Rittal SK 3269.100, SK 3269.140, SK 3265.100, SK 3262.100, SK 3266.100 Assembly Instructions Manual

Umschalten auf PerfektionUmschalten auf Perfektion
Umweltorientierte Kühltechnik
SK 3269.100 SK 3269.140 SK 3265.100 SK 3262.100 SK 3266.100
Montageanleitung Assembly instructions Notice de montage Montage-instructie Montageanvisning Istruzioni di montaggio Instrucciones de montaje
348
340
600
525
305
Ø 8
145
26
160
77
208
540
340
120
600
400
M6 SW 10
A 6.4
M6 x 40
10 x 4
M6 SW 10
A 6.4
Cover
Housing
Sealing gasket 15 x 5*
210
605 ± 1
74
400
32
635
Ø 8
64
34
Ø 8
635
400
378
360 ± 1
605 ± 1
577
16
44
194
52
15
50
23
124
635
400
248
205
45
4
Contents
1. Application
2. Technical data
3. Assembly
4. Electrical connection
5. Commencing operation and control behaviour
6. Technical information
7. Maintenance
8. Scope of supply and guarantee
9. Spares list
1. Application
Enclosure cooling units are designed and built to dissipate heat from enclosures by cooling the air inside the enclosure and protecting temperature sensitive components. Enclosure cooling units are particularly suitable for the temperature range of + 20 ° C to + 55 ° C.
2.Technical data
(see table 2.1).
3. Assembly
Prior to mounting, ensure that:
v
the site for the enclosure, and hence the arrangement of the cooling unit, is selected so as to ensure good ventilation;
v
the location is free from excessive dirt and moisture;
v
the mains connection ratings, as stated on the data plate, are available;
v
the ambient temperature is no higher than
+55 ° C (50 ° C SK 3269.... / SK 3262.100);
v
the packaging shows no signs of damage. Traces of oil are an indication of coolant loss and of leakage in the unit system. Any damage to the packaging can become the cause of a subsequent function failure;
v
the enclosure is sealed on all sides. Condensation will occur if the enclosure is leaky;
v
the separation of the units from one another and from the wall should not be less than 200 mm;
v
air inlet and outlet are not obstructed on the inside;
v
units should only be fitted vertically in the specified position. Max. deviation from true vertical: 2
o
(see 6.3);
v
condensate discharge hose has to be fitted;
v
electrical connection and repair must be carried out only by authorized specialist personnel. Use only original replacement parts!
v
to avoid an increase in condensation, a door operated switch (e.g. PS 4127.000) should be used which will switch the cooling unit off when the enclosure door is opened.
4.Electrical connection
The connected voltage and frequency must correspond to the values stated on the data plate. The cooling unit must be connected to the mains via an isolating device, which ensures at least 3 mm contact opening when switched off, The unit must not have any additional temperature control connected before it. Line protection should be provided by means of the pre-fuse specified on the data plate. Observe the relevant regulations during installation! Connection should be made to the cable attached to the unit. (See detailed wiring diagram page 18).
5. Commencing operation and control behaviour
Following the completion of mounting and a waiting period of approximately 30 minutes (to allow oil to collect in the compressor), electrical connection can be made in order to ensure lubrication and cooling.
English
Fig. 3.2 Mounting cutout SK 3269.... / SK 3262.100
Make cutouts and drill holes at the mounting position (see fig. 3.2).
Fig. 3.4 Mounting cutout SK 3265.100 / SK 3266.100
Fig. 3.1 Assembly SK 3269.... / SK 3262.100
Internal installation
External installation
Internal installation External installation
Fig. 3.3 Assembly SK 3269.... / SK 3262.100
Internal installation External installationInternal installation
* Attach the sealing gasket 15 x 5 mm, ident. no. 209631, neatly to the edges as shown in the drawing
and make a straight, right-angled cut to length! Horizontal and vertical sides must be cut to length from two pieces and not formed from just one!
Make 2 cutouts and 4 screw holes in the top of the enclosure in accordance with fig. 3.4. Stick the enclosed sealing gasket onto the enclosure roof.
5.1 Control behaviour
The cooling unit operates automatically, i.e. following the electrical connection, the evapo­rator fan will run continuously to circulate the air inside the enclosure. This provides a uniform temperature distribution in the enclosure. The
built-in temperature controller (setting the desired internal temperature) effects automatically controlled switch-off of the cooling unit by the value of the fixed switching difference setting of 5 K. This is set at the factory to + 35 ° C.
5
Tab. 2.1 Technical data
Model No. SK 3269.100 3269.140 3265.100 3262.100 3266.100
Operating voltage V/Hz 230/50/60 400/50/60 230/50/60 115/50/60 115/50/60 Dimensions mm W
(W x H x D) H
D
400 635 248
400 635 248
600 340 348
400 635 248
600 340 348
Useful cooling L35 L35 output DIN 3168 L35 L50
680 W/700 W 500 W/520 W
680 W/700 W 500 W/520 W
410 W/380 W 230 W/240 W
680 W/700 W 500 W/520 W
410 W/380 W 230 W/220 W
Rated current max. 3.1 A/ 4.0 A 1.8 A/2.3 A 2.2 A/2.5 A 5.1 A/ 6.0 A 4.5 A/ 5.2 A Starting current 12.6 A/14.4 A 7.2 A/8.3 A 6.6 A/7.2 A 25.2 A/34.3 A 13.5 A/13.5 A Pre-fuse T 6.0 A/ 6.0 A 4.0 A/4.0 A 6.0 A/6.0 A 6.0 A/10.0 A 6.0 A/ 6.0 A Nominal power L35 L35
consumption L35 L50
460 W/580 W 520 W/660 W
480 W/600 W 540 W/675 W
310 W/440 W 350 W/450 W
480 W/600 W 540 W/675 W
325 W/450 W
365 W/490 W Refrigerant R134a, 300 g R134 a, 300 g R134 a, 325 g R134a, 300 g R134 a, 325 g p. max. 24 bar Temperature range + 20 ° C
to + 50 ° C
+ 20 ° C to + 50 ° C
+ 20 ° C to + 55 ° C
+ 20 ° C to + 50 ° C
+ 20 ° C
to + 55 ° C Noise level 65 dB (A) Protective category
EN 60 529/10.91
External circuit IP 34
Internal circuit IP 54 Duty cycle 100 % Weight 32.5 kg 35 kg 26 kg 35 kg 29 kg Colour RAL 7032
5.2 Temperature setting at the controller
Fig.4.1 Thermostat
Set the desired temperature. Setting range + 20 ° C to + 55 ° C.
6.Technical information
The cooling unit (compression refrigeration unit) consists of four main components: the coolant compressor , evaporator, liquefier (condenser), and the control or expansion valve, which are connected by suitable pipework. This circuit is filled with a readily boiling substance, the coolant. The R134a (CH
2
FCF
3
) coolant is free
from chlorine. It has an ozone destroying potential (ODP) of 0 and is therefore environmentally friendly. A filter dryer which is integrated in the hermetically sealed cooling circuit, provides effective protection against moisture, acid, dirt particles, and foreign bodies within the cooling circuit.
6.1 Operation of the cooling unit
Fig. 6.1 Cooling circuit
When the coolant compressor is put into operation, the coolant vapour evaporates from the evaporator. The heat required for the evaporation of the coolant is drawn from the evaporator environment (internal circuit of the enclosure), causing it to cool down. The heat fed to the coolant in the evaporator is dissipated by the liquefier to its environment (assisted by fans), making the coolant once more liquid due to the condensation which takes place. In the thermostatically controlled expansion valve, the liquid coolant is reduced to the particular evaporator pressure required. The cooling which occurs due to the reduction of pressure, releases the heat from the liquid, which evaporates part of the coolant flow. The mixture of cold liquid and throttle vapour is returned to the evaporator.
20 30
°C °C
55
60
50
45
40
35
25
Fan 2
Fan 1
Pressostat
Compressor
Evaporator
External circuit Internal circuit
Expansion valve
Thermostat
Filter­dryer
Liquefier
The cooling cycle is thus completed, the aforementioned process of the heat transfer starts afresh.
6.2 Safety equipment
The cooling circuit of the cooling unit embodies a component tested high/low pressure monitor to VBG 20 § 7.1 which is set to maximum operating pressure and operates via an automatic reset device at recurring pressure drop. The coolant compressor and the fans are equipped with thermal winding protection against excess current and excess temperature.
6.3 Condensate discharge
SK 3269.... / SK 3262.100:
Automatic condensate evaporation. Condensate is discharged downwards. Insert the discharge socket Ø 12 mm piece into the unit aperture.
SK 3265.100 / SK 3266.100:
1. To drain away any incidental condensate, attach a discharge hose to the 12 mm dia. pipe connection piece, which protrudes from the unit. Connect the drain hose to the angled con­nection piece (1) (avoiding any kinks) and route the hose directly downwards in order to prevent any backflow and overflow of the condensate inside the unit.
2. To prevent external air flowing through the condensate discharge connection piece into the interior of the enclosure, fit the enclosed backflow preventer (2) in the drain hose. The nonwoven fabric inserted in the backflow preventer ensures safe drainage of the condensate. The backflow preventer may become contam­inated over a period of time and should be examined at least once per annum and replaced as necessary.
6.4 General
Storage temperature: The cooling units must not be subjected to temperatures above + 70 ° C during storage. Transport attitude: The cooling units must always be transported upright. Waste disposal: The closed cooling circuit contains coolant and oil which must be correctly disposed of for the protection of the environment. The disposal can be carried out at Rittal-Werk.
Fig. 6.2 Condensate discharge
2
1
min.
500 mm
7.Maintenance
As a maintenance-free, hermetically sealed system, the cooling circuit has been filled in the factory with the required amount of coolant, and tested for leaks and subjected to a function trial run. The installed maintenance­free fans use bull bearings, they are protected against moisture and dust, and are fitted with a temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling unit is thus largely maintenance-free. All that may be required from time to time is that the components of the external air circuit are cleaned by compressed air. The use of a filter mat is recommended only if large particles of lint are present in the air, so that blockage of the condenser is prevented. (Filter mat replacement, fig. 7.1). Caution: Prior to any maintenance work, the cooling unit must be switched free from potential on the supply side.
Fig. 7.1 Filter mat replacement
SK 3269.... / SK 3262.100
x = removable inlet grille
8.Scope of supply and guarantee
1 cooling unit, ready for connection 4 setscrews M6 x 30 4 nuts M6 4 serrated washers A 6,4 1 sealing cover 1 sealing tape 1 angle (SK 3265.100 / SK 3266.100) 1 backflow preventer
(SK 3265.100 / SK 3266.100) 1 drilling template 1 set of mounting and operating instructions
Guarantee:
This unit is covered by a 1-year guarantee from the date of supply, subject to correct usage. Within this period, the returned unit will be repaired in the factory or replaced free of charge. The cooling unit is to be used for the cooling of enclosures only. If it is connected or handled improperly the manufacturer’s guarantee does not apply and in this case we are not liable for any damage caused.
9.Spares list
(see page 19).
SK 3265.100 / SK 3266.100
Loading...
+ 4 hidden pages