Roberts Gorden 400, 225, 200, 300, 150 User Manual

...
Page 1
WARNING
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
®
Combat
UHA-Series
Tubular Unit Heaters
(Standard Range)
Installation, Operation
& Service Manual
Models UHA[S] 150, 175, 200, 225 250, 300, 350, 400
Quality in Any Language™
© 2008 Roberts-Gordon LLC
Roberts-Gordon LLC
1250 William Street P. O . B o x 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com
P/N 111101NA 06/08 Rev. E
Page 2
Page 3
© 2008
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility ..................................... 2
2.1 Wall Tag .......................................................................2
2.2 Corrosive Chemicals.................................................... 2
2.3 National Standards and Applicable Codes ..................2
SECTION 3: Critical Considerations ..................................... 3
3.1 Basic Information .........................................................3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances .................3
3.4 Clearances to Combustibles ........................................3
3.5 Ventilation ....................................................................3
3.6 Gas Supply.................................................................. 3
3.7 Electrical Supply.......................................................... 3
3.8 Vent..............................................................................3
3.9 Separated Combustion Installation .............................. 3
SECTION 4: National Standards and Applicable Codes .....5
4.1 Gas Codes...................................................................5
4.2 Aircraft Hangars........................................................... 5
4.3 Parking Structures and Repair Garages ......................5
4.4 Electrical ...................................................................... 5
4.5 Venting.........................................................................5
4.6 High Altitude ................................................................5
SECTION 5: Major Components............................................6
5.1 General........................................................................ 6
5.2 Suspension.................................................................. 6
SECTION 6: Venting................................................................7
6.1 Venting.........................................................................7
6.2 Vent Installation ........................................................... 7
6.3 Unvented Operation..................................................... 8
6.4 Horizontal Venting........................................................8
6.5 Vertical Venting............................................................ 8
6.6 Length Requirements ..................................................8
6.7 Vent Material................................................................ 9
SECTION 7: Air Supply......................................................... 13
7.1 Separated Combustion Installation............................. 13
7.2 Unvented Installation.................................................. 13
7.3 Building Ventilation ..................................................... 13
7.4 Outside Combustion Air Supply.................................. 13
SECTION 8: Gas Piping........................................................14
8.1 Connections............................................................... 14
SECTION 9: Wiring................................................................ 15
9.1 Positioning Thermostats ............................................ 15
9.2 Low Voltage Thermostat with One Heater ................. 15
9.3 UHA[S] Series Internal Wiring Diagram..................... 16
9.4 UHA[S] Series Ladder Wiring Diagram...................... 17
9.5 Electrical Connection to the Heater ........................... 18
SECTION 10: Operation and Maintenance.......................... 19
10.1 Pre-Start-Up Checks................................................19
10.2 Begin Start-Up ......................................................... 19
10.3 Complete the Start-Up ............................................. 21
SECTION 11: User Instructions............................................22
11.1 User Instructions.......................................................22
11.2 Heater Operation ......................................................22
11.3 Lighting Instructions..................................................22
11.4 Simple Troubleshooting.............................................22
SECTION 12: Servicing.........................................................24
12.1 Servicing Instructions...............................................24
12.2 Burner Maintenance.................................................24
12.3 Fan/Motor Assembly Maintenance...........................24
12.4 Heat Exchanger Maintenance ..................................24
12.5 Gas Valve Maintenance ...........................................24
12.6 Flue Blower ..............................................................24
12.7 Venting and Air Intake Pipe......................................24
12.8 Maintenance Checklist.............................................25
SECTION 13: Troubleshooting .............................................27
13.1 General ....................................................................27
13.2 Troubleshooting For Automatic Ignition
Burner Systems .......................................................28
13.3 Troubleshooting for Flame Supervision System .......29
13.4 Troubleshooting for Gas Valves................................30
13.5 Troubleshooting for Flue Blower...............................30
SECTION 14: Replacement Parts.........................................31
14.1 Gas Valve .................................................................31
14.2 Burner Compartment ...............................................32
14.3 Ignition Electrode and Flame Probe .........................33
14.4 Heat Exchanger .......................................................34
14.5 Louvers and Louver Spring ......................................34
14.6 Flue Blower .............................................................35
14.7 Pressure Switch........................................................36
14.8 Ignition Control .........................................................36
14.9 Axial Fan/Guard/Motor Assembly.............................36
14.10 Limit Switches ........................................................37
SECTION 15: Specifications.................................................38
15.1 Standard (Models 150 - 400) UHA[S] Series
Dimension Data .......................................................38
15.2 General Technical Data Table (All Models) ..............39
15.3 Technical Data Table (All Models) ............................39
SECTION 16: The ROBERTS GORDON
UHA-Series Warranty.....................................41
®
COMBAT
®
Printed in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Installation Clearances and Clearances
to Combustibles......................................................... 4
Figure 2: Suspension Methods ................................................. 6
Figure 3: Vent and Roof Detail ..................................................9
Figure 4: Standard Vented Heater - Vertical
and Horizontal Vent Termination................................ 9
Figure 5: Standard Vented Heater - Common
Vertical Vent Termination......................................... 10
Figure 6: Separated Combustion Heater - Vertical
and Horizontal Vent Termination.............................. 11
Figure 7: Concentric Vent Box ................................................ 11
Figure 8: Concentric Vertical and Horizontal Vent
Termination - Separated Combustion Heater .......... 12
Figure 9: Gas Connection ....................................................... 14
Figure 10: Automatic Burner Control Sequence......................20
Figure 11: Gas Valve for Models UHA[S] 150 - 400 ................ 20
Figure 12: LED Diagnostic Codes ...........................................22
Page 6
Page 7
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. Heaters are not approved for residential installation. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation. Thin sheet metal parts, including the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. Before installation, ch‘eck that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible.
SECTION 1: HEATER SAFETY
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
1
Page 8
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
CAUTION
Do not use heater in an area containing corrosive chemicals.
Avoid the use of corrosive chemicals to ensure a longer life of the burner, heat exchanger and other parts.
Failure to follow these instructions can result in property damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
2.2 Corrosive Chemicals
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a Local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for combustion, ventilation and distribution in
of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen ele­ments (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
accordance with local codes.
2.1 Wall Tag
A laminated wall tag is included with the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater.
A copy of the wall tag (P/N 91040031) is illustrated on the back cover.
Know your model number. Model number is found on the heater and in the Installation, Operation and Service Manual. See Page 9, Figure 3 through Page 14, Figure 9.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[S] heaters have automatic ignition burners for ON/OFF operation only.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with horizontal discharge.
• May be mounted on a shelf of non-combustible material.
• May be suspended from above (See Page 6, Figure 2) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table on Page 38, Section 15.1. Drop rods must be a minimum of 3/8" diameter mild steel. Four suspension points (3/8" nuts) are located on top of the heater.
• Must be installed in a manner which allows access to all serviceable components. See Page 4, Figure 1 for details.
SECTION 3: CRITICAL CONSIDERATIONS
3.7 Electrical Supply
A permanent 120 V 60 Hz 1 Ø electrical supply is required for the main electrical power. The heater also requires suitable controls in accordance with See Page 15, Section 9.
3.8 Vent
Choose heater orientation to allow for the proper location of the vent. Each heater must be fitted with a correctly sized sealed vent system.
If vented horizontally, no other appliance may be connected to the vent. See Page 7, Section 6.
3.9 Separated Combustion Installation
For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.
Separated combustion units may not be common vented. See Page 7, Section 6.
3.3 Minimum Required Installation Clearances
Clearances around the heater and vent must be as indicated on Page 4, Figure 1; Page 9, Figure 3 through Page 12, Figure 8 to ensure access for servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
1. If clearances to combustibles are not indicated,
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national codes on Page 7, Section 6.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight on Page 14, Section 8.
3
Page 10
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
6"**
(15 cm)
31" (79 cm)
3"
6"
(15 cm)
Clearances to Combustibles
24" for adequate air flow access axial fan.
10'
(3 m)
Wall
Terminal
Roof Terminal
Top
20' (6.0 m) - 30' (9.1 m)
Max. Mounting Height*
Installation Clearances
(Optional separated
combustion concentric
venting shown.)
* Recommended mounting height varies with heater input. Heaters may be mounted at a higher level if destratification fans are installed.
Note: Venting directly from top of heater not applicable on Models 150 - 400.
Clearance to Vent: 2" (5 cm)
**31" (79 cm) minimum is necessary for servicing.
The heater must always be installed at least 6' (2 m) above the floor. The vent pipe must have clearance from combustibles by 2" (5 cm). If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.
Figure 1: Installation Clearances and Clearances to Combustibles
4
Page 11
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the name plate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
• In accordance with the Standard for Parking Structures NFPA 88A, heaters must be located a minimum of 18" (50 cm) below the floor-ceiling assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision, heaters must not be installed less than 8' (2.4 m) above the floor.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.6 High Altitude
These heaters are approved for installations up to 2000' (610 m). In USA, consult factory if heater is to be installed above 2000' (610 m). In Canada, high altitude conversion kits are available for installations up to 4500' (1370 m). Installations above 4500' (1370 m) in Canada is by local or provincial authority.
5
Page 12
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod minimum.
Failure of the supports can result in death, injury or property damage.
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8" Threaded Rod
Nut
Washer
Riv Nut
Support Points
Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.
Washer
3/8"
Threaded
Rod
Nut
Unistrut
Channel Nut
SECTION 5: MAJOR COMPONENTS
5.1 General
Heaters are designed for installation above 6' (1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.
5.2 Suspension
For typical suspension, See Page 6, Figure 2.
Figure 2: Suspension Methods
6
Page 13
SECTION 6: VENTING
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
6.1 Venting
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code. Any portion of vent pipe passing through a combustible wall must have a listed thimble to conform with the above codes.
The heater may be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 8, Section 6.3 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 4, Figure 1.
The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.
Vent terminal must be beyond any combustible overhang.
Secure all joints with corrosion resistant #8 x 3/8" sheet metal screws.
For single wall venting, pressure sensitive aluminum tape or silicone sealant must be used to seal all joints.
Aluminum tape shall have a minimum temperature rating of 400° F (204° C) and meet SMACNA AFTS­100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).
6.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.
NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.
SECTION 6: VENTING
6.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
6.2 Vent Installation
For vented units, the vent must terminate outside of the building.
Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed on Page 9, Figure 3 through Page 12, Figure 8. The joints between the vent terminal and the roof or wall must be properly sealed. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.
For vent termination See Page 9, Figure 3 through Page 12, Figure 8.
6.2.1 Standard Vented Heaters (Models UHA 150 - 400)
The vent must be fitted with a low resistance terminal. See Page 9, Figure 3 through Page 9, Figure 4. Standard vented heaters do not allow outdoor air intake for combustion air.
7
Page 14
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
WARNING
6.2.2 Separated Combustion Heaters (Models UHAS 150 - 400)
The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals. See Page 12, Figure 8. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof.
6.3 Unvented Operation
6.5 Vertical Venting
Vertically vented heaters can be common vented (up to 4 heaters). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. Vent from the rear of the heater cabinet then run the vent vertically and use a condensate drain at the bottom of the vertical vent. Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3 m).
For 4'' (10 cm), an approved vent cap (P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap (P/N 90502103) must be used.
For common vertical venting of more than two heaters, See Page 10, Figure 5.
A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.
For unvented operation in commercial installations, sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).
WA R NI NG : Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
6.4 Horizontal Venting
Horizontally vented heaters must be individually vented.
Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3 m). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. For vents pitched up toward the vent terminal, place the condensation drain within 5' (1.5 m) of the heater.
In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.
Instead of an insulated vent terminal, a listed thimble (with 2" air gap) may be used with a 4" vent cap (P/N
90502102).
6.6 Length Requirements
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. The entire vent should be insulated with foil faced fiberglass insulation (1/2" thick, 1-1/2# density minimum).
Maximum Vent Lengths Table
Model UHA[S]
150 - 400
40 ft (12.2 m) 1 35 ft (10.7 m) 2
30 ft (9.1 m) 3
25 ft (7.6 m) 4
20 ft (6.1 m) 5
# of Elbows
8
Page 15
SECTION 6: VENTING
Roof
Vent
Terminal
Listed Thimble
Flashing
or Rain Collar
Vent
2" Air Gap to
Combustible Material
Vent Terminal
4" Dia.Vent
Flashing (By Others)
Listed Thimble (2" Clearance)
Vent Terminal
Vertical
Option
Horizontal
Option
Vent
Listed
Thimble
(2" Clearance)
Flashing (By Others)
12" (31 cm) Minimum
Condensate
Trap to Drain
(Optional)
Note: Vent supports not shown.
90° Bend
Model Vent Diameter Part Number
UHA 150 - 400 4" (10 cm) 90502102
6.7 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 7, Section
6.2.
If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent manufacturer's clearance from vent material is maintained. Seal annular space of the type B-1 vent as well as all joints in the remaining vent.
Figure 3: Vent and Roof Detail
Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination
9
Page 16
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Roof
18" (46 cm)
Min.
Type "B" vent cap (7" or 8") may be used. (These are not available from Roberts-Gordon.)
Roof
Flashing
Approved
Thimble
(If Applicable)
Type "B" Vent Pipe
4" (10 cm)
Single Wall Pipe
4" (10 cm)
Single Wall Pipe
"D" Area must equal sum
of open area of
individual vents.
"D"
Single Wall Pipe
The last section of vent pipe passing through the roof or wall may be Type "B" vent pipe. All other vent materials in the building must be single wall vent pipe.
TOP VIEW
SIDE VIEW
Figure 5: Standard Vented Heater - Common Vertical Vent Termination
10
Page 17
Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent Termination
Vent Termination
Listed Thimble through
Combustible Wall
Vent
12" (31 cm) Minimum from wall to vent termination.
Air Intake
Condensate
Trap to Drain
(Optional)
12" (31 cm) Minimum from air inlet to vent termination (may be horizontal or vertical clearance).
Air Intake Termination
Note: Vent supports not shown
Vent
Air Intake*
12" (31 cm)
Minimum from air inlet to vent
termination (may be horizontal
or vertical clearance).
Vertical
Option
Horizontal
Option
90° Bend
Model Vent Diameter Terminal P/N
UHAS 150 - 400 4" (10 cm) 90502102
Model *Air Intake Diameter Terminal P/N
UHAS 150 - 250 4" (10 cm) 90502102 UHAS 300 - 400 5" (13 cm) 90502105
SECTION 6: VENTING
Figure 7: Concentric Vent Box
11
Page 18
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Vent
Air Intake*
Concentric Vent Box
Vertical
Option
10' (3 m)
Maximum
Horizontal Option
Concentric Vent Box
Vent
Combustion Air Terminal
Vent Terminal with Baffle Plate
Flashing (By Others)
Condensate Trap to Drain (Optional)
4" Type B-1
Vent
Storm Collar (By Others) (Attach with 3 sheet metal screws.)
UHA 150-250: 6" Dia. Single Wall UHA 300-400: 8" Dia. Single Wall
Air Intake*
6" (16 cm)
Minimum
12" (31 cm)
Maximum
Combustion Air Terminal
Vent Terminal with Baffle Plate
4"
Type
B-1
Vent
Storm Collar (By Others) (Attach with 3 sheet metal screws.)
Description Part Number Qty. Concentric Vent Kit (150 - 250) UHVK1
Concentric Vent Box Top & Side Assembly 90504113 1 Concentric Vent Box Bottom Assembly 90504112 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" Vent Terminal with Baffle Plate 90502102R 1 6" Combustion Air Terminal 90502103 1
Description Part Number Qty. Concentric Vent Kit (300 - 400) UHVK2
Concentric Vent Box Top & Side Assembly 90504013 1 Concentric Vent Box Bottom Assembly 90504012 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" Vent Terminal with Baffle Plate 90502102R 1 8" Combustion Air Terminal 90502104 1
Model Vent Diameter
UHAS 150 - 400 4" (10 cm)
Model *Air Intake Diameter
UHAS 150 - 250 4" (10 cm) UHAS 300 - 400 5" (13 cm)
Figure 8: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater
12
Page 19
SECTION 7: AIR SUPPLY
7.1 Separated Combustion Installation
When installed as a separated combustion heater (UHAS), the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate space around heater to provide air for the axial air distribution fan.
7.2 Unvented Installation
It is important to ensure that there is adequate fresh air supply at all times for both combustion and heating requirements in accordance with local and national codes.
WARNING: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
7.3 Building Ventilation
Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.
SECTION 7: AIR SUPPLY
7.4 Outside Combustion Air Supply
If outside combustion air supply is required, separated combustion model (UHAS) heaters must be used.
IMPORTANT: If the building has a slight negative pressure or corrosive contaminants such as halogenated hydrocarbons are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints. The air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal must not be more than 1' (31 cm) above the vent terminal.
7.4.1 Length Requirements
Follow the constraints listed on Page 8, Section 6.6.
13
Page 20
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Connect gas supply according to Figure 9.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
Fire Hazard
Connect gas supply according to Figure 9.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or porperty damage.
Gas Shut-off Valve
Drip Leg
Cap
Union
Connection
Option B:
Medium or Heavy Gauge Pipe Gas Connector
Option A:
Stainless Steel Flex Gas Connector
Do not bend flexible
gas connector
sharply.
• Hold gas nipple securely with pipe wrench when attaching the flex gas connector.
• Do not t wist flexible
gas connector.
• Ensure all
joints are gas tight.
SECTION 8: GAS PIPING
• Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas pipe which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" w.c. When gas piping is not included in the layout drawing, contact the local gas supplier.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• A minimum 1/8" NPT plugged tapping accessible for test connection must be installed immediately upstream of the gas supply
It is important that the gas supply pipe and the electrical connections do not support any of the heater’s weight.
A gas meter is connected to the service pipe by the gas supply company. An existing meter should be checked, preferably by the company, to ensure that the meter is adequate for the rate of gas supply required.
Installation pipes must be fitted in accordance with local and national codes. Pipes of smaller size than the heater inlet gas connection should not be used.
connection to the heater.
• For suspended heaters, an approved metal flexible connection between the isolating valve and the heater may be used. To reduce
pressure loss, use one pipe size larger than the heater gas connection.
IMPORTANT - The complete installation must be purged and tested for gas soundness in accordance with local and national codes.
• Do not high pressure (in excess of 1/2 psi
[14" w.c.]) test the gas piping with the burner connected. Close manual shut-off valve
8.1 Connections
Connect the heater to the gas supply ensuring that the final connections are as follows:
• Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes.
during any pressure testing equal to or less than 1/2 psi (14" w.c.). Failure to follow these
instructions can result in property damage. Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
Figure 9: Gas Connection
14
Page 21
SECTION 9: WIRING
WARNING
Electrical Shock Hazard
Disconnect electrical power and gas supply before servicing.
This appliance must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death or electrical shock.
All heater models require constant 120 V 60 Hz 1Ø power supply. Check heater(s) rating plate for electrical rating for proper circuit sizing. For servicing, a disconnect switch of proper electrical rating should be installed in the vicinity of the heater.
All heaters are equipped with thermostat connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in accordance with local codes. In the absence of local
SECTION 9: WIRING
codes in accordance with: United States: refer to National Electrical Code
®
NFPA 70 - latest revision Canada: refer to Canadian Electrical Code CSA C22.1 Part I - latest revision.
9.1 Positioning Thermostats
®
A room thermostat or ROBERTS GORDON control should be mounted on a vibration-free wall or column at a height of approximately 5' (1.5 m) from the floor to measure the ambient temperature. It should be clear of both cold drafts and the direct path of warm air from the heater. Avoid mounting thermostat on outside walls or in areas directly exposed to radiant heat or sunlight. Install wall tag in a visible location near thermostat.
9.1.1 Fan Control
The heater’s axial fan can be used during the off­season for air circulation. A low voltage thermostat with fan control must be used. See Page 15, Section
9.2 for thermostat connection details.
9.2 Low Voltage Thermostat with One Heater
15
Page 22
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
BLUE
BLACK
BLACK
ORANGE
ORANGE
YELLOW
BROWN
BLACK
WHITE
WHITE
L2
L1
ORANGE
ORANGE
BLACK
BLACK
GREEN
WHITE
WHITE
GREEN
GREEN
BLUE
BLACK
BLACK
BLACK
WHITE
GREEN
BLUE
GREEN
YELLOW
24 VAC
HOT
GROUND
FLAME
BLACK
BLACK
BLACK
6
3
4
5
2
1
45
31
SENSE
ELECTRODE
LIMIT SWITCH
PRESSURE SWITCH
AXIAL FAN
GAS VALVE
IGNITION MODULE
TRANSFORMER
AXIAL FAN (UHA 300, 350, 400)
LIMIT SWITCH (UHA 300, 350, 400
MANUAL RESET LIMIT SWITCH
(UHA 30 - 125 ONLY)
THERMOSTAT INPUT: FIELD SUPPLIED
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W= HEAT DEMAND INPUT FROM THERMOSTAT (WHITE) C = COMMON SIDE OF TRANSFORMER
Flue
Blower
R
G
W
C
ACC
L1
CMB BLOWER
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and 600 volts. For supply connections use No. 14 AWG or larger wires.
9.3 UHA[S] Series Internal Wiring Diagram
16
Page 23
9.4 UHA[S] Series Ladder Wiring Diagram
NOTE:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and 600 volts. For supply connections use No. 14 AWG or larger wires.
SECTION 9: WIRING
17
Page 24
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
BX Connector
Junction Box
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1 L2
Ground
Black
White
Green
9.5 Electrical Connection to the Heater
Note: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
18
Page 25
SECTION 10: OPERATION AND MAINTENANCE
WARNING
Electrical Shock Hazard
Use extreme caution during start-up.
Controls compartment contains live electrical connections.
Failure to follow these instructions can result in death or electrical shock.
WARNING
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
Installation, service, and annual inspection of the heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation, or service of this equipment. All components are accessed via the door secured by 4 sheet metal screws. Opening the door exposes live electrical connections and hot components.
SECTION 10: OPERATION AND MAINTENANCE
10.1.2 Electrical Checks
All pre-start-up checks must be carried out before start-up the heater.
1. Check that all site wiring is connected in accordance with the appropriate wiring diagram on Page 16, Section 9.3.
10.1.3 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for gas tightness and purged in accordance with local and national codes.
Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
10.1.4 Mechanical Checks
1. Check that the fan is free to run and delivery louvers are turned to give required air deflection.
2. Check that the flue (and air intake for separated combustion units) is installed in accordance with these instructions and local regulations.
10.1 Pre-Start-Up Checks All pre-start-up checks must be carried out
before lighting the heater.
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
10.1.1 Louvers
Where fitted, the air delivery louvers need to be set during start-up to give the required air distribution.
10.2 Begin Start-Up
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off and power supply turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room temperature. The automatic ignition sequence will now begin as described on Page 20, Figure 10.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
19
Page 26
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
If at any stage the flame fails, the control will retry for ignition. The control has four trials for ignition before a one hour lockout.
½PSI IN
C
ON
OFF
Regulator
Outlet Pressure
Gas Inlet
Inlet Pressure
Top View
End View
Description Part Number
Gas Valve 150 - 225 NG 90032505 Gas Valve 150 - 225 LP 90032506 Gas Valve 250 - 400 NG 90032520 Gas Valve 250 - 400 LP 90032521
Figure 10: Automatic Burner Control Sequence
Figure 11: Gas Valve for Models UHA[S] 150 - 400
20
Page 27
SECTION 10: OPERATION AND MAINTENANCE
10.2.2 Start-Up the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.
2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Tables for the correct gas and model on Page 39, Section 15.3.
NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Tables on Page 39, Section 15.3 for inlet pressure requirement.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the commission.
10.2.5 External Controls
External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.
10.3 Complete the Start-Up
Ensure that all covers are fitted correctly and all test points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles on Page 4, Figure 1 and the user instructions on Page 22, Section 11 through Page 22, Section 11.4 and all warnings defined in this manual.
Check Gas Rate
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
10.2.3 Pressure Switch
The pressure switch is factory pre-set for each model and is not adjustable.
10.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest setting and the main burner will stop.
The fan will run until it is stopped automatically by the fan thermostat.
Do not use a disconnect switch for control of heater. Disconnect switch will turn off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly. Only use the disconnect switch for turning off heater for service or during off-season.
21
Page 28
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in death or electrical shock.
SECTION 11: USER INSTRUCTIONS
11.1 User Instructions
The UHA[S] Series heaters are fully automatic and operate from the external controls fitted on site.
11.4 Simple Troubleshooting
Some possible reasons for the heater not operating are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not "ON".
4. A limit switch may have operated. This may be caused by an interruption of the electrical supply, failure of the distribution fan or vent or heat exchanger blockage.
If a temperature limit switch persistently trips, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
11.2 Heater Operation
When the heater has been switched on by the thermostat installed on site, the main burner will automatically turn on.
The burner control box will control the safe ignition of the flame.
All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation of this heater.
11.3 Lighting Instructions
11.3.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site controls are "ON".
NOTE: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as described on Page 20, Figure 10. The heater will now operate automatically under the control of the on site controls.
11.4.1 Simple Troubleshooting (Burner Fault)
If the burner fails to ignite for any reason, it will retry for ignition (4 trials total). After 4 unsuccessful ignition trials, the control will put the heater into lockout for 1 hour.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected. There is an LED light on the ignition control that flashes codes to assist in fault correction. See Figure 12 for LED indication codes.
Figure 12: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow Flash Normal Operation - No call for heat.
Fast Flash Normal Operation - Call for heat.
2 Flashes Ignition Lockout - No flame detected.
3 Flashes Airflow Fault - Pressure switch open or closed.
4 Flashes Temperature Limit or
Manual Reset Limit Switch Open
5 Flashes Flame Sense Error - Gas valve not energized.
Steady On Internal Control Failure
11.3.2 To Turn the Heater Off
Set the thermostat to the "OFF" position. The burner will turn off immediately. The fan will continue to run for 90 seconds. To restart, turn the thermostat above room
temperature.
22
Page 29
SECTION 11: USER INSTRUCTIONS
23
Page 30
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
SECTION 12: SERVICING
12.1 Servicing Instructions
After start-up, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be necessary.
NOTE 1: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions on Page 19, Section 10 through Page 21, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 27, Section 13 through Page 30, Section 13.5.
NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.
12.3 Fan/Motor Assembly Maintenance
The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.
12.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.
12.5 Gas Valve Maintenance
No regular maintenance is required on this device. To change gas control valves, See Page 31, Section
14.1.
Do not repair or disassemble gas valve. Replace faulty gas valves with genuine
replacement parts sold and supplied by Roberts-Gordon.
12.6 Flue Blower
The flue blower should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 35, Section 14.6). Ensure that the fan is free to run and that the fan wheel is clean.
NOTE 3: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.
12.2 Burner Maintenance
1. Open the door and remove the burner compart­ment cover. See Page 32, Section 14.2.
2. Clean any deposits from the main burner which
3. Remove the ignition electrode and flame probe.
24
may have formed in the injectors or venturi of the burner. See Page 32, Section 14.2.
Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.
12.7 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that all seams are sealed and suspension points secure. Repair suspension points if any part of the venting or combustion air pipe is sagging. Check to make sure any insulation is not missing or in poor condition. Replace as necessary. Check all venting and air intake components to ensure they are in good condition, gas tight and corrosion-free.
Page 31
SECTION 12: SERVICING
WARNING
Explosion Hazard
Service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
12.8 Maintenance Checklist Installation Code and Annual Inspections: All
installations and service of ROBERTS GORDON equipment must be performed by a contractor qualified in the installation and service equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON
®
equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 3, Section 3.
®
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger or in the louvers.
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits from the screen.
See Page 13, Section 7.
Combustion Air Intake Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Heat Exchanger Make sure there are no cracks.
See Page 14, Section 8.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas Line and Shut-off Valves
Check for gas leaks. See Page 14, Section 8.
25
Page 32
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Burner Observation Window
Flue Blower Scroll, Wheel
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor Inshot Burners and
Orifices
Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark Igniter Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
Thermostat There should be no exposed wire or damage to the device or wiring.
See Page 19, Section 10.
Suspension Points Make sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 6, Figure 2.
Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas Valve Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed)
26
Page 33
SECTION 13: TROUBLESHOOTING
Ensure proper air flow
clearance for axial fan.
Open louvers slightly.
Replace axial fan if it does
not operate.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Replace limit switch.
The limit switch has
tripped. See Manual Reset
Limit Switch Figure.
No
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
Has burner “Locked Out”?
Ye s
No
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
No
Ye s
Does the flue
blower run?
No
Use Troubleshooting for
Flue Blower section to test
fan.
Ye s
Ye s
Burner has locked out due
to ignition failure. Use
Tro ubleshooting for
Automatic Ignition Burner
Systems section to test
burner.
Is ignition control showing a
"2 flashes" led code?
Ye s
No
Ye s
Fan and limit switch are
operating normally.
Replace temperature
limit switch.
Wait 10-15 minutes for
limit switch to cool. Does
fan stop running?
No
Ye s
Does axial fan run
immediately upon supplying
power to heater?
Ye s
No
Turn on supplies.
Are gas & electrical
supplies on?
No
Ye s
START
WARNING
Explosion Hazard
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Failure to follow these instructions can result in death, injury or property damage.
13.1 General
SECTION 13: TROUBLESHOOTING
27
Page 34
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Trace fault in supervision
system. See
Tro ubleshooting
for Flame Supervision
System section.
Ye s
Is ignition control showing
a "2 flashes" led code?
No
Is the flame current at
least 1 μAmp DC when
the flame ignites?
Ignition control faulty;
replace.
See Ignition Control section.
Is ignition lead okay and
connected?
Is spark electrode okay?
Ye s
Replace valve.
Is the gas valve operating?
To test valve, See
Tro ubleshooting for Gas
Valves section.
No
Does the flame light?
No
Ye s
Wait 30 - 40 seconds.
Does ignition spark
No
Ye s
Flue blower faulty;
replace
Burner control faulty or wiring
connections faulty. Repair
or replace as necessary
Check for too much vent/air inlet duct. Check for blockage in vent and combustion air circuit. Check for faulty air pressure switch. Check pressure switch hoses for leaks or cracks. Do not attempt to circumvent pressure switch circuit to place unit in operation.See Pressure Switch section for details.
Does air pressure switch
change over?
No
Ye s
Turn on controls.
Is 120 V supply at fan
connections?
Does flue blower run?
No
Are external controls (i.e. Thermostat) on?
No
Ye s
Ye s
Is ignition control showing
a "4 flashes" led code?
No
Ye s
Press in reset button on
manual reset limit switch
Turn on supplies.
Are gas & electrical
supplies on?
Ye s
START
No
Ye s
No
Ye s
WARNING
Electrical Shock Hazard
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can result in death or electrical shock.
For your safety and optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 19, Section 10.
13.2 Troubleshooting For Automatic Ignition Burner Systems
28
Page 35
13.3 Troubleshooting for Flame Supervision System
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.
START
Connect a DC ammeter in
series with the flame probe.
SECTION 13: TROUBLESHOOTING
Is the flame present and
at least 1 μA DC flame
current?
Ye s
Is there a current flowing in the flame probe circuit with
no flame present?
No
Does “lockout” occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
Tro ubleshooting section to
No
Ye s
Ye s
No
trace the fault.
Is the connecting lead
damaged? Is the flame probe
damaged or touching earthed
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
Repair or replace as
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Use General
No
necessary.
Repair or replace as
Ye s
Ye s
necessary.
Replace ignition control.
29
Page 36
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Valve faulty.
Replace with one of
correct type.
Fault elsewhere.
Correct pressure problem.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Valve Operating
TROUBLESHOOT ENDS.
No
Ye s
Valve or ignition control
faulty. Replace with one of correct type.
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
No
Ye s
Does gas pressure at outlet
of the valve rise when
valve turns on?
No
Ye s
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
No
Ye s
START
For your safety and optimum heater performance, use only genuine replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 19, Section 10.
13.4 Troubleshooting for Gas Valves
13.5 Troubleshooting for Flue Blower
START
Does flue blower run
automatically when there
is a call for heat?
Does blower turn on and
off while burner is firing
TROUBLESHOOT ENDS.
Ye s
continously?
No
Blower Operating
No
Ye s
No
Correct power
supply problem.
Ye s
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
30
Page 37
SECTION 14: REPLACEMENT PARTS
½PSI IN
C
ON
OFF
Description Part Number
Gas Valve, NG (Models UHA[S] 150 - 225) 90032505 Gas Valve, LP (Models UHA[S] 150 - 225) 90032506 Gas Valve, NG (Models UHA[S] 250 - 400) 90032520 Gas Valve, LP (Models UHA[S] 250 - 400) 90032521
NOTE: Flexible duct only applies
for models UHAS.
See warnings and notes on Page 24, Section 12 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the door on the side of the heater. Remove the sheetmetal screws.
14.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
SECTION 14: REPLACEMENT PARTS
Follow steps in Section 14.2 and See Page 32, Section 14.2.1 to remove gas valve/manifold.
Replace in reverse order. Verify that the gas flow direction of the valve is correct. Use a minimum amount of gas seal on the thread joint. Check that all the joints are leak free. Reset gas valve. See Page 21, Section 10.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVE IS USED WHEN REPLACING THESE CONTROLS.
31
Page 38
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Remove flexible
air duct from spigot
Remove
access plate
Remove screws and
pull off burner cover
Viewing port
for flame probe
Viewing port
for ignition electrode
Flame probe
Burner
compartment
cover
Rubber Seal
Ignition electrode
The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.
NOTE: Flexible duct only applies
for models UHAS.
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
14.2 Burner Compartment
14.2.1 Burner Injectors
MODEL
Orifice Quantity 7 8 9 10 11 12 14 14
Natural Gas (G20)
Orifice Marking 43 43 2.25 mm 2.25 mm 2.25 mm 40 40 40
P/N 91930043 91930043 91930225 91930225 91930225 91930040 91930040 91930040
Propane (G31)
Orifice Marking 1.35 mm 1.35 mm 54 54 54 1.45 mm 53 53
P/N 91930135 91930135 91930054 91930054 91930054 91930145 91930053 91930053
UHA[S]
150
32
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
400
Page 39
14.3 Ignition Electrode and Flame Probe
Description Part Number Qty.
Spark Electrode 90427411 1 Automatic Ignition Flame Probe 90439300 1 Transformer 90436900K 1 Ignition Module 90434008 1 Inshot Burners UHA[S] 150 92000001 7 Inshot Burners UHA[S] 175 92000001 8 Inshot Burners UHA[S] 200 92000000 9 Inshot Burners UHA[S] 225 92000000 10 Inshot Burners UHA[S] 250 92000000 11 Inshot Burners UHA[S] 300 92000000 12 Inshot Burners UHA[S] 350 92000000 14 Inshot Burners UHA[S] 400 92000002 14 Limit Switch (150 - 400) 90412103 1 Limit Switch (300 - 400) 90412105 2
To replace the electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
SECTION 14: REPLACEMENT PARTS
33
Page 40
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Push in Louver and compress spring to
remove and replace
(opposite end first)
Horizontal Louvers
Push in Louver and compress spring to
remove and replace
(opposite end first)
Horizontal Louvers
Description
UHA[S]
150 - 175
UHA[S]
200 - 250
UHA[S]
300 - 400
Horizontal Louvers P/N 11011847 11011847 11011846 Spring P/N 91901200 91901200 91901200 Quantity 7 9 11
14.4 Heat Exchanger
The standard heat exchanger assembly is compossed of multiple tubular heat exchangers in models UHA[S]150 - UHA[S]400, there is a four pass exchange.
MODEL
Aluminized Heat Exchanger Assembly
Stainless Heat Exchanger Assembly
Tube Heat Exchanger
Tube Plate 1 1 1 1 1 1 1 1
Tube Support 2 2 2 2 2 2 2 2
Tube Support Strap N/A N/A 1 1 1 1 1 1
Base Panel 1 1 1 1 1 1 1 1
End Panel Insulated 1 1 1 1 1 1 1 1
Top Panel Insulated 1 1 1 1 1 1 1 1
Rear Panel 1 1 1 1 1 1 1 1
Front Panel 1 1 1 1 1 1 1 1
Rear Fan Panel 1 1 1 1 1 1 1 1
Screws Type A/B 42 45 45 50 50 50 50 50
UHA[S]
150
P/N 12117100 12116100 12115100 12114100 12113100 12112100 1 2 11110 0 12 11110 0
P/N 12117100SS 12116100SS 12115100SS 12114100SS 12113100SS 12112100SS 1 2 11110 0 S S 12 11110 0 SS
7 8 9 10 11 12 14 14
Qty
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
400
14.5 Louvers and Louver Spring
The louvers for standard range models UHA[S]150 - UHA[S]400 are only available in horizontal configurations.
34
Page 41
14.6 Flue Blower
Vent Box
Outlet Gasket
Flue Blower
Vent Box
screws
Flue
Adapter
Flue Adapter
to Flue Blower
screws
Rear Panel
Hole
Disconnect
electrical connections
at plug in tabs.
Mounting Plate
to Vent Box
screws
Mounting
Plate
Gasket
Air Plate
Mounting Plate
to Flue Blower
screws
Vent Box
Gasket
Remove screws securing outlet flange to the flue adapter.
Refit in reverse order.
Remove screws securing flue blower mounting plate to vent box.
Remove screws securing mounting plate to blower.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is clear and not obstructed.
SECTION 14: REPLACEMENT PARTS
MODEL
Flue Blower P/N 90710405 90710403 90710402
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing an flue blower. See Page 22, Section 11.
UHA[S]
150 - 175
UHA[S]
200 - 300
UHA[S]
350 - 400
35
Page 42
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch or disabling pressure switch circuit could cause unsafe condition.
Failure to follow these instructions can result in death or serious injury.
WARNING
14.7 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches are color coded for each pressure setting.
Carry out a commission after working on or changing a pressure switch. See Page 19, Section 10.
MODEL
Pressure Switch Kit P/N
Color Code
Set Point in. w.c.
Pressure Switch Snap Ring P/N
UHA[S]
150 - 175
90439802 90439808 90439803 90439807 90439808
yellow orange gray brown orange
.32 .79 .41 .68 .79
90439850 90439850 90439850 90439850 90439850
UHA[S]
200 - 225
UHA[S]
250
UHA[S]
300 - 350
UHA[S]
400
14.8 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their positions.
Release the four mounting standoffs.
Refit in reverse. Ensure correct location of ignition cable and all other wiring.
14.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced
MODEL UHA[S] 150 - 175 UHA[S] 200- 250 UHA[S] 300 - 400
Axial Fan Guard 91901105 91901104 91901105
Axial Fan Motor 90600106 90600107 90600106
Axial Fan Blade 90709005 90709006 90709005
36
Page 43
14.9.1 Fan Removal and Replacement
Remove the screws
and washers.
Remove the mounting hardware.
SECTION 14: REPLACEMENT PARTS
Description Part Number Qty.
Axial Fan UHA[S] 150 - 175 90710416 1 Axial Fan UHA[S] 200 - 250 90710417 1 Axial Fan UHA[S] 300 - 400 90710416 2
14.9.2 To Replace the Fan Assembly
• To replace the fan assembly, reverse the procedure shown above.
• Check that the fan blades are free to rotate before turning on the power to the fan.
• Strictly comply with the color code of the fan wires to ensure correct operation.
See Page 16, Section 9.3 wiring diagram.
• Use only genuine replacement parts sold and supplied by Roberts-Gordon
14.10 Limit Switches
14.10.1 Removal and Replacement
1. Remove the electrical connections to the
switch.
2. Unscrew the two screws securing the switch.
3. Fit a new switch with two screws.See Page 39,
Section 15.3.
4. Reconnect the electrical connections and test
operation.
37
Page 44
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 15: SPECIFICATIONS
15.1 Standard (Models 150 - 400) UHA[S] Series Dimension Data
A
Width
B
Height
C
Support Spacing
D
Support Spacing
E
Support Spacing
F
Centre of Flue
Centre of
G
Flue/Air Intake
H
Position of Flue
J
Gas Inlet Position
Z
Length
38
Model
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
in
(cm)
UHA[S]
150
42.4
(108)
26.9 (68)
17.7 (45)
12.3 (31)
12.4 (32)
15.5 (39)
5.5
(14)
8.2
(21)
5.8
(15)
34
(86)
UHA[S]
175
42.4
(108)
26.9 (68)
17. 7
(45)
12.3 (31)
12.4 (32)
15.5 (39)
5.5
(14)
8.2
(21)
5.8
(15)
34
(86)
UHA[S]
200
42.4
(108)
35.2 (89)
17.7 (45)
12.3 (31)
12.4 (32)
17.5 (44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
225
42.4
(108)
35.2 (89)
17.7 (45)
12.3 (31)
12.4 (32)
17.5 (44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
250
42.4
(108)
35.2 (89)
17.7 (45)
12.3 (31)
12.4 (32)
17.5 (44)
6.4
(16)
8.8
(22)
5.8
(15)
34
(86)
UHA[S]
300
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
UHA[S]
350
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
UHA[S]
400
52.3
(133)
43.5
(110)
24.7 (63)
12.3 (31)
15.3 (39)
13.8 (35)
7
(18)
11
(28)
5.8
(15)
34
(86)
Page 45
15.2 General Technical Data Table (All Models)
SECTION 15: SPECIFICATIONS
Model
Full Load Amps @ 115 V A 5.8 5.8 10.6 10.6 10.6 11.6 11.6 11.6
Air Volume CFM 2245 2245 3716 3716 3716 4663 4663 4663
Flue and Air Intake
Flue Intake Size in (cm) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10)
Air Intake Size in (cm) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 5 (13) 5 (13) 5 (13)
*Maximum Straight Flue/Air Intake ft (m) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1) 40 (1)
UHA[S]
150
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
*Do not exceed the maximum length of flue stated or heater may not operate properly.
15.3 Technical Data Table (All Models)
Model
Total Input (Btu/h) x (1000) 150 175 200 225 250 300 350 385
Total Output (Btu/h) x (1000) 123 143.5 164 184.5 205 246 287 315.7
Efficiency % 82 82 82 82 82 82 82 82
Natural Gas (G20) Data - Inlet Pressure 5.0 in w.c. Min., 14 in w.c. Max.
Burner Pressure in. w.c. 3.2 3.4 3.7 3.7 4.0 2.7 2.7 3.3
UHA[S]
150
UHA[S]
175
UHA[S]
200
UHA[S]
225
UHA[S]
250
UHA[S]
300
UHA[S]
350
UHA[S]
400
400
LPG / Propane (G31) Data - Inlet Pressure 12.0 in w.c. Min., 14 in w.c. Max.
Burner Pressure in. w.c. 9.9 10.4 10.5 10.7 10.5 9.4 9.3 11.1
39
Page 46
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
40
Page 47
SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTY
SECTION 16: THE ROBERTS GORDON
®
COMBAT® UHA-SERIES WARRANTY ROBERTS-GORDON WILL PAY FOR:
Within 24 months from date of purchase by buyer or 27 months from date of shipment by Roberts-Gordon (whichever comes first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon will require the part in question to be returned to the factory. Roberts-Gordon will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted for a period of 18 months from date of shipment from Roberts-Gordon or the remaining ROBERTS GORDON COMBAT® UHA-Series warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ROBERTS GORDON way.
• Use of the ROBERTS GORDON Series for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON
®
COMBAT® UHA-Series as directed in the
Installation, Operation and Service manual.
• Relocation of the ROBERTS GORDON UHA-Series after initial installation
• The use of the ROBERTS GORDON UHA-Series in a corrosive atmosphere containing contaminants.
• The use of the ROBERTS GORDON UHA-Series in the vicinity of a combustible or explosive material.
• Any defect in the ROBERTS GORDON UHA-Series arising from a drawing, design, or specification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
®
COMBAT® UHA-Series in any
®
COMBAT® UHA-
®
COMBAT
®
COMBAT
®
COMBAT
®
COMBAT
®
®
®
®
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON
®
COMBAT UHA-Series is moved or transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write Roberts­Gordon:
U.S.A.
®
1250 William Street P. O . B o x 4 4 Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
Roberts-Gordon's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the ROBERTS GORDON
®
COMBAT® UHA-Series.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts­Gordon any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon's duly authorized Executive Officer.
®
WARRANTY IS VOID IF:
The ROBERTS GORDON® COMBAT® UHA-Series is not installed by an electrician qualified in the installation and service of control systems for heating equipment.
You cannot prove original purchase date and required annual maintenance history.
41
Page 48
Page 49
Page 50
Page 51
Page 52
10'
(3 m)
WARNING
© 2007 Roberts-Gordon, LLC www.rg-inc.com Printed in U.S.A. P/N 91040031 Rev B
Attach this information to the wall near the ROBERTS GORDON® heater
Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.
1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your installer/contractor qualified in the installation and service
of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Roberts-Gordon, LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA
®
Left Right
Bottom
Top
Clearances to Combustibles
Wall
Terminal
Roof Terminal
Max. Mounting Height*
Rear*
Installation Clearances
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON
®
equipment and perform service where necessary,
using only replacement parts sold and supplied by Roberts-Gordon. For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
Models 100-400 are not for residential use.
Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
*Models
Top Rear Max Mounting Height
30 - 125
1" (2.5 cm) 18" (46 cm)
12' (3.7 m) - 20' (6 m)
150 - 400
6" (15 cm)
24" (61 cm)
20' (6 m) - 30' (9 m)
Heaters can be mounted higher if destratification fans are installed. See Installation, Operation and Service Manual for specific mounting height recommendations. NOTE: Venting directly from top of heater not applicable on Models 150-400.
Models
Top Bottom Right Left Vent
30 - 125
1" (2.5 cm)
0" (0 cm)
1" (2.5 cm)
18" (46 cm)*
2" (5 cm)
150 - 400
6" (15 cm)
3" (8 cm)
31" (79 cm)*
6" (15 cm)
2" (5 cm)
* Clearance needed for servicing.
Top
Bottom
Right
Left
Models 30 - 125 Models 150 - 400
(Optional separated
combustion concentric
venting shown.)
Top*
1
1
Loading...