Installing the water heater.
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of CAN/CSA B149 - Natural
Gas and Propane Installation Code. A copy can be purchased from the Canadian Standards
Association, 5060 Spectrum Way, Mississauga, Ontario L4W 5N6.
Location
The water heater should not be located
in an area where leakage from the tank
or connections will result in damage to
the area adjacent to the heater or to
lower floors of the structure.
When such areas cannot be avoided it is
recommended that a suitable catch pan,
adequately drained, must be installed
under the water heater.
The pan must not restrict air flow to the
combustion air inlet openings
(perforation openings) located around
the lower perimeter of the water heater.
Catch pan kits are available from the store
where the water heater was purchased, or
any water heater distributor.
When installed in a closet, DO NOT
block or obstruct any of the combustion
air inlet openings located around the
perimeter of the water heater. A
minimum of 1” (2.5 cm) is required
between these combustion air inlet
openings and any obstruction.
Make certain the floor underneath the
water heater is strong enough to
sufficiently support the weight of the
water heater once it is filled with water.
A gas fired water heater or any other
appliance should not be installed
in a space where liquids which give off
flammable vapours are to be used or
stored. Such liquids include gasoline, LP
gas (butane or propane), paint or
adhesives and their thinners, solvents or
removers.
Because of natural air movement in a
room or other enclosed space, flammable
vapours can be carried some distance from
where liquids which give off flammable
vapours are to be used or stored. The open
flame of the water heater’s pilot or main
burner can ignite these vapours and create
a shut down condition of the water
heater which will not allow the water
heater to ignite until examined by a
Qualified Service Technician.
The water heater must be located so it is
not subject to physical damage, for example,
by moving vehicles, area flooding, etc.
If local codes require the use of a stand kit
to raise the water heater 18” (46 cm)
above the floor, please contact the store
where the water heater was purchased, or
any water heater distributor. These kits
must comply with local codes.
● The water heater should be installed as
close as practical to the gas vent or
chimney.
● Long hot water lines should be insulated
to conserve water and energy.
● The water heater and water lines should
be protected from exposure
to freezing temperatures.
● Do not install the water heater in
bathrooms, bedrooms, any occupied
rooms normally kept closed, or in
unprotected outdoor areas.
● Minimum clearance from combustible
construction:
If the clearances stated on the
Instruction/Warning Label, located on
the front of the heater differ, install the
water heater according to the clearances
stated on the label.
● If the water heater is installed in an
alcove or closet, the entire floor must
be covered by a wood or metal panel.
A minimum of 24” (61 cm) clearance
from the front and top should be
available for adequate inspection and
servicing.
● The water heater may be installed on
combustible floors, but not directly on
carpeting. If the water heater must be installed on carpeting, place a metal or
wood panel beneath the water heater, extending beyond its full width and depth
at least 3” (7.6 cm) in all directions.