There are a number of live tests that are required when fault finding this product. Extreme care should be used
If any of the
original wire as supplied with the appliance must
Label all wires prior to disconnection when
CAUTION
E- Series Boiler
Troubleshooting Manual
WARNING
at all times to avoid contact with energized components inside the product.
You MUST be a qualified service person before proceeding with these test instructions.
Before checking resistance readings, turn off power source to unit and then isolate each item to be checked
from the circuit by unplugging it.
When setting gas pressures on one of these units, please check the complete model number you are troubleshooting. Gas pressures and dip switches can vary among models. Always check the rating plate for complete
information and follow directions.
servicing controls. Wiring errors can cause
improper and dangerous operation.
be replaced, it must be replaced with type 18 AWG wire or its
equivalent.
Rinnai is continually updating and improving products; therefore, specifications are subject to change without
prior notice. Local, state, provincial and federal codes must be adhered to prior to and upon installation.
3
008082013GW
Page 4
Bi-metal high
Parts of the Boiler
4
008082013GW
Page 5
A detected error is indicated on the display by means of a blocking or error messages. A distinction should be made between
Block 67: A ∆T has been detected between flow and the return sensor whereas the burner is not in operation. After the
Flame present when burner is off, electrical interference, poor
Block and Errors
- Error indication (short reference)
these two messages due to the fact that a blocking code can be of a temporary nature, however, error messages are fixed
“lockouts” or hard lockouts. The control will try its utmost to prevent a lockout and will temporary switch off the unit by blocking it,
below is a list of some messages the unit will display.
Blocks: bL with a number in the last two positions indicates the type of blocking code.
bL 01 Block 01: External safety contact cut off.
bL 05 Block 05: Outdoor reset sensor not connected.
bL 60 Block 60: Incorrect parameter setting of the minimum or maximum power (Btu) of boiler.
bL 67
∆T has disappeared the block will clear itself.
bL 85 Block 85: The control has not detected water flow. The venting cycle (pro-purge) cycle has started.
If during this cycle water flow is detected, the pro-purge cycle stops, the burner will then fire up.
Error: E with a number in the last two positions indicates the type of error code.
E 00 Error 00: Poor flame forming.
E 02 Error 02: No flame forming.
E 04 Error 04: Adjustment or error due to voltage interruption.
E 05 Error 05: Adjustment.
E 12 Error 12: High limit stat.
E 18 Error 18: Maximum flow temperature exceeded.
E 19 Error 19: Maximum return water temperature exceeded.
E 28 Error 28: Fan revolutions not being measured by control board.
ground, and flame sensing wire disconnected during off cycle.
E 69 Error 69: No or incorrect display.
FUSE FUSE: 24 V fuse defective or blown.
Informationdisplayedin“TechReadoutMode”.Toenterthis
mode press and hold the “STEP” button for 5 seconds.
Operation Indication
0 - No heat demand
1 - Fan pre/post purge
2 - Ignition phase
3 - Burner active on central heating
4 - Burner active on DHW
5 - Fan check
6 - Burner off when either DHW or room thermostat is calling *
(See note 2 below).
7- Pump overrun phase for central heating
8- Pump overrun phase for hot water
9 - Burner off because of too high flow temperature
A - Automatic de-aeration program
F – Fan test still activated in Service mode
H Burner test still activated in Service mode
*Note 2; (E Boiler) a continuous code 6 can mean there is a small hot
water leak triggering the plate heat exchanger sensor to call continually
for DHW in turn locking out space heating in DHW priority. Switch PARA
36 to 20 (flow switch only) and then repair leak.
NOTE; if the unit appears to be fine but doesn’t run and no
error code is displayed check;
a. That the desired programming is on; set to
either Central Heating and/or Domestic Hot
Water.
b. The unit is not in the Showroom Mode
______________________________________
Explanation of T Sensors:
T1- Supply sensor - Water leaving heat exchanger mounts
in flow of water.
T2 - Return water sensor, surface mounted.
T3 - Domestic hot water flow sensor,. Q175C uses a
surface mount sensor. Q models with optional 3-way valve
use a sensor designed to be used in a well. (QP uses a
well)
T5 - Flue gas sensor - Optional sensor not included with
boiler.
5
008082013GW
Page 6
The 120 volt external pump is for
E and QP model boilers
WARNING: Turn off power supply before
installing jumper. Rectify error by determining
which external contact is open. If external
contacts are not being used place jumper across
terminals 24 & 25
If multiple boiler safeties are to be wired in series check with your local inspector or the local or State
codes to see if this is allowed in your area before proceeding. NEVER wire boiler safeties in parallel.
Refer to wiring diagram in the boiler manual. Trace connections 24 and 25 above back to the MCBA.
These will be located on Plug X5 on the MCBA on pins 2 and 6.
6
008082013GW
Page 7
7
008082013GW
Page 8
Maximum averageΔTof T1 supply
BL 11
operate at minimum capacity during the block.
Rectify Issue,
sensor and T2 return sensor for central
heating is repeatedly exceeded.
Operation is normally possible for the hot water
supply during the block. The pump continues to
Check following
1. Check flow through the heating system.
2. Possible causes: radiator shut off valves closed, blocked water filter.
3. Verify proper installation of the boiler plumbing, connections and all components.
4. Check minimum and maximum temperature difference in Parameter step 46 and 47.
5. Activated room sensor (RS100) in non leading room (closed thermostatic radiator
valves?) Check pump height. Should this be check pump head? Do not understand
8
008082013GW
Page 9
Maximum averageΔT of supply
BL 12
continues to operate at minimum capacity during
Rectify Issue,
sensor and return sensor for hot
water is repeatedly exceeded.
Operation is normally possible for the central
heating installation during the block. The pump
Check following
1. Check flow through the boiler and DHW tank.
2. Possible causes: radiator shut off valves closed, blocked water filter, restriction in DHW tank to high.
3. Verify proper installation of the boiler plumbing, connections and all components.
4. Ensure 3 way valve is functioning properly and is not clogged or full of pollution.
9
008082013GW
Page 10
NOTE; in order to reset all parameters in your boiler back to factory defaults follow the “Activating Factory
Settings” (Green button function) instructions found in your owner’s manual. CAUTION: All parameters you adjusted will now have to be reprogrammed if the bL60 code clears up. If after resetting the boiler the bL60
still appears, you will need to replace the sub-PC board and reprogram the MCBA. The sub PC board must be
from a conversation kit for the same gas type as your boiler.
WARNING: Before replacing the sub PC board or installing a conversion kit turn off the gas and electrical
supply to the boiler.
If conversion parts are not locally accessible contact Rinnai Tech Support for assistance. These parameters
cannot be accessed in the field and may require special instructions in an emergency situation.
10
008082013GW
Page 11
Atemperaturedifferencehasbeendetected
A temperature difference has been detected
between the supply T1 sensor and the return T2
betweenthesupplyandreturnsensorwhile
sensor while the burner is not in operation. After
theburnerisnotinoperation.Afterthe
the average ΔT has disappeared, the blocking
averageΔThasdisappeared,theblockwill
code will go away.
disappear.
Check the supply T1 sensor and the return T2 sensor for
the proper resistance valve. Replace if found to be
defective. WARNING: Turn off power and water supply
to boiler before removing the T1 or T2 sensor.
T1 Sensor
T2 Sensor
11
008082013GW
Page 12
T5 sensor is registering too high of a
and installed on the boiler.
temperature. This error can only occur if
the optional T5 sensor is was purchased
This is the location of the T5 sensor if installed.
If the red tab is in place this sensor was never
installed, which means the circuit has
somehow been jumped out. Contact Rinnai
tech support for assist if you get the bL80
without the T5 sensor being installed.
Inspect vent system and all air passages
ways for blockage
212˚F is the default temperature setting for
parameter 84. Verify to see if the temperature
setting for this parameter is set higher than
the default. If so, inspect vent system for
blockage. CAUTION: ensure all vent
components are properly seated when reinstalled.
12
008082013GW
Page 13
Explanation: The bL81 can be triggered if the flue gas plug has gotten wet and then dried out. (MCBA sees resistance when wet and
then sees no resistance when dry) This tricks the MCBA into thinking that a flue gas sensor was installed and then removed in which
the bL 81 is triggered. Moisture can come from a clog, broken or dry condensate trap. Moisture can be from a leaking concentric
vent pipe or from driving rain during extreme weather.
WARNING: Turn off power and water supply to the boiler before removing or installing any parts.
Methods to rectify:
A. ORDER AND INSTALL A FLUE GAS SENSOR (This may not be possible in cold weather when boiler must operate
immediately, if shipping the part is required.
B. CHANGE PARA 80 TO 20 AND INSTALL LOW VOLTAGE JUMPER ON FLUE GAS PLUG - (plug located on upper left hand side
of the heat exchanger in the harness) (PARA 20 setting causes the MCBA to look for an open/ close circuit and ignores any
variable resistance values like moisture or a thermistor.
C. INSTALL A 10K OHM RESISTOR ACROSS FLUE GAS TERMINALS. This will make the MCBA think that the flue gas is at a safe
temperature level (90 F)
13
008082013GW
Page 14
Flue sensor
Explanation: The bL81 can be triggered if the flue gas plug has gotten wet and then dried out. (MCBA sees resistance when wet and
then sees no resistance when dry) This tricks the MCBA into thinking that a flue gas sensor was installed and then removed in which
the bL 81 is triggered. Moisture can come from a clog, broken or dry condensate trap. Moisture can be from a leaking concentric
vent pipe or from driving rain during extreme weather.
WARNING: Turn off power and water supply to the boiler before removing or installing any parts.
Methods to rectify:
D. ORDER AND INSTALL A FLUE GAS SENSOR (This may not be possible in cold weather when boiler must operate
immediately, if shipping the part is required.
E. CHANGE PARA 80 TO 20 AND INSTALL LOW VOLTAGE JUMPER ON FLUE GAS PLUG - (plug located on upper left hand side
of the heat exchanger in the harness) (PARA 20 setting causes the MCBA to look for an open/ close circuit and ignores any
variable resistance values like moisture or a thermistor.
F. INSTALL A 10K OHM RESISTOR ACROSS FLUE GAS TERMINALS. This will make the MCBA think that the flue gas is at a safe
temperature level (90 F)
14
008082013GW
Page 15
212˚F is the default temperature setting for
parameter 84. Verify to see if the temperature
setting for this parameter is set higher than
the default. If so, inspect vent system for
blockage.
This can occur when PARA 84 has been
changed to 20 and the field installed jumper is
loose or removed.
15
008082013GW
Page 16
AIR: if boiler, inner boiler piping, or Low Loss
Header has a large air bubble in it the
pressure sensor will not see the pressure
spike that the pump generates when it starts.
The pressure spike is what tells the MCBA that
the pump has started.
The air bubble will absorb that spike. Bleed all
air from the system.
If an additional expansion tank is placed in the
system alongside an E-boiler that tank can
absorb the pump pressure spike as well. You
may need to isolate that tank to see if this
corrects the issue with BL 85.
An expansion that is not charged properly can
cause the pump’s pressure spike not to be
seen by the sensor causing a BL85.
Expansion tank pressure should be air charged
to match whatever water fill pressure that is
chosen for the closed loop. (Always above
14.5 psi)
Expansion tanks must be air charged only
when there is no water pressure on the wet
side of the diaphragm or the tank is removed
from the system. Once charged to the correct
air pressure it may be placed into the system
and the water fill pressure now may be set to
match the new tank pressure.
Check the installation for the presence of air.
If there is a secondary pump installed and it
is not hydraulically separated, it could cause
a loss of pressure difference.
Check to ensure the pump is functioning and/or water
pressure sensor is working properly.
WARNING: Turn off power and water supply to the boiler
before removing or installing any parts.
Ensure water pressure sensor is not clogged or defective.
Inspect water filter for debris.
Check pump for proper operation and flow rates.
Check for proper wiring of pump.
Check for use of balancing valves.
16
008082013GW
Page 17
The frequency of the power supply deviates more
than + or - 1.5 Hz.
If using a back-up generator ensure it is
properly grounded and providing a clean
steady voltage and sign wave of 59.3 to 60.8
Hz.
17
008082013GW
Page 18
Boiler has not been
WARNING: Turn off power and water supply to the boiler before removing or installing any parts.
burning but an
ionization flow
(flame) has been
detected.
Check whether the ionization cable and/or the electrode
are responsible for a short circuit. Remove the plugs from
the ionization cable connected to the control unit and to
the electrode. Now using a ohm meter take a
measurement between the ionization connection and the
ground. Now refit it part by part until a short circuit takes
place.
NOTE: Inadvertently unplugging the ionization
cable or spark igniter wire while the boiler is
not firing can trigger the E00 code.
18
008082013GW
Page 19
24 volt shortcircuit
E 01
Remove all 24 volt connectors, such as: fan, pump, any three port valve and the 24 volt plug to the connecting
block. Check for a short circuit in the disconnected components. Next; switch on power to the control board with all
the 24 volt components disconnected. Reconnect the components one at a time, if code E 01 appears when you
plug up a component, that component has a short circuit. Rectify any short circuits or replace defective component
causing short circuit.
19
008082013GW
Page 20
ignition
Ionization flow,
Flame Failure
Issue
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Ignition Failure Issue
ionization cable or
02 setting
Due to insufficient
ionization the burner
has shut down after
The minimum ionization current
should be 4 micro amps (Check
INFO step 48, the O2 should be a
minimum of 4.4% for NG or 4.8%
for LP.
Note: if ionization is lost while the flame is
burning no E02 will occur - unit will attempt to
relight 6 times. E02 only occurs after 6 failed
20
attempts for re-ignition.
Propane gas with low BTU value or a brand
new tank that may contain something other
than pure propane may cause E02. Check
against a good known source of gas.
008082013GW
Page 21
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Check for 24 volts DC at gas valve.
Check across terminals 4 and 5 at plug X5 on the main
control board. See wiring diagram for your boiler for
terminal locations
Control unit error - Connector not plugged into the gas valve
or defect in the wiring harness to the gas valve.
In some cases an E03 is caused from a loose
connection on wires to the gas valve. This
faulty connection may be in the Molex plug
(X5) on the MCBA. Examine plug closely for
bayonets that may have backed out of plastic
casing.
21
008082013GW
Page 22
interferenceisnolongerpresent,thismessageis
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
The boiler automatically indicates this message if
during an error read-out the electrical power to
Theboilerautomaticallyindicatesthismessageif
the boiler is shut off. After the power is once again
duringanerrorread-outtheelectricalpowerto
switched on, if the error causing the interference is
theboilerisshutoff.Afterthepowerisonce
no longer present, this message is given
againswitchedon,iftheerrorcausingthe
22
008082013GW
Page 23
If error persist
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
after reset
Software error control unit, replace control unit. Remove
the E-Prom from the defective control unit and place it
onto the new control. The controller will automatically
load the program into the new control unit.
23
008082013GW
Page 24
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace the control unit. Remove the E-Prom from
the defective control unit and place onto the new
control. The controller will automatically load the
program into the new control unit.
24
008082013GW
Page 25
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Check E-Prom to ensure it has no
damaged pins and it is properly
connected.
25
008082013GW
Page 26
WARNING: Turn off power and water supply to the boiler before removing or installing any parts.
VERY RARE THAT AIR IS AT FAULT. If air is
present it will be indicated by a gurgling
noise. Normally when an airlock is
Clean the pump and/or filter when necessary.
Flush complete system
26
008082013GW
Page 27
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace the control unit. Remove the E-Prom from
the defective control unit and place onto the new
control. The controller will automatically load the
program into the new control unit.
27
008082013GW
Page 28
- T3 flow sensor ground connection
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
T3 flow sensor failure or controller failure
To determine flow temperatures for T3 use the chart to the
left for proper resistance values for a set temperature.
When no discrepancies are found on the sensors it
may be a leakage of current coming in from an end
switch or pump relay box connected to terms 22 and
23. Install isolating relay on 22 and 23 or replace
faulty end switch / or pump relay box connected to
T3 Sensor is located behind the condensate
trap on the E series boiler; this will look different
on Q and QP boilers. This is a close up of the
T3 sensor with the condensate trap removed.
28
008082013GW
Page 29
T1 Sensor
Actualflow
determined.
WARNING:
Turn off power and wat
er s
upply
to the boiler before removing or installing any parts.
Check actual flow
temperatureshouldbe
temperature
verifiedbeforeT1is
Signal maximum flow water temperature exceeded
(T1 ˃ 212⁰F).
29
008082013GW
Page 30
WARNING: Turn off power and water supply to the boiler before removing or installing any parts
Signal maximum return water temperature
exceeded (T2 ˃ 212⁰F).
30
T2 Sensor located
under T1 sensor
008082013GW
Page 31
T1
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
and
T2 (swapped).
T2 temperature is measured to be higher than T1. Check
resistance value of T1 and T2 (See resistance chart under error
19 for resistance values. Replace T! and/or T2 if found to be
defective.
T1 Pressure Transducer
T2 sensor
31
008082013GW
Page 32
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace MCBA board, main board.
32
008082013GW
Page 33
No feedback signal from fan motor.
WARNING:
Turn off power
s
upply
to the boiler before removing or installing any parts.
Check the wiring harness to the fan motor and control
unit. Check power supply to motor during combustion
process, should be 24 volts DC.
Fan
motor
wiring harness
constant 24 volts DC.
Tachometer cable
Feedback signal
33
008082013GW
Page 34
according to the installation
instructions.
There is a negative pressure on vent system (Pressure
WARNING:
Turn off power
to the boiler before removing or installing any parts
difference). Check to see if fan motor is spinning.
Vent system and air intake must be installed
The E29 is triggered immediately after fan check code 5 during the starting sequence. If during fan
check 5 the fan remains spinning more than 150 rpms an E29 will occur.
Causes:
- Wind driving into a concentric terminal. Replace with 90 degree terminal or for best results
use a roof terminal.
- Venting running a long distance in a cold attic space causing a thermo syphon after fan check.
Use room air for combustion if conforming to NFPA 111 guidelines for room air or use
concentric terminal directly through the roof.
34
008082013GW
Page 35
Internal shut down of supply sensor T1.
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
T1 sensor short circuit is indicated by low ohm reading.
Replace defective sensor, see resistance values in chart
on E 18 above.
35
T1 Sensor
008082013GW
Page 36
Shut down of return sensor T2,
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
T2 sensor short circuit is indicated by low ohm
reading. Replace defective sensor. Refer to
36
008082013GW
Page 37
Contact for supply sensor T1 open,
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
indicated by infinite ohm reading.
37
T1 Sensor
008082013GW
Page 38
Contact for the return sensor T2 open,
Remove the plug from the flow sensor as a
WARNING:
Turn off power and water
supply
to the boiler before removing or installing any parts.
indicated by infinite ohm reading.
result of which error 32 occurs.
T2 Sensor
38
008082013GW
Page 39
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace the control unit. Remove the E-Prom from
the defective control unit and place onto the new
control. The controller will automatically load the
program into the new control unit.
39
008082013GW
Page 40
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace the control unit. Remove the E-Prom from
the defective control unit and place onto the new
control. The controller will automatically load the
program into the new control unit.
40
008082013GW
Page 41
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Electrical short circuit, possible water damage to
MCBA, main board
41
008082013GW
Page 42
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
No parameters present. Meaning the E-Prom has no
program or is blank. Replace E-Prom or display (Model
dependent).
If this error is displayed, there is no software on the
MCBA or display/EPROM. A RINNAI conversion kit
specific for the boiler model and fuel type must be
installed. Follow the conversion kit instructions to
load the software to the MCBA.
42
008082013GW
Page 43
Q-Seriesribboncableproblem
or
defectivekeypad.
No software present.
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
Replace the control unit. Remove the E-Prom from
the defective control unit and place onto the new
control. The controller will automatically load the
program into the new control unit.
43
008082013GW
Page 44
T5 sensor is reading too high of a flue gas temperature. (Adjust
reading.
parameter 84 – default 212 ⁰F) See location of T5 sensor below. If red
cap is installed, T5 sensor is not being used.
Moisture on the flue gas sensor wires or
terminals could cause a false temperature
T5 Senor, if
installed
44
008082013GW
Page 45
E 115
Replace MCBA board
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
45
008082013GW
Page 46
WARNING: Turn off power to the boiler before removing or installing the fuse.
Check fuse mounted on PC board to see if it blown. In addition, check
transformer output and wiring harness for transformer to ensure it is
plugged in properly.
This is the low voltage fuse that is located
directly next to the PCB board transformer.
The OEM fuse has colored stripes; the spare
fuse located on control cover is a clear glass.
Please verify the amp rating (4 amp) on the
metal rim of the fuse before installing it. It
must be the same amperage as the fuse being
replaced.
46
008082013GW
Page 47
Additional Troubleshooting Instructions
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
47
008082013GW
Page 48
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.
48
008082013GW
Page 49
Checking the O
Setting
2
49
008082013GW
Page 50
Boiler Controls
50
008082013GW
Page 51
Pressing R or the reset button for more than 5 seconds will activate a 17 minute de
-
aeration
cycle.
Explanation of the function buttons
51
008082013GW
Page 52
Starting up: Filling and de
-
aerating the boiler and installation
Requirements of the water system
52
008082013GW
Page 53
53
008082013GW
Page 54
Check the water pressure regularly and top off the installation when necessary. The
Note: You must have either a hot water or heat demand to activate de
-
aeration
Filling the heating system
working pressure of the installation should be between 16 and 18 PSI when the system is
cold. Adjust your auto-feed to 16 – 18 PSI.
54
008082013GW
Page 55
Altering adjustments
55
008082013GW
Page 56
See additional
definitions below
PARA 36 E Combi. setting definitions
00 = activation by temperature drop for DHW (no plate warming)
10 = activation by temperature drop for DHW (plus plate warming)
20 = flow switch activation only DHW. (No plate warming/ no temp actuation)
In either setting above - 00 or 10 the Flow switch is still in the circuit and if it sticks "closed" it can keep the boiler locked
in DHW and code 6 with appear on the screen. Unplug flow switch as it is not needed. (Do not waste time taking switch
out and cleaning it, just unplug it electrically)
PARA 36 Q combi
01 = factory setting-load sharing "on"
00 = Alternate setting - Load sharing "off" (MCBA thinks a "grey" non-modulating valve is being used in place of the
56
008082013GW
Page 57
57
008082013GW
Page 58
Activating
factory settings (Green button function)
58
008082013GW
Page 59
Isolating the boiler
59
008082013GW
Page 60
Reset service interval counter
60
008082013GW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.