Thank you for purchasing this RKC product. In order to
achieve maximum performance and ensure proper operation
of your new instrument, carefully read all the instructions in
this manual. Please place this manual in a convenient
location for easy reference.
SYMBOLS
WARNING
CAUTION
An external protection device must be installed if
failure of this instrument could result in damage to
the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to
instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to
instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than
factory-approved personnel. Malfunction can occur
and warranty is void under these conditions.
This is a Class A instrument. In a domestic environment,
this instrument may cause radio interference, in which
case the user may be required to take adequate
measures.
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire,
etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should
!
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating
procedures.
: This mark indicates supplemental information
on installation, handling and operating
procedures.
: This mark indicates where additional
information may be located.
WARNING
!
CAUTION
This instrument is protected from electric shock by
reinforced insulation. Provide reinforced insulation
between the wire for the input signal and the wires for
instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit
respectively for the following:
− If input/output or signal lines within the building are
longer than 30 meters.
− If input/output or signal lines leave the building,
regardless the length.
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such
as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating
personnel.
All precautions described in this manual should be taken
to avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect
action.
The power must be turned off before repairing work for
input break and output failure including replacement of
sensor, contactor or SSR, and all wiring must be
completed before power is turned on again.
To prevent instrument damage or failure, protect the
power line and the input/output lines from high currents
with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling
inside instrument case to avoid electric shock, fire or
malfunction.
Tighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dispensation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to
clean the instrument. Deformation or discoloration will
occur. Use a soft, dry cloth to remove stains from the
instrument.
To avoid damage to instrument display, do not rub with
an abrasive material or push front panel with a hard
object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control,
computer technology and communications.
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument
failure or indirect damage.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a
limited service life, or characteristics that change over
time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty
expressed or implied, with respect to the accuracy of the
information. The information in this manual is subject to
change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or
retrieved through any mechanical, electronic, optical or
other means without prior written approval from RKC.
ll Rights Reserved, Copyright 2002, RKC INSTRUMENT
RKC INSTRUMENT INC.
®
1. OUTLINE
A
3. PARTS DESCRIPTION
One temperature control (TIO) module [extension type] enables
temperature control corresponding to two channels.
As the temperature control (TIO) module [extension type] is not
provided with terminals for power supply and host
communication, it is always used together with the module
(temperature control module [basic type] X-TIO-A, etc.) with
terminals for power supply and host communication.
The temperature control (TIO) module [extension type] can be
connected with the temperature control (TIO) module [basic
type], the temperature control (TIO) module for PLC
communication, the digital input (DI) module and the digital
output (DO) module.
All data are set by communication. For details, see the
Module Type Controller SRX Communication
Instruction Manual (IMS01N01-E).
Host computer
Control
Control
output
output
RS-485
Digital
input
Digital
output
Temperature
control module
[basic type]
X-TIO-A
Digital output
module
X-DO-A
Temperature
control module
[extension type]
Digital input
module
X-DI-A
X-TIO-B
Terminal cover
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
3
2
4
1
5
5 5
0
6
9
7
8
3
2
4
1
5
0
6
9
7
8
Indication lamps
ddress setting
switch
Joint connector
(Right-side)
Joint connector
Terminal cover
(Left-side)
[Indication lamps]
FAIL/RUN
When normally: A green lamp turns on (RUN)
When abnormally: A red lamp turns on (FAIL)
RX/TX
During data send and receive: A green lamp turns on
EVENT 1 to 4
Display various states by setting.
During ON state: A green lamp turns on
Display contents
Event 1 state, Event 2 state, Comprehensive event state,
Output state, Control state, Executing segment state,
Time signal state
4. COMMUNICATION SETTING
Measured
input
Digital
input
Digital
output
Measured
input
SRX configuration example
2. PRODUCT CHECK
Before using this product, check each of the following:
• Model code
• Check that all of the accessories delivered are complete.
• Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
X-TIO-B- - / Y
(1) (2) (3) (4) (5) (6) (7)
(1) Type
B: Extension type (14 terminals)
(2) Input channel 1, (3) Input channel 2
K: TC K J: TC J T: TC T S: TC S
R: TC R A: TC PLⅡN: TC N E: TC E
W: TC W5Re/W26Re B: TC B
D: RTD Pt100 P: RTD JPt100
1: 0 to 10 mV DC 2: 0 to 100 mV DC 3: 0 to 1 V DC
4: 0 to 5 V DC 5: 0 to 10 V DC 6: 1 to 5 V DC
7: 0 to 20 mA DC 8: 4 to 20 mA DC
(4) Control output 1, (5) Control output 2
M: Relay contact output V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC 5 0 to 10 V DC 6: 1 to 5 V DC
7: 0 to 20 mA DC 8: 4 to 20 mA DC
Set communication setting before mounting and wiring of SRX.
4.1 Module Address Setting
Set an address of module. For this setting, use a small blade
screwdriver.
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
Address setting switch
3
2
4
1
5
5 5
0
6
9
7
8
3
2
4
1
5
0
6
9
7
8
High-order digit
3
2
4
1
5
55
setting
0
6
9
7
8
(Set value × 10)
3
2
4
Low-order digit
1
5
0
6
setting
9
7
8
(Set value × 1)
Setting range: 0 to 99
(Factory set value: 00)
For Modbus, the value obtained by adding “1” to
•
the set address corresponds to the address used
for the actual program.
Set the module address such that it is different to
•
the other addresses on the same line. Otherwise,
problems or malfunction may result.
2
IMS01N03-E3
4.2 Protocol Selections and
Communication Speed Setting
With the DIP switch which there is on the right side of module,
select communication speed, data bit configuration, protocol and
termination resistor of internal data bus.
Right side
1 2 Communication speed
OFF OFF 2400 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 9600 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit *
OFF OFF ON Data 7-bit, Even parity, Stop 1-bit *
OFF ON ON Data 7-bit, Odd parity, Stop 1-bit *
ON OFF OFF Data 8-bit, without parity, Stop 1-bit
ON OFF ON Data 8-bit, Even parity, Stop 1-bit
ON ON ON Data 8-bit, Odd parity, Stop 1-bit
*When the Modbus communication protocol selected, this
setting becomes invalid.
Factory set value: Data 8-bit, without parity
6 Protocol selection
OFF RKC communication
ON Modbus
Factory set value: RKC communication
8 Internal data bus termination resistor setting
OFF Termination resistor OFF
ON Termination resistor ON
Factory set value: Termination resistor OFF
• Switch No. 7: OFF fixed (Don’t change this one)
• When two or more modules are connected on the
same line for their use, set DIP switches
corresponding to the switches, 1 to 6 on all of the
modules to the same positions. In addition, always
turn on the switch, 8 (with the internal bus
termination resistance connected) in module of
both ends.
• Be changed into communication time setting
mode by using switch No. 4, 5 and 6.
For communication time setting mode, see the Module
Type Controller SRX Communication Instruction
Manual (IMS01N01-E).
DIP switch
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
5. MOUNTING
To prevent electric shock or instrument failure,
always turn off the power before mounting or
removing the instrument.
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature
and ambient humidity.
• Allowable ambient temperature: −10 to +50 °C
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX. W. C 29 g/m
(3) Avoid the following when selecting the mounting location:
• Rapid changes in ambient temperature, which may cause
condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or
noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Mounting consideration
• Install the module 200 mm away from the main power line.
• Ensure at least 50 mm space on top and bottom of the
control unit for maintenance and environmental reasons.
5.2 Dimensions
(Unit: mm)
125
5
WARNING
!
3
dry air at 101.3 kPa)
1106.8
78
30
IMS01N03-E3
3
5.3 DIN rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module
(A). Attach the hooks on the top of the module to the DIN rail
and push the lower section into place on the DIN rail (B).
DIN rail
(B) Push
Mounting
bracket
2. Slide the mounting bracket up to secure the module to the
DIN rail. (Fig. 2)
End Plate mounting
Hold tight both ends of the modules jointed together with the end
plates attached to the temperature control module [basic type]
and then fix the end plates with screws.
(A) Pull down
Fig. 1
Locked
Fig. 2
Temperature control module [basic type]
Removing procedures
Pull down a mounting bracket with a blade screwdriver (A). Lift
the module from bottom, and take it off (B).
(B) Lift and take off
(A) Pull down
5.4 Panel Mounting
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a
mounting hole appears.
2. Prepare one mounting bracket per module (B) sold
separately (KSRX-55) and then insert it in the rear of the
terminal board at top of the module until locked but a
mounting hole does not disappear.
3. Mount each module directly on the panel with screws which
are inserted in the mounting holes of the top and bottom
mounting brackets.
Recommended tightening torque: 0.3 N⋅m (3 kgf⋅cm)
The customer needs to provide the M3 size screws.
Select the screw length that matches the mounting
panel.
(B) Insert
Mounting bracket
(Sold separately)
[KSRX-55]
Mounting
holes
End Plate
End Plate
Joint connector cover *
*
For the conservation of the contact of connector, install a joint
connector cover (be attached to the
[basic type]) in module of both ends.
temperature control module
4
(A) Pull down
Mounting dimensions
35.25 ± 0.2
30 ± 0.2
0.2
±
130.5
M3
Module of 40.5 mm wideModule of 30 mm wide
IMS01N03-E3
r
−
−
A
−
A
5.5 Jointing Each Module
Up to 31 SRXs consisting of the each modules can be jointed
together. Joint these modules according to the following
procedure.
Jointing procedure
1. Mount the modules on the DIN rail and then joint these
modules together with the joint connector while sliding the
relevant module.
2. Lift each of the joint tabs located at the top and bottom of the
module and then insert it in the slot of the adjacent module to
fix these two modules.
For panel mounting, first joint each module and then
mount it on the panel.
Joint connecto
Joint tab
There is one joint tab at each
of the top and bottom of on
module. Therefore, fix two
adjacent modules with these
two joint tabs.
When viewed
from top
Joint tab
insertion slot
6. WIRING
To prevent electric shock or instrument failure, do
not turn on the power until all the wiring is
completed.
6.1 Wiring Cautions
For thermocouple input, use the appropriate compensation
wire.
For RTD input, use low resistance lead wire with no
difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from
instrument power line, load lines and power lines of other
electric equipment.
WARNING
!
6.2 Terminal Configuration
CT input
CT1
CT2
3
67
Input channel 1
10
B
141313
RTD1
RTD
10
B
+
Voltage/
•
Terminal No. 11 is not used.
Input channel 2 can be used as remote setting input
•
(only for voltage/current input).
In this case, control output 2 and CT input 2 become
unused.
Use the solderless terminal appropriate to the screw
•
size (M3).
5.9 mm or less
Control output 1
Voltage pulse/
Current/
Voltage
OUT1
+
2
IN1
current
Relay contact
OUT1
NO
2
5
32 1
76 5 4
11 10 9 8
14 13 12
10
13
TC1
+
−
Thermocouple
Control output 2
Voltage pulse/
Current/
Relay contact
Voltage
OUT2
+
1
5
Upper-side terminal
Lower-side terminal
Input channel 2
9
12
IN2
+
−
Voltage/
Thermocouple
current
Recommended tightening
torque: 0.4 N⋅m (4 kgf⋅cm)
OUT2
−
1
4
9
12
TC2
+
NO
4
9
B
8
12
B
RTD2
RTD
7. SPECIFICATIONS
Inputs
Number of inputs: 2 points (Isolated between each channel)
Input type:
• Thermocouple K, J, T, S, R, E, B, N (JIS-C1602-1995) PLII (NBS)
W5Re/W26Re (ASTM-E988-96)
• RTD: Pt100 (JIS-C1604-1997) JPt100 (JIS-C1604-1989, Pt100 of
JIS-C1604-1981)
• Voltage (low): 0 to 10 mV, 0 to 100 mV, 0 to 1 V
• Voltage (high): 0 to 5 V, 0 to 10 V, 1 to 5 V
• Current: 0 to 20 mA, 4 to 20 mA
(Input impedance: 250 Ω)
Sampling cycle: 25 ms
PV bias: −Input span to +Input span
CT input: 2 points
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
IMS01N03-E3
5
Outputs
Number of outputs: 2 points
(Isolated between input and output, and
between output and power supply)
Output type:
•Relay contact: 250 V AC, 3 A (Resistive load)
1a contact
Electrical life 300,000 times or more
(Rated load)
•Voltage pulse: 0/12 V DC (Load resistance 600 Ω or more)
•Current: 0 to 20 mA DC, 4 to 20 mA DC (Load resistance 600 Ω or less)
•Voltage: 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC (Load resistance 1 kΩ or more)
Control action
Number of controls: 2 points
Control method: Brilliant PID control
Reverse action or direct action is
selectable (Specify when ordering)
Additional function: Autotuning function
- With output limiter function
- With output change rate limiter
Events
Number of events: 2 points/channel
Event type: Temperature event:
Deviation high, Deviation low,
Deviation high/low, Band,
Process high, Process low
Heater break alarm (HBA) function
Number of HBA: 2 points
Setting range: 0.0 to 100.0 A (0.0 A: OFF)
Additional function: Number of event delay times:
1 to 255 times
Control loop break alarm (LBA) function
Number of LBA: 2 points
LBA time: 1 to 7200 seconds
LBA deadband (LBD) setting:
0 to Input span
Program control
Number of patterns: 16 pattern max.
(With pattern link function)
Number of segments: 16 segment/pattern max.
Time signal output: 16 point/pattern
Communications
Communication interface:
Based on RS-485, EIA standard
Communication protocol:
Connection: Internal bus
RKC communication
(ANSI X3.28 subcategory 2.5, A4)
or Modbus
Others
Power supply voltage: 24 V DC
(Supplied by temperature control
module [basic type])
Power supply voltage range:
21.6 V DC to 26.4 V DC
Current consumption: 120 mA or less/module
Ambient temperature range:
−10 to +50 °C
Ambient humidity range: 5 to 95 %RH (Non condensing)
Absolute humidity:
MAX.W.C 29 g/m
Weight: Approx. 190 g
3
dry air at 101.3 kPa
Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the
trademarks or registered trademarks of the respective companies.
The first edition: MAY 2002 [IMQ01]
The third edition: JUN. 2003 [IMQ00]