2.4 Power Connections ............................................................................................................................ 4
2.4.1 AC Units and External DC Units ................................................................................................................. 4
2.4.2 AC/Battery Units ........................................................................................................................................ 4
2.11 Serial Port Wiring............................................................................................................................... 9
2.11.1 Serial Port #1 Wiring: CPU KGR8924–1.................................................................................................. 10
2.11.2 Serial Port #2 Wiring: CPU KGR8924–1.................................................................................................. 11
4.2.2 Test Modes.............................................................................................................................................. 24
4.2.4 Communication Verification...................................................................................................................... 24
4.2.5 Analog Wiring to Host Indicator................................................................................................................ 27
4.2.6 Analog Module Serial Pass-Through......................................................................................................... 27
4.3 Option 3 – Time and Date................................................................................................................. 28
calling 715-234-9171 and asking for the training department.
Specifications subject to change without notice.
February 2003
ii
4.7.3 Standard Serial Configuration................................................................................................................... 36
5.1 Zero Calibration ................................................................................................................................ 47
5.2 Single Slope Span Calibration........................................................................................................... 47
5.3 Five-Point Linear Calibration ............................................................................................................. 48
6.0 Normal Weighing Mode Operations.......................................................................................... 49
6.2 LED Annunciators............................................................................................................................. 49
6.3 Function Keys................................................................................................................................... 49
6.4.1 Display Mode on Power Up...................................................................................................................... 49
6.4.2 ZERO Key Function.................................................................................................................................. 49
6.4.3 TARE Key Function .................................................................................................................................. 50
6.4.4 Overload and Underrange Conditions....................................................................................................... 50
6.6 Serial Output .................................................................................................................................... 51
6.6.1 Serial Data Formats.................................................................................................................................. 51
6.6.2 Demand Mode versus Continuous Data Output ....................................................................................... 52
6.6.3 Demand Print with Identification Number.................................................................................................. 52
8.0 Optional and Advanced Features............................................................................................... 62
8.1 Expanded Serial Communications .................................................................................................... 62
8.1.1 Demand Output Serial Data Format.......................................................................................................... 62
8.1.2 Continuous Condec Output Serial Data Format........................................................................................ 63
8.1.3 RS485 Data Formats................................................................................................................................ 63
8.1.4 Port 1 Remote Serial Commands............................................................................................................. 64
8.1.5 Full Duplex Parameter Entry/Recall........................................................................................................... 65
This manual is intended for use by service technicians
responsible for installing and servicing the UMC600
digital weight indicator. This manual provides
information on installation, calibration, configuration,
Authorized distributors and their
employees can view or download this
manual from the Condec distributor
site at www.4condec.com .
and operation of the UMC600.
1.0Introduction
The UMC600 is a single-channel digital weight indicator designed to operate in a wide variety of scale and
weighing applications. The indicator is housed in a NEMA 4X stainless steel sealed case. The standard unit is
equipped with a tilt stand base for tabletop or wall mounting applications. The indicator front panel consists of a
21-button keypad, six se ven-segment display digits and six LED annunciators (see Figure 1-1 on page 2).
Standard features of the UMC600 include:
•Full front panel digital configuration and calibration.
•Zero and span temperature compensation to ensure compliance with NTEP and Canadian temperature range
requirements (–10 to 40°C).
•Nonvolatile memory stores data for calibration, temperature compensation, configuration parameters, auto or fixed
tare values, PAZ and AZM values, and setpoint values.
Note: Use of more than 20,000 graduations may cause undesirable display instability in some applications.
µ
•Analog sensitivity to 0.3
•Ten updates per second, with selectable digital averaging and auto averaging; 5 Hz active analog filter for smooth
response.
•Excitation for eight 350
•Operable from AC, internal rechargeable battery with AC charger, or external DC input.
•Time and date print selection.
V/grad at 20,000 graduations.
Ω
load cells at 10 VDC.
Introduction
1
2
1.1Front Panel Keypad and Annunciators
Figure 1-1 shows the UMC600 front panel. The UMC600 display consist of six seven-segment display digits.
Table 1-1 lists the front panel keys and their functions.
Low Battery Annunicator
lb
kg
MOTION
PRINT
1 SET
POINT
2 SET
POINT
ZERO
TARE
RECALL
ZERO
NET
GROSS
CAPACITY
NET
GROSS
5000 lb. X 0.5
TARE
162738495
0
lb/kg
CONV
CE
ENT
Figure 1-1. UMC600 Front Panel
Panel Key
ZEROProvides push-button auto zero (PAZ) over ±1.9% or 100% full scale capacity. Operates only in gross
weighing mode.
GROSS/NETSwitches the unit between gross and net weighing modes.
TAREProvides push-button tare entry over 100% of scale capacity. Pressing TARE key switches to net mode
and enters tare.
PRINTProvides a manual print function if unit is wired to serial printer or other data device. Also initiates truck
in/out weighing function if that feature is enabled. See Section 3.2 on page 20 for serial output
specifications.
lb/kg CONVSwitches the displayed weight unit between pounds and kilograms.
TARE RECALLPress to recall tare value; LED annunciator lit when tare value is displayed. Also used as ID RECALL in
t
ruck weighing mode.
ON/OFFProvides power to the indicator.
Function
NOTE: On AC units, the ON/OFF switch is replaced by the blank key which becomes a start
key in setpoint batching modes.
SETPOINT 1 & 2Push to enter or recall associated setpoint values.See Section 6.0 on page 49 for details.
0–9, CE, ENT
Numeric keyboard for entry of manual tare, setpoint values, and calibration data.
ENT
(Enter) keys.
(Clear Entry) and
CE
Table 1-1. Front Panel Key Functions
UMC600 Installation Manual
Table 1-2 summarizes the front panel annunciator functions.
Annunciator
LOW BATTERYOn when 12 VDC input voltage drops to approximately 11.4 VDC.
ZEROOn when scale weight is within ±0.25 displayed graduations of zero. Used in gross or net weighing mode.
NETOn when the indicator is in net weighing mode.
GROSSOn when the indicator is in gross weighing mode.
lb/kglb or kg LED is lit to show the current displayed weight units.
MOTIONOn when scale is in motion.
1 SETPOINT
2 SETPOINT
TARE RECALLPart of the TARE RECALL key, LED flashes when tare value is displayed.
ON/OFFOn when the scale is operational.
On when the appropriate setpoint is energized or are flashing when the appropriate setpoint is recalled on
the display.
Function
Table 1-2. Front Panel Annunciators
Introduction
3
4
2.0Installation and Wiring
This section describes the procedures for installing the UMC600 indicator, including connecting the load cell,
digital input and serial communications cables to the indicator. Instructions for CPU board replacement are
included, along with assembly drawings and parts list for the service technician.
Use a wrist strap to ground yourself
!
Caution
and protect components from
electrostatic discharge (ESD) when
working inside the indicator.
2.1Unpacking and Assembly
All indicators are configured and tested prior to
shipment to ensure that they are fully functional.
Immediately after unpacking, visually inspect the
UMC600 to ensure all components are included and
undamaged. The shipping carton should contain the
indicator, tilt stand, the manual, and a parts kit. If any
parts were damaged in shipment, notify Condec and the
shipper immediately .
2.2Enclosure Disassembly
The indicator enclosure consists of a load cell
connector and cord grips for communications cables.
the enclosure must be opened to connect the
communications cables.
The UMC600 has no on/off switch.
Warning
Before opening the unit, ensure the
power cord is disconnected from the
power outlet.
Ensure power to the indicator is disconnected then
remove the screws that hold the front bezel to the
enclosure body. Place the indicator face-down on an
antistatic work mat, then lift the enclosure away from
the front bezel. Set the enclosure aside.
2.3Cable Connections
The UMC600 provides a load cell connector and three
cord grips for cabling into the indicator; one for the
power, and two to accommodate communications,
digital input, and analog output cables.
One of the two free cord grips comes with a plug
installed to prevent moisture from entering the
enclosure. Depending on your application, remove the
plug from the appropriate cord grip and install cables as
required.
Figure 2-1 shows the recommended assignments for the
UMC600 cord grips.
REAR VIEW
Analog Ouput, Digital Input
TB3 & 5
Load Cell
Connector
TB1
POWER
TB2 & 4
Serial
Communications
Figure 2-1. UMC600 Backplate
2.4Power Connections
Standard units are powered by one of the following
options.
2.4.1AC Units and External DC Units
Units are powered by standard 115 VAC power. The AC
power cord must be plugged into a 3-prong grounded
AC wall socket.
2.4.2AC/Battery Units
The battery operated version of the UMC600 uses a 2.3
amp/hour rechargeable gel cell mounted inside the unit.
A low battery LED annunciator indicates when the
battery needs to be recharged (shown below) and
automatically shuts down when the battery output can
no longer maintain accurate weighing. Refer to Section
8.3 on page 65 for more information on the battery
option.
Low Battery Annunicator
lb/kg
CONV
ENT
lb
kg
MOTION
PRINT
1 SET
CE
POINT
2 SET
POINT
ZERO
NET
ZERO
TARE
RECALL
GROSS
NET
GROSS
CAPACITY
5000 lb. X 0.5
TARE
162738495
0
Figure 2-2. Low Battery LED Annunciator
UMC600 Installation Manual
Note: The unit can be operated while charging
however will take longer to recharge than the
recommended 12 to 16 hours of charging time.
,
2.5 VAC Conversion
The UMC600 can be converted from 115VAC to
230VAC. The following steps are necessary to
complete this conversion.
Before beginning, be sure to
Warning
1. Disconnect power to the indicator. Loosen cord
grips and remove enclosure as described in
Section 2.2
2. See Section 2.6 for CPU board removal and
replacement instructions.
3. Remove the protective insulator panel from the
solder side of the CPU assembly .
4. Cut circuit traces between E7/E8 and E9/E10 as
indicated with a sharp instrument like a razor
blade or an x-acto knife. Refer to Figure 2-3.
Converting from 115V AC to 230V AC
Cut between
E7 and E8
disconnect the AC power source.
Failure to do so can result in injury
or death.
Jumper E8 to E9
Cut between
E9 and E10
2.6Board Removal
If you must remove the UMC600 CPU board, use the
following procedure:
1. Disconnect power to the indicator. Loosen cord
grips and remove enclosure as described in
Section 2.2
2. Unplug all connections to the CPU board noting
where they are connected.
3. Remove the four screws from the corners of the
CPU board.
4. Remove the CPU board from the enclosure.
To replace the CPU board, reverse the above procedure.
Be sure to reinstall tie wraps to secure all cables inside
the indicator enclosure. Replace enclosure and torque
screws to 10 in - lb (1.13 N-m).
E8 E9E10
E7
Circuit Side of CPU Board
Figure 2-3. Circuit Trace Setup
5. Add jumper, E8 to E9 using a properly insulated
wire with a minimum size of #22 AWG.
6. Replace the protective insulator panel.
7. Change the power cord.
8. Reassemble the unit, test, and label unit for
230VAC.
Installation and Wiring
5
6
2.7Instrumentation Setup
All indicators are configured and tested prior to
shipment to ensure that they are fully functional. The
unit can be turned on immediately after connecting the
input power and the load cells.
The UMC600 operates with the EPROM program
KDA1921-1(27C512). To verify the program installed
in the indicator, turn on the indicator and observe the
displayed value at the EP prompt (see Figure 2-4). The
EP prompt displays the family, set, and version level of
the installed EPROM.
EP–1.15
EPROM
Figure 2-4. EPROM Display
Set 1
To ensure that the UMC600 is in proper operating
condition, the indicator can be tested with a load cell
simulator. The input signal should be as close as
possible to the normal system millivolt value.
Figure 2-5 shows the simulator-to-indicator wiring
connection in a six-wire configuration. See Section 2.9
for more information.
Note: Six-wire configuration requires that the +SEN
lead be shorted to +EXC and the –SEN lead be shorted
to –EXC at the simulator only.
LOAD CELL
SIMULATOR
–EXC
+EXC
+SIG
–SIG
Figure 2-5. Wiring Connection to Simulator
Caution
!
–EXC
–SEN
+EXC
+SEN
+SIG
–SIG
Exceeding rated load cell load or
shorting excitation wires may
damage power supply.
Version 15
TO J1
CONNECTOR
UMC600
Notes:
•Test weights should be used to verify scale
performance.
•The tilt stand should be secured with 1/4-20 inch
screws. The location should be selected to of fer some
degree of protection for the indicator and its
associated hardware.
•Unprotected cable runs need to be installed in a
method to protect the cable from damage.
•All wiring must conform to the National Electrical
Code and RP 12.6.
2.8Load Cell Wiring
All units are equipped with a six-wire load cell
connector. The UMC600 is supplied with a six-pin
connector that needs to be attached to the existing load
cell cable by the installer.
Figure 2-6 shows the load cell output connector and the
location of J1 on the back of the indicator. Table 2-1
shows load cell connector pin assignments.
J1
Load Cell
Connector
TB3 & 5
TB1
Figure 2-6. J1 Load Cell Connector - facing
Pin
A+EXCITATION
B–EXCITATION
C+SIGNAL
D–SIGNAL
E+SENSE
F–SENSE
POWER
REAR VIEW
TB2 & 4
B
C
Function
A
F
E
D
UMC600 Installation Manual
Table 2-1. Load Cell Connector Pin Assignments
The standard connection is designed for 4-wire (non remote sensing) use. To convert to 6-wire (remote sensing)
applications, cut the two PC traces on each end of TB1 as shown in Figure 2-7.
Traces
J5
TB1
+EXC
+SEN
+SIG
–SIG
–SEN
–EXC
Traces
Note: The load cell shield wire should be connected to
one of the load cell cable clamp screws located on the
load cell mating connector.
LOAD CELL CONNECTOR
654321
J3
S3
U18
Q5
U2
F1
K1
Figure 2-7. Load Cell Wiring From Indicator
J7
J6
+ Batt -
Check load cell
color code for
proper wiring.
GND LO HI
TO POWER SUPPLY
1
2
TB5
Six-Pin Female
Shielding is connected at only one end
!
Caution
(typically at the indicator end). If
connected at the strain gauge end,
disregard Figure 2-8.
Figure 2-8. Load Cell Shield Wire Connection
2.9Standard Surge Protection Board
The UMC600 comes with a factory installed surge suppression board. The suppression board stops the flow of
excess voltage to the CPU board and attaches to TB1 on the CPU board just by pressing it into TB1 and tightening
the connector screws.
COMPONENT SIDERIGHT SIDECIRCUIT SIDE
CR3
CR2
CR4
CR1
+EXC
+SENSE
+SIG
–SIG
–SENSE
–EXC
Figure 2-9. Surge Protection Diagram
E1
E2
E3
E4
E5
E6
E7
CHGND
Installation and Wiring
7
2.10Hardware Configuration
Jumper pins are provided for:
•EPROM chip selection
•Front panel switch configuration (DC on/off or batch start)
•Power on/off relay configuration
•Dual channel (optional)
•Time and date option (SRAM selection)
These features are dependent on installed options and software. The location and jumper positions are noted in
Figure 2-10.
8
Dual Channel
(optional)
l 2 3
S7
S6
1 2 3
Enable Jumper 1-2
Disable Jumper 2-3
Front Panel On/Off
Switch Function
1 2 3
S4
S5
1 2 3
DC On/Off Jumper 1-2
Batch Start Jumper 2-3
Power On/Off
Relay
3
2
S3
1
Enable Jumper 1-2
Disable Jumper 2-3
For Toggle Switch Omit Jumper
TB1
+SIG
+SENSE
–SENSE
SHIELD
+EXC
Time and Date Option
3
2
S2
1
Enable Jumper 1-2 –
(1243 SRAM U4)
Disable Jumper 2-3 –
(1220 SRAM U4)
TB3
3
8
9
5
2
1
6
4
1
7
10
U20
S7
S6
S4
S5
R6
J4
J5
LOAD CELL CONNECTOR
–SIG
S3
654321
J3
U2
U18
F1
RF1
SHIELDED
A/D
Q5
U5
U7
J7
K1
DIGITAL OUTPUT
3
1
S2
U11
U4
EPROM Select
12 3
256k Jumper 1-2
512k Jumper 2-3
Figure 2-10. Jumper Pin Placement
Note: The lower left corner switch (S21) on the front panel, is used for the Start command in the standard setting of
S4 and S5, however, it becomes a power on/off switch when S4 and S5 are set to DC On/Off and S3 is set to the
Enable position.
UMC600 Installation Manual
2.11Serial Port Wiring
The UMC600 has two serial communications ports.
Port 1 supports full-duplex RS-232, or 20mA current loop (active or passive), or half-duplex RS-485. Switch S1
(shown in Figure 2-12), selects the interface protocol of Port 1.
Port 2 supports simplex (output only) RS-232, or 20mA current loop (active or passive).
Access to the serial communication ports is through the cord grips (TB2 and TB4) located on the back of the
enclosure (see Figure 2-11). See Figure 2-12 for serial I/O wiring termination assignments.
TB3 & 5
TB1
POWER
REAR VIEW
Figure 2-11. Serial Port TB2 Connector
U9
U13
J11
6
5
J10
4
3
2
1
1
SERIAL COMMUNICATIONS - 1
6
5
4
3
2
1
SERIAL COMMUNICATIONS - 2
S1
PASS
PORT 1 RECEIVE
1
2
3
4
RS232
20MA
RS485
ACTIVE
U8
TB2 & 4
Serial
Communications
TB4
RX+ (20 mA passive Port 1)
RX- (20 mA passive Port 1)
RX+ (20 mA active Port 1)
TX- (20 mA Port 2)
TX+ (20 mA Port 2)
TX- (20 mA active Port 1)
GND or RX 20 mA active Port 1
TX+ (20 mA active Port 1)
RX1 (RS-232 duplex Port 1) RD1
TX1 (RS-232 duplex Port 1) TD1
TX2 (RS-232 Port 2) TD2
TB2
Figure 2-12. Serial I/O Wiring Locations
Installation and Wiring
9
2.11.1Serial Port #1 Wiring: CPU KGR8924–1
Serial Port 1 supports full-duplex RS-232, or 20mA current loop (active or passive), or half-duplex RS-485. Switch
S1 (shown below), selects the interface protocol of Port 1..
1. A pull-down biasing resistor (100K OHMS typical) should be installed between TB5-1 and TB2-5.
2. A pull-down biasing resistor (100K OHMS typical) should be installed between TB5-2 and TB2-4.
3. If the UMC600 is the last device (node) on the RS-485 network, a termination resistor (100 OHMS typical) should
be installed across TB5-1 and TB5-2.
10UMC600 Installation Manual
2.11.2Serial Port #2 Wiring: CPU KGR8924–1
Serial port #2 supports simplex (output only) RS-232, or 20mA current loop (active or passi v e). The follo wing chart
illustrates Serial Port 2 pin assignments.
PortConnector/Pin #RS-23220mA Current Loop
2TB2 - 1TxD
2TB2 - 5GND
TB2 - 6
2TB4 - 1+20mA TX+ OUT (passive)
2TB4 - 2-20mA TX- OUT (active)
The standard unit has four outputs for setpoint and zero band control and four discrete inputs that allow the zero,
net/gross, and print function to be operated remotely by contact closure of these inputs to digital ground. Wire any
active digital input and outputs to connector TB3 on the CPU board. Table 2-4 shows the digital I/O assignments for
the TB3 connector and their description.
TB3 PinSignalDescription
Outputs
1+5 VDC
2DIG OUT 4Dribble control assigned to setpoint 2 (defined in parameter 11), or a zero band output
when parameter 12 is selected for 1-50.
3DIG OUT 3Setpoint 2 output (defined in parameter 11).
4DIG OUT 2Dribble control assigned to setpoint 1 (defined in parameter 11).
5DIG OUT 1Setpoint 1 output (defined in parameter 11).
Inputs
Normal ModeBatch Mode
6GND
7DIG IN 4Net/grossAbort
8DIG IN 3ZeroZero
9DIG IN 2TareStart Batch
10DIG IN 1Print Print
Table 2-4. TB3 Pin Assignments (Digital I/O)
Inputs 7 through 10 allow the zero, net/gross, tare, and print functions to be operated remotely by contact closure of
these inputs to digital ground.
Installation and Wiring11
Typically, digital outputs control relays which operate other equipment. Outputs 1 through 4 allow for setpoint and
zero band control.
Operational Mode
Relay Board TB3
TareStart BatchTB3-6IN2
ZeroZeroTB3-5IN3
Net/GrossAbortTB3-4IN4
Print PrintTB3-3IN5
TTL Inputs J11
KGR8924 CPU NormalBatch
Table 2-5. Relay Input Wiring
12UMC600 Installation Manual
3.0Configuration
ZERO
NET
GROSS
TARE
lb/kg
CONV
Prior to calibration, the UMC600 must be digitally
configured, or assigned a set of operating parameters.
The three parameters listed in Section 3.1.1 are directly
related to calibration and must be set before proceeding
to calibration mode.
3.1Digital Configuration
3.1.1Parameter Overview
Table 3-1 on page 14 lists configuration parameters and
describes their values. The following paragraphs give
the procedure for configuring the UMC600.
3.1.2Configuration Procedure
1. Unscrew the two screws on the face plate
bracket (Figure 3-1). The bracket drops down,
exposing four program switches on the left side
of the indicator.
CE
ENT
lb
kg
MOTION
PRINT
1 SET
POINT
2 SET
POINT
342
1
OPEN
ZERO
TARE
RECALL
ZERO
NET
GROSS
CAPACITY
NET
GROSS
5000 lb. X 0.5
TARE
162738495
0
lb/kg
CONV
When configuration is complete, set SW1-2 down to
return the unit to normal operating mode.
DEAD LOAD (3)
CONF (2)
CAL (1)
NORM
Parameter
Identifier
ZERO
NET
GROSS
NET
ZERO
GROSS
TARE
RECALL
1
342
OPEN
162738495
Figure 3-2. Closing Switch 2
CAPACITY
5000 lb. X 0.5
TARE
0
Selected Data
lb/kg
CONV
CE
ENT
lb
kg
MOTION
PRINT
1 SET
POINT
2 SET
POINT
Figure 3-3 defines the functional operation of each key
on the front panel of the indicator when the unit is in the
the setup mode.
ZeroNet/GrossTareUnits
Parameter
Select
NOTE: The TARE RECALL key functions as a previous
screen key in CONFIG mode.
Parameter Data
Select
Subparameter
Select
Subparameter
Data Select
Figure 3-3. Front Panel Key Functions
Figure 3-1. Accessing the Program Switches
2. Temporarily remove the unit’s flexible black
display overlay by gently pushing down and
lifting the panel up and out at its center to expose
the configuration and calibration instructions
printed on the surface below. The switch
function table defines the appropriate front panel
switch settings for the CONF and CAL modes.
3. Close switch SW1-2, marked
CONF (2), by
moving to the up position (see Figure 3-2). A
prompt appears with a parameter number and
data value.
The parameter identifier is a number, 1–14, that
correlates to the
CONFIG chart on the upper left of the
switch map panel. Selected data represents the value
being entered into the unit configuration data. For
example, 1 100 sets the indicator to 10,000 graduations
(see Table 3-2 on page 16).
Configuration13
3.1.3Digital Configuration Parameters
Table 3-1 (shown below) shows an overview of the 14 configuration parameters and their description.
Table 3-2 on page 16 lists the configuration display prompts (Prompt 1), and their value selections for displayed
graduations. Prior to calibration, the UMC600 must be digitally configured, or given its set of operating parameters.
The first three parameter selections are directly related to calibration and must be set up before proceeding to the
calibration mode. These parameters include;
• number of graduation
• resolution
• decimal point location in the weight data, all of which define the scale capacity.
ParameterDescriptionValues
1GraduationsNTEP to 10,000 (up to 80,000 available).
2Display resolution1, 2, 5, 10, 20, 50, 100
3Decimal point0.0, 0.00, 0.000, 0.0000, no decimal
5Digital averaging1, 2, 4, 8, 16, 32, A1 = 8-4-2; A2 = 16-8-4
6Tare modeATNR, AUTO, FIXED, BOTH (inhibit with motion)
7AZM bandOff, 0.5, 1, 3, 5, and 10 divisions
Use 0.5 for H-44, bench, counter and livestock applications; use 3 for vehicle,
axle-load, and railroad scales
8AZM/PAZ aperture±1.9%, 100% of capacity includes push-to-zero, H-44: 1.9%
9MotionOff, 1, 3, 5 divisions H-44: vehicle, axle, livestock, RR, 3.0; all other 1.0
10Displayed unitsLb, kg, con
11Setpoint modeSee Section 7.0 on page 55 for settings
12Zero bandOff, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 20, 30, 40, 50
13Weigh modeNormal, truck mode with transaction cancelled/stored, fixed/auto tare
14Serial outputPort 1, Port 2, demand, continuous, baud rate, G/T/N, or display
Table 3-1. Parameter Overview
14UMC600 Installation Manual
Figure 3-4 provides a graphic representation of the 14 configuration parameters associated with the UMC600.
Shown only if
SW1-2 is on
CONFIG
GRADS
100
selection
list,
see table 3-2
on page 16
Shown only if
SW1-1 is on
CALIBR
Options 1-11
shown only if
SW1-2 & 3 are on
OPTION 1 OPTION 2
RES
resolution
1
2
5
10
20
50
100
MOTION
band
Off
1
3
5
10
20
50
DECPT
decimal point
0.0
0.00
0.000
0.0000
OPTION 3
DISPLAY
kg
lb. conversion
digital average
A2=16-8-2
lb
OPTION 4
AVERAGE
1
2
4
8
16
32
A1=8-4-2
XXXXXXXXXXXXXXXXXXXXX
OPTION 5
ST PT
setpoint
off
SP
over/under
batch 1
batch 2
modes A - G
output
pos/neg
OPTION 6 OPTION 7 OPTION 8 OPTION 9 OPTION 10
TARE
enable tare
ATNR
AUTO
FIXED
BOTH
ZERO BAND
control output
AZM
band
OFF
0.5
1
3
5
10
Off
1
2
3
4
5
6
7
8
9
10
20
30
40
50
WEIGHT
mode
normal
truck
AZM/PAZ
band
1.9
FS
SERIAL
serial output
port 1 & 2
demand
continous
baud rate
G/T/N
display
OPTION 11
Figure 3-4. Configuration Menu
Refer to the following table numbers on the following pages for configuration display prompts.
Table NumberConfiguration Display PromptsPage
3-2116
3-32-316
3-45-717
3-58-1017
3-611-1418
Configuration15
Prompt DisplayInterpretationNotes
Displayed GraduationsNumber of Displayed Graduations = Scale Capacity
30No decimal point
30.0xxxxx.x
30.00xxxx.xx
30.000xxx.xxx
30.0000xx.xxxx
Displayed grads
Resolution is determined by the combination of parameters 2 and 3.
For example:
• If Parameter 2 = 1 and Parameter 3 = 0.00, display resolution is 0.01
• If Parameter 2 = 5 and Parameter 3 = 0.0, display resolution is 0.5
• If Parameter 2 = 10 and Parameter 3 = 0, display resolution is 10
Table 3-3. Configuration Display Prompts 2 – 3
16UMC600 Installation Manual
Prompt DisplayInterpretationNotes
No.
Digital Averaging
51110/sec
5225/sec
5442.5/sec
5881 sec
51616 2 sec
53232 4 sec
5A18-4-2Variable
5A216-8-4Variable
5A38-4-2VariableSelection available when option 1 is enabled. see Section 4.1.
5A416-8-2Variable
Tare EnableSelection of either fixed tare (Ft) or fixed tare and auto tare (both) in parameter 6
6AtnrAuto (stored) tare only
6AutoAuto (stored) tare only
6FtFixed (manual) tare
6bothAuto or fixed tare
AZM Capture Band (Displayed Grads)
7oFFOff
70.5±0.5
71±1.0
73±3.0
75±5.0Selection available when option 1 is enabled. See Section 4.1.
710±10.0
Averages
– no recall
only
Update
Rate
Display rate. Sets the update rate for displayed values.
allows up to a six digit fixed tare entry to be made using the numeric front panel
keys or, when configured for full duplex serial communication, a fixed tare entry
can be down loaded through the serial port.
Table 3-4. Configuration Display Prompts 5 – 7
Prompt DisplayInterpretationNotes
PAZ Aperture
81.9±1.9% of full scale
8FS100% of full scale
Motion Band
Display Grads/sec
9oFFOff
91±1.0
93±3.0
95±5.0
910±10.0
920±20.0Selections available when option 1 is enabled
950±50.0
Table 3-5. Configuration Display Prompts 8 –10
Configuration17
Prompt DisplayInterpretationNotes
Display Base (lb/kg)lb/kg CONV key functions only if parameter 10 is set to 10 Con
10lblb display only
10kgkg display only
10Conlb (base) conversion
Truck modeSee “Truck Weighing Mode” in Section 6.7, page 53, for details
13
Serial configurationSection 3.2 for details
14
for settings.
configurations. See Section 7.0 on page 55 for details.
18UMC600 Installation Manual
Table 3-6. Configuration Display Prompts 11 – 14
3.1.4Normal Configuration Setup Parameters
You must be in the configuration mode (SW1-2 closed to set the indicator from the PC) to be able to write
configuration parameters. To write commands the following Jxxyyzz<CR> sequence must be used. The following
parameters and their setup numbers are as follows: