FORM NO. A11-180 REV. 5
Supersedes Form No. A11-180 Rev. 4
CONDENSING UNITS
RARL- SERIES
Efficiencies up to 17.10 SEER
Nominal Sizes 2 to 5 Tons
[7.03 kW] to [17.06 kW]
Four Models
Cooling Capacities
22,800 to 58,000 BTU/HR
[6.68 kW] to [16.99 kW]
The Rheem Prestige Series®High Efficiency RARL- Condensing
Unit was designed with performance in mind. These units offer
comfort, energy conservation and dependability for single, multifamily and light commercial applications.
The Rheem Prestige Series
®
RARL- Condensing Units are the
result of an ongoing development program for improved efficiencies. With system SEER’s ranging to 17.10, these units continue a
tradition of high efficiency.
■ Reliable Copeland Two-Stage Scroll
™
Compressor for precise
temperature control providing ultimate comfort.
■ Comfort Alert
™
Diagnostics comes installed in each Rheem
Prestige Series model.
■ All controls are accessible by removing one service panel.
Removable top grille provides access to the condenser fan
motor and condenser coil.
■ Attractive, louvered wrap-around jacket protects the coil from
yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for allweather protection.
■ Air is discharged upward away from bushes and shrubs. The
discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.
■ Exclusive Combination Grille/Motor Mount secures the motor to
the underside of the discharge grille. The grille protects the motor
windings and bearings from rain and snow.
■ For quiet operation and improved efficiency, the 2, 3, and 4 ton
models feature an 8-pole motor with a 3-blade outdoor fan. The
5 ton model features the GE
®
ECM two-speed motor with a 3-
blade outdoor fan.
■ All models meet or exceed a 1000-hour salt spray test per ASTM
B117 Standard Practice for Operating Salt Spray Testing Apparatus.
■ On-demand dehumidification terminal, when matched with a
Prestige Series Air Handler or premium ECM Gas Furnace products, adjusts airflow to help control humidity, for unsurpassed
comfort in the cooling mode.
earth friendly refrigerant
16.0

2 Rheem Manufacturing Company
Engineering Features
RARL- Series Condensing Units
1. Copeland Scroll UltraTech™compressor is hermetically sealed
and incorporates internal high temperature motor overload
protection, and durable insulation on the motor windings. It is
externally mounted on rubber grommets to reduce vibration
and noise.
2. Compressors have an internal pressure relief assembly to
protect against excessive pressure differential.
3. All refrigerant connections are on the exterior of the unit,
located close to the ground for neat appearing installations.
4. Cabinet is constructed of powder painted galvanized
steel. The full wrap-around louvered grille protects the coil
from damage.
5. Copper Tube—Aluminum Fin coils are used on all models.
6. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
7. Service valves are standard on all models.
8. Power and control wiring are kept separate.
9. Every unit is factory charged and tested.
10. Separate compressor compartment for easy service access.
11. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
12. RARL has a 10 year compressor limited warranty and a
liquid line filter drier. The RARL Series also has factory
installed low pressure control, high pressure control, and time
delay control.
13. Hard Start Kits—Standard on all models.
14. Enhanced Compressor sound-wrap is standard.
15. The 2, 3, and 4 ton models feature an 8-pole motor with a
3-blade outdoor fan. The 5 ton model features the GE
®
ECM
two-speed motor with a 3-blade outdoor fan.
16. Control Box Cover.
COPELAND SCROLL ULTRATECH™COMPRESSOR
The Copeland Scroll UltraTech™compressor is the key to efficiency for this Rheem model. It’s the latest in
high-efficiency compressor technology. The advanced scroll compressor offers low noise and vibration
characteristics and features tolerance to liquid refrigerant and system contamination. The Copeland Scroll
UltraTech
™
also has low start torque, eliminating start problems in the field. And its unique design enables
the RARL- condensing unit to perform efficiently, quietly and reliably.
All controls and compressor are accessible
for servicing by removal of the service panel.
Drawn Painted Base Pan.
■
In operation, Comfort Alert Diagnostics monitors vital data from the Copeland
Scroll UltraTech
™
compressor and thermostat, quickly pinpointing the root
cause(s) of any cooling system malfunction—including common electrical
problems, compressor defects and broad system faults.
[ ] Designates Metric Conversions
Comfort AlertTMTrademark of Copeland Corporation
Problem-Solving Accuracy
Troubleshooting air conditioning systems with and without Comfort Alert
Accuracy
with
Comfort Alert
Accuracy
without
Comfort Alert
92%
17%
100%
63%
Entry-Level Technicians
Experienced Technicians
Comfort Alert™Diagnostics

Rheem Manufacturing Company 3
R A R L 024
COOLING
CAPACITY
024 = 24,000 BTU/HR [7.03 kW]
036 = 36,000 BTU/HR [10.55 kW]
048 = 48,000 BTU/HR [14.07 kW]
060 = 60,000 BTU/HR [17.06 kW]
J A Z
RHEEM REMOTE
CONDENSING
UNIT
16-SEER DESIGN
SERIES
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
VARIATIONS
A = STANDARD
COOLING
CONNECTION
FITTING
Z = SWEAT
W/SCROLL
—
Model Number Identification
Performance Data @ ARI Standard Conditions—Cooling
NOTES: ➀ Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Accessories
Low Ambient Control—Cycles outdoor fan to maintain adequate condensing pressures assuring liquid refrigerant flow to the coil.
Allows indoor cooling with outdoor temperatures down to 0°F [–17.8°C]. (Model No. RXAD-A07). It is recommended that this control be
installed in units to be operated at outdoor ambient temperatures under 70°F [21°C].
Compressor Crankcase Heater (Model No. 44-17402-44CCH) Add to minimize refrigeration migration and to help eliminate any
startup noise or bearing “wash out”.
Dual Function White Rodgers Thermostat (Model No. 41-1F95CA-391) Humidity & Temperature Control. It provides active comfort
Alert
™
protection.
Outdoor
Unit
RARL-
024J
036J
Model Numbers
ID
Coil
RCQD-2417A
RCHL-24
RCQD-3624A
RCQD-3621A
Air Mover
-BHM-17J ➀
COIL ONLY 18,200 [5.3] 6,400 [1.9] 600 [283] 825 [389] 11.45 24,600 [7.2] 14.25 7.4
-GFD-06?MCK? 18,550 [5.4] 6,450 [1.9] 600 [283] 800 [378] 12.24 25,000 [7.3] 15.85 7.4
-GFD-07?MCK? 18,600 [5.5] 6,400 [1.9] 600 [283] 800 [378] 12.33 25,000 [7.3] 15.90 7.4
-GPL-05?BMK 18,650 [5.5] 6,550 [1.9] 600 [283] 775 [366] 12.49 25,200 [7.4] 15.80 7.4
COIL ONLY 15,800 [4.6] 7,000 [2.1] 625 [295] 825 [389] 10.66 22,800 [6.7] 14.05 7.4
-GFD-06?MCK? 16,250 [4.8] 6,950 [2.0] 600 [283] 800 [378] 11.66 23,200 [6.8] 16.10 7.4
-GFD-07?MCK? 16,300 [4.8] 7,100 [2.1] 600 [283] 800 [378] 11.76 23,400 [6.9] 16.20 7.4
-GPL-05?BMK 16,350 [4.8] 7,050 [2.1] 600 [283] 775 [366] 11.87 23,400 [6.9] 16.10 7.4
-GGD-06?MCK 16,350 [4.8] 7,050 [2.1] 600 [283] 800 [378] 11.92 23,400 [6.9] 16.45 7.4
-GGD-07?MCK 16,350 [4.8] 7,050 [2.1] 625 [295] 800 [378] 11.82 23,400 [6.9] 16.35 7.4
-BHM-24J ➀
COIL ONLY 27,050 [7.9] 9,350 [2.7] 875 [413] 1,175 [555] 11.98 36,400 [10.7] 14.90 7.2
-GFD-09?ZCM? 27,750 [8.1] 9,250 [2.7] 850 [401] 1,150 [543] 12.91 37,000 [10.8] 16.90 7.2
-GFD-10?ZCM? 27,650 [8.1] 9,350 [2.7] 850 [401] 1,175 [555] 12.73 37,000 [10.8] 16.80 7.2
-GFD-12?ZCM? 27,700 [8.1] 9,300 [2.7] 900 [425] 1,225 [578] 12.80 37,000 [10.8] 16.75 7.2
-GPL-07?BRK 27,550 [8.1] 9,250 [2.7] 900 [425] 1,200 [566] 12.55 36,800 [10.8] 16.50 7.2
-GPL-07?BRQ 27,800 [8.1] 9,400 [2.8] 875 [413] 1,200 [566] 13.07 37,200 [10.9] 17.10 7.2
-GPL-10?BRM 27,700 [8.1] 9,300 [2.7] 925 [437] 1,225 [578] 12.87 37,000 [10.8] 16.80 7.2
-GPL-12?ARM 27,750 [8.1] 9,250 [2.7] 1,000 [472] 1,250 [590] 12.93 37,000 [10.8] 16.70 7.2
COIL ONLY 27,050 [7.9] 9,350 [2.7] 875 [413] 1,175 [555] 11.98 36,400 [10.7] 14.90 7.2
-GFD-06?MCK? 27,300 [8.0] 9,100 [2.7] 875 [413] 1,175 [555] 11.97 36,400 [10.7] 15.85 7.2
-GFD-07?MCK? 27,250 [8.0] 9,150 [2.7] 900 [425] 1,200 [566] 11.90 36,400 [10.7] 15.95 7.2
-GFD-09?ZCM? 27,700 [8.1] 9,300 [2.7] 850 [401] 1,150 [543] 12.82 37,000 [10.8] 16.85 7.2
-GFD-10?ZCM? 27,600 [8.1] 9,200 [2.7] 850 [401] 1,175 [555] 12.64 36,800 [10.8] 16.75 7.2
-GPL-05?BMK 27,300 [8.0] 9,100 [2.7] 900 [425] 1,200 [566] 12.01 36,400 [10.7] 15.85 7.2
-GPL-07?BRK 27,500 [8.1] 9,300 [2.7] 900 [425] 1,200 [566] 12.46 36,800 [10.8] 16.45 7.2
-GPL-07?BRQ 27,750 [8.1] 9,250 [2.7] 875 [413] 1,200 [566] 12.98 37,000 [10.8] 17.05 7.2
-GPL-10?BRM 27,650 [8.1] 9,350 [2.7] 925 [437] 1,225 [578] 12.77 37,000 [10.8] 16.70 7.2
ID
Stage
1
2 18,550 [5.4] 6,450 [1.9] 825 [389] 12.39 7.4
1 - dehumid 13,050 [3.8] 5,250 [1.5] 525 [248] 13.17 7.1
2 - dehumid 17,700 [5.2] 7,000 [2.1] 675 [319] 12.60 7.4
1 20,850 [6.1] 6,050 [1.8] 900 [425] 14.65
2 27,850 [8.2] 9,350 [2.7] 1,175 [555] 13.24 7.2
1 - dehumid 19,300 [5.7] 6,800 [2.0] 750 [354] 14.50 7.1
2 - dehumid 25,700 [7.5] 11,000 [3.2] 950 [448] 13.59 7.2
Net
Sensible
BTU/H [kW]
13,750 [4.0] 4,650 [1.4] 600 [283] 13.22
Net
Latent
BTU/H [kW]
Indoor Airflow
1st Stage
CFM [L/s]
2nd Stage
CFM [L/s]
ARI Rating
EER
Total
Capacity
BTU/H [kW]
25,000 [7.3] 16.10
37,200 [10.9] 17.00
SEER
Sound
Rating
7.1
7.1