Rittal 7857.433, 7857.434 Assembly And Operation Instructions Manual

Assembly and Operation Instructions
UPS System
Concept
PMC 12
4,5 and 6kVA
7857.433
7857.434
Microsoft Windows is a registered trademark of Microsoft Corporation. Acrobat Reader is a registered trademark of Adobe Systems Incorporated.
UPS-Manual
2
EN
Table of Contents
IMPORTANT SAFETY INSTRUCTIONS..3
1.1. Documentation Notes........................................3
1.2. Retention of Documents...................................3
1.3. Symbols Used.....................................................3
1.4. Safety Instructions............................................3
1.5. Proper Use .........................................................4
1.6. Storage Instructions..........................................4
2. PRODUCT INTRODUCTION ..........5
2.1. General Characteristics....................................5
2.2. Special Features.................................................5
3. UPS FUNCTIONAL DESCRIPTIONS
6
3.1. UPS Front Panel Display..................................6
3.1.1. Symbols on the LCD DisplayPanel............ 6
3.2. Rear Panel Descriptions ...................................8
3.2.1. UPS input and output.................................8
3.2.2. Battery input...............................................8
3.3. Communication Port Explanation...................9
3.3.1. EPO (Emergency Power Off).....................9
3.3.2. RS232 Port Descriptions............................ 9
4. INSTALLATION ............................10
4.1. Unpacking........................................................10
4.2. Selecting Installation Position........................11
4.3. Assembling of the different System
Components..................................................................12
4.3.1. Tower Assembling steps ..........................12
4.3.2. Rack installation step................................13
4.4. Electrical Installation......................................16
5. OPERATION .................................17
5.1. Start-Up In Normal Mode..............................17
5.2. Start-up in Battery Mode (Cold Start)......... 18
5.3. Check Measured Values & Figures detected by UPS 19
5.4. UPS Default Data and Special Function
Execution...................................................................... 20
5.5. UPS Default Settings and their alternatives. 22
5.6. UPS Is Off Due to Unknown Reason and It’s
Trouble Shooting......................................................... 22
5.7. Shut Off........................................................... 23
5.8. Maintenance Bypass Mode............................ 23
6. TROUBLESHOOTING GUIDE .....24
6.1. Troubleshooting.............................................. 24
7. BUNDLED SOFTWARE
INSTALLATION GUIDE ......................... 25
7.1. Hardware Installation.................................... 25
7.2. Software Installation...................................... 25
8. OPTIONAL COMMUNICATION
CARD......................................................25
8.1. SNMP Adapter............................................... 25
8.2. Internal SNMP Adapter................................ 26
9. HOT SWAPPABLE BATTERY
REPLACEMENT..................................... 27
10. CUSTOMER SERVICE................. 27
11. TECHNICAL DATA ...................... 28
Important Safety Instructions
UPS-Manual
3
EN
Important Safety Instructions
1.1. Documentation Notes
The audience for this guide is the technical specialist familiar with the assembly, installation and operation of the PMC12 UPS-System. You should read this operating guide prior to commissioning and store the guide so it is readily accessible for subsequent use. Rittal cannot accept any liability for damage and operational malfunctions that result from the non observance of this guide.
1.2. Retention of Documents
This guide and all associated documents are part of the product. They must be given to the operator of the unit and must be stored so they are available when needed.
1.3. Symbols Used
The following safety and other notes are used in this guide:
Symbol for handling instructions:
This bullet point indicates that you should perform an action.
Safety and other notes:
Danger!
Immediate danger to health and life!
Warning!
Possible danger for the product and the environment!
Note!
Useful information and special features.
1.4. Safety Instructions
1. Assembly and installation of the UPS, in
particular for wiring the enclosures with mains power, may be performed only by a trained electrician. Other tasks asso­ciated with the UPS, such as the as­sembly and installation of system com­ponents with tested standard connec­tors, and the operation and configura­tion of the PMC12 UPS-System may be performed only by instructed personnel.
2. Do not open the case, as there are no serviceable parts inside. Your warranty will be void.
3. Do not try to repair the unit yourself; contact your local supplier or your war­ranty will be void.
4. If liquids are spilt onto the UPS or for­eign objects dropped into the unit, the warranty will be null and void.
5. Do not install the UPS in an environ­ment with sparks, smoke or gas.
6. The batteries inside the external packages of these ups can have a strengthened gas emission of hydrogen in case of a fire or technical fault. Please refer to EN 50272-2 for references for battery ventilation.
7. This UPS is equipped with an EMI filter. To prevent potential leakage current hazard, ensure that the AC main supply is securely grounded.
8. This UPS is designed to be installed and commissioned in a sheltered, con­trolled environment as follows:
- Operating temperature 0-40°C and 30-90% non-condensing humidity.
- Always avoid contact with direct sunlight.
- Do not install the UPS in inflammable or hazardous environment.
- Dusty, corrosive and salty envi­ronments can do damage to any UPS.
- Install the UPS indoors as it is not designed for installation out­doors.
9. To prevent any overheating of the UPS, keep all ventilation openings free from obstruction, and do not place anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions.
10. The battery will discharge naturally if the system is unused for any length of time.
11. Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
12. Always switch off the UPS and discon­nect the batteries when relocating the UPS.
13. It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void. When installed and being used, the batteries will be automatically recharged and kept in top condition.
Important Safety Instructions
UPS-Manual
4
EN
14. Make sure that the AC main supply outlet is correctly grounded.
15. Please ensure that the input voltage of the UPS matches the utility supply volt­age. Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system.
16. Observe the valid regulations for the electrical installation for the country in which the unit is installed and operated, and the national regulations for accident prevention. Also observe any company­internal regulations (work, operating and safety regulations).
17. Use only genuine or recommended parts and accessories. The use of other parts can void the liability for any resulting consequences.
1.5. Proper Use
This UPS is designed for providing power to IT systems. A use different from that described here is considered to be an improper use. Rittal cannot accept any liability for damage resulting from the improper use or the non-observance of this guide. The guides for the used accessories may apply. Rittal prohibits the use for life-preserving applications (such as the use in hospitals or the direct patient care). Rittal expressly does not sell its products for such applications. Rittal will not accept any responsibility if a UPS is used in this area.
1.6. Storage Instructions
For extended storage in moderate climate, the batteries should be charged for 12 hours at 3 month intervals by connecting the UPS to the utility supply and switch on input breaker lo­cated at UPS rear panel. Repeat this procedure every 2 months if the storage ambient temperature is above 30°C.
Product Introduction
UPS-Manual
5
EN
2. Product Introduction
2.1. General Characteristics
The double-conversion technology in accordance with the specification VFI-SS-111 guarantees the power supply to connected terminal devices with a pure sinusoidal voltage.
1. The ultra-efficient PWM technology achieves a high efficiency for an almost sinusoidal output voltage. The high crest factor of the converter filters any switch-on current peaks without the loading needing to be modified.
2. A fully digitalised control circuit provides a high level of protection and enables future upgrade. In-built communication capability enhances its ability for remote control and monitoring.
3. The multi-functional LCD/LED panel will display various status of the UPS. The LED display may show UPS working status, Utility Status and UPS Abnormal status, whilst the LCD display may show Input/Output Voltage, Frequency, Load Status, Inner cabinet temperature, and Abnormal Phenomenon.
4. To protect the unit from overloading, it automatically switches to bypass mode in ~160 seconds if loading is at 105% of rating and in case of overloading of more than 150% of rating, it switches to bypass mode immediately. It will automatically switch back to inverter mode once overload condition ceases.
5. If a short-circuit occurs at the output, the UPS switches the system into standby operation. The UPS issues an audiovisual alarm and automatically interrupts the current output until the short-circuit has been corrected manually.
6. Should the unit become overheated, the internal thermal switch will detect the heat and switch to bypass mode and vice versa.
7. Maintenance-free sealed-type battery minimises after-sales service.
8. The maintenance bypass switch provides easy and safe troubleshooting or maintenance function when the utility is normal.
2.2. Special Features
The transformer-free converter technology with a housing that can be mounted in a rack or used as floor-standing enclosure allows the UPS to be integrated even in environments with restricted space.
1. The UPS is equipped with an intelligent microprocessor-based controller and offers a flexible configuration capability with remote communication and comprehensive overload protection.
2. A large 184 V ~ 288 V input voltage range permits an under voltage and overvoltage correction without unnecessary battery discharge and so ensures an increased battery lifetime.
3. The cold start function ensures that the UPS can be switched on even when no mains voltage is present (see chapter
5.2).
4. An optimum battery management system analyses the charging state of the battery in order to maximise the battery lifetime.
5. The "Active Power Factor Correction (PFC)" control function keeps the "Input Power Factor (PF)" of the UPS to a value > 0.99. This allows an excellent energy efficiency to be attained.
6. Selectable bypass input voltage tolerance (high/low sensitivity) ensures that the consumers are not supplied with under voltage or overvoltage during bypass operation. The selectable voltage ranges are:
(i) low sensitivity: 184 ~ 260 V (ii) high sensitivity: 194 ~260 V.
7. Fixed selectable output voltages (220/230/240) to satisfy the requirements for different voltage systems.
8. The UPS satisfies all relevant EMC regulations.
UPS Functional Descriptions
UPS-Manual
6
EN
3. UPS Functional Descriptions
3.1. UPS Front Panel Display
LC Display Green LED steadily lights up to indicate that
the utility input voltage is within the window; the LED flashes flickeringly to indicate that the utility input voltage is within the acceptable window.
Green LED lights up to indicate Bypass
Input is normal.
Green LED lights up to indicate the UPS
has the capability to run under redundancy mode.
UPS is working under ECO (Economic,
Line-interactive) mode.
UPS Fault or Abnormal UPS On/Alarm Silence UPS OFF Switch Special functions log in/out Go to next page Go to previous page or change the setting
of the UPS.
To re-confirm the change of UPS Setting
3.1.1. Symbols on the LCD
DisplayPanel
Item Symbol Description
1
LINE
Utility or Bypass Source
2
Battery Low
3
Battery Abnormal
4 UPS Overloading
5
UPS Working in Service Mode
1
6
A Blackout Transfer occurred in UPS Output
7
Bypass Input Abnormal, UPS fails to transfer to bypass, Bypass Abnormal at ECO mode
8
Utility Input Abnormal
9
OFF
UPS Shutoff
10
LINE OFF
UPS Abnormal Lock
11 UPS Flow Chart
12
4 Digit Measurement Display
13
Indicates the item desired to be measured
14
UPS ON Switch or Alarm Silence
15 UPS OFF Switch
1
The specified modes include Normal mode, ECO mode,
CVCF mode, etc..
UPS Functional Descriptions
UPS-Manual
7
EN
16
Previous Page or Setting Change
17 Next Page
18
Special Function Log in /out
19
Enter or Reconfirmed
20
Utility Input Normal LED
21
Utility Input Normal LED
22
UPS under Redundancy Mode
23
UPS under ECO Mode
24
UPS Fault or Abnormal Warning LED
25
EPO
Emergency Power Off
26
Er05
Battery Weak or Dead
27
Er06
Output Short Circuit
28
Er10
Inverter Over­current
29
Er11
UPS Overheat
30
Er12
UPS Output Overloading
31
Er15
Wrong Procedure to Enter Maintenance Mode
32
Er16
Output Parameters Set Error in Parallel System
33
Er17
ID Numbers are in conflict in Parallel System or ID number Error in single unit
34
Er21
Parallel communication error (communication wire disconnected or failure to find ID1 UPS ) in parallel system
35
Er24
CVCF mode with Bypass input
36
Er27
The UPS must be operated in normal mode in parallel s
y
stem
37
Er28
Bypass Overload Time out and cut off output
38
Er31
The settings of both control board and driver board are not matched each other
39
Er**
Other Error Code
UPS Functional Descriptions
UPS-Manual
8
EN
3.2. Rear Panel Descriptions
A Terminal Resistor for Parallel function B RS232 Port C EPO Port D Utility Input Breaker E CAN Bus Connection Port for Parallel System F External Battery Connector G Cooling Fan H Utility Input &UPS Output Power Connector
I Customer Options Slot J Slot
3.2.1. UPS input and output
3.2.2. Battery input
Model Maximum
Current
Conductor
Section
4,5 kVA 24 A 4 mm²
6 kVA 32 A 4 mm²
Model Maximum
Current
Conductor
Section
4,5 kVA 25 A
AWG #10,
6 mm²
6 kVA 25 A
AWG #10,
6 mm²
B A
C
D
G
I
E F
H
J
1 L in 2 N
in
PE 3 L
out
4 N out
UPS Functional Descriptions
UPS-Manual
9
EN
3.3. Communication Port Explanation
The Communication port on the UPS provides true RS232 type communication with the UPS software to remotely monitor the power and UPS status.
The bundled UPS software is compatible with many operating systems such as Windows 98, & 2000, ME, NT and XP. For other applications like Novell, NetWare, Unix, Linux, please contact your local distributor for a proper solution.
Highest Priority (in descending order),
1) EPO input port
2) Optional Interface card
3) RS232
3.3.1. EPO (Emergency Power Off)
The Pin assignments of the EPO Input port are:
1 2
1 Æ EPO+ 2 Æ Ground
To enable the EPO function, please short Pin 1 & 2.
3.3.2. RS232 Port Descriptions
The RS232 interface shall be set as follows:
Baud Rate 2400 bps Data Length 8 bits Stop Bit 1 bit Parity None
The Pin Assignments of the true RS232 port are illustrated as follows:
Pin 3: RS232 Rx Pin 2: RS232 Tx Pin 5: Ground
1
2
3
4
5
6
7
8
9