Thank you for purchasing this RKC product. In order to
achieve maximum performance and ensure proper operation
of your new instrument, carefully read all the instructions in
this manual. Please place this manual in a convenient
location for easy reference.
SYMBOLS
WARNING
CAUTION
An external protection device must be installed if
failure of this instrument could result in damage to
the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to
instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to
instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than
factory-approved personnel. Malfunction can occur
and warranty is void under these conditions.
This is a Class A instrument. In a domestic environment,
this instrument may cause radio interference, in which
case the user may be required to take adequate measures.
ll Rights Reserved, Copyright 2004, RKC INSTRUMENT INC
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire,
etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should
!
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating
procedures.
: This mark indicates supplemental information
on installation, handling and operating
procedures.
: This mark indicates where additional
information may be located.
WARNING
!
CAUTION
RKC INSTRUMENT INC.
®
This instrument is protected from electric shock by
reinforced insulation. Provide reinforced insulation between
the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit
respectively for the following:
− If input/output or signal lines within the building are
longer than 30 meters.
− If input/output or signal lines leave the building,
regardless the length.
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such
as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating
personnel.
All precautions described in this manual should be taken to
avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect
action.
The power must be turned off before repairing work for
input break and output failure including replacement of
sensor, contactor or SSR, and all wiring must be
completed before power is turned on again.
To prevent instrument damage or failure, protect the power
line and the input/output lines from high currents with a
protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling
inside instrument case to avoid electric shock, fire or
malfunction.
Tighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dispensation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean
the instrument. Deformation or discoloration will occur. Use
a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an
abrasive material or push front panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control,
computer technology and communications.
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument
failure or indirect damage.
RKC is not responsible for any damage and/or injury
resulting from the use of instruments made by imitating this
instrument.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a
limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty
expressed or implied, with respect to the accuracy of the
information. The information in this manual is subject to
change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or
retrieved through any mechanical, electronic, optical or
other means without prior written approval from RKC.
1. OUTLINE
2. PRODUCT CHECK
The temperature control module for Ethernet V-TIO-P/V-TIO-Q
has one modular connector (RJ-45) for connection to Ethernet.
This module conforms to Modbus/TCP (Modbus protocol)
operating on TCP/IP of Ethernet.
One this module enables temperature control corresponding to
two channels. It has power supply terminals in addition to
temperature control input and output terminals.
In addition, one digital input (DI) point and two digital output (DO)
points can be optionally added.
Computer
(Client)
Ethernet
Temperature control
module for Ethernet
V-TIO-P/V-TIO-Q
Network Hub
(Server)
Ethernet
Power supply
input (24 V DC)
Control
output
Measured
input
Usable modules:
Temperature control (TIO) module
•
[Basic type]: V-TIO-A/V-TIO-C
Temperature control (TIO) module
•
[Extension type]: V-TIO-B/V-TIO-D
(Up to 30 modules)
Event connector (option)
Digital input: 1 point
Digital output: 2 points
The data request side is called “client” (such as
computer) and the data response (supply) side is called
“server” (SRV).
Basically, one client corresponds to one server (SRV)
(i.e. one to one). However, one client can communicate
with two or more servers depending on the program on
the client side, but two or more clients cannot
communicate with one server.
All data are set by communication. For details, see the
Module Type Controller SRV Ethernet [Modbus/TCP]
Communication Instruction Manual (IMS01P09-E).
Before using this product, check each of the following:
• Model code
• Check that all of the accessories delivered are complete.
• Check that there are no scratch or breakage in external
K040 to 800 °C KB8 32 to 1472 °F
K16−200 to +1372 °C KB7 −328 to +2501 °FK090.0 to 400.0 °C KC2 32.0 to 752.0 °F
K35 −200.0 to +400.0 °C KC1 −328.0 to +752.0 °F
J J020 to 400 °C JC2 32 to 752 °F
J040 to 800 °C JC1 32 to 1472 °F
J15−200 to +1200 °C JB9 −328 to +2192 °FJ090.0 to 400.0 °C JC4 32.0 to 752.0 °F
J27 −200.0 to +400.0 °C JC3 −328.0 to +752.0 °F
T T080 to 400 °C TB9 32 to 752 °F
T090 to 200 °C TC1 32 to 392 °F
T16−200 to +400 °C TB8 −328 to +752 °F
T060.0 to 400.0 °C TC3 32.0 to 752.0 °F
T19 −200.0 to +400.0 °C TC2 −328.0 to +752.0 °F
E E010 to 800 °C EA8 32 to 1472 °F
E020 to 1000 °C EA7 32 to 1832 °F
S S050 to 1768 °C SA6 32 to 3214 °F
R R060 to 1768 °C RA6 32 to 3214 °F
N N020 to 1300 °C NA6 32 to 2372 °F
B B030 to 1800 °C BB1 32 to 3272 °F
PLⅡA020 to 1390 °C AA6 32 to 2534 °F
W5Re/
W26Re
[RTD input]
Type CodeRange Code Range
Pt100D170 to 400 °C DC5 32 to 752 °F D330 to 850 °C DC4 32 to 1562 °F D160.0 to 400.0 °C DC7 32.0 to 752.0 °F
D28 −200.0 to +400.0 °C DC6 −328.0 to +752.0 °F
JPt100P170 to 400 °C PC5 32 to 752 °F P230 to 600 °C PC4 32 to 1112 °F P160.0 to 400.0 °C PC7 32.0 to 752.0 °F
P28 −200.0 to +400.0 °C PC6 −328.0 to +752.0 °F
[Voltage/current input]
0 to 100 mV DC 201
0 to 5 V DC 401Programmable
0 to 10 V DC 501−2000 to +10000
1 to 5 V DC
0 to 20 mA DC701
4 to 20 mA DC801
W030 to 2300 °C WA9 32 to 4172 °F
Type CodeRange
601
(Factory set value: 0.0 to 100.0 %)
Decimal point position can be changed
2
IMS01P08-E3
A
X
X
X
(4) Control output (CH1), (5) Control output (CH2)
M: Relay contact output
V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC
5: 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(6) Event input (DI) [Optional]
N: None
1: Control RUN/STOP
2: Event interlock release
[(8), (10) code: Output type]
N: None
A: Deviation high
B: Deviation low
C: Deviation high/low
D: Band
E: Deviation high with hold action
F: Deviation low with hold action
G: Deviation high/low with hold action
H: Process high
J: Process low
K: Process high with hold action
L: Process low with hold action
Q: Deviation high with re-hold action
R: Deviation low with re-hold action
T: Deviation high/low with re-hold action
P: Heater break alarm
1: Control loop break alarm
2: Burnout
3: Temperature rise completion
(11) CT type (Each channel common code)
P: CTL-6-P-N
S: CTL-12-S56-10L-N
(12) Communication protocol
1: Modbus/TCP
* When “N” is selected in (7) or (9), (8) or (10) becomes “N.”
• For heat/cool PID control (V-TIO-Q), input channel
2 becomes unused.
• For heat/cool PID control (V-TIO-Q), Control output
(CH1) corresponds to the heating output and
Control output (CH2) corresponds to the cooling
output.
• Heater break alarm function cannot be used when
control output is voltage/current output.
Accessories
End Plate ................................................................... 2
When normally: Red lamp: OFF
When abnormally: Red lamp: ON
RUN (for Ethernet communication)
When normally: Green lamp: ON
When abnormally [Module configuration error, input error]:
Green lamp: slow flashing
Data collection just after the power is turned on:
Green lamp: rapid flashing
TX
During data send: Green lamp: flashing
RX
During data receive: Green lamp: flashing
[Indication lamps 3]
Link
10BASE-T link: Amber lamp: ON
100BASE-TX link: Green lamp: ON
[Indication lamps 4]
Activity
Half-duplex; activity: Amber lamp: Momentary ON
Full-duplex; activity: Green lamp: Momentary ON
3
4
5
5 5
6
7
8
3
4
5
6
7
8
Temperature control sideEthernet communication side
Terminal cover
Indication lamps 1
ddress setting
switch
Event
connector *
Terminal cover
Indication
lamp 1
IMS01P08-E3
3
4. COMMUNICATION SETTING
A
Set communication setting before mounting and wiring of SRV.
CAUTION
Do not separate the module mainframe from the terminal
base with the power turned on. If separated, adjusted data
may be destroyed; control be stopped, and no return can be
made.
4.1 Module Address Setting
Set a module address. For this setting, use a small blade
screwdriver.
When using two or more modules, set the desired address to
each module.
ddress setting switch
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
3
2
4
1
5
5 5
0
6
9
7
8
3
2
4
1
5
0
6
9
7
8
Set the address such that it is different to the other
addresses on the same line. Otherwise, problems or
malfunction may result.
4.2 Internal Communication Setting
Ethernet communication side setting
Set the communication speed for internal communication by
using the DIP switch 1.
Left side
1 2 Communication speed
OFF OFF 38400 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 38400 bps
• Switch No. 3 to 8: OFF fixed
(Don’t change this one)
• The communication speed sets the same value as
a temperature control side (DIP switch 3) setting.
3
2
4
1
High-order digit setting
5
55
0
6
9
(set value × 10)
7
8
3
2
4
1
5
Low-order digit setting
0
6
9
7
8
(set value × 1)
Setting range: 0 to 30
(Factory set value: 0)
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
Temperature control side setting
Set the communication speed and data bit configuration for
internal communication by using the DIP switch 3.
Terminal base
DIP switch 3
ON
Module mainframe
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
Right side
1 2 Communication speed
OFFOFFDon’t set this one
ONOFF9600 bps
OFFON19200 bps
ONON38400 bps
Factory set value: 38400 bps
3 4 5 Data bit configuration
OFFOFFOFF
OFFOFFON
OFFONOFF
Don’t set this one
OFFONON
ONOFFOFFData 8-bit, without parity, Stop 1-bit
ONOFFON
ONONOFF
Don’t set this one
ONONON
Factory set value (Fixed): Data 8-bit, without parity, Stop 1-bit
• Switch No. 6: ON fixed (Don’t change this one)
Switch No. 7, 8: OFF fixed (Don’t change this one)
• When connecting two or more modules (V-TIO-A,
V-TIO-B, V-TIO-C or V-TIO-D) to the
V-TIO-P/V-TIO-Q module, match all of their
communication speed and data bit configuration
settings with the internal settings of the
V-TIO-P/V-TIO-Q module.
4.3 Other Setting
It is possible to set the IP address using DIP switch 1 and DIP
switch 2.
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DIP switch 2
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Left side
For details of IP address setting by switch, see the
Module Type Controller SRV Ethernet [Modbus/TCP]
Communication Instruction Manual (IMS01P09-E).
ON
OFF
ON
OFF
4
IMS01P08-E3
5. MOUNTING
To prevent electric shock or instrument failure,
always turn off the power before mounting or
removing the instrument.
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature
and ambient humidity.
• Allowable ambient temperature: −10 to +50 °C
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX.W.C 29 g/m
(3) Avoid the following when selecting the mounting location.
• Rapid changes in ambient temperature, which may cause
condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or
noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Mounting consideration
• Install the module 200 mm away from the main power line.
• Ensure at least 50 mm space on top and bottom of the control
unit for maintenance and environmental reasons.
5.2 Dimensions
110
WARNING
!
3
dry air at 101.3 kPa)
(Unit: mm)
6.8
40.5
5.3 DIN rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module
(A). Attach the hooks on the top of the module to the DIN rail
and push the lower section into place on the DIN rail (B).
DIN rail
(B) Push
Mounting
bracket
2. Slide the mounting bracket up to secure the module to the
DIN rail.
End Plate mounting
Hold tight both ends of the modules jointed together with the end
plates and then fix the end plates with screws. Even if only one
V-TIO-P/V-TIO-Q module is used, also hold tight both ends of
the module with the end plates.
End Plate
(A) Pull down
Locked
V-TIO-P/V-TIO-Q
module
End Plate
125
5
78
The above figure shows when provided with the event
connector, but the same also when not provided with the
connector.
Depth in connector mounting
Conduct installation in consideration of the sizes of the
connector and cable when connector-connected.
[Usage example of SRVP-01]
Approx. 50
110
(Unit: mm)
Connector (plug):
SRVP-01 (sold separately)
Joint connector cover *
*
For the conservation of the contact of connector, install a joint
connector cover in module of both ends.
Removing procedures
Pull down a mounting bracket with a blade screwdriver (A). Lift
the module from bottom, and take it off (B).
(B) Lift and take off
(A) Pull down
IMS01P08-E3
5
5.4 Panel Mounting
r
−
A
−
−
A
−
p
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a
mounting hole appears.
2. Prepare one mounting bracket per module (B) sold
separately (KSRX-55) and then insert it in the rear of the
terminal board at top of the module until locked but a
mounting hole does not disappear.
3. Mount each module directly on the panel with screws which
are inserted in the mounting holes of the top and bottom
mounting brackets.
Recommended tightening torque: 0.3 N⋅m (3 kgf⋅cm)
The customer needs to provide the M3 size screws.
Select the screw length that matches the mounting
panel.
(B) Insert
Mounting
Mounting bracket
(Sold separately)
(A) Pull down
[KSRX-55]
30 ± 0.2
Mounting
holes
(Unit: mm)
dimensions
35.25 ± 0.2
0.2
±
M3
Module of 40.5 mm wide Module of 30 mm wide
130.5
5.5 Jointing Each Module
Up to 31 SRVs consisting of the each modules can be jointed
together. Joint these modules according to the following
procedure.
Jointing procedures
1. Mount the modules on the DIN rail and then joint these
modules together with the joint connector while sliding the
relevant module.
2. Lift each of the joint tabs located at the top and bottom of the
module and then insert it in the slot of the adjacent module to
fix these two modules.
For panel mounting, first joint each module and then
mount it on the panel.
Joint connecto
Joint tab
There is one joint tab at each
of the top and bottom of on
module. Therefore, fix two
adjacent modules with these
two joint tabs.
When viewed
from top
Joint tab
insertion slot
6. WIRING
To prevent electric shock or instrument failure, do
not turn on the power until all the wiring is
com
leted.
6.1 Wiring Cautions
For thermocouple input, use the appropriate compensation
wire.
For RTD input, use low resistance lead wire with no
difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from
instrument power line, load lines and power lines of other
electric equipment.
If there is electrical noise in the vicinity of the instrument that
could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire
pitches to achieve the most effective noise reduction.
− Always install the noise filter on a grounded panel.
Minimize the wiring distance between the noise filter output
and the instrument power supply terminals to achieve the
most effective noise reduction.
− Do not connect fuses or switches to the noise filter output
wiring as this will reduce the effectiveness of the noise filter.
Power supply wiring must be twisted and have a low voltage
drop.
For an instrument with 24 V power supply, supply power from
a SELV circuit.
6.2 Terminal Configuration
CT input Control output 1 Control output 2
CT1
Power supply
Ground
20
FG
Voltage pulse/
CT2
3
67
18
19
DC
+
24 V
• For heat/cool PID control (V-TIO-Q), Input channel
2 becomes unused.
• For heat/cool PID control (V-TIO-Q), Control output
1 corresponds to the heating output and Control
output 2 corresponds to the cooling output.
WARNING
!
Current/
Relay contact
Voltage
OUT1
+
2
1413
OUT1
NO
2
5
16 15 3 2 1
17 7 6 5 4
18 11 10 9 8
20 19 14 13 12
Input channel 1
10
10
B
B
RTD1
RTD
+
Therm ocoupl e
+
5
TC1
10
IN1
Voltage/
Voltage/
Current
Current
Voltage pulse/
Current/
Voltage
OUT2
−
+
1
4
Upper-side terminal
Lower-side terminal
9
13
−
+
Thermocouple
9
13
+
−
Voltage/
Current
Relay contact
OUT2
NO
1
4
Input channel 2
9
B
12
TC2
12
IN2
RTD
12
B
RTD2
8
6
IMS01P08-E3
• Terminal No. 11, 15, 16 and 17 are not used.
r
t
8
3
Do not connect to these terminals.
• Use the solderless terminal appropriate to the screw
size (M3)
5.9 mm or less
.
Recommended tightening
torque: 0.4 N⋅m (4 kgf⋅cm)
.2 mm or more
6.3 Pin Layout of Connector
Modular connector for Ethernet
Modular connecto
for Etherne
RJ-45
Pin layout
1
Event connector (optional)
This is a connector installed in the V-TIO-P/V-TIO-Q module only
when provided with the event input (DI) or the event output (DO).
Event connector
(socket)
Pin
No.
1
1
2
3
4
6
5
6
Description
Digital input (DI) (
Digital input (DI) (
−)
+)
Digital output (DO) 1
(Relay contact output)
Digital output (DO) 2
(Relay contact output)
Circuit configuration
1
DI
2
24 V DC
Pin No. Signal name Symbol
1
2
3
Send data + TX+
Send data − TX−
Receive data + RX+
4 Unused
5 Unused
6
Receive data − RX−
7 Unused
8 Unused
Customer must provide the Ethernet communication
cable. In addition, use straight cables when connected
to the network hub, and use a cross cable when directly
connected to the computer.
However, cables different from the above cables may
be used depending on the connecting device used.
Therefore follow the instructions for each connecting
device.
Computer
TX
TX
RX
RX
+
−
+
−
Network Hab
TX+
TX−
RX+
RX−
Load
Load
Attention in Connector (plug) Wiring
• Use the following connector (plug) as that connected to the
event input/output connector.
3
DO1
4
5
DO2
6
Connector (plug) is sold separately.
SRVP-01 (Front-screw type)
SRVP-02 (Side-screw type)
• The lead wires use the stranded wire.
2
• Use the stranded wire from size 0.2 to 2.5 mm
(AWG 24-12).
• Stripping length is as follows.
SRVP-01: 10 mm
SRVP-02: 7 mm
• Recommended tightening torque of the lead wire in the
V-TIO-P/V-TIO-Q
module
TX
+
TX
−
RX
+
RX
−
TX+
TX−
RX+
RX−
connector (plug): 0.5 to 0.6 N⋅m (5 to 6 kgf⋅cm)
Screw size: SRVP-01: M2.5
SRVP-01: M3
[SRVP-01] Front-screw type [SRVP-02] Side-screw type
Straight cable Straight c able
Computer
TX
+
TX
−
RX
+
RX
−
Cross cable
Use the RJ-45 type of modular connector as the
connector plugged into the V-TIO-P/V-TIO-Q module.
V-TIO-P/V-TIO-Q
module
TX+
TX−
RX+
RX−
IMS01P08-E3
Stripping length
10 mm
Stripping length
7 mm
Stranded wire size:
0.2 to 2.5 mm
(AWG 24-12)
Recommended tightening
torque: 0.5 to 0.6 N⋅m
(5 to 6 kgf⋅cm)
2
Stranded wire size:
0.2 to 2.5 mm
(AWG 24-12)
Recommended tightening
torque: 0.5 to 0.6 N⋅m
(5 to 6 kgf⋅cm)
2
7
[IMQ
]
7. SPECIFICATIONS
Inputs
Number of inputs: 2 points
Isolated between each channel:
Thermocouple input, Voltage (low) input
Not isolated between each channel:
RTD input, Voltage (high) input,
Current input
Input type:
•Thermocouple K, J, T, S, R, E, B, N (JIS-C1602-1995)
PLII (NBS)
W5Re/W26Re (ASTM-E988-96)
•RTD Pt100 (JIS-C1604-1997)
JPt100 (JIS-C1604-1989, Pt100 of
JIS-C1604-1981)
• Voltage (low) 0 to 100 mV
• Voltage (high) 0 to 5 V, 0 to 10 V, 1 to 5 V
• Current 0 to 20 mA, 4 to 20 mA
Sampling cycle: 500 ms
PV bias: −Input span to +Input span
CT input: 2 points
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
Outputs
Number of outputs: 2 points
(Isolated between input and output, and
between output and power supply)
Output type:
• Relay contact: 250 V AC, 3 A (Resistive load) 1a contact
Electrical life 300,000 times or more
(Rated load)
• Voltage pulse: 0/12 V DC (Load resistance 600 Ω or more)
• Current: 0 to 20 mA DC, 4 to 20 mA DC (Load resistance 600 Ω or less)
• Voltage: 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC (Load resistance 1 kΩ or more)
Control action
Number of controls: 2 points
Control method: Brilliant PID control
Reverse action or direct action is
selectable (Specify when ordering)
Heat/cool control is selectable
(Specify when ordering)
Additional function: Autotuning function
Output details: Temperature event, Heater break alarm,
Ethernet communication
Physical layer: Ethernet
Application layer: Modbus/TCP
Communication data: Based on Modbus message format
Connector type: RJ-45
Maximum connections: Up to 30 temperature control modules
Others
Power supply voltage: 24 V DC
Power supply voltage range:
Current consumption: With event input/output (option):
Control loop break alarm, Burnout,
Temperature rise completion
(Specify when ordering)
10BASE-T/100BASE-TX automatic
recognition
can be connected to one
V-TIO-P/V-TIO-Q module.
21.6 V DC to 26.4 V DC
220 mA max./module
Without event input/output (option):
200 mA max./module
−10 to +50 °C
5 to 95 %RH
Absolute humidity:
MAX.W.C 29 g/m
Approx. 270 g
Without event input/output (option):
Approx. 260 g
CSA: CAN/CSA-C22.2 No1010.1
EMC: EN55011, EN61326-1
(equivalent to EN55011)
3
dry air at 101.3 kPa
Events
Number of events: 2 points/channel
Event type: Temperature event:
Deviation high, Deviation low,
Deviation high/low, Band,
Process high, Process low
Heater break alarm,
Control loop break alarm,
Burnout, Temperature rise completion
Option
Event input (DI)
Number of inputs: 1 point
Input type: Dry contact input
Input voltage: 24 V DC (Rated)
Input current: Approx. 6 mA
Input details: Control RUN/STOP,
Event interlock release
(Specify when ordering)
Ethernet is a registered trademark of Xerox Corp.
Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the
trademarks or registered trademarks of the respective companies.
The first edition: JUN. 2004 [IMQ00]
The third edition: JUN. 2005
00
Event output (DO)
Number of outputs: 2 points
Output type: Relay contact output
JUN. 2005 IMS01P08-E3
250 V AC, 1 A (Resistive load)
1a contact
Electrical life 300,000 times or more
(Rated load)