Rheem R-410A, Prestige RARL-024JAZ, Prestige RARL-036JAZ, Prestige RARL-048JAZ, Prestige RARL-060JAZ Engineering Manual

Page 1
FORM NO. A11-180 REV. 5
Supersedes Form No. A11-180 Rev. 4
CONDENSING UNITS
RARL- SERIES
Efficiencies up to 17.10 SEER Nominal Sizes 2 to 5 Tons [7.03 kW] to [17.06 kW]
Cooling Capacities 22,800 to 58,000 BTU/HR [6.68 kW] to [16.99 kW]
The Rheem Prestige Series®High Efficiency RARL- Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi­family and light commercial applications. The Rheem Prestige Series
®
RARL- Condensing Units are the result of an ongoing development program for improved efficien­cies. With system SEER’s ranging to 17.10, these units continue a tradition of high efficiency.
Reliable Copeland Two-Stage Scroll
Compressor for precise
temperature control providing ultimate comfort.
Comfort Alert
Diagnostics comes installed in each Rheem
Prestige Series model.
All controls are accessible by removing one service panel.
Removable top grille provides access to the condenser fan motor and condenser coil.
Attractive, louvered wrap-around jacket protects the coil from
yard hazards and weather extremes. Top grille is steel rein­forced for extra strength. Cabinet is powder painted for all­weather protection.
Air is discharged upward away from bushes and shrubs. The
discharge pattern of the top grille provides minimum air restric­tion, resulting in quiet fan operation.
Exclusive Combination Grille/Motor Mount secures the motor to
the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.
For quiet operation and improved efficiency, the 2, 3, and 4 ton
models feature an 8-pole motor with a 3-blade outdoor fan. The 5 ton model features the GE
®
ECM two-speed motor with a 3-
blade outdoor fan.
All models meet or exceed a 1000-hour salt spray test per ASTM
B117 Standard Practice for Operating Salt Spray Testing Apparatus.
On-demand dehumidification terminal, when matched with a
Prestige Series Air Handler or premium ECM Gas Furnace prod­ucts, adjusts airflow to help control humidity, for unsurpassed comfort in the cooling mode.
earth friendly refrigerant
16.0
Page 2
2 Rheem Manufacturing Company
Engineering Features
RARL- Series Condensing Units
1. Copeland Scroll UltraTech™compressor is hermetically sealed
and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.
2. Compressors have an internal pressure relief assembly to
protect against excessive pressure differential.
3. All refrigerant connections are on the exterior of the unit,
located close to the ground for neat appearing installations.
4. Cabinet is constructed of powder painted galvanized
steel. The full wrap-around louvered grille protects the coil from damage.
5. Copper Tube—Aluminum Fin coils are used on all models.
6. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
7. Service valves are standard on all models.
8. Power and control wiring are kept separate.
9. Every unit is factory charged and tested.
10. Separate compressor compartment for easy service access.
11. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
12. RARL has a 10 year compressor limited warranty and a
liquid line filter drier. The RARL Series also has factory installed low pressure control, high pressure control, and time delay control.
13. Hard Start Kits—Standard on all models.
14. Enhanced Compressor sound-wrap is standard.
15. The 2, 3, and 4 ton models feature an 8-pole motor with a
3-blade outdoor fan. The 5 ton model features the GE
®
ECM
two-speed motor with a 3-blade outdoor fan.
16. Control Box Cover.
COPELAND SCROLL ULTRATECH™COMPRESSOR
The Copeland Scroll UltraTech™compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor technology. The advanced scroll compressor offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The Copeland Scroll UltraTech
also has low start torque, eliminating start problems in the field. And its unique design enables
the RARL- condensing unit to perform efficiently, quietly and reliably.
All controls and compressor are accessible
for servicing by removal of the service panel.
Drawn Painted Base Pan.
In operation, Comfort Alert Diagnostics monitors vital data from the Copeland Scroll UltraTech
compressor and thermostat, quickly pinpointing the root cause(s) of any cooling system malfunction—including common electrical problems, compressor defects and broad system faults.
[ ] Designates Metric Conversions
Comfort AlertTMTrademark of Copeland Corporation
Problem-Solving Accuracy
Troubleshooting air conditioning systems with and without Comfort Alert
Accuracy with Comfort Alert
Accuracy without Comfort Alert
92%
17%
100%
63%
Entry-Level Technicians
Experienced Technicians
Comfort Alert™Diagnostics
Page 3
Rheem Manufacturing Company 3
R A R L 024
COOLING
CAPACITY
024 = 24,000 BTU/HR [7.03 kW] 036 = 36,000 BTU/HR [10.55 kW] 048 = 48,000 BTU/HR [14.07 kW] 060 = 60,000 BTU/HR [17.06 kW]
J A Z
RHEEM REMOTE
CONDENSING
UNIT
16-SEER DESIGN
SERIES
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
VARIATIONS
A = STANDARD
COOLING
CONNECTION
FITTING
Z = SWEAT
W/SCROLL
Model Number Identification
Performance Data @ ARI Standard Conditions—Cooling
NOTES: Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Accessories
Low Ambient Control—Cycles outdoor fan to maintain adequate condensing pressures assuring liquid refrigerant flow to the coil.
Allows indoor cooling with outdoor temperatures down to 0°F [–17.8°C]. (Model No. RXAD-A07). It is recommended that this control be installed in units to be operated at outdoor ambient temperatures under 70°F [21°C].
Compressor Crankcase Heater (Model No. 44-17402-44CCH) Add to minimize refrigeration migration and to help eliminate any startup noise or bearing “wash out”.
Dual Function White Rodgers Thermostat (Model No. 41-1F95CA-391) Humidity & Temperature Control. It provides active comfort Alert
protection.
Outdoor
Unit
RARL-
024J
036J
Model Numbers
ID
Coil
RCQD-2417A
RCHL-24
RCQD-3624A
RCQD-3621A
Air Mover
-BHM-17J
COIL ONLY 18,200 [5.3] 6,400 [1.9] 600 [283] 825 [389] 11.45 24,600 [7.2] 14.25 7.4
-GFD-06?MCK? 18,550 [5.4] 6,450 [1.9] 600 [283] 800 [378] 12.24 25,000 [7.3] 15.85 7.4
-GFD-07?MCK? 18,600 [5.5] 6,400 [1.9] 600 [283] 800 [378] 12.33 25,000 [7.3] 15.90 7.4
-GPL-05?BMK 18,650 [5.5] 6,550 [1.9] 600 [283] 775 [366] 12.49 25,200 [7.4] 15.80 7.4 COIL ONLY 15,800 [4.6] 7,000 [2.1] 625 [295] 825 [389] 10.66 22,800 [6.7] 14.05 7.4
-GFD-06?MCK? 16,250 [4.8] 6,950 [2.0] 600 [283] 800 [378] 11.66 23,200 [6.8] 16.10 7.4
-GFD-07?MCK? 16,300 [4.8] 7,100 [2.1] 600 [283] 800 [378] 11.76 23,400 [6.9] 16.20 7.4
-GPL-05?BMK 16,350 [4.8] 7,050 [2.1] 600 [283] 775 [366] 11.87 23,400 [6.9] 16.10 7.4
-GGD-06?MCK 16,350 [4.8] 7,050 [2.1] 600 [283] 800 [378] 11.92 23,400 [6.9] 16.45 7.4
-GGD-07?MCK 16,350 [4.8] 7,050 [2.1] 625 [295] 800 [378] 11.82 23,400 [6.9] 16.35 7.4
-BHM-24J
COIL ONLY 27,050 [7.9] 9,350 [2.7] 875 [413] 1,175 [555] 11.98 36,400 [10.7] 14.90 7.2
-GFD-09?ZCM? 27,750 [8.1] 9,250 [2.7] 850 [401] 1,150 [543] 12.91 37,000 [10.8] 16.90 7.2
-GFD-10?ZCM? 27,650 [8.1] 9,350 [2.7] 850 [401] 1,175 [555] 12.73 37,000 [10.8] 16.80 7.2
-GFD-12?ZCM? 27,700 [8.1] 9,300 [2.7] 900 [425] 1,225 [578] 12.80 37,000 [10.8] 16.75 7.2
-GPL-07?BRK 27,550 [8.1] 9,250 [2.7] 900 [425] 1,200 [566] 12.55 36,800 [10.8] 16.50 7.2
-GPL-07?BRQ 27,800 [8.1] 9,400 [2.8] 875 [413] 1,200 [566] 13.07 37,200 [10.9] 17.10 7.2
-GPL-10?BRM 27,700 [8.1] 9,300 [2.7] 925 [437] 1,225 [578] 12.87 37,000 [10.8] 16.80 7.2
-GPL-12?ARM 27,750 [8.1] 9,250 [2.7] 1,000 [472] 1,250 [590] 12.93 37,000 [10.8] 16.70 7.2 COIL ONLY 27,050 [7.9] 9,350 [2.7] 875 [413] 1,175 [555] 11.98 36,400 [10.7] 14.90 7.2
-GFD-06?MCK? 27,300 [8.0] 9,100 [2.7] 875 [413] 1,175 [555] 11.97 36,400 [10.7] 15.85 7.2
-GFD-07?MCK? 27,250 [8.0] 9,150 [2.7] 900 [425] 1,200 [566] 11.90 36,400 [10.7] 15.95 7.2
-GFD-09?ZCM? 27,700 [8.1] 9,300 [2.7] 850 [401] 1,150 [543] 12.82 37,000 [10.8] 16.85 7.2
-GFD-10?ZCM? 27,600 [8.1] 9,200 [2.7] 850 [401] 1,175 [555] 12.64 36,800 [10.8] 16.75 7.2
-GPL-05?BMK 27,300 [8.0] 9,100 [2.7] 900 [425] 1,200 [566] 12.01 36,400 [10.7] 15.85 7.2
-GPL-07?BRK 27,500 [8.1] 9,300 [2.7] 900 [425] 1,200 [566] 12.46 36,800 [10.8] 16.45 7.2
-GPL-07?BRQ 27,750 [8.1] 9,250 [2.7] 875 [413] 1,200 [566] 12.98 37,000 [10.8] 17.05 7.2
-GPL-10?BRM 27,650 [8.1] 9,350 [2.7] 925 [437] 1,225 [578] 12.77 37,000 [10.8] 16.70 7.2
ID
Stage
1
2 18,550 [5.4] 6,450 [1.9] 825 [389] 12.39 7.4 1 - dehumid 13,050 [3.8] 5,250 [1.5] 525 [248] 13.17 7.1 2 - dehumid 17,700 [5.2] 7,000 [2.1] 675 [319] 12.60 7.4
1 20,850 [6.1] 6,050 [1.8] 900 [425] 14.65
2 27,850 [8.2] 9,350 [2.7] 1,175 [555] 13.24 7.2 1 - dehumid 19,300 [5.7] 6,800 [2.0] 750 [354] 14.50 7.1 2 - dehumid 25,700 [7.5] 11,000 [3.2] 950 [448] 13.59 7.2
Net
Sensible
BTU/H [kW]
13,750 [4.0] 4,650 [1.4] 600 [283] 13.22
Net
Latent
BTU/H [kW]
Indoor Airflow
1st Stage CFM [L/s]
2nd Stage CFM [L/s]
ARI Rating
EER
Total
Capacity
BTU/H [kW]
25,000 [7.3] 16.10
37,200 [10.9] 17.00
SEER
Sound Rating
7.1
7.1
Page 4
4 Rheem Manufacturing Company
Performance Data @ ARI Standard Conditions—Cooling (cont.)
NOTES: Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Outdoor
Unit
RARL-
036J RCHL-36
048J
060J RCQD-6024A
Model Numbers
ID
Coil
RCQD-4824A
RCQD-4821A
RCHL-48
Net
ID
Air Mover
COIL ONLY 25,000 [7.3] 9,200 [2.7] 900 [425] 1,200 [566] 11.24 34,200 [10.0] 13.95 7.2
-GFD-06?MCK? 25,100 [7.4] 9,300 [2.7] 875 [413] 1,175 [555] 11.40 34,400 [10.1] 15.05 7.2
-GFD-07?MCK? 25,050 [7.3] 9,150 [2.7] 900 [425] 1,200 [566] 11.37 34,200 [10.0] 15.15 7.2
-GFD-09?ZCM? 25,650 [7.5] 9,150 [2.7] 850 [401] 1,150 [543] 12.27 34,800 [10.2] 16.00 7.2
-GFD-10?ZCM? 25,550 [7.5] 9,250 [2.7] 850 [401] 1,175 [555] 12.11 34,800 [10.2] 15.90 7.2
-GPL-05?BMK 25,150 [7.4] 9,250 [2.7] 900 [425] 1,200 [566] 11.49 34,400 [10.1] 15.10 7.2
-GPL-07?BRK 25,450 [7.5] 9,150 [2.7] 900 [425] 1,200 [566] 11.93 34,600 [10.1] 15.60 7.2
-GPL-07?BRQ 25,750 [7.5] 9,250 [2.7] 875 [413] 1,200 [566] 12.42 35,000 [10.3] 16.20 7.2
-GPL-10?BRM 25,650 [7.5] 9,150 [2.7]
-GGD-06?MCK 25,200 [7.4] 9,200 [2.7] 900 [425] 1,225 [578] 11.54 34,400 [10.1] 15.35 7.2
-GGD-07?MCK 25,100 [7.4] 9,300 [2.7]
-GGD-09?ZCM 25,650 [7.5] 9,150 [2.7] 800 [378] 1,175 [555] 12.22 34,800 [10.2] 16.15 7.2
-GGD-10?ZCM 25,650 [7.5] 9,150 [2.7] 825 [389] 1,175 [555] 12.22 34,800 [10.2] 16.10 7.2
-BHM-25J
COIL ONLY 35,750 [10.5] 11,250 [3.3] 1,200 [566] 1,600 [755] 11.58 47,000 [13.8] 13.95 7.2
-GFD-09?ZCM? 35,750 [10.5] 11,250 [3.3] 1,150 [543] 1,600 [755] 11.56 47,000 [13.8] 15.10 7.2
-GFD-10?ZCM? 35,550 [10.4] 10,950 [3.2] 1,175 [555] 1,625 [767] 11.25 46,500 [13.6] 14.85 7.2
-GFD-12?ZCM? 35,900 [10.5] 11,100 [3.3] 1,225 [578] 1,650 [779] 11.74 47,000 [13.8] 15.00 7.2
-GPL-07?BRQ 36,050 [10.6] 10,950 [3.2] 1,225 [578] 1,625 [767] 11.97 47,000 [13.8] 15.35 7.2
-GPL-10?BRM 35,850 [10.5] 11,150 [3.3] 1,200 [566] 1,625 [767] 11.72 47,000 [13.8] 15.15 7.2
-GPL-12?ARM 36,050 [10.6] 11,450 [3.4] 1,250 [590] 1,575 [743] 12.01 47,500 [13.9] 15.20 7.2 COIL ONLY 35,750 [10.5] 11,250 [3.3] 1,200 [566] 1,600 [755] 11.58 47,000 [13.8] 13.95 7.2
-GFD-09?ZCM? 35,700 [10.5] 11,300 [3.3] 1,150 [543] 1,600 [755] 11.45 47,000 [13.8] 15.00 7.2
-GFD-10?ZCM? 35,450 [10.4] 11,050 [3.2] 1,175 [555] 1,625 [767] 11.14 46,500 [13.6] 14.70 7.2
-GPL-07?BRQ 36,000 [10.6] 11,000 [3.2] 1,225 [578] 1,625 [767] 11.87 47,000 [13.8] 15.25 7.2
-GPL-10?BRM 35,800 [10.5] 11,200 [3.3] 1,200 [566] 1,625 [767] 11.61 47,000 [13.8] 15.05 7.2 COIL ONLY 33,600 [9.8] 10,900 [3.2] 1,200 [566] 1,600 [755] 10.95 44,500 [13.0] 13.45 7.2
-GFD-09?ZCM? 33,850 [9.9] 10,650 [3.1] 1,150 [543] 1,600 [755] 11.17 44,500 [13.0] 14.75
-GFD-10?ZCM? 33,550 [9.8] 10,950 [3.2] 1,175 [555] 1,625 [767] 10.89 44,500 [13.0] 14.50 7.2
-GFD-12?ZCM? 33,950 [9.9] 11,050 [3.2] 1,225 [578] 1,650 [779] 11.26 45,000 [13.2] 14.65 7.2
-GPL-07?BRQ 34,200 [10.0] 10,800 [3.2] 1,225 [578] 1,625 [767] 11.55 45,000 [13.2] 15.00 7.2
-GPL-10?BRM 34,000 [10.0] 11,000 [3.2] 1,200 [566] 1,625 [767] 11.33 45,000 [13.2] 14.85 7.2
-GPL-12?ARM 34,250 [10.0] 10,750 [3.2] 1,250 [590] 1,575 [743] 11.56 45,000 [13.2] 14.90 7.2
-GGD-10?ZCM 33,650 [9.9] 10,850 [3.2] 1,175 [555] 1,625 [767] 10.98 44,500 [13.0] 14.65 7.2
-GGD-12?ZCM 33,800 [9.9] 10,700 [3.1] 1,225 [578] 1,650 [779] 11.14 44,500 [13.0] 14.75 7.2
-BHM-26J
COIL ONLY 40,450 [11.9] 16,550 [4.9] 1,250 [590] 1,675 [791] 11.44 57,000 [16.7] 14.20 7.8
-GFD-09?ZCM? 39,850 [11.7] 15,650 [4.6] 1,150 [543] 1,600 [755] 11.25 55,500 [16.3] 15.05 7.8
-GFD-10?ZCM? 39,650 [11.6] 15,850 [4.6] 1,175 [555] 1,625 [767] 11.00 55,500 [16.3] 14.80 7.8
-GFD-12?ZCM? 39,950 [11.7] 16,050 [4.7] 1,225 [578] 1,650 [779] 11.39 56,000 [16.4] 14.95 7.8
-GPL-07?BRQ 40,100 [11.8] 15,900 [4.7] 1,225 [578] 1,625 [767] 11.58 56,000 [16.4] 15.25 7.8
-GPL-10?BRM 39,950 [11.7] 16,050 [4.7] 1,200 [566] 1,625 [767] 11.38 56,000 [16.4] 15.10 7.8
-GPL-12?ARM 40,150 [11.8] 15,850 [4.6] 1,250 [590] 1,575 [743] 11.61 56,000 [16.4] 15.15 7.8
Stage
1 27,650 [8.1] 7,850 [2.3] 1,200 [566] 13.75
2 36,250 [10.6] 11,250 [3.3] 1,600 [755] 12.58 7.2 1 - dehumid 25,650 [7.5] 9,150 [2.7] 1,000 [472] 13.81 7.1 2 - dehumid 33,300 [9.8] 13,700 [4.0] 1,275 [602] 12.95 7.2
1 30,650 [9.0] 11,550 [3.4] 1,275 [602] 13.28
2 41,450 [12.1] 16,550 [4.9] 1,675 [791] 12.18 7.8 1 - dehumid 28,450 [8.3] 12,150 [3.6] 1,050 [496] 13.01 7.6 2 - dehumid 37,450 [11.0] 17,450 [5.1] 1,350 [637] 12.07 7.8
Sensible
BTU/H [kW]
Latent
BTU/H [kW]
Net
Indoor Airflow
1st Stage CFM [L/s]
925 [437]
925 [437] 1,225 [578] 11.43 34,400 [10.1] 15.25 7.2
2nd Stage CFM [L/s]
1,225 [578] 12.25
EER
ARI Rating
Total
Capacity
BTU/H [kW]
34,800 [10.2] 15.90 7.2
47,500 [13.9] 16.00
58,000 [17.0] 15.80
SEER
Sound Rating
7.1
7.2
7.6
Page 5
Rheem Manufacturing Company 5
Performance Data @ ARI Standard Conditions—Cooling
NOTES: Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Outdoor
Unit
RARL-
060J
Model Numbers
ID
Coil
RCHL-60
Net
ID
Air Mover
COIL ONLY 36,900 [10.8] 17,600 [5.2] 1,275 [602] 1,700 [802] 11.03 54,500 [16.0] 13.75 7.8
-GFD-09?ZCM? 37,200 [10.9] 17,800 [5.2] 1,150 [543] 1,600 [755] 11.34 55,000 [16.1] 15.00 7.8
-GFD-10?ZCM? 36,950 [10.8] 17,550 [5.1] 1,175 [555] 1,625 [767] 11.11 54,500 [16.0] 14.80 7.8
-GFD-12?ZCM? 37,300 [10.9] 17,700 [5.2] 1,225 [578] 1,650 [779] 11.42 55,000 [16.1] 14.90 7.8
-GPL-07?BRQ 37,550 [11.0] 17,450 [5.1] 1,225 [578] 1,625 [767] 11.64 55,000 [16.1] 15.20 7.8
-GPL-10?BRM 37,350 [10.9] 17,650 [5.2] 1,200 [566] 1,625 [767] 11.47 55,000 [16.1] 15.05 7.8
-GPL-12?ARM 37,600 [11.0] 17,400 [5.1] 1,250 [590] 1,575 [743] 11.66 55,000 [16.1] 15.10 7.8
-GGD-09?ZCM 36,950 [10.8] 17,550 [5.1] 1,175 [555] 1,675 [791] 11.10 54,500 [16.0] 14.95 7.8
-GGD-10?ZCM 37,050 [10.9] 17,450 [5.1]
-GGD-12?ZCM 37,200 [10.9] 17,800 [5.2] 1,225 [578] 1,650 [779] 11.32 55,000 [16.1] 15.00 7.8
Stage
Sensible
BTU/H [kW]
Latent
BTU/H [kW]
Net
Indoor Airflow
1st Stage CFM [L/s]
1,175 [555]
2nd Stage
CFM [L/s]
1,625 [767] 11.19
EER
ARI Rating
Total
Capacity
BTU/H [kW]
54,500 [16.0] 14.95 7.8
SEER
Sound Rating
Page 6
6 Rheem Manufacturing Company
Electrical and Physical Data
[ ] Designates Metric Conversions
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.
Rheem Prestige Series equipment features a 10-year limited parts warranty.*
*This ten-year limited parts warranty is applicable only to single-phase
products installed in residential applications.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
Model Number
RARL-
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
Width “W”
(Inches) [mm]
024 23 [584] 443/8 [1127] 311/2 [800]
036/048/060 33 [838] 443/8 [1127] 311/2 [800]
*HS = high speed *LS = low speed
Unit Dimensions
ELECTRICAL
Model
Number
RARL-
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Min.
Circuit Ampacity Amperes
Fuse or HACR
Circuit Breaker
Min.
Amperes
Amperes
Max.
Face Area
Sq. Ft. [m
Outdoor Coil
No.
2
Rows
]
024JAZ 1-60-208/230 10.3/10.3 52 0.8 14/14 20/20 20/20 15.8 [1.47] 1 2285 [1078] 117 [3311] 190 [86.2] 200 [90.7] 036JAZ 1-60-208/230 16.7/16.7 82 1.0 22/22
30/30 35/35 23.0 [2.14] 1 3900 [1841] 157 [4445]
048JAZ 1-60-208/230 21.2/21.2 96 1.0 28/28 35/35 45/45 23.0 [2.14] 1 3900 [1841] 154 [4354] 236 [107] 246 [111.6]
060JAZ 1-60-208/230 25.6/25.6 118 2.8 35/35 45/45 60/60 23.0 [2.14] 2
HS*3500 [1652] LS*2800 [1322]
PHYSICAL
CFM [L/s]
Net
Lbs. [kg]
236 [107]
Weight
Shipping Lbs. [kg]
246 [111.6]
R-410a
Oz. [g]
224 [6350] 305 [138] 315 [142.9]
AIR DISCHARGE
ALLOW 60 [1524 mm] CLEARANCE
W
L
ACCESS PANEL
ALLOW 24 [610 mm] ACCESS CLEARANCE
H
AIR INLETS (LOUVERS) ALLOW 6 [152 mm] MIN. CLEARANCE
ALTERNATE HIGH VOLTAGE CONNECTION (KNOCKOUT)
11
1
3 SIDES
/32[34 mm]
SERVICE FITTINGS
3
0
0
0
0
-
A
HIGH PRESSURE CONTROL MANUAL RESET (FIELD INSTALLED ACCESSORY)
VAPOR LINE CONNECTION
LOW VOLTAGE CONNECTION
7
/80 [22 mm]
LIQUID LINE CONNECTION
7
/80 [73 mm] DIA.
2 ACCESSORY KNOCKOUTS
HIGH VOLTAGE CONNECTION
11
/320 [34 mm]
1
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 240 [610 mm] CLEARANCE ONE SIDE
Page 7
Rheem Manufacturing Company 7
Condensing Unit Refrigerant Line Size Information
NOTES:
1) Do NOT use
7
/8 OD suction lines in 2-ton applications where the outdoor unit is located above the indoor coil. Suction line may not have sufficient velocity for oil return.
2) Do NOT use 1
1
/8 OD suction lines in 3-ton applications as they have insufficient velocity for oil return.
3) Do NOT use 1
1
/8 OD suction lines in 4-ton applications where the outdoor unit is located above the indoor coil. Suction line may have insufficient velocity for oil return.
4) Do NOT use 1
1
/8 OD suction lines in 5-ton applications where the outdoor unit is located above the indoor coil. Suction line may have insufficient velocity for oil return.
[ ] Designates Metric Conversions
System
Capacity
Model
Line Size
(Inch O.D.)
[mm]
1/4* [6.35] 14 [4.27]
024
5/16 [7.94] 23 [7.01] 18 [5.48] 13 [3.96] 88 [2.44] 53 [0.91] 3/8 [9.53] 25 [7.62] 24 [7.31] 22 [6.70] 20 [6.09] 18 [5.48] 5/16 [7.94] 25 [7.62] 18 [5.48] 11 [3.35]
036
3/8* [9.53] 25 [7.62] 27 [8.22] 24 [7.31] 21 [6.40] 18 [5.48] 5/16 [7.94] 19 [5.79] 55 [1.52]
048
1/2 [12.7] 25 [7.62] 30 [9.14] 29 [8.83] 29 [8.83] 28 [8.53]
5/16 [7.94]
060
1/2 [12.7] 25 [7.62] 50 [15.2] 51 [15.5] 68 [20.7]
*Standard Line Size
NOTES:
1. Example 1: A 2-ton condensing unit with a total line length of 75 feet with a vertical separa-
tion of 15 feet requires a liquid line size of 3/8".
2. This chart may also be used to size horizontal runs. Example 2: A 3-ton condensing unit may
have a total horizontal run of 100 feet if using a 3/8" liquid line.
3. If vertical separation exceeds this chart, use the extended line lengths chart.
4. Always use the smallest liquid line possible to minimize system charge.
Standard Refrigerant Charge: Liquid Line Size
RARL- Series Below Indoor Coil
Total Length—Feet [m]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10]
Vertical Separation—Feet [m]
25 [7.62] 35 [10.7] 17 [5.18]
50 [15.2] 55 [16.8] 48 [14.6] 42 [12.8]
System
Capacity
Model
(Inch O.D.)
1/4* [6.35] 25 [7.62] 21 [6.40] 88 [2.44]
024
5/16 [7.94] 25 [7.62] 39 [11.8] 33 [10.0] 28 [8.53] 23 [7.01] 3/8 [9.53] 25 [7.62] 45 [13.7] 43 [13.1] 5/16 [7.94] 25 [7.62] 38 [11.5] 29 [8.83] 15 [4.50]
036
3/8* [9.53] 25 [7.62] 48 [14.6] 45 [13.7] 41 [12.4] 38 [11.5] 5/16 [7.94]
048
3/8* [9.53] 25 [7.62] 42 [12.8] 37 [11.2] 31 [9.40] 26 [7.92]3/8* [9.53] 25 [7.62] 21 [6.40] 16 [4.87] 11 [3.35] 55 [1.52]
1/2 [12.7] 25 [7.62] 50 [15.2] 51 [15.5] 50 [15.2] 49 [14.9]
5/16 [7.94] 3/8* [9.53]060
1/2 [12.7] 25 [7.62] 50 [15.2] 75 [22.9] 79 [24.0] 78 [23.7]
*Standard Line Size IMPORTANT: Line sizing by this chart requires a supplemental refrigerant charge. Refer to
charging chart on unit for proper charging with extended line sets. NOTES:
1. Example 1: A 2-ton condensing unit with a total line length of 75 feet with a vertical separa-
tion of 15 feet requires a minimum liquid line size of 5/16".
2. This chart may also be used to size horizontal runs. Example 2: A 3-ton condensing unit
may have a total horizontal run of 100 feet if using a 5/16" liquid line.
3. The vertical separation indicated on this chart CANNOT be exceeded.
4. Always use the smallest liquid line possible to minimize system charge.
Line Size
[mm]
Extended Line Lengths for use with Supplemental Refrigerant
Charge: Liquid Line Size RARL- Series Below Indoor Coil
Total Length—Feet [m]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10]
Vertical Separation—Feet [m]
41 [12.4] 39 [11.8]
25 [7.62] 26 [7.92] 12 [3.65]
25 [7.62] 45 [13.7] 27 [8.22] 59 [2.74] 25 [7.62] 50 [15.2] 65 [19.8] 58 [17.6] 52 [15.8]3/8* [9.53] 25 [7.62]
RARL-
Unit Vapor Line
Connection Size
Vapor Line Run
Feet [m]
25'
[7.62]
50'
[15.24]
Optional Standard Optional
Optional Standard Optional
Optional
75' [22.86]
Standard Optional
Optional
100' [30.48]
Standard Optional
1
024
3
/4"[19.05 mm]
I.D. Sweat
5
/8"[15.88 mm]O.D. Opt.
3
/4"[19.05 mm]O.D. Std.
7
/8"[22.23 mm] O.D. Opt.
0.99
1.00
1.01
0.98
0.99
1.00
0.97
0.97
0.99
0.95
0.96
0.97
Vapor Line Length Size and Capacity Multiplier
2
036
7
/8"[22.23 mm]
I.D. Sweat
3
/4" [19.05 mm]O.D. Opt.
7
/8" [22.23 mm]O.D. Std.
.99
1.00
0
0.98
0.99 0
0.97
.98
0
0.96
0.97
0
3
048
7
/8"[22.23 mm]
I.D. Sweat
3
/4" [19.05 mm]O.D. Opt.
7
/8" [22.23 mm]O.D. Std.
1
1
/8"[28.58 mm]O.D. Opt.
.99
1.00
1.01
0.98
0.99
1.00
0.97
.98 .99
0.95
0.97
.98
4
060
7
/8"[22.23 mm]
I.D. Sweat
3
/4" [19.05 mm]O.D. Opt.
7
/8" [22.23 mm]O.D. Std.
1
1
/8"[28.58 mm]O.D. Opt.
.99
1.00
1.01
0.98
0.99
1.00
0.97
.98 .99
0.95
0.97
.98
Page 8
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
RHEEM AIR CONDITIONING DIVISION
5600 Old Greenwood Road, Fort Smith, Arkansas 72908
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 4-06 DC FORM NO. A11-180 REV .5
Supersedes Form No. A11-180 Rev. 4
Loading...