Rheem MPi Series Installation Instructions Manual

Page 1
This water heater must be installed and serviced by a qualified person.
Please leave this guide with the householder.
Installation Instructions
Air Sourced Integrated
Heat Pump Module
Page 2
PATENTS
This water heater may be protected by one or more patents or registered designs
in the name of Rheem Australia Pty Ltd.
TRADE MARKS
®
Registered trademark of Rheem Australia Pty Ltd.
™ Trademark of Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure accuracy in preparation of this publication.
No liability can be accepted for any consequences,
which may arise as a result of its application.
Page 3
3
CONTENTS
HOUSEHOLDER – This installation instruction booklet is intended for
the installer but you may find it of interest.
Installation .............................................................................................. 4
Heat Pump And Tank Assembly ......................................................... 13
Connections – Electrical ..................................................................... 30
Commissioning .................................................................................... 32
Water Supplies ..................................................................................... 38
Warranty Note ...................................................................................... 40
Page 4
4
INSTALLATION
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and in accordance with the installation instructions, and in compliance with Standards AS/NZS 3500.4, AS/NZS 3000 and all local
codes and regulatory authority requirements.
In New Zealand, the installation must also conform with Clause G12 of the New Zealand Building Code.
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable water. Its use in an application other than this may shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or business, then there should be redundancy within the hot water system design. This should ensure the continuity of hot water supply in the event that this water heater was to become inoperable for any reason. We recommend you provide advice to the system owner about their needs and building backup redundancy into the hot water supply system.
This water heater is recommended for connection to a minimum 16 hour per day power supply for a 325 litre storage tank and a 24 hour per day power supply for a 410 litre storage tank.
STORAGE TANK AND HEAT PUMP MODULE
The heat pump water heater is made of two main components, the storage tank and the heat pump module. For transport and handling (weight) purposes both items are shipped separately and designed to be assembled at the installation site. The water heater must not be operated until both components are assembled. Refer to “Heat Pump and Tank Assembly” on page 13.
Take care when handling the heat pump module. The jacket of the heat pump module needs to be handled gently so as not to cause damage.
Page 5
INSTALLATION
5
Care must be taken during transportation and handling. Do not lay the heat pump module down and do not tilt the heat pump module or the heat pump and storage tank assembly more than 30° from the vertical. This will
displace the compressor lubricating oil. If the heat pump module or heat pump and storage tank assembly has been tilted more than 30° from the vertical during handling, it will need one hour to drain back before the power to the water heater can be switched on, otherwise damage to the compressor may result.
All packaging materials must be removed from the heat pump module prior to its installation. This includes the removal of the cardboard base of the carton from the underside of the module.
A clearance of 300 mm is required perpendicular from both the front air inlet louvres and the outlet grille to any wall or obstruction. Refer to the dimensions
diagram on page 9.
The heat pump module must be installed on and fully supported by a stable base.
The water heater must not be installed in an area with a corrosive atmosphere where chemicals are stored or where aerosol propellants are released. Remember the air may be safe to breathe, but the chemicals may attack the materials used in the heat pump system.
Warning: This heat pump module is designed to be installed with a purpose
built water heater storage tank and may not be used for any other purpose.
Note
These instructions cover only the installation of the heat pump module onto the storage tank and the connections made between the heat pump module and storage tank. Refer to the Owner‟s Guide and Installation Instructions supplied with the storage tank for further information including:
where and how to locate the heat pump water heater how to connect the heat pump water heater to the electricity supply and to
the plumbing system
how to operate the heat pump water heater what to do if something goes wrong.
SAFE TRAY
Where damage to property can occur in the event of the water heater leaking, the water heater must be installed in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4 and all local codes and regulatory authority requirements.
Page 6
INSTALLATION
6
FREEZE PROTECTION
The water heater has a freeze protection system. The freeze protection system will protect the water heater from damage, by preventing ice forming in the waterways of the water heater, in the event of freezing conditions occurring.
If the ambient air temperature falls below 1°C and the heat pump is not operating, the system will operate the circulator periodically. During this freeze protection cycle, the circulator will operate for thirty (30) seconds and then rest for fifteen (15) minutes, before the cycle is recommenced. Water is circulated from the storage tank through the heat pump circuit, to prevent freezing in the connecting pipe work and heat pump module. The green LED will flash a series of four (4) flashes whilst the circulator is operating.
The water heater has NO WARRANTY for freeze damage if power is unavailable at the water heater.
Warning: In areas where the ambient air temperature may fall below 1°C, power must be available to the water heater at all times to prevent freezing in the heat pump circuit.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below, an approved pressure limiting valve is required. Refer to the Owner‟s Guide and Installation Instructions supplied with the storage tank for the position of the pressure limiting valve.
Model
325, 410
Relief valve setting
1000 kPa
Expansion control valve setting *
850 kPa
Max. mains supply pressure
With expansion control valve
680 kPa
Without expansion control valve
800 kPa
Min. mains supply pressure
200 kPa
* Expansion control valve not supplied with the water heater.
A minimum water supply pressure of 200 kPa is required to enable the heat pump circulator and heat pump system to operate effectively.
Page 7
INSTALLATION
7
TANK WATER SUPPLY
If the water heater is supplied with water from a tank supply and a minimum water supply pressure of 200 kPa at the water heater cannot be achieved, then a pressure pump system must be installed to allow the heat pump circulator to operate and avoid air locks in the circuit. Care must be taken to avoid air locks. The cold water line from the supply tank should be adequately sized and fitted with a full flow gate valve or ball valve.
CONDENSATE DRAIN
A drain line should be fitted to the heat pump module‟s condensate drain to carry the discharge clear of the water heater. The drain line can be extended using 12 mm rigid poly hose or conduit. The pipe work from the condensate drain should be as short as possible and fall all the way from the water heater with no restrictions. It should have no more than three right angle bends in it. The outlet of the drain line must be in such a position that flow out of the pipe can be easily seen - but arranged so water discharge will not cause damage or nuisance.
The condensate drain line must not be connected to the relief valves drain lines but may discharge at the same point.
WARNING
This water heater is only intended to be operated by persons who have the experience or the knowledge and the capabilities to do so. This water heater is not intended to be operated by persons with reduced physical, sensory or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere with the water heater.
This water heater uses 240 V AC electrical power for operation of the control systems and the electrically operated components. The removal of the access cover(s) will expose 240 volt wiring. They must only be removed by a qualified person.
ENVIRONMENT
At the end of the service life of the heat pump water heater and prior to the water heater being disposed of, a person qualified to work with refrigerants must recover the refrigerant from within the sealed system. The refrigerant must not be vented to atmosphere. Phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
Page 8
INSTALLATION
8
TO TURN OFF THE WATER HEATER
To turn off the water heater:
Switch off the electrical supply at the isolating switch to the water heater. Close the cold water isolation valve at the inlet to the water heater.
Notes
The freeze protection system will be rendered inoperable if electrical
power is not available at the water heater.
Damage caused by freezing due to the unavailability of power at the water
heater is not covered by the Rheem warranty. Refer to “Warranty Note” on page 40.
If the power has been switched off to the water heater and there is a risk of
freezing, then it is necessary to drain the water heater.
Refer to “Draining the Water Heater” in the Owner‟s Guide and Installation
Instructions supplied with the heat pump storage tank.
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Plumbing Industry Commission. This water heater must be installed by a licensed person as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that the work complies with all the relevant Standards. Only a licensed person will have insurance protecting their workmanship for 6 years. Make sure you use a licensed person to install this water heater and ask for your Compliance Certificate.
Page 9
INSTALLATION
9
DIMENSIONS AND TECHNICAL DATA
300 MIN
ELECTRICAL CONNECTION
VENTILATION CLEARANCE
1018
H
574
HOT
OUTLET
COLD
INLET
E
544
872
B
K
275
100
WALL
AIR
INLET
AIR INLET
C
AIR
OUTLET
300 MIN
VENTILATION CLEARANCE
CONDENSATE DRAIN
TPR VALVE
AIR INLET
AIR
OUTLET
300 MIN
F
A
D
Rheemglas 551 Series
Page 10
INSTALLATION
10
A
D
1018
H
574
E
544
872
K
100
WALL
AIR
INLET
AIR INLET
C
AIR
OUTLET
300 MIN
CONDENSATE DRAIN
TPR VALVE
AIR INLET
AIR
OUTLET
300 MIN
VENTILATION CLEARANCE
300 MIN
VENTILATION CLEARANCE
HOT
OUTLET
COLD
INLET
ELECTRICAL
CONNECTION
L
F
275
B
M
RheemPlus 554 Series
Page 11
INSTALLATION
11
Models
Rheemglas RheemPlus
551325 554325
551410 554410
Storage tank capacity
litres
325
410
Boost capacity 1.8 kW
litres
100 -
2.4 kW*, 3.6 kW*
litres
180
200
Dimensions A
mm
1631
1842
B
mm
894
961
C
mm
638
686
D
mm
1317
1479
E
mm
114
127
F
mm
162
650
H
deg
32
30
K
mm
619
686
554 series only L
mm
262
286
554 series only M
mm
1006
1073
Models
Rheemglas
551325
551410
Weight tank empty
kg
88
112
Weight heat pump
kg
42
42
Weight system empty
kg
130
154
Weight system full
kg
455
564
Models
RheemPlus
554325
554410
Weight tank empty
kg
90
112
Weight heat pump
kg
42
42
Weight system empty
kg
132
154
Weight system full
kg
455
564
Heat pump module model no
182550 (R)
Maximum rated power input
watts
3600
Rated heat pump power input
watts
800
Booster element ratings
kW
1.8, 2.4, 3.6
Refrigerant type
R134a
Refrigerant circuit pressure
kPa
3000
* The boost capacity of a 2.4 kW or 3.6 kW low watts density heating unit if used is 100 litres (325 litre storage tank) or 125 litres (410 litre storage tank).
Technical data is subject to change.
Page 12
INSTALLATION
12
TYPICAL INSTALLATION – OUTDOOR LOCATION
Rheemglas 551 Series Shown
Page 13
13
HEAT PUMP AND TANK ASSEMBLY
STORAGE TANK AND HEAT PUMP MODULE
The heat pump water heater is made of two main components, the storage tank and the heat pump module. For transport and handling (weight) purposes both items are shipped separately and designed to be assembled at the installation site. The water heater must not be operated until both components are assembled.
The water heater is to be installed at ground or floor level and must stand vertically upright on a stable base, as acceptable to local authorities, of a minimum 900 mm wide x 650 mm deep. The heat pump module must be fully supported by the stable base.
HEAT PUMP MODULE
The heat pump module is shipped in a box containing two hand holes to facilitate easy handling and lifting. The heat pump module is to be mounted against the side of the storage tank.
CAUTION: The heat pump module weighs approximately 42 kg. Use the hand holes provided in the sides of the packaging. Good lifting practice should be followed.
There are two flexible hoses provided inside the heat pump module. The flexible hoses are to be withdrawn from the module and fixed to the two water fittings on the heat pump storage tank, during the assembly procedure.
There are two connection points located on the underside of the control box in the heat pump module to which the power cable and tank sensor cable from the heat pump storage tank are connected, during the assembly procedure.
STORAGE TANK
The storage tank is designed to receive the heat pump module. There are two water fittings located at the side of the storage tank to which flexible hoses from the heat pump module are connected, during the assembly procedure.
A power cable is housed behind the lower cover and a tank sensor cable is located adjacent to and above to the lower cover of the storage tank. The power cable is to be withdrawn from behind the front cover and the tank sensor cable unfurled and both connected to the control box in the heat pump module during the assembly procedure.
Page 14
HEAT PUMP AND TANK ASSEMBLY
14
storage tank heat pump module heat pump water heater
KIT
There is a kit (PN 299276) supplied with the heat pump module and a kit supplied with the 410 model heat pump storage tank (PN 290122). The components supplied in the kit and required for the installation are:
299276
Kit Installation Heat Pump Module Integrated
Qty
122189
Installation instructions heat pump module integrated
1
052158
Saddle clamp 20 mm Clipsal 261/20
1
080021
Screw phillips pan head No. 8 x 13 zinc plated black
2
080156
Screw pack of 3 M6 x 12 HD bolts
2
080203
Stud M6 x 25 zinc plate
3
080204
Nut hex whizzlock M6
3
104767
Cover fan shroud
1
080191
Screw hilo 13-16 x 20 pan head combination zinc plated
1
104766
Plug plastic 13 mm black
1
290122
Kit Heat Pump Module Seal 410
Qty
087052
Cover strip heat pump housing top
1
160032
Tape foam 406E 18 mm x 7 mm thick
1
+
=
Page 15
HEAT PUMP AND TANK ASSEMBLY
15
ASSEMBLY PROCEDURE
Warning: The heat pump must be assembled, plumbed and filled with
water prior to power being connected and switched on. The following procedure should be followed to properly place the heat pump
module in position and connect to the storage tank:
1. Heat Pump Storage Tank: Remove all packaging including the carton
base from the heat pump storage tank and position in its intended location, supported by a stable base.
The water connections may be on either the left or right hand side and should be parallel to the wall.
The storage tank must be positioned at least 100 mm from the wall. If a minimum clearance of 100 mm is not allowed for, the heat pump module will not be able to be completely connected to the storage tank.
The storage tank must also be positioned such that when the heat pump module is in position, there is a clearance of at least 300 mm perpendicular from both the front air inlet louvres and the outlet grille to any wall or obstruction.
300 MIN
H
574
B
K
275
100
WALL
AIR
INLET
AIR INLET
C
AIR
OUTLET
300 MIN
VENTILATION CLEARANCE
CONDENSATE DRAIN
TPR VALVE
Step 1
position storage tank at least 100 mm from the wall
and allow for at least 300 mm ventilation clearance
(refer table on page 11 for dimensions)
551 series shown above
Page 16
HEAT PUMP AND TANK ASSEMBLY
16
2. Lower Front Cover: Remove the two screws securing the lower front
cover to the storage tank.
Remove the lower front cover from the storage tank.
Step 2 Step 3 remove screws withdraw the power cable from lower front cover
3. Power Cable: Withdraw the power cable, housed behind the lower front
cover, from the opening.
Page 17
HEAT PUMP AND TANK ASSEMBLY
17
4. Mains Power Connection – 551 Series: Connect the mains power supply
wiring to the terminal block and earth connection inside of the lower front cover.
Secure the conduit to the side of the storage tank with the saddle
clamp and screws provided. The saddle clamp must be positioned over the pilot holes provided,
otherwise the conduit will interfere with the heat pump module installation.
Refer to “Connections – Electrical” on page 30. Note: The power supply to the water heater must not be switched on until
the installation is complete, the water heater is filled with water and a satisfactory megger reading is obtained.
Step 4
Connect wiring and secure conduit with saddle clamp
Page 18
HEAT PUMP AND TANK ASSEMBLY
18
5. Lower Front Cover: Refit the lower front cover.
Step 5 Step 6 refit lower front cover remove tape from tank sensor cable
6. Tank Sensor Cable: Remove tape from tank sensor cable and unfurl.
Page 19
HEAT PUMP AND TANK ASSEMBLY
19
7. Foam Tape: (410 litre storage tank only) – Retrieve the length of foam
tape from the kit supplied with the 410 storage tank. The foam tape is to be applied to the bottom at the front of the 410 litre
storage tank. The ends of the foam tape are to line up with the two vertical slots in the
jacket. The mid point of the tape (lengthways) is to line up over the join between
the jacket of the storage tank and the jacket bottom.
Remove the backing from the foam tape and apply the foam tape to
the storage tank.
FOAM TAPE
REMOVE ADHESIVE PAPER BACKING
LINE UP EDGES OF FOAM TAPE UNDER SLOTS.
MID POINT OF FOAM TAPE TO LINE UP OVER JOIN BETWEEN JACKET AND JACKET BOTTOM.
Step 7
apply foam tape to 410 litre storage tank
8. Heat Pump Module: Remove all packaging including the carton base
from the heat pump module and position in its intended location at the storage tank.
CAUTION: The heat pump module weighs approximately 42 kg. Use the hand holes provided in the sides of the packaging. Good lifting practice should be followed.
Page 20
HEAT PUMP AND TANK ASSEMBLY
20
9. Fan Cover Shroud: Retrieve the fan cover shroud, 20 mm screw and
black plastic plug from the kit bag.
Remove the screw located immediately above the monitor label on
the front of the heat pump module and discard.
Position the fan cover shroud over the fan cowl and slide the
recessed edge of the shroud under the lip of the heat pump module top. It will slide under the top without having to remove any screws.
Align the mounting hole at the bottom of the shroud with the screw
hole in the heat pump module located immediately above the monitor label.
Secure the fan cover shroud to the heat pump module with the 20 mm
screw provided.
Insert the black plug provided into the recess to cover the head of the
screw.
FAN COVER
SHROUD
SCREW
PLUG
REMOVE AND DISCARD EXISTING SCREW
Step 9
fit the fan cover shroud to the heat pump module
Page 21
HEAT PUMP AND TANK ASSEMBLY
21
10. Cover Strip: (410 litre storage tank only) – Retrieve the length of rubber
cover strip from the kit supplied with the 410 storage tank.
Line up one end of the cover strip with one end of the heat pump
housing black top, fitting the strip over the lip of the housing, ensuring the jacket is hard up against the lip of the heat pump housing.
The cover strip will hold the jacket in position.
Apply the cover strip along the full length of the lip of the heat pump
housing.
ASSEMBLY
DETAIL
COVER STRIP
COVER STRIP
HEAT PUMP HOUSING
HEAT PUMP HOUSING
COVER STRIP
Step 10
apply cover strip to heat pump housing
Page 22
HEAT PUMP AND TANK ASSEMBLY
22
11. Heat Pump Module Cover: Remove the two screws securing the front
cover to the heat pump module.
Remove the front cover from the heat pump module.
Step 11 and 13
remove front cover from heat pump module
and feed through cables
12. Position Heat Pump Module: Position the edge of the heat pump module
which is closest to the wall against the storage tank so the screw holes in the module are adjacent to the nutserts in the storage tank.
13. Power Cable and Tank Sensor Cable: Feed the power cable from the
lower front cover and tank sensor cable through the heat pump module so they protrude out of the front of the module.
14. Flexible Braided Hoses: Retrieve the loose ends of the two flexible
braided hoses from within the heat pump module, and withdraw through the rear of the heat pump module.
Page 23
HEAT PUMP AND TANK ASSEMBLY
23
15. Cold Hose Connection: Attach the flexible braided hose, marked with a
blue stripe through the braid and attached to the bottom of the heat exchanger, to the ball valve fitting in the bottom connection on the storage tank and marked “TO HEAT PUMP”.
Tighten the swivel nut on the hose using a 24 mm spanner.
Tape or sealant is not required.
Position the hose such that when the heat pump module is moved
and secured to the tank, it does not kink.
Ball valve: Ensure the ball valve located in the connection fitting is in
the open position. In the open position, the slot is in line with the hose.
Step 15
attach flexible hose with blue stripe to inlet and ball valve in open position
Page 24
HEAT PUMP AND TANK ASSEMBLY
24
16. Hot Hose Connection: Attach the flexible braided hose, marked with a
red stripe through the braid and attached to the top of the circulator, to the non return valve fitting in the upper connection marked “OUTLET” in red on the storage tank.
Tighten the swivel nut on the hose using a 24 mm spanner.
Tape or sealant is not required.
Position the hose such that when the heat pump module is moved
and secured to the tank, it does not kink.
Step 16
attach flexible hose with red stripe to outlet
17. Check Hoses: Check to ensure the flexible hoses are not kinked.
Page 25
HEAT PUMP AND TANK ASSEMBLY
25
18. Cable Tab – 551 Series: Remove the tab on the side of the electrical
entry to the heat pump module to accommodate the electrical conduit. Pliers or tin snips may be required to remove the tab.
Step 18
remove the tab on the side of the electrical entry to the heat pump module
19. Studs: Retrieve the three (3) studs from the kit and screw into the
three (3) threaded inserts on the side of the tank closest to the wall. These studs will assist in aligning the heat pump module for connection to
the storage tank.
Step 19
screw in studs into threaded inserts
Page 26
HEAT PUMP AND TANK ASSEMBLY
26
20. Position Heat Pump Module: Position the heat pump module against the
tank.
Engage the tab at the bottom of the heat pump module, on the wall
side of the module, into the slot in the tank.
Align the holes in the side of the heat pump module over the three
studs.
21. Flange Nuts: Screw the three flange nuts onto the studs to connect the
wall side of the heat pump module to the storage tank.
Steps 20 and 21
align heat pump module over studs and screw on flange nuts
22. Tab: Engage the tab at the bottom of the heat pump module, on the front
side of the module, into the slot in the tank.
23. Fixing Bolts: Screw in the three fixing bolts to connect the front side of
the heat pump module to the storage tank.
Step 23
screw in fixing bolts to connect heat pump module to storage tank
Page 27
HEAT PUMP AND TANK ASSEMBLY
27
24. Tank Sensor Cable Connection: Insert the tank sensor cable plug to the
connector on the underside of the control box. The plug is polarised and can only be inserted one way.
Ensure the plug fully engages the locking feature on the connector.
25. Power Cable Connection: Insert the four pin power cable plug to the
connector on the underside of the control box. The plug is polarised and can only be inserted one way.
Steps 24 and 25
connect power cable and tank sensor cable
Page 28
HEAT PUMP AND TANK ASSEMBLY
28
26. Positioning of Water Heater: Complete final positioning of the water
heater. Ensure the heat pump module is firmly seated on the level slab or solid
base.
27. Water Connections: Connect the cold water supply and the hot water
pipe work to the water heater.
Connect the temperature pressure relief valve and its drain line.
Refer to “Connections – Plumbing” in the Owner‟s Guide and Installation Instructions supplied with the storage tank.
28. Water Supply: Turn on the cold water supply and fill the water heater.
Check the pipe work and the connection points for the flexible braided
hoses for leaks Refer to “To Fill And Turn On The Water Heater” on page 32,
however the electrical supply should not be turned on at this stage.
29. Heat Pump Module Cover: Replace the heat pump module cover and re-
fit the two screws.
Step 29
replace heat pump module front cover
Page 29
HEAT PUMP AND TANK ASSEMBLY
29
30. Electrical Cover – 554 Series: Remove the two screws securing the
electrical cover, adjacent to the temperature limiting valve cover, to the storage tank.
Remove the electrical cover from the storage tank.
Step 30
remove screws from electrical cover
31. Mains Power Connection – 554 Series: Connect the mains power supply
wiring to the terminal block and earth connection inside of the electrical cover.
Secure the conduit to the side of the storage tank with the saddle
clamp and screws provided. Refer to “Connections – Electrical” on page 30. Note: The power supply to the water heater must not be switched on until
the installation is complete, the water heater is filled with water and a satisfactory megger reading is obtained.
Step 31 Step 32 connect wiring to terminal block refit electrical front cover
32. Electrical Cover – 554 Series: Refit the electrical cover.
33. Commissioning: Refer to “Commissioning” in the Owner‟s Guide and Installation Instructions supplied with the storage tank.
Page 30
30
CONNECTIONS – ELECTRICAL
The power supply to the water heater must not be switched on until the water heater is filled with water and a satisfactory megger reading is
obtained.
MEGGER READING
When a megger test is conducted on this water heater, then the following should be noted.
Warning: This water heater contains electronic equipment and 500 V insulation tests must only be conducted between active and earth and between neutral and earth. An active to neutral test WILL damage the electronics.
An insulation test result of between 100 and 660 for this water heater is normal.
Typically the insulation resistance between live and earthed parts of an electrical installation should not be less than 1 MΩ. However AS/NZS 3000:2000 clause 6.3.3.3.2 „Results‟ states:
“The value of 1 MΩ may be reduced to:
0.01 MΩ for sheathed heating elements or appliances; or a value permitted in the Standard applicable to electrical equipment.”
This model water heater is categorised as a „stationary class 1 motor operated appliance‟ and has been tested to AS/NZS 3350.1:2002 clause 16 „Leakage current and electric strength‟ and has passed the requirements of this
Standard. Therefore, this model water heater complies with the condition stated in AS/NZS 3000:2000 clause 6.3.3.3.2 (b).
ELECTRICAL CONNECTION
All electrical work and permanent wiring must be carried out by a qualified person and in accordance with the Wiring Rules AS/NZS 3000 and all local codes and regulatory authority requirements.
This water heater is recommended for connection to a minimum 16 hour per day power supply for a 325 litre storage tank and a 24 hour per day power supply for a 410 litre storage tank.
Page 31
CONNECTIONS – ELECTRICAL
31
WIRING DIAGRAM
Electrical Circuit for Heat Pump – Robertshaw “ST” Thermostat
Dwn
Ch'd
App'd by
SHARP CORNERS TO BE BROKEN , UNLESS STATED
DISTRIBUTION:
REV
ECO No. DETAILS
BY
CHD
DATE
RHEEM AUSTRALIA PTY. LTD
UNLESS OTHERWISE STATED
ALL DIMENSIONS IN mm.
TOLERANCES
This drawing and the information contained herein is the sole property of
Rheem Australia Pty. Ltd, is strictly confidential and may not be used or disclosed
without the written consent of Rheem Australia Pty. Ltd.
Rev
SPECIFICATION
3RD ANGLE
PROJECTION
CCD
R
AD
WH13527
New drawing issued..
CCD
HWO
6/13
COM
NC
NO
COMP-ACOMP-N
FAN-N
FAN-A
PUMP-N PUMP-A
NEUTRAL
EARTH
COMPRESSOR
CAPACITOR
FAN
CAPACITOR
CONTROL
BOARD
CONTROL BOARD
ENCLOSURE
LED
BLUE
BLACK
GREEN/YELLOW
RED
BLUE
BLACK
F
F
F
F
T3 - ELMT
M F
1
2
COMNO
NC
COIL
Push
button
M
F
F
F
M
serial
port
PROG
1
1 1
PUMP
FAN
S
C
R
THERMOSTAT
HEATER
ELEMENT
COMPRESSOR
A
E
N
LOWER TANK
THERMISTOR
(T0)
CABLING IN CONDUIT
INSIDE TANK JACKET
PUMP PLUG
COMPRESSOR PLUG
FAN
PLUG
BLACK
BROWN
BLUE
BLUE
BLUE
BLUE
BLACK
RED
GREEN/YELLOW
RED
WHITE
RED
GREEN/YELLOW
GREEN/YELLOW
BROWN
BLACK
LIGHT
RED
BLUE
LIGHT RED
GREEN/YELLOW
GREEN/YELLOW
M
M
M
1
3
4
2
1
1
3
4
2
3
2
CABLE SET
TANK
HP
SW
HPSWPLUG
F
1
2
3
LED
RED
RED
RED
BLUE
BLACK
1
2
1
3
4
2
1
1
3
4
2
3
2
4
1
2
3
1
2
3
1
2
3
1
2
1
234
1
2
GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
1
5
23
4
BLUE
RED
RED
BLUE
YELLOW
BLACK
RED
BLACK
WHITE
BLACK
BLACK
RED
RED
GREEN
GREEN
EVAPORATOR
THERMISTOR
COMPRESSOR
THERMISTOR
HEATER MODULE ASSEMBLYTANK ASSEMBLY
F
1
2
M
1
2
3
M
1
2
BLACK
BLACK
BLACK
M
1
2
3
GREY
GREY
CONDENSER
THERMISTOR
F
1
2
3
BLACK
BLACK
YELLOW
BLUE
WHITE
RED
M
POWER PLUG
4
1
2
3
T0 - TANK
T2 - COMP
T1 - EVAP
Page 32
32
COMMISSIONING
TO FILL AND TURN ON THE WATER HEATER
The power supply to the water heater must not be switched on until the water heater is filled with water and a satisfactory megger reading is
obtained.
Open all of the hot water taps in the house (don‟t forget the shower). Open the cold water isolation valve fully to the water heater.
Air will be forced out of the taps.
Close each tap as water flows freely from it. Check the pipe work and the connection points for the flexible braided
hoses for leaks
Switch on the electrical supply at the isolating switch to the water heater. Set the timer if one is installed.
If it is necessary to adjust the outlet temperature of a RheemPlus model, refer to “Outlet Temperature Compensation Adjustment – RheemPlus” in the
Owner‟s Guide and Installation Instructions supplied with the heat pump
storage tank. Note: The water heater is preset in the factory to allow it to commence
operating with either the heat pump or booster heating unit immediately power is turned on for the first time. If power is turned on and then off at its installation, the water heater may take up to forty five (45) minutes to commence operating when the power supply is switched on again. This forty five (45) minute period can be overridden during the commissioning procedure if the power was inadvertently turned on and then off again. Refer to “System
Reset” on page 37.
The heat pump will only operate when power is available at the water heater, the water in the storage tank requires heating, the heat pump compressor is cool and the ambient air temperature is within the heat pump‟s operating temperature range of between a minimum of 3°C to 5°C and a maximum of 45°C to 55°C. If the ambient temperature is outside of this range, the water heater will commence heating with the booster heating unit.
When the heat pump is operating, the system will switch to the booster heating unit if the detected ambient air temperature is outside the operating temperature range of between a minimum of 3°C to 5°C and a maximum of 45°C to 55°C.
Page 33
COMMISSIONING
33
The system will not switch back to heat pump operation from the booster heating unit if the detected ambient air temperature has moved back within the
heat pump‟s operating temperature range. The heating cycle will be completed
by the booster heating unit. Note: The heat pump may not turn on after either having just completed a
heating cycle and more hot water is drawn from the water heater or power is shut down to the compressor, either during or at the end of a heating cycle. The heat pump will wait until the compressor has cooled down and the conditions for start up are favourable in order to protect the compressor from damage. This will be a minimum of forty five (45) minutes and may take up to ninety (90) minutes from the last heating cycle.
It is important to wait for five (5) minutes after the heat pump has activated to ensure it continues to operate and is functioning correctly.
Explain to the householder or a responsible officer the functions and operation of the heat pump water heater. Upon completion of the installation and commissioning of the water heating system, leave this guide with the householder or a responsible officer.
TO TURN OFF THE WATER HEATER
Refer to “To Turn Off the Water Heater” on page 8.
DIAGNOSTIC FEATURES OF THE HEAT PUMP CONTROLLER
An operating mode monitor is located on the front of the heat pump module and houses a green and a red LED.
The green LED, marked “NORMAL”, indicates the current operating mode (with the red LED off) of the heat pump water heater and the red LED, marked ATTENTION”, may indicate a potential fault mode.
The green LED will emit either a constant glow or a series of flashes, with a 2 second interval between each series. A series of long green flashes may also be emitted.
The red LED will emit either a solid glow or a series of flashes, with a 2 second interval between each series. A series of flashes indicates there may be a particular fault condition with the system.
Page 34
COMMISSIONING
34
The modes are:
Flashes
Operational Modes
solid green
(remains on)
Standby mode – water is hot
1 x green
Call for heating received – system checks performed Note: unit may wait and continue flashing until compressor has cooled from its last operation
2 x green
Heat pump preheating
3 x green
Heat pump operation – compressor and fan running
4 x green
Freeze protection operation – circulator on
long green
Heating unit on – ambient air temperature below 3°C to 5°C or above 45°C to 55°C
rapid green
System start up – heating unit on
no green
(remains off)
No power at the water heater or to the heat pump or a possible fault condition
Refer to notes overleaf before calling for service
Flashes
Indicator or Fault Modes
1 x red
Heating unit on compressor over temperature
(possible circulator fault)
3 x red
Heating unit on compressor cooling fault condition
4 x red
Heating unit on tank thermistor fault condition
5 x red
Heating unit on evaporator thermistor fault condition
6 x red
Heating unit on compressor thermistor fault condition
7 x red
Heating unit on heat exchanger water outlet sensor fault
8 x red
Heating unit on water flow fault condition
9 x red
Heating unit off refrigeration system (compressor)
fault condition
Call for service
solid red
(remains on) +
solid green
(remains on)
Heating unit off system reset – release button
Page 35
COMMISSIONING
35
Notes:
There is no 2 x red flash indicator or fault mode code. Power must be available at the water heater and to the heat pump for
the LEDs to glow or flash.
Time controlled power supply (power must be available at the water
heater)
If the water heater is connected to a time controlled power supply, then during periods of no power supply at the water heater the LEDs will be off.
This is not a fault condition, but a result of no power being available to energise the LEDs.
The green LED will recommence glowing or flashing when power is available again at the water heater.
Heat pump operating range (power must be available to the heat
pump)
The heat pump‟s operating range is between an ambient air temperature of a minimum of 3°C to 5°C and a maximum of 45°C to 55°C. The heat pump will not operate when the ambient air temperature is outside the heat pump‟s operating range.
If heating is required, the water heater will commence heating with the booster heating unit in booster heating mode (long green flash) instead. The water will be heated to 70°C during these periods.
At the completion of this heating cycle by the booster heating unit (long green flash), the thermostat controlling the booster heating unit opens circuit cutting power to the heat pump causing the green LED to go out. This is not a fault condition, but a result of the power being cut to the heat pump by the thermostat.
Refer to “Heat pump operating range” in the “Save A Service Call” section of the Owner‟s Guide and Installation Instructions supplied with the heat pump storage tank for further explanation.
Page 36
COMMISSIONING
36
Possible fault condition
If there is power to the water heater and the green LED is off or the red LED is flashing, this indicates there may be a fault condition with the water heater. The red LED may emit up to nine flashes in each series of flashes.
There may be a fault condition with the water heater if either:
there is power available at the water heater and the green LED is off,
and
the water heater has not operated outside of the heat pump‟s
operating range. Before phoning to arrange a service inspection due to the green LED
being off, refer to “Heat Pump Is Not Operating” in the “Save A Service Call” section of the Owner‟s Guide and Installation Instructions supplied with the heat pump storage tank.
or
the red LED is flashing – the red LED may emit up to nine flashes in
each series of flashes The fault condition which led to the red LED flashing may be cleared
after the backup heating cycle by the booster heating unit has completed. When heating is next required the red LED will recommence to flash the fault code for 27 seconds and then extinguish. If the red LED then recommences to flash or recommences to flash after the heat pump next operates, a service call may be required.
Before phoning to arrange a service inspection due to the red LED flashing, refer to “Heat Pump Is Not Operating” in the “Save A Service Call” section of the Owner‟s Guide and Installation Instructions supplied with the heat pump storage tank.
Page 37
COMMISSIONING
37
SYSTEM RESET
To reset the system and override the forty five (45) minute start delay:
1. Press and hold the red controller reset button for two (2) to three (3)
seconds until both the green and red LEDs display a solid glow. Release the button.
The reset button is located on the front left corner of the underside of the controller box.
2. The green LED will flash rapidly for three (3) seconds, then the heat pump
will commence its heating start-up cycle. A series of 2 or 3 x green flashes will commence.
reset
button
Page 38
38
WATER SUPPLIES
This water heater must be installed in accordance with this advice to be covered by the manufacturer’s warranty.
This water heater is manufactured to suit the water conditions of most public reticulated water supplies. However, there are some known water chemistries which can have detrimental effects on the water heater and its operation and / or life expectancy. If you are unsure of your water chemistry, you may be able to obtain information from your local water supply authority. This water heater should only be connected to a water supply which complies with these guidelines for the manufacturer‟s warranty to apply.
CHANGE OF WATER SUPPLY
The changing or alternating from one water supply to another can have a detrimental effect on the operation and / or life expectation of a number of components in this water heater.
Where there is a changeover from one water supply to another, e.g. a rainwater tank supply, bore water supply, desalinated water supply, public reticulated water supply or water brought in from another supply, then water chemistry information should be sought from the supplier or it should be tested to ensure the water supply meets the requirements given in these guidelines for the manufacturer‟s warranty to apply.
SATURATION INDEX
The saturation index (SI) is used as a measure of the water‟s corrosive or scaling properties.
Where the saturation index is less than –1.0, the water is very corrosive and the manufacturer‟s warranty does not apply to the water heater. In a corrosive water supply, the water can attack copper parts and cause them to fail.
Where the saturation index exceeds +0.40, the water is very scaling and the manufacturer‟s warranty does not apply to the water heater.
Water which is scaling may be treated with a water softening device to reduce the saturation index of the water.
Page 39
WATER SUPPLIES
39
CHLORIDE AND PH
Where the chloride level exceeds 250 mg/L the manufacturer‟s warranty does not apply to the water heater. In a high chloride water supply, the water can corrode stainless steel parts and cause them to fail.
Where the pH is less than 6.0 the manufacturer‟s warranty does not apply to the water heater. pH is a measure of whether the water is alkaline or acid. In an acidic water supply, the water can attack stainless steel parts and cause them to fail.
Water with a pH less than 6.0 may be treated to raise the pH. The water supply from a rainwater tank in a metropolitan area is likely to be corrosive due to the dissolution of atmospheric contaminants.
SUMMARY OF WATER CHEMISTRY ADVICE AFFECTING WARRANTY
The water heater, including this heat pump module, is not suitable for certain water chemistries. Those chemistries are listed below. If the water heater is connected at any time to a water supply with the following water chemistry, the manufacturer‟s warranty will not cover any resultant faults:
Water Chemistry
Saturation Index (SI) < -1.0
Saturation Index (SI) > +0.4
Chloride > 250 mg/L
pH < 6.0
Refer to “Water Supplies” in the Owner‟s Guide and Installation Instructions
supplied with the storage tank for the complete water supply statement.
Page 40
Revision Date: 2014 July 122189B
40
WARRANTY NOTE
The heat pump water heater is covered by the manufacturer‟s warranty. For full manufacturer‟s warranty details, refer to the Owner‟s Guide and Installation
Instructions supplied with the storage tank.
The part extracts from the “Terms Of The Warranty And The Exclusions To It”
of the water heater warranty should be noted before commencing the installation.
TERMS OF THE WARRANTY AND EXCLUSIONS TO IT
2.5 Where the water heater is installed in a position that does not allow safe or ready access,
the cost of that access, including the cost of additional materials handling and/or safety equipment, shall be the owner’s responsibility. In other words, the cost of dismantling or removing cupboards, doors or walls and the cost of any special equipment to bring the water heater to floor or ground level or to a serviceable position is not covered by this warranty.
2.7 The warranty does not cover faults that are a result of:
c) Installation not in accordance with the Owner’s Guide and Installation Instructions or
with relevant statutory and local requirements in the State or Territory in which the water heater is installed.
d) Connection at any time to a water supply that does not comply with the water supply
guidelines as outlined in the Owner’s Guide and Installation Instructions.
k) Ice formation in the waterways of a water heater system incorporating a freeze
protection system where the electricity supply has been switched off or has failed.
2.8 Subject to any statutory provisions to the contrary, this warranty excludes any and all
claims for damage to furniture, carpet, walls, foundations or any other consequential loss either directly or indirectly due to leakage from the water heater, or due to leakage from fittings and/ or pipe work of metal, plastic or other materials caused by water temperature, workmanship or other modes of failure.
Loading...