THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2008
TWO-STAGE HEAT PUMP OUTDOOR UNITS
(-)PRL-JEC 16 SEER EQUIPPED WITH THE COMFORT CONTROL
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION,
ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
HE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR
T
DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE
OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE
AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION
WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF
UNAUTH O R I Z ED COMPO N E N T S, ACCE S S O R IE S OR D EV I C ES MAY
ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY
ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS
ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE
USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE.
FAILUR E TO DO SO CAN C AUSE ELECTR ICAL SHOCK RESULTI NG IN
SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR
LEAK TEST. OXY GEN REACT S VIOLENTLY WITH O IL, WHICH CAN
CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR
DEATH.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO
CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL
INJURY OR DEATH.
WARNING
!
TURN OFF ELECTRIC POWER AT THE FUSE BOX OR SERVICE PANEL
BEFORE MAKING ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNECTION MUST BE COMPLETED BEFORE
MAKING LINE VO LTAGE CON NECTI ONS. F AILURE TO DO SO CAN
RESULT IN ELECTRICAL SHO CK, SEVER E PE RSONA L IN JURY O R
DEATH.
3
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing
R-22 evaporators can introduce mineral oil to the R-410A refrigerant forming two different liquids and decreasing oil return to the compressor. This
can result in compressor failure.
CAUTION
!
When coil is installed over a finished ceiling and/or living area, it is
recom m e nd ed tha t a sec o n da ry she e t m et a l con d e ns a te p a n be
constructed and installed under entire unit. Failure to do so can result
in property damage.
CAUTION
!
THE COMPRESSOR HAS AN INTERNAL OVERLOAD PROTECTOR. UNDER
SOME CONDITIONS, IT CAN TAKE UP TO 2 HOURS FOR THIS OVERLOAD
TO RESET. MAKE SURE OVERLOAD HAS HAD TIME TO RESET BEFORE
CONDEMNING THE COMPRESSOR.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING
Solid red light indicates a thermostat call for unit operation is present at
the ICC control. ICC control will attempt to start unit after short cycle timer
expires or when in Active Protection mode will attempt to restart unit prior
to Lockout mode.
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING
Solid red light indicates a thermostat call for unit operation is present at the
ICC. ICC will attempt to start unit after short cycle timer expires or when in
Active Protection mode will attempt to restart unit prior to Lockout mode.
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE
COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22
PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGERANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAMAGE, OR PERSONAL INJURY.
4
WARNING
!
TH E MA N UFACTU R ER’S WARRANTY DOES NOT COVER ANY
DA M A G E OR DEFECT TO THE
AIR CONDITIONER CAUSED BY
THE ATTACHMENT OR USE OF
ANY CO M PO NE N TS . A C CE S SORIE S OR DEVICES (OTHER
THAN THOSE AUTHORIZED BY
THE MANU F A C T U R E R ) INTO,
ONTO OR IN CO N J UN CT I ON
WI T H THE AIR CO N D I TIONER.
YOU SHOULD BE AWARE THAT
THE USE OF UN A U TH O RI Z E D
COMPONENTS, ACCESSORIES
OR DEVICES MAY ADVERSELY
AFFEC T THE OP E RA T IO N
OF THE AIR CONDITIONER AND
MAY AL S O EN D A NG ER LIFE
AND PROPERTY. THE MANUFACTURER DISCL A I MS ANY
RESPO N S IB IL I TY FOR SUCH
LO S S OR I N J URY RE S ULTING
FROM THE USE OF SUC H
UNAUTHORIZED COMPONENTS,
ACCESSORIES OR DEVICES.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
2.0 GENERAL INFORMATION
The (-)PRL-series of heat pump are designed to operate using the Comfort Control
System™ or traditional 24VAC controls. These units are equipped with the Comfort
Control
preferred method of installation is using the Comfort Control
have these components to use the Comfort Control
•
• Air handler or furnace equipped with the Comfort Control
• Comfort Control
If your installation does not meet the above requirements, you must use traditional
24VAC controls.
This installation instruction manual contains complete instructions for installation
and setup with using the Comfort Control
refer to the Engineering Specification Sheets for complete performance data, thermostat, and accessory listings.
The information contained in this manual has been prepared to assist in the proper
installation, operation and maintenance of the air conditioning system. Improper
installation, or installation not made in accordance with these instructions, can
result in unsatisfactory operation and/or dangerous conditions, and can cause the
related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required
to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the
condensing unit specification sheet should be used.
2.1 Checking Product Received
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either
apparent or concealed, should be filed immediately with the shipping company.
Check heat pump model number, electrical characteristics and accessories to
determine if they are correct. Check system components (evaporator coil, condensing unit, evaporator blower, etc.) to make sure they are properly matched.
2.2 Application
Before specifying any heat pump equipment, a survey of the structure and a heat
loss and heat gain calculation must be made. A heat loss calculation involves identifying all surfaces and openings that lose heat to the surrounding air and quantifying that heat loss. A cooling heat gain calculation makes similar measurements and
determines the amount of heat needed to be removed. A heat gain calculation also
calculates the extra heat load caused by sunlight and by humidity removal. These
factors must be considered before selecting a heat pump system to provide year
round comfort. The Air Conditioning Contractors of America (ACCA) J Manual
method of load calculation is one recognized procedure for determining the heating
and cooling load.
The cooling load calculation determines the heat pump size. There are two capacities that enable the equipment to provide comfort. The first is sensible capacity.
Sensible heat is the heat energy measured on the dry bulb thermometer.
The second form of heat is called latent or hidden heat. This is heat held in the
humidity in the air. Removing this heat does not affect a thermometer. However,
removing the heat held in the moisture in the air greatly increases comfort. A properly sized unit removes both forms of heat, producing a comfortable living space. An
oversized system cycles on and off too quickly and does not properly remove
humidity, producing an uncomfortable living space. Select the indoor and outdoor
equipment combination based on the manufacturer's engineering data.
After the proper equipment combination has been selected, satisfying both sensible
and latent requirements, the system must be properly installed. Only then can the
unit provide the comfort the manufacturer built into it.
There are several factors that installers must consider.
• Outdoor unit location• Indoor unit blower speed
• Proper equipment evacuation • Supply and return air duct design and sizing
• Refrigerant charge• System air balancing
• Indoor unit air flow• Diffuser and return air grille location and sizing
2
System™. To take full advantage of the Comfort Control2System™, the
2
System™ :
(-)PRL heat pump with the Comfort Control
2
thermostat
2
ystem™
S
2
or conventional 24VAC controls. Please
2
. Your installation must
2
System™
2
5
SERVICE
FITTINGS
LOW VOLTAGE
CONNECTION
7
/8" [22 mm]
HIGH VOLTAGE
CONNECTION
1
11
/32" [34 mm]
LIQUID LINE
CONNECTION
SERVICE ACCESS
TO ELECTRICAL &
VALVES ALLOW
24" [610 mm]
CLEARANCE
ONE SIDE
2
7
/8" [73 mm] DIA.
ACCESSORY
KNOCKOUTS
VAPOR LINE
CONNECTION
HIGH PRESSURE
CONTROL
MANUAL RESET
(FIELD INSTALLED
ACCESSORY)
Proper sizing and installation of this equipment is critical to achieve optimal performance. Use the information in this Installation Instruction Manual and reference the
applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper airflow are critical to achieve
rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and airflow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
hipping
bs. [kg]
3.0 LOCATING UNIT
3.1 Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a
corrosive environment. This oxidation could shorten the equipment’s useful life.
Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast
areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
•Avoid having lawn sprinkler heads spray directly on the unit cabinet.
•In coastal areas, locate the unit on the side of the building away from the waterfront.
•Shielding provided by a fence or shrubs may give some protection, but cannot
violate minimum airflow and service access clearances.
•Elevating the unit off its slab or base enough to allow air circulation will help
avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect
the unit’s finish.
WARNING
!
DISCO N N EC T A L L PO W ER T O UN I T B E F OR E S T A RT I NG
MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK
RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
•Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.
•Regular cleaning and waxing of the cabinet with a good automobile polish will
provide some protection.
•A good liquid cleaner may be used several times a year to remove matter that
will not wash off with water.
7
Several different types of protective coatings are offered in some areas. These
coatings may provide some benefit, but the effectiveness of such coating materials
cannot be verified by the equipment manufacturer.
3.2 Heat Pump Location
Consult local and national building codes and ordinances for special installation
requirements. Following location information will provide longer life and simplified
servicing of the outdoor heat pump.
NOTE: These units must be installed outdoors. No ductwork can be attached, or
other modifications made, to the discharge grille. Modifications will affect performance or operation.
3.3 Operational Issues
•IMPORTANT: Locate the unit in a manner that will not prevent, impair or com-
promise the performance of other equipment horizontally installed in proximity
to the unit. Maintain all required minimum distances to gas and electric meters,
dryer vents, exhaust and inlet openings. In the absence of National Codes, or
manufacturers’ recommendations, local code recommendations and requirements will take precedence.
•Refrigerant piping and wiring should be properly sized and kept as short as
possible to avoid capacity losses and increased operating costs.
•Locate the unit where water run off will not create a problem with the equipment. Position the unit away from the drip edge of the roof whenever possible.
Units are weatherized, but can be affected by the following:
o Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the heat pump while in operation
can impact fan blade or motor life, and coil damage may occur to a heat
pump if moisture cannot drain from the unit under freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which
generally results in less economical operation.
•Closely follow clearance recommendations on Page 6.
o 24” to the service panel access
o 60” above heat pump fan discharge (unit top) to prevent recirculation
o 6” to heat pump coil grille air inlets
3.4 For Units With Space Limitations
FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Clearances below 6 inches will reduce unit capacity and
efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6inch per unit clearance is recommended, for a total of 12” between two units. Two
combined clearances below 12 inches will reduce capacity and efficiency. Do not
reduce the 60-inch discharge, or 24-inch service, clearances.
3.5 Customer Satisfaction Issues
•The heat pump should be located away from the living, sleeping and recreational spaces of the owner and those spaces on adjoining property.
•To prevent noise transmission, the mounting pad for the outdoor unit should
not be connected to the structure, and should be located sufficient distance
above grade to prevent ground water from entering the unit.
3.6 Unit Mounting
If elevating the heat pump, eithe r on a fla t roof or on a sl ab, obse rve the
following guidelines.
•The base pan provided elevates the heat pump 3/4” above the base pad.
•If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned
to distribute unit weight evenly and prevent noise and vibration (see Figure 2).
NOTE: Do not block drain openings shown in Figure 1.
•If unit must be elevated because of anticipated snow fall, secure unit and elevating stand such that unit and/or stand will not tip over or fall off. Keep in mind
that someone may try to climb on unit.
8
FIGURE 2
ECOMMENDED ELEVATED INSTALLATION
R
3.7 Factory-Preferred Tie-Down Method
IMPORTANT: The Manufacturer approved/recommended method is a guide to securing equipment for wind and seismic loads. Other methods might provide the same
result, but the Manufacturer method is the only one endorsed by Manufacturer for
securing equipment where wind or earthquake damage can occur. Additional information is available in the PTS (Product Technial Support) section of the Manufacturer
website Rheemote.net and an be found as a listing under each outdoor model. If you
do not have access to this site, your Distributor can offer assistance.
4.0 REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with
service valves. Keep tube ends sealed until connection is to be made to prevent
system contamination.
4.1 Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
9
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
4.2 Specifications of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs
must accommodate its higher pressures. It cannot be retrofitted into R-22 heat
pumps.
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its
saturation pressure at 77°F is 224.5 psig.
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane
(HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater
than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A. Manifold sets need to range
up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard.
Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need
to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should
never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
4.3 Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times)
than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999,
R-410A refrigerant cylinders had a dip tube. These cylinders should be kept
upright for equipment charging. Post March 1999 cylinders do not have a dip
tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit. Only manufacturer approved liquid line filter driers can be used. These are Sporlan (CW083S) and Alco
(80K083S) driers. These filter driers are rated for minimum working pressure of
600 psig.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
10
5.0 REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system
must be correctly sized and cleaned or replaced. Care must be exercised that the
expansion device is not plugged. For new and replacement units, a liquid line filter
drier should be installed and refrigerant tubing should be properly sized. Test the oil
for acid. If positive, a suction line filter drier is mandatory.
IMPORTANT: WHEN REPLACING AN R-22 UNIT WITH AN R-410A UNIT,
EITHER REPLACE THE LINE SET OR ENSURE THAT THE EXISTING LINE SET
IS THOROUGHLY CLEANED OF ANY OLD OIL OR DEBRIS.
6.0 INDOOR COIL
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22
evaporators can introduce mineral oil to the R-410A refrigerant forming two different liquids and decreasing oil return to the compressor. This can result in compressor failure.
NOTE: All (-)PRL units must be installed with a TXV Evaporator.
The thermostatic expansion valve is specifically designed to operate with R-410A.
DO NOT use an R-22 TXV or evaporator. The existing evaporator must be
replaced with the factory specified TXV evaporator specifically designed for
R-410A.
6.1 Location
Do not install the indoor coil in the return duct system of a gas or oil furnace.
Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched
toward the drain connection.
CAUTION
!
When coil is in s t a ll e d ov e r a finishe d ceil i n g an d / o r livin g area , it is
recom m e nd ed t h at a s e co n da r y s h e et me t a l c o n de n sa te p a n b e
constr ucted and installed under en tire unit. Failure to do so ca n result
in property damage.
7.0 INTERCONNECTING TUBING
7.1 Vapor and Liquid Lines
Keep all lines sealed until connection is made.
Make connections at the indoor coil first.
Refer to Line Size Information in Tables 4 and 5 for correct size and multipliers to be
used to determine capacity for various vapor line diameters and lengths of run. The
losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for the unit and 15
feet of standard size interconnecting liquid and vapor lines. For different lengths,
adjust the charge as indicated below.
1/4” ± .3 oz. per foot
5/16” ± .4 oz. per foot
3/8” ± .6 oz. per foot
1/2” ± 1.2 oz. per foot
11
7.2 Maximum Length of Lines
The maximum length of interconnecting line is 150 feet. Always use the shortest
length possible with a minimum number of bends. Additional compressor oil is not
required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
7.3 Outdoor Unit Installed Above or Below Indoor Coil
Use the following guidelines when installing the unit:
1. Expansion Valve Coil:
a. The vertical separation cannot exceed the value in Tables 4 and 5.
b. No changes are required for expansion valve coils.
2. It is recommended to use the smallest liquid line size permitted to minimize the
system charge.
3. Tables 4 and 5 may be used for sizing horizontal runs.
7.4 Tubing Installation
Observe the following when installing correctly sized type “L” refrigerant tubing
between the condensing unit and evaporator coil:
•If a portion of the liquid line passes through a hot area where liquid refrigerant
can be heated to form vapor, insulating the liquid line is required.
•Always keep tubing sealed until tubing is in place and connections are to be
made.
•Blow out the liquid and vapor lines with dry nitrogen before connecting to the
outdoor unit and indoor coil. Any debris in the line set will end up plugging the
expansion device.
•As an added precaution, a high quality filter drier is standard on R-410A units.
•Do not allow the vapor line and liquid line to be in contact with each other. This
causes an undesirable heat transfer resulting in capacity loss and increased
power consumption. The vapor line must be insulated.
•If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing
cutters can affect performance dramatically, particularly on small liquid line
sizes.
•For best operation, keep tubing run as short as possible with a minimum number of elbows or bends.
•Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be
housed to prevent damage.
•If tubing is to be run underground, it must be run in a sealed watertight chase.
•Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
•Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
•The vapor line must be insulated to prevent dripping (sweating) and prevent
performance losses. Armaflex and Rubatex are satisfactory insulations for this
purpose. Use 1/2” minimum insulation thickness, additional insulation may be
required for long runs.
•Check Table 4 for the correct vapor line size. Check Table 5 for the correct liquid line size.
12
TABLE 4
SUCTION LINE SIZING – DUAL SPEED HEAT PUMP
Allowed suction line size is determined by total line length on oil return. Liquid size determines total line length and vertical separation.
After selecting allowed suction line size by outdoor unit position, see the liquid line chart for allowable vertical height and total line length.
Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed
until connections are to be made.
•Use type “L” copper refrigeration tubing. Braze the connections with the following alloys:
– copper to copper - 5%
– Silver alloy (no flux)
– copper to steel or brass - 35%
– silver alloy (with flux)
Be certain both refrigerant shutoff valves at the outdoor unit are closed.
•
•Clean the inside of the fittings and outside of the tubing with steel wool or sand
cloth before soldering. Always keep chips, steel wool, dirt, etc., out of the inside
when cleaning.
•Assemble tubing part way into fitting. Apply flux all around the outside of the
tubing and push tubing into stop. This procedure will keep the flux from getting
inside the system.
•Remove the cap and schrader core from service port to protect seals from heat
damage.
•Use an appropriate heatsink material around the copper stub and the service
valves before applying heat.
•IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
•Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen
into a service port and through the tubing while brazing.
•After brazing – use an appropriate heatsink material to cool the joint and
remove any flux residue.
•The service valves are not backseating valves. To open the valves, remove the
valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the
stem. Back out counterclockwise.
•Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a
metal-to-metal seal.
7.6 Leak Testing
•Pressurize line set and coil through service fittings with dry nitrogen to 150
PSIG maximum. Leak test all joints using liquid detergent. If a leak is found,
recover pressure and repair.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR
LEAK TEST. OXY GEN REACT S VIOLENTLY WITH O IL, WHICH CAN
CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR
DEATH.
8.0 DEMAND DEFROST CONTROL
The ICC has a demand defrost algorithm so a separate defrost control is not needed. The ICC monitors the outdoor ambient temperature, outdoor coil temperature,
and the compressor run-time to determine when a defrost cycle is required.
8.1 Defrost Initiation
A defrost will be initiated when the three conditions below are satisfied:
1) The outdoor coil temperature is below 35°F.
2) The compressor has operated for at least 34 minutes with the outdoor coil tem-
perature below 35°F.
3) The defrost algorithm determines a defrost is required.
Additionally, a defrost will be initiated if six hours of accumulated compressor runtime has elapsed without a defrost with the outdoor coil temperature below 35°F.
14
8.2 Defrost Termination
Once a defrost is initiated, the defrost will continue until fourteen minutes has
elapsed or the coil temperature has reached the terminate temperature. The terminate temperature is factory set at 70°F, although the temperature can be changed
to 50°F, 60°F, 70°F or 80°F by relocating dip switches on the ICC.
NOTE: An optional “Noise Abatement Time“ can be selected via the communicating
thermostat or the Service Tool program. When 5 second Noise Abatement is selected, the compressor will shut down for 5 seconds when unit goes into or comes out
of defrost.
8.3 Temperature Sensors
The coil sensor is clipped to the top tube on the outdoor coil at the point fed by the
distribution tubes from the expansion device (short 3/8” dia. tube).
If the ambient sensor fails the defrost control will initiate a defrost every 34 minutes
in heat mode with the coil temperature below 35°F.
8.4 Defrost Test Mode
The defrost test mode is initiated by pressing pushbutton SW2 for 1 second with
the unit running in HP mode. Upon release of pushbutton SW2, the unit will go
into defrost until termination temperature is achieved or 14 minutes has expired.
Pressing SW2 while in Defrost Test Mode will terminate test mode.
8.5 Trouble Shooting Demand Defrost
Set the indoor thermostat select switch to heat and initiate a call for heat.
Press SW2 to put the unit into defrost. If the unit goes into defrost and comes back
out of defrost, the indication is that the control is working properly.
9.0 COMPRESSOR CRANKCASE HEAT (CCH)
CCH is standard on these models due to refrigerant migration during the off cycle
that can result in a noisy start up.
Crankcase Heater Operation:
Supplemental crankcase heat is required to prevent refrigerant migration in systems
with relatively high system refrigerant charges.
The crankcase heater control is integrated into the ICC and is designed for maximum energy savings and uses a 120-minute off delay.
Summary of operation:
• The crankcase heater is off whenever the compressor is running.
• Once the compressor turns off, the crankcase heater control (CCH) begins the
two-hour timer countdown.
• If the compressor stays off for two hours, the CCH turns on the crankcase heater.
All heaters are located on the lower half of the compressor shell. Its purpose is to
drive refrigerant from the compressor shell during long off cycles, thus preventing
damage to the compressor during start-up.
At initial start-up or after extended shutdown periods, make sure the heater is energized for at least 12 hours before the compressor is started. (Disconnect switch on
and wall thermostat off.)
10.0 HARD START COMPONENTS
Factory-installed start components are standard on all models.
15
11.0 HIGH AND LOW PRESSURE CONTROLS
11.0 (HPC AND LPC)
These controls keep the compressor from operating in pressure ranges which can
cause damage to the compressor. Both controls are in the low voltage control circuit.
High pressure control (HPC) is an automatic-reset which opens near 610 PSIG and
loses near 420 PSIG.
c
The low pressure control (LPC) is an automatic-reset which opens near 15 PSIG
and closes near 40 PSIG.
NOTE: HPC and LPC are monitored by the Comfort Control
Section 12.0.
CAUTION
!
THE COMPRESSOR HAS AN INTERNAL OVERLOAD PROTECTOR. UNDER
SOME CONDITIONS, IT CAN TAKE UP TO 2 HOURS FOR THIS OVERLOAD
TO RESET. MAKE SURE OVERLOAD HAS HAD TIME TO RESET BEFORE
CONDEMNING THE COMPRESSOR.
11.1 Evacuation Procedure
Evacuation is the most important part of the entire service procedure. The life and
efficiency of the equipment is dependent upon the thoroughness exercised by the
serviceman when evacuating air and moisture from the system.
Air in the system causes high condensing temperatures and pressure, resulting in
increased power input and non-verifiable performance.
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric
and hydrochloric acids. These attack motor windings and parts, causing breakdown.
After the system has been leak checked and proven sealed, connect the vacuum
pump and evacuate system to 500 microns. The vacuum pump must be connected
to both the high and low sides of the system through adequate connections. Use
the largest size connections available since restrictive service connections may lead
to false readings because of pressure drop through the fittings.
IMPORTANT: Compressors (especially scroll type) should never be used to evacuate the air conditioning system because internal electrical arcing may result in a
damaged or failed compressor.
With thermostat in the “Off” position, turn the power on to the furnace and the heat
pump. Start the heat pump and the furnace with the thermostat. Make sure the
blower is operating.
2
System™. See
16
12.0 CONDENSING UNITS EQUIPPED WITH THE
2
12.0 COMFORT CONTROL
The Comfort Control2is the next generation of the Integrated Compressor Control
(ICC) and is an integral part of the Comfort Control
features:
12.1 Control Description (see Figure 4)
Dual 7-Segment LED
• Displays status and diagnostic codes (See Status and Diagnostic Description)
• Displays diagnostic/fault recall (See Test Mode/Fault Recall)
Red LED (Y1)
• Y1 red LED (solid on) indicates Y1 call from thermostat is present
CAUTION
!
UNIT MAY START SUDDENLY AND WITHOUT WARNING
Solid red light indicates a thermostat call for unit operation is present at
the ICC control. ICC control will attempt to start unit after short cycle timer
expires or when in Active Protection mode will attempt to restart unit prior
to Lockout mode.
Line Voltage Connector
• Line voltage is connected to control board at lug terminals L1 & L2
• Sealed single pole compressor relay switch with optical feedback feature (arc
detection)
LOW PRESSURE CONTROL INPUT
HIGH PRESSURE CONTROL INPUT
MEMORY CARD
LOW VOLT FUSE
THERMOSTAT
CONNECTION (E2)
RED LED (Y1)
AMBIENT DEFROST
CONTROL
COMPRESSOR
CONTROL (K2)
ICC (INTEGRATED
COMPRESSOR CONTROL)
SW2 BUTTON
TEST BUTTON
DEFROST SENSOR
7-SEGMENT LED
17
Thermostat Connector (E2)
Indoor Unit
1
2
C
R
WIRING INFORMATION
Line Voltage
–Field Installed - - - - - –Factory Standard
1
2
R
C
1
2
R
C
Communicating Thermostat
Outdoor Unit
• R – 24VAC from the indoor unit 24VAC transformer (40 VA minimum)
• C – 24VAC Common from the indoor unit 24VAC transformer
• 1-Data: System Communications Line 1
• 2-Data: System Communications Line 2
Low Volt Fuse
• If required replace with 3 A automotive ATC style blade fuse
Low Pressure Control (LPC Input)
• Low-pressure control is factory installed
• Low pressure control is an automatic resetting device
High Pressure Control (HPC Input)
• High-pressure control is factory installed
• High pressure control is an automatic resetting device
Ambient Temperature Sensor (included with all applications)
• Included with all applications
TEST and SW2 Buttons
• TEST and SW2 buttons used to enter Test and Fault Recall Mode
Memory Card
• The memory card stores all unit information.
• The unit information is called shared data.
• The shared data is all the information needed for proper unit operation.
SYSTEM™ CONTROL WIRING
2
COMFORT CONTROL
FIGURE 5
TYPICAL COMFORT CONTROL2SYSTEM™ WIRING DIAGRAM
18
12.2 Comfort Control2Control Wiring
Figure X – Typical Serial Communication Wiring Diagram
Zero (0) displayed The unit is in standby
he four 18AWG low voltage control wires must be installed from the thermostat to the
T
indoor unit and from indoor unit to the outdoor unit. The wire length between the thermostat and indoor unit should not be greater than 100 feet. The wire length between the
indoor unit and outdoor unit should not be greater than 125 feet.
A serial communicating HVAC system consists of:
Serial communicating heat pump or serial communicating condensing unit
Serial communicating air handler or serial communicating furnace
Serial communicating thermostat
IIMMPPOORRTTAANNTT::
tem must be wired using traditional control wiring, reference Section 12.7
Conventional 24VAC Thermostat Control Wiring.
The Comfort Control
NNoottee::
Comfort Control2requires 18 AWG thermostat wire.
NNoottee::
Term dipswitches should be in “ON” position.
If the low voltage control wiring is run in conduit with the power supply, Class I insulation is required. Class II insulation is required if run separate. Low voltage wiring
may be run through the insulated bushing provided in the 7/8 hole in the base
panel, up to and attached to the pigtails from the bottom of the control box. Conduit
can be run to the base panel if desired by removing the insulated bushing.
The serial communicating air handler or serial communicating furnace transformer
is equipped with a 24 volt, 50 VA transformer for proper system operation. See the
wiring diagram in Figure 5 for reference.
If the installed system does not meet these requirements, the sys-
2
requires four (4) control wires for unit operation:
R – 24VAC
C – 24VAC common
1 – Data wire 1
2 – Data wire 2
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
12.3 Comfort Control2ICC Control Operation
IInnssttaallllaattiioonnVVeerriiffiiccaattiioonn
• 24V AC power on R&C must be present at the ICC for it to operate
• Line voltage must be present at the ICC for the compressor and the outdoor fan
to operate
• The ICC displays a “0” for standby mode. Standby mode indicates line voltage
and 24VAC are present at the ICC and there is not a command for unit operation
from the serial communicating thermostat.
• If a command for compressor operation is received by the ICC (first stage/second
stage cooling or first stage/second stage heating), the red Y1 LED will illuminate.
• The ICC has an on/off fan delay of one (1) second for each stage of heating or
cooling.
• The ICC ignores the low pressure control for the first 90 seconds of compressor
operation.
• On heat pumps, the ICC ignores the LPC during the defrost cycle.
• The dual 7-segment LED displays five (5) operational status codes:
• The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling. The dual 7-segment LEDs will flash
“c”, “C”, “h”, or “H” while the short cycle timer is active and a command for unit
operation is received.
Lower case “d” indicates defrost operation (in heating mode)
Flashing lower case c
A command for first stage cooling has been received
Flashing upper case C
A command for second stage cooling has been received
COMFORT CONTROL
Flashing lower case h
A command for first stage heating has been received
Flashing upper case H
A command for second stage heating has been received
20
H
• The 3-minute time delay can be bypassed when a command for compressor
operation is present by pressing the TEST button for 1 second and releasing.
The compressor will begin operation and the dual 7-segment will stop flashing.
3300SSeeccoonnddMMiinnii mmuummRRuunnTTiimmeerr
• The ICC has a built in 30 second minimum unit run time. If a command for compressor operation is received by the ICC and the command is removed, the compressor will continue to operate for 30 seconds. The dual 7-segment LEDs will
flash “c”, “C”, “h”, or “H” while the minimum run timer is active.
• The ICC starts/stops the outdoor fan one (1) second after the start/stop of the
compressor upon a command for compressor operation to minimize current
inrush and/or voltage drop.
12.4 Active Compressor Protection Mode
• The ICC actively protects the compressor from harmful operation during a fault
condition.
• When the ICC detects a condition that could damage the compressor, the ICC will
enter active protection mode and lockout compressor operation
• The condition causing active protection must be resolved before ICC will restart
the system.
• The ICC will display a flashing “L” followed by a flashing 21 when a low pressure
control lockout occurs.
• The ICC addresses low pressure control faults differently depending on the mode
of unit operation (cooling or heating mode).
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
Active Protection – Code L21 – Open low pressure control
CCoooolliinnggMMooddee
• If the LPC opens three (3) times during the same command for cooling operation,
the ICC will lockout the compressor to keep it from continuing to operate and flash
a L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
HHeeaattiinn ggMMooddee
• There are two scenarios that will cause active protection during a LPC trip when
the unit is in the heating mode:
If the LPC opens three (3) times within 120 minutes for the same command for
heating operation, the ICC will lockout the compressor to keep it from continuing
to operate and flash a “L” on the dual 7-segment LEDs followed by a “21”.
If the LPC opens three (3) times for the same command for heating and the outdoor ambient temperature is below 5F, the ICC will lockout the compressor to
keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “21”. Once the outdoor ambient rises above 5F the ICC will clear
active protection automatically.
IIMMPPOORRTTAANNTT::
the outdoor temperature rises above 5F. Wait until the outdoor ambient temperature rises above 5F before performing further diagnostics.
This mode of active protection must be manually reset.
This mode of active protection must be manually reset.
This mode of active protection will automatically deactivate once
Lower case “d” indicates defrost operation (inheatingmode)
3-minute Anti-short Cycle Timer
• If the HPC opens three (3) times during the same command for unit operation, the
ICC will lockout the compressor to keep it from continuing to operate and flash a
L” on the dual 7-segment LEDs followed by a “29”.
Active Protection – Code L29 – Open high pressure control
SYSTEM™ CONTROL WIRING
IIMMPPOORRTTAANNTT::
33))LLoocckkeeddRRoottoorr
• The ICC will display a flashing “L” followed by a flashing “04” when a locked rotor
condition occurs.
If the ICC detects the compressor has run less than 15 seconds for four (4) consecutive starts during the same command for unit operation, the ICC will lockout
the compressor to keep it from continuing to operate and flash a “L” on the dual 7segment LEDs followed by a “04”.
• The ICC will display a flashing “L” followed by a flashing “06” when an open start
circuit condition occurs.
Active Protection – Code L6 – Compressor open start circuit
If the ICC detects current in the run circuit without current present in the start circuit, , the ICC will lockout the compressor to keep it from continuing to operate
and flash a “L” on the dual 7-segment LEDs followed by a “06”.
IIMMPPOORRTTAANNTT::
66))OOppeennRRuunnCCii rrccuuiittLLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “07” when an open start
circuit condition occurs.
This mode of active protection must be manually reset.
Active Protection – Code L7 – Compressor open run circuit
If the ICC detects current in the start circuit without current present in the run cir-
Lower case “t”
Fault Recall Mode – the top and bottomsegments illuminated
cuit, , the ICC will lockout the compressor to keep it from continuing to operate
and flash a “L” on the dual 7-segment LEDs followed by a “07”.
• Enter TEST mode by pressing the TEST button with an insulated probe for one
(1) second and release.
• The TEST mode causes the ICC to do the following
1) Resets the ICC from any active protection lockout mode
2) Resets the 3-minute anti-short cycle timer
3) Energizes the unit without a command for unit operation
• If the 3-minute anti-short cycle timer or 30 second minimum run timer is active (a
flashing “c”, “C”, “h”, or “H” is displayed on the dual 7-segment LEDs) and a command for unit operation is present, TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
2) The compressor will start and the outdoor fan will operate
3) The display will change to a steady “c”, “C”, “h”, or “H” to show the current
command for unit operation.
Note: If a command for unit operation is present at the end of TEST mode, the
unit will continue to operate.
• If no command for unit operation is present, TEST mode causes
1) A steady “t” appears on the dual 7-segment LEDs
2) The compressor will start
3) The compressor will turn off after 5-seconds.
Note: Entering TEST mode without a command for unit operation will cause the
compressor to run 5-seconds.
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) seconds with insulated probes and release.
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the
history has been cleared.
Fault history is cleared with the top and bottom LED
segments flash
NOTE: The memory card for the unit has specific shared data for this unit. The
memory card is attached to the control box with a tether. The tether has an identification tag that can be used to identify the memory card. For the system data faults
d1 through d8 reference the label on the memory card tether.
FFAAUULL TTRREECCAALLLL
mode after displaying stored
SYSTEM™ CONTROL WIRING
2
COMFORT CONTROL
24
12.6
7-Segment
LEDs Display
Code DiagnosticDescription
Status/PossibleCause – Troubleshooting
Information0 – StandbyNo command for unit operation
Normal operation
c - FirstStage CoolingUnit has received a command for first stagecooling
Normal operation
7-Segment
LEDs Display
Code DiagnosticDescription
Status/PossibleCause – Troubleshooting
Information0 – StandbyNo command for unit operation
Normal operation
c - FirstStage CoolingUnit has received a command for first stagecooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimumrun timer (30 seconds) active
•The unit hasreceived acommand for first stagecooling during an activeanti-shortcycletimeror minimumrun timer.
•Wait until unit timer has expiredorpressthe TEST button to reset timer.
7-Segment
LEDs Display
Code DiagnosticDescription
Status/PossibleCause – Troubleshooting
Information0 – StandbyNo command for unit operation
Normal operation
c - FirstStage CoolingUnit has received a command for first stagecooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimumrun timer (30 seconds) active
•The unit hasreceived acommand for first stagecooling during an activeanti-shortcycletimeror minimumrun timer.
•Wait until unit timer has expiredorpressthe TEST button to reset timer.
C - Second StageCooling Unit has received a command for second stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or Minimumrun timer (30 seconds) active
•Theunit hasreceived acommandfor second stage coolingduring an active anti-short cycletimer or minimum run timer.
•Wait unit timer has expiredor press theTEST
7-Segment
LEDs Display
Code DiagnosticDescription
Status/PossibleCause – Troubleshooting
Information0 – StandbyNo command for unit operation
Normal operation
c - FirstStage CoolingUnit has received a command for first stagecooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or Minimumrun timer (30 seconds) active
•The unit hasreceived acommand for first stagecooling during an activeanti-shortcycletimeror minimumrun timer.
•Wait until unit timer has expiredorpressthe TEST button to reset timer.
C - Second StageCooling Unit has received a command for second stage cooling
Normal operation
7-Segment
LEDs Display
Code DiagnosticDescription
Status/PossibleCause – Troubleshooting
Information0 – StandbyNo command for unit operation
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips haveoccurred and the average run time for each trip is less than15seconds
•Bad run capacitor
•Low line voltage
•Excessive refrigerant in compressor
•Seized bearings in compressor
05 – OpenCircuit (Compressor willnotRun)
•The ICC has received a command for unit operationbutno current is present inthe startand runcircuits.
•TheICCwillattempt to restart the unit every five (5) minutes for four (4) attempts. After that, theICC will attempt a restart everytwenty (20) minutes for up to four(4) hours.
•Check for damaged, miswired, orwrong runcapacitor
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips haveoccurred and the average run time for each trip is less than15seconds
•Bad run capacitor
•Low line voltage
•Excessive refrigerant in compressor
•Seized bearings in compressor
05 – OpenCircuit (Compressor willnotRun)
•The ICC has received a command for unit operationbutno current is present inthe startand runcircuits.
•TheICCwillattempt to restart the unit every five (5) minutes for four (4) attempts. After that, theICC will attempt a restart everytwenty (20) minutes for up to four(4) hours.
•Check for damaged, miswired, orwrong runcapacitor
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips haveoccurred and the average run time for each trip is less than15seconds
•Bad run capacitor
•Low line voltage
•Excessive refrigerant in compressor
•Seized bearings in compressor
05 – OpenCircuit (Compressor willnotRun)
•The ICC has received a command for unit operationbutno current is present inthe startand runcircuits.
•TheICCwillattempt to restart the unit every five (5) minutes for four (4) attempts. After that, theICC will attempt a restart everytwenty (20) minutes for up to four(4) hours.
•Check for damaged, miswired, orwrong runcapacitor
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips haveoccurred and the average run time for each trip is less than15seconds
•Bad run capacitor
•Low line voltage
•Excessive refrigerant in compressor
•Seized bearings in compressor
05 – OpenCircuit (Compressor willnotRun)
•The ICC has received a command for unit operationbutno current is present inthe startand runcircuits.
•TheICCwillattempt to restart the unit every five (5) minutes for four (4) attempts. After that, theICC will attempt a restart everytwenty (20) minutes for up to four(4) hours.
•Check for damaged, miswired, orwrong runcapacitor
L4 – Locked Rotor The ICC detects four (4) consecutive protector trips haveoccurred and the average run time for each trip is less than15seconds
•Bad run capacitor
•Low line voltage
•Excessive refrigerant in compressor
•Seized bearings in compressor
05 – OpenCircuit (Compressor willnotRun)
•The ICC has received a command for unit operationbutno current is present inthe startand runcircuits.
•TheICCwillattempt to restart the unit every five (5) minutes for four (4) attempts. After that, theICC will attempt a restart everytwenty (20) minutes for up to four(4) hours.
•Check for damaged, miswired, orwrong runcapacitor
09 – Low SecondaryVoltsThe secondaryvoltage at R and Cisbelow 18VAC
•Control transformer overloaded
•Low line voltage
LEDs Display
Code
Diagnostic Description
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Status/Possible Cause – Troubleshooting
Information
• Motor protector open
26
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
02 – High Side Fault
Compressor limit has opened four (4) times
within a call for operation
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
05 – Open circuit (Compressor will not
Run)
• The ICC has had a protector trip for longer
than 4 hours
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
06 – Compressor Open Start Circuit
The ICC detects current in the Run
circuit but not in the Start circuit of the
compressor four (4) times in one
compressor call
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
07 – Compressor Open Run Circuit
The ICC detects current in the Start
circuit but not in the Run circuit of the
compressor four (4) times in one
compressor call
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Low refrigerant charge
• Air ducts have substantial leakage
• Dirty indoor air filter
• Dirty outdoor coil
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
• Check thermostat wire connections (R, C, 1, &
2)
• Check thermostat location in zone (too close to
discharge grill)
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
• Seized bearings in compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong
run capacitor
• Check for broken wires, loose connectors,
or miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong
run capacitor
• Check for broken wires, loose connectors,
or miswired compressor
• Check compressor windings for continuity
• Control transformer overloaded
• Low line voltage
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor o
peration
•
Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•
Dirty indoor coil or filter (cooling mode)
•
Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
21 – LowPressureControl Open T
he ICCdetectsthe LPC is open. Note: The low pressure control is ignoredf
or the first 90seconds of compressor
operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•
Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
2
1 –Low Pressure ControlOpen
T
he ICCdetectsthe LPC is open. Note: The low pressure control is ignoredf
or the first 90seconds of compressor
operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor o
peration
•
Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•
Dirty indoor coil or filter (cooling mode)
•
Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor o
peration
•
Unit has low refrigerant charge
•
Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•
Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
21 – LowPressureControl Open T
he ICCdetectsthe LPC is open. Note: The low pressure control is ignoredf
or the first 90seconds of compressor
operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•
Outdoor coil is frozen(heating mode)
•
Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The 3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
2
1 –Low Pressure ControlOpen The ICC detects the LPC isopen. N
ote: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•
Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The 3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
83 – Condenser Coil Temperature Fault The sensordetects an abnormally low orhigh coil temperature
•Replace the sensor
21 – LowPressureControl Open The ICC detects the LPC isopen. N
ote: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•
Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The 3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
83 – Condenser Coil Temperature Fault The sensordetects an abnormally low orhigh coil temperature
•Replace the sensor
84 – OutdoorAmbientTemperatureFaultThe sensordetects an abnormally low orhigh outdoor ambienttemperature
•Checkunit placement–If theoutdoor unit is ina high temperaturearea, wait until the ambient temperaturedrops and check sensor reading.
21 – LowPressureControl Open T
he ICCdetectsthe LPC is open. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
83 – Condenser Coil Temperature Fault The sensordetects an abnormally low orhigh coil temperature
•Replace the sensor
84 – OutdoorAmbientTemperatureFaultThe sensordetects an abnormally low orhigh outdoor ambienttemperature
•Checkunit placement–If theoutdoor unit is ina high temperaturearea, wait until the ambient temperaturedrops and check sensor reading.
•Replace thesensor.
90 – Communication FaultThe ICC detects and internal fault condition
•Replace the ICC.
21 – LowPressureControl Open The ICC detects the LPC isopen. Note: The low pressure control is ignoredfor the first 90seconds ofcompressor operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
2
1 –Low Pressure ControlOpen The ICC detects the LPC isopen. N
ote: The low pressure control is ignored
f
or the first 90seconds of compressor
operation
•Unit has low refrigerant charge
•Indoor coil isfrozen(coolingmode)
•Dirty indoor coil or filter (cooling mode)
•Indoorblower is notrunning (coolingmode)
•Outdoor coil is frozen(heating mode)
•Outdoor fan isnotrunning(heating mode)
•Expansion valve isnotoperating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
TheICC has locked out thecompressordue tothree(3) consecutive LPCtrips onthe samecommand for unit operation
27 – Low Line Voltageor No LineVoltageFault
•Check incoming line voltagetothe disconnect and unit
•Check wiring connections
28– High Line Voltage Fault
•Check line voltage
29– High Pressure ControlOpen TheICC detects the HPC isopen
•Outdoor coil is dirty (coolingmode)
•Outdoor fanis not running (coolingmode)
•Dirty indoor coil or filter (heating mode)
•Indoorblower is notrunning (heating mode)
•Liquid line restriction
•Excessive refrigerantcharge
FLASHING
L29 – Active Protection High PressureControl Trip
TheICC has locked out thecompressordue tothree (3) consecutiveHPC trips onthe samecommand for unit operation
30 –Fuse Open The ICCdetects the on-board fuseis open
•The3-amp fuse on the ICCis open.
•Lowvoltage wiring atR andCis damaged or
miswired.
Dual 7-Segment
LEDs Display
Code
1 – Low Pressure Control Open
2
he ICC detects the LPC is open.
T
ote: The low pressure control is ignored
N
or the first 90 seconds of compressor
f
peration
o
21 – Active ProtectionLow Pressure
L
Control Trip
Diagnostic Description
27 – Low Line Voltage or No Line Voltage
Fault
28 – High Line Voltage Fault• Check line voltage
29 – High Pressure Control Open
The ICC detects the HPC is open
L29 – Active Protection High Pressure
Control Trip
30 – Fuse Open
The ICC detects the on-board fuse is open
80 – Low Air Flow
The ICC detects that the indoor unit is
not providing the minimum airflow
requirements.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
93 – Internal Control Fault
The control is not functioning
properly.
Status/Possible Cause – Troubleshooting
Information
Unit has low refrigerant charge
•
Indoor coil is frozen (cooling mode)
•
Dirty indoor coil or filter (cooling mode)
•
Indoor blower is not running (cooling mode)
•
Outdoor coil is frozen (heating mode)
•
Expansion valve is not operating correctly
•
PC has opened 3 times in the same cooling
L
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 21
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
LPC has opened 3 times in the same cooling
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 29
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
• Misapplied/wrong indoor air mover –
replace with properly sized unit.
• Replace the sensor
• Check sensor is installed correctly on control
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
•Misapplied/wrong indoor air mover – replacewith properly sized air handler/furnace.
LEDs Display
Code
Diagnostic Description
1 – No Shared Data• Replace memory card with correct system
d
Status/Possible Cause – Troubleshooting
Information
information.
3 – Airflow CFM Mismatch
d
he indoor air mover (air
T
andler/furnace) cannot supply the
h
required airflow for proper system
operation
d4 – (Device) Memory Card Invalid for
Device
The data in the memory card inserted
into the control board does not match
the data in the control.
d8 – Old Shared Data
System data is obsolete
CONVENTIONAL THERMOSTAT WIRING
28
Misapplied/wrong indoor air mover –
•
replace with properly sized air
handler/furnace.
• Check memory card to ensure it matches
device
• Check if memory card is present
• If system will not operate, order new
memory card to update system
information.
12.7 Conventional 24VAC Thermostat Control Wiring
The (-)PRL series of heat pumps allow the installer to use conventional 24VAC control wiring and a conventional thermostat for proper unit operation.
IIMMPPOORRTTAANNTT::
Comfort Control
This diagnostic information is not available when the (-)PRL unit is using a conventional thermostat. Reference section 12.2 Comfort Control
Wiring.
Thermostat control wiring requires a minimum of six (6) wires for proper unit operation:
Optional wiring:
L Terminal Output
• Flash 1 – Compressor running extremely long run cycle or low pressure
• Flash 2 – High pressure control trip
• Flash 3 – Unit short cycling
• Flash 4 – Locked rotor
• Flash 5 – Compressor will not run, open circuit
• Flash 6 – Open start circuit
• Flash 7 – Open run circuit
• Flash 8 – Control mis-operation
• Flash 9 – Low control voltage
When the L terminal from the outdoor unit is connected to a conventional thermostat that is L terminal compatible, the thermostat display will flash the above codes.
If the low voltage control wiring is run in conduit with the power supply, Class I insulation is required. Class II insulation is required if run separate. Low voltage wiring
may be run through the insulated bushing provided in the 7/8 hole in the base
panel, up to and attached to the pigtails from the bottom of the control box. Conduit
can be run to the base panel if desired by removing the insulated bushing.
The preferred method of unit installation and operation is by the
2
System™, which allows access to the fault history of the system.
2
System™ Control
R – 24VAC
C – 24VAC common
Y1 – First stage operation
Y2 – Second stage operation
B – Heat pump operation
D – Defrost
L – ICC fault information
B
W2
W1
B
C
G
(
-)HPL Air
Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
W
IRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y
2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
B
R
W
/R
PR
*
B
W2
W1
B
C
G
(-)HPL Air
H
andler
Y
1
E/W1
Typical Two-Stage Thermostat
(-)PRL
H
eat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
F
actory Standard
-
ODD
R
Y1
Y2
G
W
2
R
Y1
C
L
D
Y
Y
/BL
B
L
R
BR
W/R
P
R
Humidistat
*
B
W2
W1
B
C
G
(-)HPL Air
Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
BR
W/R
PR
DHM
*
B
W2
W1
B
C
G
(-)HPL Air
Handler
Y1
E/W1
Typical Two-Stage Thermostat
(-)PRL
Heat Pump
Outdoor
Unit
Y2
C
R
B
Y2
Field Installed
Line Voltage
-
WIRING INFORMATION
Factory Standard
-
ODD
R
Y1
Y2
G
W2
R
Y1
C
L
D
Y
Y/BL
BL
R
BR
W/R
PR
DHM
L
*
A thermostat and a 24-volt, 40VA minimum transformer are required for the control
circuit of the condensing unit. The furnace or the air handler transformer may be
used if sufficient. See the wiring diagram for reference. Use Table 6 to size the 24volt control wirings.
TABLE 6
IELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
F
SOLID COPPER WIRE - AWG.
3.0161412101010
2
.5161412121010
2.0181614121210
50100150200250300
Thermostat Load - Amps
(1) Wire length equals twice the run distance.
OTE: Do not use control wiring smaller than No. 18 AWG between thermostat and outdoor unit.
The following figures show the typical wiring diagrams with (-)HPL air handler and (-)PRL heat
pump. Cooling and heat pump airflows may need to be adjusted for homeowner comfort once
the system is operational.
FIGURE 6
TYPICAL 2-STAGE THERMOSTAT: HEAT PUMP WITH ELECTRIC
HEAT
FIGURE 8
TYPICAL TWO-STAGE THERMOSTAT: (-)PRL HEAT PUMP WITH
ELECTRIC HEAT USING A TWO-STAGE THERMOSTAT WITH
DEHUMIDIFICATION*
FIGURE 7
TYPICAL TWO-STAGE THERMOSTAT: (-)PRL HEAT PUMP WITH
ELECTRIC HEAT USING A HUMIDISTAT FOR DEHUMIDIFICATION*.
FIGURE 9
(-)PRL HEAT PUMP WITH ELECTRIC HEAT USING A TWO-STAGE
THERMOSTAT WITH DEHUMIDIFICATION* AND A MALFUNCTION
LIGHT
K – BLACK G – GREENPR – PURPLE Y – YELLOW
B
R – BROWN GY – GRAYR – RED
B
L – BLUEO – ORANGE W – WHITE
B
*See Section 5.11 for proper DIP switch selection.
WIRE COLOR CODE
CONVENTIONAL THERMOSTAT WIRING
*If maximum outlet temperature rise is desired, it is recommended that W1 and W2 be jumpered together.
29
– 24VAC
1 – First stage operation
– Heat pump operation
SECTION 13.4 HERE!!!!
12.9 ICC Control Operation with Conventional Thermostat Wiring
• 24V AC power on R&C must be present at the ICC for it to operate
• Line voltage must be present at the ICC for the compressor and the outdoor fan
to operate
• The ICC displays a “0” for standby mode. Standby mode indicates line voltage
and 24VAC are present at the ICC and there is not a call for unit operation from
the thermostat.
• If a call for compressor operation is received by the ICC (first stage/second stage
cooling or first stage/second stage heating), the red Y1 LED will illuminate.
• The ICC has an on/off fan delay of one (1) second for each stage of heating or
cooling.
• The ICC ignores the lower pressure control for the first 90 seconds of compressor
operation.
• On heat pumps, the ICC ignores the LPC during the defrost cycle.
• The dual 7-segment LED displays five (5) operational status codes:
• The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling. The dual 7-segment LEDs will flash
“c”, “C”, “h”, or “H” while the short cycle timer is active and a call for unit operation
is received.
CONVENTIONAL THERMOSTAT WIRING
Flashing lower case c
A call for first stage cooling has been received
Flashing upper case C
A call for second stage cooling has be received
Flashing lower case h
A call for first stage heating has been received
Flashing upper case h
A call for second stage heating has been received
H
• The 3-minute time delay can be bypassed when a call for compressor operation is
present by pressing the TEST button for 1 second and releasing. The compressor will begin operation and the dual 7-segment will stop flashing.
3300SSeeccoonnddMMiinnii mmuummRRuunnTTiimmeerr
• The ICC has a built in 30 second minimum unit run time. If a call for compressor
operation is received by the ICC and the call is removed, the compressor will continue to operate for 30 seconds. The dual 7-segment LEDs will flash “c”, “C”, “h”,
or “H” while the minimum run timer is active.
• The ICC starts/stops the outdoor fan one (1) second after the start/stop of the
compressor upon a call for compressor operation to minimize current inrush
and/or voltage drop.
31
12.10 Active Compressor Protection Mode
• The ICC actively protects the compressor from harmful operation during a fault
condition.
• When the ICC detects a condition that could damage the compressor, the ICC will
enter active protection mode and lockout compressor operation
• The condition causing active protection must be resolved then the ICC can be
reset to restart the system.
• The ICC will display a flashing “L” followed by a flashing 21 when a low pressure
control lockout occurs.
• The ICC addresses low pressure control faults differently depending on the mode
of unit operation (cooling or heating mode).
CONVENTIONAL THERMOSTAT WIRING
Active Protection – Code L21 – Open low pressure control
CCoooolliinnggMMooddee
• If the LPC opens three (3) times during the same call for cooling operation, the
ICC will lockout the compressor to keep it from continuing to operate and flash a
L” on the dual 7-segment LEDs followed by a “21”.
IIMMPPOORRTTAANNTT::
HHeeaattiinn ggMMooddee
• There are two scenarios that will cause active protection during a LPC trip when
the unit is in the heating mode:
AAccttiivveePPrrootteeccttiioonnww ii tthhhhaarrddlloocckkoouutt::
If the LPC opens three (3) times within 120 minutes for the same call for heating
operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a “L” on the dual 7-segment LEDs followed by a “21”.
If the LPC opens three (3) times for the same call for heating and the outdoor
ambient temperature is below 5F, the ICC will lockout the compressor to keep it
from continuing to operate and flash a “L” on the dual 7-segment LEDs followed
by a “21”. Once the outdoor ambient rises above 5F the ICC will clear active protection automatically.
IIMMPPOORRTTAANNTT::
the outdoor temperature rises above 5F. Wait until the outdoor ambient temperature rises above 5F before performing further diagnostics.
• If the HPC opens three (3) times during the same call for unit operation, the ICC
will lockout the compressor to keep it from continuing to operate and flash a L” on
the dual 7-segment LEDs followed by a “29”.
This mode of active protection must be manually reset.
This mode of active protection must be manually reset.
This mode of active protection will automatically deactivate once
32
Active Protection – Code L29 – Open high pressure control
IIMMPPOORRTTAANNTT::
33))LLoocckkeeddRRoottoorr
• The ICC will display a flashing “L” followed by a flashing “04” when a locked rotor
condition occurs.
This mode of active protection must be manually reset.
CONVENTIONAL THERMOSTAT WIRING
Active Protection – Code L4 – Locked rotor
If the ICC detects the compressor has run less than 15 seconds for four (4) consecutive starts during the same call for unit operation, the ICC will lockout the
compressor to keep it from continuing to operate and flash a “L” on the dual 7segment LEDs followed by a “04”.
• The ICC will display a flashing “L” followed by a flashing “06” when an open start
circuit condition occurs.
This mode of active protection must be manually reset.
Active Protection – Code L6 – Compressor open start circuit
If the ICC detects current in the run circuit without current present in the start circuit, , the ICC will lockout the compressor to keep it from continuing to operate
and flash a “L” on the dual 7-segment LEDs followed by a “06”.
IIMMPPOORRTTAANNTT::
55))OOppeennRRuunnCCiirrccuuiittLLoocckkoouutt
• The ICC will display a flashing “L” followed by a flashing “07” when an open start
circuit condition occurs.
If the ICC detects current in the start circuit without current present in the run circuit, , the ICC will lockout the compressor to keep it from continuing to operate
and flash a “L” on the dual 7-segment LEDs followed by a “07”.
This mode of active protection must be manually reset.
Active Protection – Code L7 – Compressor open run circuit
33
IIMMPPOORRTTAANNTT::
with insulated probes for one (1) second and release.
segment LEDs will illuminate.
Fault Recall Mode – the top and bottomsegments illuminated
• Enter TEST mode by pressing the TEST button with an insulated probe for one
(1) second and release.
• The TEST mode causes the ICC to do the following
1) Resets the ICC from any active protection lockout mode
2) Resets the 3-minute anti-short cycle timer
3) Energizes the unit without a call for unit operation
• If the 3-minute anti-short cycle timer or 30 second minimum run timer is active (a
flashing “c”, “C”, “h”, or “H” is displayed on the dual 7-segment LEDs) and a call
for unit operation is present, TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display
CONVENTIONAL THERMOSTAT WIRING
Lower case “t”
2) The compressor will start
3) The display will change to a steady “c”, “C”, “h”, or “H” to show the current call
for unit operation.
Note: If a call for unit operation is present at the end of TEST mode will cause the
unit to continue to operate.
• If no call for unit operation is present, TEST mode causes
1) A steady “t” appears on the dual 7-segment LEDs
2) The compressor will start
3) The compressor will turn off after 5-seconds.
Note: Entering TEST mode without a call for unit operation will cause the compressor to run 5-seconds.
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) seconds with insulated probes and release.
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the
history has been cleared.
The ICC stores the previous six history faults. The complete stored
Fault history is cleared with the top and bottom LED
segments flash
FFAAUULL TTRREECCAALLLL
mode after displaying stored
CONVENTIONAL THERMOSTAT WIRING
35
13.0 ELECTRICAL WIRING
NOTE: Check all wiring to be sure connections are securely fastened, electrically
isolated from each other and that the unit is properly grounded.
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and
any applicable local code.
13.1 Power Wiring
It is important that proper electrical power from a commercial utility is available at
the condensing unit contactor. Voltage ranges for operation are shown in Table 7.
Install a branch circuit disconnect within sight of the unit and of adequate size to
handle the starting current (see Table 1).
Power wiring must be run in a rain-tight conduit. Conduit must be run through the
connector panel below the access cover (see Figure 1) and attached to the bottom
of the control box.
Connect power wiring to line voltage lugs located in outdoor condensing unit electrical box. (See wiring diagram attached to unit access panel.)
Check all electrical connections, including factory wiring within the unit and make
sure all connections are tight.
DO NOT connect aluminum field wire to the contactor terminals.
TABLE 7
OLTAGE RANGES (60 HZ)
V
Nameplate VoltageMaximum Load Design Conditions for
208/230 (1 Phase)197 - 253
Operating Voltage Range at Copeland
Compressors
13.2 Grounding
A grounding lug is provided near the contactor for a ground wire.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO
CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL
INJURY OR DEATH.
13.3 Control Wiring
If the low voltage control wiring is run in conduit with the power supply, Class I insulation is required. Class II insulation is required if run separate. Low voltage wiring
may be run through the insulated bushing provided in the 7/8 hole in the base
panel, up to and attached to the pigtails from the bottom of the control box. Conduit
can be run to the base panel if desired by removing the insulated bushing.
A thermostat and a 24 volt, 40 VA minimum transformer are required for the control
circuit of the condensing unit. The furnace or the air handler transformer may be
used if sufficient. See the wiring diagram for reference. Use Table 7 to size the 24
volt control wiring.
14.0 START-UP AND PERFORMANCE
Even though the unit is factory charged with Refrigerant-410A, the charge must be
checked to the charge table attached to the service panel and adjusted, if required.
Allow a minimum of 5 minutes of run time before analyzing charge.
At initial start-up or after extended shutdown periods, make sure the heater is energized for at least 12 hours before the compressor is started. (Disconnect switch on
and wall thermostat off.) Connect the communicating system per Figure 5. Once all
devices are connected, power up the line and low voltage to the system. When all
devices are powered, the thermostat should detect the indoor and outdoor units
within 45 seconds.
36
15.0 CHECKING AIRFLOW
The air distribution system has the greatest effect on airflow. The duct system is
totally controlled by the contractor. For this reason, the contractor should use only
industry-recognized procedures.
The correct air quantity is critical to air conditioning systems. Proper operation, efficiency, compressor life, and humidity control depend on the correct balance
between indoor load and outdoor unit capacity. Excessive indoor airflow increases
the possibility of high humidity problems. Low indoor airflow reduces total capacity,
and causes coil icing. Serious harm can be done to the compressor by low airflow,
such as that caused by refrigerant flooding.
Heat pump systems require a specified airflow. Each ton of cooling requires
between 340 and 450 cubic feet of air per minute (CFM).
Duct design and construction should be carefully done. System performance can be
lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and
positioned to deliver treated air along the perimeter of the space. If they are too
small for their intended airflow, they become noisy. If they are not located properly,
they cause drafts. Return air grilles must be properly sized to carry air back to the
blower. If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space.
These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system.
Electric resistance heaters can use
CFM =
Gas furnaces can use
CFM =
An air velocity meter or airflow hood can give a more accurate reading of the system CFM’s.
volts x amps x 3.414
1.08 x temp rise
BTUH
∆T x 1.08
16.0 CHECKING REFRIGERANT CHARGE
Charge for all systems should be checked against the Charging Chart inside the
access panel cover. Before using the chart, the indoor conditions must be within
2°F of desired comfort conditions and system must be run until operating conditions
stabilize (15 min. to 30 min.)
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE
COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
IMPORTANT: Use industry-approved charging methods to ensure proper system
charge.
NOTE: The optimum refrigerant charge for the (-)PRL-0-36 & (-)PRL-048 is affected
more by the application than the other (-)PRL models due to the relationship
between the indoor and outdoor coil volumes. Therefore, multiple charging charts
have been developed to assist the field technician in optimizing the charge for the
application on these two models. Refer to the “Specific Charging Instructions” note
shown on the charging chart attached to the unit and choose the appropriate chart
for the specific application being installed or serviced. New installations utilizing a
downflow or horizontal right air-handler or a coil installed on a gas furnace may
require removal of refrigerant since the factory charge could result in an overcharged condition if the line set is relatively short.
16.1 Charging units with R-410A Refrigerant
Charge for all systems should be checked against the Charging Chart inside the
access panel cover.
37
IMPORTANT: Do not operate the compressor without charge in system.
Addition of R-410A will raise pressures (vapor, liquid and discharge).
If adding R-410A raises both vapor pressure and temperature, the unit is overcharged.
IMPORTANT: Use industry-approved charging methods to ensure proper system
charge.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22
PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGERANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAMAGE, OR PERSONAL INJURY.
16.2 Charging By Liquid Pressure
Liquid pressure method is used for charging systems in the cooling and heating
mode. The service port on the liquid service valve (small valve) and suction (large
valve) is used for this purpose.
Verify that the outdoor unit is running and the indoor air mover is delivering the
maximum airflow for this system size. Read and record the outdoor ambient temperature. Read and record the liquid and suction pressures at the ports on the liquid
and suction valves. If refrigerant lines are sized using the nameplate charge, the
correct liquid pressure is found at the intersection of the suction pressure and the
outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
16.3 Charging By Weight
For a new installation, evacuation of interconnecting tubing and indoor coil is adequate; otherwise, evacuate the entire system. Use the factory charge shown in
Table 1 of these instructions or unit data plate. Note that charge value includes
charge required for 15 ft. of standard size interconnecting liquid line. Calculate actual charge required with installed liquid line size and length using:
With an accurate scale (+/– 1 oz.) or volumetric charging device, adjust charge difference between that shown on the unit data plate and that calculated for the new
system installation. If the entire system has been evacuated, add the total calculated charge.
NOTE: The optimum refrigerant charge for the (-)PRL-036 & (-)PRL-048 is affected
more by the application than other (-)PRL models due to the relationship between
the indoor and outdoor volumes. Therefore, if charging by weight on these two
models, the net refrigerant charge must be reduced if the application utilizes an airhandler in the downflow or horizontal right configuration or in dual fuel applications
(coil installed on a gas furnace). The recommended net charge reduction for downflow/horizontal right air-handler and dual fuel applications is shown on the applicable charging chart attached to the (-)PRL-036 & (-)PRL-048. It is highly recommended that the refrigerant charge also be checked and adjusted based on the appropriate charging chart once the unit is put into operation.
16.4 Final Leak Testing
After the unit has been properly evacuated and charged, a halogen leak detector
should be used to detect leaks in the system. All piping within the condensing unit,
evaporator, and interconnecting tubing should be checked for leaks. If a leak is
detected, the refrigerant should be recovered before repairing the leak. The Clean
Air Act prohibits releasing refrigerant into the atmosphere.
38
WARNING
!
TURN OFF ELECTRIC POWER AT
THE FU SE BOX OR SE R V IC E
PA N E L BEF O R E MAKI N G ANY
ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNECTION M US T BE CO MP L ET ED
BEFORE MAKING LINE VOLTAGE
CONNECTIONS. FAILURE TO DO
SO CAN RESULT IN ELECTRICAL
SHOCK , S E V ER E P ER SO N AL
INJURY OR DEATH.
17.0 ACCESSORIES
17.1 Dual Fuel Kit Model (Part No. RXME-A01)
This kit is required if this unit is installed in a dual fuel application.
17.2 Remote Outdoor Temperature Model (Part No. 47-102709-03)
This is a kit that has a longer remote sensor that can be installed away from the
outdoor unit for better thermostat temperature display.
17.3 RXME-A02 Communicating 2 Wire Kit
This kit will allow the outdoor unit to communicate to the system with only 2 wires.
18.0 TROUBLESHOOTING
IMPORTANT: The JEC series units with the ICC (Integrated Compressor Control)
provide status and diagnostic information that greatly enhances the ability to quickly
diagnose system faults. Use the following troubleshooting guides as another tool in
system diagnostics.
NOTE: In diagnosing common faults in the cooling system, develop a logical
thought pattern as used by experienced technicians. The charts which follow are
not intended to be an answer to all problems but only to guide the technician’s
trouble shooting. Through a series of yes and no answers, follow the logical path to
a likely conclusion.
A novice technician should use these charts like a road map. Remember that the
chart should clarify a logical path to the solution.
18.1 Serial Communicating System Initial Startup
Connect the system.
There are four wires that need to be connected to each unit:
These wires need to be connected to each device thermostat, indoor air handler
and outdoor unit (heat pump or AC).
If the communications wires are wired backwards at any point the green LED (D52)
will always be on. If this happens check the wires at each point to ensure they are
not reversed.
Once all devices are connected power up the line and low voltage to the system.
When all devices are powered the thermostat should detect the indoor and outdoor
units within 45 seconds. The air handler and outdoor units have a set of bias dipswitches set at a factory default to the ON position. These dipswitches are for future
use DO NOT CHANGE DIP SWITCHES.
Once the system is powered the airflow settings will be configured for all devices.
The outdoor unit will send information to configure indoor airflow. If the indoor unit
is incapable of supplying the required airflow a d3 fault will be displayed on the thermostat and outdoor unit.
All devices have a LEARN button. This button is for future use and has no function
at this time.
IMPORTANT: DO NOT USE A PHONE CORD TO CONNECT INDOOR AND
OUTDOOR UNITS. THIS WILL DAMAGE THE CONTROLS.
IMPORTANT: DO NOT CONNECT THE SYSTEM TO A PHONE LINE. THIS WILL
DAMAGE THE CONTROLS.
Air HandlerAir Conditioner
FurnaceHeat Pump
39
ADVANCED SETTINGS
All adjustments for airflow are made at the thermostat at this point. Items that can
be changed are Airflow trim adjustment Dehumidification Setpoint and mode of
operation. The thermostat also has a wide range of fault and history information.
The following tables show all of the available options by unit type. To go down into
a menu press Install Config to move back up press the Menu button. See
Installation Instructions.
18.2 REPLACEMENT OF COMFORT CONTROL2SYSTEM™ CONTROL
18.2 BOARD
Each control board in the Comfort Control2System™ needs information specific to
the unit the control is installed in. This information is called shared data because it
is distributed (shared) on the HVAC network. The shared data for a unit contains
information that allows the unit to operate correctly.
FIGURE 10
TETHER
MEMORY
CARD
When a control board requires replacement, it is important that the replacement
board gets the shared data from the old control. The primary way the replacement
control gets this information is by the memory card that should be installed on the
old control. Remove the memory card from the old control, but leave it attached to
the unit by the plastic tether, replace the control and reinstall the memory card on
the new control. If for some reason the memory card has been damaged or is missing, the shared data from the network (air handler) will be used by the control. The
network shared data is considered a back up for a lost or missing memory card.
Never remove the memory card from the unit or cut the tether of the memory card
as it is the most effective way to transfer the shared data. If the memory card is
damaged or missing a new memory card can be ordered from Pro Stock. The unit
will operate without the memory card, but a D4 error will be displayed on the seven
segment displays.
The memory card from a different unit should never be used.
40
18.3 Electrical Checks Flow Chart
hermostat call
T
For cooling, no cooling
utdoor Unit
O
Running?
No
Yes
efer to panel cover/documentation
R
or Fault Code Troubleshooting.
f
heck fault history for other faults.
C
7-Segment display lit?
Yes
Y1 LED lit?
Yes
Flashing Mode Character
Yes
Alternating “C” and “##” (Code)
Yes
No
No
No
No
Check control voltage (R and C)
to control
No call received.
24V Systems: Check thermostat,
control wiring
Comm Systems: Check comm.
wiring, T-Stat
Waiting for Anti-S.C. Delay to clear
Note: For solid comm LED, check
comm wiring, term/bus switches at
ICC and AH ctrls.
Control in Lockout Mode.
Check fault history and refer to
Diagnostic Chart.
SEE PANEL COVER OR
OTHER DOCUMENTATION
FOR FAULT CODE
TROUBLESHOOTING.
41
18.4 Cooling Mechanical Checks Flow Chart
Unit Running?
ESNO
Y
Pressure problems?Checks Flow Chart
High Head PressureLow Head PressureLow Suction Pressure
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOMPOSSIBLE CAUSEREMEDY
Unit will not run• Power off or loose electrical connection• Check for correct voltage at contactor in condensing unit
Outdoor fan runs, compressor• Run or start capacitor defective• Replace
Compressor failuresLine tubing too longAdd oil to the recommended level
ine tubing too largeReduce pipe size to improve
L
Low suction pressureLow chargeCheck system charge
Refrigerant leaksRepair and recharge
Cold, Noisy compressor - Slugging Dilution of Oil with RefrigerantObserve piping guidelines
Noisy compressor MigrationCheck crankcase heater
Cold, sweating compressorFloodingCheck system charge
Low LoadReduced air flowDirty filter
Thermostat settingAdvise customer
Short cycling of compressorFaulty pressure controlReplace control
Loose wiringCheck all control wires
ThermostatIn supply air stream,
oil return
irty coil
D
Wrong duct size
Restricted duct
out of calibration,
Customer misuse
FLOODED STARTS
SYMPTOMSPOSSIBLE CAUSESCHECK OR REMEDIES
Liquid in the compressor shellFaulty or missing crankcase heaterReplace crankcase heater
Too much liquid in systemIncorrect pipingCheck Piping guidelines
OverchargeCheck and adjust charge
SLUGGING
SYMPTOMSPOSSIBLE CAUSESCHECK OR REMEDIES
On start upIncorrect pipingReview pipe size guidelines
TEV hunting when runningOversized TEVCheck TEV application
FLOODING
SYMPTOMSPOSSIBLE CAUSESCHECK OR REMEDIES
Poor system controlLoose sensing bulbSecure the bulb and insulate
using a TEV
Bulb in wrong location Relocate bulb
Wrong size TEVUse correct replacement
Improper superheat settingAdjust, if possible;
Replace, if not
Poor system control OverchargeCheck system charge
using capillary tubes
High head pressuresDirty heat pump
Restricted air flow
Recirculation of air
Evaporator air flow too lowAdjust air flow to 400 CFM/Ton
47
THERMOSTATIC EXPANSION VALVES
SYMPTOMSPOSSIBLE CAUSECHECK OR REMEDIES
High Superheat, Low Suction PressureMoisture freezing and blocking valveRecover charge, install filter-drier,
Dirt or foreign material blocking valveRecover charge, install filter-drier,
Low refrigerant chargeCorrect the charge
Vapor bubbles in liquid lineRemove restriction in liquid line
Misapplication of internally equalizedUse correct TEV
valve
Plugged external equalizer lineRemove external equalizer line
Undersized TEVReplace with correct valve
Loss of charge from power Replace power head or complete
head sensing bulbTEV
Charge migration from sensing bulb Ensure TEV is warmer than
to power head (Warm power head sensing bulb
with warm, wet cloth. Does valve
operate correctly now?)
Improper superheat adjustment Adjust superheat setting counter(Only applicable to TEV with adjustable clockwise
superheat settings)
Valve feeds too much refrigerant, Moisture causing valve to stick open.Recover refrigerant, replace filterwith low superheat and higher thandrier, evacuate system and then normal suction pressurerecharge
Dirt or foreign material causing Recover refrigerant, replace filtervalve to stick opendrier, evacuate system and
TEV seat leak (A gurgling or hissing Replace the TEV
sound is heard AT THE TEV during
the off cycle, if this is the cause.)
NOT APPLICABLE TO BLEED
PORT VALVES.
Oversized TEVInstall correct TEV
Incorrect sensing bulb locationInstall bulb with two mounting
Low superheat adjustment Turn superheat adjustment
(only applicable to TEV withclockwise
adjustable superheat setting)
Incorrectly installed, or restricted Remove restriction, or relocate
external equalizer lineexternal equalizer
Compressor flood back upon start upRefrigerant drainage from flooded Install trap riser to the top of the
evaporatorevaporator coil
Compressor in cold locationInstall crankcase heater on
Any of the causes listed under Any of the solutions listed under
Symptoms of Problem #2Solutions of Problem #2
evacuate system, recharge
evacuate system, recharge
Correct the refrigerant charge
emove non-condensible gases
R
Size liquid line correctly
restriction
recharge
straps, in 2:00 or 4:00 position on
suction line, with insulation
compressor
48
THERMOSTATIC EXPANSION VALVES
SYMPTOMSPOSSIBLE CAUSECHECK OR REMEDIES
Superheat is low to normal Unequal evaporator circuit loadingEnsure air flow is equally distributed
with low suction pressurethrough evaporator
Check for blocked distributor
tubes
Low load or airflow entering Ensure blower is moving proper air
evaporator coilCFM
Remove/Correct any air flow
restriction
Superheat and suction Expansion valve is oversizedInstall correct TEV
pressure fluctuate (valve is hunting)
Sensing bulb is affected by liquid Relocate sensing bulb in another
refrigerant or refrigerant oil flowing position around the circumference of
through suction linethe suction line
Unequal refrigerant flow throughEnsure sensing bulb is located
evaporator circuitsproperly
Check for blocked distributor
tubes
Improper superheat adjustmentReplace TEV or adjust superheat
(only possible with TEV having
superheat adjustment)
Moisture freezing and partially Recover refrigerant, change filterblocking TEVdrier, evacuate system and
Valve does not regulate at allExternal equalizer line not connected Connect equalizer line in proper
or line pluggedlocation, or remove any blockage
Sensing bulb lost its operating chargeReplace TEV
Valve body damaged during soldering Replace TEV
or by improper installation