Rheem MPi Series Installation Instructions Manual

This water heater must be installed and serviced by a qualified person.
Please leave this guide with the householder.
Installation Instructions
Air Sourced Integrated
Heat Pump Module
PATENTS
This water heater may be protected by one or more patents or registered designs
in the name of Rheem Australia Pty Ltd.
TRADE MARKS
®
Registered trademark of Rheem Australia Pty Ltd.
™ Trademark of Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure accuracy in preparation of this publication.
No liability can be accepted for any consequences,
which may arise as a result of its application.
3
CONTENTS
HOUSEHOLDER – This installation instruction booklet is intended for
the installer but you may find it of interest.
Installation .............................................................................................. 4
Heat Pump And Tank Assembly ......................................................... 13
Connections – Electrical ..................................................................... 30
Commissioning .................................................................................... 32
Water Supplies ..................................................................................... 38
Warranty Note ...................................................................................... 40
4
INSTALLATION
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and in accordance with the installation instructions, and in compliance with Standards AS/NZS 3500.4, AS/NZS 3000 and all local
codes and regulatory authority requirements.
In New Zealand, the installation must also conform with Clause G12 of the New Zealand Building Code.
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable water. Its use in an application other than this may shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or business, then there should be redundancy within the hot water system design. This should ensure the continuity of hot water supply in the event that this water heater was to become inoperable for any reason. We recommend you provide advice to the system owner about their needs and building backup redundancy into the hot water supply system.
This water heater is recommended for connection to a minimum 16 hour per day power supply for a 325 litre storage tank and a 24 hour per day power supply for a 410 litre storage tank.
STORAGE TANK AND HEAT PUMP MODULE
The heat pump water heater is made of two main components, the storage tank and the heat pump module. For transport and handling (weight) purposes both items are shipped separately and designed to be assembled at the installation site. The water heater must not be operated until both components are assembled. Refer to “Heat Pump and Tank Assembly” on page 13.
Take care when handling the heat pump module. The jacket of the heat pump module needs to be handled gently so as not to cause damage.
INSTALLATION
5
Care must be taken during transportation and handling. Do not lay the heat pump module down and do not tilt the heat pump module or the heat pump and storage tank assembly more than 30° from the vertical. This will
displace the compressor lubricating oil. If the heat pump module or heat pump and storage tank assembly has been tilted more than 30° from the vertical during handling, it will need one hour to drain back before the power to the water heater can be switched on, otherwise damage to the compressor may result.
All packaging materials must be removed from the heat pump module prior to its installation. This includes the removal of the cardboard base of the carton from the underside of the module.
A clearance of 300 mm is required perpendicular from both the front air inlet louvres and the outlet grille to any wall or obstruction. Refer to the dimensions
diagram on page 9.
The heat pump module must be installed on and fully supported by a stable base.
The water heater must not be installed in an area with a corrosive atmosphere where chemicals are stored or where aerosol propellants are released. Remember the air may be safe to breathe, but the chemicals may attack the materials used in the heat pump system.
Warning: This heat pump module is designed to be installed with a purpose
built water heater storage tank and may not be used for any other purpose.
Note
These instructions cover only the installation of the heat pump module onto the storage tank and the connections made between the heat pump module and storage tank. Refer to the Owner‟s Guide and Installation Instructions supplied with the storage tank for further information including:
where and how to locate the heat pump water heater how to connect the heat pump water heater to the electricity supply and to
the plumbing system
how to operate the heat pump water heater what to do if something goes wrong.
SAFE TRAY
Where damage to property can occur in the event of the water heater leaking, the water heater must be installed in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4 and all local codes and regulatory authority requirements.
INSTALLATION
6
FREEZE PROTECTION
The water heater has a freeze protection system. The freeze protection system will protect the water heater from damage, by preventing ice forming in the waterways of the water heater, in the event of freezing conditions occurring.
If the ambient air temperature falls below 1°C and the heat pump is not operating, the system will operate the circulator periodically. During this freeze protection cycle, the circulator will operate for thirty (30) seconds and then rest for fifteen (15) minutes, before the cycle is recommenced. Water is circulated from the storage tank through the heat pump circuit, to prevent freezing in the connecting pipe work and heat pump module. The green LED will flash a series of four (4) flashes whilst the circulator is operating.
The water heater has NO WARRANTY for freeze damage if power is unavailable at the water heater.
Warning: In areas where the ambient air temperature may fall below 1°C, power must be available to the water heater at all times to prevent freezing in the heat pump circuit.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below, an approved pressure limiting valve is required. Refer to the Owner‟s Guide and Installation Instructions supplied with the storage tank for the position of the pressure limiting valve.
Model
325, 410
Relief valve setting
1000 kPa
Expansion control valve setting *
850 kPa
Max. mains supply pressure
With expansion control valve
680 kPa
Without expansion control valve
800 kPa
Min. mains supply pressure
200 kPa
* Expansion control valve not supplied with the water heater.
A minimum water supply pressure of 200 kPa is required to enable the heat pump circulator and heat pump system to operate effectively.
INSTALLATION
7
TANK WATER SUPPLY
If the water heater is supplied with water from a tank supply and a minimum water supply pressure of 200 kPa at the water heater cannot be achieved, then a pressure pump system must be installed to allow the heat pump circulator to operate and avoid air locks in the circuit. Care must be taken to avoid air locks. The cold water line from the supply tank should be adequately sized and fitted with a full flow gate valve or ball valve.
CONDENSATE DRAIN
A drain line should be fitted to the heat pump module‟s condensate drain to carry the discharge clear of the water heater. The drain line can be extended using 12 mm rigid poly hose or conduit. The pipe work from the condensate drain should be as short as possible and fall all the way from the water heater with no restrictions. It should have no more than three right angle bends in it. The outlet of the drain line must be in such a position that flow out of the pipe can be easily seen - but arranged so water discharge will not cause damage or nuisance.
The condensate drain line must not be connected to the relief valves drain lines but may discharge at the same point.
WARNING
This water heater is only intended to be operated by persons who have the experience or the knowledge and the capabilities to do so. This water heater is not intended to be operated by persons with reduced physical, sensory or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere with the water heater.
This water heater uses 240 V AC electrical power for operation of the control systems and the electrically operated components. The removal of the access cover(s) will expose 240 volt wiring. They must only be removed by a qualified person.
ENVIRONMENT
At the end of the service life of the heat pump water heater and prior to the water heater being disposed of, a person qualified to work with refrigerants must recover the refrigerant from within the sealed system. The refrigerant must not be vented to atmosphere. Phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
INSTALLATION
8
TO TURN OFF THE WATER HEATER
To turn off the water heater:
Switch off the electrical supply at the isolating switch to the water heater. Close the cold water isolation valve at the inlet to the water heater.
Notes
The freeze protection system will be rendered inoperable if electrical
power is not available at the water heater.
Damage caused by freezing due to the unavailability of power at the water
heater is not covered by the Rheem warranty. Refer to “Warranty Note” on page 40.
If the power has been switched off to the water heater and there is a risk of
freezing, then it is necessary to drain the water heater.
Refer to “Draining the Water Heater” in the Owner‟s Guide and Installation
Instructions supplied with the heat pump storage tank.
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Plumbing Industry Commission. This water heater must be installed by a licensed person as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that the work complies with all the relevant Standards. Only a licensed person will have insurance protecting their workmanship for 6 years. Make sure you use a licensed person to install this water heater and ask for your Compliance Certificate.
INSTALLATION
9
DIMENSIONS AND TECHNICAL DATA
300 MIN
ELECTRICAL CONNECTION
VENTILATION CLEARANCE
1018
H
574
HOT
OUTLET
COLD
INLET
E
544
872
B
K
275
100
WALL
AIR
INLET
AIR INLET
C
AIR
OUTLET
300 MIN
VENTILATION CLEARANCE
CONDENSATE DRAIN
TPR VALVE
AIR INLET
AIR
OUTLET
300 MIN
F
A
D
Rheemglas 551 Series
INSTALLATION
10
A
D
1018
H
574
E
544
872
K
100
WALL
AIR
INLET
AIR INLET
C
AIR
OUTLET
300 MIN
CONDENSATE DRAIN
TPR VALVE
AIR INLET
AIR
OUTLET
300 MIN
VENTILATION CLEARANCE
300 MIN
VENTILATION CLEARANCE
HOT
OUTLET
COLD
INLET
ELECTRICAL
CONNECTION
L
F
275
B
M
RheemPlus 554 Series
INSTALLATION
11
Models
Rheemglas RheemPlus
551325 554325
551410 554410
Storage tank capacity
litres
325
410
Boost capacity 1.8 kW
litres
100 -
2.4 kW*, 3.6 kW*
litres
180
200
Dimensions A
mm
1631
1842
B
mm
894
961
C
mm
638
686
D
mm
1317
1479
E
mm
114
127
F
mm
162
650
H
deg
32
30
K
mm
619
686
554 series only L
mm
262
286
554 series only M
mm
1006
1073
Models
Rheemglas
551325
551410
Weight tank empty
kg
88
112
Weight heat pump
kg
42
42
Weight system empty
kg
130
154
Weight system full
kg
455
564
Models
RheemPlus
554325
554410
Weight tank empty
kg
90
112
Weight heat pump
kg
42
42
Weight system empty
kg
132
154
Weight system full
kg
455
564
Heat pump module model no
182550 (R)
Maximum rated power input
watts
3600
Rated heat pump power input
watts
800
Booster element ratings
kW
1.8, 2.4, 3.6
Refrigerant type
R134a
Refrigerant circuit pressure
kPa
3000
* The boost capacity of a 2.4 kW or 3.6 kW low watts density heating unit if used is 100 litres (325 litre storage tank) or 125 litres (410 litre storage tank).
Technical data is subject to change.
INSTALLATION
12
TYPICAL INSTALLATION – OUTDOOR LOCATION
Rheemglas 551 Series Shown