Reznor XBWS11, XBWS62, XBWS46, XBWS36, XBWS28 Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
FORM RZ-NA-I-XBWS-AQ21
MARCH 30, 2005
DXX-2ZERV
Applies to Model XBWS when used with Option AQ21
EN ERGY RE COV ERY VEN TI LA TOR
Vertical Supply and Return Air
INSTALLATION INSTRUCTIONS FOR ROOFTOP STAND ALONE
ENERGY RECOVERY UNIT IN SIDE BY SIDE DESIGN
Energy recovery COMPONENT certified to the ARI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with ARI Standard 1060-2000 . Actual performance in packaged equipment may vary.
I - Ship ping and Pack ing List
Package contains:
1 — Energy Recovery Ventilator Assembly
I I - Ship ping Dam age
Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found.
ETL Certified per UL 1995 and CSA 22.2
III - Gen eral
These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation.
IV - Re quire ments
When installed, the unit must be electrically wired and grounded in accordance with local codes or, in absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70.
V - Ap pli ca tion
These Energy Recovery Ventilators (ERV) are used in a down discharge manner equipped with field provided balancing damper assembly through the roof. A roof curb must be provided to Rooftop Systems specifications. These
wheels conserve energy by mixing warmer air with cooler air in the following manner:
Re cov ery Wheel Mode
The Recovery Wheel mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air. Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work. In winter, the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold, drier intake air supply during the other half rotation. In summer, the process is automatically reversed. Heat and moisture are absorbed from incoming fresh air supply and transferred to the exhaust air stream. This process allows outdoor air ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems.
VI - Rig ging Unit For Lift ing
1- Maximum weight of unit is — Varies per Series {300-1200 Lbs.} (Crated)
2- Remove crating.
3- All panels must be in place for rigging.
4- Remove barometric exhaust hood from door marked filter access. Install barometric exhaust hood over exhaust blower
outlet.
5- Duct work should be installed into roof curb before installing ERV on curb.
6- Roof curb gasket must be applied to all top surfaces of the curb.
PAGE 1
Page 2
6- Forklift channels must be removed from the base of ERV before setting unit on curb.
7 - Position unit on roof curb and provide service access to ERV control access door and wheel.
VII - Installation
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
1- Attach duct work to duct flanges on roof curb.
2- Remove forklift channels from base of ERV.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
3- Set ERV on curb. Verify ERV is positioned on curb properly.
4- Remove barometric exhaust hood from door marked filter access. Install barometric exhaust hood over exhaust blower
outlet.
5- Remove ERV control access panel to connect field wiring.
6- Route class II low voltage wire (3 conductor) from thermostat or energy management through small bushing in end
panel of ERV. See wiring diagram.
a- Thermostat (dependent) - connect in parallel at rooftop unit with "G", "C" and "W". Then connect matching color at
terminal 1, 2, and 3 respectively on ERV circuit board.
b- Energy Management - provide +24 VAC to "1" and common, 24 VAC to "2" terminals on ERV circuit board.
c- Thermostat (dedicated) - splice into +24 vac (blue wire) at (control circuit board) transformer connection run wire to
"R" terminal. Then run another wire from "G" terminal to ERV (control circuit board) terminal block #1.
7- All electrical connections must conform to any local codes and current National Electric Codes (NEC) and Canadian
Electric Codes (CEC). Refer closely to unit wiring diagram in unit and/or in these instructions for proper wiring connections.
8- Refer to the unit nameplate for minimum circuit ampacity (MCA) and maximum overcurrent protection size (fuse).
9- Electrical data is listed on unit rating plate and motor name plates.
10- Connect line voltage power supply to ERV fuse block in control box of unit from disconnect switch. See wiring
diagram.
11- Ground unit with a suitable ground connection either through unit supply wiring or an earth ground.
NOTE-Unit voltage entries must be sealed weather tight after wiring is complete.
12- Remove motor access panels. Locate belts fastened to blower assembly. Install belt onto motor and blower pulley.
Adjust motor sheave to correct blower RPM for CFM and external static pressure requirements. See charts in this instruction. Multiple pulley arrangements are available to meet the entire range.
Caution: Blower speed must be adjusted for the given external static pressure and airflow (CFM) requirements. If
blower speed is not adjusted for conditions, possible motor over loading can occur.
13- Replace access panel onto the ERV unit and secure.
PAGE 2
Page 3
14- Restore power to unit.
15- Cleanup once unit is operating properly, caulk any open joints, holes or seams to make the unit completely air and
water tight.
16- Leave this instruction manual with owner or in an envelope to be kept near unit.
VIII - Op era tion
How It Works
The unit contains an Energy Recovery Wheel (ERW) that is a new concept in rotary air-to-air heat exchangers. Designed as a packaged unit for ease of installation and maintenance, only the connection of electrical power is required to make the system operational.
When slowly rotating through counter flowing exhaust and fresh air streams the ERW adsorbs sensible heat and latent heat from the warmer air stream and transfers this total energy to the cooler air stream during the second half of its rotating cycle. Rotating at 50-60 revolutions per minute, the wheel provides constant flow of energy from warmer to cooler air stream. The large energy transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85% of the difference in total energy contained within the two air streams.
Sensible and latent heat are the two components of total heat. Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air. The latent heat load from the outdoor fresh air on an air conditioning system can often be two to three times that of the sensible heat load and in the winter it is a significant part of a humidification heat load.
During both the summer and winter, the ERW transfers moisture entirely in the vapor phase. This eliminates wet surfaces that retain dust and promote fungal growth as well as the need for a condensate pan and drain to carry water.
Because it is constantly rotating when in the air stream, the ERV is always being cleaned by air, first in one direction then the other. Because it is always dry, dust or other particles impinging on the surface during one half cycle, are readily removed during the next half cycle.
During the heating season, when outdoor air temperatures are below 15oF, it is recommended to use the (optional) low ambient kit (field installed).
Low Ambient Kit is appropriate for climates with limited HVAC system operation when outdoor temperatures are below 10oF.
The frost threshold is the outdoor temperature at which frost will begin to form on the ERV wheel. For Energy Recovery Ventilators, the frost threshold is typically below 10oF. Frost threshold is dependent on indoor temperature and humidify. The table shows how the frost threshold temperatures vary depending on indoor conditions
FROST THRESH OLD TEM PERA TURE
IN DOOR RH AT 70oF
20% 0oF
30% 5oF
40% 10oF
FROST THRESH OLD
TEM PERA TURE
Because Energy Recovery Ventilators have a low frost threshold, frost control options are not necessary in many climates. Where outdoor temperatures may drop below the frost threshold during the ERV operational hours, exhaust only frost control option is available.
Low Am bi ent Kit (Op tional)
Low Ambient Kit turns off the supply blower when outdoor temperatures fall below the frost threshold. The exhaust only thermostat set points are field adjustable. Supply fan operation is automatically restored when the exhaust air temperature rises above the thermostat set point. Provisions for introducing make-up air into the building when the supply blower is off to avoid depressurization should be considered.
Re cov ery Wheel Mode
On a thermostat call for blower operation in heating, cooling or continuous blower, the ERW will rotate between fresh air and exhaust air streams. Both the fresh air and exhaust air blowers will also be operating to overcome the air resistance of the ERV.
PAGE 3
Page 4
IX - Sys tem Check
1- Disconnect main power.
2- Turn to "Cont" for blower operation on thermostat controlled models.
3- Restore power to unit. Observe ERV wheel rotation and both fresh air and exhaust air blowers while operating.
NOTE: If Low ambient kit is used the jumper between TB37-5 & TB37-6 should be removed. Also if system check
out is being conducted at low ambient temperatures, technician should be aware that this kit can cause system not to operate.
4- Verify that the ERV (3) three phase blower motors are phased sequentially ensuring correct rotation and operation.
a - Disconnect power.
b - Reverse any two field power leads to the ERV.
c - Reapply power.
5- Verify that both blower motors are operating under their full load AMP rating (FLA). The FLA can be found on each
motor and the unit nameplate
A - Re turn Damper Set tings
Manually adjust position of field installed dampers to balance air flow.
B - Air Flow / Blower Speed Ad just ment
Blower speed selection is accomplished by changing the sheave setting on both fresh air and exhaust air blowers. To set ERV for the required air flow (CFM), the external static pressure applied to the ERV (duct static) must be known. See the CFM vs External Static Pressure chart for the appropriate unit to determine the correct blower RPM for the specified CFM and External Static Pressure.
After blower speed adjustments have been made. Ensure that when the belt is replaced it is tensioned correctly. The motor mounting plate can be adjusted to tension the belt. If using a belt tension checker, adjust the span to the appropriate setting and check the belt defection force. The belt deflection force should be between 5-8 lbs or the lowest tension at which the belt will not slip under peak load conditions.
5- Disconnect main power to unit before making adjustment to economizer and/or ERV unit.
6- Replace ERV control access cover.
7- Set thermostat to normal operating position.
8- Restore power to unit.
X - Maintenance
1- All motors use prelubricated sealed bearings; no further lubrication is necessary.
2- Make visual inspection of motors, belts and wheel rotating bearings during routine maintenance.
3- Eight pie-shaped segments are seated on stops between
the segment retainer which pivots on the wheel rim and is secured to the hub and rim of the wheel. Annual inspection of the self cleaning wheel is recommended. With power disconnected, remove ERV access panels (rear) and unplug [J150 & P150] (Refer to wiring diagram in this instruction manual). Remove segment and wash with water and/or mild detergent.
WHEEL RIM
E
D
SEGMENT RETAINER CATCH
C
SEGMENT RETAINER
A
D
4- To install wheel segments follow steps A through E . See
Figure 1. Reverse procedure for segment removal.
A- Unlock two segment retainers (one on each side of the
selected segment opening.
B- With the embedded stiffener facing the motor side,
insert the nose of the segment between the hub plates.
C- Holding segment by the two outer corners, press the
segment towards the center of the wheel and inwards against the spoke flanges. If hand pressure does not fully seat the segment, insert the flat tip of a screw driver
PAGE 4
SPOKE
SEGMENT
B
HUB
FIGURE 5
Page 5
between the wheel rim and outer corners of the segment and apply downward force while guiding the segment into place.
D- Close and latch each segment retainer under segment retaining catch.
E- Slowly rotate the wheel 180o. Install the second segment opposite the first for counterbalance. Rotate the two
installed segments 90o to balance the wheel while the third segment is installed. Rotate the wheel 180o again to install the fourth segment opposite the third. Repeat this sequence with the remaining four segments.
XI - Pul ley Kit In stal la tion
The units are shipped from the factory at the low static setting. Pulley kits are available for the medium and high static settings. To install a pulley kit.
1- Check content of pulley kit, if pulley kit contains:
A- An adjustable sheave and a fixed pitch pulley then remove belt and both motor and blower pulley
B- An adjustable sheave then remove the motor pulley.
C. A fixed pitch pulley then remove the blower pulley.
2- Replace pulley(s) with the pulley(s) from pulley kit. Make sure each pulley is installed with a key. Tighten the set screw
on the pulley(s) to 100 in.lb.
3- Install the belt that came with the pulley kit. Tension belt as explained in the blower speed adjustment section.
4- Check the speed of the blower. Adjust the motor sheave to increase or decrease the speed of the blower. See blower
adjustment section.
PAGE 5
Page 6
Stand Alone ERV’S For Down Dis charge Duct Ar range ments
Fea tures and Notes
1. Stand alone design allows higher levels of outdoor air to be introduced into the a/c space.
2. Static test ports provided to verify intake and exhaust CFM.
3. Balancing damper(s) field supplied in duct work when connected to ERV.
4. Roof curbs are available for the ERV’s.
5. See blower performance charts for airflow at various E.S.P..
6. Filter rack with 2" pleated filters included.
Roof Curbs (Op tion Codes)
Size 14" 24"
11 CJ51-11 CJ52-11
20 CJ51-20 CJ52-20
28 CJ51-28 CJ52-28
36 CJ51-36 CJ52-36
46 CJ51-46 CJ52-46
62 CJ51-62 CJ52-62
A
D
B
EXHAUST HOOD
C
FRESH AIR HOOD
EXHAUST RETURN DUCT
(FIELD SUPPLIED)
E
FRESH AIR SUPPLY DUCT
F
4
(FIELD SUPPLIED)
G
EXHAUST
RETURN
J
FRESH AIR
SUPPLY
H
I
K
J
ERV Data Di men sional Data
Size CFM Range
11 300-1100 17.00 x 11.38 44.75 32.13 33.50 11.00 43.00 39.00 17.50 30.25 26.25 11.88 2.50
20 1200-2000 21.88 x 14.00 54.36 37.25 37.50 17.50 52.75 48.75 22.38 35.50 31.50 14.50 2.50
28 1200-2800 20.25 x 17.00 52.25 42.63 43.56 17.50 49.50 45.50 20.75 41.00 37.00 17.50 2.00
36 2000- 3600 23.38 x 17.38 60.00 46.69 57.37 28.00 55.75 51.75 23.88 41.81 37.81 17.91 2.00
46 3000- 4600 23.38 x 20.38 60.00 52.69 57.37 28.00 55.75 51.75 23.88 47.81 43.81 20.91 2.00
62 4600- 6200 29.38 x 30.00 72.00 70.88 63.63 28.00 67.75 63.75 29.88 66.00 62.00 30.50 2.00
Duct Size
(G x J)
A B C D E F G H I J K
ERV Roof Curb
PAGE 6
Page 7
SCHE MATIC DIAGRAM
A131 Fixed Re lay Board
COM PO NENT CODE
B26 Mo tor, Ex haust Air
B27 Mo tor, Fresh Air
B28 Mo tor, Des ic cant W heel
B30 Mo tor, Damper (Op tional)
C23 Ca paci tor, Wheel Mo tor
C25 Ca paci tor, Ex haust Air
C26 Ca paci tor, Fresh Air
DL43 De lay, Cy cle Timer (Op tional)
F29 Fuse
J33 Jack, Cy cle Con trol (Op tional)
J34 Jack, Cy cle Con trol Har ness (Op tional)
J40 Jack, Cy cle (Op tional)
J48 Jack, Con trol Box (Fresh Air)
J50 Jack, Con trol Box (Wheel)
J51 Jack, Con trol Box (Ex haust Air)
J56 Jack, Con trol Box (Damper)
J148 Jack, Fresh Air Mo tor Har ness
J150 Jack, Wheel Mo tor Har ness
J151 Jack, Ex haust Air Mo tor Har ness
J160 Jack, Damper Mo tor Har ness
K94 Re lay, On/Off (Op tional)
K163 Con tac tor, Ex haust Air Mo tor
K164 Con tac tor, Fresh Air Mo tor
P33 Plug, Cy cle Con trol (Op tional)
P34 Plug, Cy cle Con trol Har ness (Op tional)
P40 Plug, Wheel Cy cle (Op tional)
P48 Plug, Fresh Air Mo tor Har ness
P50 Plug, Wheel Mo tor Har ness
P51 Plug, Ex haust Air Mo tor Har ness
P56 Plug, Damper Mo tor Har ness
P148 Plug, Fresh Air Mo tor
P150 Plug, Wheel Mo tor
P151 Plug, Ex haust Air Mo tor
P160 Plug, Damper Mo tor
S23 Ther mo stat - Low Am bi ent (Op tional)
S26 Switch, Low Am bi ent (Op tional)
S51 Switch, Door
S125 Switch, Am bi ent Over ride (Op tional)
T27 Trans former, Con trol
T28 Trans former, Step- down (Op tional)
WIRE COLOR
BK Black
BL Blue
GR Green
GY Gray
OR Or ange
PK Pink
RD Red
WH White
YL Yel low
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Se lec tive volt age ter mi nals for proper unit volt age.
3. Optional low ambient switch.
4. Optional motorized intake damper.
5. Op tional Stop, Start and Jog Con trol.
6. For energy man age ment systems connect +24v to "G" and common 24v to "C".
D11-21-2ZERV
PAGE 7
Page 8
WIR ING DIAGRAM
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Se lec tive volt age ter mi nals for proper unit volt age.
3. Optional low ambient switch.
4. Optional motorized intake damper.
5. Op tional Stop, Start and Jog Con trol.
6. For energy man age ment systems connect +24v to "G" and common 24v to "C".
Des ic cant Wheel for Roof top Unit
208- 230V (1 PH)
PAGE 8
Page 9
SCHE MATIC DIAGRAM
A131 Fixed Re lay Board
COM PO NENT CODE
B26 Mo tor, Ex haust Air
B27 Mo tor, Fresh Air
B28 Mo tor, Des ic cant Wheel
B30 Mo tor, Damper (Op tional)
C23 Ca paci tor, Wheel Mo tor
DL43 De lay, Cy cle Timer (Op tional)
F29 Fuse
J33 Jack, Cy cle Con trol (Op tional)
J34 Jack, Cy cle Con trol Har ness (Op tional)
J40 Jack, Cy cle (Op tional)
J48 Jack, Con trol Box (Fresh Air)
J50 Jack, Con trol Box (Wheel)
J51 Jack, Con trol Box (Ex haust Air)
J56 Jack, Con trol Box (Damper)
J148 Jack, Fresh Air Mo tor Har ness
J150 Jack, Wheel Mo tor Har ness
J151 Jack, Ex haust Air Mo tor Har ness
J152 Jack, Trans former (High Volt age)
J160 Jack, Damper Mo tor Har ness
K94 Re lay, On/Off (Op tional)
K163 Con tac tor, Ex haust Air Mo tor
K164 Con tac tor, Fresh Air Mo tor
P33 Plug, Cy cle Con trol (Op tional)
P34 Plug, Cy cle Con trol Har ness (Op tional)
P40 Plug, Wheel Cy cle (Op tional)
P48 Plug, Fresh Air Mo tor Har ness
P50 Plug, Wheel Mo tor Har ness
P51 Plug, Ex haust Air Mo tor Har ness
P56 Plug, Damper Mo tor Har ness
P148 Plug, Fresh Air Mo tor
P150 Plug, Wheel Mo tor
P151 Plug, Ex haust Air Mo tor
P152 Plug, Trans former (High Volt age)
P160 Plug, Damper Mo tor
S23 Ther mo stat - Low Am bi ent (Op tional)
S26 Switch, Low Am bi ent (Op tional)
S51 Switch, Door
S125 Switch, Am bi ent Over ride (Op tional)
T27 Trans former, Con trol
T28 Trans former, Step- down (Op tional)
WIRE COLOR
BK Black
BL Blue
GR Green
GY Gray
OR Or ange
PK Pink
RD Red
WH White
YL Yel low
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Step-down transformer assembly for 460/575 volt only units.
3. Move wire for dif fer ent volt age in put.
4. Optional low ambient switch.
5. Optional motorized intake damper.
6. For energy man age ment systems connect +24v to green and common 24v to black.
D11-D62-2ZERV
PAGE 9
Page 10
WIR ING DIAGRAM
Notes:
1. Remove jumper to install field optional low ambient switch.
2. Step-down transformer assembly for 460/575 volt units.
3. Se lec tive volt age ter mi nals for proper unit volt age.
4. Optional low ambient switch.
5. Optional motorized intake damper.
6. Op tional Stop, Start and Jog Con trol.
7. For energy man age ment systems connect +24v to "G" and common 24v to "C".
Des ic cant Wheel for Roof top Unit
208- 230/460/575V (3 PH)
PAGE 10
Page 11
SUP PLY
CFM
EXHAUST
CFM
Blower RPM for XBWS11 w/AQ21
Mist Elimi na tor Fil ter in In take Hood (1.5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 300 N/A N/A 1175 1350 1450 1605 1730 500 N/A 1170 1340 1540 1655 1725 1840 700 1295 1425 1600 1625 1795 1960 2035 900 1540 1660 1720 1790 2030 2110 2195
1100 1785 1915 2025 2185 N/A N/A N/A
Ba ro met ric Hood, 2" Pleated Fil ters (1.5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 300 N/A N/A 1030 1225 n/a n/a n/a 500 N/A 1025 1180 1265 1425 1535 n/a 700 1120 1190 1340 1445 1540 1645 1720 900 1285 1525 1500 1575 1670 1785 1865
1100 1570 1665 1670 1775 1860 1920 N/A
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
Blower RPM for XBWS20 w/AQ21
SUP PLY
Mist Elimi na tor Fil ter in In take Hood (2HP)
0 0.25 0.5 0.75 1 1.25 1.5
1200 1055 1135 1295 1420 1540 1650 1725 1400 1140 1240 1340 1490 1600 1690 1795
CFM
EXHAUST
CFM
1600 1200 1330 1460 1565 1645 1740 1830 1800 1320 1405 1525 1615 1705 1785 1885 2000 1415 1515 1605 1690 1775 1875 1960
Ba ro met ric Hood, 2" Pleated Fil ters (2HP)
0 0.25 0.5 0.75 1 1.25 1.5
1200 1010 1195 1350 1445 1580 1685 1735 1400 1125 1315 1435 1545 1620 1730 1800 1600 1185 1370 1500 1610 1695 1790 1965 1800 1305 1485 1600 1685 1781 1955 2030 2000 1410 1550 1670 1765 1855 N/A N/A
RPM Range
Low 1000- 1300 Stan dard Unit Me dium 1300- 1700 Op tional Kit High 1750-2200 Op tional Kit
Ex ter nal Static Pres sure (in wa ter)
Ex ter nal Static Pres sure (in wa ter)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
RPM Range
Low 1000- 1300 Stan dard Unit Me dium 1300- 1700 Op tional Kit High 1700- 2080 Op tional Kit
PAGE 11
Page 12
SUP PLY
CFM
EXHAUST
CFM
Blower RPM for XBWS28 w/AQ21
Mist Elimi na tor Fil ter in In take Hood (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 1200 N/A 790 960 1110 1210 1315 1380 1600 750 900 1005 1145 1230 1365 1410 2000 900 1005 1105 1210 1275 1400 1450 2400 1005 1125 1210 1275 1365 1450 1500 2800 1125 1230 1315 1380 1450 1535 1600
Ba ro met ric Hood, 2" Pleated Fil ters (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 1200 750 885 1015 1145 1260 1350 1485 1600 870 1015 1125 1215 1325 1410 1500 2000 1015 1145 1240 1345 1410 1485 1560 2400 1125 1250 1345 1430 1500 1575 1630 2800 1250 1410 1485 1520 1630 1650 1675
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
Blower RPM for XBWS36 w/AQ21
SUP PLY
Mist Elimi na tor Fil ter in In take Hood (3HP)
0 0.25 0.5 0.75 1 1.25 1.5 2000 725 825 900 1000 1070 1180 1250 2400 800 900 1000 1070 1160 1250 1275
CFM
EXHAUST
CFM
2800 900 1000 1070 1160 1250 1275 1340 3200 1000 1070 1160 1250 1275 1340 1400 3600 1055 1180 1250 1300 1360 N/A N/A
Ba ro met ric Hood, 2" Pleated Fil ters (3HP)
0 0.25 0.5 0.75 1 1.25 1.5 2000 750 865 950 1030 1100 1200 1265 2400 820 950 1035 1100 1200 1265 1300 2800 925 1035 1150 1200 1265 1315 1350 3200 1035 1160 1215 1265 1325 1350 1390 3600 1100 1215 1300 1350 1390 N/A N/A
RPM Range
Low 750-975 Stan dard Unit Me dium 1008-1314 Op tional Kit High 1311-1708 Op tional Kit
Ex ter nal Static Pres sure (in wa ter)
Ex ter nal Static Pres sure (in wa ter)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
RPM Range
Low 725-975 Stan dard Unit Me dium 1000-1315 Op tional Kit High 1215-1425 Op tional Kit
PAGE 12
Page 13
SUP PLY
CFM
EXHAUST
CFM
Blower RPM for XBWS46 w/AQ21
Mist Elimi na tor Fil ter in In take Hood (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 3000 900 1030 1100 1165 1240 1285 1350 3400 975 1085 1175 1240 1290 1350 1400 3800 1070 1175 1240 1290 1350 1400 1465 4200 1165 1240 1320 1350 1430 1465 1515 4600 1240 1320 1375 1430 1500 1515 1580
Ba ro met ric Hood, 2" Pleated Fil ters (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5 3000 955 1100 1160 1245 1280 1360 1425 3400 1055 1185 1245 1300 1375 1425 1480 3800 1160 1300 1360 1400 1425 1530 1585 4200 1245 1375 1450 1480 1500 1585 1650 4600 1360 1450 1500 1585 1600 1650 1700
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
Blower RPM for XBWS62 w/AQ21
SUP PLY
Mist Elimi na tor Fil ter in In take Hood (5HP)
0 0.25 0.5 0.75 1 1.25 1.5 4600 815 900 975 1045 1085 1125 1175 5000 880 940 1015 1060 1135 1175 1215
CFM
EXHAUST
CFM
5400 915 975 1045 1125 1150 1195 1250 5800 975 1045 1085 1175 1250 1260 N/A 6200 1000 1075 1165 1200 N/A N/A N/A
Ba ro met ric Hood, 2" Pleated Fil ters (5HP)
0 0.25 0.5 0.75 1 1.25 1.5
4600 825 915 1000 1025 1100 1140 1170 5000 890 975 1025 1100 1140 1170 1240 5400 925 1000 1085 1140 1170 1240 1280 5800 975 1025 1140 1170 1240 N/A N/A 6200 1025 1120 1170 N/A N/A N/A N/A
RPM Range
Low 780- 1020 Stan dard Unit Me dium 1000- 1315 Op tional Kit High 1315- 1700 Op tional Kit
Ex ter nal Static Pres sure (in wa ter)
Ex ter nal Static Pres sure (in wa ter)
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.
RPM Range
Low 820- 1000 Stan dard Unit Me dium 1000- 1200 Op tional Kit High 1175- 1375 Op tional Kit
PAGE 13
Page 14
Notes
1-800-695-1901; www.RezSpec.com
©2004 Thomas & Betts Corp. All rights reserved. Printed in U.S.A. Reznor® is registered in at least the United States. All other marks are the property of their respective organizations.
Loading...