USB port Configuration 41
485 Port (PC port) Configuration 42
Communication Protocols 43
Standard String 43
Extended String 43
Serial Commands 44
Modbus Protocol 47
Diagnostics 49
Programming the Setpoints 50
Restoring Factory Settings 51
Alarms 52
6 Visit our website www.RiceLake.com
Introduction
Thank you for purchasing this product.
This manual contains instructions for correct installation and commissioning of the SCT-1SX digital weight transmitters, including the
following SCT-1SX models::
•SCT-1SX-AN
•SCT-1SX-PRONET
•SCT-1SX-E/IP
•SCT-1SX-MODTCP
Also, this manual provides information on the correct operation and maintenance of the weigh transmitter. It is essential to pay the close
attention to operation procedures.
It is recommended that you carefully follow the instructions for programming the weight transmitter; performing actions not indicated in
this manual could compromise the functionality of the scale.
Manuals are available from Rice Lake Weighing Systems at www.ricelake.com/manuals
i
Warranty information is available at www.ricelake.com/warranties
Any problem with the product must be reported to the manufacturer or to the retailer where it was purchased.
Always TURN OFF THE POWER SUPPLY prior to installation or repair action.
Observe the following conditions for correct installation of the transmitter and the load receiver:
•Flat, level support surface.
•Stability and absence of vibrations.
•Absence of aggressive dusts and vapor.
•Absence of drafts.
•Ensure the platform is level or that the load cells are evenly supported.
•Moderate temperature and humidity: 59°F - 86°F (15°C - 30°C) and 40% - 70%.
•Do not install in an environment where there is a risk of explosion.
•All transmitter connections must be made in accordance with applicable regulations in the area and environment of installation.
Read the electrical precautions listed in the section “Electrical Precautions”.
•Ensure the system is correctly grounded, see the relevant section “System Grounding”.
•Do not perform welding when the load cells have already been installed.
•If necessary, use watertight sheaths and fittings to protect the load cell cables.
•Any junction boxes must be watertight.
•Anything not expressly described in this manual constitutes improper use of the equipment.
8 Visit our website www.RiceLake.com
Electrical Precautions
•Use a regulated mains supply within ± 10% of the rated voltage.
•The electrical protections (fuses, etc.) are the responsibility of the installer.
•Observe the recommended minimum distances between cables of dierent categories (see table on page 10).
•The following cables must comply with the maximum permissible lengths (see table on page 10), they must be shielded and must be
inserted alone in metal conduits or pipes:
- the load cell extension cables;
- the signal amplifier cables;
- the cables for connecting the serial ports;
- the analog output cables.
•The cell or amplifier cables must have an independent input in the electrical panel. They must be connected (if possible) directly to
the terminal block of the transmitter without passing through the conduit with other cables.
•Fit “RC” filters:
- on the contactor coils;
- on the solenoid valve coils;
- on all devices that produce electrical interference.
•If condensation can occur inside the weight transmitter, it is advisable to keep the equipment powered at all times.
•Connections to load cells and any external device must be as short as possible.
•The cable ends (connectors, leads, terminals, etc.) must be installed correctly; the cable shielding must be kept intact until close to
the connection point.
•If the transmitter is placed inside an electrical panel, a shielded cable must also be used for the power supply.
analog digital signals
< 25 V (sensors, load
cells...).
Low voltage power
supply cables (< 60 V).
Coaxial cables.
MAXIMUM ALLOWED LENGTHS
Load cellRS232RS485Analog output
164 ft (50 m) with 6 x 24
AWG (0.25 mm
328 ft (100 m) with 6 x 22
AWG (0.5 mm
2)
cable;
2)
cable.
49 ft (15 m) with baud
rate up to 19200.
DC supply cables with
voltage > 60 V and <
400 V.
AC supply cables with
voltage > 25 V and <
400 V.
3937 ft (1200 m) with
shielded 2 x 24 AWG
twisted pair with outer
braid + aluminium strip.
Power supply cables
with voltage > 400 V.
Telephone cables.
Any cable subject to
lightning danger.
CURRENT:
•328 ft (100 m) with 2 x 24 AWG (0.25 mm
cable);
•492 ft (150 m) with 2 x 22 AWG (0.5 mm
cable);
•984 ft (300 m) with 2 x 17 AWG (1 mm
cable).
VOLTAGE:
•164 ft (50 m) with 2 x 24 AWG (0.25 mm
cable);
•246 ft (75 m) with 2 x 22 AWG (0.5 mm
cable);
•150 meters with 2 x 17 AWG (1 mm2 cable).
2
2
2
2
2
10 Visit our website www.RiceLake.com
System Grounding
For correct earthing and optimal system operation, the transmitter, load cells, junction box, if any, and weighing structure must be
earthed.
TRANSMITTER
The earth connection must be made via the appropriate terminal. The cable cross-section must be less than 14 AWG (2.5 mm
2
). The
transmitter must be powered by a dedicated power supply with earth reference. Do not connect EARTH and GND terminals together!
SCT-1SX Correct earth connection
1 2
GND Vdc
+-
SCT-1SX
Incorrect earth connection
1 2
GND Vdc
+-
LOAD CELLS AND JUNCTION BOX
The connection must be made by connecting the ground cables to the ground bar (cables that must have a cross-section of at least 6
AWG/16 mm
2
); finally, connect the earth bar to the earth post with a cable having a cross-section of at least 1-1/0 AWG (50 mm2).
EXAMPLES:
• If more load cells are connected to the transmitter through a junction box, the cable shield from the transmitter and the cell cable shields
must be connected to the earth socket of the junction box (refer to the junction box manual) and the junction box must be earthed using
a copper cable with a cross-section of not less than
6 AWG (16 mm2)
.
• If the load cell is connected directly to the transmitter (without using the junction box), the cell cable shields must be connected to
theearthing point (or earth bar).
• If the weighing system involves large and/or outdoor structures (weighbridges, silos, etc.) and the distance between the junction box
andthe weight transmitter is greater than 33 ft (10 m), connect the cell cable shields to the earth socket in the junction box.
WEIGHING STRUCTURE
Earth the weighing structure and/or any unconnected structures (e.g. silos that release material onto the weighing structure) using cables
with a cross-section of not less than 6 AWG (16 mm
2
).
Also connect the upper part with the lower part of each cell by means of a copper braid with a cross-section not less than 6 AWG (16
2
mm
) (refer to the grounding examples on page 12 and page 13).
SERIAL CABLES AND CONNECTED INSTRUMENTS
Connect the serial cable shield to the earthing point (or earth bar) inside the panel. To avoid any undesired eects, the earth reference of
the connection cable, power supply and transmitter must be at the same potential.
•All earth cables must be of suitable length, so as to obtain an overall resistance of the earthing system of less than 1 .
•If the weighing system involves large and/or outdoor structures (weighbridges, silos, etc.):
- the earth connection must be made by connecting the earth cables to an earth bar and the earth bar to the earth post
with a cable having a cross-section of not less than 1-1/0 AWG (50 mm2);
- the earth post must be placed at a distance of at least 33 ft (10 m) from the structure.
•If the load receiver is more than 33 ft (10 m) from the transmitter, we recommend using the SENSE line and load cells
equipped with a (SENSE) compensation circuit.
12 Visit our website www.RiceLake.com
EXAMPLE OF GROUNDING OF A WEIGHBRIDGE
Junction box
placed on the side wall of the pit
Weight transmitter
Load cell
Weighbridge
Weighbridge
Drilled copper plate positioned
on the side wall
Load cell bypass jumper
Ground cables
Ø 8 - sec. 1-1/0 AWG (50 mm
Ø 11.3 - sec. 95 AWG (100 mm
Earth post
positioned under
or near the
weighbridge
•Voltage: 0 - 5 VDC, 0 - 10 VDC.
The maximum applicable resistance on the current output is 300 while the minimum applicable resistance on the voltage output is 1 k.
After carrying out the instructions for the platform or load receiver, the shielded cable from the cell must be properly connected to the
terminal block of the transmitter (see page 17).
The transmitter has one channel for 6-wire connection to load cells (using the REFERENCE).
The REFERENCE allows you to compensate for any voltage drop on the section of cable connecting the transmitter to the load receiver.
It is especially useful when the distance between the transmitter and the load receiver is more than 32 ft (10 meters), or in high-resolution
applications.
Semi-automatic zeroing.
Decreases the selected digit.
Semi-automatic tare.
Increases the selected digit.
Activates the function.
Selects the digit to be changed.
Confirms a value.
Prints / Transmits data.
C
Reboots the transmitter.
C
1 2 3 4 5 6
NumberDescription
1
2
3
4
5
6
Gross weight on zero.
Unstable weight.
A tare is active.
A special function is active.
Output 1 is active.
Output 2 is active.
Quick Menu
The transmitter is equipped with a quick menu, through which you can program the main parameters of the scale.
To enter the quick menu, follow the procedure below:
1. Reboot the transmitter.
2. Press the
For further information, refer to the transmitter Quick Start Guide.
Gravity of calibration zone / zone of use (page 30).
4
Calib
5
0.Calib
6
unit 2
1
deCi
2
u.m.
3
div
4
ranGe1
5
ranGe2
6
Calib.p
7
theo.Ca
8
adj.Cal
9
man.Cal
Calibration parameters
Real calibration with sample weights (page 24).
Theoretical calibration (page 23).
Calibration adjustment.
Manual calibration (page 26).
Zero calibration (page 26).
Second unit configuration (page 36).
Complete menu
on pages
21 - 22
22 Visit our website www.RiceLake.com
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
LEGEND:
Theoretical Calibration
888888f.mode
A
CALIBRATION PROCEDURE:
1
ConfiG
1B
4
pre.CalSetup
Calib
1
deCi
2
u.m.
3
div
4
ranGe1
7
theo.Ca
1
Cel.sen
2
Cel.CAp
3
dead.ld
4
kno.wGt
1. Set the calibration parameters:
deCi= Number of decimals.
u.m.= Unit of measurement (kG, G, t, lb).
div= Minimum division.
ranGe1 = Maximum range.
2. Set the cell data:
sen.Cel = Cell sensitivity (given by the average mV/V value of cells).
Cel.Cap = Total capacity of the cells (given by the sum of the capacities of each cell).
3. Enter the weight value of the structure in the dead.ld parameter. If you do not know this value, enter “0”.
4. If the structure contains a quantity of material whose weight value is known (e.g. full silo), enter this value in the KNo.WGT parameter.
5. Application of theoretical calibration:
Press the
calibration, or the
C key to exit the calibration menu. The display shows th.Cal?. Press the key to confirm the use of the theoretical
If you know the number of ADC converter points for a known weight (for example if you want to copy the calibration from one transmitter
to another) the calibration points can be entered manually:
1. The display shows mod.pnt, and then the last calibration point.
2. Using the
Press the
3. The display shows weiGht, use the
Press the
4. The display shows points, use the
Press the
A
f.mode
B
Setup
and keys, select the calibration point you want to enter / change (from 0 to 8).
key to confirm.
key to confirm.
key to confirm.
11
ConfiGpre.Cal
4
Calib
, and keys to enter the weight value.
, and keys to enter the converter points value.
1
deCi
8
man.Cal
i
Repeat procedure for each calibratin point.
Quick Zero Calibration (Pre-tare Reset)
888888
ADC
A
f.mode
B
Setup
11
ConfiGpre.Cal
5
0.Calib
ADC
Tp 0Tp n
Complete menu
on pages
21 - 22
26 Visit our website www.RiceLake.com
Kg
Tp 0Tp n
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
Kg
LEGEND:
ADC Converter Precalibration
888888
A
f.mode
B
Setup
Filter and Stability
Filter adjustment
888888
A
f.mode
B
Setup
1
ConfiG
1
ConfiG
1
1
pre.CAl
Param
1
1
pre.CAl
Param
For manufacturer use only
1
12
FilterUpdating frequency (Hz)Response time (ms)Use
F 1
f 2
f 3
f 4
f 5
f 6
f 7
f 8
f 9
f 10
F 11
55000High resolution or
102500
201000Simple weighing
40450
80300
160150
32550
65035
130020
260010
48005
i
In the case of an approved transmitter, it is possible to select only filter F 3.
Stabil
StabilParam
loads
Dosing
High-speed weight
transmission
The filter aects the speed of the PC port only if ALL.MAX mode has been selected.
The transmitter has an additional filter for the elimination of sudden weight peaks (e.g. shocks or falling material).
The following parameters, opportunely configured, allow you to eliminate the peak by blocking the weight for its entire duration.
The weight is blocked if it remains within the number of divisions set in PK.LK.DV for the time set in PK.LK.TM and is subsequently
unblocked if the weight deviates from the blocking value for a number of divisions greater than PK.DIV (or PK.BN.DV) or if the time set in
PK.TIME has elapsed.
888888
A
F.Mode
B
Setup
1
ConfiG
1
pre.Cal
21
paramstabil
91
Peak.flP k.l k.d v
2
P k.l k.t m
3
Pk.div
4
P k.b n.d v
5
Pk.time
Stability Detection Divisions
It is possible to decide that tare and zero functions (from keypad or serial command / PLC) are performed only if the weight is stable.
888888
A
f.mode
B
Setup
1
ConfiG
1
pre.Cal
21
Paramstabil
6
div.stb
The value 0 disables the stability control.
By entering a value other than 0, you enable stability control.
Enter the number of deviation divisions beyond which the transmitter detects instability.
Complete menu
on pages
21 - 22
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
From 0 to 99.
= 02.
= 02.
28 Visit our website www.RiceLake.com
LEGEND:
Stability Detection Time
888888
A
f.mode
B
Setup
1
ConfiG
1
pre.Cal
2
Param
1
stabil
7
tim.stb
If the weight remains within the number of divisions set in DIV.STB for the time set in this parameter, the weight is
stable.
Enter the value in ms. In case of a restricted transmitter, the value is fixed at 500 ms.
Additional Filter for Stability Detection
888888
A
f.mode
from 10 to 10000.
500.
= 500.
B
Setup
1
ConfiG
1
pre.Cal
2
Param
1
stabil
8
stb.flt
1
S.f.time
2
S.F.divs
Additional filter that locks the weight if it oscillates around a value for a maximum of 10 divisions. The weight is
unlocked if the value increases/decreases for the number of divsions set in in the parameter S.T.DIVS for a time
value greater than the time set in the parameter S.T.TIME.
The value 0 disables the filter.
This parameter allows you to correct the gravity acceleration value.
Before calibration, set the value of the calibration zone.
Next, set this value to the value of the zone of use.
Any dierence between the two values will be automatically compensated.
i
In the case of legal for trade transmitters, the value is read-only.
EXAMPLE:
From 9.75001 to 9.84999.
= 9.80543.
1.
Before calibration, in the GRAV parameter enter the value
9.80543.
2. Calibrate the transmitter.
Calibration zone
Italy
g = 9.80543
Zone of use
Wisconsin
g = 9
.80549
3. Before using the transmitter, in the GRAV parameter enter the
value 9.80549.
Complete menu
on pages
21 - 22
30 Visit our website www.RiceLake.com
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
LEGEND:
Reset Functions and Parameters
888888
A
f.mode
B
Setup
11
ConfiGPre.Cal
Auto-zeroing on Start-up
2
auto.0
1
2
disab
enab
1
C.perC
21
paramstabil
2
auto.0
3
0-perC
4
0.traCk
5
0.trk.sp
Disabled.
Enabled, enter in C.PERC the % value of the capacity.
% auto-zeroing on start-up.
% manual zeroing.
Zero tracking.
Zero tracking time.
from 0 to 50%.
from 0 to 10%.
Maximum Percentage of Manual Zeroing
3
0-perc
Indicates repeated pressing of
key.
the
Indicates the weight value that can be zeroed by key or command.
The value is expressed as % of the full scale. For example: if the scale has a full scale
(RANGE1) of 1000 kg, by setting 3% it is possible to zero up to 30 kg.
The value 0 disables the ZERO key and the zeroing commands.
This menu allows to set zero tracking, i.e. the compensation parameter of the thermal drift of the scale; the set value corresponds to
the number of divisions that is reset to zero in the fixed time of 1 second.
4
0.traCk
1
tr 10
2
3
4
5
6
7
8
9
TR no
tr 8
tr 6
tr 4
tr 2
tr 1
tr1/2
tr1/4
Zero Tracking Time
5
0.trk.sp
Once stability is reached, the transmitter waits for the time set in this parameter before
bringing the weight back to zero (if it is within the divisions set in 0.traCk).
10 divisions.
8 divisions.
6 divisions.
4 divisions.
2 divisions.
1 division.
1/2 division.
1/4 division.
Tracking disabled.
from 100 to 5000
.
1000
= 1000.
.
Restoring Zero
888888F.mode
A
1
funCt
5
rs.zero
DISAB
ENAB
Zero restoring disabled.
Zero restoring enabled.
If auto.0 = disab:
The last zero in the memory before turning o the power is always
restored.
auto.0 =
If
The last zero in the memory before turning o the power is restored
only if the auto-zeroing fails.
enab /
CyCle:
Semi-automatic Zeroing
By pressing the key, or sending the zero command, the transmitter zeroes the gross weight on the scale. For a moment the display
shows “zero” and then it shows 0 (gross weight).
The semi-automatic zeroing cannot be performed if:
•The weight on the scale is greater than the zero capacity (0.perC).
•The weight is unstable.
Complete menu
on pages
21 - 22
32 Visit our website www.RiceLake.com
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
LEGEND:
Tare Functions and Parameters
Tare Mode
888888F.mode
A
1
5
funCt
tare
loCk
unloCK
Disab
Tare blocked. When the gross weight drops to 0, the tare remains
engaged.
Tare unlocked. When the gross weight drops to 0, the tare is cleared.
Tare disabled.
Semi-automatic tare
By pressing the key, or sending the tare command, the transmitter sets as tare the weight on the scale. For a moment the display shows
“tare” and then it shows 0 (net weight). The
The semi-automatic tare cannot be performed if:
• The weight is less than one division.
• The weight is overloaded.
3 light indicates that the net weight is shown on the display.
Predetermined Tare
By holding down the key, or by means of the predetermined tare command, it is possible to enter a tare value manually.
For a moment the display shows “-tm-” and shows the tare present (or 0 if no tare is present).
Enter the tare value and press
to confirm.
Clearing the Tare
The tare can be cleared in dierent ways:
• By unloading the scale and performing a semi-automatic tare.
• By entering a predetermined tare value of 0.
• If the weight is negative, pressing the ke y.
Restoring the Tare
888888F.mode
A
1
funCt
5
rs.tare
DISAB
ENAB
Restoring tare disabled.
Restoring tare enabled. When restarting, the last tare in the memory
before turning o the power is restored.
The alibi memory allows you to store the weight values transmitted to the computer for further processing and/or data integration.
The stored values can then be retrieved from the PC port or directly on the display of the transmitter for later checking.
Enabling the Alibi Memory
888888F.mode
C
11
funCtviss
4
alibi
Saving a Weighing Operation in the Alibi Memory
A weighing operation is stored after receiving the PID serial command (see “Serial commands”page 44) or after pressing the
The transmitter transmits on the PC port the gross weight, the tare and an ID code that uniquely identifies the weighing. The ID has the
following format:
• rewrite number: 5-digit number (from 00000 to 00255) indicating the number of complete rewrites;
• weighing number: 6-digit number (from 000000 to 131072) indicating the weighing number in the current rewrite.
Each time it is saved, the weighing number is increased by 1; when it reaches the value 131072, it starts again from 000000 and the
rewrite number is increased by 1.
Example
If the weighing that has been saved is as follows:
PIDST,1, 1.000lb, 1.000lb,00126-131072
The next one will be:
PIDST,1, 1.000lb, 1.000lb,00127-000000
A weighing operation can only be saved if the weight ≥ 0, stable and valid (not underloaded or overloaded).
To store the weighing operation by key, the function must be active.
In addition, if the transmitter is restricted, the weight must exceed 20 divisions.
key.
If these conditions are not met:
• the response to the PID command will have “NO” instead of the ID (PIDST,1, 1.000lb, 1.000lb,NO);
• there is no transmission when the
Complete menu
on pages
21 - 22
key is pressed.
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
34 Visit our website www.RiceLake.com
LEGEND:
Reading the Alibi Memory
FROM THE TRANSMITTER (MANUAL)
By pressing the
you will be asked to enter the rewrite number “rew.id” (from 0 to 255) and the ID number “id” (from 0 to 131072).
The weighing data are shown. Use the
•“Ch. X”, where X indicates the scale number.
•“Um YY”, where YY indicates the unit of measurement (kG, G, t or lb).
•“Gross”, followed by the gross weight.
•“Tare / tarept”, followed by the tare value.
Press the
The weighing of an ID can only be verified if:
• it has a rewrite number equal to the current alibi memory number and a weighing number ≤ the last value received with the PID command;
• it has a rewrite number ≥ 0, but 1 less than the current alibi memory value, and a weighing number greater than the last value received
with the PID command.
FROM PC
T
o read a weighing operation from a PC,
C key to return to weighing.
key you can read a saved weight:
and keys to scroll through the following information:
see the serial command “READING A WEIGHING OPERATION IN THE ALIBI MEMORY” on
page 46.
FROM PLC
To read a weighing operation from a PLC,
refer to the Modbus and Fieldbus protocol manuals.
i
If the alibi memory is empty, when the key is pressed the display shows “empty” for one second and returns to weighing mode.
If an invalid ID is entered, the display shows “No id” and returns to weighing mode.
Initializing the Alibi Memory
888888
i
This operation deletes all saved weighing operations; it is not possible to delete a weighing operation individually.
A
f.mode
B
Setup
Indicates repeated pressing of
key.
the
1
ConfiG
4
ini.al
Parameter visible only
under certain conditions.
Not visible if the transmitter is legal for trade.
Weight display in high resolution (x10). Press the key to activate or deactivate the function.
When the weight is displayed in high resolution, the
In the case of a restricted transmitter, the high-resolution weight display is automatically deactivated after 5 seconds.
Peak Detection
peak
Detection of the maximum weight value during a time interval. Press the key to activate the function. The display shows
“-peak-” every 5 sec and the transmitter shows the maximum weight reached since the function was activated.
To deactivate the function press the
weight again.
11
funCtviss
2
3
4
5
peak
Conver
alibi
none
No function
4 light is lit.
again, the display shows “peakof” for a moment and shows the instantaneous
Converting Units of Measure
conver
Converting the scale unit of measurement using a free conversion factor. Press the
next available unit. By holding down the
weight.
Example: to show the cubic meters of water on the scale, enter the value 997 as the conversion factor. The
key can be used to switch from the main unit of measurement to the secondary unit at any time.
When the secondary unit of measurement is displayed, the
888888
A
f.mode
B
Setup
Alibi Memory
alibi
(See section “Alibi memory” page 34).
Complete menu
on pages
21 - 22
key, you can enter a free conversion factor, which will be multiplied by the
11
ConfiGpre.Cal
6
Unit 2
Press the key during the startup procedure.
4 light is lit.
1
deCi 2
2
u.m. 2
3
div 2
Press the
SAVE?
key to convert the weight to the
Second unit decimals.
Second unit of measure (LB / Custom).
Second unit division.
key several times, until the display shows
. Press the key to confirm.
36 Visit our website www.RiceLake.com
LEGEND:
Input Configuration
The indicator has two configurable inputs (bidirectional optocouplers).
888888
INPUT CONNECTION:
A
f.mode
B
Setup
1
ConfiG
5
inputs
1
inp.01
2
inp.02
Such as inp.02 ( = zero).
1
NoNE
2
zero
3
tare
4
mode
5
print
6
C
7
off
8
Dis.key
No function.
key.
key.
key.
key.
C key.
Reboots the transmitter.
Disable keypad (and re-enable).
345
VdcGND
Indicates repeated pressing of
key.
the
i
The input is activated when there is a potential dierence
IN2) and terminal 3 (INCOM). The inputs are bidirectional, therefore it is possible to invert GND
and Vdc.
Connect a multimeter to the
Enter the parameter to be changed:
ao 0v / ao 10v / ao 0ma /
ao.20ma
Voltage output
63300 ~ 10 V
0 ~ 0 V
and set an approximate value.
transmitter
Current output
58200 ~ 20 mA
0 ~ 0 mA
D
Press
the multimeter.
to update the output value on
B
.
Press to update the output value on
the multimeter.
E
Repeat the procedure from point “
until the desired value is reached, then
press
to save.
C”
C
Increase or decrease the D/A points
value to reach the desired output.
100 D/A points ~ 0.015 V - 0.035 mA
1000 D/A points ~ 0.15 V - 0.35 mA
Example:
Increase
to 63550.
ao 10v
from 63300
F
Save the changes (press the
several times until you reach the
message
key to confirm).
save?
, then press the
C key
ANALOG OUTPUT GRAPHS:
Positive weight operation
i
Voltage or current operation is determined by the connection to the transmitter terminals:
Current: 9 (+) and 10 (-).
Voltage: 11 (+) and 12 (-).
Negative weight operation
Complete menu
on pages
21 - 22
40 Visit our website www.RiceLake.com
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
LEGEND:
Serial Communication Configuration
All models are equipped with a micro-USB port that is always accessible for transmitter configuration and diagnostics.
The SCT-1SX and SCT-1SX-AN models also have an RS485 port.
888888
A
f.mode
B
Setup
1
ConfiG
3
serial
USB port Configuration
1
com.PC
2
usb
1
PCmode
2
baud
3
parity
4
5
stop
bit
Visible only on SCT-1SX-AN models.
Transmission mode.
Baud rate.
Parity.
Data bits.
Stop bits.
888888
A
f.mode
B
Setup
1
ConfiG
3
serial
1
com.PC
2
Usb
Useful for the configuration of the instrument from PC with Rice Lake Tools.
By selecting the PC port on demand mode (onde), you can communicate with the transmitter via serial commands.
For each command received, the transmitter emits a string containing the response (refer to the command description) or one of the following
signals:
OK<CRLF>Command sent when sending a correct command. This response does not imply that the command is executed.
ERR01<CRLF>Command sent correctly but followed by letters entered unintentionally (e.g. READF, TARES).
ERR02<CRLF>Incorrect command data.
ERR03<CRLF>Command sent not allowed (transmitter busy, or not used in the selected operating mode).
ERR04<CRLF>Command sent non-existent.
i
If the 485 protocol has been selected, you must precede the command with the transmitter address (e.g. 01READ).
WEIGHT READING (standard string)
Format
Response
WEIGHT READING IN HIGH RESOLUTION X10AUTOMATIC TARE
Format
Response
READ <CR LF>
Standard string<CR LF>.
GR10<CR LF>
Standard string with weight in resolution x10 <CR LF>.
EXTENDED WEIGHT READING
Format
Response
Format
Response
REXT<CR LF>
Extended string<CR LF>.
TARE[I] <CR LF>
OK<CR LF> (or ERRxx).
Send the TAREI command to perform tare without
stability control.
MANUAL TARE
Format
Where
Response
TMANtttttt
<CR LF>
tttttttare value
OK<CR LF> (or ERRxx).
ZEROING
Format
Response
ZERO[I] <CR LF>
OK<CR LF> (or ERRxx).
Send the ZEROI command to perform zeroing without
By entering a manual tare value of 0, the tare on the
To simulate pressing a key, you must send the KEYP and
KEYR commands in succession.
If more than 1.5 s pass after the KEYP command is sent,
the transmitter will execute the function associated with
prolonged pressing of the key.
Response
RELEASING A KEYBRIDGE BETWEEN THE SERIAL PORTS
Format
Response
SCALE INFORMATION
Format
Response
Where
OK<CR LF> (or ERRxx).
KEYR<CR LF>
OK<CR LF> (or ERRxx).
RALL<CR LF>
ss,b,NNNNNNuu,LLLLLLuu,
YYTTTTTTuu,SSS,AAA,CCCC
,,RRRRR-IIIIII<CR LF >
UL = Underload.
ss
bNumber of the active scale.
NNNNNNuu Net weight with unit of measurement.
LLLLLLuuGross weight with unit of measurement.
YYPT if a manual tare is present or “ ”.
TTTTTTuuTare with unit of measurement.
SSS
AAA
CCCCCode of last key pressed.
RRRRRLast rewrite number saved to Alibi memory.
IIIIIILast ID number saved to Alibi memory.
OL = Overload.
ST = Stable weight.
US = Unstable weight.
Scale status:
000 = scale weighing.
001 = entering a numerical value.
002 = scale in technical menu.
Last command result.
Last command result.
Last command result.
Processed command count.
Processed command count.
Processed command count.
Processed command count.
(lsb)
No function.
Bit 7
No function.
(msb)
...
Bit 2
Bit 1
Bit 0
...
No function.
Digital output 1 status (0 = OFF; 1 = ON).
Digital output 2 status (0 = OFF; 1 = ON).
(lsb)
This manual contains the main registers for reading data / sending commands.
Refer to the Modbus protocol manual for a complete list of available registers.
First command parameter.
The parameter is always expressed as an absolute value (no decimal / sign).
Second command parameter.
The parameter is always expressed as an absolute value (no decimal / sign).
EXAMPLE 2
To reset the weight on the scale:
2. Set the command in register 40001
To set a predetermined tare of 1000kg:
1. Set the value in parameter 1 (registers 40002-40003)
2. Set the command in register 40001
Byte
Value
100 Hex
201 Hex
Byte
100 Hex
203 Hex
3
400 Hex
503 Hex
6
This manual contains the main registers for reading data / sending commands.
Refer to the Modbus protocol manual for a complete list of available registers.
(MSB)
(LSB)
Value
00 Hex
E8 Hex
48 Visit our website www.RiceLake.com
LEGEND:
Diagnostics
888888
1
prG.ver
2
manuf.d
3
div.int
4
adC.uv
A
TYPE
C
diaG
Display of firmware release (e.g. 01.06.00).
Display of firmware libraries (for use by the manufacturer).
Display of calibration internal divisions.
Display of the V related to the weight on the scale.
For correct operation, the value of the V of each channel must be less than 30000 with a weight equal to the maximum capacity.
This value must be stable, and increase if a load is applied to the cell.
5
ADC.pnt
Display of the A/D points of the converter related to the weight on the scale.
For correct operation, the value of A/D points must be stable, and increase if a load is applied to the cell.
6
weiGht
Display of the weight on the scale.
7
Cal.pts
8
displa
9
keyb
10
output
11
inputs
Display of calibration points with corresponding A/D point values.
Activation of all display segments and indicators.
The code of last key pressed is shown on the display:
8001
8002
8003
8004
80AA
C
Press the same key 3 consecutive times to exit.
Activation of the output shown on the display (rel.1 / rel.2).
Use the
Checking the status of the inputs:
value 0 indicates that the input is disabled, value 1 indicates that the input is enabled.
Use the
, , keys to enter the D/A point value of the analog output.
key to confirm and update the V / mA value of the analog output.
13
ser.num
14
Cel.Chk
Display of transmitter serial number.
Voltage value test (used to display load cell error "CEL.ERR").
Programming the Setpoints
In weighing mode, if the output functions (1 Gross / 2 net) have been set correctly, pressing for 3 seconds will enter the setpoint
programming menu:
s.1 on0.000
s.1 off
s.2 on
s.2 off
Once you have entered the desired values, press
Output 1 activation value.
Output 1 deactivation value.
Output 2 activation value.
Output 2 deactivation value
C. The display shows “store” and returns to weighing mode.
visible only if rl.ist = ist.on
.
visible only if rl.ist = ist.on
Complete menu
on pages
21 - 22
50 Visit our website www.RiceLake.com
Press the key during the startup procedure.
Press the
key several times, until the display shows
SAVE?
. Press the key to confirm.
LEGEND:
Restoring Factory Settings
888888
A
f.mode
B
Setup
1
ConfiG
8
defau
The transmitter is initialized and the default parameters (indicated by the symbol) are activated. Pressing
the display shows “dflt?” confirm further with or exit by pressing another key.
The actual activation of the default parameters is performed by saving the settings (save?) while exiting the menu.
Displayed if you try to calibrate a point without first confirming the number of calibration points (ntp).
Calibration error: unstable weight during point acquisition.
Calibration error: during the acquisition of a calibration point a NULL value was read from the converter.
Error that occurs if the capacity of channel X is not set, or there is an error in the calibration parameters of
channel X, where X indicates the number of the channel to which the error refers.
Error that occurs if the capacity of channel X is not set, or there is an error in the calibration parameters of
channel X, where X indicates the number of the channel to which the error refers.
Calibration error: a sample weight that is too low was used; it is recommended to use a weight of at least half
the scale’s capacity.
Calibration error: The acquired calibration point (tp1 / tp2 / tp3) is equal to the zero point (tp0).
Scale to be calibrated (we recommend resetting the transmitter to the factory default “defau” settings before
proceeding).
Scale to be calibrated (we recommend resetting the transmitter to the factory default “defau” settings before
proceeding).
Negative internal points were calculated during calibration:
•the calibration point is below the zero point;
•the signal is negative (check the connections).
Internal points below the minimum value were calculated during calibration:
•the calibration point is equal to the zero point;
•too high a capacity has been set with respect to the division.
Hardware error: software not compatible with the installed hardware.
al.err
busy
unstab
un.over
------
------
Gros.er
ner.err
no.0.uns
Conv
err,CLk
Cel.err
Displayed when the alibi memory is enabled and the transmitter does not detect the presence of the card
when the power is turned on. The Conv function is set automatically, but not saved in the setup environment.
Printing in progress (printer serial port busy) or transmitter waiting to transmit a print to PC.
You are trying to print with an unstable weight.
You are trying to print with the weight in underload / overload.
The weight is overloaded (9 divisions over the maximum capacity).