RKC V-TIO-Q Instruction Manual

A
Module Type Controller SRV
Temperature Control Module for Ethernet
Instruction Manual
IMS01P08-E3
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
An external protection device must be installed if
failure of this instrument could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
This is a Class A instrument. In a domestic environment,
this instrument may cause radio interference, in which case the user may be required to take adequate measures.
ll Rights Reserved, Copyright 2004, RKC INSTRUMENT INC
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken, damage to the instrument may result.
: This mark indicates that all precautions should
!
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating procedures.
: This mark indicates supplemental information
on installation, handling and operating procedures.
: This mark indicates where additional
information may be located.
WARNING
!
CAUTION
RKC INSTRUMENT INC.
®
This instrument is protected from electric shock by
reinforced insulation. Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit
respectively for the following:
If input/output or signal lines within the building are longer than 30 meters.
If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to
avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage or failure, protect the power
line and the input/output lines from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling
inside instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dispensation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean
the instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an
abrasive material or push front panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury
resulting from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
1. OUTLINE
2. PRODUCT CHECK
The temperature control module for Ethernet V-TIO-P/V-TIO-Q has one modular connector (RJ-45) for connection to Ethernet. This module conforms to Modbus/TCP (Modbus protocol) operating on TCP/IP of Ethernet. One this module enables temperature control corresponding to two channels. It has power supply terminals in addition to temperature control input and output terminals. In addition, one digital input (DI) point and two digital output (DO) points can be optionally added.
Computer
(Client)
Ethernet
Temperature control module for Ethernet V-TIO-P/V-TIO-Q
Network Hub
(Server)
Ethernet
Power supply input (24 V DC)
Control
output
Measured
input
Usable modules:
Temperature control (TIO) module
[Basic type]: V-TIO-A/V-TIO-C Temperature control (TIO) module
[Extension type]: V-TIO-B/V-TIO-D
(Up to 30 modules)
Event connector (option)
Digital input: 1 point Digital output: 2 points
The data request side is called “client” (such as computer) and the data response (supply) side is called “server” (SRV).
Basically, one client corresponds to one server (SRV) (i.e. one to one). However, one client can communicate with two or more servers depending on the program on the client side, but two or more clients cannot communicate with one server.
All data are set by communication. For details, see the
Module Type Controller SRV Ethernet [Modbus/TCP] Communication Instruction Manual (IMS01P09-E).
Before using this product, check each of the following:
Model code
Check that all of the accessories delivered are complete.
Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
V–TIO–  /Y
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)
*
(1) Type
P: Module for Ethernet, heat control Q: Module for Ethernet, heat/cool control
(2) Control action (Each channel common code)
[For heat control] F: PID action with autotuning (AT) (reverse action) D: PID action with autotuning (AT) (direct action)
[For heat/cool control] B: Heat/cool PID action with autotuning (AT) (air cooling) W: Heat/cool PID action with autotuning (AT) (water cooling)
(3) Input range (Each channel common code)
[Thermocouple input]
Type Code Range Code Range
K K02 0 to 400 °C KB9 32 to 752 °F
K04 0 to 800 °C KB8 32 to 1472 °F K16 200 to +1372 °C KB7 328 to +2501 °F K09 0.0 to 400.0 °C KC2 32.0 to 752.0 °F K35 200.0 to +400.0 °C KC1 328.0 to +752.0 °F
J J02 0 to 400 °C JC2 32 to 752 °F
J04 0 to 800 °C JC1 32 to 1472 °F J15 200 to +1200 °C JB9 328 to +2192 °F J09 0.0 to 400.0 °C JC4 32.0 to 752.0 °F J27 200.0 to +400.0 °C JC3 328.0 to +752.0 °F
T T08 0 to 400 °C TB9 32 to 752 °F
T09 0 to 200 °C TC1 32 to 392 °F T16 200 to +400 °C TB8 −328 to +752 °F T06 0.0 to 400.0 °C TC3 32.0 to 752.0 °F T19 200.0 to +400.0 °C TC2 328.0 to +752.0 °F
E E01 0 to 800 °C EA8 32 to 1472 °F
E02 0 to 1000 °C EA7 32 to 1832 °F S S05 0 to 1768 °C SA6 32 to 3214 °F R R06 0 to 1768 °C RA6 32 to 3214 °F N N02 0 to 1300 °C NA6 32 to 2372 °F B B03 0 to 1800 °C BB1 32 to 3272 °F
PL A02 0 to 1390 °C AA6 32 to 2534 °F W5Re/ W26Re
[RTD input]
Type Code Range Code Range
Pt100 D17 0 to 400 °C DC5 32 to 752 °F D33 0 to 850 °C DC4 32 to 1562 °F D16 0.0 to 400.0 °C DC7 32.0 to 752.0 °F D28 200.0 to +400.0 °C DC6 328.0 to +752.0 °F
JPt100 P17 0 to 400 °C PC5 32 to 752 °F P23 0 to 600 °C PC4 32 to 1112 °F P16 0.0 to 400.0 °C PC7 32.0 to 752.0 °F P28 200.0 to +400.0 °C PC6 328.0 to +752.0 °F
[Voltage/current input]
0 to 100 mV DC 201 0 to 5 V DC 401 Programmable 0 to 10 V DC 501 2000 to +10000 1 to 5 V DC
0 to 20 mA DC 701 4 to 20 mA DC 801
W03 0 to 2300 °C WA9 32 to 4172 °F
Type Code Range
601
(Factory set value: 0.0 to 100.0 %)
Decimal point position can be changed
2
IMS01P08-E3
A
X
X
X
(4) Control output (CH1), (5) Control output (CH2)
M: Relay contact output V: Voltage pulse output 0/12 V DC 4: 0 to 5 V DC 5: 0 to 10 V DC 6: 1 to 5 V DC 7: 0 to 20 mA DC 8: 4 to 20 mA DC
(6) Event input (DI) [Optional]
N: None 1: Control RUN/STOP 2: Event interlock release
(7) (8) Event output 1 (DO1) [Optional] (9) (10) Event output 2 (DO2) [Optional]
* *
[(7), (9) code: Channel selection] N: None 1: Input channel 1 2: Input channel 2
[(8), (10) code: Output type] N: None A: Deviation high B: Deviation low C: Deviation high/low D: Band E: Deviation high with hold action F: Deviation low with hold action G: Deviation high/low with hold action H: Process high J: Process low K: Process high with hold action L: Process low with hold action Q: Deviation high with re-hold action R: Deviation low with re-hold action T: Deviation high/low with re-hold action P: Heater break alarm 1: Control loop break alarm 2: Burnout 3: Temperature rise completion
(11) CT type (Each channel common code)
P: CTL-6-P-N S: CTL-12-S56-10L-N
(12) Communication protocol
1: Modbus/TCP
* When “N” is selected in (7) or (9), (8) or (10) becomes “N.”
For heat/cool PID control (V-TIO-Q), input channel 2 becomes unused.
For heat/cool PID control (V-TIO-Q), Control output (CH1) corresponds to the heating output and Control output (CH2) corresponds to the cooling output.
Heater break alarm function cannot be used when control output is voltage/current output.
Accessories
End Plate ................................................................... 2
Joint connector cover................................................. 2
Instruction Manual (IMS01P08-E3) ........................... 1
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
3. PARTS DESCRIPTION
FAIL/RUN
Indication lamps 2
Indication lamp 3
RX/TX
EVENT1 EVENT2
EVENT3 EVENT4
2
1
0
9
2
1
0
9
Modular connector
for Ethernet
RJ-45
Indication lamp 4
Ethernet communication side Temperature control side
* Installed when provided with the event input or output (optional).
Indication lamp 2
FAIL
RUN
FAIL/RUN RX/T EVENT1 EVENT2
T
R
EVENT3 EVENT4
[Indication lamps 1] FAIL/RUN (for temperature control)
When normally: Green lamp: ON (RUN) When abnormally: Red lamp: ON (FAIL) During self-diagnostic error: Green lamp: flashing
RX/TX (for internal communication)
During data send and receive: Green lamp: ON
EVENT 1 to 4
Display various states by setting.
Display contents: Event 1 state, Event 2 state, Comprehensive event state,
Output state, Control state
[Indication lamps 2] FAIL (for Ethernet communication)
When normally: Red lamp: OFF When abnormally: Red lamp: ON
RUN (for Ethernet communication)
When normally: Green lamp: ON When abnormally [Module configuration error, input error]: Green lamp: slow flashing Data collection just after the power is turned on: Green lamp: rapid flashing
TX
During data send: Green lamp: flashing
RX
During data receive: Green lamp: flashing
[Indication lamps 3] Link
10BASE-T link: Amber lamp: ON 100BASE-TX link: Green lamp: ON
[Indication lamps 4] Activity
Half-duplex; activity: Amber lamp: Momentary ON Full-duplex; activity: Green lamp: Momentary ON
3
4
5
5 5
6
7
8
3
4
5
6
7
8
Temperature control sideEthernet communication side
Terminal cover
Indication lamps 1
ddress setting
switch
Event connector *
Terminal cover
Indication lamp 1
IMS01P08-E3
3
4. COMMUNICATION SETTING
A
Set communication setting before mounting and wiring of SRV.
CAUTION
Do not separate the module mainframe from the terminal base with the power turned on. If separated, adjusted data may be destroyed; control be stopped, and no return can be made.
4.1 Module Address Setting
Set a module address. For this setting, use a small blade screwdriver. When using two or more modules, set the desired address to each module.
ddress setting switch
FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVTNT4
3
2
4
1
5
5 5
0
6
9
7
8
3
2
4
1
5
0
6
9
7
8
Set the address such that it is different to the other addresses on the same line. Otherwise, problems or malfunction may result.
4.2 Internal Communication Setting
Ethernet communication side setting
Set the communication speed for internal communication by using the DIP switch 1.
Left side
1 2 Communication speed
OFF OFF 38400 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 38400 bps
Switch No. 3 to 8: OFF fixed (Don’t change this one)
The communication speed sets the same value as a temperature control side (DIP switch 3) setting.
3
2
4
1
High-order digit setting
5
5 5
0
6
9
(set value × 10)
7
8
3
2
4
1
5
Low-order digit setting
0
6
9
7
8
(set value × 1)
Setting range: 0 to 30 (Factory set value: 0)
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
Temperature control side setting
Set the communication speed and data bit configuration for internal communication by using the DIP switch 3.
Terminal base
DIP switch 3
ON
Module mainframe
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
Right side
1 2 Communication speed
OFF OFF Don’t set this one
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 38400 bps
3 4 5 Data bit configuration
OFF OFF OFF OFF OFF ON OFF ON OFF
Don’t set this one
OFF ON ON
ON OFF OFF Data 8-bit, without parity, Stop 1-bit ON OFF ON ON ON OFF
Don’t set this one
ON ON ON
Factory set value (Fixed): Data 8-bit, without parity, Stop 1-bit
Switch No. 6: ON fixed (Don’t change this one) Switch No. 7, 8: OFF fixed (Don’t change this one)
When connecting two or more modules (V-TIO-A, V-TIO-B, V-TIO-C or V-TIO-D) to the V-TIO-P/V-TIO-Q module, match all of their communication speed and data bit configuration settings with the internal settings of the V-TIO-P/V-TIO-Q module.
4.3 Other Setting
It is possible to set the IP address using DIP switch 1 and DIP switch 2.
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DIP switch 2
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Left side
For details of IP address setting by switch, see the
Module Type Controller SRV Ethernet [Modbus/TCP] Communication Instruction Manual (IMS01P09-E).
ON
OFF
ON
OFF
4
IMS01P08-E3
5. MOUNTING
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature
and ambient humidity.
Allowable ambient temperature: 10 to +50 °C
Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX.W.C 29 g/m
(3) Avoid the following when selecting the mounting location.
Rapid changes in ambient temperature, which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splashes.
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity, magnetic fields or
noise.
Direct air flow from an air conditioner.
Exposure to direct sunlight.
Excessive heat accumulation.
(4) Mounting consideration
Install the module 200 mm away from the main power line.
Ensure at least 50 mm space on top and bottom of the control
unit for maintenance and environmental reasons.
5.2 Dimensions
110
WARNING
!
3
dry air at 101.3 kPa)
(Unit: mm)
6.8
40.5
5.3 DIN rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module (A). Attach the hooks on the top of the module to the DIN rail and push the lower section into place on the DIN rail (B).
DIN rail
(B) Push
Mounting
bracket
2. Slide the mounting bracket up to secure the module to the DIN rail.
End Plate mounting
Hold tight both ends of the modules jointed together with the end plates and then fix the end plates with screws. Even if only one V-TIO-P/V-TIO-Q module is used, also hold tight both ends of the module with the end plates.
End Plate
(A) Pull down
Locked
V-TIO-P/V-TIO-Q
module
End Plate
125
5
78
The above figure shows when provided with the event connector, but the same also when not provided with the connector.
Depth in connector mounting
Conduct installation in consideration of the sizes of the connector and cable when connector-connected.
[Usage example of SRVP-01]
Approx. 50
110
(Unit: mm)
Connector (plug): SRVP-01 (sold separately)
Joint connector cover *
*
For the conservation of the contact of connector, install a joint connector cover in module of both ends.
Removing procedures
Pull down a mounting bracket with a blade screwdriver (A). Lift the module from bottom, and take it off (B).
(B) Lift and take off
(A) Pull down
IMS01P08-E3
5
5.4 Panel Mounting
r
A
A
p
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a mounting hole appears.
2. Prepare one mounting bracket per module (B) sold separately (KSRX-55) and then insert it in the rear of the terminal board at top of the module until locked but a mounting hole does not disappear.
3. Mount each module directly on the panel with screws which are inserted in the mounting holes of the top and bottom mounting brackets.
Recommended tightening torque: 0.3 Nm (3 kgf⋅cm)
The customer needs to provide the M3 size screws. Select the screw length that matches the mounting panel.
(B) Insert
Mounting
Mounting bracket (Sold separately)
(A) Pull down
[KSRX-55]
30 ± 0.2
Mounting
holes
(Unit: mm)
dimensions
35.25 ± 0.2
0.2
±
M3
Module of 40.5 mm wide Module of 30 mm wide
130.5
5.5 Jointing Each Module
Up to 31 SRVs consisting of the each modules can be jointed together. Joint these modules according to the following procedure.
Jointing procedures
1. Mount the modules on the DIN rail and then joint these modules together with the joint connector while sliding the relevant module.
2. Lift each of the joint tabs located at the top and bottom of the module and then insert it in the slot of the adjacent module to fix these two modules.
For panel mounting, first joint each module and then mount it on the panel.
Joint connecto
Joint tab
There is one joint tab at each of the top and bottom of on module. Therefore, fix two adjacent modules with these two joint tabs.
When viewed from top
Joint tab insertion slot
6. WIRING
To prevent electric shock or instrument failure, do not turn on the power until all the wiring is com
leted.
6.1 Wiring Cautions
For thermocouple input, use the appropriate compensation
wire.
For RTD input, use low resistance lead wire with no
difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from
instrument power line, load lines and power lines of other electric equipment.
If there is electrical noise in the vicinity of the instrument that
could affect operation, use a noise filter.
Shorten the distance between the twisted power supply wire
pitches to achieve the most effective noise reduction.
Always install the noise filter on a grounded panel.
Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction.
Do not connect fuses or switches to the noise filter output
wiring as this will reduce the effectiveness of the noise filter.
Power supply wiring must be twisted and have a low voltage
drop.
For an instrument with 24 V power supply, supply power from
a SELV circuit.
6.2 Terminal Configuration
CT input Control output 1 Control output 2
CT1
Power supply
Ground
20
FG
Voltage pulse/
CT2
3
67
18
19
DC
+
24 V
For heat/cool PID control (V-TIO-Q), Input channel 2 becomes unused.
For heat/cool PID control (V-TIO-Q), Control output 1 corresponds to the heating output and Control output 2 corresponds to the cooling output.
WARNING
!
Current/
Relay contact
Voltage
OUT1
+
2
14 13
OUT1
NO
2
5
16 15 3 2 1
17 7 6 5 4
18 11 10 9 8
20 19 14 13 12
Input channel 1
10
10
B
B
RTD1
RTD
+
Therm ocoupl e
+
5
TC1
10
IN1
Voltage/
Voltage/
Current
Current
Voltage pulse/
Current/ Voltage
OUT2
+
1
4
Upper-side terminal
Lower-side terminal
9
13
+
Thermocouple
9
13
+
Voltage/
Current
Relay contact
OUT2
NO
1
4
Input channel 2
9
B
12
TC2
12
IN2
RTD
12
B
RTD2
8
6
IMS01P08-E3
Terminal No. 11, 15, 16 and 17 are not used.
r
t
8
3
Do not connect to these terminals.
Use the solderless terminal appropriate to the screw
size (M3)
5.9 mm or less
.
Recommended tightening torque: 0.4 Nm (4 kgfcm)
.2 mm or more
6.3 Pin Layout of Connector
Modular connector for Ethernet
Modular connecto
for Etherne
RJ-45
Pin layout
1
Event connector (optional)
This is a connector installed in the V-TIO-P/V-TIO-Q module only when provided with the event input (DI) or the event output (DO).
Event connector
(socket)
Pin No.
1
1
2
3
4
6
5
6
Description
Digital input (DI) (
Digital input (DI) (
−)
+)
Digital output (DO) 1 (Relay contact output)
Digital output (DO) 2 (Relay contact output)
Circuit configuration
1
DI
2
24 V DC
Pin No. Signal name Symbol
1
2
3
Send data + TX+
Send data TX
Receive data + RX+
4 Unused
5 Unused
6
Receive data RX
7 Unused
8 Unused
Customer must provide the Ethernet communication cable. In addition, use straight cables when connected to the network hub, and use a cross cable when directly connected to the computer. However, cables different from the above cables may be used depending on the connecting device used. Therefore follow the instructions for each connecting device.
Computer
TX
TX
RX
RX
+
+
Network Hab
TX+
TX−
RX+
RX−
Load
Load
Attention in Connector (plug) Wiring
Use the following connector (plug) as that connected to the event input/output connector.
3
DO1
4
5
DO2
6
Connector (plug) is sold separately. SRVP-01 (Front-screw type) SRVP-02 (Side-screw type)
The lead wires use the stranded wire.
2
Use the stranded wire from size 0.2 to 2.5 mm
(AWG 24-12).
Stripping length is as follows. SRVP-01: 10 mm SRVP-02: 7 mm
Recommended tightening torque of the lead wire in the
V-TIO-P/V-TIO-Q
module
TX
+
TX
RX
+
RX
TX+
TX−
RX+
RX−
connector (plug): 0.5 to 0.6 Nm (5 to 6 kgf⋅cm)
Screw size: SRVP-01: M2.5 SRVP-01: M3
[SRVP-01] Front-screw type [SRVP-02] Side-screw type
Straight cable Straight c able
Computer
TX
+
TX
RX
+
RX
Cross cable
Use the RJ-45 type of modular connector as the connector plugged into the V-TIO-P/V-TIO-Q module.
V-TIO-P/V-TIO-Q
module
TX+
TX−
RX+
RX−
IMS01P08-E3
Stripping length
10 mm
Stripping length
7 mm
Stranded wire size:
0.2 to 2.5 mm (AWG 24-12)
Recommended tightening torque: 0.5 to 0.6 N⋅m (5 to 6 kgf⋅cm)
2
Stranded wire size:
0.2 to 2.5 mm (AWG 24-12)
Recommended tightening torque: 0.5 to 0.6 N⋅m (5 to 6 kgf⋅cm)
2
7
[IMQ
]
7. SPECIFICATIONS
Inputs
Number of inputs: 2 points
Isolated between each channel:
Thermocouple input, Voltage (low) input
Not isolated between each channel:
RTD input, Voltage (high) input, Current input
Input type:
Thermocouple K, J, T, S, R, E, B, N (JIS-C1602-1995)
PLII (NBS) W5Re/W26Re (ASTM-E988-96)
RTD Pt100 (JIS-C1604-1997)
JPt100 (JIS-C1604-1989, Pt100 of JIS-C1604-1981)
Voltage (low) 0 to 100 mV
Voltage (high) 0 to 5 V, 0 to 10 V, 1 to 5 V
Current 0 to 20 mA, 4 to 20 mA
Sampling cycle: 500 ms PV bias: Input span to +Input span CT input: 2 points
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
Outputs
Number of outputs: 2 points
(Isolated between input and output, and between output and power supply)
Output type:
Relay contact: 250 V AC, 3 A (Resistive load) 1a contact Electrical life 300,000 times or more (Rated load)
Voltage pulse: 0/12 V DC (Load resistance 600 or more)
Current: 0 to 20 mA DC, 4 to 20 mA DC (Load resistance 600 or less)
Voltage: 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC (Load resistance 1 k or more)
Control action
Number of controls: 2 points Control method: Brilliant PID control
Reverse action or direct action is selectable (Specify when ordering) Heat/cool control is selectable (Specify when ordering)
Additional function: Autotuning function
Output details: Temperature event, Heater break alarm,
Ethernet communication
Physical layer: Ethernet
Application layer: Modbus/TCP Communication data: Based on Modbus message format Connector type: RJ-45 Maximum connections: Up to 30 temperature control modules
Others
Power supply voltage: 24 V DC Power supply voltage range:
Current consumption: With event input/output (option):
Rush current: 12 A/module max. Allowable ambient temperature:
Allowable ambient humidity:
Weight: With event input/output (option):
Standard
Safety standard: UL: UL61010A-1
CE marking: LVD: EN61010-1
C-Tick: AS/NZS CISPR 11
Control loop break alarm, Burnout, Temperature rise completion (Specify when ordering)
10BASE-T/100BASE-TX automatic recognition
can be connected to one V-TIO-P/V-TIO-Q module.
21.6 V DC to 26.4 V DC
220 mA max./module Without event input/output (option): 200 mA max./module
10 to +50 °C
5 to 95 %RH Absolute humidity: MAX.W.C 29 g/m
Approx. 270 g Without event input/output (option): Approx. 260 g
CSA: CAN/CSA-C22.2 No1010.1
EMC: EN55011, EN61326-1
(equivalent to EN55011)
3
dry air at 101.3 kPa
Events
Number of events: 2 points/channel Event type: Temperature event:
Deviation high, Deviation low, Deviation high/low, Band, Process high, Process low Heater break alarm, Control loop break alarm, Burnout, Temperature rise completion
Option
Event input (DI)
Number of inputs: 1 point Input type: Dry contact input Input voltage: 24 V DC (Rated) Input current: Approx. 6 mA Input details: Control RUN/STOP,
Event interlock release (Specify when ordering)
Ethernet is a registered trademark of Xerox Corp. Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the
trademarks or registered trademarks of the respective companies.
The first edition: JUN. 2004 [IMQ00] The third edition: JUN. 2005
00
Event output (DO)
Number of outputs: 2 points Output type: Relay contact output
JUN. 2005 IMS01P08-E3
250 V AC, 1 A (Resistive load) 1a contact Electrical life 300,000 times or more (Rated load)
HEADQUARTERS:16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585)
RKC INSTRUMENT INC.
®
Loading...