Rittal PMC12, 7857.430, 7857.431, 7857.432, 7857.482 User Manual

...
Rittal PMC12 UPS – User Manual
1phase UPS-System with online-double-conversion technology
Powerrange 1 - 3 kVA
(Art.-Nr. 7857.430, 7857.431, 7857.432, 7857.482, 7857.483)
FRIEDHELM LOH GROUP
R i t t a l GmbH &
Co.
KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n Germany
Email: Info@rittal.de http://www.rittal.com Service -Tel. : (+49) - (0)2772 / 505 - 9052
A 38333 13 IT 74e.doc
2
EN
Microsoft Windows is a registered trademark of Microsoft Corporation. Acrobat Reader is a registered trademark of Adobe Systems Incorporated.
UPS-Manual
3
EN
Table of Contents
1. IMPORTANT SAFETY INSTRUCTION
.........................................4
1.1. D
OCUMENTATION NOTES
................................4
1.2. R
ETENTION OF THE DOCUMENTS
.....................4
1.3. U
SED SYMBOLS
...............................................4
1.4. S
AFETY INSTRUCTIONS
....................................4
1.5. P
ROPER
USE
...................................................5
1.6. S
TORAGE INSTRUCTIONS
.................................5
2. PRODUCT INTRODUCTION
.......6
2.1. G
ENERAL CHARACTERISTICS
..........................6
2.2. S
PECIAL FEATURES
.........................................6
3. UPS FUNCTIONAL DESCRIPTIONS
......................................7
3.1. UPS F
RONT PANEL DISPLAY
...........................7
3.1.1.
Symbols on the LCD Display Panel .......7
3.2. R
EAR PANEL DESCRIPTION
PMC12 ................8
3.3. R
EAR PANEL DESCRIPTION
PMC12
COMPACT
9
3.4. O
PERATING MODES
& UPS C
ONFIGURATION
10
3.4.1.
System Configuration...........................10
3.4.2.
Using the Software...............................10
3.4.3.
Configuration of the programmable
outlets 10
3.5. C
OMMUNICATION PORT EXPLANATION
.........11
3.5.1.
True RS232 Port Descriptions .............12
3.5.2.
USB Port Descriptions.........................12
3.5.3.
EPO (Emergency Power Off)...............12
4. INSTALLATION AND OPERATION
...........................................12
4.1. U
NPACKING
...................................................12
4.2. S
ELECTING INSTALLATION POSITION
............12
4.3. S
ET UP
...........................................................13
4.3.1.
Tower Configuration Setup..................13
4.3.2.
Power Module + Battery Module ........13
4.3.3.
Rack-Mount Configuration Setup ........13
4.4. O
PERATION
...................................................14
4.4.1.
Start Up In Normal Mode ....................14
4.4.2.
Start-up in Battery Mode (Cold Start) .15
4.4.3.
Check Measured Values & Figures
detected by UPS.....................................................15
4.4.4.
UPS Default Data and Special Function
Execution 16
4.4.5.
UPS default settings and their
alternatives............................................................17
4.4.6.
UPS is off due to unknown reason and is
trouble thooting.....................................................18
4.4.7.
Shut Off ................................................18
4.4.8.
Bypass Mode........................................18
4.5. S
TATUS
& A
LARM BUZZER
...........................19
4.6. B
ATTERY REPLACEMENT
..............................20
5. UPS WORKING PRINCIPLE
.....22
5.1. UPS S
YSTEM BLOCK DIAGRAM
................... 22
5.2. W
HEN MAINS IS AVAILABLE
........................ 22
5.3. W
HEN MAINS IS ABSENT
.............................. 23
5.4. O
VERLOAD CONDITION
................................ 23
5.5. I
NVERTER FAILURE
....................................... 23
5.5.1.
Output Load short circuit when supply
via inverter............................................................ 23
5.5.2.
Inverter/Internal Over temperature .... 24
5.5.3.
Inverter Over-current and Inverter
Output Voltage out of tolerance ........................... 24
6. MAINTENANCE GUIDE
..............24
6.1. T
ROUBLE SHOOTING
..................................... 24
6.2. E
RROR CODES AND THEIR DESCRIPTIONS
..... 26
6.3. M
AINTENANCE
............................................. 26
7. BUNDLE SOFTWARE INSTALLATION
.....................................26
7.1. H
ARDWARE INSTALLATION
.......................... 26
7.2. S
OFTWARE INSTALLATION
........................... 26
8. OPTIONAL COMMUNICATION CARD
.........................................................27
8.1. SNMP A
DAPTER
.......................................... 27
8.2. I
NTERNAL
SNMP A
DAPTER
......................... 27
9. CUSTOMER SERVICE
................27
10. TECHNICAL SPECIFICATIONS
28
Important Safety Instruction
UPS-Manual
4
EN
1. Important Safety Instruction
1.1. Documentation Notes
The audience for this guide is the technical specialist familiar with the assembly, installation and operation of the PMC12 UPS-System. You should read this operating guide prior to commissioning and store the guide so it is readily accessible for subsequent use. Rittal cannot accept any liability for damage and operational malfunctions that result from the non observance of this guide.
1.2. Retention of the Documents
This guide and all associated documents are part of the product. They must be given to the operator of the unit and must be stored so they are available when needed.
1.3. Used Symbols
The following safety and other notes are used in this guide:
Symbol for handling instructions:
This bullet point indicates that you should perform an action.
Safety and other notes:
Danger!
Immediate danger to health and life!
Warning!
Possible danger for the product and the environment!
Note!
Useful information and special features.
1.4. Safety Instructions
1. Assembly and installation of the UPS, in
particular for wiring the enclosures with mains power, may be performed only by a trained electrician. Other tasks asso­ciated with the UPS, such as the as­sembly and installation of system com­ponents with tested standard connec­tors, and the operation and configura-
tion of the PMC12 UPS-System may be performed only by instructed personnel.
2. Observe the valid regulations for the electrical installation for the country in which the unit is installed and operated, and the national regulations for accident prevention. Also observe any company­internal regulations (work, operating and safety regulations).
3. Do not open the case, as there are no serviceable parts inside. Your warranty will be void.
4. Do not try to repair the unit yourself; contact your local supplier or your war­ranty will be void.
5. If liquids are spilt onto the UPS or for­eign objects dropped into the unit, the warranty will be null and void.
6. Do not install the UPS in an environ­ment with sparks, smoke or gas.
7. This UPS is equipped with an EMI filter. To prevent potential leakage current hazard, ensure that the AC main supply is securely grounded.
8. This UPS is designed to be installed and commissioned in a sheltered, con­trolled environment as follows:
- Operating temperature 0-40°C and 30-90% non-condensing humidity.
- Always avoid contact with direct sunlight.
- Do not install the UPS in in­flammable or hazardous envi­ronment.
- Dusty, corrosive and salty envi­ronments can do damage to any UPS.
- Install the UPS indoors as it is not designed for installation out­doors.
9. To prevent any overheating of the UPS, keep all ventilation openings free from obstruction, and do not place anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions.
10. The battery will discharge naturally if the system is unused for any length of time.
11. Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
12. Always switch off the UPS and discon­nect the batteries when relocating the UPS.
13. It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void.
Important Safety Instruction
UPS-Manual
5
EN
When installed and being used, the batteries will be automatically recharged and kept in top condition.
14. Make sure that the AC Utility outlet is correctly grounded.
15. Please ensure that the input voltage of the UPS matches the utility supply volt­age. Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system.
16. Use only genuine or recommended parts and accessories. The use of other parts can void the liability for any re­sulting consequences.
1.5. Proper
Use
This UPS is designed for providing power to IT systems. A use different from that described here is considered to be an improper use. Rittal cannot accept any liability for damage resulting from the improper use or the non-observance of this guide. The guides for the used accesso­ries may apply.
Rittal prohibits the use for life-preserving appli­cations (such as the use in hospitals or the di­rect patient care). Rittal expressly does not sell its products for such applications. Rittal will not accept any responsibility if a UPS is used in this area.
1.6. Storage Instructions
For extended storage in moderate climate, the batteries should be charged for 12 hours at 3 month intervals by connecting the UPS to the utility supply and switch on input breaker lo­cated at UPS rear panel. Repeat this procedure every 2 months if the storage ambient temperature is above 30°C.
Product Introduction
UPS-Manual
6
EN
2. Product Introduction
2.1. General Characteristics
True online technology continuously supplies your critical device with stable, regulated, tran­sient-free pure sine wave AC Power.
1. High-efficiency 20 kHz PWM sine-wave to­pology yields an excellent overall perform­ance. The high crest factor of the inverter handles all high in-rush current loads without the need to upgrade the power rating.
2. A fully digitalised control circuit provides a high level of protection and enables future upgrade. In-built communication capability enhances its ability for remote control and monitoring.
3. The multi-functional LCD panel will display various status of the UPS. The LCD dis­play may show Input/Output Voltage, Fre­quency, Load Status, Inner cabinet tem­perature, and Abnormal Phenomenon.
4. Should the output become short-circuited, the UPS holds the system and cuts the output automatically till the short circuit situation is removed manually.
5. Should the unit become overheated, the internal thermal switch will detect the heat and switch to bypass mode and vice versa.
6. Maintenance-free sealed-type battery minimises after-sales service.
7. The maintenance bypass switch provides easy and safe troubleshooting or mainte­nance function when the utility is normal.
8. User-friendly plug-and-play guarantees a simple installation. As standard, all sys­tems up to 3 kVA are supplied with power supply cable and output connections.
9. To protect the system against overload, the UPS is switched automatically within 30 seconds to bypass operation when the loading reaches a value of 105% ~ 120% of the rated loading. The system is auto­matically switched back into converter op­eration when the overload state no longer exists.
2.2. Special Features
High Frequency Transformer-less technology with rack/tower convertible enclosure enables
the UPS to integrate even in the most difficult of environments with space constraints.
1. This UPS is equipped with fully digitalised control logic for greater functionality and enhanced high level of power protection. Digital signal processing (DSP) also pro­vides the UPS with powerful communica­tion capability, which enhances the flexibil­ity for easy remote control and monitoring
2. Wide input voltage tolerance from 160V~280V allows under-voltage or over­voltage correction without unnecessary battery drain and helps extend the battery life span.
3. The cold start function ensures the start-up of UPS even during power outages. (see Section 4.4.2)
4. Revolutionary battery management circuit analyses battery discharging status to ad­just battery cut-off point and extend the batteries’ life span.
5. Active Power Factor Correction (PFC) control function constantly maintains the UPS Input Power Factor (PF) at > 0.99 for superb energy efficiency.
6. Fast Selectable Output Voltages (200 / 208 / 220 /230 / 240 V) to meet various voltage systems.
7. Selectable Bypass input voltage tolerance (Sensitivity low/high) to prevent under or over voltage being supply to the loads at Bypass mode. The selectable Voltage ranges are:
(i) Sensitivity Low: 184~260V & (ii) Sensitivity High: 194~260V.
8. Intelligent temperature-controlled fan may not only extend the life span, but also reduce annoying noise because of sudden fan spin. Your office remains quiet and comfortable as usual.
9. When the UPS is out of order, you may read out the possible fault reason from the LCD screen directly, which may reduce downtime.
10. The UPS is designed to comply with vari­ous stringent international standards for Electromagnetic Interference & protection (EMC).
UPS Functional Descriptions
UPS-Manual
7
EN
3. UPS Functional Descriptions
3.1. UPS Front Panel Display
LCD Display
Green LED steadily lights up to indicate that
the Utility input voltage is within the window (160Vac~288Vac).
③, ④
Green LED lights up to indicate there is an output available at the Programmable Outlet 1 & Programmable Outlet 2.
Amber LED lights up to indicate the Bypass
Input is normal.
General Fault LED
UPS On/Alarm Silence
UPS OFF Switch
Special functions log in/out
Go to next page
Go to previous page or change the setting
of the UPS.
To re-confirm the change of UPS Setting
3.1.1. Symbols on the LCD Display Panel
Item
Symbol Description
1
LINE
Utility or Bypass Source
2
Battery Low
3
Battery Abnormal
4 UPS Overloading
5
Site Wiring Fault
6
UPS
Working in
Service Mode
7
OFF
UPS Shutoff
8
FAIL
UPS Abnormal Lock
9 UPS Flow Chart
10
4 Digits Measurement Display
11
Indicate the item desired to be measured
12
Er05
Battery Weak or Dead
13
Er06
Output Short Circuit
14
Er10
Inverter Over­current
15
Er11
UPS Overheat
16
Er12
UPS Output Overloading
17
Er**
Other Error Code
UPS Functional Descriptions
UPS-Manual
8
EN
230V
1KVA
2KVA
3KVA
3.2. Rear Panel Description PMC12
1. USB Port
2. RS232 Port
3. Emergency Power Off (EPO) Dry Contact Signal inputs
4. Communication Card Options Slot
5. External Battery Connector
6. AC power connection socket
7. AC Outlets
8. Two programmable outlets
9. Utility Input fuse holder
10. Cooling Fans
11. Output fuse holders
12. Output fuse holders for two programmable outlets
UPS Functional Descriptions
UPS-Manual
9
EN
3.3. Rear Panel Description PMC12
compact
1. USB Port
2. RS232 Port
3. Emergency Power Off (EPO) Dry Contact Signal inputs
4. Communication Card Options Slot
5. External Battery Connector
6. AC power connection socket
7. AC Outlets
8. Two programmable outlets
9. Utility Input fuse holder
10. Cooling Fans
11. Output fuse holders
12. Output fuse holders for two programmable outlets
2KVA
3KVA
1 2
3
4
6
5109
8
7
1 2
3
4
6
5109
8
7
12
11
UPS Functional Descriptions
UPS-Manual
10
EN
3.4. Operating Modes & UPS Configuration
Install the “Rittal PMC12 UPS-Software“ from the enclosed CD or download it from
http://www.rimatrix5.com/service_support/downloads.asp.
Run the programm „UPSMan Configuration“. The following Window appears:
3.4.1. System Configuration
1. Select the UPS-type and the number of
battery packs you have connected. The data in the lower part of the window will be filled in automatically..
2. Name the location of the UPS
3. Choose the port on which the UPS is
connected to your PC. (If you choose „CS122“, you have to write down the IP­address of the UPS-System).
4. If you did not write down a valid licence key
during the installation you have the possibility to switch your 30-days trial version into a full-version later, by tipping in a valid key.
5. The button „Advanced User“ allows you to
edit the before locked fields of the window. This function should only be used by persons who have detailed knowledge about the UPS-System. Rittal takes no responsibility for system failure which is caused by false data.
6. To save the settings press “OK”. To activate the configuration you have to restart the UPS­System.
3.4.2. Using the Software
1. Run the program „UPSMonitor“
2. Choose the connection on which the UPS is connected to the PC.
3. After the connection was successful the main menu of the program will open. There you have an overview about all parameters of the UPS. The configuration of the UPS is finished.
3.4.3. Configuration of the programmable outlets
The UPS has 2 programmable outlets on which uncritical loads can be connected. These outlets can be switched off and offer therefor a longer power supply to even more critical loads in case of a power fail or overload of the UPS.
Click in the upper side of the window on the button “Functions" „Device Functions“ and then click in „Extended Cmds“.
Here you can manually switch the two outlets and initiate a restart or switch off the UPS.
The button „Programmable Outlet Settings“ allows you to program the outlets.
Loading...