Qty. Concentric Vent Kit (150 - 250) UHVK1
Concentric Vent Box Top & Side Assembly 90504113 1 Concentric Vent Box Bottom Assembly 90504112 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" Vent Terminal with Baffle Plate 90502102R 1 6" Combustion Air Terminal 90502103 1
Description Part Number Qty. Concentric Vent Kit (300 - 400) UHVK2
Concentric Vent Box Top & Side Assembly 90504013 1 Concentric Vent Box Bottom Assembly 90504012 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" Vent Terminal with Baffle Plate 90502102R 1 8" Combustion Air Terminal 90502104 1
Concentric Vent Box
Combustion Air Terminal
Model Vent Diameter
UHAS 150 - 400 4" (10 cm)
Model *Air Intake Diameter
UHAS 150 - 250 4" (10 cm) UHAS 300 - 400 5" (13 cm)
Storm Collar (By Others) (Attach with 3 sheet metal screws.)
12
Page 19
SECTION 7: AIR SUPPLY
7.1 Separated Combustion Installation
When installed as a separated combustion heater, the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate space around heater to provide air for the axial air distribution fan.
7.2 Unvented Installation
It is important to ensure that there is adequate fresh air supply at all times for both combustion and heating requirements in accordance with local and national codes.
WARNING: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
7.3 Building Ventilation
Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.
SECTION 7: AIR SUPPLY
7.4 Outside Combustion Air Supply
If outside combustion air supply is required, separated combustion model (UHAS) heaters must be used.
IMPORTANT: If the building has a slight negative pressure or corrosive contaminants such as halogenated hydrocarbons are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints. The air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal must not be more than 1' (31 cm) above the vent terminal.
7.4.1 Length Requirements
Follow the constraints listed on Page 8, Section 6.6.
13
Page 20
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 8: GAS PIPING
• Meter and service must be large enough to
WARNING
handle all the burners being installed plus any other connected load. The gas pipe which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" w.c. When gas piping is not included in the layout drawing, contact the local gas supplier.
Fire Hazard
Fire Hazard
Connect gas supply according to Figure 9.
Connect gas supply according to Figure 9.
Gas can leak if not installed properly.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death,
Failure to follow these instructions can result in death,
injury or porperty damage.
injury or property damage.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• A minimum 1/8" NPT plugged tapping accessible for test connection must be installed immediately upstream of the gas supply connection to the heater.
It is important that the gas supply pipe and the electrical connections do not support any of the heater’s weight.
A gas meter is connected to the service pipe by the gas supply company. An existing meter should be checked, preferably by the company, to ensure that the meter is adequate for the rate of gas supply required.
Installation pipes must be fitted in accordance with local and national codes. Pipes of smaller size than the heater inlet gas connection should not be used.
• For suspended heaters, an approved metal flexible connection between the isolating valve and the heater may be used. To reduce
pressure loss, use one pipe size larger than the heater gas connection.
IMPORTANT - The complete installation must be purged and tested for gas soundness in accordance with local and national codes.
• Do not high pressure (in excess of 1/2 psi
[14" w.c.]) test the gas piping with the burner connected. Close manual shut-off valve
8.1 Connections
Connect the heater to the gas supply ensuring that the final connections are as follows:
• Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes.
during any pressure testing equal to or less than 1/2 psi (14" w.c.). Failure to follow these
instructions can result in property damage. Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
Figure 9: Gas Connection
• Hold gas nipple securely with pipe wrench when attaching the flex gas connector.
• Do not twist flexible
gas connector.
• Ensure all
joints are gas tight.
14
Do not bend flexible
gas connector
sharply.
Gas Shut-off Valve
Union
Connection
Option A:
Stainless Steel Flex Gas Connector
Option B:
Medium or Heavy Gauge Pipe Gas Connector
Drip Leg
Cap
Page 21
SECTION 9: WIRING
WARNING
Electrical Shock Hazard
Disconnect electrical power and gas supply before servicing.
This appliance must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death or electrical shock.
All heater models require constant 120 V 60 Hz 1Ø power supply. Check heater(s) rating plate for electrical rating for proper circuit sizing. For servicing, a disconnect switch of proper electrical rating should be installed in the vicinity of the heater.
All heaters are equipped with thermostat connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in accordance with local codes. In the absence of local
SECTION 9: WIRING
codes in accordance with: United States: refer to
®
National Electrical Code
ANSI/NFPA 70 - latest revision Canada: refer to Canadian Electrical Code CSA C22.1 Part I - latest revision.
9.1 Positioning Thermostats
A room thermostat or ROBERTS GORDON® control should be mounted on a vibration-free wall or column at a height of approximately 5' (1.5 m) from the floor to measure the ambient temperature. It should be clear of both cold drafts and the direct path of warm air from the heater. Avoid mounting thermostat on outside walls or in areas directly exposed to radiant heat or sunlight. Install wall tag in a visible location near thermostat.
9.1.1 Fan Control
The heater’s axial fan can be used during the off­season for air circulation. A low voltage thermostat with fan control must be used.
See Page 15, Section
9.2 for thermostat connection details.
9.2 Low Voltage Thermostat with One Heater
24 Volt Thermostat Heating Only
R
W
24 Volt Thermostat with Fan Control
R
G
W
C
Electrical
Supply
Terminal
Strip
R G W C
Terminal
Strip
R G
W
C
Electrical
Supply
15
Page 22
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
9.3 UHA(S) Series Internal Wiring Diagram
BLOWER
PRESSURE SWITCH
LIMIT SWITCH (UH 300, 350, 400 ONLY)
ELECTRODE
AXIAL FAN
MANUAL RESET LIMIT SWITCH
(UH 30 - 125 ONLY)
SENSE
ORANGE
ORANGE
AXIAL FAN (UH 300, 350, 400 ONLY)
WHITE
GREEN
BLACK
WHITE
GREEN
BLUE
BLUE
LIMIT SWITCH
BLACK
BLACK
BLACK
GREEN
WHITE
ORANGE
FLAME
WHITE
GREEN
TRANSFORMER
BLUE
HOT
24 VAC
3
GROUND
ORANGE
IGNITION MODULE
ACC
BLACK
2
6
5
YELLOW
1
4
L1
L2
WHITE
BLACK
31
45
R
G
W
C
CMB BLOWER
L1
YELLOW
GREEN
BLACK
BLACK
BLACK
GAS VALVE
BROWN
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W= HEAT DEMAND INPUT FROM THERMOSTAT (WHITE) C = COMMON SIDE OF TRANSFORMER
THERMOSTAT INPUT: FIELD SUPPLIED
BLACK
BLACK
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and 600 volts. For supply connections use No. 14 AWG or larger wires.
16
Page 23
9.4 UHA(S) Series Ladder Wiring Diagram
SECTION 9: WIRING
120 VAC
FLAME
SENSOR
ELECTRODE
CIRCULATION FAN
CIRCULATION FAN
COMBUSTION BLOWER
2
1
3 6
4
5
FLAME
IGNITION MODULE
SPARK
TRANSFORMER
GAS
VALVE
PRESSURE SWITCH
LIMIT SWITCH
UH 300, 350, 400 Only
LIMIT SWITCH (UH 300, 350, 400 ONLY)
MANUAL RESET LIMIT SWITCH (UH 30 - 125 ONLY)
THERMOSTAT CONNECTION
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and 600 volts. For supply connections use No. 14 AWG or larger wires.
17
Page 24
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
9.5 Electrical Connection to the Heater
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1 L2
Ground
Black
White
Green
BX Connector
Junction Box
Note: Junction box is not provided with heater. Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
18
Page 25
SECTION 10: OPERATION AND MAINTENANCE
Installation, service, and annual inspection of the heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation, or service of this equipment. All components are accessed via the door secured by 4 sheet metal screws. Opening the door exposes live electrical connections and hot components.
WARNING
Electrical Shock Hazard
Use extreme caution during start-up.
Controls compartment contains live electrical connections.
SECTION 10: OPERATION AND MAINTENANCE
10.1.2 Electrical Checks
All pre-start-up checks must be carried out before start-up the heater.
1. Check that all site wiring is connected in accordance with the appropriate wiring diagram on Page 16, Section 9.3.
10.1.3 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for gas tightness and purged in accordance with local and national codes.
Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
10.1.4 Mechanical Checks
1. Check that the fan is free to run and delivery louvers are turned to give required
air deflection.
2. Check that the flue (and air intake for separated combustion units) is installed in accordance with these instructions and local regulations.
Failure to follow these instructions can result in death or electrical shock.
10.1 Pre-Start-Up Checks All pre-start-up checks must be carried out
before lighting the heater.
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
10.1.1 Louvers
Where fitted, the air delivery louvers need to be set during start-up to give the required air distribution (optional vertical louvers).
WARNING
10.2 Begin Start-Up
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off and power supply turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room temperature. The automatic ignition sequence will now begin as described on Page 20, Figure 10.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
19
Page 26
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
½PSI IN
C
ON
OFF
Regulator
Outlet Pressure
Gas Inlet
Inlet Pressure
Top View
End View
Figure 10: Automatic Burner Control Sequence
Burner Sequence for Ignition Control
START
Thermostat 24 V
RUN
SHUT DOWN
Flue Fan
Pressure
Switch
Ignition Spark
Start Gas Valve
Flame Signal
Axial Fan
NO
P
C
NC
*Purge time begins at pressure switch change over.
30 Sec. Purge*
ts = 10 seconds
30 Sec. Delay 90 Sec. Delay
Required Incoming Signals
Signals Output By Control
Figure 11: Gas Valve for Models UHA(S) 150 - 400
30 Sec. Post Purge
If at any stage the flame fails, the control will retry for ignition. The control has four trials for ignition before a one hour lockout.
Description Part Number
Gas Valve 150 - 225 NG 90032505 Gas Valve 150 - 225 LP 90032506 Gas Valve 250 - 400 NG 90032520 Gas Valve 250 - 400 LP 90032521
20
Page 27
SECTION 10: OPERATION AND MAINTENANCE
10.2.2 Start-Up the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.
2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Tables for the correct gas and model
on Page 38, Section 15.3.
NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Tables
on
Page 38, Section 15.3 for inlet pressure
requirement.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the commission.
10.2.5 External Controls
External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.
10.3 Complete the Start-Up
Ensure that all covers are fitted correctly and all test points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles and the user instructions
on Page 22,
Section 11 through Page 22, Section 11.5 and all
warnings defined in this manual.
Check Gas Rate
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
10.2.3 Pressure Switch
The pressure switch is factory pre-set for each model and is not adjustable.
10.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest setting and the main burner will stop.
The fan will run until it is stopped automatically by the fan thermostat.
Do not use a disconnect switch for control of heater. Disconnect switch will turn off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly. Only use the disconnect switch for turning off heater for service or during off-season.
21
Page 28
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 11: USER INSTRUCTIONS
11.1 User Instructions
The UHA(S) Series heaters are fully automatic and operate from the external controls fitted on site.
11.5 Simple Troubleshooting
Some possible reasons for the heater not operating are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not "ON".
4. A limit switch may have operated. This may be caused by an interruption of the electrical supply, failure of the distribution fan or vent or heat exchanger blockage.
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in death or electrical shock.
If a temperature limit switch persistently trips, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
11.2 Heater Operation
When the heater has been switched on by the thermostat installed on site, the main burner will automatically turn on.
The burner control box will control the safe ignition of the flame.
All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation of this heater.
11.3 Common User Controls
11.4 Lighting Instructions
11.4.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site controls are "ON".
NOTE: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as described
on Page 20, Figure 10. The heater will now operate automatically under the control of the on site controls.
11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry for ignition (4 trials total). After 4 unsuccessful ignition trials, the control will put the heater into lockout for 1 hour.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected. There is an LED light on the ignition control that flashes codes to assist in fault correction.
See Figure 12 for LED indication
codes.
Figure 12:
LED INDICATION FAULT MODE
Slow Flash Normal Operation - No call for heat.
Fast Fl ash Normal Operation - Call for heat.
2 Flashes Ignition Lockout - No flame detected.
3 Flashes Airflow Fault - Pressure switch open or closed.
4 Flashes Temperature Limit or
5 Flashes Flame Sense Error - Gas valve not energized.
Steady On Internal Control Failure
LED Diagnostic Codes
Manual Reset Limit Switch Open
11.4.2 To Turn the Heater Off
Set the thermostat to the "OFF" position. The burner will turn off immediately. The fan will continue to run for 90 seconds. To restart, turn the thermostat above room
temperature.
22
Page 29
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
SECTION 11: USER INSTRUCTIONS
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
23
Page 30
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 12: SERVICING
12.1 Servicing Instructions
After start-up, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be necessary.
12.3 Fan/Motor Assembly Maintenance
The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.
WARNING
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
NOTE 1: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions Page 21, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts through Page 30, Section 13.5.
NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.
NOTE 3: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.
12.2 Burner Maintenance
1. Open the door and remove the burner compart­ment cover. See Page 32, Section 14.2.
2. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner.
3. Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.
on Page 19, Section 10 through
on Page 27, Section 13
See Page 32, Section 14.2.
12.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.
12.5 Gas Valve Maintenance
No regular maintenance is required on this device. To change gas control valves,
See Page 31, Step
14.1 and Page 35, Section 14.5.
Do not repair or disassemble gas valve. Replace faulty gas valves with genuine
®
ROBERTS GORDON
replacement parts.
12.6 Combustion Fan
The combustion fan should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the combustion fan from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet
See Page 34, Section 14.4). Ensure that the fan is
( free to run and that the fan wheel is clean.
12.7 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that all seams are sealed and suspension points secure. Repair suspension points if any part of the venting or combustion air pipe is sagging. Check to make sure any insulation is not missing or in poor condition. Replace as necessary. Check all venting and air intake components to ensure they are in good condition, gas tight and corrosion-free.
24
Page 31
SECTION 12: SERVICING
12.8 Maintenance Checklist Installation Code and Annual Inspections: All
WARNING
installations and service of ROBERTS GORDON equipment must be performed by a contractor qualified in the installation and service equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS
®
GORDON
manuals and all applicable
governmental authorities pertaining to the
Explosion Hazard
Service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
installation, service and operation of the equipment. To help facilitate optimum performance and safety,
Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
GORDON necessary, using only replacement parts sold and supplied by Roberts-Gordon.
®
equipment and perform service where
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 3, Section 3.
®
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger or in the louvers.
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits from the screen.
See Page 13, Section 7.
Combustion Air Intake Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Heat Exchanger Make sure there are no cracks.
Gas Line and Shut-off Valves
See Page 14, Section 8.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Check for gas leaks. See Page 14, Section 8.
25
Page 32
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Burner Observation Window
Combustion Fan Scroll,
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Wheel and Motor Inshot Burners and
Orifices
Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark Igniter Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
Thermostat There should be no exposed wire or damage to the device or wiring.
See Page 19, Section 10.
Suspension Points Make sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 6, Figure 2.
Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas Valve Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed)
26
Page 33
SECTION 13: TROUBLESHOOTING
13.1 General
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Failure to follow these instructions can result in death, injury or property damage.
Start
SECTION 13: TROUBLESHOOTING
WARNING
Explosion Hazard
Are gas & electrical
supplies on?
Ye s
Does axial fan run
immediately upon supplying
power to heater?
No
Is ignition control showing a
"2 flashes" led code?
No
Does the combustion
fan run?
No
Ye s
Ye s
No
Turn on supplies.
Wait 10-15 minutes for limit
switch to cool. Does fan
stop running?
Replace temperature
limit switch.
Burner has locked out due
to ignition failure. Use
Troubleshooting for Automatic
Ignition Burner Systems
section to test burner.
Use Troubleshooting for
Combustion Fan section to
No
test fan.
Ye s
Fan and limit switch are
operating normally.
Ye s
Ye s
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
Ye s
Heater Operating
TROUBLESHOOT ENDS.
Has burner Locked Out?
No
Ye s
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
If problems persist, contact
No
Roberts-Gordon, LLC at
www.rg-inc.com
No
The limit switch has
tripped. See Manual Reset
Limit Switch Figure.
Ensure proper air flow
clearance for axial fan.
Open louvers slightly.
Replace axial fan if it does
not operate.
Ye s
No
Replace limit switch.
27
Page 34
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
13.2 Troubleshooting For Automatic Ignition Burner Systems
Start
Are gas & electrical
supplies on?
Ye s
Are external controls (i.e. Thermostat) on?
Ye s
Is ignition control showing
a "4 flashes" led code?
No
Does flue fan run?
No
No
Ye s
No
Turn on supplies.
Turn on controls.
Press in reset button on
manual reset limit switch
Is 120 V supply at fan
connections?
Burner control faulty or wiring
connections faulty. Repair
or replace as necessary
No
WARNING
Electrical Shock Hazard
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can result in death or electrical shock.
Ye s
Flue fan faulty; replace
Ye s
Does air pressure switch
change over?
Ye s
Wait 30 - 40 seconds.
Does ignition spark operate?
Ye s
Does the flame light?
Ye s
Is ignition control showing
a "2 flashes" led code?
No
Heater Operating
TROUBLESHOOT ENDS.
Check for too much vent/air inlet duct. Check for blockage in vent and combustion air circuit. Check for faulty air pressure
No
switch. Check pressure switch hoses for leaks or cracks. Do not attempt to circumvent pressure switch circuit to place unit in operation.See Pressure Switch section for details.
Is ignition lead okay and
No
No
Ye s
No
connected?
Is spark electrode okay?
Is the gas valve operating?
To test valve, See
Troubleshooting for Gas
Valves section.
Is the flame current at
least 1 µAmp DC when
the flame ignites?
If problems persist, contact
Roberts-Gordon, LLC at
www.rg-inc.com
Ye s
No
Ye s
Ignition control faulty;
replace.
See Ignition Control section.
Replace valve.
Trace fault in supervision
system. See
Troubleshooting
for Flame Supervision
System section.
For your safety and optimum heater performance, use only ROBERTS GORDON
Conduct start-up procedure as shown on Page 19, Section 10.
®
replacement parts.
28
Page 35
13.3 Troubleshooting for Flame Supervision System
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.
START
Connect a DC ammeter in
series with the flame probe.
SECTION 13: TROUBLESHOOTING
Is the flame present and
at least 1 µA DC flame
current?
Ye s
Is there a current flowing in the
flame probe circuit with no
flame present?
No
Does lockout occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
Use General
Troubleshooting section to
No
Ye s
Ye s
No
trace the fault.
Is the connecting lead damaged? Is the flame probe damaged or touching earthed
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
No
Repair or replace as
necessary.
If problems persist, contact
Roberts-Gordon, LLC at
www.rg-inc.com
Repair or replace as
Ye s
Ye s
necessary.
Replace ignition control.
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
29
Page 36
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
13.4 Troubleshooting for Gas Valves
START
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
Ye s
Does gas pressure at outlet
of the valve rise when
valve turns on?
Ye s
Ye s
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Ye s
Valve Operating
TROUBLESHOOT ENDS.
13.5 Troubleshooting for Combustion Fan
No
No
No
No
Fault elsewhere.
Correct pressure problem.
Valve or ignition control
faulty. Replace with
one of correct type.
Valve faulty.
Replace with one of
correct type.
If problems persist, contact
Roberts-Gordon, LLC at
www.rg-inc.com
START
Does combustion fan run
automatically when there
is a call for heat?
Ye s
Does fan turn on and
off while burner is firing
continously?
No
Fan Operating
TROUBLESHOOT ENDS.
No
Ye s
No
Correct power
supply problem.
Ye s
Fan motor faulty.
Replace with correct type.
Check fan motor leads for
loose connections.
If problems persist, contact
Roberts-Gordon, LLC at
www.rg-inc.com
For your safety and optimum heater performance,
®
use only genuine ROBERTS GORDON
replacement parts.
Conduct start-up procedure as shown on Page 19, Section 10.
30
Page 37
SECTION 14: REPLACEMENT PARTS
See warnings and notes on Page 24, Section 12 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the door on the side of the heater. Remove the sheetmetal screws.
14.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
SECTION 14: REPLACEMENT PARTS
½PSI IN
C
ON
Description Part Number
Gas Valve, NG (Models UHA[S] 150 - 225) 90032505 Gas Valve, LP (Models UHA[S] 150 - 225) 90032506 Gas Valve, NG (Models UHA[S] 250 - 400) 90032520 Gas Valve, LP (Models UHA[S] 250 - 400) 90032521
Follow steps in Section 14.2 and Section 14.2.1 to remove gas valve/manifold.
Replace in reverse order. Verify that the gas flow direction of the valve is correct. Use a minimum amount of gas seal on the thread joint. Check that all the joints are leak free. Reset gas valve.
See
Page 21, Section 10.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVE IS USED WHEN REPLACING THESE CONTROLS.
OFF
31
Page 38
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Unscrew
Injectors
Manifold
14.2 Burner Compartment
The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.
Burner
compartment
cover Flame probe Viewing port
for flame probe
Remove flexible
air duct from spigot
Ignition electrode
Viewing port
for ignition electrode
Remove
access plate
Rubber Seal
Remove screws and
pull off burner cover
14.2.1
Burner Injectors
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
Remove manifold
Burner venturi
MODEL
Orifice Quantity 7 8 9 10 11 12 14 14
Natural Gas (G20)
Orifice Marking 43 43 2.25 mm 2.25 mm 2.25 mm 40 40 40
RG P/N 91930043 91930043 91930225 91930225 91930225 91930040 91930040 91930040
Propane (G31)
Orifice Marking 1.35 mm 1. 35 m m 54 54 54 1. 45 mm 53 53
RG P/N 91930135 91930135 91930054 91930054 91930054 91930145 91930053 91930053
UHA[S]
150
UHA[S]
175
UHA[S]
Manifold
screws and pull
out manifold
Marking
Folded
Hem
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
Burners
Injectors
Burner
Screws
UHA[S]
350
UHA[S]
400
32
Page 39
14.3 Ignition Electrode and Flame Probe
Burners
SECTION 14: REPLACEMENT PARTS
Limit
Thermostat
Flame
Probe
Burner Compartment
Front Views
Ignition
Electrode
Burners
.120
(3 mm)
spark
gap
Remove all
burner compartment
screws to remove
the burner
compartment and
access the
"Front View".
Flame
Probe
Remove
Screw
Ignition
Electrode
To replace the electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
Description Part Number Qty.
Spark Electrode 90427411 1 Automatic Ignition Flame Probe 90439300 1 Inshot Burners (150, 175) 92000001 1 Inshot Burners (200 - 400) 92000002 1 Limit Switch (150 - 400) 90412103 1 Limit Switch (300 - 400) 90412105 2
33
Page 40
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
14.4 Combustion Fan Vertical Installation
Vent Box
Vent Box
Screws
Gasket
Mounting Plate
to Flue Fan
Screws
Mounting
Plate
Hole
Vent Box
Rear Panel
Flue Adapter
to Flue Fan
screws
Flue Outlet Gasket
Flue Fan
electrical connections
at plug in tabs.
Mounting Plate
Gasket
Air Plate
Adapter
Disconnect
to Vent Box
Screws
Remove screws securing outlet flange to the flue adapter.
Refit in reverse order.
Remove screws securing flue fan mounting plate to vent box. Remove screws securing mounting plate to fan. Refit in reverse. Use new gaskets. Ensure sealed joints. Ensure mounting plate orifice is clear and not obstructed.
MODEL
Exhaust Fan P/N 90710405 90710403 90710402
UHA[S]
150 - 175
UHA[S]
200 - 300
UHA[S]
350 - 400
IT IS IMPORTANT THAT ONLY THE CORRECT COMBUSTION FAN SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing a combustion fan. See Page 22, Section 11.
34
Page 41
14.5 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting.
WARNING
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch or disabling pressure switch circuit could cause unsafe condition.
SECTION 14: REPLACEMENT PARTS
Failure to follow these instructions can result in death or serious injury.
Carry out a commission after working on or changing a pressure switch.
See Page 19, Section
10.
Pressure Switch
P/N 90439802 90439808 90439803 90439807 90439808
Color Code yellow orange gray brown orange
Set Point in. w.c. .32 .79 .41 .68 .79
UHA[S]
150 - 175
UHA[S]
200 - 225
UHA[S]
250
UHA[S]
300 - 350
UHA[S]
400
35
Page 42
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
14.6 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their positions.
Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition
cable and all other wiring.
14.7 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced.
14.7.1 Fan Removal
Remove the mounting hardware.
and Replacement
Remove the screws
and washers.
14.8 Limit Switches
14.8.1 Removal and Replacement
1. Remove the electrical connections to the switch.
2. Unscrew the two screws securing the switch.
3. Fit a new switch with two screws. See Page 38, Section 15.3.
4. Reconnect the electrical connections and test operation.
Description Part Number Qty.
Axial Fan UHA[S] 150 - 175 90710416 1 Axial Fan UHA[S] 200 - 250 90710417 1 Axial Fan UHA[S] 300 - 400 90710416 2
14.7.2 To Replace the Fan Assembly
To replace the fan assembly, reverse the procedure shown above.
• Check that the fan blades are free to rotate before turning on the power to the fan.
• Strictly comply with the color code of the fan wires to ensure correct operation.
See Page 16,
Section 9.3 wiring diagram.
• Use only genuine ROBERTS GORDON
®
replacement parts.
36
Page 43
SECTION 15: SPECIFICATIONS
15.1 Standard (Models 150 - 400) UHA(S) Series Dimension Data
SECTION 15: SPECIFICATIONS
Support Centers
19 3/8"
(49 cm)
77
F
Top View
E
I
Rear View
Air Intake (UHAS only)
H
Heater must be supported at these points from above or below.
C
G
Flue
D
4 x 3/8" Captive Nuts Provided
End View
Z
25 1/2" (65 cm)
B
6 1/2"
(17 cm)
A
Width
B
Height
C
Support Spacing
D
Support Spacing
E
Support Spacing
F
Centre of Flue
Centre of
G
Flue/Air Intake
H
Position of Flue
I
Gas Inlet Position
Z
Length
Gas Supply
Lockout Reset
Model
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
Electrical Cable Entry
UHA[S]
150
42.4
(108)
26.9 (68)
17.7 (45)
12.3 (31)
12.4 (32)
15.5 (39)
5.5
(14)
8.2
(21)
5.8
(15)
34
(86)
A
UHA[S]]
175
42.4 (108)
26.9 (68)
17.7 (45)
12.3 (31)
12.4 (32)
15.5 (39)
5.5
(14)
8.2
(21)
5.8
(15)
34
(86)
UHA[S]
200
42.4
(108)
35.2 (89)
17.7
(45)
12.3 (31)
12.4 (32)
17.5
(44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
225
42.4
(108)
35.2 (89)
17.7 (45)
12.3 (31)
12.4 (32)
17.5 (44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
250
42.4
(108)
35.2 (89)
17.7 (45)
12.3 (31)
12.4 (32)
17.5 (44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
300
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
UHA[S]
350
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
UHA[S]
400
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
37
Page 44
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
15.2 General Technical Data Table (All Models)
Model
Full Load Amps @ 115 V A 5.8 5.8 10.6 10.6 10.6 11. 6 11.6 11.6
Air Volume CFM 2245 2245 3716 3716 3716 4663 4663 4663
Flue and AIr Intake
Flue Intake Size in (cm) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10)
Air Intake Size in (cm) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 5 (13) 5 (13) 5 (13)
*Maximum Straight Flue/Air Intake ft (m) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1)
UHA[S]
150
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
*Do not exceed the maximum length of flue stated or heater may not operate properly.
15.3 Technical Data Table (All Models)
Model
Total Input (Btu/h) x (1000) 150 175 200 225 250 300 350 385
Total O u t p u t (Btu/h) x (1000) 123 143.5 164 184.5 205 246 287 315.7
Efficiency % 82 82 82 82 82 82 82 82
UHA[S]
150
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
400
400
Natural Gas (G20) Data - Inlet Pressure 5.0 in w.c. Min., 14 in w.c. Max.
Burner Pressure in. w.c. 3.2 3.4 3.7 3.7 4.0 2.7 2.5 3.3
LPG / Propane (G31) Data - Inlet Pressure Inlet Pressure 12.0 in w.c. Min., 14 in w.c. Max.
Burner Pressure in. w.c. 9.9 10.4 10. 5 10.7 10.7 9.4 9.3 11.1
38
Page 45
SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SE-
SECTION 16: THE ROBERTS GORDON
®
COMBAT® UHA-SERIES WARRANTY ROBERTS-GORDON WILL PAY FOR:
Within 24 months from date of purchase by buyer or 27 months from date of shipment by Roberts-Gordon (whichever comes first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon will require the part in question to be returned to the factory. Roberts-Gordon will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ROBERTS GORDON® Replacement Parts are warranted for a period of 18 months from date of shipment from Roberts-Gordon or the remaining ROBERTS GORDON
®
COMBAT® UHA-Series warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ROBERTS GORDON® COMBAT® UHA-Series in any
way.
• Use of the ROBERTS GORDON® COMBAT® UHA­Series for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON
Installation, Operation and Service manual.
• Relocation of the ROBERTS GORDON® COMBAT UHA-Series after initial installation
• The use of the ROBERTS GORDON® COMBAT UHA-Series in a corrosive atmosphere containing contaminants.
• The use of the ROBERTS GORDON® COMBAT UHA-Series in the vicinity of a combustible or explosive material.
• Any defect in the ROBERTS GORDON® COMBAT UHA-Series arising from a drawing, design, or specification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
®
COMBAT® UHA-Series as directed in the
®
®
®
®
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON® COMBAT UHA-Series is moved or transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write Roberts­Gordon:
U.S.A.
1250 William Street P. O . B ox 4 4 Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
Roberts-Gordon's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the ROBERTS GORDON
®
COMBAT® UHA-Series.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts­Gordon any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon's duly authorized Executive Officer.
®
WARRANTY IS VOID IF:
The ROBERTS GORDON® COMBAT® UHA-Series is not installed by an electrician qualified in the installation and service of control systems for heating equipment.
You cannot prove original purchase date and required annual maintenance history.
39
Page 46
Page 47
Page 48
Attach this information to the wall near the ROBERTS GORDON® heater
®
Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.
TO TURN OFF THE HEATER
1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your installer/contractor qualified in the installation and service
of gas-fired heating equipment.
Installation Clearances
Roof Terminal
(Optional separated
combustion concentric
venting shown.)
Top*
WARNING
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances to Combustibles
Top
Left Right
Left
Top
Right
Wall
Terminal
Rear*
10'
(3 m)
Max. Mounting Height*
*Models
Top Rear
1
Heaters can be mounted higher if destratification fans are installed. See Installation, Operation and Service Manual for specific mounting height recommendations. NOTE: Venting directly from top of heater not applicable on Models 150-400.
Max Mounting Height
Roberts-Gordon, LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON using only replacement parts sold and supplied by Roberts-Gordon.
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level. Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
Models 100-400 are not for residential use.
© 2007 Roberts-Gordon, LLC www.rg-inc.com Printed in U.S.A. P/N 91040031 Rev B
1
30 - 125
1" (2.5 cm)
18" (46 cm)
12' (3.7 m) - 20' (6 m)
Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
150 - 400
6" (15 cm)
24" (61 cm)
20' (6 m) - 30' (9 m)
Models
Top Bottom Right Left Vent
* Clearance needed for servicing.
Bottom
Models 30 - 125 Models 150 - 400
30 - 125
1" (2.5 cm)
0" (0 cm)
1" (2.5 cm)
18" (46 cm)*
2" (5 cm)
®
equipment and perform service where necessary,
Bottom
150 - 400
6" (15 cm)
3" (8 cm)
31" (79 cm)*
6" (15 cm)
2" (5 cm)
Loading...