Rheem ASL-JEC 18 Seer, RASL-024JEC, RASL-036JEC, RASL-039JEC, RASL-048JEC Installation Instructions Manual

...
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALLATION INSTRUCTIONS
ISO 9001:2008
AIR-COOLED CONDENSING UNITS
(-)ASL-JEC 18 SEER EQUIPPED WITH THE COMFORT CONTROL SYSTEM™ AND FEATURING DUAL DRIVE COMPRESSORS IN SELECT MODELS
2
[ ] INDICATES METRIC CONVERSIONS
Featuring Industry Standard R-410A Refrigerant
92-101691-05-06
SUPERSEDES 92-101691-05-05
TABLE OF CONTENTS
1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Electrical and Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.0 LOCATING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
.2 Condenser Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3
3.3 Operational Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 For Condensers With Space Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Customer Satisfaction Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.6 Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.7 Factory-Preferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Tools Required for Installing & Servicing R-410A Models . . . . . . . . . . . . . . 9
4.2 Specifications of R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Quick Reference Guide for R-410-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 REPLACEMENT UNITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.0 INDOOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.0 INTERCONNECTING TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.1 Vapor and Liquid Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.2 Maximum Length of Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.3 Outdoor Unit Installed Above or Below Indoor Coil . . . . . . . . . . . . . . . . . . 12
7.4 Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.5 Tubing Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.6 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.0 DUAL DRIVE COMPRESSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 Compressor Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.2 Comfort Control
8.3 Comfort Control
9.0 COMPRESSOR CRANKCASE HEAT (CCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10.0 HARD START COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11.0 HIGH AND LOW PRESSURE CONTROLS (HPC AND LPC). . . . . . . . . . . . . . . 17
11.1 Evacuation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12.0 CONDENSING UNITS EQUIPPED WITH THE COMFORT CONTROL
SYSTEM™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12.1 Control Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12.2 Comfort Control
12.3 Comfort Control
12.4 Comfort Control
12.5 Active Compressor Protection Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12.6 Test and Fault Recall Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
12.7 ICC Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
12.8 Conventional 24VAC Thermostat Control Wiring . . . . . . . . . . . . . . . . . . . 29
12.9 Typical Non-Communicating Thermostat Wiring Diagrams. . . . . . . . . . . . 30
12.10 Diagnostic Codes in Dual Drive Condensing Units With Conventional
Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12.11 ICC Control Operation with Conventional Thermostat Wiring . . . . . . . . . . 31
12.12 Active Compressor Protection Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12.13 Test and Fault Recall Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
13.0 ELECTRICAL WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13.1 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13.2 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
13.3 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
14.0 START-UP AND PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
15.0 CHECKING AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
16.0 CHECKING REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16.1 Charging Units With R-410A Refrigerant. . . . . . . . . . . . . . . . . . . . . . . . . . 37
16.2 Charging By Liquid Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16.3 Charging By Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16.4 Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
17.0 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
17.1 Remote Outdoor Temperature Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
17.2 RXME-A02 Communicating 2 Wire Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
18.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
18.1 Comfort Control
18.2 Replacement of Comfort Control
18.3 Electrical Checks Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
18.4 Cooling Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . 41
18.5 General Trouble Shooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
18.6 Service Analyzer Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-47
18.7 Subcooling Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
19.0 WIRING DIAGRAMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-50
2
System™ Control Identification . . . . . . . . . . . . . . . . . . . 16
2
System™ Control Operation . . . . . . . . . . . . . . . . . . . . . 17
2
2
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2
Diagnostic Codes in Dual Drive . . . . . . . . . . . . . . . . . . . 20
2
ICC Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2
System™ System Initial Startup . . . . . . . . . . . . . . . . . . 38
2
System™ Control Board . . . . . . . . . . . 39
2
1.0 SAFETY INFORMATION
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL­LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNA U THOR I ZED COM P ONEN T S, ACCE S SORI E S O R DEVI C ES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUS E ELECTRIC AL SHO CK R ESULTIN G IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXYGE N REAC TS VIOLENTLY WITH OIL, WHI CH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
TURN OFF ELECTRIC POWER AT THE FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNECTION MUST BE COMPLETED BEFORE MAKING LINE VOLT AGE CO NNECT IONS. FAILU RE TO DO SO CAN RESULT IN ELECTRICAL SHOCK, SEVERE PERSONAL INJURY OR DEATH.
Continued on next page
3
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant form­ing two different liquids and decreasing oil return to the compressor. This can result in compressor failure.
CAUTION
!
When coil is installed over a finished ceiling and/or living area, it is rec o m mended t h a t a s econd a r y sheet me t a l conden s ate pan be constructed and installed under entire unit. Failure to do so can result in property damage.
CAUTION
!
THE COMPRESSOR HAS AN INTERNAL OVERLOAD PROTECTOR. UNDER SOME CONDITIONS, IT CAN TAKE UP TO 2 HOURS FOR THIS OVERLOAD TO RESET. MAKE SURE OVERLOAD HAS HAD TIME TO RESET BEFORE CONDEMNING THE COMPRESSOR.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING Solid red light indicates a thermostat call for unit operation is present at the ICC control. ICC control will attempt to start unit after short cycle timer expires or when in Active Protection mode will attempt to restart unit prior to Lockout mode.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING Solid red light indicates a thermostat call for unit operation is present at the ICC. ICC will attempt to start unit after short cycle timer expires or when in Active Protection mode will attempt to restart unit prior to Lockout mode.
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22 PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGER­ANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAM­AGE, OR PERSONAL INJURY.
4
WARNING
!
TH E MANUFAC TUR ER’S WAR­RANTY DOES NOT COVER ANY DA MAGE OR DEFE CT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COM P O NENTS. ACC E S­SOR IES OR DEV ICES (OTH ER THAN THOSE AUTHORIZED BY THE M A NUFAC T U RER) IN T O, ONT O OR IN C ONJUN C T ION WI TH THE AIR CO NDI TIONER. YOU SHOULD BE AWARE THAT THE U SE OF UN AUTHO R IZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFF E C T TH E OPER A T ION OF THE AIR CONDITIONER AND MAY AL S O EN DANGE R LI F E AND PROPERTY. THE MANUFAC­TUR E R DIS C L AIMS ANY RES P O NSIBIL I TY FO R SU C H LO SS OR IN JUR Y RE SULTING FRO M THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
2.0 GENERAL INFORMATION
The (-)ASL-series of condensing units are designed to operate using the Comfort Control Comfort Control Control
• (-)ASL condensing unit equipped with the Comfort Control
• An air handler or furnace equipped with the Comfort Control
If your installation does not meet the above requirements, you must use traditional 24VAC controls.
T and setup using Comfort Control the Engineering Specification Sheets for complete performance data, thermostat, and accessory listings.
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the air conditioning system. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions (noise and component fail­ure), and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the condensing unit specification sheet should be used.
2.1 CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check condensing unit model number, electrical characteristics and accessories to determine if they are correct. Check system components (evaporator coil, condens­ing unit, evaporator blower, etc.) to make sure they are properly matched.
2
System™ or traditional 24VAC controls. These units are equipped with the
2
System™ :
A Comfort Control
his installation instruction manual contains complete instructions for installation
2
. Your installation must have these components to use Comfort
2
System™
2
2
hermostat
t
2
or conventional 24VAC controls. Please refer to
System™
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
2.2 APPLICATION
Before specifying any air conditioning equipment, a survey of the structure and a heat gain calculation must be made. A heat gain calculation begins by measuring all external surfaces and openings that gain heat from the surrounding air and quantifying that heat gain. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal.
Air conditioning systems are sized on the cooling load calculation. There are two capacities that enable the equipment to provide comfort. The first is sensible capacity.
Sensible heat is the heat energy measured on the dry bulb thermometer as it is added or removed.
The second form of heat is called latent or hidden heat. This is heat held in the humidity in the air.
A properly-sized unit removes both forms of heat, producing a comfortable living space. An oversized system cycles on and off too quickly and does not properly remove humidity, producing an uncomfortable living space. Select the indoor and outdoor equipment combination based on the manufacturer’s engineering data.
After the equipment combination has been selected, satisfying both sensible and latent conditioning requirements, the system must be properly installed. Only then can the unit provide the comfort the manufacturer intends.
There are several factors that the installers must consider:
Outdoor unit location Proper equipment evacuation
System refrigerant charge Indoor unit airflow
Indoor unit blower speed Supply and return air duct design and sizing
System air balancing • Diffuser and return air grille location and sizing
5
A
IR INLETS
(
LOUVERS)
A
LLOW 120 [305 mm]
M
IN. CLEARANCE
3
SIDES
AIR DISCHARGE
ALLOW 600 [1524 mm] CLEARANCE
ALLOW 240 [610 mm] ACCESS CLEARANCE
ACCESS PANEL
L
W
H
ALTERNATE HIGH VOLTAGE CONNECTION (KNOCKOUT) 1
11
/320[34 mm]
SERVICE F
ITTINGS
LOW VOLTAGE CONNECTION
7
/8"
[22 mm]
HIGH VOLTAGE CONNECTION 1
1
1
/32" [34 mm]
LIQUID LINE CONNECTION
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 24" [610 mm] CLEARANCE ONE SIDE
2
7
/8" [73 mm] DIA. ACCESSORY KNOCKOUTS
VAPOR LINE CONNECTION
A-00002
2.3 DIMENSIONS
FIGURE 1
DIMENSIONS AND INSTALLATION CLEARANCES
AIR DISCHARGE
ALLOW 60" [1524 mm] CLEARANCE
ACCESS PANEL
LLOW 24" [610 mm]
A ACCESS CLEARANCE
UNIT MODEL NUMBER EXPLANATION
AIR INLETS (LOUVERS) ALLOW 6” [152 mm] MIN. CLEARANCE 3 SIDES
ALTERNATE LINE VOLTAGE
ENTRY (KNOCKOUT)
111⁄32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
-)ASL – 036 JEC
(
L = DESIGN SERIES (R-410A)
S = 18 SEER
A = REMOTE CONDENSING UNIT
TRADE NAME
BASE PAN
C = EQUIPPED WITH THE
E
COMFORT CONTROL
- 208/230-1-60
J
NOMINAL CAPACITY)
( 024 = 24000 BTU/HR
036 = 36000 BTU/HR 039 = 39000 BTU/HR 048 = 48000 BTU/HR 060 = 60000 BTU/HR
2
SYSTEM™
LINE VOLTAGE
ENTRY
7
8" [22 MM]
LINE VOLTAGE ENTRY
11
32" [34 MM]
1
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
SERVICE ACCESS FOR 024 & 036 MODELS
2.4 ELECTRICAL & PHYSICAL DATA
TABLE 1
(-)ASL-JEC ELECTRICAL DATA
Rev. 2/24/2010
Model
Number
RASL-
Phase
Frequency
(Hz)
Voltage
(Volts)
024JEC 1-60-208/230 10.3/10.3 52 0.5 14/14 20/20 20/20 15.8 [1.47] 1 2500 [1038] 144 [4082] 236 [107] 263.5 [119.5]
036JEC 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1 3400 [1321] 150 [4252] 250.5 [113.6] 314.5 [142.7]
039JEC 1-60-208/230 17.9/17.9 96 2.8 26/26 30/30 40/40 23 [2.14] 2 3500 [1321] 268 [7598] 326 [147.9] 345 [156.5]
048JEC 1-60-208/230 26.9/26.9 117 2.8 37/37 45/45 60/60 23 [2.14] 2 3500 [1321] 253 [7173] 326 [147.9] 348 [157.9]
060JEC 1-60-208/230 28.2/28.2 146 2.8 39/39 50/50 60/60 23 [2.14] 2 3500 [1321] 241 [6832] 328 [148.8] 346 [156.9]
6
Rated Load
Amperes
ELECTRICAL PHYSICAL
Compressor
(RLA)
Locked
Rotor
Amperes
(LRA)
Fan
Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
SERVICE ACCESS FOR 039, 048 & 060 MODELS
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
HIGH LINE VOLTAGE 1
Face Area
Sq. Ft. [m
BOTTOM VIEW SHOWING DRAIN OPENINGS (\\\\\ SHADED AREAS).
SERVICE FITTING
LOW LINE VOLTAGE7⁄8"
1
4"
Outdoor Coil Weight
No.
2
]
Rows
CFM [L/s}
LOW LINE VOLTAGE
7
8"
Refrig.
Per Circuit Oz. [g]
LIQUID LINE CONNECTION
Net
Lbs. [kg]
VAPOR LINE CONNECTION
Shipping Lbs. [kg]
2.5 PROPER INSTALLATION
Proper sizing and installation of this equipment is critical to achieve optimal perfor­mance. Use the information in this Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENER­GY STAR
ents. However, proper refrigerant charge and proper airflow are critical to achieve
n rated capacity and efficiency. Installation of this product should follow the manufac­turer’s refrigerant charging and airflow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
®
criteria for energy efficiency when matched with appropriate coil compo-
3.0 LOCATING UNIT
3.1 Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
WARNING
!
DIS C O NNECT AL L POWE R T O UNIT B E FORE ST A RTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
3.2 CONDENSER LOCATION
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor condenser.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perfor­mance or operation.
7
3.3 Operational Issues
IMPORTANT: Locate the unit in a manner that will not prevent, impair or com-
promise the performance of other equipment horizontally installed in proximity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or
anufacturers’ recommendations, local code recommendations and require-
m ments will take precedence.
Refrigerant piping and wiring should be properly sized and kept as short as possible to avoid capacity losses and increased operating costs.
Locate the unit where water run off will not create a problem with the equip­ment. Position the unit away from the drip edge of the roof whenever possible. Units are weatherized, but can be affected by the following:
o Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the heat pump while in operation can impact fan blade or motor life, and coil damage may occur to a heat pump if moisture cannot drain from the unit under freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which generally results in less economical operation.
Closely follow clearance recommendations on Page 6.
o 24” to the service panel access
o 60” above heat pump fan discharge (unit top) to prevent recirculation
o 6” to heat pump coil grille air inlets
3.4 For Units With Space Limitations
FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Clearances below 6 inches will reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6­inch per unit clearance is recommended, for a total of 12” between two units. Two combined clearances below 12 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service, clearances.
3.5 Customer Satisfaction Issues
The condensing unit should be located away from the living, sleeping and recreational spaces of the owner and those spaces on adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from entering the unit.
3.6 Unit Mounting
If elevating the condensing unit, either on a flat roof or on a slab, observe the following guidelines.
The base pan provided elevates the heat pump 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration (see Figure 2).
NOTE: Do not block drain openings shown in Figure 1.
3.7 Factory-Preferred Tie-Down Method for Outdoor Units
IMPORTANT: The Manufacturer approved/recommended method is a guide to secur­ing equipment for wind and seismic loads. Other methods might provide the same result, but the Manufacturer method is the only one endorsed by Manufacturer for securing equipment where wind or earthquake damage can occur. Additional informa­tion is available in the PTS (Product Technical Support) section of the Manufacturer website Rheemote.net and can be found as a listing under each outdoor model. If you do not have access to this site, your Distributor can offer assistance.
8
FIGURE 2
ECOMMENDED ELEVATED INSTALLATION
R
4.0 REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
4.1 Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
9
IMPORTANT: The Rheem approved/recommended method is a guide to securing equipment for wind and seismic loads. Other methods might provide the same result, but the Rheem method is the only one endorsed by Rheem for securing equipment where wind or earthquake damage can occur. Additional information is available in the PTS (Product Technical Support) section of the Rheem website Rheemote.net and can be found as a listing under each outdoor model. If you do not have access to this site, your Distributor can offer assistance.
4.2 Specifications of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 heat pumps.
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its saturation pressure at 77°F is 224.5 psig.
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane (HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
4.3 Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit. Only manufacturer approved liq­uid line filter driers can be used. These are Sporlan (CW083S) and Alco (80K083S) driers. These filter driers are rated for minimum working pressure of 600 psig.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
10
Loading...
+ 23 hidden pages