Roberts Gorden 400, 225, 200, 300, 150 User Manual

...
WARNING
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
®
Combat
UHA-Series
Tubular Unit Heaters
(Standard Range)
Installation, Operation
& Service Manual
Models UHA[S] 150, 175, 200, 225 250, 300, 350, 400
Quality in Any Language™
© 2008 Roberts-Gordon LLC
Roberts-Gordon LLC
1250 William Street P. O . B o x 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com
P/N 111101NA 06/08 Rev. E
© 2008
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility ..................................... 2
2.1 Wall Tag .......................................................................2
2.2 Corrosive Chemicals.................................................... 2
2.3 National Standards and Applicable Codes ..................2
SECTION 3: Critical Considerations ..................................... 3
3.1 Basic Information .........................................................3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances .................3
3.4 Clearances to Combustibles ........................................3
3.5 Ventilation ....................................................................3
3.6 Gas Supply.................................................................. 3
3.7 Electrical Supply.......................................................... 3
3.8 Vent..............................................................................3
3.9 Separated Combustion Installation .............................. 3
SECTION 4: National Standards and Applicable Codes .....5
4.1 Gas Codes...................................................................5
4.2 Aircraft Hangars........................................................... 5
4.3 Parking Structures and Repair Garages ......................5
4.4 Electrical ...................................................................... 5
4.5 Venting.........................................................................5
4.6 High Altitude ................................................................5
SECTION 5: Major Components............................................6
5.1 General........................................................................ 6
5.2 Suspension.................................................................. 6
SECTION 6: Venting................................................................7
6.1 Venting.........................................................................7
6.2 Vent Installation ........................................................... 7
6.3 Unvented Operation..................................................... 8
6.4 Horizontal Venting........................................................8
6.5 Vertical Venting............................................................ 8
6.6 Length Requirements ..................................................8
6.7 Vent Material................................................................ 9
SECTION 7: Air Supply......................................................... 13
7.1 Separated Combustion Installation............................. 13
7.2 Unvented Installation.................................................. 13
7.3 Building Ventilation ..................................................... 13
7.4 Outside Combustion Air Supply.................................. 13
SECTION 8: Gas Piping........................................................14
8.1 Connections............................................................... 14
SECTION 9: Wiring................................................................ 15
9.1 Positioning Thermostats ............................................ 15
9.2 Low Voltage Thermostat with One Heater ................. 15
9.3 UHA[S] Series Internal Wiring Diagram..................... 16
9.4 UHA[S] Series Ladder Wiring Diagram...................... 17
9.5 Electrical Connection to the Heater ........................... 18
SECTION 10: Operation and Maintenance.......................... 19
10.1 Pre-Start-Up Checks................................................19
10.2 Begin Start-Up ......................................................... 19
10.3 Complete the Start-Up ............................................. 21
SECTION 11: User Instructions............................................22
11.1 User Instructions.......................................................22
11.2 Heater Operation ......................................................22
11.3 Lighting Instructions..................................................22
11.4 Simple Troubleshooting.............................................22
SECTION 12: Servicing.........................................................24
12.1 Servicing Instructions...............................................24
12.2 Burner Maintenance.................................................24
12.3 Fan/Motor Assembly Maintenance...........................24
12.4 Heat Exchanger Maintenance ..................................24
12.5 Gas Valve Maintenance ...........................................24
12.6 Flue Blower ..............................................................24
12.7 Venting and Air Intake Pipe......................................24
12.8 Maintenance Checklist.............................................25
SECTION 13: Troubleshooting .............................................27
13.1 General ....................................................................27
13.2 Troubleshooting For Automatic Ignition
Burner Systems .......................................................28
13.3 Troubleshooting for Flame Supervision System .......29
13.4 Troubleshooting for Gas Valves................................30
13.5 Troubleshooting for Flue Blower...............................30
SECTION 14: Replacement Parts.........................................31
14.1 Gas Valve .................................................................31
14.2 Burner Compartment ...............................................32
14.3 Ignition Electrode and Flame Probe .........................33
14.4 Heat Exchanger .......................................................34
14.5 Louvers and Louver Spring ......................................34
14.6 Flue Blower .............................................................35
14.7 Pressure Switch........................................................36
14.8 Ignition Control .........................................................36
14.9 Axial Fan/Guard/Motor Assembly.............................36
14.10 Limit Switches ........................................................37
SECTION 15: Specifications.................................................38
15.1 Standard (Models 150 - 400) UHA[S] Series
Dimension Data .......................................................38
15.2 General Technical Data Table (All Models) ..............39
15.3 Technical Data Table (All Models) ............................39
SECTION 16: The ROBERTS GORDON
UHA-Series Warranty.....................................41
®
COMBAT
®
Printed in U.S.A.
TABLE OF FIGURES
Figure 1: Installation Clearances and Clearances
to Combustibles......................................................... 4
Figure 2: Suspension Methods ................................................. 6
Figure 3: Vent and Roof Detail ..................................................9
Figure 4: Standard Vented Heater - Vertical
and Horizontal Vent Termination................................ 9
Figure 5: Standard Vented Heater - Common
Vertical Vent Termination......................................... 10
Figure 6: Separated Combustion Heater - Vertical
and Horizontal Vent Termination.............................. 11
Figure 7: Concentric Vent Box ................................................ 11
Figure 8: Concentric Vertical and Horizontal Vent
Termination - Separated Combustion Heater .......... 12
Figure 9: Gas Connection ....................................................... 14
Figure 10: Automatic Burner Control Sequence......................20
Figure 11: Gas Valve for Models UHA[S] 150 - 400 ................ 20
Figure 12: LED Diagnostic Codes ...........................................22
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. Heaters are not approved for residential installation. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation. Thin sheet metal parts, including the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. Before installation, ch‘eck that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible.
SECTION 1: HEATER SAFETY
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
1
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
CAUTION
Do not use heater in an area containing corrosive chemicals.
Avoid the use of corrosive chemicals to ensure a longer life of the burner, heat exchanger and other parts.
Failure to follow these instructions can result in property damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
2.2 Corrosive Chemicals
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a Local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for combustion, ventilation and distribution in
of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen ele­ments (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
accordance with local codes.
2.1 Wall Tag
A laminated wall tag is included with the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater.
A copy of the wall tag (P/N 91040031) is illustrated on the back cover.
Know your model number. Model number is found on the heater and in the Installation, Operation and Service Manual. See Page 9, Figure 3 through Page 14, Figure 9.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[S] heaters have automatic ignition burners for ON/OFF operation only.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with horizontal discharge.
• May be mounted on a shelf of non-combustible material.
• May be suspended from above (See Page 6, Figure 2) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table on Page 38, Section 15.1. Drop rods must be a minimum of 3/8" diameter mild steel. Four suspension points (3/8" nuts) are located on top of the heater.
• Must be installed in a manner which allows access to all serviceable components. See Page 4, Figure 1 for details.
SECTION 3: CRITICAL CONSIDERATIONS
3.7 Electrical Supply
A permanent 120 V 60 Hz 1 Ø electrical supply is required for the main electrical power. The heater also requires suitable controls in accordance with See Page 15, Section 9.
3.8 Vent
Choose heater orientation to allow for the proper location of the vent. Each heater must be fitted with a correctly sized sealed vent system.
If vented horizontally, no other appliance may be connected to the vent. See Page 7, Section 6.
3.9 Separated Combustion Installation
For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.
Separated combustion units may not be common vented. See Page 7, Section 6.
3.3 Minimum Required Installation Clearances
Clearances around the heater and vent must be as indicated on Page 4, Figure 1; Page 9, Figure 3 through Page 12, Figure 8 to ensure access for servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
1. If clearances to combustibles are not indicated,
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national codes on Page 7, Section 6.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight on Page 14, Section 8.
3
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
6"**
(15 cm)
31" (79 cm)
3"
6"
(15 cm)
Clearances to Combustibles
24" for adequate air flow access axial fan.
10'
(3 m)
Wall
Terminal
Roof Terminal
Top
20' (6.0 m) - 30' (9.1 m)
Max. Mounting Height*
Installation Clearances
(Optional separated
combustion concentric
venting shown.)
* Recommended mounting height varies with heater input. Heaters may be mounted at a higher level if destratification fans are installed.
Note: Venting directly from top of heater not applicable on Models 150 - 400.
Clearance to Vent: 2" (5 cm)
**31" (79 cm) minimum is necessary for servicing.
The heater must always be installed at least 6' (2 m) above the floor. The vent pipe must have clearance from combustibles by 2" (5 cm). If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.
Figure 1: Installation Clearances and Clearances to Combustibles
4
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the name plate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
• In accordance with the Standard for Parking Structures NFPA 88A, heaters must be located a minimum of 18" (50 cm) below the floor-ceiling assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision, heaters must not be installed less than 8' (2.4 m) above the floor.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.6 High Altitude
These heaters are approved for installations up to 2000' (610 m). In USA, consult factory if heater is to be installed above 2000' (610 m). In Canada, high altitude conversion kits are available for installations up to 4500' (1370 m). Installations above 4500' (1370 m) in Canada is by local or provincial authority.
5
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod minimum.
Failure of the supports can result in death, injury or property damage.
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8" Threaded Rod
Nut
Washer
Riv Nut
Support Points
Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.
Washer
3/8"
Threaded
Rod
Nut
Unistrut
Channel Nut
SECTION 5: MAJOR COMPONENTS
5.1 General
Heaters are designed for installation above 6' (1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.
5.2 Suspension
For typical suspension, See Page 6, Figure 2.
Figure 2: Suspension Methods
6
SECTION 6: VENTING
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
6.1 Venting
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code. Any portion of vent pipe passing through a combustible wall must have a listed thimble to conform with the above codes.
The heater may be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 8, Section 6.3 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 4, Figure 1.
The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.
Vent terminal must be beyond any combustible overhang.
Secure all joints with corrosion resistant #8 x 3/8" sheet metal screws.
For single wall venting, pressure sensitive aluminum tape or silicone sealant must be used to seal all joints.
Aluminum tape shall have a minimum temperature rating of 400° F (204° C) and meet SMACNA AFTS­100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).
6.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.
NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.
SECTION 6: VENTING
6.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
6.2 Vent Installation
For vented units, the vent must terminate outside of the building.
Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed on Page 9, Figure 3 through Page 12, Figure 8. The joints between the vent terminal and the roof or wall must be properly sealed. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.
For vent termination See Page 9, Figure 3 through Page 12, Figure 8.
6.2.1 Standard Vented Heaters (Models UHA 150 - 400)
The vent must be fitted with a low resistance terminal. See Page 9, Figure 3 through Page 9, Figure 4. Standard vented heaters do not allow outdoor air intake for combustion air.
7
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
WARNING
6.2.2 Separated Combustion Heaters (Models UHAS 150 - 400)
The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals. See Page 12, Figure 8. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof.
6.3 Unvented Operation
6.5 Vertical Venting
Vertically vented heaters can be common vented (up to 4 heaters). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. Vent from the rear of the heater cabinet then run the vent vertically and use a condensate drain at the bottom of the vertical vent. Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3 m).
For 4'' (10 cm), an approved vent cap (P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap (P/N 90502103) must be used.
For common vertical venting of more than two heaters, See Page 10, Figure 5.
A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.
For unvented operation in commercial installations, sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).
WA R NI NG : Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
6.4 Horizontal Venting
Horizontally vented heaters must be individually vented.
Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3 m). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. For vents pitched up toward the vent terminal, place the condensation drain within 5' (1.5 m) of the heater.
In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.
Instead of an insulated vent terminal, a listed thimble (with 2" air gap) may be used with a 4" vent cap (P/N
90502102).
6.6 Length Requirements
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. The entire vent should be insulated with foil faced fiberglass insulation (1/2" thick, 1-1/2# density minimum).
Maximum Vent Lengths Table
Model UHA[S]
150 - 400
40 ft (12.2 m) 1 35 ft (10.7 m) 2
30 ft (9.1 m) 3
25 ft (7.6 m) 4
20 ft (6.1 m) 5
# of Elbows
8
SECTION 6: VENTING
Roof
Vent
Terminal
Listed Thimble
Flashing
or Rain Collar
Vent
2" Air Gap to
Combustible Material
Vent Terminal
4" Dia.Vent
Flashing (By Others)
Listed Thimble (2" Clearance)
Vent Terminal
Vertical
Option
Horizontal
Option
Vent
Listed
Thimble
(2" Clearance)
Flashing (By Others)
12" (31 cm) Minimum
Condensate
Trap to Drain
(Optional)
Note: Vent supports not shown.
90° Bend
Model Vent Diameter Part Number
UHA 150 - 400 4" (10 cm) 90502102
6.7 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 7, Section
6.2.
If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent manufacturer's clearance from vent material is maintained. Seal annular space of the type B-1 vent as well as all joints in the remaining vent.
Figure 3: Vent and Roof Detail
Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination
9
COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Roof
18" (46 cm)
Min.
Type "B" vent cap (7" or 8") may be used. (These are not available from Roberts-Gordon.)
Roof
Flashing
Approved
Thimble
(If Applicable)
Type "B" Vent Pipe
4" (10 cm)
Single Wall Pipe
4" (10 cm)
Single Wall Pipe
"D" Area must equal sum
of open area of
individual vents.
"D"
Single Wall Pipe
The last section of vent pipe passing through the roof or wall may be Type "B" vent pipe. All other vent materials in the building must be single wall vent pipe.
TOP VIEW
SIDE VIEW
Figure 5: Standard Vented Heater - Common Vertical Vent Termination
10
Loading...
+ 36 hidden pages