Rittal SK 3209.100, SK 3209.110, SK 3209.140, SK 3210.100, SK 3210.140 Assembly And Operating Instructions Manual

...
Air/water heat exchangers
SK 3209.XXX
SK 3210.XXX
Assembly and operating instructions
Contents
EN
Contents
1 Notes on documentation .................. 3
1.2 Storing the documents................................. 3
1.3 Symbols used in these operating instructions 3
1.4 Other applicable documents ........................ 3
2 Safety instructions ............................ 3
3 Device description ............................ 4
3.1 Functional description .................................. 4
3.1.1 How it works ......................................................... 4
3.1.2 Control .................................................................. 4
3.1.3 Bus mode (e-Comfort controller only) .................... 5
3.1.4 Safety equipment .................................................. 5
3.1.5 Condensation ....................................................... 5
3.1.6 Leak detection ...................................................... 5
3.1.7 Door limit switch (e-Comfort controller only) .......... 5
3.1.8 Additional interface X3 (e-Comfort controller only) . 5
3.2 Proper use, foreseeable misuse ................... 5
3.3 Scope of supply........................................... 5
4 Installation ........................................ 6
4.1 Safety instructions........................................ 6
4.2 Choosing the installation site ........................ 6
4.3 Assembly procedure .................................... 6
4.3.1 Assembly instructions ........................................... 6
4.3.2 Make a mounting cut-out ...................................... 7
4.3.3 Assembling the air/water heat exchanger .............. 7
4.3.4 Connecting the condensate discharge .................. 8
4.4 Connecting the water connection................. 9
4.4.1 Connection on the side of the unit ......................... 9
4.4.2 Connection on the rear of the unit ......................... 9
4.4.3 Notes on water quality ........................................ 10
4.4.4 Preparation and maintenance of the water in
recooling systems ............................................... 10
4.5 Electrical connection .................................. 10
4.5.1 Notes on electrical installation ............................. 10
4.5.2 Door limit switch (e-Comfort controller only) ........ 11
4.5.3 Potential equalisation .......................................... 11
4.5.4 Install the power supply ....................................... 11
6.2.2 Launching test mode .......................................... 17
6.2.3 General programming information ....................... 17
6.2.4 Eco-mode ........................................................... 18
6.2.5 Editable parameters ............................................ 19
6.2.6 Bus connection (only when interconnecting several
units with an e-Comfort controller) ...................... 19
6.2.7 Programming overview of e-Comfort controller ... 21
6.2.8 Defining system messages for evaluation ............ 22
6.2.9 Setting the Master-slave identifier ........................ 22
6.2.10 Evaluating system messages .............................. 23
7 Inspection and maintenance .......... 24
8 Emptying, storage and disposal ..... 26
9 Technical specifications ................. 27
10 List of spare parts .......................... 29
11 Hydrological data ........................... 30
12 Appendix ....................................... 31
12.1 Characteristic curves.................................. 31
12.2 Dimensions ................................................ 33
13 Declaration of conformity ............... 34
5 Commissioning ............................... 14
6 Operation ....................................... 14
6.1 Control using the Basic controller............... 14
6.1.1 Display and system analysis ................................ 14
6.1.2 Properties ........................................................... 14
6.1.3 General programming information ....................... 14
6.1.4 Operation of the basic controller ......................... 14
6.1.5 Setting the temperature ...................................... 14
6.1.6 Setting of system messages ............................... 14
6.1.7 Programming and control of the Basic controller . 15
6.1.8 Reset of r6 and r7 (min./max. internal
temperature) ....................................................... 15
6.1.9 System message contact (K1; floating) ................ 15
6.1.10 Programming overview of Basic controller ........... 16
6.2 Control using the e-Comfort controller ....... 17
6.2.1 Properties ........................................................... 17
2 Rittal air/water heat exchangers

1 Notes on documentation

1 Notes on documentation

1.1 CE label

Rittal GmbH & Co. KG confirms the conformity of the air/ water heat exchanger with the European Union's Ma­chinery Directive 2006/42/EC and EMC Directive 2014/ 30/EU. A corresponding declaration of conformity has been issued and enclosed with the unit.

1.2 Storing the documents

The assembly and operating instructions as well as all other applicable documents are an integral part of the product. They must be issued to everyone who works with the air/water heat exchanger and must always be available and on hand for operating and maintenance personnel.
1.3 Symbols used in these operating in­structions
The following symbols are used in this documentation:
Warning! Hazardous situation which may lead to
death or serious injury if the instructions are not followed.
Caution! Hazardous situation which may lead to (minor) injuries if the instructions are not followed.

2 Safety instructions

Please observe the following general safety notes when assembling and operating the unit: – Assembly, installation and servicing may only be per-
formed by properly trained specialists.
– The minimum water inlet temperature of +1°C must
not be reduced at any point in the water cycle. Other­wise there is danger of frost damage!
– Use antifreeze agents only with the manufacturer's
consent.
– Do not obstruct the air inlet and air outlet of the air/wa-
ter heat exchanger inside the enclosure (see sec­tion4.3.1 "Assembly instructions").
– The heat loss of the components installed in the enclo-
sure must not exceed the specific useful cooling out­put of the air/water heat exchanger.
– The air/water heat exchanger must always be trans-
ported in a vertical position. – Use only original spare parts and accessories. – Do not make any changes to the air/water heat ex-
changer other than those described in these instruc-
tions or associated instructions. – The mains connector of the air/water heat exchanger
must only be connected and disconnected with the
system de-energised. Connect the pre-fuse specified
on the rating plate.
Other than these safety instructions, ensure you also
observe the specific safety instructions when perform-
ing the tasks described in the following chapters.
EN
Attention! Potential threat to the product and the
environment.
Note: Important notices and indication of situations
which may result in material damage.
This symbol indicates an "Action Point" and shows that you should perform an operation/procedure.

1.4 Other applicable documents

Assembly and operating instructions exist as paper doc­uments for the air/water heat exchanger described here and are enclosed with the equipment.
We cannot accept any liability for damage associated with failure to observe these instructions. Where applica­ble, the instructions for any accessories used also apply.
Rittal air/water heat exchangers 3

3 Device description

12
13
14
15
17 16
11
EN
3 Device description
Depending on the model chosen, your air/water heat ex­changer may vary in appearance from the illustrations contained in these instructions. However, the functions are identical in principle.
1
2
3
4, 5, 6
7

3.1.1 How it works

The air/water heat exchanger comprises three main components (see fig.2):
– Heat exchanger package (item 2), – fan (item 3) and – magnetic valve (item 5), connected with each other using pipes.
Fig. 2: Air/water heat exchanger
8 9 10
Fig. 1: Device description
Key
1Cover 2Rating plate 3Display 4 X2 master/slave connection (e-Comfort controller) 5 X1 terminal strip (underside of the unit) 6 X3 optional serial interface (underside of the unit) 7 Dispatch bag 8 Cooling water inlet 9 Cooling water return 10 Condensate discharge
Key
1Non-return valve 2 Heat exchanger 3Fan 4 Temperature control 5Magnetic valve 6 Cooling water inlet 7 Cooling water return
The heat loss of the enclosure is dissipated in a mem­brane heat exchanger to the water coolant. A fan (item 3) blows the internal enclosure air over the heat ex­changer (item 2); except for the inlet and outlet water and the condensed water discharge, the unit is closed to the environment. The magnetic valve (item 5) controls the cooling output by changing the water flow volume depending on the re­quired target temperature and the water inlet tempera-

3.1 Functional description

ture. Air/water heat exchangers are designed and built to dis­sipate heat from enclosures by cooling the air inside the enclosure and so protect the temperature sensitive components. Air/water heat exchangers are particularly appropriate for the temperature range of up to +70°C where compa­rable units, such as air/air heat exchangers, enclosure

3.1.2 Control

Rittal air/water heat exchangers are fitted with a control-
ler for setting the functions of the heat exchanger. De-
pending on the design, this is either a Basic controller or
an e-Comfort controller (display plus extended func-
tions, see section 6 "Operation"). cooling units or fan-and-filter units, cannot be used for
system reasons to effectively and economically dissipate heat loss. It is mounted on the roof of an enclosure.
4 Rittal air/water heat exchangers
3 Device description

3.1.3 Bus mode (e-Comfort controller only)

The serial interface X2 allows you to create a bus con­nection with up to ten air/water heat exchangers using the master-slave cable (shielded, four-wire cable, Model No. 3124.100).
This allows you to implement the following functions: – Parallel unit control (the air/water heat exchangers in
the network can be switched on and off simultaneous-
ly) – Parallel door status message ("door open") – Parallel collective fault message Data is exchanged via the master-slave connection. During commissioning, assign an address to each unit that also includes the identifier "master” or "slave” (see section6.2.9 "Setting the Master-slave identifier").

3.1.4 Safety equipment

– To protect against overcurrent and overtemperature,
the fan is equipped with a thermal winding protection. – The device has floating contacts on the connection
pins (terminals 1 – 3), via which system messages
from the device may be polled, e.g. using a PLC (1 x
change-over contact Basic controller, 2 x normally
open contacts e-Comfort controller). – The air/water heat exchanger has a leak and conden-
sate warning.

3.1.5 Condensation

At high levels of humidity and low cooling water temper­atures inside the enclosure, condensation may form on the heat exchanger.
Any condensation that forms on the heat exchanger (with high humidity and low water temperatures) is rout­ed to the right and/or rear out of the unit via a drain opening in the plastic tray. For this purpose, a hose must be connected to one of the two condensate nozzles (see section 4.3.4 "Connecting the condensate discharge"). The drain which is not required should be tightly sealed. The condensate must be able to run off freely. The hose used for draining off condensate must be laid free from kinks and checked for correct drainage.
Condensate hoses are available as accessories (refer also to the accessories section in the Rittal Catalogue).

3.1.6 Leak detection

If a leakage or pipe breakage occurs in the water circuit of the air/water heat exchanger, a magnetic valve stops the cooling water supply and the fault signal contact is activated. For units with e-Comfort controller, the fans are switched off additionally. Basic controller: The warning "IA" appears on the dis­play. e-Comfort controller: The warning "A08" appears on the display.

3.1.7 Door limit switch (e-Comfort controller only)

The air/water heat exchanger may be operated with a door limit switch connected.The door limit switch is not included with the supply (available as an accessory, Model No. 4127.010).
The door limit switch function causes the fan and the magnetic valve in the air/water heat exchanger to be switched off after approximately 15 seconds when the enclosure door is opened (contacts 1 and 2 closed). This prevents the formation of condensation inside the enclo­sure while the enclosure door is open.
The fan will start up after about 15 seconds on closure of the door.
Note: The door limit switches must only be con­nected free from potential. No external volt­ages!
3.1.8 Additional interface X3 (e-Comfort control­ler only)
Note: The electrical signals at the interface are of an
extra-low voltage (not extra-low safety volt­ages to EN 60 335).
An additional interface card may be connected to the 9­pole SUB-D connector X3 in order to incorporate the air/ water heat exchanger into higher-level monitoring sys­tems (available as an accessory, interface card Model No. 3124.200).

3.2 Proper use, foreseeable misuse

The air/water heat exchanger is designed for cooling closed enclosures. Under no circumstances should the limit values specified in the technical specifications (see section9) be exceeded. Assembly, installation and ser­vicing may only be performed by properly trained spe­cialists.
Improper use may cause hazards. Improper use may be for example:
– Use of the cooling unit for a long period with an open
enclosure
– Use of accessories not approved by Rittal GmbH &
Co. KG
– Use of an incorrect cooling medium

3.3 Scope of supply

The unit is supplied in a packaging unit in a fully assem­bled state.
Please check the scope of supply for completeness.
Qty. Description
EN
1 Air/water heat exchanger
Tab. 1: Scope of supply
Rittal air/water heat exchangers 5

4 Installation

EN
Qty. Description
1 Dispatch bag:
1 – Plug-in terminal strip
1 – Sealing frame
1 – Sealing plate
1 – Assembly and installation instructions
2 – Hose sleeves (1/2")
2 – Sealing ring (R 3/8")
11 – Twin-threaded bolt including assembly
parts
5–Screw-in elbow
1 – Angle screw socket
1 – Right-angle connector
1 Drilling template
Tab. 1: Scope of supply
4 Installation

4.1 Safety instructions

Warning! Please observe the maximum permissi-
ble weight to be lifted by one person. Use suitable lifting devices, if needed.
Warning! Work on electrical systems or equip-
ment may only be carried out by an elec­trician or by trained personnel under the guidance and supervision of an electri­cian. All work must be carried out in ac­cordance with electrical engineering regulations.
The air/water heat exchanger may only be connected after the aforementioned personnel have read this information!
Warning! The air/water heat exchanger must be connected to the mains via an all-pole disconnecting device to overvoltage categoryIII (IEC 61 058-1).
The air/water heat exchanger is not de­energised until all of the voltage sources have been disconnected!

4.2 Choosing the installation site

When choosing the installation site for the enclosure, please observe the following: – The air/water heat exchanger must be installed and
operated in a vertical position. – The ambient temperature must not exceed +70°C. – It must be possible to fit a condensate discharge (see
section4.3.4 "Connecting the condensate dis-
charge"). – It must be possible to fit a cooling water supply and re-
turn (see section 4.4 "Connecting the water connec-
tion"). – The mains connection data as stated on the rating
plate of the unit must be guaranteed.

4.3 Assembly procedure

4.3.1 Assembly instructions

Check the packaging carefully for signs of damage.
Packaging damage may be the cause of a subsequent
functional failure. – The enclosure must be sealed on all sides (IP 54). In-
creased condensation will occur if the enclosure is not
airtight. – The air inlet and outlet must not be obstructed on the
inside of the enclosure. – In order to avoid excessive condensation inside the
enclosure, we recommend installing a door limit
switch (e.g. 4127.010) which deactivates the air/water
heat exchanger when the enclosure door is opened
(see section 3.1.7 "Door limit switch (e-Comfort con-
troller only)").
Use only insulated tools.
The connection regulations of the ap­propriate power supply company are to be followed.
Fig. 3: Never direct the cold airflow at active components
6 Rittal air/water heat exchangers
When arranging the components inside the enclosure, please ensure that the cold airflow from the air/water heat exchanger is not directed at active components.
Please also ensure that the cold airflow is not directed at the warm exhaust airflow from active components such as converters.
This may lead to an air short-circuit and therefore pre­vent adequate climate control, or may even cause the air/water heat exchanger's internal safety devices to cease cooling operation.
Exercise particular caution with the airflow from the blowers of built-in electronic components (fig. 3). Components for targeted air routing are available as accessories – please refer to the Rittal Catalogue.
When using an air duct system, care must be taken to ensure that it is laid straight and without kinks wherev­er possible.
This minimises the resistance to the cold airflow.
It is important to ensure even air circulation inside the enclosure.
Under no circumstances should air inlet and outlet openings be obstructed, otherwise the cooling perfor­mance of the unit will be reduced.
Ensure a suitable distance from electronic compo­nents and other installed enclosures so that the re­quired air circulation is not obstructed and prevented.
– One cold air outlet from the air/water heat exchanger
must be kept open at all times when operating with the air duct, to prevent the accumulation of cold air inside the unit.
4 Installation
Fig. 5: Cover bungs

4.3.2 Make a mounting cut-out

The enclosure air/water heat exchanger is fitted on the roof of the enclosure. To this end, the roof plate must be cut out as per the drilling template included with the sup­ply.
Note: Pre-configured, reinforced roof plates with cut-outs to match your enclosure are availa­ble as accessories; refer to the Rittal Cata­logue.
Stick the supplied drilling template onto the roof of the enclosure using adhesive tape.
There are dimensioning lines on the drilling template to suit the installation type for your air/water heat ex­changer.
Drill all the required holes and make the mounting cut­out.
Carefully deburr all drilled holes and the cut-out to pre­vent injuries caused by sharp edges.
EN
Caution! Drilled holes and cut-outs that have not
been fully deburred may cause cut inju­ries, particularly when assembling the cooling unit.
Fig. 4: Targeted air routing inside the enclosure
Note:

4.3.3 Assembling the air/water heat exchanger

Stick the supplied sealing frame onto the cut out roof plate.
When using the cover bungs, no more than 2 cold air outlets should be sealed.
Rittal air/water heat exchangers 7
EN
4 Installation
Fig. 6: Sealing frame on roof plate
Stick the supplied sealing plate onto the underside of the unit.
Mount the air/water heat exchanger on the enclosure roof.
Screw the supplied twin-threaded bolts into the holes in the plastic base on the underside of the device.
Secure the unit using the supplied washers and nuts.
Note: In order to achieve a permanent seal be-
tween the air/water heat exchanger and the enclosure, the mounting surface should be reinforced or supported if necessary. This is particularly applicable with large roof areas.
Accessories for roof plate reinforcement with TS (refer also to Accessories in the Rittal Catalogue):
– Punched rail –U nut – Fastening bracket – Threaded block

4.3.4 Connecting the condensate discharge

A flexible condensate discharge hose Ø 12mm (½") can be fitted to the air/water heat exchanger.
The condensate discharge – must be laid with a suitable and constant gradient (no
siphoning) – must be laid without kinks – must not have a reduced cross-section if extended The condensate hose is available as an accessory (refer
also to Accessories in the Rittal Catalogue).
1
2
3
Fig. 7: Roof plate reinforcement for the TS 8 enclosure
Fig. 8: Connect the condensate discharge to the side of the
unit
Key
1Cooling water connection (inlet) 2 Cooling water connection (return) 3 Condensate water discharge
Connect a suitable hose from the right or rear to the
condensate nozzle screwed into the unit, and secure
it with a hose clip (with 2 Nm torque).
Lay the condensate hose, e.g. into a drain. Alternatively, the condensate discharge can also be connected on the rear of the unit.
In this case, proceed as described in section 4.4.2
"Connection on the rear of the unit".
Note: To avoid kinking of the condensate hose, use
the angled connector contained in the scope of supply.
8 Rittal air/water heat exchangers
Ø 12 mm (½")
Fig. 9: Lay the condensate discharge to the side of the unit

4.4 Connecting the water connection

A compression-proof flexible condensate discharge hose Ø 12 mm (1/2") for both the supply and the return can be fitted to the air/water heat exchanger. The cooling water hose – must be laid without kinks – must not have a reduced cross-section if extended
and
– must be insulated, if necessary.
4 Installation
When doing so, ensure that the pre-assembled screw connector is not loosened from the unit (SW 22 span­ner).
Connect a suitable hose to each of the two cooling water connection nozzles (at the side or rear of the unit) and secure each one with a hose clip (with 25 Nm torque).

4.4.2 Connection on the rear of the unit

Remove the sealing bung.
Screw-in the threaded connector that is far from the device side and seal the joints with Teflon tape or hemp and sealing compound.
Proceed as described in section 4.4.1 "Connection on the side of the unit".
Subsequently use the sealing bungs to close the open connector holes on the side of the unit.
Warning! Switch off the power supply to the air/
water heat exchanger before working on the water circuit and take suitable pre­cautions against it being accidentally switched on again.
Note: The water circuit should be protected from ingress of dirt or excess pressure (maximum permitted operating pressure 10 bar)!
EN
Fig. 10: Connect the cooling water inlet (top) and return (centre)
to the side of the unit

4.4.1 Connection on the side of the unit

Push the sealing rings onto the screw connector and tighten the nozzles contained in the accessory pack with min. 25 Nm and max. 30 Nm.
Attention! Volumetric flows > 400 l/h may cause
damage to the device. Suitable meas­ures should be taken to regulate the vol­umetric flow, such as flow regulator valves (Model Nos. 3301.930/.940,
3201.990). Damage caused by excessive volumetric flows will not be covered by Rittal's warranty.
Note: No considerable increase in cooling output is
achieved with flow rates > 400 l/h.
Note: Observe the flow direction and check for
leaks!
Note: The unused cooling water connecting pieces must be closed appropriately with sealing bungs.
Rittal air/water heat exchangers 9
4 Installation
EN
The units do not have any separate ventilation.
For pressure-sealed systems, install the appropriate ventilation equipment on the water side.

4.4.3 Notes on water quality

To ensure the reliable operation of the above-mentioned units, the VBG guidelines for cooling water must be ob­served (VGB R 455 P).
The cooling water must not contain any limescale de­posits; in other words, it should have a low level of hard­ness, in particular, a low level of calcium hardness. In particular, for recooling within the plant, the calcium hardness should not be too high. On the other hand, the water should not be so soft that it attacks the materials. When recooling the cooling water, the salt content should not be allowed to increase excessively due to the evaporation of large quantities of water, since electrical conductivity increases as the concentration of dissolved substances rises, and the water thereby becomes more corrosive.
Always add the appropriate volume of fresh water.
Always remove part of the enriched water.
The following criteria for the cooling water must be ob­served: – Water with high gypsum content is unsuitable for cool-
ing purposes because it has a tendency to form boiler scale that is particularly difficult to remove.
– The cooling water should be free from iron and man-
ganese, otherwise deposits may occur that accumu­late in the pipes and block them.
– At best, organic substances should only be present in
small quantities, otherwise sludge deposits and micro­biological contamination may occur.

4.4.4 Preparation and maintenance of the water in recooling systems

Depending on the type of installation to be cooled, cer­tain requirements are placed on the cooling water with respect to purity. According to the level of contamination and the size and design of the recooling systems, a suit­able process is used to prepare and/or maintain the wa­ter.
The most common types of contamination and most fre­quently used techniques to eliminate them in industrial cooling are:
Contamination of the water
Mechanical contamination Filter the water using:
Excessive hardness Water softening via ion ex-
Tab. 2: Contamination and procedures for eliminating it
Procedure
– Mesh filter – Gravel filter – Cartridge filter – Precoated filter
change
Contamination of the water
Moderate content of me­chanical contaminants and hardeners
Moderate content of chemi­cal contaminants
Biological contaminants, slime bacteria and algae
Tab. 2: Contamination and procedures for eliminating it
Procedure
Addition of stabilisers and/ or dispersing agents to the water
Addition of passifiers and/or inhibitors to the water
Addition of biocides to the water

4.5 Electrical connection

4.5.1 Notes on electrical installation

When carrying out the electrical installation, it is impor­tant to observe all valid national and regional regula­tions as well as the provisions of the responsible power supply company.
The electrical installation must comply with EN 61 439 and may only be carried out by a qualified electrician who is responsible for compliance with the applicable standards and regulations.
Connection data
– The connected voltage and frequency must corre-
spond to the values stated on the rating plate.
– The air/water heat exchanger must be connected to
the mains via a category III all-pole disconnecting de­vice (IEC 61 058-1) that ensures at least 3 mm contact opening when switched off.
– No additional temperature control may be connected
upstream of the unit at the supply end.
– The mains connection must ensure low-noise poten-
tial equalisation.
Overvoltage protection and supply line load
– The unit does not have its own overvoltage protection.
Measures must be taken by the operator at the supply end to ensure effective lightning and overvoltage pro­tection. The mains voltage must not exceed a toler­ance of ±10%.
– In accordance with IEC 61 000-3-11, the unit is in-
tended solely for use at sites with a continuous cur­rent-carrying capacity (incoming mains power supply) of more than 100 A per phase and with a supply volt­age of 400/230 V. If necessary, the power supply company must be consulted to ensure that the contin­uous current-carrying capacity at the point of connec­tion to the public grid is sufficient for connection of such a unit.
– The fans in single- and three-phase units are intrinsi-
cally safe (thermal winding protection). The same also applies to all transformer versions and to special-volt­age units which are likewise equipped with a trans­former.
10 Rittal air/water heat exchangers
Install the pre-fuse specified on the rating plate to pro­tect the cable and equipment from short circuits.
Select a suitable motor circuit-breaker/transformer cir­cuit-breaker in accordance with the information spec­ified in the rating plate: Set it to the rated current.
This will achieve the best short-circuit protection for cables and equipment.
Example: Specified setting range MS/TS 6.3 – 10A; set to 6.3A.

4.5.2 Door limit switch (e-Comfort controller only)

– Each door limit switch must only be assigned to one
air/water heat exchanger.
– Several door limit switches may be connected in par-
allel and operated on one air/water heat exchanger.
– The minimum cross-section for the connection cable
is 0.3 mm the use of a shielded cable.
– The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
– The door limit switch only supports a floating connec-
tion; no external voltages.
– The contact of the door limit switch must be closed
when the door is open. The safety extra-low voltage for the door limit switch is provided by the internal power pack: Current approx. 30 mA DC.
Connect the door limit switch to terminals 1 and 2 of
the connector.
2
for a cable length of 2 m. We recommend
4 Installation
EN
Note: The door limit switch is available as an acces-
sory (Model No. 4127.010).

4.5.3 Potential equalisation

If, for EMC reasons, the unit is to be integrated into the customer's existing potential equalisation system, a conductor can be connected to the potential equalisa­tion connection point. The connection point is marked with a schematic symbol.
Note: According to the standard, the PE conductor
in the mains connection cable is not classified as an equipotential bonding conductor.

4.5.4 Install the power supply

Use the electrical circuit diagram to complete the elec-
trical installation within the air/water heat exchanger.
If you would like the system messages from the air/
water heat exchanger to be evaluated via the system
message relay, you should also connect a suitable
low-voltage cable to connection terminals 3 – 5 (1 x
change-over contact Basic controller, 2 x normally
open contacts e-Comfort controller).
Rittal air/water heat exchangers 11
Loading...
+ 25 hidden pages