Rheem PNL-*AZ Series, PPL-JAZ Series Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORT TION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
ANT SAFETY INFORMA
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLAT I ON, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE AT TEMPTING INSTALLATION OR OPERATION. FA ILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLAT I ON, ADJUSTMENT,SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
HEAT PUMP OUTDOOR UNITS FEATURING EARTH-FRIENDLY R-410A REFRIGERANT
(-)PNL-*AZ MODEL SERIES - 13 SEER (-)PPL-JAZ MODEL SERIES - 14 SEER
[ ] INDICATES METRIC CONVERSIONS
(14 SEER MODELS & 13 SEER MODELS IN
CERTAIN MATCHED
SYSTEMS)
SUPERSEDES 92-20522-43-06
92-20522-43-07
Page 2
TABLE OF CONTENTS
1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
.1 Checking Product Received. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2
2.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Electrical and Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 LOCATING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Heat Pump Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Operational Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
.4 For Units With Space Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3
3.5 Customer Satisfaction Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.6 Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.7 Factory-Prepferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 REPLACEMENT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.0 INDOOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.0 INTERCONNECTING TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.1 Vapor & Liquid Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.2 Maximum Length of Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.3 Vertical Separation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.4 Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.5 Tubing Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.6 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.0 DEMAND DEFROST CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.1 Defrost Initiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.2 Defrost Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.3 Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.4 Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.5 Demand Defrost Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.6 High/Low Pressure Control Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.7 Enhanced Feature Defrost Control Diagnostic Codes . . . . . . . . . . . . . . . . . 15
9.0 EVACUATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.0 START UP & PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11.0 CHECKING AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
12.0 CHECKING REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
12.1 Charging By Liquid Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
12.2 Charging By Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
12.3 Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
13.0 ELECTRICAL WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
13.1 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
13.2 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
13.3 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14.0 FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14.1 Compressor Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14.2 Time Delay Control (TDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
14.3 Low Ambient Control (LAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
15.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.1 Electrical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.2 Cooling Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
15.3 Heating Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
15.4 Defrost Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
15.5 Subcooling Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
15.6 General Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15.7 Service Analyzer Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
16.0 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2
Page 3
1.0 SAFETY INFORMATION
WARNING
!
These instructions are intended as an aid to qualified, licensed service per­sonnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjust­ment, service or maintenance possibly resulting in fire, electrical shock, prop­erty damage, personal injury or death.
WARNING
!
The manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories
r devices (other than those authorized by the manufacturer) into, onto or in
o conjunction with the air conditioner. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
WARNING
!
Disconnect all power to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
WARNING
!
Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in severe per­sonal injury or death.
WARNING
!
Turn off electric power at the fuse box or service panel before making any electrical connections.
Also, the ground connection must be completed before making line voltage connections. Failure to do so can result in electrical shock, severe personal injury or death.
WARNING
!
The unit must be permanently grounded. Failure to do so can cause electrical shock resulting in severe personal injury or death.
WARNING
!
Secure elevated unit and elevating stand in order to prevent tipping. Failure to do this may result in severe personal injury or death.
CAUTION
Wh e n coil is insta l led over a fini s hed ceili n g and/or livi n g area, it is recommended th a t a se c o n d a r y sh e et meta l co n d e n s a te pan be constructed and installed under entire unit. Failure to do so may result in property damage.
CAUTION
Single-pole contactors are used on all standard single-phase units up through 5 tons. Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor. Two pole contactors are used on some three phase units.
CAUTION
Dual fuel (fossil fuel) applications require the use of a high pressure control in the heat pump section. If a high pressure control was not originally provided with the heat pump section from the factory, a factory approved high pressure control kit must be purchased from the manufacturer and installed in the heat pump. Dual fuel (fossil fuel) applications in which a high pressure control is not installed in the outdoor heat pump section will void the safety approval of the product.
3
Page 4
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
2.0 GENERAL
WARNING
!
The manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components. Accessories or devices (other than those authorized by the manufactur­er) into, onto or in conjunction with the air conditioner. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized compo-
ents, accessories or devices.
n
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the heat pump equipment. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions, and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the heat pump specification sheet should be used.
2.1 CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check heat pump model number, electrical characteristics and accessories to determine if they are correct. Check system components to make sure they are properly matched.
2.2 APPLICATION
Before installing any heat pump equipment, a duct analysis of the structure and a heat gain calculation must be made. A heat gain calculation begins by measuring all external surfaces and openings that gain heat from the surrounding air and quantifying that heat gain. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal.
There are several factors that installers must consider.
Outdoor unit location Indoor unit blower speed
Proper equipment evacuation • Supply and return air duct design and sizing
Refrigerant charge System air balancing
Indoor unit air flow Diffuser and return air grille location and sizing
4
Page 5
AIR INLETS (LOUVERS) ALLOW 120 [305 mm] M
IN. CLEARANCE
3 SIDES
AIR DISCHARGE
A
LLOW 600 [1524 mm] CLEARANCE
ALLOW 240 [610 mm] ACCESS CLEARANCE
ACCESS PANEL
L
W
H
ALTERNATE HIGH VOLTAGE CONNECTION (KNOCKOUT) 1
1
1
/320[34 mm]
SERVICE FITTINGS
LOW VOLTAGE CONNECTION
7
/8" [22 mm]
HIGH VOLTAGE CONNECTION 1
11
/32" [34 mm]
LIQUID LINE CONNECTION
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 24" [610 mm] CLEARANCE ONE SIDE
2
7
/8" [73 mm] DIA. ACCESSORY KNOCKOUTS
VAPOR LINE CONNECTION
HIGH PRESSURE CONTROL MANUAL RESET (FIELD INSTALLED ACCESSORY)
A
-000
03
A-00002
BOTTOM VIEW SHOWING DEFROST CONDENSATE DRAIN OPENINGS (\\\\\\
SHADED AREAS).
2.3 DIMENSIONS (SEE FIGURE 1)
IGURE 1
F
DIMENSIONS AND INSTALLATION CLEARANCES
IR DISCHARGE
A
LLOW 60” [1524 mm] CLEARANCE
A
ACCESS PANEL
W
ALTERNATE HIGH VOLTAGE
CONNECTION (KNOCKOUT)
111⁄32" [34 mm]
UNIT MODEL NUMBER EXPLANATION
(-)PNL – 036*AZ
COOLING CONNECTION FITTING Z-SWEAT WITH SCROLL
- COMPRESSOR
Z
ARIATIONS
V A - SERIES = FULL-FEATURED
ELECTRICAL DESIGNATION
= 208/230V-1-60
J
= 208/230V-3-60 (Available only on (-)PNL
C
= Models)
H
AIR INLETS (LOUVERS) ALLOW 6" [153 mm] MIN. CLEARANCE 3 SIDES
C
= 460V-3-60 (Available only on (-)PNL
D
= Models)
D
OOLING CAPACITY
C
18 = 18,000 BTU/HR
0 024 = 24,000 BTU/HR
30/031 = 30,000 BTU/HR
0 036 = 36,000 BTU/HR
42/043 = 42,000 BTU/HR
0 048/049 = 48,000 BTU/HR
60 = 60,000 BTU/HR
0
ESIGN SERIES (R-410A)
D
N = STANDARD EFFICIENCY (13 SEER)
= HIGH EFFICIENCY (14 SEER)
P
ALLOW 24" [610 mm] ACCESS CLEARANCE
P = REMOTE HEAT PUMP
TRADENAME
BASE PAN
REQUIRED PUMP-UP INSTALLATION LOCATIONS
NOTE: SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 24” [610 mm] CLEARANCE ON SIDE
DIMENSIONAL DATA
(-)PNL
(-)PPL
HEIGHT “H” (INCHES) [mm] LENGTH “L” (INCHES) [mm]
WIDTH“W” (INCHES) [mm]
018, 024, 031
018, 024
19” [482]
40-1/2” [1028]
27-5/8” [701]
030
19” [482]
44-3/8” [1127]
31-1/2” [800]
030, 043, 049
036, 042, 048, 060
036, 042, 048, 060
29” [736]
44-3/8” [1127]
33” [838]
44-3/8” [1127]
31-1/2” [800] 31-1/2” [800]
5
Page 6
2.4 ELECTRICAL & PHYSICAL DATA (SEE TABLES 1 & 2)
TABLE 1
-)PNL ELECTRICAL AND PHYSICAL DATA
(
ELECTRICAL
Model
Number
(-)PNL-
v. 12/16/2008
018JAZ 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 8.18 (0.76) 1 1925 [908] 83 [2353] 155 [70.3] 165 [74.8] 024JAZ 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 8.18 [0.76] 1 1925 [908] 86 [2438] 155 [70.3] 165 [74.8]
30JAZ 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 20.13 [1.87] 1 2650 [1251] 133 [3771] 200 [90.7] 210 [95.3]
0
31JAZ 1-60-208/230 14.1/14.1 73 0.6 20/20 25/25 30/30 13 [1.21] 1 1925 [908] 101 [2863] 164.5 [74.6] 174.5 [79.2]
0
36CAZ 3-60-208/230 13.2/13.2 88 1.2 18/18 25/25 30/30 23.01 [2.14] 1 3575 [1687] 145 [4111] 246.5 [111.8] 256.5 [116.3]
0
36DAZ 3-60-460 6 44 0.6 9 15 15 23.01 [2.14] 1 3575 [1687] 145 [4111] 246.5 [111.8] 256.5 [116.3]
0
36JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 23.01 [2.14] 1 3575 [1687] 145 [4111] 246.5 [111.8] 256.5 [116.3]
0 042CAZ 3-60-208/230 13.6/13.6 83.1 1.2 19/19 25/25 30/30 23.01 [2.14] 1 3575 [1687] 160 [4536] 257 [116.6] 267 [121.1] 042DAZ 3-60-460 6.1 41 0.6 9 15 15 23.01 [2.14] 1 3575 [1687] 160 [4536] 257 [116.6] 267 [121.1]
042JAZ 1-60-208/230 20.5/20.5 109 1.2 27/27 35/35 45/45 23.01 [2.14] 1 3575 [1687] 160 [4536] 257 [116.6] 267 [121.1] 043CAZ 3-60-208/230 13.6/13.6 83.1 1 18/18 25/25 35/35 20.1 [1.87] 1 2650 [1251] 168 [4763] 227 [103] 237 [107.5]
43DAZ 3-60-460 6.1 41 0.6 10 15 15 20.1 [1.87] 1 2650 [1251] 168 [4763] 227 [103] 237 [107.5]
0
43JAZ 1-60-208/230 20.5/20.5 109 1 27/27 35/35 45/45 20.1 [1.87] 1 2650 [1251] 168 [4763] 227 [103] 237 [107.5]
0
48CAZ 3-60-208/230 13.7/13.7 83.1 1.2 19/19 25/25 30/30 23.01 [2.14] 1 3575 [1687] 160 [4536] 246 [111.6] 256 [116.1]
0 048DAZ 3-60-460 6.2 41 0.6 9 15 15 23.01 [2.14] 1 3575 [1687] 160 [4536] 246 [111.6] 256 [116.1]
48JAZ 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3575 [1687] 160 [4536] 246 [111.6] 256 [116.1]
0
49CAZ 3-60-208/230 13.7/13.7 83.1 1 19/19 25/25 30/30 20.1 [1.87] 1 2650 [1251] 157 [4451] 229 [103.9] 239 [108.4]
0 049DAZ 3-60-460 6.2 41 0.6 9 15 15 20.1 [1.87] 1 2650 [1251] 157 [4451] 229 [103.9] 239 [108.4]
049JAZ 1-60-208/230 21.8/21.8 117 1 29/29 35/35 50/50 20.1 [1.87] 1 3575 [1687] 157 [4451] 229 [103.9] 239 [108.4] 060CAZ 3-60-208/230 15.6/15.6 110 1.2 21/21 25/25 35/35 23.01 [2.14] 1 3350 [1581] 242 [6861] 260 [117.9] 270 [122.5] 060DAZ 3-60-460 7.8 52 0.6 11 15 15 23.01 [2.14] 1 3350 [1581] 242 [6861] 260 [117.9] 270 [122.5]
60JAZ 1-60-208/230 26.3/26.3 134 1.2 35/35 45/45 60/60 23.01 [2.14] 1 3350 [1581] 242 [6861] 260 [117.9] 270 [122.5]
0
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. (m
Outdoor Coil
No.
2
)
Rows
CFM [L/s]
PHYSICAL
Refrig.
Circuit Oz. [g]
Per
Net
Lbs. [kg]
Weight
Shipping Lbs. [kg]
TABLE 2
(-)PPL ELECTRICAL AND PHYSICAL DATA
Model
Number
(-)PPL-
Phase Frequency (Hz)
Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
ELECTRICAL
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. (m
Outdoor Coil
No.
2
)
Rows
CFM [L/s]
PHYSICAL
Refrig.
Per Circuit Oz. [g]
Net
Lbs. [kg]
Weight
Shipping Lbs. [kg]
018JAZ 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 8.18 [0.76] 1 1925 [908] 83 [2353] 156 [70.8] 166 [75.3] 024JAZ 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 8.18 [0.76] 1 1925 [908] 86 [2438] 156 [70.8] 167 [75.8] 030JAZ 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 12.87 [1.2] 1 1925 [908] 101 [2863] 175 [79.4] 186 [84.4] 036JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 23.01 [2.14] 1 3575 [1687] 145 [4111] 246 [111.6] 256 [116.1] 042JAZ 1-60-208/230 20.5/20.5 109 1.2 27/27 35/35 45/45 23.01 [2.14] 1 3575 [1687] 160 [4536] 256 [116.1] 266 [120.7] 048JAZ 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3575 [1687] 160 [4536] 258 [117] 268 [121.6] 060JAZ 1-60-208/230 26.3/26.3 134 1.2 35/35 45/45 60/60 44 [4.09] 1 3100 [1463] 277 [7853] 308 [139.7] 318 [144.2]
2.5 PROPER INSTALLATION
Proper sizing and installation of this equipment is critical to achieve optimal perfor­mance. Use the information in this Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENER­GY STAR nents. However, proper refrigerant charge and proper airflow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufac­turer’s refrigerant charging and airflow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
®
criteria for energy efficiency when matched with appropriate coil compo-
6
Page 7
3.0 LOCATING UNIT
3.1 CORROSIVE ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
WARNING
!
Disconnect all power to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with an automobile polish will pro­vide some protection.
A liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coil coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
3.2 HEAT PUMP LOCATION
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor heat pump.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perfor­mance or operation.
3.3 OPERATIONAL ISSUES
IMPORTANT: Locate the unit in a manner that will not prevent, impair or com­promise the performance of other equipment horizontally installed in proximity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or manaufacturers’ recommendations, local code recommendations and require­ments will take presidence.
Refrigerant piping and wiring should be properly sized and kept as short as possible to avoid capacity losses and increased operating costs.
Locate the unit where water run off will not create a problem with the equip­ment. Position the unit away from the drip edge of the roof whenever possible. Units are weatherized, but can be affected by the following:
o Water from the junction of rooflines, without protective guttering, entering the
heat pump while in operation, can impact fan blade or motor life. Coil dam­age may occur to a heat pump if moisture cannot drain from the unit under freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which generally results in less economical operation.
Closely follow clearance recommendations (see Figure 1). o 24” to the service panel access o 60” above heat pump fan discharge (unit top) to prevent recirculation
o 6” to heat pump coil grille air inlets (per heat pump).
7
Page 8
FIGURE 2
ECOMMENDED ELEVATED INSTALLATION
R
ELEVATION ABOVE ANTICIPATED SNOW­’FALL IS NECESSARY.
O NOT BLOCK
D
PENINGS IN BASE
O
AN. REFER TO
P
IGURE 1.
F
3.4 FOR UNITS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances: Single Unit Applications: Heat pump grille side clearances below 6 inches will
reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24­inch service clearances.
Multiple Unit Applications: When multiple heat pump grille sides are aligned, a 6­inch per unit clearance is recommended, for a total of 12 inches between multiple units. Two combined clearances below 12 inches will reduce capacity and efficien­cy. Do not reduce the 60-inch discharge, or 24-inch service clearances.
Do not obstruct the bottom drain opening in the heat pump base pan. It is essential to provide defrost condensate drainage to prevent possible refreezing of the condensation. Provide a base pad for mounting the unit, which is slightly pitched away from the structure. Route condensate off the base pad to an area which will not become slippery and result in personal injury.
Where snowfall is anticipated, the heat pump must be elevated above the base pad to prevent ice buildup that may crush the tubing of the heat pump coil or cause fin damage. Heat pump units should be mounted above the average expected accumulated snowfall for the area.
8
3.5 CUSTOMER SATISFACTION ISSUES
The heat pump should be located away from the living, sleeping and recre­ational spaces of the owner and those spaces on adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from entering the unit.
3.6 UNIT MOUNTING
If eleva ting th e heat pump, either on a flat roof or on a slab, observe the following guidelines. (See Figure 2.)
The base pan provided elevates the heat pump 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration.
NOTE: Do not block drain openings shown in Figure 1.
If unit must be elevated because of anticipated snow fall, secure unit and ele­vating stand such that unit and/or stand will not tip over or fall off.
CAUTION
!
Secure elevated unit and elevating stand in order to prevent tipping. Failure to do this may result in minor or moderate injury.
Page 9
3.7 FACTORY-PREFERRED TIE-DOWN METHOD INSTRUCTIONS
IMPORTANT: These instructions are intended as a guide to securing equipment for wind-load ratings of “120 MPH sustained wind load” and “3-second, 150 MPH gust.” While this procedure is not mandatory, the Manufacturer does recommend that equipment be properly secured in areas where high wind damage may occur.
STEP 1: Before installing, clear pad of any dirt or debris.
STEP 2: Center base pan on pad, ensuring it is level. STEP 3: Using basepad as a guide, mark spots on concrete where 4 holes will be
STEP 4: Drill four pilot holes in pad, ensuring that the hole is at least 1/4” deeper
STEP 5: Center basepan over pre-drilled holes and insert concrete screws. STEP 6: Tighten concrete screws.
STEP 7: Finish unit assembly per unit’s installation instructions.
IMPORTANT: The pad must be constructed of industry-approved materials, and must be thick enough to accommodate the concrete fastener.
drilled (see Figure 3).
than the concrete screw being used.
NOTE: Do not over-tighten the concrete screws. Doing so can weaken the integrity of the concrete screw and cause it to break.
FIGURE 3
SCREW LOCATIONS ON BASEPAN
TABLE 3
BASEPAN DIMENSIONS
MODEL NUMBER LWAB CD
PNL-018/024, PPL-018/024 37.625” 25.938” 15” 34” 3.5” 22.5”
PNL-030/031/036/042/043/048/049/060, PPL-030/036/042/048/060
41.5” 29.813” 15” 38” 3.5” 26.5”
9
Page 10
4.0 REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
5.0 REPLACEMENT UNITS
To prevent failure of a new heat pump unit, the existing tubing system must be cor­rectly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized. Test the oil for acid. If positive, a liquid line filter drier is mandatory.
6.0 INDOOR COIL
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUC­TIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
6.1 LOCATION
Do not install the indoor coil in the return duct system of a gas or oil furnace. Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched toward the drain connection.
CAUTION
When coil is installed over a finished ceiling and/or living area, it is recomm e n d e d that a se c onda r y she e t met a l con d e n s ate pan be constructed and installed under entire unit. Failure to do so may result in property damage.
7.0 INTERCONNECTING TUBING
7.1 VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made.
Make connections at the indoor coil first.
Refer to Line Size Information in Tables 4 and 5 for correct size and multipliers to be used to determine capacity for various vapor line diameters and lengths of run. The losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for 15 feet of inter­connecting lines. The factory refrigeration charge in the outdoor unit is sufficient for the unit and 15 feet of standard size interconnecting liquid and vapor lines. For dif­ferent lengths, adjust the charge as indicated below.
1/4” ± .3 oz. per foot
5/16” ± .4 oz. per foot
3/8” ± .6 oz. per foot
1/2” ± 1.2 oz. per foot
10
7.2 MAXIMUM LENGTH OF LINES
The maximum length of interconnecting line is 150 feet. Always use the shortest length possible with a minimum number of bends. Additional compressor oil is not required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
Page 11
7.3 VERTICAL SEPARATION
Keep the vertical separation to a minimum. Use the following guidelines when installing the unit:
1. DO NOT exceed the vertical separations as indicated on Table 5.
2. It is recommended to use the smallest liquid line size permitted to minimize sys-
tem charge which will maximize compressor reliability.
3. Table 5 may be used for sizing horizontal runs.
7.4 TUBING INSTALLATION
Observe the following when installing correctly sized type “L” refrigerant tubing between the condensing unit and evaporator coil:
If a portion of the liquid line passes through a hot area where liquid refrigerant
can be heated to form vapor, insulating the liquid line is required.
Use clean, dehydrated, sealed refrigeration grade tubing.
Always keep tubing sealed until tubing is in place and connections are to be
made.
Blow out the liquid and vapor lines with dry nitrogen before connecting to the
outdoor unit and indoor coil. Any debris in the line set will end up plugging the expansion device.
As an added precaution, a high quality, bi-directional filter drier is recommend-
ed to be installed in the liquid line, if not factory installed.
Do not allow the vapor line and liquid line to be in contact with each other. This
causes an undesirable heat transfer resulting in capacity loss and increased power consumption. The vapor line must be insulated.
If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes.
For best operation, keep tubing run as short as possible with a minimum num-
ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
The vapor line must be insulated to prevent dripping (sweating) and prevent
performance losses. Armaflex and Rubatex are satisfactory insulations for this purpose. Use 1/2” minimum insulation thickness, additional insulation may be required for long runs.
Check Table 4 for the correct vapor line size. Check Table 5 for the correct liq-
uid line size.
11
Page 12
TABLE 4
SUCTION LINE LENGTH/SIZE VS. CAPACITY MULTIPLIER (R-410A)
1
1
Unit Size
Suction Line
Connection Size
Suction Line Run -
Feet [m]
ptional
O
tandard
S
5’
2
ptional
O
Optional
0’
5
Standard
Optional
Optional
100’
150’
OTES:
N
Standard
*
ote: Using suction line larger than shown in chart will result in poor oil return and is not recommended
N
Standard
Optional
Optional
Standard
Optional
2 Ton
/4
.D.
3
I
"
5/8
3/4*
.00 1.00 1.00 1.00 1.00 1.00 1.00
1
.00 1.00 1.00 1.00 1.00 1.00 1.00
1
.98 0.98 0.96 0.98 0.99 0.99 0.99
0
.99 0.99 0.98 0.99 0.99 0.99 0.99
0
——0.99 ————
.95 0.95 0.94 0.96 0.96 0.96 0.97
0
.96 0.96 0.96 0.97 0.98 0.98 0.98
0
——0.97 ————
.92 0.92 0.91 0.94 0.94 0.95 0.94
0
.93 0.94 0.93 0.95 0.96 0.96 0.97
0
2 Ton
/4
.D.
3
I
"
/8 5/8
5
3/4* 3/4*
7/8*
1.00 ————
0.95 ————
2
3
1
2 Ton
/4
"
3 Ton
/8
.D.
I
.D.
7
I
"
/4
3
7/8*
7.5 TUBING CONNECTIONS
Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed until connections are to be made.
Use type “L” copper refrigeration tubing. Braze the connections with accepted industry practices.
Be certain both refrigerant shutoff valves at the outdoor unit are closed.
Clean the inside of the fittings before brazing.
Remove the cap and schrader core from service port to protect seals from heat damage.
Use an appropriate heatsink material around the copper stub and the service valves before applying heat.
IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen into a service port and through the tubing while brazing.
The service valves are not backseating valves. To open the valves, remove the valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the stem. Back out counterclockwise.
Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a metal-to-metal seal.
3
7
1
2 Ton
/8
"
/4
3
7/8*
4 Ton
.D.
I
7/8"I.D.
/8
7
1 1/8*
5 Ton
/8
7
1 1/8*
.D.
I
"
/8
7
12
7.6 LEAK TESTING
Pressurize line set and coil through service fittings with dry nitrogen to 150 PSIG maximum. Leak test all joints using liquid detergent. If a leak is found, relieve pressure and repair.
WARNING
!
Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death.
Page 13
TABLE 5
LIQUID LINE SIZE — OUTDOOR UNIT ABOVE OR BELOW INDOOR COIL
Outdoor unit above or below indoor coil
(Heat Pumps Only)
Total Equivalent Length - Feet
aximum Vertical Separation - Feet
M
System
apacity
C
Line Size
Connection
ize
S
(Inch I.D.)
Line Size
Inch OD)
(
25 50 75 100 125 150
1/4 25 40 25 9 N/A N/A
Liquid Line Size
1
1
2 Ton 3/8” 5/16 25 50 62 58 53 49
3/8* 25 50 75 72 70 68
1/4 23 N/A N/A N/A N/A N/A
2 Ton 3/8” 5/16 25 36 29 23 16 9
3/8* 25 50 72 70 68 65
1/4 25 N/A N/A N/A N/A N/A
1
2
2 Ton 3/8” 5/16 25 49 38 27 17 6
3/8* 25 50 68 65 62 58
3 Ton 3/8”
1
2 Ton 3/8”
3
4 Ton 3/8”
5 Ton 3/8”
NOTES:
*Standard N/A = Application not recommended
5/16 25 50 37 22 7 N/A
3/8* 25 50 68 63 58 53
5/16 25 23 4 N/A N/A N/A
3/8* 25 50 43 36 30 24 3/8* 25 46 38 30 22 15
1/2 25 50 56 55 53 52
3/8* 25 50 56 44 32 20
1/2 25 50 75 81 79 76
13
Page 14
8.0 DEMAND DEFROST CONTROL AND HIGH/LOW
PRESSURE CONTROLS
The demand defrost control is a printed circuit board assembly consisting of solid state control devices with electro-mechanical outputs. The demand defrost control monitors the outdoor ambient temperature, outdoor coil temperature, and the com­pressor run-time to determine when a defrost cycle is required.
Enhanced Feature Demand Defrost Control (part number 47-2157-22): Found in units with models numbers ending in “AZ” and units equipped with the field installed Enhanced Compressor Protection Kit (RXPG-A02). Has high and low pres­sure control inputs with unique pressure switch logic built into the microprocessor to
rovide compressor and system protection without nuisance lock-outs. Cycles the
p compressor off for 5 seconds at the beginning and end of the defrost cycle to elimi­nate the increased compressor noise caused by rapidly changing system pressures when the reversing valve switches. See section 8.7 for diagnostic flash codes for the two diagnostic LED’s provided on the control.
8.1 DEFROST INITIATION
A defrost will be initiated when the three conditions below are satisfied:
1) The outdoor coil temperature is below 35°F.
2) The compressor has operated for at least 34 minutes with the outdoor coil tem-
perature below 35°F.
3) The measured difference between the ambient temperature and the outdoor
coil temperature is greater than the calculated delta T.
Additionally, a defrost will be initiated if six hours of accumulated compressor run­time has elapsed without a defrost with the outdoor coil temperature below 35°F.
8.2 DEFROST TERMINATION
Once a defrost is initiated, the defrost will continue until fourteen minutes has elapsed or the coil temperature has reached the terminate temperature. The termi­nate temperature is factory set at 70°F, although the temperature can be changed to 50°F, 60°F, 70°F or 80°F by relocating a jumper on the board.
8.3 TEMPERATURE SENSORS
The coil sensor is clipped to the top tube on the outdoor coil at the point feed by the distribution tubes from the expansion device (short 3/8” dia. tube). The air sensor is located on the defrost control board.
If the ambient sensor fails the defrost control will initiate a defrost every 34 minutes with the coil temperature below 35°F.
If the coil sensor fails the defrost control will not initiate a defrost.
8.4 TEST MODE
The test mode is initiated by shorting the TEST pins. In this mode of operation, the enable temperature is ignored and all timers are sped up by a factor of 240. To initi­ate a manual defrost, short the TEST pins. Remove the short when the system switches to defrost mode. The defrost will terminate on time (14 minutes) or when the termination temperature has been achieved. Short TEST pins again to termi­nate the defrost immediately.
8.5 TROUBLE SHOOTING DEMAND DEFROST
Set the indoor thermostat select switch to heat and thermostat lever to a call for heat.
Jumper the “test pins” to put the unit into defrost. If the unit goes into defrost and comes back out of defrost, the indication is that the control is working properly.
If the unit did not go into defrost using the test pins, check to ensure that 24V is being supplied to the control board. If 24V is present then replace the control.
14
Page 15
8.6 HIGH/LOW PRESSURE CONTROL MONITORING - ENHANCED DEFROST CONTROL ONLY (Units with Model Numbers Ending with “AZ”).
Status of high and low pressure controls is monitored by the enhanced feature demand defrost control and the following actions are taken.
igh Pressure Control – Provides active protection in both cooling and heating
H
modes at all outdoor ambient temperatures. The high pressure control is an auto­matic reset type and opens at approximately 610 psig and closes at approximately 420 psig. The compressor and fan motor will stop when the high pressure control opens and will start again if the high side pressure drops to approximately 420 psig when the automatic reset high pressure control resets. If the high pressure control opens 3 times within a particular call for heating or cooling operation, the defrost control will lock out compressor and outdoor fan operation.
Low Pressure Control – Provides active protection in both heating and cooling modes at all outdoor ambient temperatures. The low pressure control is an auto­matic reset type and opens at approximately 25 psig and closes at approximately 40 psig. Operation is slightly different between cooling and heating modes.
Cooling Mode: The compressor and fan motor will stop when the low pressure control opens and will start again when the low side pressure rises to approxi­mately 40 psig when the low pressure control automatically resets. If the low pressure switch opens 3 times within a particular call for cooling operation, the defrost control will lock out compressor and outdoor fan operation.
Heating Mode: The compressor and fan motor will stop when the low pressure control opens and will start again when the low side pressure rises to approxi­mately 40 psig when the low pressure control automatically resets. If the low pressure switch trips 3 times within 120 minutes of operation during a particular call for heating operation, the defrost control will lock out compressor and out­door fan operation. If the lock-out due to low pressure occurs at an outdoor ambient temperature below 5°F, the defrost control will automatically exit the lock-out mode when the outdoor ambient temperature rises to 5°F. This feature is necessary since the low pressure control could possibly have opened due to the outdoor ambient being very low rather than an actual system fault.
Exiting Lock-Out Mode: To exit the lock-out mode, remove 24 volts to the defrost
control by removing power to indoor air-handler/furnace or by shorting the two defrost control test pins together.
8.7 ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC CODES
LED 1 LED 2 Control Board Status
OFF OFF No Power ON ON Coil Sensor Failure OFF ON Ambient Sensor Failure FLASH FLASH Normal OFF FLASH Low Pressure Lockout (short test pins to reset) FLASH OFF High Pressure Lockout (short test pins to reset) ON FLASH Low Pressure Control Open FLASH ON High Pressure Control Open
Alternate Flashing 5 Minute Time Delay
9.0 EVACUATION PROCEDURE
The life and efficiency of the equipment is dependent upon the thoroughness exer­cised by the technician when evacuating air and moisture from the system.
Air in the system causes high condensing temperatures and pressure, resulting in increased power input and non-verifiable performance.
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric and hydrochloric acids. These attack motor windings and parts, causing breakdown.
After the system has been leak checked and proven sealed, connect the vacuum pump and evacuate system to 500 microns. The vacuum pump must be connected
15
Page 16
to both the high and low sides of the system through adequate connections. Use the largest size connections available since restrictive service connections may lead to false readings because of pressure drop through the fittings.
IMPORTANT: Compressors (especially scroll type) should never be used to evacu­ate the heat pump system because internal electrical arcing may result in a dam­aged or failed compressor.
10.0 START UP AND PERFORMANCE
Even though the unit is factory-charged with Refrigerant R-410A, the charge must be checked to the charge table on the service panel and adjusted, if required. (See Tables 1 and 2.) Allow the unit to run for a minimum of five minutes. Before analyz­ing charge, see the instructions on the unit service panel rating plate for marking the total charge.
11.0 CHECKING AIRFLOW
The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures.
Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet air­flow to all rooms in the home. This ensures a comfortable living space.
An air velocity meter or airflow hood can give a reading of the system CFM’s.
12.0 CHECKING REFRIGERANT CHARGE
Charge for all systems should be checked against the Charging Chart inside the access panel cover.
IMPORTANT: Do not operate the compressor without charge in system. Addition of R-410A will raise pressures (vapor, liquid and discharge). If adding R-410A raises both vapor pressure and temperature, the unit is over-
charged. IMPORTANT: Use industry-approved charging methods to ensure proper system
charge.
12.1 CHARGING BY LIQUID PRESSURE
Liquid pressure method is used for charging systems in the cooling and heating mode. The service port on the liquid service valve (small valve) and suction (large valve) is used for this purpose.
Verify that the outdoor unit is running and the indoor air mover is delivering the maximum airflow for this system size. Read and record the outdoor ambient tem­perature. Read and record the liquid and suction pressures at the ports on the liquid and suction valves. If refrigerant lines are sized using the nameplate charge, the correct liquid pressure is found at the intersection of the suction pressure and the outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
12.2 CHARGING BY WEIGHT
For a new installation, evacuation of interconnecting tubing and indoor coil is ade­quate; otherwise, evacuate the entire system. Use the factory charge shown in Tables 1 through 6 of these instructions or unit data plate. Note that charge value includes charge required for 15 ft. of standard size interconnecting liquid line.
16
Page 17
Calculate actual charge required with installed liquid line size and length using: 1/4” O.D. = .3 oz./ft.
5/16” O.D. = .4 oz./ft. 3/8” O.D. = .6 oz./ft. 1/2” O.D. = 1.2 oz./ft.
With an accurate scale (+/– 1 oz.) or volumetric charging device, adjust charge dif­ference between that shown on the unit data plate and that calculated for the new system installation. If the entire system has been evacuated, add the total calculat­ed charge.
12.3 FINAL LEAK TESTING
After the unit has been properly evacuated and charged, a halogen leak detector should be used to detect leaks in the system. All piping within the condensing unit, evaporator, and interconnecting tubing should be checked for leaks. If a leak is detected, the refrigerant should be recovered before repairing the leak. The Clean Air Act prohibits releasing refrigerant into the atmosphere.
13.0 ELECTRICAL WIRING
WARNING
!
Turn off electric power at the fuse box or service panel before making any electrical connections.
Also, the ground connection must be completed before making line volt­age connections. Failure to do so can result in electrical shock, severe personal injury or death.
!
Single-pole contactors are used on all standard single-phase units up through 5 tons. Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor.
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local code.
13.1 POWER WIRING
It is important that proper electrical power from a commercial utility is available at the condensing unit contactor. Voltage ranges for operation are shown in Table 6.
Install a branch circuit disconnect within sight of the unit and of adequate size to handle the starting current (see Tables 1 and 2).
Power wiring must be run in a rain-tight conduit. Conduit must be run through the connector panel below the access cover (see Figure 1) and attached to the bottom of the control box.
Connect power wiring to contactor located in outdoor condensing unit electrical box. (See wiring diagram attached to unit access panel.)
Check all electrical connections, including factory wiring within the unit and make sure all connections are tight.
DO NOT connect aluminum field wire to the contactor terminals.
TABLE 6
VOLTAGE RANGES (60 HZ)
Nameplate Voltage Maximum Load Design Conditions for
208/230 (1 Phase) 187 - 253
208/230 (3 Phase) 187 - 253
CAUTION
Operating Voltage Range at Copeland
Compressors
460 414 - 506
575 517 633
17
Page 18
13.2 GROUNDING
FIGURE 4
CONTROL WIRING FOR AIR HANDLER
B
W2
G
Y
W1
B
ODD
C
R
Air Handler
Y
G
W2
E
Heat Pump Thermostat
Heat Pump Outdoor Unit
C
R
Y
B
R
D
C
Y
F
ield Installed
L
ine Voltage
-
W
IRING INFORMATION
Factory Standard
-
W
H/BL
GR/BK
YL
WH/BK
GR/YL
BR
BL
RD
YL/BL
Optional Field Installed Jumper (see note 1)
1
*
*
*
2
*Not present on all air-handler models.
OPTIONAL
- 1 STAGE HEAT
YL
BR
B
L
RD
P
R
NOTES:
1. Jumper “E” to “W2” on thermostat to transfer control of supplemental heat to 1st stage when the emergency heat switch is on.
2. This wire turns on elec­tric heat strip during defrost, omit for most economical operation.
WIRE COLOR CODE
BK = BLACK BL = BLUE BR = BROWN GR = GREEN PR = PURPLE RD = RED WH = WHITE YL = YELLOW
A grounding lug is provided near the contactor for a ground wire.
WARNING
!
The unit must be permanently grounded. Failure to do so can cause elec­trical shock resulting in severe personal injury or death.
13.3 CONTROL WIRING
(See Figure 4)
If the low voltage control wiring is run in conduit with the power supply, Class I insu­lation is required. Class II insulation is required if run separate. Low voltage wiring may be run through the insulated bushing provided in the 7/8 hole in the base panel, up to and attached to the pigtails from the bottom of the control box. Conduit can be run to the base panel if desired by removing the insulated bushing.
A thermostat and a 24 volt, 40 VA minimum transformer are required for the control circuit of the condensing unit. The furnace or the air handler transformer may be used if sufficient. See the wiring diagram for reference. Use Table 7 to size the 24 volt control wiring.
18
TABLE 7
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.
3.0 16 14 12 10 10 10
2.5 16 14 12 12 10 10
2.0 18 16 14 12 12 10
50 100 150 200 250 300
Thermostat Load - Amps
(1) Wire length equals twice the run distance.
NOTE: Do not use control wiring smaller than No. 18 AWG between thermostat and outdoor unit.
14.0 FIELD INSTALLED ACCESSORIES
14.1 COMPRESSOR CRANKCASE HEATER (CCH)
While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added. Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase heater to minimize refrigeration migration, and to help eliminate any start up noise or bearing “wash out.”
Length of Run - Feet (1)
Page 19
NOTE: The installation of a crankcase heater is recommended if the system charge
exceeds the values in Table 8. All 3-phase models come with a crankcase heater facto­ry installed.
ABLE 8
T
AXIMUM SYSTEM CHARGE VALUES: (-)PNL/(-)PPL
M
Model Compressor Without
Size* Model Number Crankcase Heater*
-018 ZP16K5E 8.0 lbs.
-024 ZP21K5E 8.0 lbs.
-030/-031 ZP25K5E 8.0 lbs.
-036 ZP34K5E 10.0 lbs.
-042/-043 ZP38K5E 10.0 lbs.
-048/-049 ZP42K5E 10.0 lbs.
*-060 comes with the crankcase heater factory-installed.
Charge Limit
All heaters are located on the lower half of the compressor shell. Its purpose is to drive refrigerant from the compressor shell during long off cycles, thus preventing damage to the compressor during start-up.
At initial start-up or after extended shutdown periods, make sure the heater is energized for at least 12 hours before the compressor is started. (Disconnect switch on and wall thermostat off.)
14.2 TIME DELAY CONTROL (TDC)
The time delay (TDC) is in the low voltage control circuit. When the compressor shuts off due to a power failure or thermostat operation, this control keeps it off at least 5 minutes which allows the system pressure to equalize, thus not damaging the compressor or blowing fuses on start-up.
14.3 LOW AMBIENT CONTROL (LAC) – RXAD-A08
This component senses compressor head pressure and shuts the heat pump fan off when the head pressure drops to approximately 220 PSIG. This allows the unit to build a sufficient head pressure at lower outdoor ambient (down to 0°F) in order to maintain sys­tem balance and obtain improved capacity. Low ambient control should be used on all equipment operated below 70°F ambient.
19
Page 20
15.0 TROUBLE SHOOTING
In diagnosing common faults in the heat pump system, develop a logical thought pattern as used by experienced technicians. The charts which follow are not intend­ed to be an answer to all problems but only to guide the technician’s thinking. Through a series of yes and no answers, follow the logical path to a likely conclu­sion.
A novice technician should use these charts like a road map. Remember that the
hart should clarify a logical path to the problem’s solution.
c
15.1 ELECTRICAL CHECKS FLOW CHART
Unit Running?
NO YES
Thermostat Problem? Go to
YES NO for Cooling or Heating
Repair and Recheck
Transformer Problem?
YES NO
Repair and Recheck
Voltage on Compressor
Side of Contactor?
YES NO
Run Capacitor Voltage on Line
Start Capacitor
NO YES
Potential Relay
Circuit Breakers Compressor Contactor Failure
Compressor Internal or Fuses Open
Overload Open Hi Pressure Cut-Out/Lock-Out
YES
Mechanical Checks
Side of Contactor?
(see section 8.6 & 8.7)
Compressor Winding Open Low Pressure Cut-Out/Lock-Out
Unit Wiring and Grounded Compressor Time-Delay
Connections
20
Compressor Winding
(see section 8.6 & 8.7)
Outdoor Fan Motor Unit Wiring and
Grounded Connections
Grounded Capacitor
Replace Fuses
or Reset Breakers
and Recheck System
Page 21
15.2 COOLING MECHANICAL CHECKS FLOW CHART
Unit Running?
Y
ES NO
Pressure problems? Checks Flow Chart
High Head Pressure Low Head Pressure Low Suction Pressure
Dirty Outdoor Coil Low on Charge Dirty Filters
Inoperative Outdoor Fan Open IPR Valve Dirty Indoor Coil
Overcharge Low Ambient Temperature Inadequate Indoor Air Flow
Recirculation of Inoperative Compressor Broken Indoor
Outdoor Air Valves Blower Belt
Non-condensibles Outdoor Check Valve Inoperative Indoor Blower
Closed
Higher than Ambient Low on Charge
Air Entering Outdoor Coil
Restricted Indoor Restricted Indoor
Wrong Outdoor Fan Rotation Metering Device Metering Device
Go to Electrical
Restricted Restriction in System Filter Drier
Reversing Valve Indoor Air
Failure
Recirculation of
Wrong Indoor
Blower Rotation
Inadequate Ducts
Outdoor Check Valve Closed
Restricted Filter Drier
21
Page 22
15.3 HEATING MECHANICAL CHECKS FLOW CHART
Unit Running?
YES NO
Pressure problems? Checks Flow Chart
High Head Pressure Low Head Pressure Low Suction Pressure
Dirty Filters Low on Charge Dirty Outdoor Coil
Dirty Indoor Coil Low Indoor Temperature Inadequate Air Flow
Inoperative Indoor Blower Open IPR Valve
Closed Indoor Inoperative OD Fan
Overcharge Check Valve (Check Defrost Control)
Inadequate Indoor Inoperative Compressor Low On Charge
Air Flow Valves
Non-condensibles Restricted Outdoor Restricted Outdoor
Metering Device Metering Device
Broken Indoor
Blower Belt Restricted Restriction in System
Filter Drier
Go to Electrical
Over Outdoor Coil
Wrong Indoor Blower Rotation Closed Indoor Check Valve
Inadequate Ducts Recirculation of Outdoor Air
Reversing Valve
Failure
Restricted Filter Drier
22
Page 23
15.4 DEFROST MECHANICAL CHECKS FLOW CHART
DEFROST SYSTEM
No Defrost Incomplete Defrost Excessive Defrost
Reversing Valve Stuck Poor Sensor Location Wrong Defrost Control
No Defrost Timer Wrong Defrost Control
Control Power Timer Setting Poor Sensor Location
Failed Defrost Control Failed Defrost Relay Low System Charge
(doesn’t stop O.D. Fan)
Failed Defrost Relay Thermostat Satisfies Wind Affecting
During Defrost in Defrost
Loose Defrost
Sensor
Timer Setting
23
Page 24
TABLE 10
TEMPERATURE PRESSURE CHART
TEMP R-410A
(Deg. F) PSIG
-150
-140
-130
-120
-110
-100
-90 — 80
-
-70
-60 0.4
-50 5.1
-40 10.9
-35 14.2
-30 17.9
-25 22.0
-20 26.4
-15 31.3
-10 36.5
-5 42.2 0 48.4 5 55.1
10 62.4 15 70.2 20 78.5 25 87.5 30 97.2 35 107.5 40 118.5 45 130.2 50 142.7 55 156.0 60 170.1 65 185.1 70 201.0 75 217.8 80 235.6 85 254.5 90 274.3
95 295.3 100 317.4 105 340.6 110 365.1 115 390.9 120 418.0 125 446.5 130 476.5 135 508.0 140 541.2 145 576.0 150 612.8
15.5 SUBCOOLING CALCULATION
1. Measure the liquid pressure at the liquid line service valve.
2. Convert the liquid line pressure to saturated temperature. See Table 10.
3. Measure the liquid line temperature at the liquid line service valve.
4. Compare the liquid line temperature to the saturated temperature.
5. The difference between saturated temperature and liquid line temperature is the subcooling. Subcooling normal range 9° to 12°.
NOTE: The subcooling charging method should only be used in the cooling mode as the heating subcooling design level varies widely from one unit to the next while
he cooling subcooling design level is fairly consistent at 8-12 degrees.
t
TABLE 11
EAT PUMP SYSTEM TROUBLESHOOTING TIPS
H
HEAT PUMP SYSTEM
ROUBLESHOOTING TIPS
T
SYSTEM PROBLEM
Overcharge High High Low High High
Undercharge Low Low High Low Low
Liquid Restriction (Drier) Low Low High High Low
Low Evaporator Airflow Low Low Low Low Low
Dirty Heat Pump High High Low Low High
Low Outside Ambient Temperature Low Low High High Low
Inefficient Compressor Low High High High Low
TEV Feeler Bulb Charge Lost Low Low High High Low
Poorly Insulated Sensing Bulb High High Low Low High
DISCHARGE SUCTION
PRESSURE PRESSURE AMPS
INDICATORS
SUPERHEAT SUBCOOLING
COMPRESSOR
24
Page 25
15.6 GENERAL TROUBLE SHOOTING CHART
!
WARNING
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can
ause electrical shock resulting in personal injury or death.
c
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing unit
Outdoor fan runs, compressor • Run or start capacitor defective • Replace
doesn’t • Start relay defective • Replace
Insufficient cooling • Improperly sized unit • Recalculate load
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
Registers sweat • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component
High head-high or normal vapor • Dirty outdoor coil • Clean coil
pressure - Cooling mode • Refrigerant overcharge • Correct system charge
Low head-high vapor pressures • Flowcheck piston size too large • Change to correct size piston
Low vapor pressure - cool • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
compressor - iced indoor coil filter
High vapor pressure • Excessive load • Recheck load calculation
Fluctuating head & vapor • TEV hunting • Check TEV bulb clamp - check air distribution on coil - replace
pressures TEV
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
• Thermostat out of calibration-set too high • Reset
• Defective contactor • Check for 24 volts at contactor coil - replace if contacts are open
• Blown fuses / tripped breaker • Replace fuses / reset breaker
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) or defrost • The high pressure control opens at 610 PSIG. Check for blocked
control lockout due to 3 high pressure control trips. coils, failed fan or blower motor, wiring issues, or defective high
• Low pressure control open (if provided) or defrost pressure control. See section 8.6 to reset defrost control.
control lockout due to 3 low pressure control trips. • The low pressure control opens at 25 PSIG. Check for low
charge, blocked coils, wiring issues, or defective low pressure control. See section 8.6 to reset defrost control.
• Loose connection • Check for correct voltage at compressor ­check & tighten all connections
• Compressor stuck, grounded or open motor winding, • Wait at least 2 hours for overload to reset.
open internal overload. If still open, replace the compressor.
• Low voltage condition • Add start kit components
• Improper indoor airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
nameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
filter
• Flowcheck piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
• Outdoor fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
• Defective Compressor valves • Replace compressor
• Incorrect capillary tubes • Replace coil assembly
• Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
• Low refrigerant charge • Repair leak, evacuate, & recharge.
• Defective compressor • Replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
25
Page 26
15.7 SERVICE ANALYZER CHARTS
COMPRESSOR OVERHEATING
SYMPTOMS POSSIBLE CAUSE CHECK/REMEDIES
High superheat Low charge Check system charge
Faulty metering device Restricted cap tube, TEV (TXV)
Power element superheat adjustment
Foreign matter stopping flow
High internal load Hot air (attic) entering return
eat source on; mis-wired or
H faulty control
Restriction in liquid line Drier plugged
Line kinked
Low head pressure Low charge
Operating in low ambient temperatures
Suction or liquid line subjected Hot attic to high heat source
Low voltage Loose wire connections Check wiring
Dirty or pitted compressor Replace contactor contactor contacts
Power company problem, Have problem corrected before transformer diagnosis continues
Undersized wire feeding unit Correct and complete diagnosis
High voltage Power company problem Have problem corrected
High head pressure Overcharge Check system charge
Dirty heat pump coil Clean coil
Faulty or wrong size Replace fan motor heat pump fan motor
Faulty fan blade Replace fan blade or wrong rotation
Recirculation of air Correct installation
Additional Heat Source Check for dryer vent near unit
Non-condensibles Recover refrigerant, Evacuate and
Equipment not matched Correct mis-match
Short cycling of compressor Faulty pressure control Replace pressure control
Loose wiring Check unit wiring
Thermostat Located in supply air stream
TEV Internal foreign matter
Capillary tube Restricted with foreign matter
Hot water line
Replace with correct rotation motor
Check for recirculation from other equipment
recharge system
Differential setting too close
Customer misuse
Power element failure
Valve too small
Distributor tube/tubes restricted
Kinked I.D. reduced from previous
compressor failure
26
Page 27
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Short cycling of compressor (cont.) Low charge Check system charge
ow evaporator air flow Dirty coil
L
Dirty filter
Duct too small or restricted
Faulty run capacitor Replace
Faulty internal overload Replace compressor
Faulty Compressor Valves Fast equalization/ Replace compressor and examine
Low pressure difference system to locate reason
ELECTRICAL
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Voltage present on load side Compressor start components Check start capacitor of compressor contactor and compressor won’t run Check potential relay
Run capacitor Check with ohmmeter
Internal overload Allow time to reset
Compressor windings Check for correct ohms
Voltage present on line side of Thermostat Check for control voltage to com­pressor contactor only contactor coil
Compressor control circuit High pressure switch open
Low pressure switch open
Ambient thermostat Solid state protection control or
internal thermal sensors
Compressor timed off/on control or interlock
Defrost control locked out due to 3 high or low pressure control trips. See sections 8.6 & 8.7
No voltage on line side Blown fuses or tripped circuit breaker Check for short in wiring or unit of compressor contactor
Improper wiring Re-check wiring diagram
Improper voltage High voltage Wrong unit
Power supply problem
Low voltage Wrong unit
Power supply problem
Wiring undersized
Loose connections
Single Phasing (3 phase) Check incoming power and fusing
CONTAMINATION
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Moisture Poor evacuation on installation In each case, the cure is the same.
High head pressure Non-condensibles air
Unusual head and suction readings Wrong refrigerant
Foreign Matter­copper filings Copper tubing cuttings
Copper oxide Dirty copper piping
Welding scale Nitrogen not used
Soldering flux Adding flux before seating
Excess soft solder Wrong solder material
or during service Recover refrigerant. Add filter drier,
evacuate and re-charge
copper part way
27
Page 28
LOSS OF LUBRICATION
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Compressor failures Line tubing too long Add oil to the recommended level
ine tubing too large Reduce pipe size to improve
L
Low suction pressure Low charge Check system charge
Refrigerant leaks Repair and recharge
Cold, Noisy compressor - Slugging Dilution of Oil with Refrigerant Observe piping guidelines
Noisy compressor Migration Check crankcase heater
Cold, sweating compressor Flooding Check system charge
Low Load Reduced air flow Dirty filter
Thermostat setting Advise customer
Short cycling of compressor Faulty pressure control Replace control
Loose wiring Check all control wires
Thermostat In supply air stream,
oil return
irty coil
D
Wrong duct size
Restricted duct
out of calibration,
Customer misuse
FLOODED STARTS
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
Liquid in the compressor shell Faulty or missing crankcase heater Replace crankcase heater
Too much liquid in system Incorrect piping Check Piping guidelines
Overcharge Check and adjust charge
SLUGGING
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
On start up Incorrect piping Review pipe size guidelines
TEV hunting when running Oversized TEV Check TEV application
FLOODING
SYMPTOMS POSSIBLE CAUSES CHECK OR REMEDIES
Poor system control Loose sensing bulb Secure the bulb and insulate using a TEV
Bulb in wrong location Relocate bulb
Wrong size TEV Use correct replacement
Improper superheat setting Adjust, if possible;
Replace, if not
Poor system control Overcharge Check system charge using capillary tubes
High head pressures Dirty heat pump
Restricted air flow
Recirculation of air
Evaporator air flow too low Adjust air flow to 350-400 CFM/Ton
28
Page 29
THERMOSTATIC EXPANSION VALVES
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
High Superheat, Low Suction Pressure Moisture freezing and blocking valve Recover charge, install filter-drier,
Dirt or foreign material blocking valve Recover charge, install filter-drier,
Low refrigerant charge Correct the charge
Vapor bubbles in liquid line Remove restriction in liquid line
Misapplication of internally equalized Use correct TEV valve
Plugged external equalizer line Remove external equalizer line
Undersized TEV Replace with correct valve
Loss of charge from power Replace power head or complete head sensing bulb TEV
Charge migration from sensing bulb Ensure TEV is warmer than to power head (Warm power head sensing bulb with warm, wet cloth. Does valve operate correctly now?)
Improper superheat adjustment Adjust superheat setting counter­(Only applicable to TEV with adjustable clockwise superheat settings)
Valve feeds too much refrigerant, Moisture causing valve to stick open. Recover refrigerant, replace filter­with low superheat and higher than drier, evacuate system and then nor­mal suction pressure recharge
Dirt or foreign material causing Recover refrigerant, replace filter­valve to stick open drier, evacuate system and
TEV seat leak (A gurgling or hissing Replace the TEV sound is heard AT THE TEV during the off cycle, if this is the cause.) NOT APPLICABLE TO BLEED PORT VALVES.
Oversized TEV Install correct TEV
Incorrect sensing bulb location Install bulb with two mounting
Low superheat adjustment Turn superheat adjustment (only applicable to TEV with clockwise adjustable superheat setting)
Incorrectly installed, or restricted Remove restriction, or relocate external equalizer line external equalizer
Compressor flood back upon start up Refrigerant drainage from flooded Install trap riser to the top of the
evaporator evaporator coil
Compressor in cold location Install crankcase heater on
Any of the causes listed under Any of the solutions listed under Symptoms of Problem #2 Solutions of Problem #2
evacuate system, recharge
evacuate system, recharge
Correct the refrigerant charge
emove non-condensible gases
R
Size liquid line correctly
restriction
recharge
straps, in 2:00 or 4:00 position on suction line, with insulation
compressor
29
Page 30
THERMOSTATIC EXPANSION VALVES
SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIES
Superheat is low to normal Unequal evaporator circuit loading Ensure air flow is equally distributed with low suction pressure through evaporator
Check for blocked distributor tubes
Low load or airflow entering Ensure blower is moving proper air evaporator coil CFM
Remove/Correct any air flow restriction
Superheat and suction Expansion valve is oversized Install correct TEV pressure fluctuate (valve is hunting)
Sensing bulb is affected by liquid Relocate sensing bulb in another refrigerant or refrigerant oil flowing position around the circumference of through suction line the suction line
Unequal refrigerant flow through Ensure sensing bulb is located evaporator circuits properly
Check for blocked distributor tubes
Improper superheat adjustment Replace TEV or adjust superheat (only possible with TEV having superheat adjustment)
Moisture freezing and partially Recover refrigerant, change filter­blocking TEV drier, evacuate system and
Valve does not regulate at all External equalizer line not connected Connect equalizer line in proper
or line plugged location, or remove any blockage
Sensing bulb lost its operating charge Replace TEV
Valve body damaged during soldering Replace TEV or by improper installation
recharge
30
Page 31
16.0 WIRING DIAGRAMS
FIGURE 5
SINGLE-PHASE WIRING DIAGRAM (-)PNL/(-)PPL-***JAZ (208/230V SINGLE PHASE)
31
Page 32
FIGURE 6
HREE-PHASE WIRING DIAGRAM (-)PNL-***CAZ (208/230V THREE-PHASE)
T
32
Page 33
FIGURE 7
HREE-PHASE — 480V WIRING DIAGRAM (-)PNL-***DAZ (460V THREE-PHASE)
T
33
Page 34
34
Page 35
35
Page 36
36
CM 1208
Loading...