RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2008
PACKAGE GAS ELECTRIC FEATURING NEW INDUSTRY
STANDARD R-410A REFRIGERANT
THE MANUFACTURER’S WARRANTY
DOES NOT COVER ANY DAMAGE OR
DEFECT TO THE AIR CONDITIONER
CAUSED BY THE ATTACHMENT OR
USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN
THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE
THAT THE USE OF UNAUTHORIZED
COMPONENTS, ACCESSORIES OR
DEVICES MAY ADVERSELY AFFECT
THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER
LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY
RESPONSIBILITY FOR SUCH LOSS
OR INJURY RESULTING FROM THE
USE OF SUCH UNAUTHORIZED
COMPONENTS, ACCESSORIES OR
DEVICES.
▲WARNING
!
UNITS ARE NOT DESIGN CERTIFIED
TO BE INSTALLED INSIDE THE
STRUCTURE. DOING SO CAN CAUSE
INADEQUATE UNIT PERFORMANCE
AS WELL AS PROPERTY DAMAGE
AND CARBON MONOXIDE POISONING RESULTING IN PERSONAL
INJURY OR DEATH.
▲WARNING
!
PROVIDE ADEQUATE COMBUSTION
AND VENTILATION AIR TO THE UNIT
SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR
SECTION OF THESE INSTRUCTIONS.
CHECKING PRODUCT RECEIVED
This booklet contains the installation and operating instructions for your combination
gas heating/electric cooling unit. There are some precautions that should be taken to
derive maximum satisfaction from it. Improper installation can result in unsatisfactory
operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required
to make up the system prior to installation. Give this booklet to the owner and explain
its provisions. The owner should retain this booklet for future reference.
EQUIPMENT PROTECTION FROM THE
ENVIRONMENT
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. IMPORTANT: Check the unit model number, heating size, electrical character-
istics, and accessories to determine if they are correct.
I. SPECIFICATIONS
A. GENERAL
The Combination Gas Heating/Electric Cooling Rooftop is available in 250,000 AND
350,000 BTUH heating input with nominal cooling capacity of 15 tons. 300,000 and
400,000 BTUH heating inputs are available in nominal cooling capacity of 20 tons.
Units are convertible from bottom supply and return to side supply and return by relocation of supply and return air cover panels. See cover installation detail and Figures
10 &11.
The units are weatherized for mounting outside of the building.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed refrigerating system consisting of a scroll
compressor, condenser coil, evaporator coil with capillary tube assembly or TXV, a
circulation air blower, condenser fans, a heat exchanger assembly, gas burner and
control assembly, combustion air motors and fan, and all necessary internal electrical
wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.
C. R410A REFRIGERANT
All units are factory charged with R-410A refrigerant.
1. Specification of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must
accommodate its higher pressures. It cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-
22. Recovery and recycle equipment, pumps, hoses, and the like need to have design
pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig
high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a
service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service
pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never
be done with a mixture of R-410A and air. Leak checking can be performed safely with
nitrogen or a mixture of R-410A and nitrogen.
2. Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-
22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil.
3
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for
equipment charging. Post March 1999 cylinders do not have a dip tube and should be
inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
3. Evaporator Coil/ Expansion Device
The capillary tubes are specifically designed to operate with R-410A. DO NOT use an R22 expansion device. The existing evaporator must be replaced with the factory
specified evaporator specifically designed for R-410A.
4. Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High Side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
▲CAUTION
!
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
4
SAFETY INFORMATION
!
▲WARNING
USE ONLY WITH TYPE OF GAS
APPROVED FOR THIS UNIT. REFER
TO THE UNIT RATING PLATE.
▲WARNING
!
INSTALL THIS UNIT ONLY IN A LOCATION AND POSITION AS SPECIFIED
IN THE LOCATION REQUIREMENTS
AND CONSIDERATIONS SECTION OF
THESE INSTRUCTIONS. PROVIDE
ADEQUATE COMBUSTION AND VENTILATION AIR TO THE UNIT SPACE
AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
▲WARNING
!
PROVIDE ADEQUATE COMBUSTION
AND VENTILATION AIR TO THE UNIT
SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR
SECTION OF THESE INSTRUCTIONS.
▲WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE
DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN
GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
▲WARNING
!
ALWAYS INSTALL UNIT TO OPERATE WITHIN THE UNIT'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED
IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO UNIT RATING
PLATE.
!
▲WARNING
WHEN A UNIT IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE UNIT TO AREAS OUTSIDE THE SPACE CONTAINING THE
UNIT, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED
TO THE UNIT CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE UNIT.
▲WARNING
!
COMBUSTION PRODUCTS MUST BE
DISCHARGED OUTDOORS.
CONNECT THIS UNIT TO AN
APPROVED VENT SYSTEM ONLY, AS
SPECIFIED IN VENT PIPE
INSTALLATION SECTION OF THESE
INSTRUCTIONS.
▲WARNING
!
THIS UNIT MAY BE USED TO HEAT THE BUILDING OR STRUCTURE DURING
CONSTRUCTION IF THE FOLLOWING INSTALLATION REQUIREMENTS ARE
MET. INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING
PLATE MARKING;
• MEANS OF PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND
80°F (27°C); AND
• INSTALLATION OF EXHAUST AND COMBUSTION AIR INLET HOODS
COMPLETED;
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY
FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE,
TEMPERATURE RISE AND VENTING ACCORDING TO THE INSTRUCTIONS.
5
Unit
Dimensions
FOR CLEARANCES
SEE PAGE 12, FIGURE 12.
IMPORTANT: THIS
UNIT MUST BE
MOUNTED LEVEL IN
BOTH DIRECTIONS TO
ALLOW WATER TO
DRAIN FROM THE
CONDENSER SECTION AND CONDENSATE PAN.
FIGURE 1
BOTTOM VIEW
Typical Dimensions Shown
in Inches
ST-A1182-02A-00
FIGURE 2
SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS –
BOTTOM VIEW
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
No. Used/Diameter in. [mm]2/18x9 [457x229]2/18x9 [457x229]2/18x9 [457x229]2/18x9 [457x229]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP3555
Motor RPM1725172517251725
Motor Frame Size56184184184
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
No. Used/Diameter in. [mm]3/24 [609.6]3/24 [609.6]3/24 [609.6]3/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]10000 [4719]10000 [4719]10000 [4719]10000 [4719]
No. Motors/HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP3 at 1/2 HP
Motor RPM1075107510751075
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508](8)2x25x20 [51x635x508]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
10.5/NA
Nominal CFM/AHRI Rated CFM [L/s]8000/7825 [3775/3693]
AHRI Net Cooling Capacity Btu [kW]240,000 [70.32]
Net Sensible Capacity Btu [kW]175,000 [51.27]
Net Latent Capacity Btu [kW]65,000 [19.04]
3
IEER
10.5
Net System Power kW22.88
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)200,000/400,000 [58.6/117.2]
Heating Output Btu [kW] (1st Stage / 2nd Stage)162,000/324,000 [47.47/94.93]
Temperature Rise Range °F [°C] (1st Stage / 2nd Stage) 25-55 [13.9-30.6] / 25-55 [13.9-30.6]
Steady State Efficiency (%)81
No. Burners14
No. Stages2
Gas Connection Pipe Size in. [mm]0.75 [19]
Compressor
No./Type2/Scroll
Outdoor Sound Rating (dB)
5
91
Outdoor Coil—Fin TypeLouvered
Tube TypeMicroChannel
MicroChannel Depth in. [mm]1 [25.4]
Face Area sq. ft. [sq. m]50.8 [4.72]
Rows / FPI [FPcm]1 / 23 [9]
Indoor Coil—Fin TypeLouvered
Tube TypeRifled
Tube Size in. [mm]0.375 [9.5]
Face Area sq. ft. [sq. m]26.67 [2.48]
Rows / FPI [FPcm]3 / 13 [5]
Refrigerant ControlCapillary Tubes
Drain Connection No./Size in. [mm]1/1 [25.4]
Outdoor Fan—TypePropeller
No. Used/Diameter in. [mm]3/24 [609.6]
Drive Type/No. SpeedsDirect/1
CFM [L/s]10000 [4719]
No. Motors/HP3 at 1/2 HP
Motor RPM1075
Indoor Fan—TypeFC Centrifugal
No. Used/Diameter in. [mm]2/18x9 [457x229]
Drive Type/No. SpeedsBelt/Variable
No. Motors1
Motor HP7 1/2
Motor RPM1725
Motor Frame Size213
Filter—TypeDisposable
FurnishedYes
(NO.) Size Recommended in. [mm x mm x mm](8)2x25x20 [51x635x508]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]200/219 [5670/6209]
Weights
Net Weights lbs. [kg]2092 [949]
Ship Weights lbs. [kg]2218 [1006]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is
based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.