Rheem RRNA-B SERIES Installation Instructions Manual

Page 1
92-21916-28-03
SUPERSEDES 92-21916-28-02
PACKAGE GAS ELECTRIC
RRNA-B SERIES (2-5 TONS)
INSTALLATION INSTRUCTIONS
ISO 9001:2000
Page 2
2
I. Table of Contents ..................................................................................................2
II. Introduction............................................................................................................3
III. Checking Product Received ..................................................................................3
IV. Specifications ........................................................................................................3
A. General .............................................................................................................3
B. Major Components............................................................................................3
V. Safety Information .................................................................................................4
VI. Unit Dimensions ....................................................................................................5
VII. Installation .............................................................................................................7
A. General .............................................................................................................7
1. Pre-Installation Check ..................................................................................7
2. Location Considerations...............................................................................7
B. Outside Installation............................................................................................8
C. Attaching Exhaust and Combustion Air Inlet Hoods .........................................9
D. Cover Panel Installation/Conversion Procedure ...............................................9
1. Horizontal to Downflow .................................................................................9
2. Downflow to Horizontal .................................................................................9
E. Clearances ......................................................................................................11
F. Rooftop Installation .........................................................................................13
G. Ductwork .........................................................................................................13
H. Return Air........................................................................................................14
I. Filters ..............................................................................................................14
VIII. Gas Supply, Condensate Drain and Piping .........................................................16
A. Gas Connection ..............................................................................................16
B. LP Conversion.................................................................................................17
C. NOx Models ....................................................................................................18
D. Adjusting or Checking Furnace Input..............................................................18
E. Condensate Drain ...........................................................................................19
IX. Wiring ..................................................................................................................19
A. Power Supply ..................................................................................................19
B. Hook Up ..........................................................................................................21
C. Internal Wiring.................................................................................................21
D. Thermostat......................................................................................................21
X. Furnace Section Controls and Ignition System ...................................................22
Normal Furnace Operating Sequence.................................................................22
Operating Instructions .........................................................................................23
Burners ................................................................................................................24
Manual Reset Overtemperature Control..............................................................24
Pressure Switch...................................................................................................24
Limit Control ........................................................................................................24
XI. System Operating Information.............................................................................24
Advise the Customer ...........................................................................................24
Furnace Section Maintenance.............................................................................24
Lubrication ...........................................................................................................25
Cooling Section Maintenance..............................................................................26
Replacement Parts ..............................................................................................27
Troubleshooting...................................................................................................27
Wiring Diagrams ..................................................................................................27
Charging ..............................................................................................................27
Blower Motor Speed Taps ...................................................................................27
XII. General Data ..................................................................................................29-41
XIII. Miscellaneous......................................................................................................42
Electrical Data ....................................................................................................42
Airflow Performance .......................................................................................43-44
Wiring Diagrams.............................................................................................45-49
Charge Charts ................................................................................................50-55
Troubleshooting..............................................................................................56-57
Page 3
3
II. INTRODUCTION
This booklet contains the installation and operating instructions for your combination gas heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference.
III. CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. IMPORTANT: Check the unit model number, heating size, electrical characteristics, and accessories to determine if they are correct.
IV. SPECIFICATIONS
A. GENERAL
The Combination Gas Heating/Electric Cooling Rooftop is available in 40,60, 80 and 100 BTU/Hr. heating inputs and cooling capacities of 1
1
2, 2, 21⁄2, 3, 31⁄2 , 4 and 5 nominal tons of cooling. Units are convertible from end supply and return to bottom supply and return by relocation of supply and return air access panels. See cover installation detail.
The units are weatherized for mounting outside of the building.
The information on the rating plate is in compliance with the FTC and DOE rating for sin­gle phase units. The following information is for three phase units which are not covered under the DOE certification program.
1. The energy consumption of the ignition system used with this unit is 9 watts.
2. The efficiency rating of this unit is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with capillary tube assembly), a circulation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assembly, combus­tion air motor and fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.
!
WARNING
THE MANUFACTURER’S WARRAN­TY DOES NOT COVER ANY DAM­AGE OR DEFECT TO THE AIR CON­DITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFAC­TURER) INTO, ONTO OR IN CON­JUNCTION WITH THE AIR CONDI­TIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHO­RIZED COMPONENTS, ACCES­SORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERA­TION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFAC­TURER DISCLAIMS ANY RESPON­SIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
!
WARNING
UNITS ARE NOT DESIGN CERTIFIED TO BE INSTALLED INSIDE THE STRUC­TURE. DOING SO CAN CAUSE INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE AND CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
Page 4
4
V. SAFETY INFORMATION
!
WARNING
DO NOT USE THIS UNIT DURING CONSTRUCTION IF AIR LADEN CORROSIVE COMPOUNDS ARE PRESENT SUCH AS CHLORINE AND FLUORINE. OTHER­WISE, PROVISIONS MUST BE TAKEN TO PROVIDE CLEAN, UNCONTAMINAT­ED COMBUSTION AND VENTILATION AIR TO THE UNIT. COMBUSTION AND VENTILATION AIR CONTAMINATED WITH THESE COMPOUNDS FORMS ACIDS DURING COMBUSTION WHICH CORRODES THE HEAT EXCHANGER AND COMPONENT PARTS. SOME OF THESE CONTAMINANTS ARE FOUND IN, BUT NOT LIMITED TO, PANELING, DRY WALL, ADHESIVES, PAINTS, STAINS, VARNISHES, SEALERS, AND MASONRY CLEANING MATERIALS.
!
WARNING
USE ONLY WITH TYPE OF GAS APPROVED FOR THIS UNIT. REFER TO THE UNIT RATING PLATE.
!
WARNING
INSTALL THIS UNIT ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILA­TION AIR TO THE UNIT SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
!
WARNING
PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE UNIT SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
!
WARNING
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS UNIT TO AN APPROVED VENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
!
WARNING
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIAL­LY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
!
WARNING
ALWAYS INSTALL UNIT TO OPERATE WITHIN THE UNIT'S INTENDED TEM­PERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO UNIT RATING PLATE.
!
WARNING
WHEN A UNIT IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCU­LATED BY THE UNIT TO AREAS OUTSIDE THE SPACE CONTAINING THE UNIT, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE UNIT CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE UNIT.
Page 5
5
VI. UNIT DIMENSIONS
FOR CLEARANCES SEE FIGURE 9.
OUTDOOR COIL PROTECTIVE GRILLE
OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS
FIELD CONTROL WIRE ENTRANCE
FLUE EXHAUST HOOD
COMBUSTION AIR INLET HOOD
BOTTOM RETURN DUCT OPENING
BOTTOM SUPPLY DUCT OPENING
OUTDOOR FAN GRILLE & COMPRESSOR ACCESS
BLOWER/EVAPORATOR ACCESS PANEL
SIDE SUPPLY DUCT OPENING
SIDE RETURN DUCT OPENING
FLUE EXHAUST
FIELD POWER WIRE ENTRANCE
LIQUID PRESSURE SERVICE PORT
THREADED PVC CONDENSATE DRAIN CONNECTION (3/4 NPT)
SUCTION PRESSURE SERVICE PORT
TOP VIEW
BOTTOM VIEW
FIGURE 1
479⁄16
5013⁄16
313⁄16
49⁄10
33⁄16
497⁄16” INSIDE
11⁄2
TYP.
141⁄4
TYP.
13⁄16
TYP.
451⁄16” INSIDE
191⁄2
153⁄8
30% ± 2%
29% ± 2%
20% ± 2%
21% ± 2%
CORNER WEIGHTS
% OF TOTAL UNIT
WEIGHT
Page 6
6
FILTER ACCESS PANEL (FOR UNIT MOUNTED FILTER ACCESSORY)
SIDE SUPPLY DUCT OPENING
SIDE RETURN DUCT OPENING
OUTDOOR COIL PROTECTIVE GRILLE
FLUE EXHAUST HOOD
GAS SUPPLY ENTRANCE
BLOWER/ EVAPORATOR ACCESS PANEL
SIDE VIEW
FRONT VIEW
BACK VIEW
SIDE VIEW
FIGURE 1 (CONTINUED)
MODEL
B024, B030,
B036
B042, B048,
B060
“A” HEIGHT
35.91”
40.97”
SHOWN WITH DUCT COVERS REMOVED.
207⁄8
227⁄8
1315⁄16
75⁄16
2211⁄16
471⁄2
3515⁄16
39⁄16
3515⁄16
131⁄4
47⁄16
81⁄2
TYP.
143⁄16
TYP.
133⁄4
TYP.
47⁄8
191⁄8
15”
41
1015⁄16
111⁄16
527⁄16
Page 7
7
VII.INSTALLATION
A. GENERAL
1. INSTALLATION — Install this unit in accordance with The American National Standard Z223.1-latest edition booklet entitled “National Fuel Gas Code,” and the requirements or codes of the local utility or other authority having jurisdiction.
Additional helpful publications available from the “National Fire Protection Association” are: NFPA-90A - Installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B - Warm Air Heating and Air Conditioning Systems 1984.
These publications are available from:
National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269
NOTE: Remove wood shipping base before installing unit.
1. PRE-INSTALLATION CHECK-POINTS — Before attempting any installation,
carefully consider the following points:
Structural strength of supporting members
(Rooftop Installation) Clearances and provision for servicing Power supply and wiring Gas supply and piping Air duct connections and sizing Drain facilities and connections Location for minimum noise and vibration
2. LOCATION CONSIDERATIONS
The metal parts of this unit may be subject to rust or deterioration in adverse envi­ronmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petrole­um refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment location and exposure.
1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.
2. In coastal areas locate the unit on the side of the building away from the water­front.
3. Shielding by a fence or shrubs may give some protection.
4. Elevate the unit off its slab or base enough to allow air circulation and avoid hold­ing water against the basepan.
!
WARNING
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PER­SONAL INJURY OR DEATH.
REGULAR MAINTENANCE WILL REDUCE THE BUILDUP OF CONTAMINANTS AND HELP TO PROTECT THE UNIT’S FINISH.
Page 8
8
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
2. Regular cleaning and waxing of the cabinet with a good automobile polish will pro­vide some protection.
3. Use a good liquid cleaner several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be ver­ified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
B. OUTSIDE INSTALLATION
(Typical outdoor slab installation is shown in Figure 2.)
1. Select a location where external water drainage cannot collect around unit.
2. Provide a slab sufficiently high enough above grade to prevent surface water from entering the unit. Where snowfall is anticipated, mount the unit above the anticipat­ed maximum snow depth for your area. The slab should be isolated from the foun­dation wall.
3. Pitch the slab approximately
1
2” so that the unit will be pitched toward the drain. See
Figure 3.
4. The location of the unit should be such as to provide proper access for inspection and servicing as shown in Figure 9.
!
WARNING
THESE UNITS ARE DESIGNED CERTIFIED FOR OUTDOOR INSTALLATION ONLY. INSTALLATION INSIDE ANY PART OF A STRUCTURE CAN RESULT IN INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE. INSTALLATION INSIDE CAN ALSO CAUSE RECIRCULATION OF FLUE PROD­UCTS INTO THE CONDITIONED SPACE RESULTING IN PERSONAL INJURY OR DEATH.
2
Page 9
9
5. Locate unit where operating sounds will not disturb owner or neighbors.
6. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
7. Where snowfall is anticipated, the height of the unit above the ground level must be considered. Mount unit high enough to be above average area snowfall and to allow combustion air to enter the combustion air inlet.
C. ATTACHING EXHAUST AND COMBUSTION AIR INLET HOODS
IMPORTANT: Do not operate this unit without the exhaust and combustion air inlet hood properly installed. These hoods are shipped in a carton in the return air compart­ment inside the unit and must be attached when the unit is installed. See Figure 4.
To attach exhaust and combustion air inlet hood:
1. Remove 3 screws securing filter access panel and remove filter access panel. For loca­tion of filter access panel, see Figure 1.
2. Remove both exhaust and combustion air inlet hoods from their carton, located inside the return air compartment.
3. Attach filter access panel.
4. Attach the combustion air inlet hood and the exhaust hood each with 4 screws as shown in Figure 4. Screws are in parts bag shipped in the burner compartment.
5. Vent the unit using the flue exhaust hood, as supplied from the factory, without alteration or addition. The only exception is with factory approved additions. Consult your local util­ity or other authority having jurisdiction for accepted venting techniques.
D. COVER PANEL INSTALLATION/CONVERSION PROCEDURE
1.HORIZONTAL TO DOWNFLOW
a. Remove screws and covers from the supply and return bottom sections. NOTE:
Rotate the supply cover 90° and remove.
b. Install gasket (supplied with parts bag) around perimeter of cover on the insulated
side. See Figure 6.
c. Secure covers to the side of the unit using existing screws and those supplied in
the parts bag.
2.DOWNFLOW TO HORIZONTAL
a. Remove screws and covers from the supply and return bottom sections.
b. Install gasket (supplied with parts bag) around perimeter of cover as illustrated in
Figure 5.
EXHAUST HOOD W/(4) SCREWS
COMBUSTION AIR INLET HOOD W/(4) SCREWS
FIGURE 3
PITCHING UNIT TO INSURE PROPER CONDENSATE DRAINAGE.
1/8 BUBBLE OFF LEVEL
LEVEL
FRONT OF UNIT
FIGURE
COMBUSTION AIR INLET HOOD & EXHAUST HOOD INSTALLATION
4
THIS END APPROX.
1/2” HIGHER THAN FRONT
LEVEL PLANE
CONDENSATE DRAIN CONNECTION
I655
COMBUSTION AIR INLET HOOD W/(4) SCREWS
EXHAUST HOOD W/(4) SCREWS
I250
Page 10
10
FIGURE 5
COVER GASKET DETAIL FOR UNITS SHIPPED FOR DOWNFLOW APPLICATION BEING CONVERTED TO SIDE DISCHARGE
SUPPLY/RETURN AIR COVER
TAPE AROUND FLANGE
FIGURE 7
DUCT COVER INSTALLATION SIDE MOUNTING
(ATTACH WITH 6 SCREWS)
DUCT COVER
(ATTACH WITH 6 SCREWS)
SUPPLY
DUCT COVER
RETURN
I264
FIGURE 6
COVER GASKET DETAIL FOR UNITS SHIPPED FOR SIDE DISCHARGE APPLICATION BEING CONVERTED TO DOWNFLOW
SUPPLY/RETURN AIR COVER
TAPE AROUND FLANGE
FIGURE 8
DUCT COVER INSTALLATION BASE PAN MOUNTING
I654
BASE PAN
LANCE AT BACK OF BOTTOM SUPPLY DUCT OPENING
SUPPLY DUCT COVER
SUPPLY DUCT COVER
*
(INSULATION SIDE UP), ATTACH WITH TWO SCREWS.
*
ROTATE SUPPLY COVER 90° AFTER IT IS INSERTED THROUGH OPENING. SLIP FLANGE OF COVER UNDER LANCE AT BACK OF BOTTOM SUPPLY DUCT OPENING. SEE DETAILAT LEFT. THEN SECURE COVER BY INSTALLING 2 SCREWS USING HOLE NEAREST THE OUTSIDE OF UNIT.
RETURN DUCT COVER (INSULATION SIDE UP, ATTA CH WITH 4 SCREWS)
I265
Page 11
11
c. Install covers in the unit bottom with the insulated side up. NOTE: Supply cover
must be inserted through supply opening with narrow side toward unit. Once cover is through opening, rotate 90° and slip back flange of cover under tab at the back of bottom duct opening. See Figure 8.
d. Secure supply cover to base of unit with 2 screws, engaging prepunched holes in
raised duct opening flange.
e. Secure return covers to base of unit with screws engaging prepunched holes in
raised duct opening flange.
E.CLEARANCES
The following minimum clearances must be observed for proper unit performance and serviceability. See Figure 9.
1. Provide 48” minimum clearance at front of the unit. Provide 24” minimum clearance on right side of unit. If economizer is used, a 24” minimum clearance is required on left side of unit. (See Figure 9.) If no economizer is required, then a 12” clearance is required on left side of unit.
2. Provide 60” minimum clearance between top of unit and maximum 3 foot overhang.
3. Unit is design certified for 2” minimum clearance between supply duct and a com­bustible structure for the first 3 feet of duct. 0” clearance is allowed after 3 feet.
!
WARNING
THIS UNIT MUST NOT BE INSTALLED DIRECTLY ON WOOD FLOORING, CLASS A, CLASS B OR CLASS C ROOF COVERING MATERIALS, OR ANY OTHER COM­BUSTIBLE STRUCTURE EXCEPT AS SPECIFIED IN FIGURE 13. FAILURE TO ADHERE TO THIS WARNING CAN CAUSE A FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Page 12
12
FIGURE 10
EXCEPTION TO NON-COMBUSTIBLE FLOORING REQUIREMENT
I458
BOTH ENDS MUST BE OPEN FOR DOWNFLOW OR SIDEFLOW DUCTWORK TO PROVIDE VENTILATION
COMBUSTIBLE STRUCTURE
1” MIN.
NOMINAL 4 x 4 TIMBER (SIDES ONLY)
SIDEFLOW
SUPPLY
PLENUM
CONNECTION
SUPPLY
PLENUM
(DOWNFLOW)
RETURN PLENUM
(DOWNFLOW)
SIDEFLOW
RETURN PLENUM
CONNECTION
3-1/2” MIN.
Page 13
13
F. ROOFTOP INSTALLATION
1. Before locating the unit on the roof, make sure that the roof structure is adequate to support the weight involved. (See electrical & physical tables in this book for weight of unit.) THIS IS VERY IMPORTANT AND THE INSTALLER’S RESPONSIBILITY.
2. For rigging and roofcurb details, see Figures 14, 15, and 16.
3. The location of the unit on the roof should be such as to provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately, block off supply and return air openings to prevent excessive condensation.
G. DUCTWORK
The installing contractor should fabricate ductwork in accordance with local codes. Use industry manuals as a guide when sizing and designing the duct system. Contact Air Conditioning Contractors of America, 1513 16th St. N.W., Washington, D.C. 20036.
Place the unit as close to the conditioned space as possible allowing clearances as indi­cated. Run ducts as directly as possible to supply and return outlets. Use of non-flam­mable weatherproof flexible connectors on both supply and return connections at unit to reduce noise transmission is recommended.
On ductwork exposed to outside temperature and humidity, use a minimum of 2” of insulation and a vapor barrier. Distribution system in attic, furred space or crawl space should be insulated with at least 2” of insulation.
1
2” to 1” thick insulation is usually suffi-
cient for ductwork inside the air conditioned space.
Provide balancing dampers for each branch duct in the supply system. Properly support ductwork from the structure.
!
WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING DEVICE SUCH AS FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY, OR PROPERTY DAMAGE.
13
Page 14
14
IMPORTANT: In the event that the return air ducts must be run through an “unconfined” space containing other fuel burning equipment, it is imperative that the user/homeowner must be informed against future changes in construction which might change this to a “confined space.” Also, caution the user/homeowner against any future installation of additional equipment (such as power ventilators, clothes dryers, etc., within the existing unconfined and/or confined space which might create a negative pressure within the vicinity of other solid, liquid, or gas fueled appliances.
H. RETURN AIR
II
. FILTERS
The installer must install field supplied filters in the return air duct. A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspec­tion and cleaning. Filters must have adequate face area for the rated air quantity of the unit. See air delivery tables for recommended filter size. A field installed internal filter kit RXRY-B01 is available.
!
WARNING
NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTS TO ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED. ALL OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS AND SEALED AIRTIGHT.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCU­LATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CAROBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
Page 15
15
FIGURE 15
ROOFCURB
INSULATION PANELS
16
MAX.
FIGURE 16
ROOFCURB
GASKET
NAILING STRIP
ROOFTOP UNIT
TIE DOWN SCREW *
ROOFCURB
1
/2 MAX.
RETURN PLENUM
SUPPLY PLENUM
3
/8 MAX.
16
1
/2
20
NAILING STRIP
CAULK ALL JOINTS WATERTIGHT
DUCT FLANGE (NOT TO EXCEED 1()
ROOFCURB
I342
** DUCT *
INSULATION
INSULATION *
**BY CONTRACTOR
**FOR INSTALLATION OF DUCT AS SHOWN, USE RECOMMENDED
DUCT SIZES FROM ROOFCURB INSTALLATION INSTRUCTIONS. FOR DUCT FLANGE ATTACHMENT TO UNIT, SEE UNIT INSTALLATION INSTRUCTIONS (FIGURE 1) FOR SIZE OF DUCT OPENINGS.
*
ROOF FLASHING
ROOFING *
CANT STRIP *
ROOF DECK *
*
I255
Page 16
16
VIII. GAS SUPPLY, CONDENSATE DRAIN AND
VIII. PIPING
A. GAS CONNECTION
IMPORTANT: Connect this unit only to gas supplied by a commercial utility.
1. Install gas piping in accordance with local codes and regulations of the local utility company. In the absence of local codes, the installation must conform to the specifi­cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.
NOTE: The use of flexible gas connectors is not permitted.
NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be a T-handle gas cock.
2. Connect the gas line to the gas pipe inlet opening provided into the 1/2” inlet valve. See Figure 2 for typical piping.
3. Size the gas line to the furnace adequate enough to prevent undue pressure drop and never less than 1/2”.
4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possi­ble.
5. Install an outside ground joint union to connect the gas supply to the control assem­bly at the burner tray.
6. Gas valves have been factory installed. Install a manual gas valve where local codes specify a shut-off valve outside the unit casing. (See Figure 19.)
7. Make sure piping is tight. A pipe compound resistant to the action of liquefied
petroleum gases must be used at all threaded pipe connections.
8. IMPORTANT: Any additions, changes or conversions required for the furnace to sat­isfactorily meet the application should be made by a qualified installer, service agency or the gas supplier, using factory-specified or approved parts. In the com­monwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
IMPORTANT: Disconnect the furnace and its individual shutoff valve from the gas sup­ply piping during any pressure testing of that system at test pressures in excess of 1/2 psig or isolate the system from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of this gas supply system at pressures equal to or less than 1/2 PSIG.
Nominal
Iron Pipe
Size,
Inches
Equivalent Length of Pipe, Feet
10 20 30 40 50 60 70 80
1
/2 132 92 73 63 56 50 46 43
3
/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 11/4 1,050 730 590 500 440 400 370 350 11/2 1,600 1,100 890 760 670 610 560 530
TABLE 1
GAS PIPE CAPACITY TABLE (CU. FT./HR.)
FIGURE 19
SUGGESTED GAS PIPING
ROOF OR GROUND LEVEL INSTALLATION
FROM GAS METER
MANUAL GAS SHUT-OFF VALV E
Factory supplied grommet must be utilized.
*
UNIT GAS SUPPLY CONNECTION
*
Page 17
17
TO CHECK FOR GAS LEAKS, USE A SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD. DO NOT USE AN OPEN FLAME.
IMPORTANT: Check the rating plate to make certain the appliance is equipped to burn
the type of gas supplied. Care should be taken after installation of this equipment that the gas control valve not be subjected to high gas supply line pressure.
In making gas connections, avoid strains as they may cause noise and damage the con­trols. A backup wrench is required to be used on the valve to avoid damage.
The capacities of gas pipe of different diameters and lengths in cu. ft. per hr. with pres­sure drop of 0.5 in. and specific gravity of 0.60 (natural gas) are shown in Table 2.
After determining the pipe length, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Gas Input of Furnace (BTU/HR)
Cu. Ft. Per Hr. Required =
Heating Value of Gas (BTU/FT
3
)
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT
3
) may be determined by consulting the local natural gas utility or the
L.P. gas supplier.
B. LP CONVERSION
Convert the valve to use liquefied petroleum (LP) gas by replacing the pressure regulator spring with the conversion kit spring. This LP kit spring allows the regulator to maintain the proper manifold pressure for LP gas. The correct burner LP orifices are included in the kit. See Figure 20.
NOTE: Order the correct LP conversion kit from the furnace manufacturer.
See Conversion Kit Index shipped with unit for proper LP kit number. Furnace conver­sion to LP gas must be performed by a qualified technician.
!
WARNING
DO NOT USE AN OPEN FLAME TO CHECK FOR LEAKS. THE USE OF AN OPEN FLAME CAN RESULT IN FIRE, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
WARNING
THIS UNIT IS EQUIPPED AT THE FACTORY FOR USE ON NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES A SPECIAL KIT SUPPLIED BY THE DIS­TRIBUTOR OR MANUFACTURER. MAILING ADDRESSES ARE LISTED ON THE FURNACE RATING PLATE, PARTS LIST AND WARRANTY. FAILURE TO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POI­SONING, EXPLOSION, PERSONAL INJURY, PROPERTY DAMAGE OR DEATH.
FIGURE 20
Page 18
18
D. ADJUSTING OR CHECKING FURNACE INPUT
– Natural Gas Line Pressure 5” - 10.5” W.C. – LP Gas Line Pressure 11” - 13” W.C.
– Natural Gas Manifold Pressure 3.5” W.C – LP Gas Manifold Pressure - 10” W.C.
Supply and manifold pressure taps are located on the gas valve body 1/8” N.P.T.
Use a properly calibrated manometer gauge for accurate gas pressure readings.
Only small variations in the gas flow should be made by means of the pressure regulator adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas con­trol valve.
To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace
the regulator cap securely.
Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices. To change orifice spuds, shut off the manual main gas valve and remove the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings apply. For high altitudes (elevations over 2,000 ft.), see conversion kit index 92-21519-XX for derating and orifice spud sizes.
Check of input is important to prevent over-firing of the furnace beyond its design­rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate.
Heating Value of Gas (BTU/Cu. Ft.) x 3600
Cu. Ft. Per Hr. Required =
Time in Seconds (for 1 Cu. Ft.) of Gas
C. NOx MODELS
When converting units equipped with NOx inserts to LP gas, the stainless steel mesh inserts in the entrance of the tubular exchangers are not required to meet SCAQMD NOx emission levels. Carefully remove these inserts before firing this furnace on LP gas. This furnace is not designed to operate on LP gas with the NOx inserts in place.
Step by step instructions on removing the NOx inserts and retaining rod are included in the Conversion Kit Installation Instructions.
TABLE 2
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal Iron Pipe Size, Inches
1/2 3/4
1 1-1/4 1-1/2
2
Example (LP): Input BTU requirement of unit, 150,000
10 20 30 40 50 60 70 80 90 100 125 150
275 189 152 129 114 103 96 89 83 78 69 63
567 393 315 267 237 217 196 182 173 162 146 132 1,071 732 590 504 448 409 378 346 322 307 275 252 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
Equivalent length of pipe, 60 ft. = 3/4IPS required.
Length of Pipe, Feet
Page 19
19
Start the furnace and measure the time required to burn one cubic foot of gas. Prior to checking the furnace input, make certain that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS): The main burner orifices in your furnace and in these kits are sized for the nameplate input and intended for installations at elevations up to 2,000 feet in the USA or Canada, or for ele­vations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated at the factory. For elevations above 2,000 feet (610 meters) IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1,000 feet (305 meters) above sea level.
NOTICE: DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD IS UNLAWFUL IN CANADA (REFER TO CAN/CGA 2.17). UNITS INSTALLED IN ALTITUDES GREATER THAN 2,000 FEET (610 METERS) MUST BE SHIPPED FROM THE FACTORY OR FROM A FACTORY AUTHORIZED CONVERSION STATION WITH THE HEATING INPUT DERATED BY 10% SO AS TO OPERATE PROPERLY IN ALTITUDES FROM 2,000 - 4,500 FEET (610 - 1,373 METERS).
E.CONDENSATE DRAIN
The evaporator coil condensate drain ends with a threaded 3/4” nominal PVC stub. A trap is built in for proper condensate drainage and to prevent debris from being drawn into the unit. Do not connect the drain to a closed sewer line. Connection to a vented sewer line is allowed. It is recommended that a PVC cement not be used so that the drain line can be easily cleaned in the future.
IMPORTANT: DO NOT INSTALL AN EXTERNAL TRAP. DOING SO CAN CAUSE IMPROPER DRAINAGE OF THE CONDENSATE AND RESULT IN FLOODING WITH­IN THE UNIT.
IX. WIRING
A. POWER SUPPLY
!
WARNING
TURN OFF THE MAIN ELECTRICAL POWER AT THE BRANCH CIRCUIT DISCON­NECT CLOSEST TO THE UNIT BEFORE ATTEMPTING ANY WIRING. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
TABLE 3
INPUT
BTU/HR
40,000
60,000
80,000
100,000
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
METER
SIZE
CU. FT.
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
ONE 1 21 1 30 1 34 1 39 3 45
TEN 13 30 15 0 15 36 16 30 37 30
ONE 0 54 1 0 1 3 1 6 2 30
TEN 9 0 10 0 10 24 11 0 25 0
ONE 0 41 0 45 0 47 0 50 1 53
TEN 6 45 7 30 7 48 8 15 18 45
ONE 0 33 0 36 0 38 0 40 1 30
TEN 5 24 6 0 6 15 6 36 15 0
OR LP GAS
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
Page 20
20
1. All wiring should be made in accordance with the National Electrical Code. Consult the local power company to determine the availability of sufficient power to operate the unit. Check the voltage at power supply to make sure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT. Install a branch circuit disconnect near the rooftop, in accordance with the N.E.C., C.E.C. or local codes.
2. It is important that proper electrical power is available at the unit. Voltage should not vary more than 10% from that stamped on the unit nameplate. On three phase units, phases must be balanced within 3%.
3. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined from Table 4 using the circuit ampacity found on the unit rating plate. Use the smallest wire size allowable in Table 4 from the unit dis­connect to unit. The disconnect must be in sight and readily accessible of the unit.
NOTES:
1. Wire size based on 60°C rated wire insulation and 30°C Ambient Temp. (86°F).
2. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.
When installed, the unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70, if an external electrical source is utilized.
IMPORTANT: THIS UNIT IS APPROVED FOR USE WITH COPPER CONDUCTORS ONLY
CONNECTED TO UNIT CONTACTOR.
WARRANTY MAY BE JEOPARDIZED IF ALUMINUM WIRE IS CONNECTED TO UNIT CONTACTOR.
Special instructions apply for power wiring with aluminum conductors: Warranty is void if connections are not made per instructions.
Attach a length (6” or more) of recommended size copper wire to the unit contactor ter­minals L1 and L3 for single phase, L1, L2 and L3 for three phase.
Select the equivalent aluminum wire size from the tabulation below:
Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for copper­aluminum splices. Please exercise the following instructions very carefully to obtain a positive and lasting connection:
1. Strip insulation from aluminum conductor.
2. Coat the stripped end of the aluminum wire with the recommended inhibitor, and wire brush the aluminum surface through inhibitor. INHIBITORS: Brundy-Pentex “A”; Alcoa-No. 2EJC; T & B-KPOR Shield.
3. Clean and recoat aluminum conductor with inhibitor.
4. Make the splice using the above listed wire nuts or split bolt connectors.
5. Coat the entire connection with inhibitor and wrap with electrical insulating tape.
TABLE 4
BRANCH CIRCUIT COPPER WIRE SIZE (BASED ON 1% VOLTAGE DROP)*
200 6 4 4 4 3 3 2 2
SUPPLY WIRE
LENGTH-FEET
150 8 6 6 4 4 4 3 3
100 10 8 8 6 6 6 4 4
50 14 12 10 10 8 8 6 6
15 20 25 30 35 40 45 50
BRANCH CIRCUIT AMPACITY
*Taken from National Electric Code
TABLE 5
AWG Copper AWG Aluminum Connector Type and Size
Wire Size Wire Size (or equivalent)
#12 #10 T & B Wire Nut PT2 #10 # 8 T & B Wire Nut PT3 # 8 # 6 Sherman Split Bolt TSP6 # 6 # 4 Sherman Split Bolt TSP4 # 4 # 2 Sherman Split Bolt TSP2
Page 21
21
B. HOOK-UP
To wire unit, refer to the following hook-up diagram. Refer to Figure 1 for location of wiring entrances. Wiring to be done in the field between the unit and devices not attached to the unit, or
between separate devices which are field installed and located, shall conform with the temperature limitation for Type T wire [63°F rise (35°C)] when installed in accordance with the manufacturer’s instructions.
L2 connection 3Phase only
C. INTERNAL WIRING
IMPORTANT: Some single phase units are equipped with a single pole contactor. Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor.
A diagram of the internal wiring of this unit is located under the electrical box cover and in this manual. If any of the original wire as supplied with the appliance must be replaced, the wire gauge and insulation must be same as original wiring.
Transformer is factory wired for 230 volts on 208/230 volt models and must be changed for 208 volt applications. See unit wiring diagram for 208 volt wiring.
D. THERMOSTAT
The room thermostat must be compatible with the spark ignition control on the unit. Generally, all thermostats that are not of the “current robbing” type are compatible with the integrated furnace control. The low voltage wiring should be sized as shown in Table
7.
Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat. Run the thermostat lead wires inside the blower compartment and connect to low voltage terminals as shown on the wiring diagram. Never install the ther­mostat on an outside wall or where it will be influenced by drafts, concealed hot or cold water pipes or ducts, lighting fixtures, radiation from fireplace, sun rays, lamps, televi­sions, radios or air streams from registers. Refer to instructions packed with the thermo­stat for “heater” selection or adjustment.
The following is a list of recommended thermostats to be used with or without an econo­mizer:
*
*
SINGLE STAGE COOL W/O
ECONOMIZER
MAPLE CHASE - MODEL #0970 HONEYWELL - MODEL #T8602C MAPLE CHASE - MODEL #0960 WHITE RODGERS - MODEL #1F91-59 ROBERTSHAW - MODEL #CM64A-USAJ
TWO STAGE COOL W/
ECONOMIZER
HONEYWELL - MODEL #T7300-A1005 HONEYWELL - MODEL #T874D-1959
Page 22
X. FURNACE SECTION CONTROLS AND
IGNITION SYSTEM
NORMAL FURNACE OPERATING SEQUENCE
This unit is equipped with an integrated direct spark ignition control.
1. The thermostat calls for heat.
2. The control board will run a self check to verify that the limit control and manual reset overtemperature control are closed and that the pressure switch is open. If so, the induced draft blower (inducer) begins a prepurge cycle.
3. The air proving negative pressure switch closes.
4. 15 seconds after the pressure switch closes, the gas valve opens and the spark is initiated for a 7 second trial for ignition.
5. Burners ignite and flame sensor proves all burners have lit.
6. The circulating air blower is energized after 30 seconds.
7. The control board enters a normal operation loop in which all safety controls are moni­tored continuously.
8. Thermostat is satisfied and opens.
9. The gas valve is de-energized and closes, shutting down the burner flame.
10. The control board will de-energize the inducer after a five second post purge.
11. The circulating air blower is de-energized after 90 seconds.
• The integrated control board has a three ignition system.
• After a total of three trials for ignition without sensing main burner flame, the system goes into a 100% lockout mode.
• After one hour, the ignition control repeats the prepurge and ignition cycles for 3 tries and then goes into 100% lockout mode again.
• It continues this sequence of cycles and lockout each hour until ignition is successful or power is interrupted.
• During the lockout mode, neither the spark ignition control or gas valve will be energized until the system is reset by turning the thermostat to the “OFF” position or interrupting the electrical power to the unit for 3 seconds or longer.
• The induced draft blower and main burner will shut off when the thermostat is satisfied.
• The circulating air blower will start and run on the heating speed if the thermostat fan switch is in the “ON” position.
The integrated furnace control is equipped with diagnostic LED. The LED is lit continuously when there is power to the control, with or without a call for heat. If the LED is not lit, there is either no power to the control or there is an internal component failure within the control, and the control should be replaced.
If the control detects the following failures, the LED will flash on for approximately 1/4 sec­ond, then off for 3/4 second for designated failure detections.
1 Flash: Failed to detect flame within the three tries for ignition. 2 Flash: Pressure switch or induced draft blower problem detected. 3 Flash: High limit or auxiliary limit open. 4 Flash: Flame sensed and gas valve not energized or flame sensed with no “W” signal. 5 Flash: Overtemperature switch open.
22
ABLE
T
(1) thermostat and back to the furnace.
NOTE: DO NOT USE CONTROL A
6
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.
3.0161412101010
2.5161412121210
2.0181614121210
50 100 150 200 250 300
Thermostat Load - Amps
The total wire length is the distance from the furnace to the
WG.
Length of Run – Feet (1)
WIRING SMALLER THAN NO. 18
Page 23
23
OPERATING INSTRUCTIONS
This appliance is equipped with a direct spark intermittent ignition device. This device lights the main burners each time the room thermostat (closes) calls for heat. See operat­ing instructions on the back of the furnace/controls access panel.
TO START THE FURNACE
1. STOP! Read the safety information on the Operating Instructions Label located on this appliance.
2. Set the thermostat to its lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance does not have a pilot. It is equipped with an ignition device which auto­matically lights the burner. Do NOT
try to light the burner by hand.
5. Remove control door/access panel.
6. Move switch to the “OFF” position.
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP!
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire department. If you don’t smell gas, go to the next step.
8. Move the switch from “OFF” position to “ON” position.
9. Replace the control door.
10. Turn on all electric power to the appliance.
11. Set the thermostat to the desired setting.
12. If the appliance will not operate, follow the instructions below on how to shut down the furnace.
The initial start-up on a new installation may require the control system to be energized for some time until any air has bled through the system and fuel gas is available at the burn­ers.
TO SHUT DOWN FURNACE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control door.
4. Move switch to the “OFF” position.
5. Replace control door.
!
WARNING
DO NOT ATTEMPT TO MANUALLY LIGHT THIS FURNACE WITH A MATCH OR ANY OPEN FLAME. ATTEMPTING TO DO SO CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
WARNING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
!
WARNING
THE SPARK IGNITOR AND IGNITION LEAD FROM THE IGNITION CONTROL ARE HIGH VOLTAGE. KEEP HANDS OR TOOLS AWAY TO PREVENT ELEC­TRICAL SHOCK. SHUT OFF ELECTRICAL POWER BEFORE SERVICING ANY OF THE CONTROLS. FAILURE TO ADHERE TO THIS WARNING CAN RESULT IN PERSONAL INJURY OR DEATH.
Page 24
BURNERS
Burners for these units have been designed so that field adjustment is not required. Burners are tray-mounted and accessible for easy cleaning when required.
MANUAL RESET OVERTEMPERATURE CONTROL
A manual reset overtemperature control is located on the burner shield. This device sens­es blockage in the heat exchanger or insufficient combustion air. This shuts off the main burners if excessive temperatures occur in the burner compartment.
Operation of this control indicates an abnormal condition. Therefore, the unit should be examined by a qualified installer, service agency, or the gas supplier before being placed back into operation.
PRESSURE SWITCH
This furnace has a pressure switch for sensing a blocked exhaust or a failed induced draft blower. It is normally open and closes when the induced draft blower starts, indicating air flow through the combustion chamber.
LIMIT CONTROL
The supply air high temperature limit cut-off is set at the factory and cannot be adjusted. It is calibrated to prevent the air temperature leaving the furnace from exceeding the maxi­mum outlet air temperature. WARNING: DO NOT JUMPER THIS DEVICE! Replace
this control only with the identical replacement part.
XI. SYSTEM OPERATING INFORMATION
ADVISE THE CUSTOMER
1. Keep the air filters clean. The heating system operates better, more efficiently and more economically.
2. Arrange the furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
3. Close doors and windows. This reduces the heating load on the system.
4. Avoid excessive use of exhaust fans.
5. Do not permit the heat generated by television, lamps or radios to influence the ther­mostat operation.
6. Except for the mounting platform, keep all combustible articles three feet from the unit and exhaust system.
7.
IMPORTANT: Replace all blower doors and compartment cover after servicing the
unit. Do not operate the unit without all panels and doors securely in place.
8. Do not allow snow or other debris to accumulate in the vicinity of the appliance.
FURNACE SECTION MAINTENANCE
The unit’s furnace should operate for many years without excessive scale build-up in flue passageways; however, it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the exhaust system and the burners for continued safe operation, paying particular attention to deterioration from corrosion or other sources.
If during inspection the flue passageways and exhaust system are determined to require cleaning, the following procedures should be followed (by a qualified installer, service
agency, or gas supplier):
24
!
WARNING
DO NOT JUMPER THIS DEVICE! DO NOT reset the overtemperature control without taking corrective action to assure that an adequate supply of combus­tion air is maintained under all conditions of operation. Failure to do so can result in carbon monoxide poisoning or death. Replace this control only with the identical replacement part.
!
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, SHUT OFF THE MANUAL GAS VALVE TO THE APPLIANCE BEFORE SHUT­TING OFF THE ELECTRICAL SUPPLY. FAILURE TO DO SO CAN RESULT IN AN EXPLOSION OR FIRE CAUSING PROPERTY DAMAGE, SEVERE PERSON­AL INJURY OR DEATH!
Page 25
25
1. Turn off the electrical power to the unit and set the thermostat to the lowest tem­perature.
2. Shut off the gas supply to the unit either at the meter or at manual valve in the supply piping.
3. Remove the furnace controls access panel and the control box cover.
4. Disconnect the gas supply piping from the gas valve.
5. Disconnect the wiring to the induced draft blower motor, gas valve, flame sensor, and flame roll-out control, and ignitor cable. Mark all wires disconnected for proper reconnection.
6. Remove the screws (4) connecting the burner tray to the heat exchanger mounting panel.
7. Remove the burner tray and the manifold assembly from the unit.
8. Remove the screws (4) connecting the induced draft blower to the collector box and screws (16) connecting the collector box to the heat exchanger mounting panel. Remove the induced draft blower and the collector box from the unit.
9. Remove the turbulators from inside the heat exchangers by inserting the blade of a screwdriver under the locking tabs. Pop the tabs out of the expanded grooves of the heat exchanger. Slide the turbulators out of the heat exchangers.
10. Direct a water hose into the outlet of the heat exchanger top. Flush the inside of each heat exchanger tube with water. Blow out each tube with air to remove excessive moisture.
11. Reassemble (steps 1 through 10 in reverse order). Be careful not to strip out the
screw holes used to mount the collector box and inducer blower. Replace induc­er blower gasket and collector box gasket with factory replacements if dam­aged.
The manufacturer recommends that a qualified installer, service agency or the gas suppli­er visually inspect the burner flames for the desired flame appearance at the beginning of the heating season and approximately midway in heating season.
The manufacturer also recommends that a qualified installer, service agency or the gas supplier clean the flame sensor with steel wool at the beginning of the heating season.
LUBRICATION
IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the warranty.
The blower motor and induced draft blower motor are prelubricated by the manufacturer and do not require further attention.
A qualified installer, service agency or the gas supplier must periodically clean the motors to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. And, as suggested elsewhere in these instruc­tions, the air filters should be kept clean because dirty filters can restrict air flow and the motor depends upon sufficient air flowing across and through it to prevent overheating.
!
WARNING
HOLES IN THE EXHAUST TRANSITION OR HEAT EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME. THE EXHAUST TRANSITION OR HEAT EXCHANGER MUST BE REPLACED IF THEY HAVE HOLES OR CRACKS IN THEM. FAILURE TO DO SO CAN CAUSE CARBON MONOXIDE POISONING RESULTING IN PERSONAL NJURY OR DEATH.
!
WARNING
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPT­ING MAINTENANCE. FAILURE TO DO SO MAY RESULT IN ELECTRICAL SHOCK OR SEVERE PERSONAL INJURY OR DEATH.
!
WARNING
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CON­TROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPER­ATION RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PER­SONAL INJURY OR DEATH.
Page 26
COOLING SECTION MAINTENANCE
It is recommended that at the beginning of each cooling season a qualified installer or service agency inspect and clean the cooling section of this unit. The following areas should be addressed: evaporator coil, condenser coil, condenser fan motor and venturi area.
To inspect the evaporator coil:
1. Remove the filter access panel and the blower/evaporator coil access panel.
2. Unplug the wires from the circulating air blower and the limit control. Remove the two screws and slide the blower out of the unit sideways.
3. Shine a flashlight on the evaporator coil (both sides) and inspect for accumulation of lint, insulation, etc.
4. If coil requires cleaning, follow the steps shown below.
Cleaning Evaporator Coil
1. Remove screws form condenser fan grille assembly and lay grille over on the unit top panel.
2. Remove the controls access panel and the control box cover.
3. Disconnect the outdoor fan motor wiring from the compressor contactor and capaci­tor. Remove the strain relief in the bulkhead and pull the fan motor wires through. Set grille assembly to the side.
4. Remove the screws that secure the unit top to the unit. Remove the top and set the unit top to the side.
5. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacu­um it with a soft brush attachment. Be careful not to bend the coil fins.
6. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solu­tion. Rinse the coil thoroughly with water. IMPORTANT: Do not
use excessive water pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
7. Go to next section for cleaning the condenser coil.
Cleaning Condenser Coil, Drain Pan, Condensate Drain, Condenser Fan, Circulation Air Blower and Venturi
1. Remove the screws from the condenser coil protective grille and remove the grille from the unit. Ensure the filter access panel is still removed to access all of the screws securing the grille.
2. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
3. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solu­tion. Rinse the coil thoroughly with water. IMPORTANT: Do not
use excessive water pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
4. Inspect the drain pan and condensate drain at the same time the condenser coil is checked. Clean the drain pan by flushing with water and removing any matters of obstructions which may be present.
5. Flush the drain tube with water. If the drain tube is blocked, it can usually be cleared wth high pressure water.
6. The venturi should also be inspected for items of obstruction such as collections of grass, dirt or spider webs. Remove any that are present.
7. Inspect the circulating air blower wheel and motor for accumulation of lint, dirt or other obstruction and clean if necessary. Inspect the blower motor mounts and the blower housing for loose mounts or other damage. Repair or replace if necessary.
26
!
WARNING
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE UNIT. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
!
WARNING
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPT­ING MAINTENANCE. FAILURE TO DO SO MAY RESULT IN ELECTRICAL SHOCK OR SEVERE PERSONAL INJURY OR DEATH.
Page 27
27
Re-assembly
1. Place the condenser coil protective grille back on unit and replace all screws.
2. Place top pane back on unit and replace all screws.
3. Set condenser fan grille assembly on top of the unit with the fan on top and the motor wires on the venturi side. Run the fan motor wires through the bulkhead and pull wires through the hole on the bottom of the control box on the left side and into the control box. Reconnect fan motor wires per the wiring diagram attached to the back of the control box cover.
4. Replace wire strain relief in bulkhead after the slack is pulled out of the wires on the fan side. This will assure wires will not be damaged by the fan during unit operation.
5. Turn the condenser fan grille assembly over and into the recess in the unit top. Secure the grille to the unit with the four long #8 screws removed earlier.
6. Replace the circulating air blower, making sure that all wires are properly reconnect­ed per the unit wiring diagram.
7. Replace the filter and blower/evaporator coil access panels.
8. Replace the control box cover and controls access panel.
9. Restore electrical power to the unit and check for proper operation, especially the condenser fan motor.
REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
TROUBLESHOOTING
Refer to Troubleshooting Chart included in this manual.
WIRING DIAGRAMS
Refer to the appropriate wiring diagram included in this manual.
CHARGING
Refer to the appropriate charge chart included in this manual.
BLOWER MOTOR SPEED TAPS
After determining necessary CFM and speed tap data, follow the steps below to change speeds.
1. Remove the furnace/control access panel.
2. Remove the control box cover. See Figure 21 for location of the furnace control board.
3. Reference Figure 22 for the proper location of the red and black wires on the speed tap block and on the furnace control board to obtain the speed tap you have chosen.
4. After adjusting the wires accordingly, attach the control box cover, furnace control access panel and the blower access panel to the unit.
FIGURE 21
INTEGRATED FURNACE CONTROL BOARD
Page 28
28
* 460 volt units: Do not adjust from factory speed.
460 volt units: Low speed heat only; field conversion diagram for medium
speed cool provided on Figure 22.
*
*
FIGURE 22
208/230 Volt Only
460 Volt Only
FIGURE 23
FACTORY SET BLOWER SPEEDS W/ELEC. HEAT
2.0 TON W/40K HEAT HIGH LOW
2.0 TON W/60K HEAT HIGH HIGH
2.0 TON W/80K HEAT HIGH HIGH
2.5 TON/ALL HEATS LOW LOW
3.0 TON/ALL HEATS MED. LOW
3.5 TON/ALL HEATS HIGH LOW
4.0 TON/ALL HEATS HIGH LOW
5.0 TON/ALL HEATS HIGH LOW
MODEL
FACTORY SET
BLOWER SPEED
COOL HEAT
Page 29
29
XII. GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series
Weights
Net Weight lbs. [kg] 409 [186] 409 [186] 413 [187] 413 [187] Ship Weight lbs. [kg] 418 [190] 418 [190] 422 [191] 422 [191]
Model RRNA- Series B024JK04E B024JK04X B024JK06E B024JK06X Cooling Performance
Gross Cooling Capacity Btu [kW] 24,800 [7.27] 24,800 [7.27] 24,800 [7.27] 24,800 [7.27] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 800/800 [378/378] 800/800 [378/378] 800/800 [378/378] ARI Net Cooling Capacity Btu [kW] 24,000 [7.03] 24,000 [7.03] 24,000 [7.03] 24,000 [7.03] Net Sensible Capacity Btu [kW] 17,171 [5.03] 17,171 [5.03] 17,171 [5.03] 17,171 [5.03] Net Latent Capacity Btu [kW] 6,829 [2] 6,829 [2] 6,829 [2] 6,829 [2] Net System Power kW 2.04 2.04 2.04 2.04
Heating Performance (Package Gas/Electric)
Heating Input Btu [kW] 40,000 [11.72] 40,000 [11.72] 60,000 [17.58] 60,000 [17.58] Heating Output Btu [kW] 31,000 [9.08] 31,000 [9.08] 47,000 [13.77] 47,000 [13.77] Temperature Rise Range °F [°C]
AFUE %
Steady State Efficiency (%) 81 81 81 81 No. Burners 2233 No. Stages 1111 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB) Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] Rows / FPI [FPcm] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2500 [1180] 2500 [1180] 2500 [1180] 2500 [1180] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/9x7 [228.6x177.8] 1/9x7 [228.6x177.8] 1/9x7 [228.6x177.8] Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 Direct/2 No. Motors 1111 Motor HP 1/4 1/4 1/4 1/4 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48 Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x20x20 [25x508x508] Refrigerant Charge Oz. [g] 69.6 [1973] 69.6 [1973] 69.6 [1973] 69.6 [1973]
2
4
1
11.8/13 11.8/13 11.8/13 11.8/13
3
30-60 [16.7/33.3] 30-60 [16.7/33.3] 40-70 [22.2/38.9] 40-70 [22.2/38.9]
80 80 80 80
5
76 76 76 76
(1)1x20x20 [25x508x508] (1)1x20x20 [25x508x508] (1)1x20x20 [25x508x508]
Continued ->
800/800 [378/378]
1/Copeland Scroll
1/9x7 [228.6x177.8]
Page 30
30
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series
Weights
Net Weight lbs. [kg] 418 [190] 418 [190] 416 [189] 416 [189] Ship Weight lbs. [kg] 427 [194] 427 [194] 425 [193] 425 [193]
Model RRNA- Series B024JK08E B024JK08X B030JK04E B030JK04X Cooling Performance
Gross Cooling Capacity Btu [kW] 24,800 [7.27] 24,800 [7.27] 31,200 [9.14] 31,200 [9.14] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 800/800 [378/378] 800/800 [378/378] 1000/1000 [472/472] ARI Net Cooling Capacity Btu [kW] 24,000 [7.03] 24,000 [7.03] 30,000 [8.79] 30,000 [8.79] Net Sensible Capacity Btu [kW] 17,171 [5.03] 17,171 [5.03] 20,984 [6.15] 20,984 [6.15] Net Latent Capacity Btu [kW] 6,829 [2] 6,829 [2] 9,016 [2.64] 9,016 [2.64] Net System Power kW 2.04 2.04 2.7 2.7
Heating Performance (Package Gas/Electric
Heating Input Btu [kW] 80,000 [23.44] 80,000 [23.44] 40,000 [11.72] 40,000 [11.72] Heating Output Btu [kW] 62,000 [18.17] 62,000 [18.17] 31,000 [9.08] 31,000 [9.08] Temperature Rise Range ºF [ºC] 55-85 [30.6/47.2] 55-85 [30.6/47.2] 20-50 [11.1/27.8] 20-50 [11.1/27.8]
AFUE %
Steady State Efficiency (%) 81 81 81 81 No. Burners 4422 No. Stages 1111 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB) Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] Rows / FPI [FPcm] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2500 [1180] 2500 [1180] 2500 [1180] 2500 [1180] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/9x7 [228.6x177.8] 1/9x7 [228.6x177.8] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/2 Direct/2 Direct/3 Direct/3 No. Motors 1111 Motor HP 1/4 1/4 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48 Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x20x20 [25x508x508] Refrigerant Charge Oz. [g] 69.6 [1973] 69.6 [1973] 72 [2041] 72 [2041]
2
4
1
11.8/13 11.8/13 11.1/13 11.1/13
3
)
80 80 80 80
5
76 76 76 76
(1)1x20x20 [25x508x508] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Continued ->
1000/1000 [472/472]
1/Copeland Scroll
1/10x9 [254x228.6]
Page 31
31
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series
Weights
Net Weight lbs. [kg] 421 [191] 421 [191] 426 [193] 426 [193] Ship Weight lbs. [kg] 430 [195] 430 [195] 435 [197] 435 [197]
Model RRNA- Series B030JK06E B030JK06X B030JK08E B030JK08X Cooling Performance
Gross Cooling Capacity Btu [kW] 31,200 [9.14] 31,200 [9.14] 31,200 [9.14] 31,200 [9.14] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 1000/1000 [472/472] 1000/1000 [472/472] 1000/1000 [472/472] ARI Net Cooling Capacity Btu [kW] 30,000 [8.79] 30,000 [8.79] 30,000 [8.79] 30,000 [8.79] Net Sensible Capacity Btu [kW] 20,984 [6.15] 20,984 [6.15] 20,984 [6.15] 20,984 [6.15] Net Latent Capacity Btu [kW] 9,016 [2.64] 9,016 [2.64] 9,016 [2.64] 9,016 [2.64] Net System Power kW 2.7 2.7 2.7 2.7
Heating Performance (Package Gas/Electric)
Heating Input Btu [kW] 60,000 [17.58] 60,000 [17.58] 80,000 [23.44] 80,000 [23.44] Heating Output Btu [kW] 47,000 [13.77] 47,000 [13.77] 62,000 [18.17] 62,000 [18.17] Temperature Rise Range ºF [ºC] 30-60 [16.7/33.3] 30-60 [16.7/33.3] 40-70 [22.2/38.9] 40-70 [22.2/38.9]
AFUE %
Steady State Efficiency (%) 81 81 81 81 No. Burners 3344 No. Stages 1111 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB) Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] 10.56 [0.98] Rows / FPI [FPcm] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2500 [1180] 2500 [1180] 2500 [1180] 2500 [1180] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1111 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48 Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] Refrigerant Charge Oz. [g] 72 [2041] 72 [2041] 72 [2041] 72 [2041]
2
4
1
11.1/13 11.1/13 11.1/13 11.1/13
3
80 80 80 80
5
76 76 76 76
(1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Continued ->
1000/1000 [472/472]
1/Copeland Scroll
1/10x9 [254x228.6]
Page 32
32
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
B036CK04E
Model RRNA - B Series
Weights
Net Weight lbs. [kg] 431 [196] 431 [196] 430 [195] 435 [197] Ship Weight lbs. [kg] 440 [200] 440 [200] 439 [199] 444 [201]
Model RRNA- Series B030JK10E B030JK10X Cooling Performance
Gross Cooling Capacity Btu [kW] 31,200 [9.14] 31,200 [9.14] 37,400 [10.96] 37,400 [10.96] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 1000/1000 [472/472] 1000/1000 [472/472] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 30,000 [8.79] 30,000 [8.79] 36,000 [10.55] 36,000 [10.55] Net Sensible Capacity Btu [kW] 20,984 [6.15] 20,984 [6.15] 25,736 [7.54] 25,736 [7.54] Net Latent Capacity Btu [kW] 9,016 [2.64] 9,016 [2.64] 10,264 [3.01] 10,264 [3.01] Net System Power kW 2.7 2.7 3.07 3.07
Heating Performance (Package Gas/Electric)
Heating Input Btu [kW] 100,000 [29.3] 100,000 [29.3] 40,000 [11.72] 60,000 [17.58] Heating Output Btu [kW] 77,000 [22.56] 77,000 [22.56] 32,400 [9.49] 48,600 [14.24] Temperature Rise Range ºF [ºC] 45-85 [25/47.2] 45-85 [25/47.2] 20-50 [11.1/27.8] 30-60 [16.7/33.3]
AFUE % Steady State Efficiency (%) 81 81 81 81 No. Burners 5523 No. Stages 1111 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB) Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 10.56 [0.98] 10.56 [0.98] 14.8 [1.37] 14.8 [1.37] Rows / FPI [FPcm] 1 / 18 [7] 1 / 18 [7] 1 / 22 [9] 1 / 22 [9] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2500 [1180] 2500 [1180] 2700 [1274] 2700 [1274] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1111 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48 Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] Refrigerant Charge Oz. [g] 72 [2041] 72 [2041] 83.2 [2359] 83.2 [2359]
2
4
1
11.1/13 11.1/13 11.7/13 11.7/13
3
80 80 80 80
5
76 76 76 76
(1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
B036CK06E
Continued ->
1200/1200 [566/566]
1/Copeland Scroll
1/10x9 [254x228.6]
Page 33
33
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B036CK08E B036CK10E B036DK06E B036DK08E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] EER/SEER
2
11.7/13 11.7/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] Net Sensible Capacity Btu [kW] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] Net Latent Capacity Btu [kW] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] Net System Power kW 3.07 3.07 3.07 3.07
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 80,000 [23.44] 100,000 [29.3] 60,000 [17.58] 80,000 [23.44] Heating Output Btu [kW] 64,800 [18.99] 81,000 [23.73] 48,600 [14.24] 64,800 [18.99] Temperature Rise Range °F [°C] 40-70 [22.2/38.9] 45-85 [25/47.2] 30-60 [16.7/33.3] 40-70 [22.2/38.9] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 4 5 3 4 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2700 [1274] 2700 [1274] 2700 [1274] 2700 [1274] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/2 Direct/2 No. Motors 1 1 1 1 Motor HP 1/2 1 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 83.2 [2359] 83.2 [2359] 83.2 [2359] 83.2 [2359] Weights
Net Weight lbs. [kg] 422 [191] 426 [193] 435 [197] 440 [200] Ship Weight lbs. [kg] 462 [210] 466 [211] 444 [201] 449 [204]
Continued ->
Page 34
34
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B036DK10E B036JK04E B036JK04X B036JK06E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] EER/SEER
2
11.7/13 11.7/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] Net Sensible Capacity Btu [kW] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] Net Latent Capacity Btu [kW] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] Net System Power kW 3.07 3.07 3.07 3.07
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 40,000 [11.72] 40,000 [11.72] 60,000 [17.58] Heating Output Btu [kW] 81,000 [23.73] 31,000 [9.08] 31,000 [9.08] 47,000 [13.77] Temperature Rise Range °F [°C] 45-85 [25/47.2] 20-50 [11.1/27.8] 20-50 [11.1/27.8] 30-60 [16.7/33.3] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 5 2 2 3 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2700 [1274] 2700 [1274] 2700 [1274] 2700 [1274] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/2 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 83.2 [2359] 83.2 [2359] 83.2 [2359] 83.2 [2359] Weights
Net Weight lbs. [kg] 444 [201] 412 [187] 412 [187] 417 [189] Ship Weight lbs. [kg] 453 [205] 452 [205] 452 [205] 457 [207]
Continued ->
Page 35
35
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B036JK06X B036JK08E B036JK08X B036JK10E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] 37,400 [10.96] EER/SEER
2
11.7/13 11.7/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] 36,000 [10.55] Net Sensible Capacity Btu [kW] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] 25,736 [7.54] Net Latent Capacity Btu [kW] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] 10,264 [3.01] Net System Power kW 3.07 3.07 3.07 3.07
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 60,000 [17.58] 80,000 [23.44] 80,000 [23.44] 100,000 [29.3] Heating Output Btu [kW] 47,000 [13.77] 62,000 [18.17] 62,000 [18.17] 77,000 [22.56] Temperature Rise Range °F [°C] 30-60 [16.7/33.3] 40-70 [22.2/38.9] 40-70 [22.2/38.9] 45-85 [25/47.2] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 3 4 4 5 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] 14.8 [1.37] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] 5.54 [0.51] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2700 [1274] 2700 [1274] 2700 [1274] 2700 [1274] No. Motors/HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP 1 at 1/5 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 83.2 [2359] 83.2 [2359] 83.2 [2359] 83.2 [2359] Weights
Net Weight lbs. [kg] 417 [189] 422 [191] 422 [191] 426 [193] Ship Weight lbs. [kg] 457 [207] 462 [210] 462 [210] 466 [211]
Continued ->
Page 36
36
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B036JK10X B042CK04E B042CK06E B042CK08E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 37,400 [10.96] 42,500 [12.45] 42,500 [12.45] 42,500 [12.45] EER/SEER
2
11.7/13 11.5/13 11.5/13 11.5/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1400/1350 [661/637] 1400/1350 [661/637] 1400/1350 [661/637] ARI Net Cooling Capacity Btu [kW] 36,000 [10.55] 41,000 [12.01] 41,000 [12.01] 41,000 [12.01] Net Sensible Capacity Btu [kW] 25,736 [7.54] 28,511 [8.35] 28,511 [8.35] 28,511 [8.35] Net Latent Capacity Btu [kW] 10,264 [3.01] 12,489 [3.66] 12,489 [3.66] 12,489 [3.66] Net System Power kW 3.07 3.57 3.57 3.57
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 40,000 [11.72] 60,000 [17.58] 80,000 [23.44] Heating Output Btu [kW] 77,000 [22.56] 32,400 [9.49] 48,600 [14.24] 64,800 [18.99] Temperature Rise Range °F [°C] 45-85 [25/47.2] 20-50 [11.1/27.8] 30-60 [16.7/33.3] 40-70 [22.2/38.9] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 5 2 3 4 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 14.8 [1.37] 16.65 [1.55] 16.65 [1.55] 16.65 [1.55] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 5.54 [0.51] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 2700 [1274] 3500 [1652] 3500 [1652] 3500 [1652] No. Motors/HP 1 at 1/5 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 83.2 [2359] 104 [2948] 104 [2948] 104 [2948] Weights
Net Weight lbs. [kg] 426 [193] 422 [191] 427 [194] 432 [196] Ship Weight lbs. [kg] 466 [211] 462 [210] 467 [212] 472 [214]
Continued ->
Page 37
37
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B042CK10E B042JK04E B042JK04X B042JK06E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 42,500 [12.45] 42,500 [12.45] 42,500 [12.45] 42,500 [12.45] EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1350 [661/637] 1400/1350 [661/637] 1400/1350 [661/637] 1400/1350 [661/637] ARI Net Cooling Capacity Btu [kW] 41,000 [12.01] 41,000 [12.01] 41,000 [12.01] 41,000 [12.01] Net Sensible Capacity Btu [kW] 28,511 [8.35] 28,511 [8.35] 28,511 [8.35] 28,511 [8.35] Net Latent Capacity Btu [kW] 12,489 [3.66] 12,489 [3.66] 12,489 [3.66] 12,489 [3.66] Net System Power kW 3.07 3.57 3.57 3.57
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 40,000 [11.72] 40,000 [11.72] 60,000 [1758] Heating Output Btu [kW] 81,000 [23.73] 31,000 [9.08] 31,000 [9.08] 47,000 [13.77] Temperature Rise Range °F [°C] 45-85 [25/47.2] 20-50 [11.1/27.8] 20-50 [11.1/27.8] 30-60 [16.7/33.3] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 5 2 2 3 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.65 [1.55] 16.65 [1.55] 16.65 [1.55] 16.65 [1.55] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3500 [1652] 3500 [1652] 3500 [1652] 3500 [1652] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 104 [2948] 104 [2948] 104 [2948] 104 [2948] Weights
Net Weight lbs. [kg] 437 [198] 422 [191] 422 [191] 427 [194] Ship Weight lbs. [kg] 477 [216] 462 [210] 462 [210] 467 [212]
Continued ->
Page 38
38
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B042JK06X B042JK08E B042JK08X B042JK10E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 42,500 [12.45] 42,500 [12.45] 42,500 [12.45] 42,500 [12.45] EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1350 [661/637] 1400/1350 [661/637] 1400/1350 [661/637] 1400/1350 [661/637] ARI Net Cooling Capacity Btu [kW] 41,000 [12.01] 41,000 [12.01] 41,000 [12.01] 41,000 [12.01] Net Sensible Capacity Btu [kW] 28,511 [8.35] 28,511 [8.35] 28,511 [8.35] 28,511 [8.35] Net Latent Capacity Btu [kW] 12,489 [3.66] 12,489 [3.66] 12,489 [3.66] 12,489 [3.66] Net System Power kW 3.57 3.57 3.57 3.57
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 60,000 [17.58] 80,000 [23.44] 80,000 [23.44] 100,000 [29.3] Heating Output Btu [kW] 47,000 [13.77] 62,000 [18.17] 62,000 [18.17] 77,000 [22.56] Temperature Rise Range °F [°C] 30-60 [16.7/33.3] 40-70 [22.2/38.9] 40-70 [22.2/38.9] 45-85 [25/47.2] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 3 4 4 5 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 76 76 76
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.65 [1.55] 16.65 [1.55] 16.65 [1.55] 16.65 [1.55] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3500 [1652] 3500 [1652] 3500 [1652] 3500 [1652] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 104 [2948] 104 [2948] 104 [2948] 104 [2948] Weights
Net Weight lbs. [kg] 427 [194] 432 [196] 432 [196] 437 [198] Ship Weight lbs. [kg] 467 [212] 472 [214] 472 [214] 477 [216]
Continued ->
Page 39
39
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B042JK10X B048CK06E B048CK08E B048CK10E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 42,500 [12.45] 50,500 [14.8] 50,500 [14.8] 50,500 [14.8] EER/SEER
2
11.5/13 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1350 [661/637] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] ARI Net Cooling Capacity Btu [kW] 41,000 [12.01] 48,500 [14.21] 48,500 [14.21] 48,500 [14.21] Net Sensible Capacity Btu [kW] 28,511 [8.35] 34,516 [10.11] 34,516 [10.11] 34,516 [10.11] Net Latent Capacity Btu [kW] 12,489 [3.66] 13,984 [4.1] 13,984 [4.1] 13,984 [4.1] Net System Power kW 3.57 4.18 4.18 4.18
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 60,000 [17.58] 80,000 [23.44] 100,000 [29.3] Heating Output Btu [kW] 77,000 [22.56] 48,600 [14.24] 64,800 [18.99] 81,000 [23.73] Temperature Rise Range °F [°C] 45-85 [25/47.2] 30-60 [16.7/33.3] 40-70 [22.2/38.9] 45-85 [25/47.2] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 5 3 4 5 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
76 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.65 [1.55] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] Rows / FPI [FPcm] 1 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3500 [1652] 3300 [1557] 3300 [1557] 3300 [1557] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 3/4 3/4 3/4 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 104 [2948] 153.6 [4355] 153.6 [4355] 153.6 [4355] Weights
Net Weight lbs. [kg] 437 [198] 452 [205] 457 [207] 462 [210] Ship Weight lbs. [kg] 477 [216] 492 [223] 497 [225] 502 [228]
Continued ->
Page 40
40
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B048DK10E B048JK06E B048JK06X B048JK08E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 50,500 [14.8] 50,500 [14.8] 50,500 [14.8] 50,500 [14.8] EER/SEER
2
11.6/13 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] ARI Net Cooling Capacity Btu [kW] 48,500 [14.21] 48,500 [14.21] 48,500 [14.21] 48,500 [14.21] Net Sensible Capacity Btu [kW] 34,516 [10.11] 34,516 [10.11] 34,516 [10.11] 34,516 [10.11] Net Latent Capacity Btu [kW] 13,984 [4.1] 13,984 [4.1] 13,984 [4.1] 13,984 [4.1] Net System Power kW 4.18 4.18 4.18 4.18
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 60,000 [17.58] 60,000 [17.58] 80,000 [23.44] Heating Output Btu [kW] 81,000 [23.73] 47,000 [13.77] 47,000 [13.77] 62,000 [18.17] Temperature Rise Range °F [°C] 45-85 [25/47.2] 30-60 [16.7/33.3] 30-60 [16.7/33.3] 40-70 [22.2/38.9] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 5 3 3 4 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3300 [1557] 3300 [1557] 3300 [1557] 3300 [1557] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/2 Direct/3 Direct/3 Direct/3 No. Motors 1 1 1 1 Motor HP 3/4 3/4 3/4 3/4 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 153.6 [4355] 153.6 [4355] 153.6 [4355] 153.6 [4355] Weights
Net Weight lbs. [kg] 551 [250] 461 [209] 461 [209] 466 [211] Ship Weight lbs. [kg] 560 [254] 501 [227] 501 [227] 506 [230]
Continued ->
Page 41
41
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRNA - B Series B048JK08X B048JK10E B048JK10X B060CK10E
Cooling performance
1
Gross Cooling Capacity Btu [kW] 50,500 [14.8] 50,500 [14.8] 50,500 [14.8] 60,000 [17.58] EER/SEER
2
11.6/13 11.6/13 11.6/13 11.1/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 2000/1850 [897/873] ARI Net Cooling Capacity Btu [kW] 48,500 [14.21] 48,500 [14.21] 48,500 [14.21] 58,000 [16.99] Net Sensible Capacity Btu [kW] 34,516 [10.11] 34,516 [10.11] 34,516 [10.11] 40,561 [11.88] Net Latent Capacity Btu [kW] 13,984 [4.1] 13,984 [4.1] 13,984 [4.1] 17,439 [5.11] Net System Power kW 4.18 4.18 4.18 5.2
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 80,000 [23.44] 100,000 [29.3] 100,000 [29.3] 100,000 [29.3] Heating Output Btu [kW] 62,000 [18.17] 77,000 [22.56] 77,000 [22.56] 81,000 [23.73] Temperature Rise Range °F [°C] 40-70 [22.2/38.9] 45-85 [25/47.2] 45-85 [25/47.2] 45-85 [25/47.2] AFUE %
4
80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 4 5 5 5 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3300 [1557] 3300 [1557] 3300 [1557] 3300 [1557] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/3 Direct/3 Direct/3 Direct/2 No. Motors 1 1 1 1 Motor HP 3/4 3/4 3/4 1 Motor RPM 1075 1075 1075 1075 Motor Frame Size 48 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x30 [25x610x762]
Refrigerant Charge Oz. [g] 153.6 [4355] 153.6 [4355] 153.6 [4355] 145.6 [4128] Weights
Net Weight lbs. [kg] 466 [211] 471 [214] 471 [214] 532 [241] Ship Weight lbs. [kg] 506 [230] 511 [232] 511 [232] 577 [262]
Continued ->
Page 42
42
GENERAL DATA - RRNA-B MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
NOTES:
1 Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. AFUE is rated in accordance with DOE test procedures.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model RRNA - B Series B060DK10E B060JK10E B060JK10X
Cooling performance
1
Gross Cooling Capacity Btu [kW] 60,000 [17.58] 60,000 [17.58] 60,000 [17.58] EER/SEER
2
10.8/12.1 11.1/13 11.1/13 Nominal CFM/ARI Rated CFM [L/s] 2000/1850 [897/873] 2000/1850 [897/873] 2000/1850 [897/873] ARI Net Cooling Capacity Btu [kW] 57,500 [16.85] 58,000 [16.99] 58,000 [16.99] Net Sensible Capacity Btu [kW] 40,169 [11.77] 40,561 [11.88] 40,561 [11.88] Net Latent Capacity Btu [kW] 17,331 [5.08] 17,439 [5.11] 17,439 [5.11] Net System Power kW 5.31 5.2 5.2
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW] 100,000 [29.3] 100,000 [29.3] 100,000 [29.3] Heating Output Btu [kW] 81,000 [23.73] 77,000 [22.56] 77,000 [22.56] Temperature Rise Range °F [°C] 45-85 [25/47.2] 45-85 [25/47.2] 45-85 [25/47.2] AFUE %
4
80 80 80 Steady State Efficiency (%) 81 81 81 No. Burners 5 5 5 No. Stages 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.23 [1.51] 16.23 [1.51] 16.23 [1.51] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 7.39 [0.69] 7.39 [0.69] 7.39 [0.69] Rows / FPI [FPcm] 2 / 15 [6] 2 / 15 [6] 2 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/22 [558.8] 1/22 [558.8] 1/22 [558.8] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM [L/s] 3300 [1557] 3300 [1557] 3300 [1557] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x228.6] 1/10x9 [254x228.6] 1/10x9 [254x228.6] Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 No. Motors 1 1 1 Motor HP 1 1 1 Motor RPM 1075 1075 1075 Motor Frame Size 48 48 48
Filter - Type Field Supplied Field Supplied Field Supplied
Furnished No No No (NO.) Size Recommended in. [mm x mm x mm] (1)1x24x30 [25x610x762] (1)1x24x30 [25x610x762] (1)1x24x30 [25x610x762]
Refrigerant Charge Oz. [g] 145.6 [4128] 145.6 [4128] 145.6 [4128] Weights
Net Weight lbs. [kg] 574 [260] 532 [241] 532 [241] Ship Weight lbs. [kg] 583 [264] 577 [262] 577 [262]
Page 43
43
XII. MISCELLANEOUS
187-253 187-253 187-253 414-506 414-506 414-506 187-253 187-253 187-253 187-253 187-253 187-253 414-506 187-253 414-506
16/16 22/22 22/22 9 9 9 25/25 32/32 42/42 16/16 18/18 22/22 11 33/33 12
20/20 25/25 30/30 15 15 15 30/30 40/40 50/50 20/20 20/20 25/25 15 40/40 15
25/25 35/35 35/35 15 15 15 40/40 50/50 60/60 25/25 25/25 30/30 15 45/45 15
1111 1 111 11 1111 1
208/230 208/230 208/230 460 460 460 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 460
1113 3 311 13 3333 3
2 1/6 2 2/3 3 1/3 3 1/3 3 1/3 3 1/3 3 1/2 4 5 3 1/3 3 1/2 4 4 5 5
3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450
10.4/10.4 14.1/14.1 14.4/14.4 5.8 5.8 5.8 16.5/16.5 20.2/20.2 25/25 9.6/9.6 10.3/10.3 12.2/12.2 6.1 17.3/17.3 6.7
54/54 68/68 77/77 35 35 35 95/95 137/137 148/148 88/88 77/77 80.8/80.8 41 123/123 49.5
1111 1 111 11 1111 1
208/230 208/230 208/230 460 460 460 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 460
1111 1 111 11 1111 1
1/5 1/5 1/5 1/5 1/5 1/5 1/3 1/3 1/3 1/5 1/3 1/3 1/3 1/3 1/3
1.3 1.3 1.3 0.5 0.5 0.5 2 2 2 1.3 2 2 1 2 1
2.3 2.3 2.3 1.1 1.1 1.1 3.9 3.9 3.9 2.3 3.9 3.9 2.2 3.9 2.2
1111 1 111 11 1111 1
208/230 208/230 208/230 460 460 460 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 460
1111 1 111 11 1111 1
1/4 1/2 1/2 1/2 1/2 1/2 1/2 3/4 1 1/2 1/2 3/4 3/4 1 3/4
1.3 2.4 2.4 1.2 1.2 1.2 2.4 4.4 9.1 2.4 2.4 4.4 2.3 9.1 2.3
2.3 5.1 5.1 2.2 2.2 2.2 5.1 9.5 0 5.1 5.1 9.5 5 0 5
Unit InformationCompressor MotorCondenser MotorEvaporator Fan
ELECTRICAL DATA – RRNA-B SERIES
-B024JK -B030JK -B036JK -B036DK06E -B036DK08E -B036DK10E -B042JK -B048JK -B060JK -B036CK -B042CK -B048CK -B048DK10E -B060CK -B060DK10E
Unit Operating Voltage Range
Minimum Circuit
Ampacity
Minimum Overcurrent
Protection Device Size
Maximum Overcurrent
Protection Device Size
No.
Volts
Phase
HP
RPM
Amps (FLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)
1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
Page 44
44
INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE GAS ELECTRIC UNITS
DIRECT DRIVE
NOTE: On 4 ton models, switch to medium speed for cooling if external static pressure is less than 0.4" W.C. at 230 or 460 volts or less than 0.3" W.C. at 208 volts.
WARNING: 1. Do not operate unit in area of airflow table shown in bold (CFM greater than 1700 for 4 ton models) due to possibility of water blow-off.
WARNING: Observe airflow operating limits if operating in area of airflow table shown in bold.
[ ] Designates Metric Conversions
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 771 [364] 751 [354] 725 [342] 691 [326] 654 [304] 584 [276] 546 [258]
RPM 825 870 910 950 985 1010 1030
Watts 253 242 230 217 204 189 181
CFM 946 [446] 922 [435] 882 [416] 830 [392] 769 [363] 701 [331] 630 [298]
RPM 990 1015 1035 1055 1070 1085 1100
Watts 315 303 288 273 257 241 226
CFM 1206 [569] 1182 [558] 1157 [546] 1128 [532] 1091 [515] 1044 [493] 983 [464]
RPM 760 815 870 910 950 975 1000
Watts 419 406 394 381 368 353 334
CFM 1411 [666] 1368 [646] 1327 [626] 1285 [606] 1238 [584] 1183 [558] 1116 [527]
RPM 865 900 935 970 1000 1020 1035
Watts 498 481 464 447 430 411 391
CFM 1641 [774] 1577 [744] 1515 [715] 1455 [687] 1393 [657] 1329 [627] 1262 [596]
RPM 980 1000 1020 1035 1050 1065 1080
Watts 589 565 543 523 503 481 456
CFM 1412 [666] 1395 [658] 1371 [647] 1339 [632] 1296 [612] 1242 [586] 1176 [555]
RPM 859 905 951 981 1011 1034 1057
Watts 557 530 506 483 461 437 409
CFM 1793[846] 1731[817] 1665 [786] 1594 [752] 1519 [717] 1440 [680] 1356 [640]
RPM 1053 1067 1080 1091 1101 1110 1119
Watts 667 637 606 574 543 512 483
CFM 1889[892] 1826[862] 1753[827] 1672 [789] 1586 [749] 1499 [707] 1413 [667]
RPM 1110 1117 1124 1129 1133 1139 1144
Watts 736 715 683 646 608 574 551
CFM 1500 [707]
RPM 895 952 1010 1064 1102 1144 1196
Watts 318 358 400 442 469 500 541
CFM 1850 [873]
RPM 1096 1145 1191 1237 1278 1317 1353
Watts 593 643 692 743 791 836 875
CFM 1388 [654] 1380 [651] 1371 [646] 1351 [637] 1325 [625] 1294 [610] 1225 [577]
RPM 741 794 858 904 947 985 1021
Watts 595 583 564 539 510 484 453
CFM 1943 [916] 1895 [893] 1840 [867] 1774 [836] 1700 [801] 1618 [763] 1525 [719]
RPM 995 1024 1040 1057 1041 1087 1100
Watts 785 751 717 674 643 599 561
CFM 2150 [1014] 2072 [977] 1991 [939] 1917 [904] 1820 [858] 1722 [812] 1627 [767]
RPM 1080 1093 1100 1106 1115 1123 1130
Watts 889 884 796 768 725 687 651
CFM [L/s] Air Delivery/RPM/Watts — 230/460 VOLTS
Side Discharge — Wet Coil
External Static Pressure — Inches W.C. [kPa]
Nominal
Cooling
Capacity
Tons [kW]
Motor Speed
From Factory
Heating
Input
BTU/HR [kW]
Blower Size/
Motor HP [W] &
# of Speeds
Motor
Speed
INDOOR AIRFLOW PERFORMANCE — 230/460 VOLTS
Cool Heat
Low
Low
High
Med
High
High
Med Low
Low
Low Low
High
2.0 [7.03]
2.5 [8.79]
3.0 [10.55]
40,000 [11.72]
All
Inputs
40,000 [11.72]
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
All
Inputs
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
100,000 [29.31]
60,000 [17.58]
80,000 [23.45]
9 x 7
1/4 HP
2 Speed Motor
10 x 9
1/2 HP
3 Speed Motor
10 x 9
3/4 HP
3 Speed Motor
10 x 9
1 HP ECM
(Constant CFM)
High
High
Low
3.5 [12.31]
Low
High
(See
Note
Below)
Low
Low
4.0 [14.07]
Med
High
100,000 [29.31]
10 x 9
3/4 HP
3 Speed Motor
Low
High
Low
5.0 [17.59] (460 Volt only)
Med
High
Low
High
High
5.0 [17.59] (230 Volt only)
Page 45
45
INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE GAS ELECTRIC UNITS
DIRECT DRIVE
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 675 [319] 657 [310] 634 [299] 602 [284] 560 [264] 505 [238] 435 [205]
RPM 695 785 870 905 940 980 1020
Watts 221 214 203 191 171 193 149
CFM 898 [424] 861 [406] 822 [388] 777 [367] 721 [340] 651 [307] 562 [265]
RPM 940 965 995 1020 1045 1070 1090
Watts 292 278 266 253 239 221 199
CFM 1076 [508] 1059 [500] 1032 [490] 996 [470] 950 [448] 896 [423] 832 [393]
RPM 730 775 820 865 905 940 975
Watts 356 349 341 331 320 305 287
CFM 1222 [577] 1197 [565] 1179 [556] 1162 [548] 1137 [537] 1097 [518] 1033 [488]
RPM 765 810 855 890 920 960 995
Watts 423 415 407 397 386 370 351
CFM 1514 [715] 1461 [670[ 1415 [668] 1370 [647] 1322 [624] 1266 [597] 1197 [565]
RPM 895 930 965 985 1005 1025 1045
Watts 538 514 493 473 454 434 412
CFM 1204 [568] 1202 [567] 1191 [562] 1171 [553] 1143 [539] 1107 [522] 1065 [503]
RPM 734 810 886 923 959 988 1016
Watts 476 468 450 427 403 380 363
CFM 1674 [790] 1620 [765] 1566 [739] 1511 [713] 1451 [685] 1384 [653] 1305 [616]
RPM 997 1019 1040 1058 1076 1088 1100
Watts 625 596 567 539 512 484 455
CFM 1843[870] 1763[832] 1693 [799] 1627 [768] 1560 [736] 1485 [701] 1398 [660]
RPM 1085 1094 1102 1110 1118 1126 1134
Watts 699 663 632 604 576 548 517
CFM 1500 [707]
RPM 896 956 1008 1062 1093 1145 1194
Watts 317 358 393 435 457 493 531
CFM 1850 [873]
RPM 1091 1141 1185 1233 1267 1308 1336
Watts 579 630 673 724 759 800 826
CFM [L/s] Air Delivery/RPM/Watts — 208 VOLTS
Side Discharge — Wet Coil
External Static Pressure — Inches W.C. [kPa]
Nominal
Cooling
Capacity
Tons [kW]
Motor Speed
From Factory
Heating
Input
BTU/HR [kW]
Blower Size/
Motor HP [W] &
# of Speeds
Motor
Speed
INDOOR AIRFLOW PERFORMANCE — 208 VOLTS
Cool Heat
Low
Low
High
Med
High
High
Med Low
Low
Low Low
High
2.0 [7.03]
2.5 [8.79]
3.0 [10.55]
40,000 [11.72]
All
Inputs
40,000 [11.72]
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
All
Inputs
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
100,000 [29.31]
60,000 [17.58]
80,000 [23.45]
9 x 7
1/4 HP
2 Speed Motor
10 x 9
1/2 HP
3 Speed Motor
10 x 9
3/4 HP
3 Speed Motor
10 x 9
1 HP ECM
(Constant CFM)
HighHigh Low3.5 [12.31]
Low
High
(See
Note
Below)
Low
Low
4.0 [14.07]
Med
High
Low
High
High5.0 [17.59]
NOTE: On 4 ton models, switch to medium speed for cooling if external static pressure is less than 0.4" W.C. at 230 volts or less than 0.3" W.C. at 208 volts.
WARNING: 1. Do not operate unit in area of airflow table shown in bold (CFM greater than 1700 for 4 ton models) due to possibility of water blow-off.
WARNING: Observe airflow operating limits if operating in area of airflow table shown in bold.
DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s] 600 [283] 800 [378] 1000 [472] 1200 [566] 1440 [661] 1600 [755] 1800 [850] 2000 [944]
Pressure Drop—Inches W.C. [kPa] .00 .01 [.002] .02 [.005] .03 [.007] .05 [.012] .07 [.017] .08 [.019] .09 [.022]
MINIMUM RECOMMENDED FILTER SIZES
Nominal Cooling Capacity Tons [kW] 2.0 [7.03] 2.5 [8.79] – 4.0 [14.07] 5.0 [17.59]
Minimum Filter Size—Inches [mm] 20 x 20 x 1 [508 x 508 x 25] 24 x 24 x 1 [610 x 610 x 25] 24 x 30 x 1 [610 x 762 x 1]
Page 46
46
FIGURE 24
WIRING DIAGRAM
Page 47
47
FIGURE 25
WIRING DIAGRAM
Page 48
48
FIGURE 26
WIRING DIAGRAM
Page 49
49
FIGURE 27
WIRING DIAGRAM
Page 50
50
FIGURE 28
WIRING DIAGRAM
Page 51
51
FIGURE 29
SYSTEM CHARGE CHARTS
2 TON COOLING - 13 SEER
Page 52
52
FIGURE 30
SYSTEM CHARGE CHARTS
2.5 TON COOLING - 13 SEER
Page 53
53
FIGURE 31
SYSTEM CHARGE CHARTS
3 TON COOLING - 13 SEER
Page 54
54
FIGURE 32
SYSTEM CHARGE CHARTS
3.5 TON COOLING - 13 SEER
Page 55
55
FIGURE 33
SYSTEM CHARGE CHARTS
4 TON COOLING - 13 SEER
Page 56
56
FIGURE 34
SYSTEM CHARGE CHARTS
5 TON COOLING - 13 SEER
Page 57
57
FIGURE 35
COOLING TROUBLE SHOOTING CHART
!
WARNING
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in control
• Thermostat out of calibration-set too high • Reset
• Failed contactor • Check for 24 volts at contactor coil - replace if contacts are
• Blown fuses • Replace fuses
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) • Reset-also see high head pressure remedy-The high pressure
• Interconnecting low voltage wiring damaged • Replace thermostat wiring
Condenser fan runs, compressor • Run or start capacitor failed (single phase only) • Replace
doesn’t • Start relay defective 9single phase only) • Replace
• Loose connection • Check for correct voltage at compressor -
• Compressor stuck, grounded or open motor winding • Wait at least 2 hours for overload to reset. open internal overload. If still open, replace the compressor.
• Low voltage condition At compressor terminals, voltage must be within 10% of rating
• Low voltage condition • Add start kit components
Insufficient cooling • Improperly sized unit • Recalculate load
• Improper airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage • At compressor terminals, voltage must be within 10% of rating
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
Registers sweat • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
box
open
control opens at 450 PSIG
check & tighten all connections
plate volts when unit is operating.
plate volts when unit is operating.
nameplate marking when unit is operating.
filter
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component
High head-high or normal vapor • Dirty condenser coil • Clean coil
pressure - Cooling mode • Refrigerant overcharge • Correct system charge
Low head-high vapor pressures • Defective Compressor valves • Replace compressor
Low vapor - cool compressor - • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
iced evaporator coil filter
High vapor pressure • Excessive load • Recheck load calculation
Fluctuating head & vapor • TXV hunting • Check TXV bulb clamp - check air distribution on coil - replace
pressures TXV
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
Circulating air blower & inducer • Manual reset overtemperature control • Reset or replace
run continuously, • tripped
compressor will not start • Wire loose in limit circuit • Check wiring
• Flow check piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
• TXV does not open • Replace TXV
• Condenser fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
• Incorrect capillary tubes • Replace coil assembly
• Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
• Defective compressor • Replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
Page 58
58
FIGURE 36
15 SECOND PREPURGE
Page 59
59
Page 60
60
CM 1005
Loading...