Rheem PRL-JEC Installation Manual

INSTALLATION INSTRUCTIONS
ISO 9001:2008
TWO-STAGE HEAT PUMP OUTDOOR UNITS
(-)PRL-JEC 16 SEER EQUIPPED WITH THE COMFORT CONTROL
SYSTEM™
2
[ ] INDICATES METRIC CONVERSIONS
SUPERSEDES 92-20522-63-05
92-20522-63-06
TABLE OF CONTENTS
1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
2.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Electrical and Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5 Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.0 LOCATING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Heat Pump Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Operational Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 For Units With Space Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Customer Satisfaction Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.6 Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.7 Factory-Preferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Tools Required for Installing & Servicing R-410A Models . . . . . . . . . . . . . 9
4.2 Specification of R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Quick Reference Guide for R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.0 REPLACEMENT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.0 INDOOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.0 INTERCONNECTING TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.1 Vapor & Liquid Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.2 Maximum Length of Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.3 Outdoor Unit Installed Above or Below Indoor Coil . . . . . . . . . . . . . . . . . 13
7.4 Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.5 Tubing Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.6 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.0 DEMAND DEFROST CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.1 Defrost Initiation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.2 Defrost Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.3 Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.4 Defrost Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.5 Trouble Shooting Demand Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9.0 COMPRESSOR CRANKCASE HEAT (CCH) . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10.0 HARD START COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11.0 HIGH & LOW PRESSURE CONTROLS (HPC AND LPC) . . . . . . . . . . . . . . . . 17
11.1 Evacuation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
12.0 CONDENSING UNITS EQUIPPED WITH COMFORT CONTROL
SYSTEM™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12.1 Control Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12.2 Comfort Control2Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
12.3 Comfort Control2ICC Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . 20
12.4 Active Compressor Protection Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12.5 Test and Fault Recall Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
12.6 ICC Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-29
12.7 Conventional 24VAC Thermostat Control Wiring . . . . . . . . . . . . . . . . . . 29
12.8 Typical Thermostat Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12.9 ICC Control Operation with Conventional Thermostat Wiring . . . . . . . . . 31
12.10 Active Compressor Protection Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.11 Test and Fault Recall Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13.0 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
13.1 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
13.2 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
13.3 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
14.0 START UP & PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
15.0 CHECKING AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
16.0 CHECKING REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
16.1 Charging Units with R-410A Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . 39
16.2 Charging By Liquid Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
16.3 Charging By Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
16.4 Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
17.0 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
17.1 Dual Fuel Kit Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
17.2 Remote Outdoor Temperature Model . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
17.3 RXME-A02 Communicating 2 Wire Kit . . . . . . . . . . . . . . . . . . . . . . . . . . 40
18.0 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
18.1 Serial Communicating System Initial Startup. . . . . . . . . . . . . . . . . . . . . . 40
18.2 Replacement of Comfort Control2 System™ Control Board . . . . . . . . . . 41
18.3 Electrical Checks Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
18.4 Cooling Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . 43
18.5 Defrost Mechanical Checks Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . 44
18.6 General Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
18.7 Service Analyzer Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-50
18.8 Subcooling Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
19.0 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-53
2
2
1.0 SAFETY INFORMATION
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL­LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
HE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR
T DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTH O R I Z ED COMPO N E N T S, ACCE S S O R IE S OR D EV I C ES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILUR E TO DO SO CAN C AUSE ELECTR ICAL SHOCK RESULTI NG IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXY GEN REACT S VIOLENTLY WITH O IL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
TURN OFF ELECTRIC POWER AT THE FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNECTION MUST BE COMPLETED BEFORE MAKING LINE VO LTAGE CON NECTI ONS. F AILURE TO DO SO CAN RESULT IN ELECTRICAL SHO CK, SEVER E PE RSONA L IN JURY O R DEATH.
3
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant form­ing two different liquids and decreasing oil return to the compressor. This can result in compressor failure.
CAUTION
!
When coil is installed over a finished ceiling and/or living area, it is recom m e nd ed tha t a sec o n da ry she e t m et a l con d e ns a te p a n be constructed and installed under entire unit. Failure to do so can result in property damage.
CAUTION
!
THE COMPRESSOR HAS AN INTERNAL OVERLOAD PROTECTOR. UNDER SOME CONDITIONS, IT CAN TAKE UP TO 2 HOURS FOR THIS OVERLOAD TO RESET. MAKE SURE OVERLOAD HAS HAD TIME TO RESET BEFORE CONDEMNING THE COMPRESSOR.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING Solid red light indicates a thermostat call for unit operation is present at the ICC control. ICC control will attempt to start unit after short cycle timer expires or when in Active Protection mode will attempt to restart unit prior to Lockout mode.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING Solid red light indicates a thermostat call for unit operation is present at the ICC. ICC will attempt to start unit after short cycle timer expires or when in Active Protection mode will attempt to restart unit prior to Lockout mode.
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22 PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGER­ANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAM­AGE, OR PERSONAL INJURY.
4
WARNING
!
TH E MA N UFACTU R ER’S WAR­RANTY DOES NOT COVER ANY DA M A G E OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY CO M PO NE N TS . A C CE S ­SORIE S OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANU F A C T U R E R ) INTO, ONTO OR IN CO N J UN CT I ON WI T H THE AIR CO N D I TIONER. YOU SHOULD BE AWARE THAT THE USE OF UN A U TH O RI Z E D COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFEC T THE OP E RA T IO N OF THE AIR CONDITIONER AND MAY AL S O EN D A NG ER LIFE AND PROPERTY. THE MANUFAC­TURER DISCL A I MS ANY RESPO N S IB IL I TY FOR SUCH LO S S OR I N J URY RE S ULTING FROM THE USE OF SUC H UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
2.0 GENERAL INFORMATION
The (-)PRL-series of heat pump are designed to operate using the Comfort Control System™ or traditional 24VAC controls. These units are equipped with the Comfort Control
preferred method of installation is using the Comfort Control have these components to use the Comfort Control
• Air handler or furnace equipped with the Comfort Control
Comfort Control
If your installation does not meet the above requirements, you must use traditional 24VAC controls.
This installation instruction manual contains complete instructions for installation and setup with using the Comfort Control refer to the Engineering Specification Sheets for complete performance data, ther­mostat, and accessory listings.
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the air conditioning system. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions, and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the condensing unit specification sheet should be used.
2.1 Checking Product Received
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check heat pump model number, electrical characteristics and accessories to determine if they are correct. Check system components (evaporator coil, condens­ing unit, evaporator blower, etc.) to make sure they are properly matched.
2.2 Application
Before specifying any heat pump equipment, a survey of the structure and a heat loss and heat gain calculation must be made. A heat loss calculation involves iden­tifying all surfaces and openings that lose heat to the surrounding air and quantify­ing that heat loss. A cooling heat gain calculation makes similar measurements and determines the amount of heat needed to be removed. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal. These factors must be considered before selecting a heat pump system to provide year round comfort. The Air Conditioning Contractors of America (ACCA) J Manual method of load calculation is one recognized procedure for determining the heating and cooling load.
The cooling load calculation determines the heat pump size. There are two capaci­ties that enable the equipment to provide comfort. The first is sensible capacity. Sensible heat is the heat energy measured on the dry bulb thermometer.
The second form of heat is called latent or hidden heat. This is heat held in the humidity in the air. Removing this heat does not affect a thermometer. However, removing the heat held in the moisture in the air greatly increases comfort. A prop­erly sized unit removes both forms of heat, producing a comfortable living space. An oversized system cycles on and off too quickly and does not properly remove humidity, producing an uncomfortable living space. Select the indoor and outdoor equipment combination based on the manufacturer's engineering data.
After the proper equipment combination has been selected, satisfying both sensible and latent requirements, the system must be properly installed. Only then can the unit provide the comfort the manufacturer built into it.
There are several factors that installers must consider.
• Outdoor unit location • Indoor unit blower speed
• Proper equipment evacuation • Supply and return air duct design and sizing
• Refrigerant charge • System air balancing
• Indoor unit air flow • Diffuser and return air grille location and sizing
2
System™. To take full advantage of the Comfort Control2System™, the
2
System™ :
(-)PRL heat pump with the Comfort Control
2
thermostat
2
ystem™
S
2
or conventional 24VAC controls. Please
2
. Your installation must
2
System™
2
5
SERVICE FITTINGS
LOW VOLTAGE CONNECTION
7
/8" [22 mm]
HIGH VOLTAGE CONNECTION 1
11
/32" [34 mm]
LIQUID LINE CONNECTION
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 24" [610 mm] CLEARANCE ONE SIDE
2
7
/8" [73 mm] DIA. ACCESSORY KNOCKOUTS
VAPOR LINE CONNECTION
HIGH PRESSURE CONTROL MANUAL RESET (FIELD INSTALLED ACCESSORY)
A
-00003
A-00002
BOTTOM VIEW SHOWING DEFROST CONDENSATE DRAIN OPENINGS (\\\\\\
SHADED AREAS).
2.3 DIMENSIONS
FIGURE 1
DIMENSIONS AND INSTALLATION CLEARANCES
AIR DISCHARGE
ALLOW 60” [1524 mm] CLEARANCE
W
H
AIR INLETS (LOUVERS) ALLOW 6” [152 mm] MIN. CLEARANCE 3 SIDES
UNIT MODEL NUMBER EXPLANATION
036 JEC(– ) P R L
C = EQUIPPED WITH THE
E
EC = COMFORT CONTROL
C = SYSTEM™
L
OOLING CAPACITY
C BTUH x 1000 (NOMINAL CAPACITY)
24 = 24,000 BTU/HR
ACCESS
ANEL
P
ALLOW 24” [610 mm] SERVICE ACCESS CLEARANCE
REMOTE HEAT PUMP
0 036 = 36,000 BTU/HR 048 = 48,000 BTU/HR
60 = 60,000 BTU/HR
0
DESIGN SERIES
-410A
R
16 SEER
E
LECTRICAL DESIGNATION
E J-208/230-1-60
2
DIMENSIONAL DATA
TRADE NAME
REQUIRED PUMP-UP INSTALLATION LOCATIONS
BASE PAN
6
HEIGHT “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH“W” (INCHES)
024, 036, 048, 060HEAT PUMP MODEL (-)PRL
33
44-3/4 31-1/2
2.4 Electrical And Physical Data
TABLE 1
(-)PRL ELECTRICAL AND PHYSICAL DATA
ELECTRICAL PHYSICAL
ompressor
ated Load
R
mperes
A
RLA)
(
C
ocked Rotor
L
mperes
A
LRA)
(
an Motor
F
ull Load
F
mperes
A
FLA)
(
inimum
M
ircuit
C mpacity
A
mperes
A
odel
M
umber
N
RPRL-
Rev. 2/24/2010
024JEC 1-60-208/230 10.3 / 10.3 52 1 14/14 20/20 20/20 23 [2.14] 1 152 [4309] 257 [116.6] 264 [119.8]
036JEC 1-60-208/230 16.7 / 16.7 82 1.7 23/23 30/30 35/35 22.22 [2.06] 2 245 [6946] 311 [141.1] 315 [142.9]
48JEC 1-60-208/230 21.2 / 21.2 96 2 29/29 40/40 45/45 22.22 [2.06] 2 256 [7258] 300 [136.1] 322 [146.1]
0
060JEC 1-60-208/230 25.6 / 25.6 118 2.2 35/35 45/45 50/50 22.22 [2.06] 2 3800 [1793] 284 [8051] 316 [143.3] 343 [155.6]
hase
P
requency (Hz)
F
oltage (Volts)
V
Fuse or HACR
Circuit Breaker
inimum
M
mperes
A
aximum
M
mperes
A
ace Area
F
q. Ft. [m
S
Outdoor Coil Weight
No.
2
Rows
]
FM
C
L/s]
[
2300/2800
[1085/1321]
800/3700
2 1321/1746]
[
800/3500
2 1321/1652]
[
Refrig.
Per Circuit Oz. [g]
N
bs. [kg]
L
et
S L
2.5 Proper Installation
Proper sizing and installation of this equipment is critical to achieve optimal perfor­mance. Use the information in this Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENER­GY STAR criteria for energy efficiency when matched with appropriate coil compo­nents. However, proper refrigerant charge and proper airflow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufac­turer’s refrigerant charging and airflow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
hipping bs. [kg]
3.0 LOCATING UNIT
3.1 Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
WARNING
!
DISCO N N EC T A L L PO W ER T O UN I T B E F OR E S T A RT I NG MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
7
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
3.2 Heat Pump Location
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor heat pump.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perfor­mance or operation.
3.3 Operational Issues
IMPORTANT: Locate the unit in a manner that will not prevent, impair or com-
promise the performance of other equipment horizontally installed in proximity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or manufacturers’ recommendations, local code recommendations and require­ments will take precedence.
Refrigerant piping and wiring should be properly sized and kept as short as possible to avoid capacity losses and increased operating costs.
Locate the unit where water run off will not create a problem with the equip­ment. Position the unit away from the drip edge of the roof whenever possible. Units are weatherized, but can be affected by the following:
o Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the heat pump while in operation can impact fan blade or motor life, and coil damage may occur to a heat pump if moisture cannot drain from the unit under freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which generally results in less economical operation.
Closely follow clearance recommendations on Page 6. o 24” to the service panel access
o 60” above heat pump fan discharge (unit top) to prevent recirculation
o 6” to heat pump coil grille air inlets
3.4 For Units With Space Limitations
FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Clearances below 6 inches will reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6­inch per unit clearance is recommended, for a total of 12” between two units. Two combined clearances below 12 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service, clearances.
3.5 Customer Satisfaction Issues
The heat pump should be located away from the living, sleeping and recre­ational spaces of the owner and those spaces on adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from entering the unit.
3.6 Unit Mounting
If elevating the heat pump, eithe r on a fla t roof or on a sl ab, obse rve the following guidelines.
The base pan provided elevates the heat pump 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration (see Figure 2).
NOTE: Do not block drain openings shown in Figure 1.
If unit must be elevated because of anticipated snow fall, secure unit and ele­vating stand such that unit and/or stand will not tip over or fall off. Keep in mind that someone may try to climb on unit.
8
FIGURE 2
ECOMMENDED ELEVATED INSTALLATION
R
3.7 Factory-Preferred Tie-Down Method
IMPORTANT: The Manufacturer approved/recommended method is a guide to secur­ing equipment for wind and seismic loads. Other methods might provide the same result, but the Manufacturer method is the only one endorsed by Manufacturer for securing equipment where wind or earthquake damage can occur. Additional informa­tion is available in the PTS (Product Technial Support) section of the Manufacturer website Rheemote.net and an be found as a listing under each outdoor model. If you do not have access to this site, your Distributor can offer assistance.
4.0 REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
4.1 Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
9
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
4.2 Specifications of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 heat pumps.
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its saturation pressure at 77°F is 224.5 psig.
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane (HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
4.3 Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit. Only manufacturer approved liq­uid line filter driers can be used. These are Sporlan (CW083S) and Alco (80K083S) driers. These filter driers are rated for minimum working pressure of 600 psig.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
10
5.0 REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized. Test the oil for acid. If positive, a suction line filter drier is mandatory.
IMPORTANT: WHEN REPLACING AN R-22 UNIT WITH AN R-410A UNIT, EITHER REPLACE THE LINE SET OR ENSURE THAT THE EXISTING LINE SET IS THOROUGHLY CLEANED OF ANY OLD OIL OR DEBRIS.
6.0 INDOOR COIL
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUC­TIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant forming two differ­ent liquids and decreasing oil return to the compressor. This can result in com­pressor failure.
NOTE: All (-)PRL units must be installed with a TXV Evaporator.
The thermostatic expansion valve is specifically designed to operate with R-410A.
DO NOT use an R-22 TXV or evaporator. The existing evaporator must be replaced with the factory specified TXV evaporator specifically designed for R-410A.
6.1 Location
Do not install the indoor coil in the return duct system of a gas or oil furnace. Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched toward the drain connection.
CAUTION
!
When coil is in s t a ll e d ov e r a finishe d ceil i n g an d / o r livin g area , it is recom m e nd ed t h at a s e co n da r y s h e et me t a l c o n de n sa te p a n b e constr ucted and installed under en tire unit. Failure to do so ca n result in property damage.
7.0 INTERCONNECTING TUBING
7.1 Vapor and Liquid Lines
Keep all lines sealed until connection is made.
Make connections at the indoor coil first.
Refer to Line Size Information in Tables 4 and 5 for correct size and multipliers to be used to determine capacity for various vapor line diameters and lengths of run. The losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for the unit and 15 feet of standard size interconnecting liquid and vapor lines. For different lengths, adjust the charge as indicated below.
1/4” ± .3 oz. per foot 5/16” ± .4 oz. per foot 3/8” ± .6 oz. per foot 1/2” ± 1.2 oz. per foot
11
7.2 Maximum Length of Lines
The maximum length of interconnecting line is 150 feet. Always use the shortest length possible with a minimum number of bends. Additional compressor oil is not required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
7.3 Outdoor Unit Installed Above or Below Indoor Coil
Use the following guidelines when installing the unit:
1. Expansion Valve Coil:
a. The vertical separation cannot exceed the value in Tables 4 and 5.
b. No changes are required for expansion valve coils.
2. It is recommended to use the smallest liquid line size permitted to minimize the system charge.
3. Tables 4 and 5 may be used for sizing horizontal runs.
7.4 Tubing Installation
Observe the following when installing correctly sized type “L” refrigerant tubing between the condensing unit and evaporator coil:
If a portion of the liquid line passes through a hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required.
Use clean, dehydrated, sealed refrigeration grade tubing.
Always keep tubing sealed until tubing is in place and connections are to be made.
Blow out the liquid and vapor lines with dry nitrogen before connecting to the outdoor unit and indoor coil. Any debris in the line set will end up plugging the expansion device.
As an added precaution, a high quality filter drier is standard on R-410A units.
Do not allow the vapor line and liquid line to be in contact with each other. This causes an undesirable heat transfer resulting in capacity loss and increased power consumption. The vapor line must be insulated.
If tubing has been cut, make sure ends are deburred while holding in a position to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes.
For best operation, keep tubing run as short as possible with a minimum num­ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a good tubing bender on the vapor line to prevent kinking.
Route the tubing using temporary hangers, then straighten the tubing and install permanent hangers. Line must be adequately supported.
The vapor line must be insulated to prevent dripping (sweating) and prevent performance losses. Armaflex and Rubatex are satisfactory insulations for this purpose. Use 1/2” minimum insulation thickness, additional insulation may be required for long runs.
Check Table 4 for the correct vapor line size. Check Table 5 for the correct liq­uid line size.
12
TABLE 4
SUCTION LINE SIZING – DUAL SPEED HEAT PUMP
Allowed suction line size is determined by total line length on oil return. Liquid size determines total line length and vertical separation. After selecting allowed suction line size by outdoor unit position, see the liquid line chart for allowable vertical height and total line length.
Standard Line
onnection
-)PRL
(
024 3/4” [19.05] 3/4” [19.05]
-
-036 3/4” [19.05] 3/4” [19.05]
048 7/8” [22.23] 3/4” [19.05]
-
-060
C
Size
nch (I.D.) [mm]
I
7/8” [22.23] 7/8” [22.23]
Line Size Inch O.D.)
(
mm]
[
/8” [15.88]
5
7/8” [22.23]
5/8” [15.88]
7/8” [22.23]
/8” [15.88]
5
/8” [22.23]
7
3/4” [19.05]
1-1/8” [28.58]
SUCTION LINE SIZE
Outdoor unit ABOVE Indoor Coil
5 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72]
2
efer to Liquid Line Table for vertical Separation
R
ot Allowed for any length
N
ot Allowed for any length
N
efer to Liquid Line Table for vertical Separation
R
Not Allowed for any length
ot Allowed for any length
N
efer to Liquid Line Table for vertical Separation
R
efer to Liquid Line Table for vertical Separation
R
efer to Liquid Line Table for vertical Separation
R
Refer to Liquid Line Table for vertical Separation
efer to Liquid Line Table for vertical Separation
R
ot Allowed for any length
N
5 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72]
2
efer to Liquid Line Table for vertical Separation
R
Refer to L.L. table
efer to Liquid Line Table for vertical Separation
R
efer to Liquid Line Table for vertical Separation
R
Refer to Liquid Line Table for vertical Separation
Refer to Liquid Line Table for vertical Separation
Refer to Liquid Line Table for vertical Separation
Refer to Liquid Line Table for vertical Separation
Refer to Liquid Line Table for vertical Separation
Refer to Liquid Line Table for vertical Separation
SUCTION LINE SIZE
Outdoor unit BELOW Indoor Coil
Total line length-feet [m]Total line length-feet [m]
Not allowed above 75 ft.length
Not Allowed for any length
Not Allowed for any length
NOTES: Using suction line larger than shown in table will result in poor oil return and is not recommended.
TABLE 5
IQUID LINE SIZING – DUAL SPEED HEAT PUMP
L
2-Stage R-410A
System
Capacity
Model
Line Size
Connection
Size (Inch I.D.) [mm]
Line Size
(Inch O.D.)
[mm]
Outdoor unit Above or Below Indoor Coil
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72]
Liquid Line Size
Total Line Length - Feet [M]
Maximum Vertical Separation - Feet [M]
1/4” [6.35] 25 [7.62] N/A N/A N/A N/A N/A
-024 3/8” [9.53] 5/16” [7.93] 25 [7.62] 36 [10.97] 33 [10.06] 28 [8.53] 22 [6.71] 16 [4.88]
3/8” [9.52] 25 [7.62] 41 [12.50] 40 [12.19] 39 [11.89] 37 [11.28] 36 [10.97]
5/16” [7.93] 25 [7.62] 22 [6.71] 9 [2.74] N/A N/A N/A
-036 3/8” [9.53] 3/8” [9.52] 25 [7.62] 39 [11.89] 34 [10.36] 30 [9.14] 25 [7.62] 21 [6.40]
1/2” [12.70] 25 [7.62] 46 [14.02] 45 [13.72] 44 [13.41] 43 [13.11] 42 [12.80]
5/16” [7.93] 25 [7.62] 17 [5.18] N/A N/A N/A N/A
-048 3/8” [9.53] 3/8” [9.52] 25 [7.62] 47 [14.33] 39 [11.89] 31 [9.45] 23 [7.01] 16 [4.88]
1/2” [12.70] 25 [7.62] 50 [15.24] 58 [17.68] 56 [17.07] 54 [16.46] 53 [16.15]
3/8” [9.52] 25 [7.62] 18 [5.49] 11 [3.35] N/A N/A N/A
-060 3/8” [9.53]
1/2” [12.70] 25 [7.62] 29 [8.84] 27 [8.23] 26 [7.93] 25 [7.62] 23 [7.01]
NOTES: N/A - Application Not Recommended
13
7.5 Tubing Connections
Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed until connections are to be made.
Use type “L” copper refrigeration tubing. Braze the connections with the follow­ing alloys:
– copper to copper - 5% – Silver alloy (no flux) – copper to steel or brass - 35% – silver alloy (with flux)
Be certain both refrigerant shutoff valves at the outdoor unit are closed.
Clean the inside of the fittings and outside of the tubing with steel wool or sand cloth before soldering. Always keep chips, steel wool, dirt, etc., out of the inside when cleaning.
Assemble tubing part way into fitting. Apply flux all around the outside of the tubing and push tubing into stop. This procedure will keep the flux from getting inside the system.
Remove the cap and schrader core from service port to protect seals from heat damage.
Use an appropriate heatsink material around the copper stub and the service valves before applying heat.
IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen into a service port and through the tubing while brazing.
After brazing – use an appropriate heatsink material to cool the joint and remove any flux residue.
The service valves are not backseating valves. To open the valves, remove the valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the stem. Back out counterclockwise.
Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a metal-to-metal seal.
7.6 Leak Testing
Pressurize line set and coil through service fittings with dry nitrogen to 150 PSIG maximum. Leak test all joints using liquid detergent. If a leak is found, recover pressure and repair.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXY GEN REACT S VIOLENTLY WITH O IL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
8.0 DEMAND DEFROST CONTROL
The ICC has a demand defrost algorithm so a separate defrost control is not need­ed. The ICC monitors the outdoor ambient temperature, outdoor coil temperature, and the compressor run-time to determine when a defrost cycle is required.
8.1 Defrost Initiation
A defrost will be initiated when the three conditions below are satisfied:
1) The outdoor coil temperature is below 35°F.
2) The compressor has operated for at least 34 minutes with the outdoor coil tem-
perature below 35°F.
3) The defrost algorithm determines a defrost is required.
Additionally, a defrost will be initiated if six hours of accumulated compressor run­time has elapsed without a defrost with the outdoor coil temperature below 35°F.
14
8.2 Defrost Termination
Once a defrost is initiated, the defrost will continue until fourteen minutes has elapsed or the coil temperature has reached the terminate temperature. The termi­nate temperature is factory set at 70°F, although the temperature can be changed to 50°F, 60°F, 70°F or 80°F by relocating dip switches on the ICC.
NOTE: An optional “Noise Abatement Time“ can be selected via the communicating thermostat or the Service Tool program. When 5 second Noise Abatement is select­ed, the compressor will shut down for 5 seconds when unit goes into or comes out of defrost.
8.3 Temperature Sensors
The coil sensor is clipped to the top tube on the outdoor coil at the point fed by the distribution tubes from the expansion device (short 3/8” dia. tube).
If the ambient sensor fails the defrost control will initiate a defrost every 34 minutes in heat mode with the coil temperature below 35°F.
8.4 Defrost Test Mode
The defrost test mode is initiated by pressing pushbutton SW2 for 1 second with the unit running in HP mode. Upon release of pushbutton SW2, the unit will go into defrost until termination temperature is achieved or 14 minutes has expired. Pressing SW2 while in Defrost Test Mode will terminate test mode.
8.5 Trouble Shooting Demand Defrost
Set the indoor thermostat select switch to heat and initiate a call for heat.
Press SW2 to put the unit into defrost. If the unit goes into defrost and comes back out of defrost, the indication is that the control is working properly.
9.0 COMPRESSOR CRANKCASE HEAT (CCH)
CCH is standard on these models due to refrigerant migration during the off cycle that can result in a noisy start up.
Crankcase Heater Operation:
Supplemental crankcase heat is required to prevent refrigerant migration in systems with relatively high system refrigerant charges.
The crankcase heater control is integrated into the ICC and is designed for maxi­mum energy savings and uses a 120-minute off delay.
Summary of operation:
• The crankcase heater is off whenever the compressor is running.
• Once the compressor turns off, the crankcase heater control (CCH) begins the two-hour timer countdown.
• If the compressor stays off for two hours, the CCH turns on the crankcase heater.
All heaters are located on the lower half of the compressor shell. Its purpose is to drive refrigerant from the compressor shell during long off cycles, thus preventing damage to the compressor during start-up.
At initial start-up or after extended shutdown periods, make sure the heater is ener­gized for at least 12 hours before the compressor is started. (Disconnect switch on and wall thermostat off.)
10.0 HARD START COMPONENTS
Factory-installed start components are standard on all models.
15
11.0 HIGH AND LOW PRESSURE CONTROLS
11.0 (HPC AND LPC)
These controls keep the compressor from operating in pressure ranges which can cause damage to the compressor. Both controls are in the low voltage control cir­cuit.
High pressure control (HPC) is an automatic-reset which opens near 610 PSIG and
loses near 420 PSIG.
c
The low pressure control (LPC) is an automatic-reset which opens near 15 PSIG and closes near 40 PSIG.
NOTE: HPC and LPC are monitored by the Comfort Control Section 12.0.
CAUTION
!
THE COMPRESSOR HAS AN INTERNAL OVERLOAD PROTECTOR. UNDER SOME CONDITIONS, IT CAN TAKE UP TO 2 HOURS FOR THIS OVERLOAD TO RESET. MAKE SURE OVERLOAD HAS HAD TIME TO RESET BEFORE CONDEMNING THE COMPRESSOR.
11.1 Evacuation Procedure
Evacuation is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the system.
Air in the system causes high condensing temperatures and pressure, resulting in increased power input and non-verifiable performance.
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric and hydrochloric acids. These attack motor windings and parts, causing breakdown.
After the system has been leak checked and proven sealed, connect the vacuum pump and evacuate system to 500 microns. The vacuum pump must be connected to both the high and low sides of the system through adequate connections. Use the largest size connections available since restrictive service connections may lead to false readings because of pressure drop through the fittings.
IMPORTANT: Compressors (especially scroll type) should never be used to evacu­ate the air conditioning system because internal electrical arcing may result in a damaged or failed compressor.
With thermostat in the “Off” position, turn the power on to the furnace and the heat pump. Start the heat pump and the furnace with the thermostat. Make sure the blower is operating.
2
System™. See
16
12.0 CONDENSING UNITS EQUIPPED WITH THE
2
12.0 COMFORT CONTROL
The Comfort Control2is the next generation of the Integrated Compressor Control (ICC) and is an integral part of the Comfort Control features:
12.1 Control Description (see Figure 4) Dual 7-Segment LED
• Displays status and diagnostic codes (See Status and Diagnostic Description)
• Displays diagnostic/fault recall (See Test Mode/Fault Recall)
Red LED (Y1)
• Y1 red LED (solid on) indicates Y1 call from thermostat is present
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING Solid red light indicates a thermostat call for unit operation is present at the ICC control. ICC control will attempt to start unit after short cycle timer expires or when in Active Protection mode will attempt to restart unit prior to Lockout mode.
Line Voltage Connector
• Line voltage is connected to control board at lug terminals L1 & L2
• Maximum wire size accepted is 6 AWG copper wire
• # 4 – 6 AWG 45 in/lbs # 8 AWG 40 in/lbs # 10 – 14 AWG 35 in/lbs (Check wire terminations annually)
SYSTEM™
2
System™ with the following
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
FIGURE 4
ICC BOARD
COMPRESSOR WIRING CONNECTOR
LINE VOLTAGE CONNECTION
{
O.D. FAN (OFM) RELAY
Compressor Control (K2)
• Sealed single pole compressor relay switch with optical feedback feature (arc detection)
LOW PRESSURE CONTROL INPUT
HIGH PRESSURE CONTROL INPUT
MEMORY CARD
LOW VOLT FUSE
THERMOSTAT CONNECTION (E2)
RED LED (Y1)
AMBIENT DEFROST CONTROL
COMPRESSOR CONTROL (K2)
ICC (INTEGRATED COMPRESSOR CONTROL)
SW2 BUTTON
TEST BUTTON
DEFROST SENSOR
7-SEGMENT LED
17
Thermostat Connector (E2)
Indoor Unit
1
2
C
R
WIRING INFORMATION Line Voltage –Field Installed - - - - - ­ –Factory Standard
1
2
R
C
1
2
R
C
Communicating Thermostat
Outdoor Unit
R – 24VAC from the indoor unit 24VAC transformer (40 VA minimum)
C – 24VAC Common from the indoor unit 24VAC transformer
1-Data: System Communications Line 1
2-Data: System Communications Line 2
Low Volt Fuse
• If required replace with 3 A automotive ATC style blade fuse
Low Pressure Control (LPC Input)
• Low-pressure control is factory installed
• Low pressure control is an automatic resetting device
High Pressure Control (HPC Input)
• High-pressure control is factory installed
• High pressure control is an automatic resetting device
Ambient Temperature Sensor (included with all applications)
• Included with all applications
TEST and SW2 Buttons
• TEST and SW2 buttons used to enter Test and Fault Recall Mode
Memory Card
• The memory card stores all unit information.
• The unit information is called shared data.
• The shared data is all the information needed for proper unit operation.
SYSTEM™ CONTROL WIRING
2
COMFORT CONTROL
FIGURE 5
TYPICAL COMFORT CONTROL2SYSTEM™ WIRING DIAGRAM
18
12.2 Comfort Control2Control Wiring
Figure X – Typical Serial Communication Wiring Diagram
Zero (0) displayed The unit is in standby
he four 18AWG low voltage control wires must be installed from the thermostat to the
T indoor unit and from indoor unit to the outdoor unit. The wire length between the thermo­stat and indoor unit should not be greater than 100 feet. The wire length between the indoor unit and outdoor unit should not be greater than 125 feet.
A serial communicating HVAC system consists of: Serial communicating heat pump or serial communicating condensing unit Serial communicating air handler or serial communicating furnace Serial communicating thermostat IIMMPPOORRTTAANNTT::
tem must be wired using traditional control wiring, reference Section 12.7 Conventional 24VAC Thermostat Control Wiring.
The Comfort Control
NNoottee::
Comfort Control2requires 18 AWG thermostat wire.
NNoottee::
Term dipswitches should be in “ON” position.
If the low voltage control wiring is run in conduit with the power supply, Class I insu­lation is required. Class II insulation is required if run separate. Low voltage wiring may be run through the insulated bushing provided in the 7/8 hole in the base panel, up to and attached to the pigtails from the bottom of the control box. Conduit can be run to the base panel if desired by removing the insulated bushing.
The serial communicating air handler or serial communicating furnace transformer is equipped with a 24 volt, 50 VA transformer for proper system operation. See the wiring diagram in Figure 5 for reference.
If the installed system does not meet these requirements, the sys-
2
requires four (4) control wires for unit operation: R – 24VAC C – 24VAC common 1 – Data wire 1 2 – Data wire 2
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
12.3 Comfort Control2ICC Control Operation
IInnssttaallllaattiioonn VVeerriiffiiccaattiioonn
• 24V AC power on R&C must be present at the ICC for it to operate
• Line voltage must be present at the ICC for the compressor and the outdoor fan to operate
• The ICC displays a “0” for standby mode. Standby mode indicates line voltage and 24VAC are present at the ICC and there is not a command for unit operation from the serial communicating thermostat.
CCoommmmaanndd ffoorr CCoommpprreessssoorr OOppeerr aatt iioonn ((YY11 LLEEDD))
• If a command for compressor operation is received by the ICC (first stage/second stage cooling or first stage/second stage heating), the red Y1 LED will illuminate.
• The ICC has an on/off fan delay of one (1) second for each stage of heating or cooling.
• The ICC ignores the low pressure control for the first 90 seconds of compressor operation.
• On heat pumps, the ICC ignores the LPC during the defrost cycle.
• The dual 7-segment LED displays five (5) operational status codes:
11)) FFiirrsstt SSttaaggee CCoooolliinngg OOppeerraattiioonn
stage cooling operation, a lower case “c” is displayed on the dual 7-segment LEDs.
Zero (0) displayed The unit is in standby
– When the ICC receives a command for first
Lower case “c” indicates first stage cooling operation
22)) SSeeccoo nndd SSttaaggee CCoooolliinngg OOppeerraatt ii oonn
second stage cooling operation, an upper case “C” is displayed on the dual 7­segment LEDs.
– When the ICC receives a command for
19
Upper case “C” indicates second stage cooling operation
Flashing lower case h and 1 A command for first stage heating has been received
33)) FFiirrss tt SSttaaggee HHeeaattii nngg OOppeerraattiioonn stage heating operation, “h” is displayed on the dual 7-segment LEDs.
“h” indicates first stage heating operation
44)) SSeeccoo nndd SSttaaggee HHeeaatt ii nngg OOppeerraattiioonn second stage heating operation, “H” is displayed on the dual 7-segment LEDs.
- When the ICC receives a command for first
- When the ICC receives a command for
H
“H” indicates second stage heating operation
55)) DDeeffrrooss tt OOppeerraattiioonn displayed on the dual 7-segment LEDs.
– When the ICC starts a defrost cycle, a lower case “d” is
SYSTEM™ CONTROL WIRING
2
33--mmiinnuutt ee AAnnttii--sshhoorrtt CCyyccll ee TTii mmeerr
• The ICC has a built in 3-minute time delay between compressor operations to protect the compressor against short cycling. The dual 7-segment LEDs will flash “c”, “C”, “h”, or “H” while the short cycle timer is active and a command for unit operation is received.
Lower case “d” indicates defrost operation (in heating mode)
Flashing lower case c A command for first stage cooling has been received
Flashing upper case C A command for second stage cooling has been received
COMFORT CONTROL
Flashing lower case h A command for first stage heating has been received
Flashing upper case H
A command for second stage heating has been received
20
H
• The 3-minute time delay can be bypassed when a command for compressor operation is present by pressing the TEST button for 1 second and releasing. The compressor will begin operation and the dual 7-segment will stop flashing.
3300 SSeeccoonndd MMiinnii mmuumm RRuunn TTiimmeerr
• The ICC has a built in 30 second minimum unit run time. If a command for com­pressor operation is received by the ICC and the command is removed, the com­pressor will continue to operate for 30 seconds. The dual 7-segment LEDs will flash “c”, “C”, “h”, or “H” while the minimum run timer is active.
11 SSeeccoonndd CCoommpprreessssoorr //FFaann DDeell aayy
• The ICC starts/stops the outdoor fan one (1) second after the start/stop of the compressor upon a command for compressor operation to minimize current inrush and/or voltage drop.
12.4 Active Compressor Protection Mode
• The ICC actively protects the compressor from harmful operation during a fault condition.
• When the ICC detects a condition that could damage the compressor, the ICC will enter active protection mode and lockout compressor operation
• The condition causing active protection must be resolved before ICC will restart the system.
• There are five (5) active protection modes:
11)) LLooww PPrreessss uurree CCoonnttrrooll LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing 21 when a low pressure control lockout occurs.
• The ICC addresses low pressure control faults differently depending on the mode of unit operation (cooling or heating mode).
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
Active Protection – Code L21 – Open low pressure control
CCoooolliinngg MMooddee
• If the LPC opens three (3) times during the same command for cooling operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
HHeeaattiinn gg MMooddee
• There are two scenarios that will cause active protection during a LPC trip when the unit is in the heating mode:
AAccttiivvee PPrrootteeccttiioonn wwiitthh hhaarrdd ll oocckkoo uutt::
If the LPC opens three (3) times within 120 minutes for the same command for heating operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
AAccttiivvee PPrrootteeccttiioonn wwiitthh ssoofftt lloocckkoouutt::
If the LPC opens three (3) times for the same command for heating and the out­door ambient temperature is below 5F, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs fol­lowed by a “21”. Once the outdoor ambient rises above 5F the ICC will clear active protection automatically.
IIMMPPOORRTTAANNTT:: the outdoor temperature rises above 5F. Wait until the outdoor ambient tempera­ture rises above 5F before performing further diagnostics.
This mode of active protection must be manually reset.
This mode of active protection must be manually reset.
This mode of active protection will automatically deactivate once
21
22)) HHiigg hh PPrreessssuurree CCoonnttrr ooll LLoocckkoouutt
Lower case “d” indicates defrost operation (in heating mode)
3-minute Anti-short Cycle Timer
• If the HPC opens three (3) times during the same command for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L” on the dual 7-segment LEDs followed by a “29”.
Active Protection – Code L29 – Open high pressure control
SYSTEM™ CONTROL WIRING
IIMMPPOORRTTAANNTT::
33)) LLoocckkeedd RRoottoorr
• The ICC will display a flashing “L” followed by a flashing “04” when a locked rotor condition occurs.
If the ICC detects the compressor has run less than 15 seconds for four (4) con­secutive starts during the same command for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7­segment LEDs followed by a “04”.
IIMMPPOORRTTAANNTT::
44)) CCoommpprr eessssoorr PPrrootteecctt oorr TTrriipp
• If ICC detects a protector trip it will display a “P”. If protector doesn’t reset within 4 hours, the ICC display will change to “5”.
This mode of active protection must be manually reset.
Active Protection – Code L4 – Locked rotor
This mode of active protection must be manually reset.
2
COMFORT CONTROL
22
Compressor Protector – Code P – Protector Trip
55)) OOppeenn SSttaarrtt CCiirrccuuiitt LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “06” when an open start circuit condition occurs.
Active Protection – Code L6 – Compressor open start circuit
If the ICC detects current in the run circuit without current present in the start cir­cuit, , the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “06”.
IIMMPPOORRTTAANNTT::
66)) OOppeenn RRuunn CCii rrccuuiitt LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “07” when an open start circuit condition occurs.
This mode of active protection must be manually reset.
Active Protection – Code L7 – Compressor open run circuit
If the ICC detects current in the start circuit without current present in the run cir-
Lower case “t”
Fault Recall Mode – the top and bottom segments illuminated
cuit, , the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “07”.
IIMMPPOORRTTAANNTT::
EExxiittiinngg AAccttiivv ee CCoommpprreessssoorr PPrrootteeccttiioonn LLoocckkoouutt
There are three methods to reset the ICC after an active protection lockout:
1) Cycle the line voltage to the unit
2) Cycle 24VAC to the ICC (remove the R or C connection to the ICC)
3) Push the TEST button down with an insulated probe for one (1) second and release
Note: The ICC will attempt to start the unit when the TEST button is pressed and released
NNoottee::
The preferred method of resetting the ICC is to push the TEST button down
for one (1) second.
This mode of active protection must be manually reset.
12.5 Test and Fault Recall Modes
TTeesstt MMooddee ((TTeesstt BBuuttttoonn oonn tt hhee IICCCC))
• Enter TEST mode by pressing the TEST button with an insulated probe for one (1) second and release.
• The TEST mode causes the ICC to do the following
1) Resets the ICC from any active protection lockout mode
2) Resets the 3-minute anti-short cycle timer
3) Energizes the unit without a command for unit operation
• If the 3-minute anti-short cycle timer or 30 second minimum run timer is active (a flashing “c”, “C”, “h”, or “H” is displayed on the dual 7-segment LEDs) and a com­mand for unit operation is present, TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
2) The compressor will start and the outdoor fan will operate
3) The display will change to a steady “c”, “C”, “h”, or “H” to show the current
command for unit operation.
Note: If a command for unit operation is present at the end of TEST mode, the unit will continue to operate.
• If no command for unit operation is present, TEST mode causes
1) A steady “t” appears on the dual 7-segment LEDs
2) The compressor will start
3) The compressor will turn off after 5-seconds.
Note: Entering TEST mode without a command for unit operation will cause the compressor to run 5-seconds.
FFaauulltt RReeccaallll MMooddee ((TTEESSTT aanndd SSWW22 BBuuttttoonnss))
• Enter
• When entering and exiting FAULT RECALL mode the top and bottom segments
• When entering
FFAAUULL TT RREECCAALLLL
same time with insulated probes for one (1) second and release.
of the dual 7-segment LEDs will illuminate.
Fault Recall Mode – the top and bottom segments on the right side are illuminated
FFAAUULLTT RREECCAALLLL
stored faults on the dual 7-segment LEDs.
Lower case “t”
mode by pressing the
mode, the ICC will automatically scroll through
TTEESSTT
and
SSWW22
buttons at the
23
• Each fault is displayed one time with the top right hand segment of the dual 7-
Fault history is cleared with the top and bottom LED segments flash
segment display activated between faults.
• Each fault is displayed with the most recent fault displayed first.
• A maximum of six individual faults can be stored
• A maximum of three consecutive identical faults are stored.
• A “0” will be displayed with no faults are stored
• The ICC will automatically exit the faults
CClleeaarr FFaauu lltt HHiissttoorryy ((TTEESSTT aanndd SSWW22 BBuu ttttoonnss))
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) sec­onds with insulated probes and release.
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the history has been cleared.
Fault history is cleared with the top and bottom LED segments flash
NOTE: The memory card for the unit has specific shared data for this unit. The memory card is attached to the control box with a tether. The tether has an identifi­cation tag that can be used to identify the memory card. For the system data faults d1 through d8 reference the label on the memory card tether.
FFAAUULL TT RREECCAALLLL
mode after displaying stored
SYSTEM™ CONTROL WIRING
2
COMFORT CONTROL
24
12.6
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
c - First Stage Cooling Unit has received a command for first stage cooling
Normal operation
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
c - First Stage Cooling Unit has received a command for first stage cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer.
Wait until unit timer has expired or press the TEST button to reset timer.
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
c - First Stage Cooling Unit has received a command for first stage cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer.
Wait until unit timer has expired or press the TEST button to reset timer.
C - Second Stage Cooling Unit has received a command for second stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
c - First Stage Cooling Unit has received a command for first stage cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer.
Wait until unit timer has expired or press the TEST button to reset timer.
C - Second Stage Cooling Unit has received a command for second stage cooling
Normal operation
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
Status/Possible Cause – Troubleshooting
Information 0 – Standby No command for unit operation
Normal operation
c - First Stage Cooling Unit has received a command for first stage cooling
Normal operation
c - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer.
Wait until unit timer has expired or press the TEST button to reset timer.
C - Second Stage Cooling Unit has received a command for second stage cooling
Normal operation
C - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST button to reset timer.
h1 - First Stage Heat Pump Unit has received a command for first stage heat pump
Normal operation
h1 - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST button to reset timer.
h2 - Second Stage Heat Pump Unit has received a command for second stage heat pump
Normal operation
h2 - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST button to reset timer.
d - Defrost Active The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
COMFORT CONTROL2SYSTEM™ CONTROL WIRING
CONVENTIONAL THERMOSTAT WIRING
ICC DIAGNOSTIC CODES
ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
AND
Dual 7-Segment
LEDs Display
Code
0 – Standby No command for unit operation
FLASHING
H H
FLASHING
c - First Stage Cooling Unit has received a command for first stage cooling
c - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
C - Second Stage Cooling Unit has received a command for second stage cooling
C - Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
h - First Stage Heat Pump Unit has received a command for first stage heat pump
h – Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
H – Second Stage Heat Pump Unit has received a command for second stage heat pump
H – Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
d – Defrost Active The unit is undergoing a defrost cycle
t - Test Mode The ICC is in TEST mode
Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
Normal operation
Normal operation
• The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer.
• Wait until unit timer has expired or press the TEST button to defeat short cycle delay.
Normal operation
• The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer.
• Wait unit timer has expired or press the TEST button to defeat short cycle delay.
Normal operation
• The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run timer.
• Wait unit timer has expired or press the TEST button to defeat short cycle delay.
Normal operation
• The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer.
• Wait unit timer has expired or press the TEST button to defeat short cycle delay.
Normal operation
25
Dual 7-Segment
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) c
annot supply the required airflow for
proper system operation
Misapplied/wrong indoor air mover – replace w
ith properly sized air handler/furnace.
P – Protector Trip A command for compressor operation is present but no current is measured to the
Motor protector open
Line voltage disconnected
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for p
roper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P
– Protector Trip A command for compressor operation is p
resent but no current is measured to the compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) c
annot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip A
command for compressor operation is present but no current is measured to the c
ompressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
d
1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d
3 Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace
w
ith properly sized air handler/furnace.
P – Protector Trip A command for compressor operation is present but no current is measured to the compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) c
annot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace w
ith properly sized air handler/furnace.
P – Protector Trip A command for compressor operation is present but no current is measured to the compressor
Motor protector open
Line voltage disconnected
0
1Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for p
roper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P
– Protector Trip
A
command for compressor operation is
p
resent but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil 02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit every five (5) minutes for four (4) attempts. After that, the ICC will attempt a restart every twenty (20) minutes for up to four (4) hours.
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch T
he indoor air mover (air handler/furnace) cannot supply the required airflow for p
roper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P
– Protector Trip A command for compressor operation is p
resent but no current is measured to the compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit every five (5) minutes for four (4) attempts. After that, the ICC will attempt a restart every twenty (20) minutes for up to four (4) hours.
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P – Protector Trip A command for compressor operation is present but no current is measured to the compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit every five (5) minutes for four (4) attempts. After that, the ICC will attempt a restart every twenty (20) minutes for up to four (4) hours.
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit The ICC detects current in the Start circuit but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
d
1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d
3 Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip A
command for compressor operation is present but no current is measured to the c
ompressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit every five (5) minutes for four (4) attempts. After that, the ICC will attempt a restart every twenty (20) minutes for up to four (4) hours.
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit The ICC detects current in the Start circuit but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch T
he indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P – Protector Trip A command for compressor operation is present but no current is measured to the compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not Run)
The ICC has received a command for unit operation but no current is present in the start and run circuits.
The ICC will attempt to restart the unit every five (5) minutes for four (4) attempts. After that, the ICC will attempt a restart every twenty (20) minutes for up to four (4) hours.
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit The ICC detects current in the Start circuit but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run capacitor
Check for broken wires, loose connectors, or miswired compressor
Check compressor windings for continuity
09 Low Secondary Volts The secondary voltage at R and C is below 18VAC
Control transformer overloaded
Low line voltage
LEDs Display
Code
Diagnostic Description
P – Protector Trip A command for compressor operation is present but no current is measured to the compressor
Status/Possible Cause – Troubleshooting
Information
• Motor protector open
26
01 – Long Run Time (Compressor) The compressor has continuously run for more than 18 hours in the cooling mode.
02 – High Side Fault Compressor limit has opened four (4) times within a call for operation
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds
05 – Open circuit (Compressor will not Run)
• The ICC has had a protector trip for longer than 4 hours
06 – Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor
06 – Compressor Open Start Circuit The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call
07 – Compressor Open Run Circuit The ICC detects current in the Start circuit but not in the Run circuit of the compressor
07 – Compressor Open Run Circuit The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call
09 – Low Secondary Volts The secondary voltage at R and C is below 18VAC
• Low refrigerant charge
• Air ducts have substantial leakage
• Dirty indoor air filter
• Dirty outdoor coil
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
• Check thermostat wire connections (R, C, 1, &
2)
• Check thermostat location in zone (too close to discharge grill)
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
• Seized bearings in compressor
• Check for damaged, miswired, or wrong run capacitor
• Check for broken wires, loose connectors, or miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong run capacitor
• Check for broken wires, loose connectors, or miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong run capacitor
• Check for broken wires, loose connectors, or miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong run capacitor
• Check for broken wires, loose connectors, or miswired compressor
• Check compressor windings for continuity
• Control transformer overloaded
• Low line voltage
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor o
peration
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
21 Low Pressure Control Open T
he ICC detects the LPC is open. Note: The low pressure control is ignored f
or the first 90 seconds of compressor
operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
2
1 Low Pressure Control Open
T
he ICC detects the LPC is open. Note: The low pressure control is ignored f
or the first 90 seconds of compressor
operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor o
peration
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor o
peration
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
21 Low Pressure Control Open T
he ICC detects the LPC is open. Note: The low pressure control is ignored f
or the first 90 seconds of compressor
operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
2
1 Low Pressure Control Open The ICC detects the LPC is open. N
ote: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
83Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature
Replace the sensor
21 Low Pressure Control Open The ICC detects the LPC is open. N
ote: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
83Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature
Replace the sensor
84 Outdoor Ambient Temperature Fault The sensor detects an abnormally low or high outdoor ambient temperature
Check unit placement If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading.
21 Low Pressure Control Open T
he ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
83Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature
Replace the sensor
84 Outdoor Ambient Temperature Fault The sensor detects an abnormally low or high outdoor ambient temperature
Check unit placement If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading.
Replace the sensor.
90 Communication Fault The ICC detects and internal fault condition
Replace the ICC.
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
2
1 Low Pressure Control Open The ICC detects the LPC is open. N
ote: The low pressure control is ignored
f
or the first 90 seconds of compressor
operation
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
29 High Pressure Control Open The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure Control Trip
The ICC has locked out the compressor due to three (3) consecutive HPC trips on the same command for unit operation
30 Fuse Open The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
Dual 7-Segment
LEDs Display
Code
1 – Low Pressure Control Open
2
he ICC detects the LPC is open.
T
ote: The low pressure control is ignored
N
or the first 90 seconds of compressor
f
peration
o
21 – Active ProtectionLow Pressure
L Control Trip
Diagnostic Description
27 – Low Line Voltage or No Line Voltage Fault
28 – High Line Voltage Fault • Check line voltage
29 – High Pressure Control Open The ICC detects the HPC is open
L29 – Active Protection High Pressure Control Trip
30 – Fuse Open The ICC detects the on-board fuse is open
80 – Low Air Flow The ICC detects that the indoor unit is not providing the minimum airflow requirements.
83 – Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature
84 – Outdoor Ambient Temperature Fault The sensor detects an abnormally low or high outdoor ambient temperature
93 – Internal Control Fault The control is not functioning properly.
Status/Possible Cause – Troubleshooting
Information
Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Expansion valve is not operating correctly
PC has opened 3 times in the same cooling
L operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21
• Check incoming line voltage to the disconnect and unit
• Check wiring connections
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or miswired.
• Misapplied/wrong indoor air mover – replace with properly sized unit.
• Replace the sensor
• Check sensor is installed correctly on control
• Check unit placement – If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading.
• Replace the sensor.
• Check sensor is installed correctly on control
• Check control for proper system operation.
• Replace control
27
Dual 7-Segment
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch T
he indoor air mover (air handler/furnace) cannot supply the required airflow for p
roper system operation
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
P
– Protector Trip A command for compressor operation is p
resent but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor) The compressor has continuously run for m
ore than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open T
he ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling The ICC detects the run time for the past four (4) compressor cycles is less than three (3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to discharge grill)
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
21 Low Pressure Control Open The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor o
peration
Unit has low refrigerant charge
Indoor coil is frozen (cooling mode)
Dirty indoor coil or filter (cooling mode)
Indoor blower is not running (cooling mode)
Outdoor coil is frozen (heating mode)
Outdoor fan is not running (heating mode)
Expansion valve is not operating correctly
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to three (3) consecutive LPC trips on the same command for unit operation
27 – Low Line Voltage or No Line Voltage Fault
Check incoming line voltage to the disconnect and unit
Check wiring connections
28 High Line Voltage Fault
Check line voltage
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for
Misapplied/wrong indoor air mover – replace with properly sized air handler/furnace.
LEDs Display
Code
Diagnostic Description
1 – No Shared Data • Replace memory card with correct system
d
Status/Possible Cause – Troubleshooting
Information
information.
3 – Airflow CFM Mismatch
d
he indoor air mover (air
T
andler/furnace) cannot supply the
h required airflow for proper system operation
d4 – (Device) Memory Card Invalid for Device The data in the memory card inserted into the control board does not match the data in the control.
d8 – Old Shared Data System data is obsolete
CONVENTIONAL THERMOSTAT WIRING
28
Misapplied/wrong indoor air mover –
• replace with properly sized air handler/furnace.
• Check memory card to ensure it matches device
• Check if memory card is present
• If system will not operate, order new memory card to update system information.
12.7 Conventional 24VAC Thermostat Control Wiring
The (-)PRL series of heat pumps allow the installer to use conventional 24VAC con­trol wiring and a conventional thermostat for proper unit operation.
IIMMPPOORRTTAANNTT::
Comfort Control
This diagnostic information is not available when the (-)PRL unit is using a conven­tional thermostat. Reference section 12.2 Comfort Control Wiring.
Thermostat control wiring requires a minimum of six (6) wires for proper unit opera­tion:
Optional wiring:
L Terminal Output
• Flash 1 – Compressor running extremely long run cycle or low pressure
• Flash 2 – High pressure control trip
• Flash 3 – Unit short cycling
• Flash 4 – Locked rotor
• Flash 5 – Compressor will not run, open circuit
• Flash 6 – Open start circuit
• Flash 7 – Open run circuit
• Flash 8 – Control mis-operation
• Flash 9 – Low control voltage
When the L terminal from the outdoor unit is connected to a conventional thermo­stat that is L terminal compatible, the thermostat display will flash the above codes.
If the low voltage control wiring is run in conduit with the power supply, Class I insu­lation is required. Class II insulation is required if run separate. Low voltage wiring may be run through the insulated bushing provided in the 7/8 hole in the base panel, up to and attached to the pigtails from the bottom of the control box. Conduit can be run to the base panel if desired by removing the insulated bushing.
The preferred method of unit installation and operation is by the
2
System™, which allows access to the fault history of the system.
2
System™ Control
R – 24VAC
C – 24VAC common
Y1 – First stage operation
Y2 – Second stage operation
B – Heat pump operation
D – Defrost
L – ICC fault information
B
W2
W1
B
C
G
(
-)HPL Air Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
W
IRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y
2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
B
R
W
/R
PR
*
B
W2
W1
B
C
G
(-)HPL Air
H
andler
Y
1
E/W1
Typical Two-Stage Thermostat
(-)PRL
H
eat Pump Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
F
actory Standard
-
ODD
R
Y1
Y2
G
W
2
R
Y1
C
L
D
Y
Y
/BL
B
L
R
BR
W/R
P
R
Humidistat
*
B
W2
W1
B
C
G
(-)HPL Air
Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
BR
W/R
PR
DHM
*
B
W2
W1
B
C
G
(-)HPL Air
Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
BR
W/R
PR
DHM
L
*
A thermostat and a 24-volt, 40VA minimum transformer are required for the control circuit of the condensing unit. The furnace or the air handler transformer may be used if sufficient. See the wiring diagram for reference. Use Table 6 to size the 24­volt control wirings.
TABLE 6
IELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
F
SOLID COPPER WIRE - AWG.
3.0 16 14 12 10 10 10 2
.5 16 14 12 12 10 10
2.0 18 16 14 12 12 10
50 100 150 200 250 300
Thermostat Load - Amps
(1) Wire length equals twice the run distance.
OTE: Do not use control wiring smaller than No. 18 AWG between thermostat and outdoor unit.
N
Length of Run - Feet (1)
12.8 Typical Non-Communicating Thermostat Wiring Diagrams
The following figures show the typical wiring diagrams with (-)HPL air handler and (-)PRL heat pump. Cooling and heat pump airflows may need to be adjusted for homeowner comfort once the system is operational.
FIGURE 6
TYPICAL 2-STAGE THERMOSTAT: HEAT PUMP WITH ELECTRIC HEAT
FIGURE 8
TYPICAL TWO-STAGE THERMOSTAT: (-)PRL HEAT PUMP WITH ELECTRIC HEAT USING A TWO-STAGE THERMOSTAT WITH DEHUMIDIFICATION*
FIGURE 7
TYPICAL TWO-STAGE THERMOSTAT: (-)PRL HEAT PUMP WITH ELECTRIC HEAT USING A HUMIDISTAT FOR DEHUMIDIFICATION*.
FIGURE 9
(-)PRL HEAT PUMP WITH ELECTRIC HEAT USING A TWO-STAGE THERMOSTAT WITH DEHUMIDIFICATION* AND A MALFUNCTION LIGHT
K – BLACK G – GREEN PR – PURPLE Y – YELLOW
B
R – BROWN GY – GRAY R – RED
B
L – BLUE O – ORANGE W – WHITE
B
*See Section 5.11 for proper DIP switch selection.
WIRE COLOR CODE
CONVENTIONAL THERMOSTAT WIRING
*If maximum outlet temperature rise is desired, it is recommended that W1 and W2 be jumpered together.
29
– 24VAC
1 – First stage operation
– Heat pump operation
SECTION 13.4 HERE!!!!
12.9 ICC Control Operation with Conventional Thermostat Wiring
IInnsstt aall llaattii oonn VVeerriiffii ccaattii oonn
• 24V AC power on R&C must be present at the ICC for it to operate
• Line voltage must be present at the ICC for the compressor and the outdoor fan to operate
• The ICC displays a “0” for standby mode. Standby mode indicates line voltage and 24VAC are present at the ICC and there is not a call for unit operation from the thermostat.
Zero (0) displayed
The unit is in standby
CCaallll ffoorr CCoommpprreessss oorr OOppeerraattiioonn ((YY11 LLEEDD))
• If a call for compressor operation is received by the ICC (first stage/second stage cooling or first stage/second stage heating), the red Y1 LED will illuminate.
• The ICC has an on/off fan delay of one (1) second for each stage of heating or cooling.
• The ICC ignores the lower pressure control for the first 90 seconds of compressor operation.
• On heat pumps, the ICC ignores the LPC during the defrost cycle.
• The dual 7-segment LED displays five (5) operational status codes:
11)) FFiirrsstt SSttaaggee CCoooolliinngg OOppeerraattiioonn
cooling operation, a lower case “c” is displayed on the dual 7-segment LEDs.
– When the ICC receives a call for first stage
CONVENTIONAL THERMOSTAT WIRING
Lower case “c” indicates first stage cooling operation
22)) SSeeccoonndd SSttaaggee CCoooolliinngg OOppeerr aattiioonn
stage cooling operation, an upper case “C” is displayed on the dual 7-segment LEDs.
Upper case “C” indicates second stage cooling operation
33)) FFiirrsstt SSttaaggee HHeeaattiinngg OOppeerr aatt iioonn
heating operation, “h” is displayed on the dual 7-segment LEDs.
“h” indicates first stage heating operation
– When the ICC receives a call for second
- When the ICC receives a call for first stage
30
44)) SSeeccoonndd SSttaaggee HHeeaattiinngg OOppeerraattiioonn
h2” indicates second stage heating operation
Lower case “dindicates defrost operation (in heating mode)
Flashing lower case h and 1 A call for first stage heating has been received
“h2” indicates second stage heating operation
Lower case “dindicates defrost operation (in heating mode)
stage heating operation, “H” is displayed on the dual 7-segment LEDs.
- When the ICC receives a call for second
H
“H” indicates second stage heating operation
55)) DDeeffrroosstt OOppeerraattiioonn displayed on the dual 7-segment LEDs.
– When the ICC starts a defrost cycle, a lower case “d” is
Lower case “d” indicates defrost operation (in heating mode)
33--mmiinnuutt ee AAnnttii--sshhoorrtt CCyyccll ee TTii mmeerr
• The ICC has a built in 3-minute time delay between compressor operations to protect the compressor against short cycling. The dual 7-segment LEDs will flash “c”, “C”, “h”, or “H” while the short cycle timer is active and a call for unit operation is received.
CONVENTIONAL THERMOSTAT WIRING
Flashing lower case c A call for first stage cooling has been received
Flashing upper case C A call for second stage cooling has be received
Flashing lower case h A call for first stage heating has been received
Flashing upper case h A call for second stage heating has been received
H
• The 3-minute time delay can be bypassed when a call for compressor operation is present by pressing the TEST button for 1 second and releasing. The compres­sor will begin operation and the dual 7-segment will stop flashing.
3300 SSeeccoonndd MMiinnii mmuumm RRuunn TTiimmeerr
• The ICC has a built in 30 second minimum unit run time. If a call for compressor operation is received by the ICC and the call is removed, the compressor will con­tinue to operate for 30 seconds. The dual 7-segment LEDs will flash “c”, “C”, “h”, or “H” while the minimum run timer is active.
11 SSeeccoonndd CCoommpprreessssoorr //FFaann DDeell aayy
• The ICC starts/stops the outdoor fan one (1) second after the start/stop of the compressor upon a call for compressor operation to minimize current inrush and/or voltage drop.
31
12.10 Active Compressor Protection Mode
• The ICC actively protects the compressor from harmful operation during a fault condition.
• When the ICC detects a condition that could damage the compressor, the ICC will enter active protection mode and lockout compressor operation
• The condition causing active protection must be resolved then the ICC can be reset to restart the system.
• There are five (5) active protection modes:
11)) LLooww PPrreessss uurree CCoonnttrrooll LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing 21 when a low pressure control lockout occurs.
• The ICC addresses low pressure control faults differently depending on the mode of unit operation (cooling or heating mode).
CONVENTIONAL THERMOSTAT WIRING
Active Protection – Code L21 – Open low pressure control
CCoooolliinngg MMooddee
• If the LPC opens three (3) times during the same call for cooling operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
HHeeaattiinn gg MMooddee
• There are two scenarios that will cause active protection during a LPC trip when the unit is in the heating mode:
AAccttiivvee PPrrootteeccttiioonn ww ii tthh hhaarrdd lloocckkoouutt::
If the LPC opens three (3) times within 120 minutes for the same call for heating operation, the ICC will lockout the compressor to keep it from continuing to oper­ate and flash a “L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
AAccttiivvee PPrrootteeccttiioonn wwiitthh ssoofftt lloocckkoouutt::
If the LPC opens three (3) times for the same call for heating and the outdoor ambient temperature is below 5F, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “21”. Once the outdoor ambient rises above 5F the ICC will clear active pro­tection automatically.
IIMMPPOORRTTAANNTT:: the outdoor temperature rises above 5F. Wait until the outdoor ambient tempera­ture rises above 5F before performing further diagnostics.
22)) HHiigg hh PPrreessssuurree CCoonnttrr ooll LLoocckkoouutt
• If the HPC opens three (3) times during the same call for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L” on the dual 7-segment LEDs followed by a “29”.
This mode of active protection must be manually reset.
This mode of active protection must be manually reset.
This mode of active protection will automatically deactivate once
32
Active Protection – Code L29 – Open high pressure control
IIMMPPOORRTTAANNTT::
33)) LLoocckkeedd RRoottoorr
• The ICC will display a flashing “L” followed by a flashing “04” when a locked rotor condition occurs.
This mode of active protection must be manually reset.
CONVENTIONAL THERMOSTAT WIRING
Active Protection – Code L4 – Locked rotor
If the ICC detects the compressor has run less than 15 seconds for four (4) con­secutive starts during the same call for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7­segment LEDs followed by a “04”.
IIMMPPOORRTTAANNTT::
44)) OOppeenn SStt aarrtt CCiirrccuuiitt LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “06” when an open start circuit condition occurs.
This mode of active protection must be manually reset.
Active Protection – Code L6 – Compressor open start circuit
If the ICC detects current in the run circuit without current present in the start cir­cuit, , the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “06”.
IIMMPPOORRTTAANNTT::
55)) OOppeenn RRuunn CCiirrccuuiitt LLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “07” when an open start circuit condition occurs.
If the ICC detects current in the start circuit without current present in the run cir­cuit, , the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “07”.
This mode of active protection must be manually reset.
Active Protection – Code L7 – Compressor open run circuit
33
IIMMPPOORRTTAANNTT::
with insulated probes for one (1) second and release.
segment LEDs will illuminate.
Fault Recall Mode – the top and bottom segments illuminated
EExxiittiinngg AAccttiivvee CCoommpprreessssoorr PPrrootteeccttiioonn LLoocc kkoouutt
Three are three methods to reset the ICC after an active protection lockout:
1) Cycle the line voltage to the unit
2) Cycle 24VAC to the ICC (remove the R or C connection to the ICC)
3) Push the TEST button down for one (1) second and release
Note: The ICC will attempt to start the unit when the TEST button is pressed and released
NNoottee::
The preferred method of resetting the ICC is to push the TEST button down
for one (1) second.
This mode of active protection must be manually reset.
12.11 Test and Fault Recall Modes
TTeesstt MMooddee ((TTeesstt BBuuttttoonn oonn tt hhee IICCCC))
• Enter TEST mode by pressing the TEST button with an insulated probe for one (1) second and release.
• The TEST mode causes the ICC to do the following
1) Resets the ICC from any active protection lockout mode
2) Resets the 3-minute anti-short cycle timer
3) Energizes the unit without a call for unit operation
• If the 3-minute anti-short cycle timer or 30 second minimum run timer is active (a flashing “c”, “C”, “h”, or “H” is displayed on the dual 7-segment LEDs) and a call for unit operation is present, TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display
CONVENTIONAL THERMOSTAT WIRING
Lower case “t”
2) The compressor will start
3) The display will change to a steady “c”, “C”, “h”, or “H” to show the current call
for unit operation.
Note: If a call for unit operation is present at the end of TEST mode will cause the unit to continue to operate.
• If no call for unit operation is present, TEST mode causes
1) A steady “t” appears on the dual 7-segment LEDs
2) The compressor will start
3) The compressor will turn off after 5-seconds.
Note: Entering TEST mode without a call for unit operation will cause the com­pressor to run 5-seconds.
FFaauulltt RReeccaallll MMooddee ((TTEESSTT aanndd SSWW22 BBuuttttoonnss))
• Enter
• When entering and exiting FAULT RECALL mode the top and bottom segments
• When entering
FFAAUULLTT RREECCAALLLL
same time with insulated probes for one (1) second and release.
of the dual 7-segment LEDs will illuminate.
FFAAUULLTT RREECCAALLLL
stored faults on the dual 7-segment LEDs.
mode by pressing the
Fault Recall Mode – the top and bottom segments on the right hand are illuminated
mode, the ICC will automatically scroll through
TTEESSTT
and
SSWW22
buttons at the
34
• Each fault is displayed one time with the top right hand segment of the dual 7-
Fault Recall Mode – the top and bottom segments illuminated
segment display activated between faults.
• Each fault is displayed with the most recent fault displayed first.
• A maximum of six individual faults can be stored
• A maximum of three consecutive identical faults are stored.
• A “0” will be displayed with no faults are stored
• The ICC will automatically exit the faults
IIMMPPOORRTTAANNTT:: fault history cannot be displayed using a conventional thermostat.
CClleeaarr FFaauu lltt HHiissttoorryy ((TTEESSTT aanndd SSWW22 BBuu ttttoonnss))
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) sec­onds with insulated probes and release.
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the history has been cleared.
The ICC stores the previous six history faults. The complete stored
Fault history is cleared with the top and bottom LED segments flash
FFAAUULL TT RREECCAALLLL
mode after displaying stored
CONVENTIONAL THERMOSTAT WIRING
35
13.0 ELECTRICAL WIRING
NOTE: Check all wiring to be sure connections are securely fastened, electrically isolated from each other and that the unit is properly grounded.
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local code.
13.1 Power Wiring
It is important that proper electrical power from a commercial utility is available at the condensing unit contactor. Voltage ranges for operation are shown in Table 7.
Install a branch circuit disconnect within sight of the unit and of adequate size to handle the starting current (see Table 1).
Power wiring must be run in a rain-tight conduit. Conduit must be run through the connector panel below the access cover (see Figure 1) and attached to the bottom of the control box.
Connect power wiring to line voltage lugs located in outdoor condensing unit electri­cal box. (See wiring diagram attached to unit access panel.)
Check all electrical connections, including factory wiring within the unit and make sure all connections are tight.
DO NOT connect aluminum field wire to the contactor terminals.
TABLE 7
OLTAGE RANGES (60 HZ)
V
Nameplate Voltage Maximum Load Design Conditions for
208/230 (1 Phase) 197 - 253
Operating Voltage Range at Copeland
Compressors
13.2 Grounding
A grounding lug is provided near the contactor for a ground wire.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
13.3 Control Wiring
If the low voltage control wiring is run in conduit with the power supply, Class I insu­lation is required. Class II insulation is required if run separate. Low voltage wiring may be run through the insulated bushing provided in the 7/8 hole in the base panel, up to and attached to the pigtails from the bottom of the control box. Conduit can be run to the base panel if desired by removing the insulated bushing.
A thermostat and a 24 volt, 40 VA minimum transformer are required for the control circuit of the condensing unit. The furnace or the air handler transformer may be used if sufficient. See the wiring diagram for reference. Use Table 7 to size the 24 volt control wiring.
14.0 START-UP AND PERFORMANCE
Even though the unit is factory charged with Refrigerant-410A, the charge must be checked to the charge table attached to the service panel and adjusted, if required. Allow a minimum of 5 minutes of run time before analyzing charge.
At initial start-up or after extended shutdown periods, make sure the heater is ener­gized for at least 12 hours before the compressor is started. (Disconnect switch on and wall thermostat off.) Connect the communicating system per Figure 5. Once all devices are connected, power up the line and low voltage to the system. When all devices are powered, the thermostat should detect the indoor and outdoor units within 45 seconds.
36
15.0 CHECKING AIRFLOW
The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures.
The correct air quantity is critical to air conditioning systems. Proper operation, effi­ciency, compressor life, and humidity control depend on the correct balance between indoor load and outdoor unit capacity. Excessive indoor airflow increases the possibility of high humidity problems. Low indoor airflow reduces total capacity, and causes coil icing. Serious harm can be done to the compressor by low airflow, such as that caused by refrigerant flooding.
Heat pump systems require a specified airflow. Each ton of cooling requires between 340 and 450 cubic feet of air per minute (CFM).
Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet air­flow to all rooms in the home. This ensures a comfortable living space.
These simple mathematical formulas can be used to determine the CFM in a resi­dential or light commercial system.
Electric resistance heaters can use
CFM =
Gas furnaces can use
CFM =
An air velocity meter or airflow hood can give a more accurate reading of the sys­tem CFM’s.
volts x amps x 3.414
1.08 x temp rise
BTUH
∆T x 1.08
16.0 CHECKING REFRIGERANT CHARGE
Charge for all systems should be checked against the Charging Chart inside the access panel cover. Before using the chart, the indoor conditions must be within 2°F of desired comfort conditions and system must be run until operating conditions stabilize (15 min. to 30 min.)
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
IMPORTANT: Use industry-approved charging methods to ensure proper system
charge. NOTE: The optimum refrigerant charge for the (-)PRL-0-36 & (-)PRL-048 is affected
more by the application than the other (-)PRL models due to the relationship between the indoor and outdoor coil volumes. Therefore, multiple charging charts have been developed to assist the field technician in optimizing the charge for the application on these two models. Refer to the “Specific Charging Instructions” note shown on the charging chart attached to the unit and choose the appropriate chart for the specific application being installed or serviced. New installations utilizing a downflow or horizontal right air-handler or a coil installed on a gas furnace may require removal of refrigerant since the factory charge could result in an over­charged condition if the line set is relatively short.
16.1 Charging units with R-410A Refrigerant
Charge for all systems should be checked against the Charging Chart inside the access panel cover.
37
IMPORTANT: Do not operate the compressor without charge in system.
Addition of R-410A will raise pressures (vapor, liquid and discharge).
If adding R-410A raises both vapor pressure and temperature, the unit is over­charged.
IMPORTANT: Use industry-approved charging methods to ensure proper system charge.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22 PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGER­ANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAM­AGE, OR PERSONAL INJURY.
16.2 Charging By Liquid Pressure
Liquid pressure method is used for charging systems in the cooling and heating mode. The service port on the liquid service valve (small valve) and suction (large valve) is used for this purpose.
Verify that the outdoor unit is running and the indoor air mover is delivering the maximum airflow for this system size. Read and record the outdoor ambient tem­perature. Read and record the liquid and suction pressures at the ports on the liquid and suction valves. If refrigerant lines are sized using the nameplate charge, the correct liquid pressure is found at the intersection of the suction pressure and the outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
16.3 Charging By Weight
For a new installation, evacuation of interconnecting tubing and indoor coil is ade­quate; otherwise, evacuate the entire system. Use the factory charge shown in Table 1 of these instructions or unit data plate. Note that charge value includes charge required for 15 ft. of standard size interconnecting liquid line. Calculate actu­al charge required with installed liquid line size and length using:
1/4” O.D. = .3 oz./ft. 5/16” O.D. = .4 oz./ft. 3/8” O.D. = .6 oz./ft. 1/2” O.D. = 1.2 oz./ft.
With an accurate scale (+/– 1 oz.) or volumetric charging device, adjust charge dif­ference between that shown on the unit data plate and that calculated for the new system installation. If the entire system has been evacuated, add the total calculat­ed charge.
NOTE: The optimum refrigerant charge for the (-)PRL-036 & (-)PRL-048 is affected more by the application than other (-)PRL models due to the relationship between the indoor and outdoor volumes. Therefore, if charging by weight on these two models, the net refrigerant charge must be reduced if the application utilizes an air­handler in the downflow or horizontal right configuration or in dual fuel applications (coil installed on a gas furnace). The recommended net charge reduction for down­flow/horizontal right air-handler and dual fuel applications is shown on the applica­ble charging chart attached to the (-)PRL-036 & (-)PRL-048. It is highly recommend­ed that the refrigerant charge also be checked and adjusted based on the appropri­ate charging chart once the unit is put into operation.
16.4 Final Leak Testing
After the unit has been properly evacuated and charged, a halogen leak detector should be used to detect leaks in the system. All piping within the condensing unit, evaporator, and interconnecting tubing should be checked for leaks. If a leak is detected, the refrigerant should be recovered before repairing the leak. The Clean Air Act prohibits releasing refrigerant into the atmosphere.
38
WARNING
!
TURN OFF ELECTRIC POWER AT THE FU SE BOX OR SE R V IC E PA N E L BEF O R E MAKI N G ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNEC­TION M US T BE CO MP L ET ED BEFORE MAKING LINE VOLTAGE CONNECTIONS. FAILURE TO DO SO CAN RESULT IN ELECTRICAL SHOCK , S E V ER E P ER SO N AL INJURY OR DEATH.
17.0 ACCESSORIES
17.1 Dual Fuel Kit Model (Part No. RXME-A01)
This kit is required if this unit is installed in a dual fuel application.
17.2 Remote Outdoor Temperature Model (Part No. 47-102709-03)
This is a kit that has a longer remote sensor that can be installed away from the outdoor unit for better thermostat temperature display.
17.3 RXME-A02 Communicating 2 Wire Kit
This kit will allow the outdoor unit to communicate to the system with only 2 wires.
18.0 TROUBLESHOOTING
IMPORTANT: The JEC series units with the ICC (Integrated Compressor Control) provide status and diagnostic information that greatly enhances the ability to quickly diagnose system faults. Use the following troubleshooting guides as another tool in system diagnostics.
NOTE: In diagnosing common faults in the cooling system, develop a logical thought pattern as used by experienced technicians. The charts which follow are not intended to be an answer to all problems but only to guide the technician’s trouble shooting. Through a series of yes and no answers, follow the logical path to a likely conclusion.
A novice technician should use these charts like a road map. Remember that the chart should clarify a logical path to the solution.
18.1 Serial Communicating System Initial Startup
Connect the system. There are four wires that need to be connected to each unit:
• R 24 VAC
• C 24 VAC common
• 1 Communications
• 2 Communications
Thermostat Indoor Outdoor R – – – – – – – – – – – – – – – – – – R – – – – – – – – – – – – – R 1 – – – – – – – – – – – – – – – – – – 1 – – – – – – – – – – – – – 1 2 – – – – – – – – – – – – – – – – – – 2 – – – – – – – – – – – – – 2 C – – – – – – – – – – – – – – – – – – C – – – – – – – – – – – – – C
These wires need to be connected to each device thermostat, indoor air handler and outdoor unit (heat pump or AC).
If the communications wires are wired backwards at any point the green LED (D52) will always be on. If this happens check the wires at each point to ensure they are not reversed.
Once all devices are connected power up the line and low voltage to the system. When all devices are powered the thermostat should detect the indoor and outdoor units within 45 seconds. The air handler and outdoor units have a set of bias dip­switches set at a factory default to the ON position. These dipswitches are for future use DO NOT CHANGE DIP SWITCHES.
Once the system is powered the airflow settings will be configured for all devices. The outdoor unit will send information to configure indoor airflow. If the indoor unit is incapable of supplying the required airflow a d3 fault will be displayed on the ther­mostat and outdoor unit.
All devices have a LEARN button. This button is for future use and has no function at this time.
IMPORTANT: DO NOT USE A PHONE CORD TO CONNECT INDOOR AND OUTDOOR UNITS. THIS WILL DAMAGE THE CONTROLS.
IMPORTANT: DO NOT CONNECT THE SYSTEM TO A PHONE LINE. THIS WILL DAMAGE THE CONTROLS.
Air Handler Air Conditioner
Furnace Heat Pump
39
ADVANCED SETTINGS
All adjustments for airflow are made at the thermostat at this point. Items that can be changed are Airflow trim adjustment Dehumidification Setpoint and mode of operation. The thermostat also has a wide range of fault and history information. The following tables show all of the available options by unit type. To go down into a menu press Install Config to move back up press the Menu button. See Installation Instructions.
18.2 REPLACEMENT OF COMFORT CONTROL2SYSTEM™ CONTROL
18.2 BOARD
Each control board in the Comfort Control2System™ needs information specific to the unit the control is installed in. This information is called shared data because it is distributed (shared) on the HVAC network. The shared data for a unit contains information that allows the unit to operate correctly.
FIGURE 10
TETHER
MEMORY
CARD
When a control board requires replacement, it is important that the replacement board gets the shared data from the old control. The primary way the replacement control gets this information is by the memory card that should be installed on the old control. Remove the memory card from the old control, but leave it attached to the unit by the plastic tether, replace the control and reinstall the memory card on the new control. If for some reason the memory card has been damaged or is miss­ing, the shared data from the network (air handler) will be used by the control. The network shared data is considered a back up for a lost or missing memory card. Never remove the memory card from the unit or cut the tether of the memory card as it is the most effective way to transfer the shared data. If the memory card is damaged or missing a new memory card can be ordered from Pro Stock. The unit will operate without the memory card, but a D4 error will be displayed on the seven segment displays.
The memory card from a different unit should never be used.
40
18.3 Electrical Checks Flow Chart
hermostat call
T
For cooling, no cooling
utdoor Unit
O
Running?
No
Yes
efer to panel cover/documentation
R
or Fault Code Troubleshooting.
f
heck fault history for other faults.
C
7-Segment display lit?
Yes
Y1 LED lit?
Yes
Flashing Mode Character
Yes
Alternating “C” and “##” (Code)
Yes
No
No
No
No
Check control voltage (R and C) to control
No call received. 24V Systems: Check thermostat, control wiring Comm Systems: Check comm. wiring, T-Stat
Waiting for Anti-S.C. Delay to clear
Note: For solid comm LED, check comm wiring, term/bus switches at ICC and AH ctrls.
Control in Lockout Mode. Check fault history and refer to Diagnostic Chart.
SEE PANEL COVER OR
OTHER DOCUMENTATION
FOR FAULT CODE
TROUBLESHOOTING.
41
18.4 Cooling Mechanical Checks Flow Chart
Unit Running?
ES NO
Y
Pressure problems? Checks Flow Chart
High Head Pressure Low Head Pressure Low Suction Pressure
Dirty Outdoor Coil Low on Charge Dirty Filters
Inoperative Outdoor Fan Open IPR Valve Dirty Indoor Coil
Overcharge Low Ambient Temperature Inadequate Indoor Air Flow
Recirculation of Inoperative Compressor Inoperative Indoor Blower
Outdoor Air Valves
Non-condensibles Outdoor Check Valve Low on Charge
Closed
Higher than Ambient Restricted Indoor
Air Entering Outdoor Coil Metering Device
Restricted Indoor
Wrong Outdoor Fan Rotation Metering Device Restriction in System
Go to Electrical
Restricted Recirculation of
Filter Drier Indoor Air
Wrong Indoor
Blower Rotation
Inadequate Ducts
Outdoor Check Valve Closed
Restricted Filter Drier
42
18.5 Defrost Mechanical Checks Flow Chart
No Defrost Incomplete Defrost Excessive Defrost
Reversing Valve Stuck Poor Sensor Location
(doesn’t stop O.D. Fan)
Welded Rev Valve Thermostat Satisfies Wind Affecting
Relay During Defrost in Defrost
DEFROST SYSTEM
Wrong Defrost
Timer Setting Poor Sensor Location
Failed Defrost Relay Low System Charge
Loose Defrost
Sensor
Check Coil Sensor
Connector
43
18.6 General Trouble Shooting Chart
!
WARNING
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing unit
Outdoor fan runs, compressor • Run or start capacitor defective • Replace
doesn’t • Start relay defective • Replace
Insufficient cooling • Improperly sized unit • Recalculate load
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
Registers sweat • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component
High head-high or normal vapor • Dirty outdoor coil • Clean coil
pressure - Cooling mode • Refrigerant overcharge • Correct system charge
Low head-high vapor pressures • Flowcheck piston size too large • Change to correct size piston
Low vapor - cool compressor - • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
iced indoor coil filter
High vapor pressure • Excessive load • Recheck load calculation
Fluctuating head & vapor • TXV hunting • Check TXV bulb clamp - check air distribution on coil - replace
pressures TXV
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
• Thermostat out of calibration-set too high • Reset
• Defective contactor • Check for 24 volts at contactor coil - replace if contacts are open
• Blown fuses / tripped breaker • Replace fuses / reset breaker
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) • Reset-also see high head pressure remedy-The high pressure control opens at 450 PSIG
• Loose connection • Check for correct voltage at compressor ­check & tighten all connections
• Compressor stuck, grounded or open motor winding, • Wait at least 2 hours for overload to reset.
open internal overload. If still open, replace the compressor.
• Low voltage condition • Add start kit components
• Improper indoor airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
nameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
filter
• Flowcheck piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
• Outdoor fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
• Defective Compressor valves • Replace compressor
• Incorrect capillary tubes • Replace coil assembly
• Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
• Defective compressor • Replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
44
Unit will not run • Miswiring of communications (communication light • Check communication wiring
on continuously)
18.7 Service Analyzer Charts
COMPRESSOR OVERHEATING
SYMPTOMS POSSIBLE CAUSE CHECK/REMEDIES
High superheat Low charge Check system charge
Faulty metering device Restricted cap tube, TEV (TXV)
Power element superheat adjustment
Foreign matter stopping flow
High internal load Hot air (attic) entering return
eat source on; mis-wired or
H faulty control
Restriction in liquid line Drier plugged
Line kinked
Low head pressure Low charge
Operating in low ambient temperatures
Suction or liquid line subjected Hot attic to high heat source
Low voltage Loose wire connections Check wiring
Power company problem, Have problem corrected before transformer diagnosis continues
Undersized wire feeding unit Correct and complete diagnosis
High voltage Power company problem Have problem corrected
High head pressure Overcharge Check system charge
Dirty heat pump coil Clean coil
Faulty or wrong size Replace fan motor heat pump fan motor
Faulty fan blade Replace fan blade or wrong rotation
Recirculation of air Correct installation
Additional Heat Source Check for dryer vent near unit
Non-condensibles Recover refrigerant, Evacuate and
Equipment not matched Correct mis-match
Short cycling of compressor Faulty pressure control Replace pressure control
Loose wiring Check unit wiring
Thermostat Located in supply air stream
TEV Internal foreign matter
Capillary tube Restricted with foreign matter
Hot water line
Replace with correct rotation motor
Check for recirculation from other equipment
recharge system
Differential setting too close
Customer misuse
Power element failure
Valve too small
Distributor tube/tubes restricted
Kinked I.D. reduced from previous
compressor failure
45
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Short cycling of compressor (cont.) Low charge Check system charge
ow evaporator air flow Dirty coil
L
Dirty filter
Duct too small or restricted
Faulty run capacitor Replace
Faulty internal overload Replace compressor
Faulty Compressor Valves Fast equalization/ Replace compressor and examine
Low pressure difference system to locate reason
ELECTRICAL
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Voltage present on load side Compressor start components Check start capacitor of compressor contactor and compressor won’t run Check potential relay
Run capacitor Check with ohmmeter
Internal overload Allow time to reset
Compressor windings Check for correct ohms
Voltage present on line side of Thermostat Check for control voltage to com­pressor contactor only contactor coil
Compressor control circuit High pressure switch
Low pressure switch
Ambient thermostat
Solid state protection control or internal thermal sensors
Compressor timed off/on control or interlock
No voltage on line side Blown fuses or tripped circuit breaker Check for short in wiring or unit of compressor contactor
Improper wiring Re-check wiring diagram
Improper voltage High voltage Wrong unit
Power supply problem
Low voltage Wrong unit
Power supply problem
Wiring undersized
Loose connections
Single Phasing (3 phase) Check incoming power and fusing
CONTAMINATION
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Moisture Poor evacuation on installation In each case, the cure is the same.
or during service Recover refrigerant. Add filter drier,
High head pressure Non-condensibles air
Unusual head and suction readings Wrong refrigerant
Foreign Matter­copper filings Copper tubing cuttings
Copper oxide Dirty copper piping
Welding scale Nitrogen not used
Soldering flux Adding flux before seating
copper part way
Excess soft solder Wrong solder material
46
evacuate and re-charge
LOSS OF LUBRICATION
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Compressor failures Line tubing too long Add oil to the recommended level
ine tubing too large Reduce pipe size to improve
L
Low suction pressure Low charge Check system charge
Refrigerant leaks Repair and recharge
Cold, Noisy compressor - Slugging Dilution of Oil with Refrigerant Observe piping guidelines
Noisy compressor Migration Check crankcase heater
Cold, sweating compressor Flooding Check system charge
Low Load Reduced air flow Dirty filter
Thermostat setting Advise customer
Short cycling of compressor Faulty pressure control Replace control
Loose wiring Check all control wires
Thermostat In supply air stream,
oil return
irty coil
D
Wrong duct size
Restricted duct
out of calibration,
Customer misuse
FLOODED STARTS
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
Liquid in the compressor shell Faulty or missing crankcase heater Replace crankcase heater
Too much liquid in system Incorrect piping Check Piping guidelines
Overcharge Check and adjust charge
SLUGGING
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
On start up Incorrect piping Review pipe size guidelines
TEV hunting when running Oversized TEV Check TEV application
FLOODING
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
Poor system control Loose sensing bulb Secure the bulb and insulate using a TEV
Bulb in wrong location Relocate bulb
Wrong size TEV Use correct replacement
Improper superheat setting Adjust, if possible;
Replace, if not
Poor system control Overcharge Check system charge using capillary tubes
High head pressures Dirty heat pump
Restricted air flow
Recirculation of air
Evaporator air flow too low Adjust air flow to 400 CFM/Ton
47
THERMOSTATIC EXPANSION VALVES
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
High Superheat, Low Suction Pressure Moisture freezing and blocking valve Recover charge, install filter-drier,
Dirt or foreign material blocking valve Recover charge, install filter-drier,
Low refrigerant charge Correct the charge
Vapor bubbles in liquid line Remove restriction in liquid line
Misapplication of internally equalized Use correct TEV valve
Plugged external equalizer line Remove external equalizer line
Undersized TEV Replace with correct valve
Loss of charge from power Replace power head or complete head sensing bulb TEV
Charge migration from sensing bulb Ensure TEV is warmer than to power head (Warm power head sensing bulb with warm, wet cloth. Does valve operate correctly now?)
Improper superheat adjustment Adjust superheat setting counter­(Only applicable to TEV with adjustable clockwise superheat settings)
Valve feeds too much refrigerant, Moisture causing valve to stick open. Recover refrigerant, replace filter­with low superheat and higher than drier, evacuate system and then nor­mal suction pressure recharge
Dirt or foreign material causing Recover refrigerant, replace filter­valve to stick open drier, evacuate system and
TEV seat leak (A gurgling or hissing Replace the TEV sound is heard AT THE TEV during the off cycle, if this is the cause.) NOT APPLICABLE TO BLEED PORT VALVES.
Oversized TEV Install correct TEV
Incorrect sensing bulb location Install bulb with two mounting
Low superheat adjustment Turn superheat adjustment (only applicable to TEV with clockwise adjustable superheat setting)
Incorrectly installed, or restricted Remove restriction, or relocate external equalizer line external equalizer
Compressor flood back upon start up Refrigerant drainage from flooded Install trap riser to the top of the
evaporator evaporator coil
Compressor in cold location Install crankcase heater on
Any of the causes listed under Any of the solutions listed under Symptoms of Problem #2 Solutions of Problem #2
evacuate system, recharge
evacuate system, recharge
Correct the refrigerant charge
emove non-condensible gases
R
Size liquid line correctly
restriction
recharge
straps, in 2:00 or 4:00 position on suction line, with insulation
compressor
48
THERMOSTATIC EXPANSION VALVES
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Superheat is low to normal Unequal evaporator circuit loading Ensure air flow is equally distributed with low suction pressure through evaporator
Check for blocked distributor tubes
Low load or airflow entering Ensure blower is moving proper air evaporator coil CFM
Remove/Correct any air flow restriction
Superheat and suction Expansion valve is oversized Install correct TEV pressure fluctuate (valve is hunting)
Sensing bulb is affected by liquid Relocate sensing bulb in another refrigerant or refrigerant oil flowing position around the circumference of through suction line the suction line
Unequal refrigerant flow through Ensure sensing bulb is located evaporator circuits properly
Check for blocked distributor tubes
Improper superheat adjustment Replace TEV or adjust superheat (only possible with TEV having superheat adjustment)
Moisture freezing and partially Recover refrigerant, change filter­blocking TEV drier, evacuate system and
Valve does not regulate at all External equalizer line not connected Connect equalizer line in proper
or line plugged location, or remove any blockage
Sensing bulb lost its operating charge Replace TEV
Valve body damaged during soldering Replace TEV or by improper installation
recharge
49
TABLE 8
TEMPERATURE PRESSURE CHART
TEMP R-410A
(Deg. F) PSIG
-150
-140
-130
-120
-110
-100
-90 — 80
-
-70
-60 0.4
-50 5.1
-40 10.9
-35 14.2
-30 17.9
-25 22.0
-20 26.4
-15 31.3
-10 36.5
-5 42.2 0 48.4 5 55.1
10 62.4 15 70.2 20 78.5 25 87.5 30 97.2 35 107.5 40 118.5 45 130.2 50 142.7 55 156.0 60 170.1 65 185.1 70 201.0 75 217.8 80 235.6 85 254.5 90 274.3
95 295.3 100 317.4 105 340.6 110 365.1 115 390.9 120 418.0 125 446.5 130 476.5 135 508.0 140 541.2 145 576.0 150 612.8
18.8 Subcooling Calculation
1. Measure the liquid pressure at the liquid line service valve.
2. Convert the liquid line pressure to saturated temperature. See Table 8.
3. Measure the liquid line temperature at the liquid line service valve.
4. Compare the liquid line temperature to the saturated temperature.
5. The difference between saturated temperature and liquid line temperature is the subcooling. Subcooling normal range 9° to 12°.
TABLE 9
IR CONDITIONING SYSTEM TROUBLESHOOTING TIPS
A
AIR CONDITIONING SYSTEM
ROUBLESHOOTING TIPS
T
SYSTEM PROBLEM
Overcharge High High Low High High
Undercharge Low Low High Low Low
Liquid Restriction (Drier) Low Low High High Low
Low Evaporator Airflow Low Low Low Low Low
Dirty Heat Pump High High Low Low High
Low Outside Ambient Temperature Low Low High High Low
Inefficient Compressor Low High High High Low
TXV Feeler Bulb Charge Lost Low Low High High Low
Poorly Insulated Sensing Bulb High High Low Low High
DISCHARGE SUCTION
PRESSURE PRESSURE AMPS
INDICATORS
SUPERHEAT SUBCOOLING
COMPRESSOR
50
19.0 WIRING DIAGRAMS
FIGURE 11
IRING DIAGRAM FOR 2, 3, & 4 TON
W
51
FIGURE 12
IRING DIAGRAM FOR 5 TON
W
52
CM 0610
Loading...