Rio RIO09HP115V1A, RIO09HP230V1A, RIO12HP230V1B, RIO12HP115V1A, RIO18HP230V1A Installation, Service & Troubleshooting

...
Page 1
DUCTLESS SYSTEM
Installation, Service & Troubleshooting
Models:
RIO09HP115V1A RIO12HP115V1A RIO09HP230V1A
RIO09HP230V1B
RIO12HP230V1A
RIO12HP230V1B
RIO18HP230V1A RIO24HP230V1A
Page 2
Table of Contents
Safety Precautions & Warnings.........................................................................................................................
Model Number Identication............................................................................................................................
Physical & Electrical Data.................................................................................................................................
Product Introduction.........................................................................................................................................
Refrigeration Cycles and Components............................................................................................................
Indoor & Outdoor Components.......................................................................................................................
Basic & Protection Functions............................................................................................................................
Remote Control Operation................................................................................................................................
Refrigerant Lines, Connection, Evacuating and Charging............................................................................
Installation and Filter Maintenance.................................................................................................................
Electrical Schematics..........................................................................................................................................
3
4
5 - 7
8
9 - 13
14 - 15
16 - 21
22 - 25
26 - 29
30 -35
36 - 44
Outdoor Circuit Board........................................................................................................................................
Troubleshooting Indoor Components..............................................................................................................
Troubleshooting Outdoor Components...........................................................................................................
Fault Codes & Status Displays...........................................................................................................................
Troubleshooting Flow Charts............................................................................................................................
Disassembly of Indoor Units.............................................................................................................................
Disassembly of 9,000 & 12,000 btuh Outdoor Systems.................................................................................
Disassembly of 18,000 and 24,000 btuh Outdoor systems.............................................................................
Appendix 1 - 3 Temperature Sensor Resistance Tables..................................................................................
45
46 - 47
48 - 56
57 - 78
79 - 105
106 - 111
112 - 117
118 - 123
123 - 129
2
Page 3
Safety Precautions & Warnings
!
Installing, starting up, and servicing air conditioner can be hazardous due to system pressure, electrical components,
and equipment location, etc. Only trained, qualied
installers and service personnel are allowed to install, start­up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When handling the equipment, observe precautions in the manual and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and
re extinguisher nearby when brazing. Read the instructions
thoroughly and follow all warnings or cautions in literature and attached to the unit. Consult local building codes and current editions of national as well as local electrical codes.
Recognize the following safety information:
Warning: Incorrect handling could result in
!
personal injury or death.
Caution: Incorrect handling may result in minor
!
injury, or damage to product or property.
Warning
!
Never install the unit in a place where a combustible
gas might leak, or it may lead to re or explosion.
Make a proper provision against noise when the unit is installed at a telecommunication center or hospital.
Provide a GFIC circuit when the local or national electric code requires it.
Never wash the unit with water.
Handle unit transportation with care. Use two people
when the weight exceeds the capacity for one person.
Never touch the heat exchanger ns with bare hands, sharp edges could cause personal injury.
Never touch the compressor or refrigerant tubing without proper hand protection.
Do not operate th unit without the air lters in place.
Should any emergency occur, stop the unit and disconnect the electrical supply.
Properly insulate tubing running inside the room to prevent water damage from condensation.
!
All installation or repair work shall be performed by your dealer or a specialized subcontractor as there is the risk of
re, electric shock, explosion or injury
Caution
Warning
!
All electrical work must be performed by a qualied,
licensed electrician according to local and national codes as well mas the instructions provided in the manual.
Before installing, modifying, or servicing the system, the main electrical disconnect must be off. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
Never supply power to the unit unless all wiring and tubing are completed, reconnected and checked.
This system adopts highly dangerous electrical voltage. Incorrect connections or inadequate grounding can cause personal injury or death.
Refer to your local and national codes for proper
grounding.
Have the unit properly grounded with all connections tight. Loose connections can cause
overheating and a possible re hazard.
Warning
!
Warning
Pressurized Refrigerant
Personal injury could result in failure to follow this warning. Systems contain oil and refrigerant under high pressure, proper refrigerant handling techniques should be
completed by a qualied technician.
!
Warning
Live Electrical Components
Personal injury, property damage, or death could result in failure to follow this warning. Follow all electrical precautions when servicing this system, it may be necessary to service or troubleshoot with live electrical circuits. All work should be completed by a
qualied technician.
3
Page 4
Model Number Identication
Product Catalog Number-Nomenclature
Example RIO24HP230V1AH
RIO 24 HP 230V 1 A H
S - System O - Outdoor H - Indoor High Wall D - Indoor Duct C - Indoor Cassette F - Indoor Floor/Ceiling
RIO
NEO
TERRA
Revision Level
09 - 9,000 btuh 12 - 12,000 btuh 18 - 18,000 btuh 24 - 24,000 btuh
AC - Cooling Only HP - Heat Pump HC - Heat/Cool
Style/Color Designation
230V - 208/20V 60Hz 1PH 115V - 115V 60Hz 1PH
4
Page 5
Physical & Electrical Data, cont.
Model RIO09HP115V1A RIO12HP115V1A
System Type Heat Pump
Power Supply 115v / 60Hz 115V / 60Hz
Rated Current Cooling Amps 9.0 15.0
Rated Current Heating Amps 9.5 15.5
System Performance
Cooling Cap (Min/Max) Btu/h 9,000 (3,500-11,000) 11,800 (3,300-12,500)
Heating Cap (Min/Max) Btu/h 9,800 (2,500-11,000) 13,000 (3,400-13,500)
Operating Range - Cooing deg F 64 - 113 64 - 113
Operating Range - Heating deg F 5 - 75 5 - 75
System Specications
Compressor Type DC Inverter-driven Twin Rotary
Sound Pressure - Outdoor dBA 53 55
Net/Gross Weight Indoor lbs 19/26 19/26
Net/Gross Weight Outdoor lbs 75/84 75/84
Condenser Coil Type
Refrigerant/Charge oz R410a /37.5 R410a / 41.1
Line Set Size Liq. - Suction 1/4” - 3/8” 1/4” - 3/8”
Pre-Charged Lineset Ft. Feet 25 25
Additional Refrigerant charge/additional feet
Max. Total Piping Length Feet 66 66
Max. Elevation Feet 33 33
MCA Amps 13 15
MOCP/Breaker Size Amps 20 25
Wire Size to Outdoor Unit, # of Wires per Local Code
Wire Size and # of Conductors from Indoor to Outdoor unit
oz 0.2 0.2
awg 14* 12*
14awg/4c*
*Comply with National Electric Code or Local Electric Code in selecting proper wire and circuit breaker size. National Code or Local Code, should supersede wire sizes above.
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please refer to specic installation manual for current information.
refer to specic installation manual for current information.
5
Page 6
Physical & Electrical Data, cont.
Model RIO09HP230V1A & 1B
System Type Heat Pump
Power Supply 208-230v / 60Hz 208-230V / 60Hz
Rated Current Cooling Amps 3.9 5.4
Rated Current Heating Amps 3.4 4.7
System Performance
Cooling Cap (Min/Max) Btu/h 9,000 (3,800-11,500) 12,000 (3,300-12,500)
Heating Cap (Min/Max) Btu/h 9,000 (3,300-11,500) 12,000 (3,400-12,500)
Operating Range - Cooing deg F 5 - 109 5 - 109
Operating Range - Heating deg F 5 - 75 5 - 75
System Specications
Compressor Type DC Inverter-driven Twin Rotary
Sound Pressure - Outdoor dBA 49 52
Net/Gross Weight Indoor lb 19/25 20/27
Net/Gross Weight Outdoor lb 64/73 68/77
Condenser Coil Type
Refrigerant/Charge oz R410a / 26.1 R410a / 35.3
Line Set Size Liq. - Suction 1/4” - 3/8” 1/4” - 3/8”
Pre-Charged Lineset Ft. Feet 25 25
Additional Refrigerant charge/additional feet
Max. Total Piping Length Feet 50 50
Max. Elevation Feet 33 33
MCA Amps 10 10
MOCP/Breaker Size Amps 15 15
Wire Size to Outdoor Unit, # of Wires per Local Code
Wire Size and # of Conductors from Indoor to Outdoor unit
oz 0.2 0.2
awg 14* 14*
14awg/4c*
RIO12HP230V1A & 1B
*Comply with National Electric Code or Local Electric Code in selecting proper wire and circuit breaker size. National Code or Local Code, should supersede wire sizes above.
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please refer to specic installation manual for current information.
6
Page 7
Physical & Electrical Data, cont.
Model RIO18HP230V1A RIO24HP230V1A
System Type Heat Pump
Power Supply 208-230v / 60Hz 208-230V / 60Hz
Rated Current Cooling Amps 7.9 11.5
Rated Current Heating Amps 11.8 13.0
System Performance
Cooling Cap (Min/Max) Btu/h 18,000 (4,500-21,000) 22,000 (6,400-24,000)
Heating Cap (Min/Max) Btu/h 19,200 (4,000-23000) 24,200 (4,100-26,600)
Operating Range - Cooing deg F 5 - 109 5 - 109
Operating Range - Heating deg F 5 - 75 19 - 75
System Specications
Compressor Type DC Inverter-driven Twin Rotary
Sound Pressure - Outdoor dBA 56 53
Net/Gross Weight Indoor lb 27/35 33/44
Net/Gross Weight Outdoor lb 106 / 117 115 / 126
Condenser Coil Type
Refrigerant/Charge oz R410a / 45.9 R410a / 54.7
Line Set Size Liq. - Suction 1/4” - 1/2” 1/4” - 1/2”
Pre-Charged Lineset Ft. Feet 25 25
Additional Refrigerant charge/additional feet
Max. Total Piping Length Feet 82 82
Max. Elevation Feet 33 33
MCA Amps 15 17
MOCP/Breaker Size Amps 25 25
Wire Size to Outdoor Unit, # of Wires per Local Code
Wire Size and # of Conductors from Indoor to Outdoor unit
oz 0.2 0.2
awg 14* 14*
14awg/4c*
*Comply with National Electric Code or Local Electric Code in selecting proper wire and circuit breaker size. National Code or Local Code, should supersede wire sizes above.
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please refer to specic installation manual for current information.
7
Page 8
Product Introduction
System Overview
e RIO Ductless split heat pumps are single zone units available in size from 9000 btuh to 24,000 btuh providing heating and cooling. All comfort settings are controlled by a remote control. e RIO unit has many features to enhance comfort and eciency. e operation of these features will be explained later in this service manual.
Superior inverter technology is used to control capacity while maintaining maximum eciency. e RIO systems are equipped with G10 inverter technology providing precise control over the compressor frequency based on operating pressures and temperatures. Should an abnormal condition occur, the soware will adjust the compressor frequency or shut down the system indicating the appropriate fault.
Indoor Display
e indoor unit contains a digital display, which will indicate the current fault. e evaporator, swing motors, fan motors and circuit board are also components of the indoor unit. e indoor units have a on/o switch to bypass the remote control if lost or batteries fail. is will be explained later in this service manual.
e systems require R410A and are pre-charged for 25’ of lineset. Please refer to your installation manual for additional charge for linesets longer than 25’.
e maximum allowable line li and distances vary by model, please refer to the charts in the manual for proper lineset applications.
e systems use a PVE oil and should require no additional oil. All RIO units utilize an Oil Return Mode which will return oil to the compressor should the need arise.
Circuit Board with
G10 Technology
8
Compressor
Page 9
Refrigeration Cycles and Components
Refrigeration Components
Indoor Unit
Temperature
Sensor
Heat Exchanger
Strainer
Outdoor Unit
Heat
Exchanger
Temperature
Sensor
Electronic Expansion
Val ve
Accumulator
Compressor
Inverter
Compressor
4-way
Discharge Sensor
Note: Component locations may vary depending on models.
9
Page 10
Cooling Mode
Cooling Mode
Refrigeration Cycles and Components
Outdoor Unit
Strainer
Indoor Unit
Heat Exchanger
Temperature
Sensor
Strainer
Temperature
Sensor
*Electronic
expansion
valve
Accumulator not
Exchanger
on all sizes
Heat
Compressor
Inverter
4-way
4-way
valve
valve
Discharge
Silencer
Discharge
Temperature
Sensor
10
Page 11
Refrigeration Cycles and Components
Cooling Mode
A. Hot gas is discharged from the compressor. e temperature of the gas is monitored by the Discharge Temperature sensor and sent to the outdoor control panel.
B. e hot gas is directed through the 4-way valve, then enters the outdoor coil. e hot gas will be slightly subcooled, however there are no pressure ports to take measurements.
C. e subcooled liquid will enter the lter to remove contaminates.
D. e subcooled liquid will enter the metering device and regulate the superheat level. e adjustment process and compressor speed are controlled by the outdoor circuit board.
E. e refrigerant leaving the metering device will be in a low pressure/temperature saturated state. is cold saturated refrigerant will move through the coil absorbing heat. is liquid will ash to a vapor and will be superheated to about 10 degrees F. Since this tubing is cold, it must be insulated.
F. e superheated vapor will be returned to the outdoor unit’s 4-way valve.
G. e refrigerant will ow to the accumulator (not all models will have an accumulator) where liquid and vapor are separated.
H. e refrigerant will ow to the compressor and complete another refrigeration cycle.
e control board will monitor the temperature and pressures and adjust the frequency of the compressor. ere are no pressure charts to evaluate temperature or pressures.
11
Page 12
Heating Mode
Refrigeration Cycles and Components
Outdoor Unit
Filter
Indoor Unit
Heat Exchanger
Temperature
Sensor
Temperature
Sensor
*Electronic
expansion
valve
Accumulator not
Exchanger
on all sizes
Heat
Compressor
Inverter
4-way
4-way
valve
valve
Discharge
Silencer
Discharge
Temperature
Sensor
12
Page 13
Refrigeration Cycles and Components
Heating Mode
A. Hot gas is discharged from the compressor. e temperature of the gas in monitored by the Discharge Temperature sensor and sent to the outdoor control panel.
B. e hot gas is directed through the 4-way valve to the appropriate indoor coil making the line a hot gas line.
C. e hot gas will enter the indoor coil and condense to a saturated mix as it travel through the coil and will be slightly subcooled.
D. e refrigerant returns to the outdoor unit through the lter, then through the metering device reducing the refrigerant to a low pressure liquid and will maintain the proper superheat.
E. e cold refrigerant will travel through the outdoor coil (evaporator) and will pickup heat from the outdoor air. is will cause the cold saturated refrigerant to ash to a saturated mixture which will be superheated to 10 degrees F.
F. e superheated vapor will travel through the 4-way valve to the accumulator which will prevent liquid oodback.
G. e superheated gas will enter the compressor for another refrigeration cycle.
e control board will monitor the temperature and pressures and adjust the frequency of the compressor. ere are no pressure charts to evaluate temperature or pressures.
13
Page 14
Indoor Unit Components
Indoor Unit Components
RIO 12,000 btuh model Other RIO models may very slightly.
Indoor Circuit
Board
Indoor Tube ermistor
Fan Motor
Swing Motor
Ambient
Temperature
Sensor
Note: Component locations may vary depending on models.
14
Page 15
Outdoor Unit Components
Outdoor Unit Components
RIO 12,000 btuh Outdoor Unit Other RIO models may very slightly.
Outdoor Fan
Capacitors
Outdoor Sensor, (mounted
on outside of coil)
AP1 Board
4-Way Valve
Expansion Valve
Exhaust Temp
Sensor
Crankcase Heater
Note: Component locations may vary depending on models.
Outdoor Tube
Sensor
Compressor
15
Page 16
Basic & Protection Functions
Basic Functions
e compressor should stay o for at least 3 minutes before starting the unit. e compressor circuit has a 3 minute delay if the compressor is de-energized during a run cycle. If the compressor starts from a de-energized cycle, there will be no time delay. e compressor has a minimum runtime of 6 minutes regardless of room temperature.
1) Cooling Mode
Cooling Process
When the indoor ambient rises 4 F above the preset temperature from a stopped state, the unit will start the cooling cycle. e outdoor fan and compressor will start. e indoor fan will run continuously at the selected speed. e outdoor unit will monitor the appropriate temperatures and pressure and adjust the compressor speed and the EEV as required. If the indoor ambient is > 4 F than the preset temperature, the compressor will increase the frequency; < 4 F the compressor will begin reducing the frequency. e EEV will be closed on indoor units with no cooling requirement. e G10 technology will control compressor speed based on indoor load and compressor amperage. When the indoor temperature is satised, the compressor will stop, then 30 seconds later the outdoor fan will stop. When the cooling mode transfers to heating mode, the 4-way valve will be energized aer a two minute compressor delay.
Evaporator Freeze Protection
e soware will monitor the indoor evaporator coil form freezing. e following will occur 6 minutes aer the compressor has been operating in the cooling or dry mode: If the evaporator temperature drops below 36 F, the compressor will operate at a reduced frequency. If the evaporator is below 30 F for 3 minutes, the compressor will stop, 30 seconds later the outdoor fan will stop. In cooling mode, the indoor fan and swing motor will remain on. If the evaporator temperature is >= 50 F and the compressor is o for at least 3 minutes, the compressor will resume its normal operation state.
Overcurrent Protection
e soware will monitor the compressor current to maintain it in a safety and reliable operating range. If the total current is greater than the rating, the compressor will stop; the outdoor fan will continue to run for 30 seconds, then stop.
2) Dry Mode
Drying Process
is feature will not take the place of a dehumidier, it is intended to dry the lter and slightly cool the air. If the indoor ambient temperature is greater than the preset temperature, the unit will enter the cooling and drying mode, in which case the compressor will operate and the indoor fan will run at a low speed. When the indoor ambient temperature is at or below the preset temperature, the unit will operate in it previous running state. When the indoor ambient drops to more than 4 F below the preset temperature the compressor will stop running, then 30 seconds later the outdoor fan will stop, the indoor fan will run at low speed.
- 2 F
60 Sec 60 Sec
30 Sec 30 Sec
16
Page 17
Basic & Protection Functions
Basic Functions
3)Heating Mode
Heating Process
When the indoor ambient drops 4 F below the preset temperature, the unit will start the heating cycle. e outdoor fan, compressor and 4-way valve will operate. e indoor fan will operate in the “Cold Air Prevention” mode in which the indoor fan will have a 2 minute delay aer the call for heating. e indoor evaporator coil temperature must reach 104 F before the indoor fan will start, this will prevent cold air from discharging from the indoor coil. When the indoor evaporator coil temperature is > 104 F, the indoor fan will operate at low speed for 1 minute. With 1 minute of operation or 2 minutes of no fan operation and the indoor evaporator coil temperature is > 108 F, the indoor fan will operate at its preset condition.
If the indoor ambient temperature is < 9 F and > 2 F of the preset temperature, the unit will run in its original mode of operation.
If the compressor is running and the mode is changed from heating to cooling, the compressor will stop, the 4-way valve will be de-energized 2 minutes later, the outdoor fan will stop aer a 1 minute delay.
If the indoor ambient temperature is >= 9 F than the preset temperature, the compressor will stop and the outdoor fan will stop aer a 30 second delay. e indoor fan will continue to operate at its preset mode. e G10 technology will determine compressor frequency based on ambient temperatures.
+9 F
+ 2 F
Stop heating
17
Page 18
Basic & Protection Functions
Basic Functions
Defrost Process
You may force a defrost in heat mode by pressing the “+” and “-” buttons alternately three times within 5 seconds.
1) e unit will enter defrost when the following conditions are met: A. Outdoor ambient <= 41 F B. Compressor had accumulated more than 3 hours of operation in heating mode C. e outdoor coil <= 32 F
Note: e compressor runtime will be cleared when the outdoor ambient is > 41 F or when the compressor has started up aer changing to cooling or drying mode and defrost has nished. e runtime will not be cleared when the unit has stopped aer reaching the setpoint temperature, a protection fault or changing to fan mode.
ere are 3 perimeters used in the defrost algorithms, Outdoor ambient(T a calculated T
T
compensation
D. Aer power-up, for the rst defrost T E. T F. T
compensation
is calculated by the following:
tube > 36 F then T
outdoor
tube <= 36 F then T
outdoor
compensation = 32
compensation = 32
compensation = 37
 F
 F
 F
ambient), Outdoor tube(T
outdoor
outdoor
tube) and
2) When heating has operated continuously for 45 minutes, or accumulated for 90 minutes, the unit will enter defrost
mode in 3 minutes aer meeting any of the conditions below:
A. Outdoor ambient >= 41 F and outdoor coil <= 28 F B. 28 F <= T
C. 23 F <= T D. 14 F <= T
ambient< 41 F, “Toutdoortube -Tcompensation ≤ 21F”
outdoor
ambient < 28 F <= Toutdoortube -Tcompensation ≤ 18F”
outdoor
ambient < 23 F , T
outdoor
outdoor
tube -T
compensation
<= (T
ambient - 37 F)
outdoor
E. Toutdoorambient < 14 F, Toutdoortube -Tcompensation <= (Toutdoorambient - 37 F)
3) During defrost, if run time for the compressor does not reach 3 minutes, the defrost cycle will not start for the next
2 hours. At that time the compressor stops operation and 30 seconds later the outdoor fan will stop. 30 seconds aer this the 4-way reversing valves will de-energized. Following another 30 second delay, the compressor will increase its compressor speed for defrosting. Defrosting will last for 450 seconds or until the T
tube >= 50 F, at this temperature
outdoor
the compressor will decrease it compressor speed for 30 seconds, then will stop. In another 30 seconds the 4-way valve will energize, the 60 seconds later the compressor and outdoor fan will start. e compressor speed for defrosting will be 85hz. During Defrost mode, a “H1” will be displayed on the indoor front panel display indicating the user selected mode has been overridden and the system is performing a outdoor coil defrost operation.
4) Defrost Sequence:
When a defrost condition has been met, the compressor will stop, all expansions valves will open fully, the outdoor fan will stop 40 seconds aer the compressor stops. e 4-way valve will reverse direction (cooling mode) , then the compressor will start and enter the defrost frequency. e control, board along with ambient sensors will calculate defrost time.
5) Oil Return:
Oil return condition can be met if the unit operates at a low frequency for an extended time. e indoor display will indicate “H1” for this condition and is a normal procedure.
18
Page 19
Basic & Protection Functions
Basic Functions
Cold Air Prevention (Heating mode with compressor running)
e system guards against discharging cold air in heating mode. It will delay the indoor fan until the evaporator coil has warmed up to discharge warm, comfortable air into the room.
1) When the T
ambient < 75 F and the T
indoor
to run at low speed aer a 2 minute delay. is will reduce cold air upon heating startup. Within 2 minutes, if T
tube > 104 F, the indoor fan will run at low speed. Aer 1 minute of operation, the fan will run at the preset fan
indoor
mode. Within 1 minute of low speed operation or 2 minutes of no fan operation, with the T run at the preset mode.
tube <= 104 F with the fan in a stopped state, the indoor fan will begin
indoor
tube > 108 F, the fan will
indoor
2) If the T
ambient >= 75 F and the T
indoor
at the preset mode. Aer 1 minute of low speed operation, if the and the T
tube <= 108 F the indoor fan will run at low speed for 1 minute than run
indoor
tube > 108 F the fan will operate at its
indoor
preset mode.
Note: e T
Overcurrent and Speed Protection (Total Current = I
ambient in 1 & 2 above refers to the unit going into the heating mode coming out of defrost.
indoor
)
total
e soware will monitor the compressor current draw and adjust the compressor speed in order to maintain the inverter and compressor in a safety and reliable operating range.
A. If I B. If I C. If I D. If I
<= 13a, an increase in frequency will be allowed
total
>= 15a, increasing the frequency is not allowed.
total
>= 17a, the compressor will decrease its frequency
total
>= 19a, the compressor will stop and the indoor fan will stop aer 30 seconds.
total
4)Fan Mode
Under this mode, the fan will run at the preset speed and the outdoor fan, compressor and 4-way valve will stop.
5)Auto Mode
Auto Mode Process
Setting the auto mode will run the unit in heat or cool automatically depending on T
1)Operating Parameters A. If the T B. If the T
C. When the T
ambient >= 79 F the unit will operate in cooling mode. e set temperature is 77 F.
indoor
ambient <= 72 F the unit will operate in heat mode. e set temperature is 68 F.
indoor
ambient <= 73 F and >= 77 F, the unit will operate in the previous state. If it is energized
indoor
for the rst time, it will run in Fan mode D. In auto mode, the cooling frequency will be the same as the cooling only mode and the heating frequency will be the same as the heating only mode.
2) Protection A. In cooling operation, protection is the same as the cooling only mode B. In heating operation, protection is the same as the heating only mode
C. When the indoor ambient temperature changes, the operation mode will be automatically selected. Once started the compressor will have a 6 minute runtime.
indoor
ambient
19
Page 20
Basic & Protection Functions
Protection Functions
Common Protection Functions and Fault Displays
Coil High Temperature Protection
T
= measured temperature of outdoor coil in cooling mode, measured temperature of indoor coil in heating mode.
tube
1) Outdoor Coil High Temperature Protection - In cooling mode the soware will monitor the outdoor coil for an
abnormal high temperature condition.
A. If T B. If T
C. If T D. If T
2) Indoor Coil Temperature Protection - In heating mode the soware will monitor the indoor coil for an abnormal high
temperature condition.
A. If T B. If T
C. If T D. If T
<= 126 F, the unit will return to its original operation state
tube
>= 131 F, frequency rise is not allowed
tube
>= 136 F, the compressor will run at reduced frequency
tube
>= 144 F, the compressor will stop and the indoor fan will operate at preset speed
tube
<= 122 F, the unit will return to its original operation state
tube
>= 127 F, frequency rise is not allowed
tube
>= 133 F, the compressor will run at reduced frequency
tube
>= 140 F, the compressor will stop and the indoor fan will blow residual heat and then stop
tube
3) Compressor Discharge Temperature Protection
e soware will monitor the compressor discharge for an abnormal high temperature condition.
A. If T B. If T
C. If T D. If T
>= 208 F, frequency rise is not allowed
tube
>= 217 F, the compressor will run at reduced frequency
tube
>= 230 F, the compressor will stop
tube
<= 194 F and the compressor has been off for at least 3 minutes, the compressor will resume operation
tube
4) Compressor High Pressure Protection (Not available on 115v 9k & 12k models)
When the high pressure switch is detected for 6 seconds or more, the compressor will stop and can only be started by powering o the unit. Dirty coils, refrigerant overcharge and outdoor fan problems can cause this fault.
5) Compressor Phase-lacking Protection
If one of the compressor phases are detected open before startup, the compressor will enter phase-locking protection. e malfunction will be cleared aer 1 min, then the unit will try a restart. If an error has been detected for 6 times continuously, the compressor will lock out and will need to have power cycled. e errors will be cleared aer the compressor has run for 7 minutes continuously.
6) Module Protection (IPM)
Under module protection mode, the compressor will stop. When the compressor remains o for 3 minutes, the compressor will resume operation. If the module protection occurs six times in succession, the compressor will remain o. Power will need to be cycled to start unit. is is a thermal protection for the indoor module.
7) DC Buss Voltage Protection
e soware will monitor the DC bus voltage.
If voltage on the DC Bus is below 150 or over 420v, the compressor will stop and the outdoor fan will stop in 30 seconds. When the voltage on the DC bus returns to normal and the compressor has been o for 3 minutes, the compressor will resume its operation.
20
Page 21
Basic & Protection Functions
Protection Functions
8) Communication Fault
If the unit fails to receive correct signals for a 3 minutes, communication fault will occur and the whole system will stop and a “E6” will be displayed on the front panel of the indoor unit.
21
Page 22
Remote Buttons
Remote Control Operation
Note:
is remote control is used in other models and some features may or may not be available. Consult the owners manual for specic features for your model. ere should be no obstructions between the remote control and the indoor unit for proper operation. Keep the remote from direct sunlight or any source that generates heat, keep clean and dry. Change batteries frequently.
Note:
For detailed explanation of the functions, refer to the “Other Controls” section of this manual for your model.
Button Identication
e function and operation of each button will be explained later in this manual under Product Functions.
1. On/O button
2. Mode, press to select desired operation
3. Decrease temperature
4. Increase temperature
5. Fan, press to select fan speed
6. Swing angle button (up & down)
7. Health/Save button, not available on all models
8. Swing angle button (le & right)
9. X-Fan button
10. Temperature Display
11. Timer Button
12. Turbo Fan Button
13. Sleep Button
14. Light Button
Press “mode” and “-” buttons to switch between Fahrenheit & Centigrade
Press “-” & “+” to lock control
22
Page 23
Display Icons
15. Mode icons
16. Lock icon
17. Light icon
18. Sleep icon
19. Temperature icon
20. Up & down swing icon
21. Le & right swing icon
22. Set time icon
23. Digital display
24. Fan speed icon
Remote Control Operation
Replacing Batteries:
1. Locate the battery cover on the back of the remote.
2. Slide the cover downward.
3. Make sketch of battery polarities, then replace with two “AAA” batteries.
4. Replace cover.
23
Page 24
Product Introduction
Remote Control Functions
1)On/O
e on-o state will change with each button press.
2) Mode Setting
Each time you press this button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, FAN,and HEAT Aer energization, AUTO mode is defaulted. In AUTO mode, the set temperature will not be displayed on the LCD, and the unit will automatically select the suitable operation mode in accordance with the room temperature to make indoor room comfortable.
3)”-” Button
Press this button to decrease set temperature. Hold it down for above 2 seconds to rapidly decrease set temperature. In AUTO mode, set temperature is not adjustable.
4)”+” Button
Press this button to increase set temperature. Hold it down for above 2 seconds to rapidly increase set temperature. In AUTO mode, set temperature is not adjustable.
5) Fan
is button is used for setting fan speed in the sequence that goes from AUTO, low, medium, high, then back to auto.
6) Up & Down Swing
Press button to start or stop up & down swing function. e remote controller defaults to simple swing condition. Press + button and button at the same time at unit OFF to switch between simple swing and static swing; blinks for 2 seconds. In static swing condition, pressing louver positions. If the unit is turned o during swing operation,the louver will stop at present position.
button, the swing angle up & down
7) Health Save
Press HEALTH part of this button to turn on or o HEALTH function.(only for some model)
Pressing SAVE this button, SE is displayed and the unit goes into SAVE operation mode. Press SAVE button again to cancel SAVE function. During SAVE operation , the temperature and fan speed is not adjustable.
8) Le & Right Swing
Press button to start or stop le & right swing function. e remote controller defaults to a simple swing position.
Press + button and button at the same time at unit OFF to switch between simple swing and static swing;
blinks for two seconds
In static swing position, pressing button the swing angle will change positions.
24
Page 25
Product Introduction
Remote Control Functions
9) X-Fan
Allows fan to run aer cooling cycle to dry o the coil and inhibit the growth of bacteria and mildew. Works with “Auto” mode.
10)Temp Button
Toggles the display between set temperature, indoor temperature and outdoor temperature.
11) Timer On Button
Press TIMER button at unit ON to set TIMER OFF; HOUR OFF blinks. Press TIMER button at unite OFF to set TIMER ON; HOUR ON blinks. In this case, pressing + or - button changes time setting. Holding down either button rapidly changes time setting (time setting range 0.5 - 24 hours). Press TIMER button again to conrm setting; HOUR ON/OFF stops blinking. If there is not any operation of button within 5 seconds during HOUR ON/OFF blinking, TIMER setting will be canceled.
12) Turbo Button
Boost the cooling or heating airow, allowing the unit to reach the preset temperature in the shortest amount of time.
13) Sleep Button
Press this button to go into the SLEEP operation mode. Press it again to cancel this function. is function is available in COOL , HEAT (Only for models with heating function) or DRY mode to maintain the most comfortable temperature for you.
14) Light Button
Turns the light on the indoor display on and o.
15) Combination of “+” and “-” Buttons
Press “+” and “-” buttons simultaneously to lock or unlock the keypad
16) Combination of “Mode” and “-” Buttons
Press “Mode” and “-” buttons simultaneously will switch between Fahrenheit and Centigrade.
25
Page 26
Refrigerant Lines Connection, Evacuating and Charging
Refrigerant Lines Preparation & Connection
The refrigerant lines should be kept sealed until ready to be connected. Follow the following steps to ensure a quality leak
proof installation:
Step 1. Refrigerant Line Connection
Carefully bend and cut the tubing to prepare for aring. Use a aring tool designed for R410a, following the recommended manufacturer’s procedure. Tighten the are nut to the
indicated torque by using a spanner wrench and a toque
wrench. Connect the indoor unit rst, then the outdoor unit. Use the 3/8” to 1/2” are adapter if needed.
Note:
Over tightening are nuts may damage are connections and
may cause leaks.
Tubing Size Torque (foot-pounds) Torque (inch-pounds)
1/4” 10-13 124-159 3/8” 25-31 301-372 1/2” 36-45 434-540 5/8” 50-60 602-726
Step 2. System Leak Check
Refrigerant lines should be pressurized prior to evacuating
system to check for leaks.
Use only dry nitrogen with a pressure regulator for
pressurizing unit. Pressurize with 150 psi of dry nitrogen.
Apply soap and water to check whether the joints are leaky. A leak detector may also be used for a leakage test.
Hint:
You may want to perform leak testing and evacuation before wiring to save time, electrical connections can be completed while your vacuum pump is running.
Step 3. System Evacuation
Note: The outdoor unit contains a refrigerant charge, leave
liquid and gas valves closed.
1. After no leaks have been detected, connect a vacuum pump to the outdoor unit.
2. Connect appropriate hoses to manifold gauge, vacuum pump and unit refrigeration connections.
3. Evacuate the system until the micron gauge reads no higher than 350 microns.
4. Close valve to vacuum pump; if pressure does not rise above 500 microns after one minute, the evacuation
should be complete.
5. If it does rise, check for leaks and/or evacuate longer.
6. For refrigerant lines longer than 25 feet, refer to
installation instructions chart included with the unit installation manual for additional charge.
26
Page 27
Refrigerant Charging Procedure
Please refer to your units installation manual for proper charge. If your lineset exceeds the chart below for your model, additional charge may be required. e charge must we weighed in with a refrigerant charging scale.
You can only add additional refrigerant to a new installation. If a low or high charge is suspected, you must reclaim the refrigerant, then weigh in the correct amount per specications including any additional for long linesets. It is important to check for leaks before adding refrigerant.
1. Determine addition refrigerant charge.
e RIO single zone units contain a factory charge adequate for up to a total length of refrigerant line as indicated in the chart below. Additional refrigerant will need to be added for total lengths over the listed length. Conrm the following chart with your installation manual for additional charge amounts:
RIO09HP115V
1A
Additional Charge 0.2 oz./. 0.2 oz./. 0.2 oz./. 0.2 oz./. Max Length without
Additional Charge
Factory Charge
Max. Total Piping Length
Max. Elevation
Additional Charge
Max Length without Additional Charge
Factory Charge
Max. Total Piping Length
Max. Elevation
25 . 25 . 25 . 25 .
35.3 oz. 35.3 oz. 26.1 oz. 35.3 oz.
49 . 66 . 50 . 50 .
33 . 33 . 33 . 33 .
RIO14HP230V1ARIO24HP230V
0.2 oz./. 0.22 oz./.
25 . 25 .
45.9 oz. 54.7 oz.
50 . 50 .
33 . 33 .
RIO12HP115V
1A
1A
RIO09HP230V
1A & 1B
RIO12HP230V
1A & 1B
27
Page 28
Refrigerant Charging Procedure
2. Leak Testing
Follow the procedures for leak testing with nitrogen prior to adding charge on a new installation or existing one suspected for leaks. See preceding page.
3. Attach hoses to the unit and vacuum pump
5/16” x 1/4” adapter may be required to connect hose to port. Check to insure that the liquid and gas valves are closed on the unit. Close all valves on your gauge set, then connect the vacuum pump to your gauge set. Pump down lineset and indoor unit. is step will be repeated for all zones.
4. Zero charging scale
Place the refrigerant tank on the charging scale. Open the tank valve, turn on the scale, then zero the scale.
28
Page 29
Refrigerant Charging Procedure, cont.
5. Begin adding additional refrigerant
Charging should be completed with the unit o (not running) and through the liquid side with liquid refrigerant. If there are no ports on the liquid side, use the gas side port connection, charging with liquid.
Record the amount of additional charge for future reference.
6. Charge to the correct weight
If the scale was zeroed with the refrigerant tank on the scale, the amount added to the system will be a negative amount since it was removed from the tank. Aer the proper amount of refrigerant has been weighed in, close the manifold valve.
7. Remove refrigerant tank
Close the tank valve, then carefully remove the hose and adapter. Replace the charging port cap back on the outdoor unit valves. On new installations, open all liquid and vapor service valves.
29
Page 30
Installation
Proper installation site is vital for correct and ecient operation of the unit. Avoid the following sites where:
Strong heat sources, vapors, ammable gas or volatile liquids are emitted.
High-frequency electro-magnetic waves are generated by radio equipment, welders and medical equipment.
e air is contaminated with industrial vapors and oils.
e air contains sulfurous gas such as in hot spring zones.
Poor air quality exists.
Indoor Unit
Outdoor Unit
e air inlet and outlet should be away from any obstructions. Ensure the air will easily circulate through the entire room.
1. Select a site where the condensate can be easily routed or consider a condensate removal pump.
2. Select a place where it is out of reach of children.
3. Select a place that has adequate mounting structure, strong enough to withstand the full weight and vibration of the unit.
4. Be sure to leave enough space to allow access for routine maintenance. Refer to unit installation specications for clearances. Select a place more than 3 feet away from any TV or other electrical appliances
1. Select a suitable site where proper drainage will occur.
2. Select a site where there is sucient ventilation.
3. Select a site where there is no obstruction blocking the inlet and outlet.
4. e site should be able to withstand the full weight of the unit.
5. Try to limit expose to direct sunlight or strong winds.
6. Make sure that the outdoor unit is installed in accordance with the installations instructions, and is convenient for maintenance and repair.
7. Refer to your outdoor unit installation manual for maximum lineset lengths and heights. is could be a factor in determining outdoor location.
8. Select a place where it is out of reach of children.
9. Install Heat Pump legs to allow for proper drainage.
10. Install drain tting in bottom of outdoor unit
30
Page 31
Mounting Plate Installation
Locate and Drill Hole
Installation
1. e mounting plate should be installed horizontally and level.
2. Measure the center of the indoor unit. Please note, that depending on model, the center of the bracket may not correspond with the center of the unit.
3. Attach the mounting plate on the wall with screws.
4. Be sure that the mounting plate has been attached rmly enough to withstand approximately 132 pounds.
5. Refer to specic models for dimensional data.
1. e piping can exit the indoor unit from either side, see pictured below.
2. Drill a 2-1/2” diameter hole at a slightly downward angle to the outdoor side.
3. Note: e outdoor hole should be approximately 1/4” lower than the indoor hole.
4. Insert the piping-hole sleeve into the hole to prevent the piping and wiring from being damaged when passing through the hole.
31
Page 32
Install Drain Hose
Install Line Set
Installation
1. Connect the drain hose to the outlet pipe of the indoor unit using appropriate connections.
2. Insulate the condensate to prevent condensation.
3. Fasten the condensate, lineset and wring together to prevent damage and movement. Slant the drain hose downward for smooth drainage.
1. Install lineset and wiring from the outside through the wall sleeve.
2. Bend the indoor lineset. Note: a tube bender will speed up the process.
3. Carefully remove are nut from indoor coil. Listen for holding charge from indoor unit. No charge may indicate a leak and should be tested.
4. Use a aring tool if necessary to create the are, connect tubing tightening to the torque listed below.
Tubing Size Torque (foot-pounds) Torque (inch-pounds)
1/4” 10-13 124-159 3/8” 25-31 301-372 1/2” 36-45 434-540 5/8” 50-60 602-726
32
Page 33
Pressure and Leak Test
Installation
1. Use only dry nitrogen with a pressure regulator for pressurizing unit. Pressurize with 150 psi of dry nitrogen.
2. Apply soap and water to check whether the joints are leaky. A leak detector can also be applied for a leakage test.
Hint: You may want to perform leak testing and evacuation before wiring to save time, electrical connections can be completed while your vacuum pump is running.
Evacuating the System
Note: e outdoor unit contains a refrigerant charge, leave liquid and gas valves closed.
1. Aer no leaks have been detected, connect a vacuum pump to the outdoor unit.
2. Connect appropriate hoses to manifold gauge, vacuum pump and unit refrigeration connections.
3. Evacuate the system until the micron gauge reads no higher than 350 microns.
4. Close valve to vacuum pump; if pressure does not rise above 500 microns aer one minute, the evacuation should be complete.
5. If it does rise, check for leaks and/or evacuate longer.
6. For refrigerant lines longer than 25 feet, refer to installation instructions chart included with the unit installation manual for additional charge.
33
Page 34
Connect the Outdoor Wiring
115 volt unit
shown
Installation
115 Volt unit
1. Remove the handle on the right side plate of the outdoor unit.
2. Connect wiring from indoor unit to 1,2,3 & ground, being careful to match color code of indoor connections. Repeat this for each indoor unit.
3. Connect power wiring form outdoor disconnect to N, L and ground.
4. Check all connections to tightness.
5. Reinstall the cover/handle.
Note: Follow all local electrical codes for electrical wiring.
240 Volt unit
1. Remove the handle on the right side plate of the outdoor unit.
2. Connect wiring from indoor unit to 1,2,3 & ground, being careful to match color code of indoor connections. Repeat this for each indoor unit.
3. Connect power wiring form outdoor disconnect to L1, L2 and ground.
4. Check all connections to tightness.
5. Reinstall the cover/handle.
Note: Follow all local electrical codes for electrical wiring.
34
Page 35
Filter Maintenance and Emergency Operation
Cleaning Air Filter
1. Li open the front panel as shown on the picture
2. e rst stage lter can be cleaned with a vacuum cleaner or by washing with a mild soap and < 113º F water.
3. e 2nd lter can be washed, use a vacuum cleaner to clean any dust, lint, etc.
4. roughly dry lters before replacing in unit.
1st Stage Filter
Removable 2nd Stage Filter
35
Page 36
9K, 12K 115V
Symbol Color Symbol Symbol Color Symbol
WH White BN Brown
UE Ye l low BU Blue
RD Red BK Black
YEGN Yellow/Green Protective Earth
Electrical Schematics
Indoor Board
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
36
Page 37
9K, 12K 115V
Symbol Parts Name Symbol Parts Name
N L Neutral Wire, 110v Live Wire WH White 4YV 4-Way Valve YE Yell o w EKV Electric Expansion Valve RD Red
L Reactor BN Brown
COMP Compressor BU Blue
SAT Overload YEGN Yellow/Green
Electrical Schematics
Outdoor Unit
Protective Earth BK Black
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
37
Page 38
9K, 12K 230V
Electrical Schematics
Indoor Board
9 & 12k
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
38
Page 39
9K, 12K 230V
Outdoor Unit
Electrical Schematics
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
39
Page 40
18K Indoor Unit
Electrical Schematics
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
40
Page 41
24K Indoor Unit
Electrical Schematics
41
Page 42
24K Indoor Unit
Electrical Schematics
42
Page 43
18K, 24K
Electrical Schematics
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
43
Page 44
18K, 24K
Electrical Schematics
ese circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
44
Page 45
AP-1 Circuit Board
Compressor Heater Band
N2 - Voltage
Terminal
4-Way Valve
Printed Circuit Boards
Compressor Wires
ermistor wires
45
Page 46
Troubleshooting Indoor Components
Indoor Fan Motor Troubleshooting
To check the condition of the indoor fan motor voltage measurements and resistance measurements can be compared to the following charts. Care must be taken when checking voltage measurements, all wires and terminals must be isolated for safety. Resistance measurements must be taken with power o and “PG” connector removed from the circuit board.
e following chart indicates approximate voltage measurements, readings may vary slightly depending on models and should be used as a reference only. Voltages should be taken with unit running.
PG Wire Connector Low Medium High Turbo
Brown - White 130 vac 147 vac 161 vac 225 vac
Brown - Red 148 vac 184 vac 210 vac 340 vac
White - Red 123 vac 150 vac 180 vac 205 vac
e following chart indicates approximate resistance measurements, readings may vary slightly depending on models and should be used as a reference only. Turn power o and remove connector from circuit board before reading measurements.
PG Wire Connector Resistance (ohms)
Brown - White 97 Ω
Brown - Red 174 Ω
White - Red 78 Ω
46
Page 47
Troubleshooting Indoor Components
Step Motor Troubleshooting
To check the condition of the indoor step (swing) motor resistance measurements may be compared to the following chart. Resistance measurements must be taken with power o and the connector removed from the board. e following charts indicate approximate readings and may vary with dierent models. Turn power o and remove connector from circuit board.
Connector Blue Pink Yel l ow Orange Red
Blue 397 Ω 402 Ω 400 Ω 198 Ω Pink 400 Ω 402 Ω 198 Ω
Yell o w 402 Ω 198 Ω
Orange 198 Ω
Red
47
Page 48
Troubleshooting Outdoor Components
EEV Troubleshooting
Cooling Mode
Input
To check the operation of the EEV Valve in cooling mode, using a digital thermometer record the temperature of the input line and the output line of the valve as indicated in the picture above. With the compressor running, the input side of the valve should have a higher reading then the output side indicating that the valve is metering. If the temperature readings are the same, the valve is fully open and the valve is not metering. Since the pressures and frequency are controlled by the G10 technology of the outdoor circuit board, there are no pressure checks that can be made.
Heating Mode
Output
InputOutput
To check the operation of the EEV Valve in heating mode, using a digital thermometer record the temperature of the input line and the output line of the valve as indicated in the picture above. With the compressor running, the input side of the valve should have a higher reading then the output side indicating that the valve is metering. If the temperature readings are the same, the valve is fully open and the valve is not metering. Since the pressures and frequency are controlled by the G10 technology of the outdoor circuit board, there are no pressure checks that can be made.
Resistance readings of EEV valve with wire plug disconnected from circuit board. Power to unit should be o when making resistance readings. Readings below are approximate values and may vary slightly with dierent outdoor models.
EEV Ω Orange Red Yel lo w Black Blue
Orange 94.6 Ω 94.8 Ω 94.4 Ω 47.0 Ω
Red 94.7 Ω 94.4 Ω 47.5 Ω
Yell o w 94.6 Ω 47.7 Ω
Black 47.4 Ω
Blue
48
Page 49
Troubleshooting Outdoor Components
4-Way Valve Troubleshooting
Cooling Mode
To Accumulator
To Condenser
Suction Line
Compressor
Discharge
Checking the 4-way valve in cooling mode requires the measurement of 4 readings. First record the temperature of the compressor discharge tubing, secondly record the temperature of the tubing going to the condenser. ere should be no more than a 10 degrees dierence between the two readings.
Coil
Heating Mode
To Accumulator
To Condenser
Suction Line
Compressor
Discharge
Checking the 4-way valve in heating mode requires the measurement of 4 readings. First record the temperature of the compressor discharge tubing, secondly record the temperature of the suction line tube. ere should be no more than a 10 degrees dierence between the two readings.
Coil
e next set of readings will require recording the temperature of the tubing going to the suction line and the temperature of the tubing going to the accumulator. Again, if there should be less than 10 degrees dierence between these readings.
A temperature reading higher than 10 degrees may indicate a leaky valve (not fully shied) or a blockage in the valve.
4-Way valve solenoid resistance check:
Be sure all power is o to the unit. Remove the plug connecting the 4-way vale to the circuit board. Check the resistance with an ohmmeter. e reading should indicate 1.8k Ω. If the reading is infinite, replace the solenoid coil.
e next set of readings will require recording the temperature of the tubing going to the condenser coil and the temperature of the tubing going to the accumulator. Again, if there should be less than 10 degrees dierence between these readings.
A temperature reading higher than 10 degrees may indicate a leaky valve (not fully shied) or a blockage in the valve.
49
Page 50
Troubleshooting Outdoor Components
Temperature Sensor Check
Temperature
Sensor
Using a glass of ice water, place the sensor into the glass with a digital thermometer. Wait a few minutes for the reading to stabilize. Compare the readings to the sensor tables in Appendix “A”, it the reading are not comparable, replace the sensor. When replacing the sensor, be sure to fasten the sensor securely if it is attached to a tube.
Temp
(ºC) 0 32.0 49.02 52 125.6 4.986 104 219.2 0.898 1 33.8 46.6 53 127.4 4.802 105 221.0 0.873 2 35.6 44.31 54 129.2 4.625 106 222.8 0.848 3 37.4 42.14 55 131.0 4.456 107 224.6 0.825 4 39.2 40.09 56 132.8 4.294 108 226.4 0.802 5 41.0 38.15 57 134.6 4.139 109 228.2 0.779 6 42.8 36.32 58 136.4 3.99 110 230.0 0.758 7 44.6 34.58 59 138.2 3.848 111 231.8 0.737 8 46.4 32.94 60 140.0 3.711 112 233.6 0.717 9 48.2 31.38 61 141.8 3.579 113 235.4 0.697
Temp
(ºF)
Resistance
(k)
Temp
(ºC)
Temp
(ºF)
Resistance
(k)
Temp
(ºC)
Temp
(ºF)
Resistance
(k)
50
Page 51
Troubleshooting Outdoor Components
Compressor Windings
Red, Yellow & Blue Wires
Compressor Winding Resistance Check:
Compressor Windings
Slightly depress tab for
easy removal
Remove the compressor wires from the AP1 circuit board. e wires red to yellow, yellow to blue & red to blue should have readings from 2 - 4 ohms. ere should be no reading from any wire to chassis ground. If the readings between the windings dier greatly, the windings are bad. If there is a reading from any wire to the chassis, there is leakage in the windings.
Reactor
e reactor lters out electrical noise and transient voltage spikes to the control board. ere will be a reading of less than 1 Ω after the wires are removed. There should be no reading from either reactor terminal to ground.
51
Page 52
Troubleshooting Outdoor Components
Outdoor Fan Motor
Outdoor Motor Winding Resistance Check:
Disconnect power to the unit, all reading are made with no power and fan motor wires disconnected from circuit board. e chart below will indicate the approximate resistance values in ohms. is motor is a brush-less DC motor, readings may vary slightly for dierent models. Plugging a known good motor in the board would provide a quick troubleshooting technique.
Motor Leads Red Yell ow White
Red 75 Ω 74 Ω
Yell o w 75 Ω 74 Ω
White 74 Ω 74 Ω
52
Page 53
Troubleshooting Outdoor Components
Compressor Crankcase Heater Check
Compressor Crankcase Heater Resistance Check:
Unplug the wire connector from the circuit board. e resistance should read approximately 2.15K ohms. ere should be no reading from either wire to ground. If readings vary from these measurements, replace the heater.
Refrigerant Temperature Sensors
ese sensors are a negative coecient thermistor that decrease in resistance as the temperature increases. e sensors are used to monitor the temperature of the refrigerant. Please refer to the troubleshooting section for error codes generated by a sensor fault. Temperature sensors and locations will vary depending on models.
53
Page 54
Troubleshooting Outdoor Components
Liquid Line Temperature Sensors
ese sensors are a negative coecient thermistor that decrease in resistance as the temperature increases. e sensors are used to monitor the temperature of the refrigerant leaving the EEV to maintain a correct superheat operation. Please refer to the troubleshooting section for error codes generated by a sensor fault. Temperature sensors and locations will vary depending on models.
54
Page 55
Troubleshooting Outdoor Components
Exhaust Temperature Sensor
e exhaust temperature sensor monitors the refrigerant discharge temperature and will send information to the inverter control board for system operation. e following actions can occur: Exhaust Temperature > 208 F - Compressor will not rise above present level Exhaust Temperature > 217 F - Compressor will run at reduced frequency Exhaust Temperature < 194 F - Compressor o for 3 minutes minimum, the compressor will restart
Error Code F5 will be generated if the sensor is open or shorted. Please refer to the troubleshooting section for more detailed information.
55
Page 56
Troubleshooting Outdoor Components
Outdoor Temperature Sensor
is sensor is a negative coecient thermistor that will decrease in resistance as the temperature increases. is sensor will monitor the temperature of the outdoor air. e reading will be used by the inverter board to adjust frequency calculations.
Error Code F3 will be generated if the sensor is open or shorted. Please refer to the troubleshooting section for more detailed information.
56
Page 57
Fault Displays
Troubleshooting Faults
Observe all electrical precautions during service of indoor and outdoor units. During Static service (serving nit without power applied), wait 10 minutes before service units. During dynamic service (servicing while unit is energized), be sure unit is properly grounded.
Troubleshooting procedure:
1. Conrmation
2. Judgment of ashing LED of Indoor/Outdoor unit
3. Check the part associated with the fault code.
Precautions:
A large capacity electrolytic capacitor is used in the outdoor unit controller (inverter). Capacitor should be discharged before attempting to work on board. Electrical shock hazard will be present even aer unit is disconnecte3d from power source.
Conrmation:
Conrm that the unit has proper voltage within 10% of rated value.
Observe ashing LED of indoor/outdoor unit for diagnostic information.
4 Minutes aer protection stop of motor, the malfunction error code is shown. In other situations, the malfunction will be displayed by pressing the light button for 6 times within 4 seconds.
57
Page 58
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
1 High pressure
protection of system
2 Antifreezing
protection
3 System block
or refrigerant leakage
4 High discharge
temperature protection of compressor
E1 OFF 3s
and blink once
E2 OFF 3S
and blink twice
E3 OFF 3S
and blink 3 times
E4 OFF 3S
and blink 4 times
OFF 3S and blink 3 times
OFF 3S and blink 7 times
OFF 3S and blink 9 times
During cooling and drying operation, except indoor fan operates, all loads stop operation. During heating operation, the complete unit stops.
During cooling and drying operation, comporessor and outdoor fan stop while indoor fan operates.
e Dual-8 Code Display will show E3 until the low pressure switch stop operation.
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heatin operation, all loads stop
Possible reasons:
1. Refrigerant was superabundant; 2. Poor heat exchange (including lth blockage of heat exchanger and bad radiating environment); Ambient temperature is too high.
1. Poor air-return in indoor unit; 2. Fan speed is abnormal; 3. Evaporator is dirty
1. Low-pressure protection; 2. Low pressure protection of system; 3. Low pressure protection of compressor
Please refer to the malfunction analysis (discharge protection, overload).
5 Overcurrent
protection
E5 OFF 3S
and blink 5 times
58
OFF 3S and blink 5 times
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heatin operation, all loads stop
1. Supply voltage is unstable; 2. Supply voltage is too low and load is too high; 3. Evaporator is dirty.
Page 59
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
7 High
temperature resistant protection
8 EEPROM
malfunction
9 Limit/decrease
frequency due to high temperature of module
10 Malfunction
protection of jumper cap
11 Gathering
refrigerant
E8 OFF 3S
and blink 8 times
EE OFF
3S and blink 15 times
EU OFF
3S and blink 6 times
OFF 3S and blink 6 times
C5 OFF 3S
and blink 15 times
F0 OFF 3S
and blink 1 time
OFF 3S and blink 1 time
OFF 3S and blink 6 times
OFF 3S and blink 11 times
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heatin operation, all loads stop
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heatin operation, all loads stop
All loads operate normally, while operation frequency for compressor is decreased
Wireless remote receiver and button are eective, but can not dispose the related command
When the outdoor unit receive signal of Gathering refrigerant, the system will be forced to run under cooling mode for gathering refrigerant
Refer to the malfunction analysis (overload, high temperature resistant).
Replace outdoor control panel AP1
Discharging aer the complete unit is de-energized for 20 mins, check whether the thermal grease on IPM module of outdoor control panel AP1 is sucient and whether the radiateor is inserted tightly. If its no use, please replace control panel AP1.
1. No jumper cap insert on mainboard;
2. Incorrect insert of jumper cap; 3. Jumper cap damaged; 4. Abnormal detecting circuit of mainboard.
Nominal cooling mode
59
Page 60
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
12 Indoor
ambient temperature sensor is open/ short circuited
13 Indoor
evaporator temperature sensor is open/ short circuited
14 Outdoor
ambient temperature sensor is open/ short circuited
15 Outdoor
condenser temperature sensor is open/ short circuited
F1 OFF
3S and blink 1 time
F2 OFF
3S and blink twice
F3 OFF
3S and blink 3 times
F4 OFF
3S and blink 4 times
OFF 3S and blink 6 times
OFF 3S and blink 5 times
During cooling and drying operation, indoor unit operates while other loads will stop; during heating operation, the complete unit will stop operation
AC stops operation once reaches the setting temperature. Cooling, drying: internal fan motor stops operation while other loads stop operation; heating: AC stop operation
During cooling and drying operating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
During cooling and drying operating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
1. Loosening or bad contact of indoor ambient temp sensor and mainboard terminal;
2. Components in mainboard fell down leads short circuit; 3. Indoor ambient temp sensor damaged (check with sensor resistance value chart); 4. Mainboard damaged.
1. Loosening or bad contact of indoor evaporator temp sensor and mainboard terminal;
2. Components on the mainboard fall down leads short cirtui; 3. Indoor evaporator temp sensor damaged (check temp sensor value chart for testing) 4. Mainboard damaged
Outdoor temperature sensor hasn’t been connected well is damaged. Please check it by referring to the resistance table for temperature sensor
Outdoor temperature sensor hasn’t been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor
60
Page 61
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
16 Outdoor
discharge temperature sensor is open/ short circuited
17 Limit/decrease
frequency due to overload
18 Decrease
frequency due to overcurrent
19 Decrease
frequency due to high air discharge
20 Limit/decrease
frequency due to antifreezing
21 Voltage for DC
bus-bar is too high
F5 OFF
3S and blink 5 times
F6 OFF
3S and blink 6times
F8 OFF
3S and blink 8times
F9 OFF
3S and blink 9 times
FH OFF
3S and blink 2 times
PH OFF
3S and blink 11 times
OFF 3S and blink 2 times
OFF 3S and blink 7 times
OFF 3S and blink 3 times
OFF 3S and blink 1 time
OFF 3S and blink 13 times
OFF 3S and blink twice
OFF 3S and blink 4 times
During cooling and drying operation, compressor will stop aer operating for about 3 mins, while indoor fan will operate; During heating operation, the complete unit will stop aer operating for about 3 mins
All loads operate normally, while operation frequency for compressor is decreased
All loads operate normally, while operation frequency for compressor is decreased
All loads operate normally, while operation frequency for compressor is decreased
All loads operate normally, while operation frequency for compressor is decreased
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
1. Outdoor temperature sensor hasn’t been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor;
2. e head head of temperature sensor hasn’t been inserted into the copper tube
Refer to the malfunction analysis (overload, high temperature resistant)
e input supply voltage is too low; System pressure is too high and overload
Overload or temperature is too high; Refrigerant is insucient; Malfunction of electric expansion valve (EKV)
Poor air-return in indoor unit or fan speed is too low
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 265VAC, turn on the unit aer the supply voltage is increased to the normal range; 2. If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
61
Page 62
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
22 Voltage of DC
bus-bar is too low
23 Compressor
Min frequence in test state
24 Compressor
rated frequence in test state
25 Compressor
maximum frequence in test state
26 Compressor
intermediate frequence in test state
27 Overcurrent
protection of phase current for compressor
28 Charging
malfunction of capacitor
PL OFF
3S and blink 21 times
OFF 3S and blink 12 times
During cooling and drying operation, compressor will stop while indoor fan operate; During heating operation, the complete unit will stop
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 265VAC, turn on the unit aer the supply voltage is increased to the normal range; 2. If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
P0 (during (during Showing durin min
cooling or min heating test
P1 (during (during Showing during
nominal cooling or nominal heating test
P2 (during (during Showing during max
cooling or max heating test
P3 (during (during Showing during middle
cooling or middle heating test
P5 OFF
3S and blink 15 times
PU OFF
3S and blink 17 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operationg, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will
Refer to the malfunction analysis (IPM protection, loss of synchronism preoteciton and overcurrent protection of phase current for compressor
Refer to the part three
- charging malfunction analysis of capacitor
operate; During heating operationg the complete unit will stop
62
Page 63
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
29 Malfunction
of module temperature sensor circuit
30 Module high
temperature protection
31 Decrease
frequency due to high temperature resistant during heating operation
32 Static
dedusting protection
33 Overload
protection for compressor
34 System is
abnormal
P7 OFF
3S and blink 18 times
P8 OFF
3S and blink 19 times
H0 OFF
3S and blink 10 times
H2 OFF
3S and blink twice
H3 OFF
3S and blink 3 times
H4 OFF
3S and blink 4 times
OFF 3S and blink 8 times
OFF 3S and blink 6 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operationg the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operationg the complete unit will stop
All loads operate normally, while operation frequency for compressor is decreased
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operationg the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Replace outdoor control panel AP1
Aer the complete unit is de-energized for 20 mins, check whether the thermal grease on IPM Module of outdoor control panel AP1 is sucient and whether the radiator is inserted tightly. If its no use, please replace control panel AP1.
Refer to the malfunction analysis (overload, high temperature resistant)
1. Wiring terminal OVC-COMP is loosened. In normal state, the resistance for this terminal should be less than 1ohm; 2. Refer to the malfunction analysis (discharge protection, overload)
Refer to the malfunction analysis (overload, high temperature resistant)
63
Page 64
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
35 IPM protection H5 OFF
3S and blink 5 times
36 Module
temperature is too high
H5 OFF
3S and blink 5 times
37 Internal motor
(fan motor) do not operate
H6 OFF 3S
and blink 11 times
38 H7 OFF
3S and blink 7 times
39 PFC protection HC OFF
3S and blink 6 times
40 Outdoor DC
fan motor malfunction
L3 OFF 3S
and blink 23 times
OFF 3S and blink 4 times
OFF 3S and blink 10 times
OFF 3S and blink 14 times
OFF 3S and blink 14 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Internal fan motor, external fan motor, compressor and electric heater stop operationg, guide louver stops and present location.
During cooling and drying operation, compressor will stop while indoor fan operate; During heating operationg, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan operate; During heating operationg, the complete unit will stop operation.
Outdoor DC fan motor malfunction lead to compressor stop operation.
Refer to the malfunction analysis (IPM protection, loss of syncrhonism protection and overcurrent protection of phase current for compressor.
1. Bad contact of DC motor feedback terminal; 2. Bad contact of DC motor control end; 3. Fan motor is stalling; 4. Motor malfunction;
5. Malfunction of mainboard rev detecting circuit
Refer to the malfunction analysis (IPM protection, loss of syncrhonism protection and overcurrent protection of phase current for compressor.
Refer to the malfunction analysis (IPM protection, loss of syncrhonism protection and overcurrent protection of phase current for compressor.
DC fan motor malfunction or system blocked or the connector loosed
64
Page 65
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
41 Power
protection
L9 OFF 3S
and blink 20 times
42 Indoor unit
and outdoor unit doesn't
LP OFF 3S
and blink 19 times
match
43 Failure start-up LC OFF
3S and blink 11 times
44 Malfunction of
phase current detection circuit for
U1 OFF
3S and blink 13 times
compressor
45 Malfunction
of voltage dropping for DC bus-bar
46 Malfunction
of complete units current detection
U3 OFF
3S and blink 20 times
U5 OFF
3S and blink 13 times
OFF 3S and blink 9 times
OFF 3S and blink 16 times
Compressor stop operation and Outdoor fan motor will stop 30S later, 3 minutes later fan motor and compressor will restart
Compressor and outdoor fan motor can't work
During cooling and drying operation, compressor will stop while indoor fan operate; During heating operationg, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
To protect the electronical components when detect high power
Indoor unit and outdoor unit doesn't match
Refer to the malfunction analysis
Replace outdoor control panel AP1
Supply voltage is unstable
eres circuit malfunction on outdoor units control panel AP1. Please replace the outdoor unit control panel AP1.
65
Page 66
No.
Malfuntiuon
Name
Fault Displays
9,000 and 12,000 btuh units
Display Method of Indoor Unit Display Method of Outdoor Unit
Indicator has 3 kinds of display status and during blinking, ON
0.5ws and OFF 0.5s
Yellow
Indicator
Red
Indicator
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
A/C Status Possible Causes
Green
Indicator
47 e four-
way valve is abnormal
U7 OFF
3S and blink 20 times
48 Zero-crossing
malfunction of outdoor unit
49 Frequency
limiting (power)
U9 OFF 3S
and blink 18 times
OFF 3S and blink 13 times
50 Compressor
running
OFF 3S and blink once
51 e
temperature for turning on the unit is
OFF 3S and blink 8 times
reached
52 Frequency
limiting (module temperature)
OFF 3S and blink 11 times
53 Normal OFF
0.5S and blink once
54 Defrosting OFF
3S and blink once
OFF
0.5S and blink twice
(during
If this malfunction occurs during heating operationg, the complete unit will stop operation
During cooling operation, compressor will stop while indoor fan will operate; during heating, the complete unit will stop operation.
Defrosting will occur in heating mode. Compressor will operate while indoor fan will stop operation.
1. Supply voltage is lower than AC175V; 2. Wiring terminal 4V is loosened or broken, 3. 4V is damaged, please replace 4V
Replace outdoor control panel AP1
It’s the normal state.
66
Page 67
Fault Displays
9,000 and 12,000 btuh units
If malfunction occurs, corresponding code will display and the unit will resume normal until protection or malfunction disappears.
Indoor Display of
outdoor unit
Compressor starts (normal)
Defrosting (normal display of indoor unit)
Anti-freezing protection (normal disply of
indoor unit)
IPM Protection
Overcurrent Protection
Overload Protection
Exhaust Protection
Overload protection of compressor
Cooling (dehumidfy) or heating >= dropped
frequency current
Exhaust temp. >= dropped frequency
temperature
Yellow indicator blinks once
Yellow indicator blinks twice
Yellow indicator blinks 3 times
Yellow indicator blinks 4 times
Yellow indicator blinks 5 times
Yellow indicator blinks 6 times
Yellow indicator blinks 7 times
Yellow indicator blinks 8 times
Red indicator blinks once
Red indicator blinks twice
T
Outdoor condenser temp sensor malfunction
Outdoor ambient temp sensor malfunction
Outdoor exhaust temp sensor malfunction
Tube temp. >= dropped frequency
temperature
<= dropped frequency temperature
tube-in
Starting at temperature does not reach
Communication is not normal
Red indicator blinks 3 times
Red indicator blinks 4 times
Red indicator blinks 5 times
Red indicator blinks 6 times
Red indicator blinks 7 times
Red indicator blinks 8 times
Green indicator does not blink
67
Page 68
Malfunction
Name
High pressure protection of system
Anti-freezing protection
High discharge temperature protection of compressor
Overcurrent protection
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Dual-8
Code
Display
D1
E2
D4
E5
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
OFF 3s
and blink
once
OFF 3s
and blink
twice
OFF 3s
and blink
4 times
OFF 3s
and blink
5 times
Cooling
LED
Heating
LED
Indicator has 3 kinds of display status and
during blinking, ON 0.5s and OFF 0.5s
D40/D5 D41/D6 D42/D16
o
n o n o
n o n
o n o
D43/
D30
A/C Status Malfunctions
During cooling and drying operation, except indoor fan operates, all loads stop operation. During heating operation the complete stops
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including lth blockage of heat exchanger and bad radiating environment); Ambient temperature is too high.
1. Poor air return in indoor unit,
2. Fan speed is abnormal, 3. Evaporator is dirty
Please refer to the malfunction analysis (discharge protection overload)
1. Supply voltage is unstable, 2. Supply voltage is too low and load is too high,
3. Evaporator is dirty
o = OFF n = Illuminated = Blink
68
Page 69
Malfunction
Name
Communication Malfunction
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Dual-8
Code
Display
E6
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
OFF 3s
and blink
6 times
Cooling
LED
Heating
LED
Indicator has 3 kinds of display status and
during blinking, ON 0.5s and OFF 0.5s
D40/D5 D41/D6 D42/D16 D43/D30
o o o
A/C Status Malfunctions
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop
Refer to the corresponding malfunction analysis
Circuit PG motor (indoor fan) has circuit malfunction by zero cross detection
PG motor (indoor fan motor) does not operate
High temperature resistant protection
o = OFF n = Illuminated = Blink
U8
H6
E8
OFF 3s
and blink
17 times
OFF 3s
and blink
11 times
OFF 3s
and blink
8 times
n o n n
Operation of remote controller or control panel is available, but the unit wont act
e complete unit will stop operation
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop
Control board is damaged.
Poor connection for PGF in circuit diagram, Malfunction of indoor units control panel AP1, Malfunction of indoor units motor M1
Refer to the corresponding malfunction analysis
69
Page 70
Malfunction
Name
Malfunction protection of jumper cap
Indoor ambient temperature sensor is open/short circuit
Indoor evaporator temperature sensor is open/short circuited
Outdoor ambient temperature sensor is open/short circuited
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
D40/D5D41/D6D42/
o o n
Dual-8
Code
Display
C5
F1
F2
F3
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
OFF 3s
and blink
15 times
Cooling
LED
OFF 3s
and blink
once
OFF 3s
and blink
twice
OFF 3s
and blink
3 times
Heating
LED
D16
D43/
D30
A/C Status Malfunctions
e complete unit will stop operation
During cooling and drying operation, indoor unit operates while other loads will stop during heating operation, the complete unit will stop
During cooling and drying operation, indoor unit will operate while other loads will stop; During heating operation, the complete unit will stop operation
During cooling and drying operating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
Poor connection for the jumper cap on indoor units, control panel AP1, please reinsert or replace the jumper cap
1. Room temperature sensor hasn’t been connected well with indoor units control panel AP1 (refer to the wiring diagram for indoor unit), 2. Room temperature sensor is damaged (please refer to the resistance table of temperature sensor)
1. Room temperature sensor hasn't been connected well with indoor units control panel AP1 (refer to the wiring diagram for indoor unit) 2. Room temperature sensor is damaged (please refer to the resistance table of temperature sensor)
Outdoor temperature sensor hasn't been connected well or is damaged. Please check it by referring to the resistance table for the temperature sensor.
o = OFF n = Illuminated = Blink
70
Page 71
Malfunction
Name
Outdoor condenser temperature sensor is open/ short circuited
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display
status and during blinking, ON 0.5s
and OFF 0.5s
D40/D5D41/D6D42/
D16
o o o
Dual-8
Code
Display
F4
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
OFF 3s
and blink
4 times
Heating
LED
D43/
D30
A/C Status Malfunctions
During cooling and drying operating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
Outdoor temperature sensor hasn't been connected well or is damaged. Please check it by referring to the resistance table for the temperature sensor.
Outdoor condenser temperature sensor is open/ short circuited
Limit/decrease frequency due to overload
Decrease frequency due to overcurrent
F5
F6
F8
OFF 3s
and blink
5 times
OFF 3s
and blink
6 times
OFF 3s
and blink
8 times
o o
n o
n n o n
During cooling and drying operation, compressor will stop aer operating for about 3 mins, while indoor fan will operate; During heating operation, the complete unit will stop aer operating for about 3 mins
All loads operate normally, while operating frequency for compressor is decreased
All loads operate normally, while operating frequency for compressor is decreased
1. Outdoor temperature sensor hasn't been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor. 2. e head of temperature sensor hasn't been inserted into the copper tube
Refer to the malfunction analysis (overload, high temperature resistant)
e input supply voltage is too low, system pressure is too high and overload
o = OFF n = Illuminated = Blink
71
Page 72
Malfunction
Name
Decrease frequency due to high air discharge
Voltage for DC bus-bar is too high
Malfunction of complete units current detection
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and OFF
0.5s
D40/D5D41/D6D42/
D16
n n o o
o n o
o n n
Dual-8
Code
Display
F9
PH
U5
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
OFF 3s
and blink
9 times
OFF 3s
and blink
11 times
OFF 3s
and blink
13 times
Heating
LED
D43/
D30
A/C Status Malfunctions
All loads operate normally, while operating frequency for compressor is decreased
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operating the complete unit will stop operation
During cooling and drying operating, the compressor will stop while indoor fan will operate; During heating operation the complete unit will stop operating
Overload or temperature is too high, refrigerant is insucient, Malfunction of electric expansion valve (EEV)
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 265VAC, turn on the unit aer the supply voltage is increased to the normal range. 2. If the AC input is normal measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
eres circuit malfunction on outdoor units control panel AP1, please replace the outdoor units control panel AP1
o = OFF n = Illuminated = Blink
72
Page 73
Malfunction
Name
Malfunction of complete units current detection
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display status and during blinking, ON
0.5s and OFF 0.5s
D40/D5D41/D6D42/
D16
o n n
Dual-8
Code
Display
U5
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
OFF 3s
and blink
13 times
Heating
LED
D43/
D30
During cooling and drying operating, the compressor will stop while indoor fan will operate; During heating operation the complete unit will stop operating
A/C Status Malfunctions
eres circuit malfunction on outdoor units control panel AP1, please replace the outdoor units control panel AP1
Overcurrent protection of phase current for compressor
Defrosting H1
Static dedusting protection
Overload protection for compressor
o = OFF n = Illuminated = Blink
P5
H2
H3
OFF 3s
and blink
15 times
OFF
3s and
blink
once
OFF
3s and
blink twice
OFF
3s and
blink 3
times
o o o
o o
During cooling and drying operating, the compressor will stop while indoor fan will operate; During heating operation the complete unit will stop operating
Defrosting will occur in heating mode. Compressor will operate while indoor fan will stop operation
/ /
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
It’s the normal state
1. Wiring terminal OVC-COMP is loosened. In normal state, the resistance for this terminal should be less than 1ohm 2. Refer to the malfunction analysis (discharge protection, overload)
73
Page 74
Malfunction
Name
System is abnormal
IPM protection H5
PFC protection HC
Desynchronizing of compressor
Dual-8
Code
Display
H4
H7
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
Heating
LED
OFF
3s and
blink 4
times
OFF
3s and
blink 5
times
OFF
3s and
blink 6
times
OFF
3s and
blink 7
times
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and OFF
0.5s
D40/D5D41/D6D42/
D16
n o n n
o o n
o n
o n
D43/
D30
A/C Status Malfunctions
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (overload, high temperature resistant)
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor)
Refer to the malfunction analysis
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor)
o = OFF n = Illuminated = Blink
74
Page 75
Malfunction
Name
Decrease frequency due to high temperature resistant during heating operation
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display
status and during blinking, ON 0.5s
and OFF 0.5s
D40/D5D41/D6D42/
D16
n o
Dual-8
Code
Display
H0
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
Heating
LED
OFF
3s and
blink 10
times
D43/
D30
A/C Status Malfunctions
All loads operate normally, while operation frequency for compressor is decreased
Refer to the malfunction analysis (overload, high temperature resistant)
Failure startup LC
Malfunction of phase current detection circuit for compressor
EEPROM malfunction
Charging malfunction of capacitor
o = OFF n = Illuminated = Blink
U1
EE
PU
OFF
3s and
blink 11
times
OFF
3s and
blink 13
times
OFF
3s and
blink 15
times
OFF
3s and
blink 17
times
o o
o n o
o o o n
o n o n
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Refer to the malfunction analysis
Replace outdoor control panel AP1
Replace outdoor control panel AP1
Refer to the part three--charging malfunction analysis of capacitor
75
Page 76
Malfunction
Name
Malfunction of module temperature sensor circuit
Module high temperature protection
Malfunction of voltage dropping for DC bus-bar
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and OFF
0.5s
D40/D5D41/D6D42/
D16
o o n
n o n
o n n n
Dual-8
Code
Display
P7
P8
U3
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
Heating
LED
OFF
3s and
blink 18
times
OFF
3s and
blink 19
times
OFF
3s and
blink 20
times
D43/
D30
A/C Status Malfunctions
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Replace outdoor control panel AP1
Aer the complete unit is deenergized for 20 mins, check whether the thermal grease on IPM Module of outdoor control panel AP1 is sucient and whether the radiator is inserted tightly. If its no use, please replace control panel AP1
Supply voltage is unstable
o = OFF n = Illuminated = Blink
76
Page 77
Malfunction
Name
Voltage of DC bus-bar is too low
Limit/decrease frequency due to high temperature of module
e four-way valve is abnormal
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display
status and during blinking, ON 0.5s
and OFF 0.5s
D40/D5D41/D6D42/
D16
o n n o
n n n
n o o
Dual-8
Code
Display
PL
EU
U7
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
Heating
LED
OFF
3s and
blink 21
times
D43/
D30
A/C Status Malfunctions
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
All loads operate normally, while operation frequency for compressor is decreased
If this malfunction occurs during heating operation, the complete unit will drop operation
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 150VAC, turn on the unit aer the supply voltage is increased to the normal range. 2. If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel AP1
Discharging aer the complete unit is de-energized for 20 mins, check whether the thermal grease on IPM Module of outdoor control panel AP1 is sucient and whether the radiator is inserted tightly. If its no use, please replace control panel AP1
1. Supply voltage is lower than AC175V;
2. Wiring terminal 4V is loosened or broken; 3. 4V is damaged, please replace 4V
o = OFF n = Illuminated = Blink
77
Page 78
Malfunction
Name
Zero crossing malfunction of outdoor unit
Limit/ decrease frequency due to anti freezing
Fault Displays
18,000 and 24,000 btuh units
Indoor Unit Displaying Method Outdoor Unit Display (LED)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and OFF
0.5s
D40/D5D41/D6D42/
D16
n n o
n n n o
Dual-8
Code
Display
U9
FH
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s
Running
LED
Cooling
LED
Heating
LED
D43/
D30
A/C Status Malfunctions
During cooling operation, compressor will stop while indoor fan will operate; during heating the complete unit will stop operation
All loads operate normally, while operation frequency for compressor is decreased
Replace outdoor control panel AP1
Poor air-return in indoor unit or fan speed is too low
o = OFF n = Illuminated = Blink
78
Page 79
Troubleshooting 9,000 & 12,000 Units
Indoor Fan does not Operate
Is the indoor control board fastened securely and wired correctly?
Are the input voltages within 10% of rated value?
Energize the unit
Proper Voltage between
L & N
Yes
Check connection on
indoor board
Yes
Replace indoor board
No
No
Check power
supply
Repair connections
No
operating properly
Is system
Yes
Yes
Is system
operating properly
Yes
End Troubleshooting
No
Replace indoor
motor
Yes
79
Page 80
Troubleshooting 9,000 & 12,000 Units
Temperature Sensor Malfunction
Start Temperature Sensor
Troubleshooting
Temperature sensor malfunction
F1 & F2 will relate to indoor sensor faults F4 & F5 will relate to outdoor sensor faults
Is the sensor wire plug loose from
control board
No
Is there a short or open circuit in the
wire or sensor?
No
Yes
Insert the plug correctly
Is problem corrected?
Yes
Replace sensor or correct
wire problem
Is problem corrected?
Yes
Do the temperature sensor readings
compare to the resistance table in
the Appendix?
Yes
Replace the controller with the same
part number
End Troubleshooting
80
No
Replace the sensor with
appropriate part number
Is problem corrected?
Yes
Page 81
Troubleshooting 9,000 & 12,000 Units
Start Failure Malfunction
Energize and
start the unit
No
The stop duration of the unit
is not long enough, the high
and low side pressure of
the system is not balanced,
restart it after 3 minutes
Is the stop duration of the compressor longer than
3 minutes.
Yes
Are the wire connections
on the compressor
connected properly
Yes
Is the unit overcharged
Yes
Charge the unit according
to the “Charging” section of
this manual
Eliminate the malfunction
No
No
Yes
Reconnect the wires
according to the wiring
diagram
Eliminate the malfunction
Yes
No
Replace the outdoor main
board
Eliminate the malfunction
No
Replace the compressor
End Troubleshooting
Yes
81
Page 82
Troubleshooting 9,000 & 12,000 Units
Desynchronizing of Compressor aer Unit is Started
H7
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Troubleshooting Procedure for Synchronizing Fault after Unit is Started
Start Troubleshooting after unit
is powered off for 3 minutes
Are the compressor terminal
connected properly?
Yes
Replace Control Board AP1
No
1. Check the resistance of the compressor terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
4. Check for dirty coils and lters
Compressor Wires
Yes
Remove Malfunction?
No
Replace Compressor
End Troubleshooting
Correct wiring
problem
Illustration is for reference only, actual model may vary.
82
Page 83
Troubleshooting 9,000 & 12,000 Units
Desynchronizing of Compressor During Operation
H7
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Troubleshooting Procedure for Synchronizing Fault During Operation
Start Troubleshooting
Is the outdoor fan working
properly?
Yes
Are there any airow obstructions?
Yes
No
Are wire connections
proper?
Yes
Replace Fan
Capacitor C1
1. Check the resistance of the compressor
terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
Wire per diagram.
Fan Operating
Properly?
Yes
No
Is input voltage normal?
Yes
Is unit overcharged?
Replace Control Board
AP1
No
No
Improve airow
Correct voltage
problem
Charge per
installation manual
Malfunction corrected
Yes
Replace Outdoor Fan
Motor?
No
Replace Compressor
Yes
End Troubleshooting
83
Page 84
Troubleshooting 9,000 & 12,000 Units
Overload and Discharge Malfunction
Start
Replace the overload
protector
Is the Overload connections OK
Yes
No
Check the resistance between the
two ends of the overload protector in
ambient temperature. Is the resistance
below 1K
Yes
Is the wiring of the
electronic expansion valve
connected well
Yes
Check the coil of the electronic expansion
valve per instructions in this manual.
Replace if faulty
No
No
Reconnect according to the
wring diagram
Check the refrigerant status, if there is leakage,
84
Eliminate the malfunction
No
recharge according to this service manual.
Eliminate the malfunction
No
Replace outdoor main
board
Yes
Yes
End Troubleshooting
Page 85
Troubleshooting 9,000 & 12,000 Units
Communication Failure
E6
Communication Failure
Status:
Cooling operation, compressor stops while indoor fans runs. Heating operation, complete unit stops
Communication failure of
some units
De-energize, check the wire
connections of indoor and outdoor
units and power to outdoor unit
Are all connections
correct?
No
1. Improper voltages
2. Mis-matched indoor and outdoor units
3. Improper wiring between indoor and outdoor
units
Correct connections
Did this correct the
problem?
No
Yes
De-energize, change the communication wire
of the working/communication indoor unit and
malfunctioning/non-communicating indoor unit,
then energize the unit and wait for 3 minutes
The malfunction
indoor unit
resumes normal
Yes
Replace the main board of the malfunctioning
indoor unit
Yes
End Troubleshooting
Replace outdoor main board
85
Page 86
Troubleshooting 18,000 & 24,000 Units
Temperature sensor malfunction
Start Temperature Sensor
Troubleshooting
Is the sensor wire plug loose from
the control board?
No
Is there a short or open circuit in the
wire or sensor?
No
Yes
Insert the plug correctly
Is problem corrected?
Yes
Replace sensor or correct
wire problem
Is problem corrected?
Yes
Do the temperature sensor readings
compare to the resistance table in
the Appendix?
Yes
Replace the controller with the same
part number
End Troubleshooting
86
No
Replace the sensor with
appropriate part number
Is problem corrected?
Yes
Page 87
Troubleshooting 18,000 & 24,000 Units
Indoor fan does not operate
Possible causes:
1. Fan motor locked
2. The control or feedback terminal of PG not connected properly
3. Damaged motor
4. Main board malfunction
Energize the unit
Does fan turn freely?
Yes
Is the feedback
terminal PG motor
loose?
Is the control terminal
of PG motor loose?
Re-energize unit to turn unit on.
Measure within one minute after the
louvers are opened whether the output
voltage on the control terminal of the
PG motor is > 50 volts
No
Yes
Yes
Find obstruction
Repair connections
Repair connections
Yes
Replace indoor
OK
OK
OK
motor
No
Replace indoor board
End Troubleshooting
87
Page 88
Troubleshooting 18,000 & 24,000 Units
Jumper Cap Malfunction
C5
Jumper Cap Malfunction
Status:
Wireless remote will not send command to indoor unit.
Start Troubleshooting
Is there a jumper cap on the
controller?
Yes
Is the jumper cap
inserted correctly?
No
No
1. No jumper cap inserted on board
2. Jumper cap not fully seated
3. Jumper cap damaged
4. Bad control board
Install a matching
jumper cap
Yes
Is system
operating properly
Re-insert the jumper
cap
Yes
88
Yes
Replace the jumper
cap
Is system
operating properly
No
Replace the main
control board
End Troubleshooting
Yes
No
Is system
operating properly
Yes
Page 89
Troubleshooting 18,000 & 24,000 Units
Overcurrent Protection
E5
Overcurrent Protection
Status:
During cooling & dehumidifying, indoor unit operates while other functions stop; During heating operation, complete unit stops
Fault & Status Possible Causes
Start Troubleshooting
Check if compressor’s connection
line is properly connected
Yes
Check if current value is higher than
the protectors setting
No
No
1. Supply voltage is unstable
2. Supply voltage is too low
3. Coils are dirty
4. Improper refrigerant charge
Adjust compressor’s
connection line
Replace overcurrent protector
Yes
Is units high pressure normal
Yes
Check if unit voltage is normal
Yes
Replace main board
No
No
Refer to high pressure
protection error
Check connections, contact
electric utility company
89
Page 90
Troubleshooting 18,000 & 24,000 Units
Capacity Charging Malfunction
PU
Charging Malfunction of Capacitor
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Start Troubleshooting after unit
is powered on for 1 minute
Use a DC voltmeter to
measure the voltage
across the terminals of the
electrolytic capacitor
Voltage higher than 200v
No
Yes
1. Improper input voltage
2. Poor connection on reactor
3. Reactor damaged
4. Bad AP1 control board
The detection circuit
of the outdoor
mainboard has
malfunctioned
Replace outdoor main
board
Check if the inductor wiring is
loose or induction is cut off
No
Shut down power and wait 20
minutes or connect a DC voltmeter
to the electrolytic capacitor until the
voltage is less than 20 v
No
Replace the outdoor mainboard
End Troubleshooting
Yes
Replace the inductor
or reconnect wires
Is the malfunction
corrected?
No
Yes
90
Page 91
Troubleshooting 18,000 & 24,000 Units
IPM Protection Malfunction (unit will not run)
Fault & Status
IPM Protection
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Start Troubleshooting after unit
is powered off for 3 minutes
Are the compressor terminal
connected properly?
Yes
Check the compressor winding
resistance
Possible Causes
1. Dirty indoor and outdoor coils
2. Faulty indoor or outdoor fans
3. High system pressure
4. Over charge of refrigerant
No
Is the resistance normal?
Yes
Test the isolation impedance between
the three phases of the compressor
and copper tubing
No
Is the resistance above
500M?
Replace Compressor
Is Malfunction eliminated?
No
Replace the outdoor mainboard
No
Correct wiring
problem
End Troubleshooting
91
Page 92
Troubleshooting 18,000 & 24,000 Units
Compressor Overload, Discharge Protection Malfunction
1. Check the resistance of the compressor terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
4. Check for dirty coils and lters
Start
Replace the overload
protector
Is the Overload connections OK
Yes
No
Check the resistance between the
two ends of the overload protector in
ambient temperature. Is the resistance
below 1K
Yes
Is the wiring of the
electronic expansion valve
connected well
Yes
Check the coil of the electronic expansion
valve per instructions in this manual.
Replace if faulty
No
No
Reconnect according to the
wring diagram
Check the refrigerant status, if there is leakage,
recharge according to this service manual.
92
Eliminate the malfunction
No
Eliminate the malfunction
No
Replace outdoor main
board
End Troubleshooting
Yes
Yes
Page 93
Troubleshooting 18,000 & 24,000 Units
Desynchronize Malfunction, continued next page
H7
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Troubleshooting Procedure for Synchronizing Fault after Unit is Started
Start Troubleshooting after unit
is powered off for 3 minutes
Are the compressor terminal
connected properly?
Yes
Replace Control Board AP1
No
1. Check the resistance of the compressor terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
4. Check for dirty coils and lters
Yes
Remove Malfunction?
No
Replace Compressor
End Troubleshooting
Correct wiring
problem
93
Page 94
Troubleshooting 18,000 & 24,000 Units
Desynchronize Malfunction, continued
H7
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop, indoor fan will run. Heating mode all units stop.
Troubleshooting Procedure for Synchronizing Fault During Operation
Start Troubleshooting
Is the outdoor fan working
properly?
Yes
Are there any airow obstructions?
Yes
No
Are wire connections
proper?
Yes
Replace Fan Capacitor C1
1. Check the resistance of the compressor
terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
Wire per diagram.
Fan Operating
Properly?
Yes
No
Is input voltage normal?
Yes
Is unit overcharged?
Replace Control Board
AP1
No
No
Improve airow
Correct voltage
problem
Charge per
installation manual
Malfunction corrected
Yes
Replace Outdoor Fan
Motor?
No
Replace Compressor
Yes
End Troubleshooting
94
Page 95
Troubleshooting 18,000 & 24,000 Units
Anti-High Temperature, Overload Protection
High Discharge Temperature Protection of Compressor.
Status:
Cooling operation, compressor stops while indoor fans runs. Heating operation, complete unit stops
Start Troubleshooting
Is outdoor temperature above 127 0F
Remove power, then restart after 20
minutes
Are indoor and outdoor coils clean
and free from obstructions?
Yes
No
1. Is unit running in proper outdoor ambient range
2. Faulty outdoor temperature sensor
3. Refrigerant leak
4. Poor airow of outdoor unit
5. Follow Troubleshooting procedure
Normal protection, outdoor
ambient is higher than normal
parameters
Clean Coils
Yes
Are indoor and outdoor fans
operating properly?
Yes
Replace AP1 control board
End Troubleshooting
1. Check fan for obstruction
No
2. Check resistance of fan leads and voltage to motor
3. Check fan connections
Replace fan
95
Page 96
Unit Will Not Start
Troubleshooting 18,000 & 24,000 Units
Indoor and
outdoor unit
inoperative
Power voltage low
Outdoor unit will not start
Remote controller not
responding
Ensure proper voltage, should be withing 10%
of nameplate
No power
Poor electrical connection Check wire connections
Controller fuse open Replace fuse
Defective controller board
No power at remote
controller
Check fuses or circuit
breakers
Replace controller board
Replace remote controller
batteries
96
Circuit breaker tripping
Remote controller
malfunction
Indoor receiver defective
Breaker trips
immediately
Breaker trips within minutes
of turning on
Breaker is warm to touch
Press the “Auto” button.
If no response, check
for proper voltage and
connections. If there is
a response, check for
defective remote controller
or indoor receiver.
Check for shorted wires,
reactor or AP2 board
Individual components
could be defective.
Eliminate by checking
resistance on each
individual component.
Check insulation on wires
and proper positioning of
wires.
Check for defective
breaker, poor wire
connections
Page 97
Startup Failure
Troubleshooting 18,000 & 24,000 Units
Energize and
start the unit
No
The stop duration of the unit
is not long enough, the high
and low side pressure of
the system is not balanced,
restart it after 3 minutes
Is the stop duration of the compressor longer than
3 minutes.
Yes
Are the wire connections
on the compressor
connected properly
Yes
Is the unit overcharged
Yes
Charge the unit according
to the “Charging” section of
this manual
Eliminate the malfunction
No
No
Yes
Reconnect the wires
according to the wiring
diagram
Eliminate the malfunction
Yes
No
Replace the outdoor main
board
Eliminate the malfunction
No
Replace the compressor
End Troubleshooting
Yes
97
Page 98
Troubleshooting 18,000 & 24,000 Units
Compressor Overload, Discharge Protection Malfunction
Start
Replace the overload
protector
Is the Overload connections OK
Yes
No
Check the resistance between the
two ends of the overload protector in
ambient temperature. Is the resistance
below 1K
Yes
Is the wiring of the
electronic expansion valve
connected well
Yes
Check the coil of the electronic expansion
valve per instructions in this manual.
Replace if faulty
No
No
Reconnect according to the
wring diagram
Check the refrigerant status, if there is leakage,
98
Eliminate the malfunction
No
recharge according to this service manual.
Eliminate the malfunction
No
Replace outdoor main
board
Yes
Yes
End Troubleshooting
Page 99
Troubleshooting 18,000 & 24,000 Units
PFC Malfunction (correction for power factor)
HC
PFC (Power Factor Correction) Protection
Status:
During cooling & dehumidifying, indoor unit operates while other functions stop; During heating operation, complete unit stops
Start Troubleshooting
Check wiring of the reactor
(L) and PFC capacitor
(Outdoor Unit)
1. Check for damage to the reactor and PFC
capacitor of the outdoor unit
2. Refer to troubleshooting procedure below
Are wires connected proper
Are wires connected proper
with no short circuits?
with no short circuits?
Yes
Remove the PFC Capacitor
and test resistance of the
two terminals.
Is the resistance
about zero?
No
Disconnect the reactor wires & measure
the resistance between the two terminals
of the reactor
Is the reactor
damaged or
shorted?
No Yes
Yes
Yes
Correct according to circuit diagram.
Replace the
capacitor
Replace the reactor
Is problem corrected?
No
Is problem corrected?
No
Is problem corrected?
Yes
Yes
Replace the AP1
control panel
End Troubleshooting
No
99
Page 100
Troubleshooting 18,000 & 24,000 Units
Communication Malfunction of Indoor Unit, continued next page for Outdoor Unit
E6
Communication Failure
Status:
Cooling operation, compressor stops while indoor fans runs. Heating operation, complete unit stops
Communication failure of
some indoor units
De-energize, check the wire
connections of indoor and outdoor
units and power to outdoor unit
1. Improper voltages
2. Mis-matched indoor and outdoor units
3. Improper wiring between indoor and outdoor
units
Are all connections
correct?
De-energize, change the communication wire
of the working/communication indoor unit and
malfunctioning/non-communicating indoor unit,
then energize the unit and wait for 3 minutes
The malfunction
indoor unit
resumes normal
Yes
Replace the main board of the malfunctioning
indoor unit
No
Yes
End Troubleshooting
Correct connections
Replace outdoor main board
Did this correct the
problem?
No
Yes
100
Loading...