Thank you for purchasing this RKC product. In order to
achieve maximum performance and ensure proper operation
of your new instrument, carefully read all the instructions in
this manual. Please place this manual in a convenient
location for easy reference.
SYMBOLS
WARNING
CAUTION
An external protection device must be installed if
failure of this instrument could result in damage to
the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to
instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to
instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than
factory-approved personnel. Malfunction can occur
and warranty is void under these conditions.
This is a Class A instrument. In a domestic environment,
this instrument may cause radio interference, in which
case the user may be required to take adequate measures.
ll Rights Reserved, Copyright 2004, RKC INSTRUMENT INC
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire,
etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should
!
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating
procedures.
: This mark indicates supplemental information
on installation, handling and operating
procedures.
: This mark indicates where additional
information may be located.
WARNING
!
CAUTION
RKC INSTRUMENT INC.
®
This instrument is protected from electric shock by
reinforced insulation. Provide reinforced insulation between
the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit
respectively for the following:
− If input/output or signal lines within the building are
longer than 30 meters.
− If input/output or signal lines leave the building,
regardless the length.
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such
as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating
personnel.
All precautions described in this manual should be taken to
avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect
action.
The power must be turned off before repairing work for
input break and output failure including replacement of
sensor, contactor or SSR, and all wiring must be
completed before power is turned on again.
To prevent instrument damage or failure, protect the power
line and the input/output lines from high currents with a
protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling
inside instrument case to avoid electric shock, fire or
malfunction.
Tighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dispensation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean
the instrument. Deformation or discoloration will occur. Use
a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an
abrasive material or push front panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control,
computer technology and communications.
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument
failure or indirect damage.
RKC is not responsible for any damage and/or injury
resulting from the use of instruments made by imitating this
instrument.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a
limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty
expressed or implied, with respect to the accuracy of the
information. The information in this manual is subject to
change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or
retrieved through any mechanical, electronic, optical or
other means without prior written approval from RKC.
1. OUTLINE
The V-TIO-G/V-TIO-H (temperature control module for PROFIBUS)
can send/receive data to/from PROFIBUS compatible programmable
controllers (PLC) via PROFIBUS.
[The features of V-TIO-G/V-TIO-H module]
• One module (V-TIO-G or V-TIO-H) enables temperature control
corresponding to two channels.
• It has power supply and communication terminals in addition to
temperature control input and output terminals.
• One digital input (DI) point and two digital output (DO) points
can be optionally added.
• All data are set by communication.
For PROFIBUS, see the Module Type Controller SRV
PROFIBUS Communication Instruction Manual
(IMS01P07-E).
Temperature control
module for PROFIBUS
V-TIO-G/ V-TIO-H
For details when dividing two or more temperature
control modules into some groups and then installed,
Programmable
controller (PLC)
Modbus
Control
output
Measured
input
Power supply
(24 V DC)
PROFIBUS-DP
Host communication or
Division of modules terminals
Used when starting host communication
or two or more temperature control
modules are divided into some groups
and then installed.
Usable modules:
Temperature control (TIO) module
[Basic type]: V-TIO-A, C
Temperature control (TIO) module
[Extension type]: V-TIO-B, D
(Up to 30 modules)
Event input/output
connector (option)
Digital input: 1 point
Digital output: 2 points
see the Module Type Controller SRV PROFIBUS Communication Instruction Manual (IMS01P07-E).
For communication using host communication terminals,
see the Module Type Controller SRV Communication
Instruction Manual (IMS01P01-E).
2. PRODUCT CHECK
Before using this product, check each of the following:
• Model code
• Check that all of the accessories delivered are complete.
• Check that there are no scratch or breakage in external
appearance (case, front panel, terminal, etc).
V–TIO– – – –
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
(1) Type
G: Module for PROFIBUS, heat control
H: Module for PROFIBUS, heat/cool control
(2) Control action (Each channel common code)
[For heat control]
F: PID action with autotuning (AT) (reverse action)
D: PID action with autotuning (AT) (direct action)
K040 to 800 °C KB8 32 to 1472 °F
K16−200 to +1372 °C KB7 −328 to +2501 °FK090.0 to 400.0 °C KC2 32.0 to 752.0 °F
K35 −200.0 to +400.0 °C KC1 −328.0 to +752.0 °F
J J020 to 400 °C JC2 32 to 752 °F
J040 to 800 °C JC1 32 to 1472 °F
J15−200 to +1200 °C JB9 −328 to +2192 °FJ090.0 to 400.0 °C JC4 32.0 to 752.0 °F
J27 −200.0 to +400.0 °C JC3 −328.0 to +752.0 °F
T T080 to 400 °C TB9 32 to 752 °F
T090 to 200 °C TC1 32 to 392 °F
T16−200 to +400 °C TB8 −328 to +752 °F
T060.0 to 400.0 °C TC3 32.0 to 752.0 °F
T19 −200.0 to +400.0 °C TC2 −328.0 to +752.0 °F
E E010 to 800 °C EA8 32 to 1472 °F
E020 to 1000 °C EA7 32 to 1832 °F
S S050 to 1768 °C SA6 32 to 3214 °F
R R060 to 1768 °C RA6 32 to 3214 °F
N N020 to 1300 °C NA6 32 to 2372 °F
B B030 to 1800 °C BB1 32 to 3272 °F
PLⅡA020 to 1390 °C AA6 32 to 2534 °F
W5Re/
W26Re
W030 to 2300 °C WA9 32 to 4172 °F
[RTD input]
Type CodeRange Code Range
Pt100D170 to 400 °C DC5 32 to 752 °F D330 to 850 °C DC4 32 to 1562 °F D160.0 to 400.0 °C DC7 32.0 to 752.0 °F
D28 −200.0 to +400.0 °C DC6 −328.0 to +752.0 °F
JPt100P170 to 400 °C PC5 32 to 752 °F P230 to 600 °C PC4 32 to 1112 °F P160.0 to 400.0 °C PC7 32.0 to 752.0 °F
P28 −200.0 to +400.0 °C PC6 −328.0 to +752.0 °F
[Voltage/current input]
CodeType Code Type
Voltage2010 to 100 mV DC 401 0 to 5 V DC
5010 to 10 V DC 601 1 to 5 V DC
Current7010 to 20 mA DC 801 4 to 20 mA DC
(4) Control output (CH1), (5) Control output (CH2)
M: Relay contact output V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC 5: 0 to 10 V DC 6: 1 to 5 V DC
7: 0 to 20 mA DC 8: 4 to 20 mA DC
(6) Event input (DI) [Optional]
N: None
1: Control RUN/STOP
2: Event interlock release
N: None A: Deviation high B: Deviation low
C: Deviation high/low D: Band
E: Deviation high with hold action F: Deviation low with hold action
G: Deviation high/low with hold action H: Process high
J: Process low K: Process high with hold action
L: Process low with hold action
Q: Deviation high with re-hold action
R: Deviation low with re-hold action
T: Deviation high/low with re-hold action
P: Heater break alarm 1: Control loop break alarm
2: Burnout 3: Temperature rise completion
* When “N” is selected in (7) or (9), (8) or (10) becomes “N.”
(11) CT type (Each channel common code)
P: CTL-6-P-N S: CTL-12-S56-10L-N
IMS01P06-E2
A
r
L
X
X
X
A
A
For heat/cool PID control (V-TIO-H), Control output
(CH1) corresponds to the heating output and
4. COMMUNICATION SETTING
Control output (CH2) corresponds to the cooling
output.
Heater break alarm function can not be used when
control output is voltage/current output.
Accessories
Floppy disk (GSD file) ................................................1
End Plate ....................................................................2
If any of the products are missing, damaged, or if your
manual is incomplete, please contact RKC sales office
or the agent.
3. PARTS DESCRIPTION
Indication lamps 2
Address setting
switch 2
PROFIBUS
connecto
(COM.PORT)
Joint connector
(Left-side)
FAIL/RUN
RX/TX
EVENT1
ON
RUN
FAIL
EVENT2
TX/R
EVENT3
4
5
6
3
7
2
8
1
EVTNT4
9
0
A
F
B
E
D
C
3
2
4
1
5
5
4
5
6
3
0
6
7
2
9
8
1
7
8
9
0
A
F
B
E
D
C
3
2
4
1
5
5
0
6
9
7
8
Terminal cover
Indication lamps 1
ddress setting
switch 1
Event input/output
connector *
Joint connector
(Right-side)
Terminal cover
Set communication setting before mounting and wiring of SRV.
CAUTION
Do not separate the module mainframe from the terminal
base with the power turned on. If separated, adjusted data
may be destroyed; control be stopped, and no return can be
made.
4.1 Address Setting
PROFIBUS address setting
Set an address of PROFIBUS. For this setting, use a small blade
screwdriver.
Module address setting
ddress setting switch 2
High-order digit
setting
(Set value × 10h)
Low-order digit
setting
(Set value × 1h)
Setting range:
01h to 7Dh [hexadecimal]
Factory set value: 00h
4
5
6
3
7
2
8
1
9
0
A
F
B
E
D
C
4
5
6
3
7
2
8
1
9
0
A
F
B
E
D
C
No communication with PROFIBUS can be conducted
with each factory set value (00h) left as it is. Always
set the PROFIBUS address.
Set an address of module. For this setting, use a small blade
PROFIBUS side Temperature control side
* Installed when provided with the event input/output (optional).
Indication
lamps 2
FAIL
RUN
FAIL/RUN
RX/T
EVENT1
EVENT2
ONL
TX/R
EVENT3
EVENT4
Indication
lamps 1
Temperature control sidePROFIBUS side
[Indication lamps 1]
FAIL/RUN (for temperature control side)
When normally: A green lamp turns on (RUN)
When abnormally: A red lamp turns on (FAIL)
RX/TX (for Modbus)
During data send and receive: A green lamp turns on
EVENT 1 to 4
Display various states by setting.
During ON state: A green lamp turns on
screwdriver.
When setting module address, always set their
address from address number “0” in succession.
Otherwise, problems or malfunction may result.
For host communication (Modbus), the value obtained
by adding “1” to the set address corresponds to the
address used for the actual program.
Set the module address such that it is different to
the other addresses on the same line. Otherwise,
problems or malfunction may result.
ddress setting switch 1
3
High-order digit
2
4
1
5
55
setting
0
6
9
7
8
(Set value × 10)
3
2
4
1
Low-order digit
5
0
6
9
7
setting
8
(Set value × 1)
Setting range: 0 to 30
Factory set value: 0
Display contents
Event 1 state, Event 2 state, Comprehensive event state, Output state,
and Control state
[Indication lamps 2]
FAIL (for PROFIBUS side)
When hardware is normal: A red lamp turns off
When hardware is abnormal: A red lamp turns on
RUN (for internal communication)
When normally: A green lamp turns on
When abnormally: A green lamp is flashing
ONL
During PROFIBUS connection establishment:
A green lamp turns on
RX/TX (for PROFIBUS communication)
During data send and receive: A green lamp turns on
IMS01P06-E2
3
4.2 PROFIBUS/Host Communication
Transfer Setting
With the dip switch 1 which there is on the left side of module,
select PROFIBUS/Host communication transfer, communication
speed for internal communication in PROFIBUS.
Internal communication is communication that
V-TIO-G/V-TIO-H module conduct to other temperature
control modules in PROFIBUS.
Dip switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
4.3 Host Communication Setting
With the dip switch 2 which there is on the right side of module,
select communication speed for host communication.
When host communication is not used, dip switch 2
need not be set.
Dip switch 2
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
Left side (PROFIBUS side)
1 2 Internal communication speed
OFF OFF 38400 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 38400 bps (1: OFF, 2: OFF)
7
PROFIBUS/Host communication transfer
OFF PROFIBUS (Internal communication validity)
Host communication (Internal communication
ON
invalidity)
Factory set value:
Switch No. 3 to 6, 8: OFF fixed (Don’t change the
factory set values)
PROFIBUS (Internal communication validity)
[Factory set value]
• Internal communication speed: 38400 bps
• Internal communication protocol: Modbus
[Factory set value of the dip switch 1]
No. 1: OFF No. 5: OFF
No. 2: OFF No. 6: OFF
No. 3: OFF No. 7: OFF
No. 4: OFF No. 8: OFF
For host communication (Modbus), see the Module
Type Controller SRV Communication Instruction
Manual (IMS01P01-E).
Right side (
1 2 Host communication speed
temperature control side
)
OFFOFF 2400 bps
ONOFF 9600 bps
OFFON 19200 bps
ONON 38400 bps
Factory set value: 38400 bps
Switch No. 3 to 8: OFF fixed (Don’t change the
factory set values)
[Factory set value]
• Host communication speed: 38400 bps
• Host communication protocol: Modbus
[Factory set value of the dip switch 2]
No. 1: ON No. 5: OFF
No. 2: ON No. 6: ON
No. 3: ON No. 7: OFF
No. 4: OFF No. 8: OFF
When connecting two or more modules (V-TIO-A,
V-TIO-B, V-TIO-C or V-TIO-D) to the module (V-TIO-G
or V-TIO-H), match all of the switch No. 1, 2 settings
with the internal settings of the module (V-TIO-G or
V-TIO-H).
4
IMS01P06-E2
5. MOUNTING
5.3 DIN rail Mounting
Mounting procedures
To prevent electric shock or instrument failure,
always turn off the power before mounting or
removing the instrument.
WARNING
!
1. Pull down the mounting bracket at the bottom of the module
(A). Attach the hooks on the top of the module to the DIN rail
and push the lower section into place on the DIN rail (B).
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature
and ambient humidity.
• Allowable ambient temperature: −10 to +50 °C
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX. W. C 29 g/m
3
dry air at 101.3 kPa)
(3) Avoid the following when selecting the mounting location:
2. Slide the mounting bracket up to secure the module to the
DIN rail.
• Rapid changes in ambient temperature, which may cause
condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or
noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Mounting consideration
• Install the module 200 mm away from the main power line.
• Ensure at least 50 mm space on top and bottom of the
control unit for maintenance and environmental reasons.
5.2 Dimensions
End Plate mounting
Hold tight both ends of the modules jointed together with the end
plates and then fix the end plates with screws. Even if only one
(Unit: mm)
110
6
6.8
40.5
module (V-TIO-G or V-TIO-H)
the module with the end plates.
DIN rail
Mounting
bracket
(A) Pull down
Locked
is used, also hold tight both ends of
V-TIO-G/V-TIO-H module
(B) Push
125
5
78
The above figure shows when provided with the event
connector, but the same also when not provided with the
connector.
Depth in connector mounting
Conduct installation in consideration of the sizes of the
connector and cable when connector-connected.
110
*
(Unit: mm)
End Plate
For the conservation of the contact of connector, install a joint
*
connector cover in module of both ends.
Removing procedures
Joint connector cover *
End Plate
Pull down a mounting bracket with a blade screwdriver (A). Lift
the module from bottom, and take it off (B).
(B) Lift and take off
IMS01P06-E2
* Provide space in consideration of the sizes of using
the connector and cable when connector-connected.
(A) Pull down
5
±
r
−
A
−
−
−
A
5.4 Panel Mounting
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a
mounting hole appears.
2. Prepare one mounting bracket per module (B) sold
separately (KSRX-55) and then insert it in the rear of the
terminal board at top of the module until locked but a
mounting hole does not disappear.
3. Mount each module directly on the panel with screws which
are inserted in the mounting holes of the top and bottom
mounting brackets.
Recommended tightening torque: 0.3 N⋅m (3 kgf⋅cm)
The customer needs to provide the M3 size screws.
Select the screw length that matches the mounting
panel.
(B) Insert
Mounting
Mounting bracket
(Sold separately)
(A) Pull down
(KSRX-55)
30
0.2
Mounting
holes
dimensions
35.25 ± 0.2
130.5 ± 0.2
M3
Module of 40.5 mm wide Modul e of 30 mm wide
5.5 Jointing Each Module
Up to 30 modules (V-TIO-A, V-TIO-B, V-TIO-C or V-TIO-D) can
be connected to one module (V-TIO-G or V-TIO-H).
modules according to the following procedure.
Jointing procedure
1. Mount the modules on the DIN rail and then joint these
modules together with the joint connector while sliding the
relevant module.
2. Lift each of the joint tabs located at the top and bottom of the
module and then insert it in the slot of the adjacent module to
fix these two modules.
For panel mounting, first joint each module and then
mount it on the panel.
Joint connecto
Joint tab
There is one joint tab at each
of the top and bottom of on
module. Therefore, fix two
adjacent modules with these
two joint tabs.
6
Joint these
When viewed
from top
Joint tab
insertion slot
6. WIRING
To prevent electric shock or instrument failure, do not
turn on the power until all the wiring is completed.
6.1 Wiring Cautions
For thermocouple input, use the appropriate compensation
wire.
For RTD input, use low resistance lead wire with no
difference in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from
instrument power line, load lines and power lines of other
electric equipment.
If there is electrical noise in the vicinity of the instrument that
could affect operation, use a noise filter.
- Shorten the distance between the twisted power supply wire
pitches to achieve the most effective noise reduction.
- Always install the noise filter on a grounded panel.
Minimize the wiring distance between the noise filter output
and the instrument power supply terminals to achieve the
most effective noise reduction.
- Do not connect fuses or switches to the noise filter output
wiring as this will reduce the effectiveness of the noise filter.
Power supply wiring must be twisted and have a low voltage
drop.
For an instrument with 24 V power supply, supply power from
a SELV circuit.
6.2 Terminal Configuration
Internal communication
or
Host communication
RS-485
T/R(A)
T/R(B)
16
SG
17
Ground
20
FG
5.9 mm or less
Recommended tightening torque:
0.4 N
CT input
CT1
15
Power supply
18
19
DC
+
24 V
⋅m (4 kgf⋅cm)
For heat/cool PID control (V-TIO-H), Input channel 2
becomes unused.
For heat/cool PID control (V-TIO-H), Control output 1
corresponds to the heating output and Control
output 2 corresponds to the cooling output.
WARNING
!
Control output 1
Voltage pulse/
Current/
Voltage
CT2
3
OUT1
+
2
67
16 15 3 2 1
17 7 6 5 4
18 11 10 9 8
20 19 14 13 12
Input channel 1
10
B
1413
RTD1
B
RTD
Relay contact
OUT1
−
2
5
10
13
+
TC1
Thermocou ple
10
13
+
IN1
Voltage/
Voltage/
Current
Current
Voltage pulse/
Current/
Voltage
+
NO
1
5
Upper-side terminal
Lower-side terminal
Input channel 2
9
12
TC2
−
+
Thermocouple
9
12
+
−
IN2
Voltage/
Current
Control output 2
Relay contact
OUT2
OUT2
NO
1
4
9
B
12
B
RTD2
RTD
IMS01P06-E2
4
8
Terminal No. 11 is not used.
Use the solderless terminal appropriate to the screw
size (M3).
6.3 Pin Layout of Connector
PROFIBUS connector
PROFIBUS connector
(COM. PORT)
Circuit configuration
1
DI
2
Load
3
DO1
4
24 V DC
9
6
5
1
Pin No. Signal name Symbol
1
2
3
Receive data/transmission data (plus)
4
5
6
Termination resistor supply voltage (5 V)
7
8
Receive data/transmission data (negative)
9
Signal ground
Unused
Unused
RxD/TxD-P
Unused
DGND
VP
Unused
RxD/TxD-N
Unused
The PROFIBUS cable (a connection cable of PLC and
SRV) is provided by customer. As for the PROFIBUS
cable, there is a case prepared by a PLC manufacturer.
The details except the above are connected to a home
page of PROFIBUS International, and obtain necessary
information.
URL: http://www.profibus.com/
Event connector
This is a connector installed in the V-TIO-G/V-TIO-H module
only when provided with the event input (option) or the event
output (option).
Event connector
(socket)
Pin
No.
1
1
2
3
6
4
5
6
Description
Digital input (DI) (
Digital input (DI) (
−)
+)
Digital output (DO) 1
(Relay contact output)
Digital output (DO) 2
(Relay contact output)
Load
5
DO2
6
Attention in connector (plug) wiring
• Use the following connector (plug) as that connected to the
event connector.
Connector (plug) is sold separately.
• Recommended tightening torque of the lead wire in the
connector (plug): 0.5 to 0.6 N⋅m (5 to 6 kgf⋅cm)
Screw size: SRVP-01: M2.5
SRVP-01: M3
[SRVP-01] Front-screw type [SRVP-02] Side-screw type
Stripping length
10 mm
Stranded wire size:
0.2 to 2.5 mm
(AWG 24-12)
Recommended tightening
torque: 0.5 to 0.6 N⋅m
(5 to 6 kgf⋅cm)
2
2
(AWG 24-12).
Stripping length
7 mm
Stranded wire size:
0.2 to 2.5 mm
(AWG 24-12)
Recommended tightening
torque: 0.5 to 0.6 N⋅m
(5 to 6 kgf⋅cm)
2
IMS01P06-E2
7
Option
7. SPECIFICATIONS
Inputs
Number of inputs: 2 points
Input type:
• Thermocouple K, J, T, S, R, E, B, N (JIS-C1602-1995) PLII (NBS)
W5Re/W26Re (ASTM-E988-96)
• RTD: Pt100 (JIS-C1604-1997) JPt100 (JIS-C1604-1989, Pt100 of
JIS-C1604-1981)
• Voltage (low): 0 to 100 mV
• Voltage (high): 0 to 5 V, 0 to 10 V, 1 to 5 V
• Current: 0 to 20 mA, 4 to 20 mA
Sampling cycle: 500 ms
PV bias: −Input span to +Input span
CT input: 2 points
Outputs
Number of outputs: 2 points
Output type:
•Relay contact: 250 V AC, 3 A (Resistive load)
1a contact
Electrical life 300,000 times or more
(Rated load)
•Voltage pulse: 0/12 V DC (Load resistance 600 Ω or more)
•Current: 0 to 20 mA DC, 4 to 20 mA DC (Load resistance 600 Ω or less)
•Voltage: 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC (Load resistance 1 kΩ or more)
Control action
Number of controls: 2 points
Control method: Brilliant PID control
Additional function: Autotuning function
Events
Number of events: 2 points/channel
Event type: Temperature event:
Heater break alarm (HBA) function
Number of HBA: 2 points
Setting range: 0.0 to 100.0 A (0.0 A: OFF)
Additional function: Number of event delay times:
Control loop break alarm (LBA) function
Number of LBA: 2 points
LBA time: 1 to 7200 seconds
LBA deadband (LBD) setting:
IMS01P06-E2
NOV. 2005
Isolated between each channel:
Thermocouple input, Voltage (low) input
Not isolated between each channel:
RTD input, Voltage (high) input,
Current input
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
(Isolated between input and output, and
between output and power supply)
Reverse action or direct action is
selectable (Specify when ordering)
Heat/cool control is selectable
(Specify when ordering)
Deviation high, Deviation low,
Deviation high/low, Band,
Process high, Process low
Heater break alarm,
Control loop break alarm,
Burnout, Temperature rise completion
1 to 255 times
0 to Input span
Event input
Number of inputs: 1 point
Input type: Dry contact input
Input voltage: 24 V DC (Rated)
Input current: Approx. 6 mA
Input details: Control RUN/STOP,
Event interlock release
(Specify when ordering)
Event output
Number of outputs: 2 points
Output type: Relay contact output
Output details: Temperature event, Heater break alarm,
Communications
Communication interface:
Based on RS-485, EIA standard
Communication protocol:
PROFIBUS: PROFIBUS-DP
Internal communication: Modbus RTU
Host communication: Modbus RTU
Others
Power supply voltage: 24 V DC
Power supply voltage range:
Current consumption: With event input/output (option):
Allowable ambient temperature range:
Allowable ambient humidity range:
Weight: With event input/output (option):
Standard
Safety standard: UL: UL61010A-1
CE marking: Low voltage directive: EN61010-1
C-Tick: AS/NZS 2064 (equivalent to EN55011)
Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the
trademarks or registered trademarks of the respective companies.