Reznor VPT150 Installation Manual

Page 1
INSTALLATION / OPERATION / MAINTENANCE
Applies to: Model VPT 120V 60Hz
Low-Intensity Infrared Heater
Model VPT
High/Low Burner/Control Box
with 20 - 70 ft Tube/Reflector Length
Doc No 700106 (06-15), Page
Part No. 270684
Page 2
Introduction.
Welcome to the new range of powered HiLo infra-red heaters. Local regulations may vary and it is the installer’s responsibility to ensure that such regulations are satisfied.
All installation, assembly, commissioning and service procedures must be carried out by suitable qualified competent persons and conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the National Gas and Propane Installation Code CSA B149.1.
When assembling, installing, commissioning
Document Index.
1 Installation Requirements
1.1 Health & Safety
1.2 Heater Suspension
1.3 Clearance to Combustibles
1.4 Gas Connection & Supply Details
1.5 Electrical Connections
1.6 Ventilation Requirements
1.6.1 Unvented Units
1.6.2 Vertical Venting
1.6.3 Horizontal Venting
1.7 Fresh Air Intake
1.8 Technical Details
2 Assembly Instructions
2.1 Tools Required
2.2 Assembly Notes
2.2.1 Emitter tubes
2.2.2 Turbulator Strips and Burner Inserts
2.2.3 Brackets
2.2.4 Couplers
2.2.5 Reflectors
2.2.6 End Caps (optional)
2.2.7 Bends (where required)
2.2.8 Burner/Fan Assembly
2.2.9 Detailed Assembly Drawings
and servicing is undertaken on radiant tube heaters specified in these instructions, due care and attention is required to ensure that working at height regulations are adhered to
PLEASE READ this document prior to
installation to familiarize yourself with the components and tools you require at the various stages of assembly.
All Dimensions shown are in inches unless otherwise stated.
The manufacturer reserves the right to alter specifications without prior notice.
3 Start Up Instructions
3.1 Tools Required
3.2 Start up procedure
4 Servicing Instructions
4.1 Tools Required
4.2 Burner Description
4.3 Burner Removal
4.4 Burner Gas Injector Servicing
4.5 Burner Head and Electrode Servicing
4.6 Combustion Fan Assembly
4.7 Emitter Tube Servicing
4.8 Reflector Servicing
4.9 Cleaning of Vent
4.10 Re-commissioning after Service
5 Troubleshooting Guide 6 Replacing Parts
6.1 Burner Controller Replacement
6.2 Air Pressure Switch Replacement
6.3 Gas Valve Replacement
7 User and Operating Instructions
7.1 To Start Heater
7.2 To Switch Off Heater
7.3 Servicing
1. Installation Requirements.
1.1 Health and Safety
A. Heater is intended for heating
non-residential indoor spaces and should only be installed where flammable gases or vapors are not present.
B. Heaters can be suspended horizontally or at
any angle along the axis of the tubes but can only be rotated about the burner head 0 to 55°. See section 1.3 for clearance dimensions.
Doc No 700106 (06-15), Page 2
C. The installation must conform with local
building codes or, in the absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
D. The unit shall be electrically grounded in
accordance with National Electric Code ANSI/NFPA 70 and Canadian Electrical Code CSA C22.1.
E. The heater may be installed in aircraft
hangars in accordance with the Standard for Aircraft Hangars, ANSI/NFPA 409 and in
Page 3
automotive garages when installed in accordance with the Standard for Parking Structures, ANSI/NFPA 88A, or the Standard for Repair Garages, ANSI/NFPA
88B, or the Canadian Natural Gas and Propane Installation Code, CSA B149.1,
and are so marked. Ensure that minimum clearances will be maintained to vehicles parked below the heater.
F. The standard heaters are approved for
installations between 0 - 2000ft (0 - 610m)
above sea level for the US and 0 - 4500 ft
(1370m) above sea level for Canada.
Conversion kits are available for installations
above these heights in the USA.
G. Massachusetts Requirement: If the heater is being installed in the Commonwealth of Massachusetts, this unit must be installed by a licensed plumber or licenced gas fitter.
1.2 Heater Suspension
Attachment to the heater support lugs should be made by D shackle. The hanging attachments to overhead steelwork etc. have
to be designed and produced in accordance with sound engineering practices. They must be adequately fixed and designed to carry the whole weight of the heater. In the event of suitable roof steelwork being unavailable, additional steelwork should be fitted to enable vertical hangers to be used for suspending the heaters.
These methods are illustrated in Figure 1. If there are any doubts as to the strength or suitability of roof steelwork to which heaters are to be suspended, please refer to a Consultant, Architect or owner of the building.
It is recommended that the heater is raised to its final position once the assembly of the emitter tube/bracket/reflector has been completed. Longer tube assemblies may be raised in more than one sub-assembly with final emitter tube connection made in the air.
Ensure that the installer uses the burner roof support mounting bracket when suspending the heater. This is situated on the front of the burner. When packed the bracket is reversed and must be turned to its correct state for mounting. (ref page 15)
WARNING:
If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which are known to the state of California to cause cancer, birth defects or other reproductive harm.
U TUBE VARIANTS
NOTE. 'S' HOOKS ARE TO
BE CLOSED UP AFTER ASSEMBLY
SUITABLE CHAIN
WORKING LOAD
LIMIT 100LB
EXHAUST
END
CHAIN
55° SUSPENSION
Figure 1. Recommended Methods of Heater Suspension.
Doc No 700106 (06-15), Page 3
BURNER
END
Page 4
ON VENTED HEATERS, THE HEATER SHOULD SLOPE DOWNWARDS AWAY FROM THE BURNER AND ON UNVENTED HEATERS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. ½” FOR HORIZONTAL INSTALLATIONS AS SHOWN BELOW (DIAGRAMS EXAGGERATED FOR CLARITY)
1/2”
VENTED
1/2”
UNVENTED
1.3 Clearance to Combustibles.
Minimum clearance to combustibles are shown in Table 1 below.
IMPORTANT:
The stated clearance to combustibles represents a surface temperature of 90°F (50° C) above room temperature. Building material with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
Table 1
MODEL A A1 / A2 B B1 C1 C2 C3 D1 D2 E
Clearance to Combustibles, inches (cm)
60
74
(188)
29
(74)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
12
(31)
12
(31)
80
74
(188)
29
(74)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
12
(31)
12
(31)
15° = 72 (183) 25° = 68 (173)
100
74
(188)
35° = 61 (155) 45° = 53 (135)
32
(82)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
16
(41)
12
(31)
55° = 43 (110)
125
150
170
74
(188)
74
(188)
86
(219)
15° = 82 (209) 25° = 78 (199)
39
(99)
39
(99)
48
(122)
47
(120)
48
(122)
48
(122)
20 (51) /
10* (26)*
20 (51) /
10* (26)*
20 (51) /
10* (26)*
8
(21)
8
(21)
11
(28)
22
(56)
22
(56)
22
(56)
20
(51)
20
(51)
20
(51)
18
(46)
18
(46)
20
(51)
12
(31)
12
(31)
12
(31)
35° = 71 (181) 45° = 61 (155)
200
* distance with end caps fitted.
86
(219)
WARNING:
55° = 50 (127)
Minimum clearance from the heater must be maintained from vehicles parked below heater. In all situations, clearances to combustibles must be
48
(122)
48
(122)
20 (51) /
10* (26)*
11
(28)
22
(56)
20
(51)
20
(51)
12
(31)
maintained. Signs should be posted in storage areas to specify maximum stacking height to maintain required clearance to combustibles. Such signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location. Refer to mounting clearance tables.
Doc No 700106 (06-15), Page 4
Page 5
Figure 2 Clearance to Combustibles (Standard indoor reflectors)..
The minimum clearances to combustible materials are given in Table 1 These minimum
distances MUST be adhered to at all times. Adequate clearance MUST be provided around air openings into the combustion chamber and there MUST be suitable clearance for accessibility and for combustion / ventilating air supplies.
D2
A2
.
0° to 55°
Angled view.
Return end on
U tube heater
A1
C3
WARNING!
combustion and ventilation air supply.
provision in the building for
Ensure that there is adequate
Installation must meet minimum
B
requirements and applicable codes.
Below
A
Outlet end.
heater
D1
End
B1
Side
unvented
unvented
unvented
Above outlet
Above
Reflector
C2
Burner end.
B
Side
Doc No 700106 (06-15), Page 5
vented
End view.
C1
Above
Burner
Above
C1
Burner
E
E
Service
distance
Service
distance
Page 6
1.4 Gas Connection and Supply
WARNING: Before installation, check
that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The gas connection on the heater is ½” N.P.T internal thread.
Injector sizes and manifold pressure for the burners are shown in the table 3. The gas supply piping and connections must be installed so that the minimum pressure stated is achieved.
A gas shut off valve and union should be fitted in the gas supply line close to the heater and a ” N.P.T plugged tapping, accessible for test gauge connection, provided immediately upstream of the appliance gas inlet.
It is essential to provide some flexibility in the final gas connection by use of an approved flexible gas connector. (See Fig 4.)
Take care when making a gas connection to the heater not to apply excessive turning
force to the internal controls.
Care must be taken to observe the pipe bend diameter of 12” (30cm) and pipe displacement distance of 3” (7.62cm).
The correct installation as shown will allow for approx 4” of movement due to
expansion.
Figure 3. Correct orientation of Ball Valve
Gas Flow
Gas Flow
Figure 4. Correct Installation of Flexible Gas Connection
* Connector must be certified for use on a radiant tube type infrared heater and must comply with Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 or with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas, CAN/CGA 8.1.
For heaters up to 150,000Btu/h, ½” ID x 24” long For heaters 150,000Btu/h and above, ¾” ID x 36” long NOTE: For Canada all heaters MUST use a hose 36” long (See Table 3)
Table 3
HOSE SIZE USA CANADA
3/4” CE4
CONTACT FACTORY
WARNING: FIRE OR EXPLOSION HAZARD - It is essential to provide some flexibility in
the final gas line connection by use of an approved flexible connector as shown in the
drawings. Expansion of the radiant pipe occurs with each firing cycle causing the burner to move with respect to the gas line. This can result in a gas leak producing an unsafe condition.
Doc No 700106 (06-15), Page 6
Page 7
CONNECTOR MUST BE INSTALLED IN A “U” CONFIGURATION. FOR HEATERS UP
TO 150,000 BTU/H, A 24” LONG CONNECTOR OF AT LEAST ½” ID MUST BE USED. FOR HEATERS ABOVE 150,000 BTU/H, A 36” LONG CONNECTOR OF AT LEAST ¾” NOMINAL ID MUST BE USED.
Table 4 Gas Supply Pressures
Gas Type
Min Required Gas Pressure (in W.C)
Max Supply Pressure (in W.C)
Natural Gas LP/Propane Gas
7.0 11.0
14.0 14.0
Gas Supply Connection ½” N.P.T thread
1.5 Electrical Connections
Important: All electrical work should be done by a qualified electrician in strict accordance with the
WARNING: Before making electrical
connections, switch OFF the main electrical disconnect. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
National Electrical Code ANSI/NFPA 70 or Canadian Codes CSA C22.1.
The electrical supply to the heater is by three wires: hot (Live), neutral and ground connections.
Install in accordance with
This appliance must be electrically grounded
Supply 120V 60Hz single phase. Standard heater 0.16HP. Current rating (inductive):
1.8 amp max (models 60 - 150)
1.0 amp max (models 170 & 200)
all state & local codes.
Where alternative manufacturers controls are used, please refer to their instructions for their installation details.
Fuse: external 3 amp.
Figure 5. External Wiring Schematic
Burner 1
BK
BL R
O
120V AC
Supply
24V AC
Terminals
(120V AC Fan
Terminals)
BK
G
W
Doc No 700106 (06-15), Page 7
R
C
W1
W2
F1
F2
E
N
L
E
N
24V AC 2-Stage
Thermostat (Ext.)
W1 W2
RC
KEY:
BK-BLACK
BL-BLUE
R-RED
O-ORANGE
G-GREEN
W-WHITE
Notes:
Use 18/4 class 2 thermostat cable between heater and thermostat.
Max. length @ 18 Awg (0.8mm²) = 100ft.
Only one burner can operate from one thermostat as supplied.
When servicing heaters ensure the electricity supply is isolated from the mains supply.
120V AC supply is still present at each burner when the thermostat is switched off.
Page 8
Figure 6a. Internal Burner Wiring Diagram.
24V Two stage
Thermostat
R
BR
24V AC Stat
Terminals
R
BR
YY
Pressure Switch
E
LN
W2W1
C
G
O
BL
120V AC Fan
W
BK
120V AC
G
R
K
Terminals
W2W1
C
O
BL
F1 NEF2
K
G
R
W
BK
BK
Supply
LNE
G
BK
W
KEY:
BL - BLUE
BK - BLACK
W
BR - BROWN
GR - GREY
G - GREEN
E
E
K - PINK
R - RED
W - WHITE
Y - YELLOW
BK
120V/24VAC 60Hz
Transformer
BR
W
O - ORANGE
P - PURPLE
Power ON (red)
BL BR
High Fire
Low Fire
Relay
R
1222
A2
24V AC RELAY
21
NC
A1
COIL
1424
NO
11
COM
BL
BK
R
Y
Y
P
R
BK
L1
IND
MV
O
BR
R
W1
PS1
PS0
BR
BL
GR
X
C
COM
Gas Control
(amber)
High Fire
P
M
GR
C
K
HI
NOTES:­Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner.
Additional wiring is required to install an optional extra thermostat and / or time clock. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
PGR
KGR
Gas Valve
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
Doc No 700106 (06-15), Page 8
Page 9
1.5.1 Multiple burner configurations (Master & Slave) via Optional Relay . Refer to figure 6b and 6d.
Multiple VPT burners can be controlled via one main burner. In this scenario the main burner is knows as the ‘Master’ and any additional burners are known as ‘Slaves’.
The external two stage thermostat is connected to the Master burner and powered via the inbuilt transformer. The total burner load for the Master is 20VA. Each additional ‘Slave’ burner is 1.6VA
The Thermostat chosen to control the multiple heaters must not have a power requirement exceeding the spare capacity as shown in the examples below:
CONFIGURATION TOTAL BURNER LOAD SPARE FOR THERMOSTAT
Master PLUS 1 Slave 21.6VA
Master PLUS 3 Slaves 24.8VA
Master PLUS 5 Slaves 28.0VA
Master PLUS 7 Slaves 31.3VA
Figure 6b. Wiring schematic. Multiple Burners Master and Slave.
GND L2 L1 (HOT)
120V 60Hz 1 Ph
Supply circuit
R C W1 W2
MASTER BURNER
W1 W2
R C
THERMOSTAT
24VAC 60Hz 1 Ph Hi/Lo circuit
1.5.2 Multiple burner configuration via independently powered two stage thermostats. Refer to figures 6c and 6d.
Note: If the thermostat has an independent power supply, all burners in the zone to be controlled MUST be Slave burners.
The maximum number of Slave burners per thermostat is dependent on the maximum power output of the thermostat selected.
LEN
SLAVE
BURNER
W1 W2
Each ‘Slave’ burner is rated at 1.6VA 24VAC 60Hz.
The external two stage thermostat is powered via its own power supply and must output to each Slave burner - 24VAC for low fire to terminal W1 and 24VAC for hi fire to both terminals W1 and W2
Refer to thermostat manufactures literature for details.
18.4VA
15.2VA
12.0VA
8.8VA
LENLENLEN
SLAVE
BURNER
W1 W2 W1 W2
SLAVE
BURNER
Figure 6c. Wiring schematic. Multiple Burners via independently powered Relay.
GND
L2
L1 (HOT)
120V 60Hz 1 Ph Supply circuit
Low fire output
Hi fire output
THERMOSTAT
Supply Circuit
(by others)
Doc No 700106 (06-15), Page 9
24VAC 60Hz 1 Ph Hi/Lo circuit
W1 W2
SLAVE
BURNER
LEN
SLAVE
BURNER
W1 W2
LENLENLEN
SLAVE
BURNER
W1 W2 W1 W2
SLAVE
BURNER
Page 10
Figure 6d. Internal Slave Burner Wiring/External Schematic Diagram with Optional Relay.
1222
A2
24V AC
RELAY
21
R
A1
COIL
O
1424
NO
11
BL
OPTIONAL RELAY WIRING
COM
O
BR
BL
Relay mini harness leads
5A connector
24V Two stage
Thermostat
R
24V AC Stat
Terminals
R
BR
YY
Pressure Switch
W2W1
C
K
O
G
R
W
BK
120V AC Fan
Terminals
W2W1
C
BL
F1 NEF2
K
G
R
W
BK
E
E
L
G
BK
120V AC
Supply
LNE
G
BK
E
N
W
KEY:
BL - BLUE
BK - BLACK
W
BR - BROWN
GR - GREY G - GREEN
K - PINK
R - RED
W - WHITE
Y - YELLOW
BK
120V/24VAC 60Hz
Transformer
BR
W
O - ORANGE
P - PURPLE
Power ON (red)
BL BR
PGR
High Fire
Relay
R
1222
A2
24V AC RELAY
21
NC
A1
COIL
1424
NO
11
COM
BL
BK
R
Y
Y
P
R
BK
L1
MV
IND
O
BR
R
W1
PS1
PS0
BL
BR
GR
X
C
COM
Gas Control
Low Fire
(amber)
High Fire
P
M
GR
C
K
HI
KGR
Gas Valve
NOTES:­Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner. Additional wiring is required to install an optional extra thermostat and / or time clock. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
Doc No 700106 (06-15), Page 10
Page 11
1.6 Vent Requirements and Details
1.6.1 Unvented units
Heaters may be installed unvented providing the governing building codes are met and consideration is properly given to possibilities of condensation on cold surfaces.
Installation shall meet the following requirements when unvented:
Natural or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1000 BTU per hour input of installed heaters.
Combustion gases shall not impinge on combustible materials.
1.6.2 Vertical venting
The heater can be installed with a vertical vent.
All vent piping should be adequately supported from the building structure and terminated with an approved terminal.
recommended vent length is 25ft (7.6m) with a maximum of two elbows
should be properly sealed. refer fig 7a
1.6.3 Horizontal venting
Individual units can be vented horizontally through side walls. Recommended terminals are Part Numbers 111848 for 4” and 111850 for 6”.
Distances from adjacent public walkways, adjacent buildings, openable windows and building openings, consistent with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
The maximum recommended vent length is 25ft (7.6m) with a maximum of two 90° elbows.
However runs up to 12ft (3.6m) can use 4” (101mm) vent pipe. Runs over 12ft (3.6m) should always use 6” (152mm) vent pipe.
An approved clearance thimble is required when the flue pipe passes through combustible materials. Follow the requirements of the thimble manufacturer.
Standard vent terminals must extend at least 6” (152mm) from the wall and at least
The maximum
. All connections
24” (609mm) from any combustible overhang. This protects the building material from degradation by the vent gases.
Vent joints should be sealed and secured according to the vent manufacturers instructions. Should condensation occur the vent should be shortened or insulated.
The terminal should be at least 3ft (0.91m) from any air intake to the building.
The vent terminal must be installed at a suitable height above the ground to prevent blockage by snow.
1.7 Fresh Air Intake
Whenever the heater is installed in locations where airborne dust or other pollutants are present, a fresh air supply should be ducted to the burner.
If the heater is equipped with ducted combustion air, the vent terminal must be at least 3ft (0.91m) away from the air inlet and located higher than the inlet.
A fresh air duct of 4” (101mm) diameter should be installed from the fresh air to the air intake connection on the fan housing. A flexible jointing piece should be installed at the fan connection with hose clamps to facilitate expansion and contraction.
The maximum recommended length air duct is 25ft (7.6m) and the maximum number of elbows is two. The minimum length is 18” (456mm).
The location of the fresh air duct inlet must be where it will receive dust free clean air. An inlet cap with bird screen must be fitted at the inlet of the duct. If the duct inlet is located above the roof the underside of the inlet terminal must be at least 2ft (0.61m) above roof level (or above projected snow load) and at least 10” (254mm) above any projection on the roof within 7ft (2.1m) of the inlet. Intake pipe, fittings and sealant are not furnished by the manufacturer. Refer fig 7c & d.
Note the vent terminal must NOT be installed below the fresh air intake, and should have a minimum separation distance of 36” from the air intake.
Note The vent terminal should be installed so as to be in the same atmospheric pressure zone as the combustion air inlet of the appliance.
Doc No 700106 (06-15), Page 11
Page 12
Figure 7.a Vertical Venting.
Figure 7.b Horizontal Venting (plan view shown).
Approved clearance thimble is required when the flue pipe extends through combustible materials. Follow the requirements of the thimble and/or Category III vent pipe manufacturer.
Approved clearance thimble is required when the flue pipe extends through combustible materials. Follow the requirements of the thimble and/or Category III vent pipe manufacturer.
Aluminum 4” (101mm) O.D. pipe. Max length = 25’0” (7.62M) with 2
x 90° long radius bends.
Clamps
4” (101mm) O.D. flexible duct
Burner
Note The vent terminal should be installed so as to be in the same atmospheric pressure zone as the combustion air inlet of the appliance.
Note the vent terminal must NOT be installed below the fresh air intake, and should have a minimum separation distance of 36” from the air intake.
Figure 7.c Fresh Air Ducted Intake.
Doc No 700106 (06-15), Page 12
Page 13
1.8 Technical Details - Table 5
No of Injectors
Gas Connection
Electrical Supply
Vent size (in)
Unitary Fan Motor Details
Current Rating
Ignition
Natural Gas LP Gas
MODEL
High / Low High / Low
60
80
100
125
150
60,000/48,000 60,000/48,000
80,000/60,000 80,000/60,000
100,000/75,000 100,000/75,000
123,500/95,000 125,000/95,000
150,000/100,000 150,000/100,000
1
½” N.P.T
120 volt 1 phase 60Hz
4” or 6” (101mm or 152mm)
120 volt 1 phase 60Hz
1.8A MAX (models 60 - 150); 1.0A MAX (models 170 & 200)
Electronic Program Start up with Spark Ignition
Min. Heater
Length
Max. Heater
Length
Min. Heater
Length
Max. Heater
Length
S ft S ft U ft U ft
20 40 20 40
30 40 40 40
30 40 40 40
30 50 40 40
40 60 40 60
170
200
169,000/125,000 169,000/125,000
200,000/160,000
N/A
50 70 60 60
50 70 60 60
Appliances can be installed up to 10,000ft above sea level in the USA. Altitude conversion kits are available on request.
USA 0- 2000 ft (0-610m) above sea level
Size
Gas
Hi “WC
Lo “WC
60 80 100 125 150 170 200
Natural Gas
3.9 3.5 4.5 4.3 4.0 3.3 4.0
2.6 2.3 3.0 2.7 2.1 1.9 2.5
USA 0- 2000 ft (0-610m) above sea level
Size
Gas
Hi “WC
60 80 100 125 150 170 200
LP Gas
5.5 5.2 8.0 7.6 7.0 6.1 N/A
CANADA 0- 2000 ft (0-610m) above sea level
Size
Gas
Hi “WC
Lo “WC
60 80 100 125 150 170 200
Natural Gas
3.9 3.5 4.5 4.3 4.0 3.3 4.0
2.6 2.3 3.0 2.7 2.1 1.9 2.5
CANADA 0- 2000 ft (0-610m) above sea level
Size
Gas
Hi “WC
60 80 100 125 150 170 200
LP Gas
5.5 5.2 8.0 7.6 7.0 6.1 N/A
Lo “WC
Doc No 700106 (06-15), Page 13
3.5 2.9 4.4 4.6 3.3 3.6 N/A
Lo “WC
3.5 2.9 4.4 4.6 3.3 3.6 N/A
Page 14
Technical Details continued
USA & CANADA Natural Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate Part No.
Flame Plate Part No.
Fan Part No.
Fan Orifice Part No.
Injector Part No.
Injector Carrier Part No.
Pressure Switch Part No.
60 80 100 125 150 170 200
269941 269942 269943 269944 1005513 269946 269946
N/A
270464
269922 269925 269925 269930 269931 266935 269938
270400 270402 270403 270405 270407 270409 270410
270375 270376
270389 270390
USA & CANADA LP Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate Part No.
Flame Plate Part No.
Fan Part No.
Fan Orifice Part No.
Injector Part No.
Injector Carrier Part No.
Pressure Switch Part No.
60 80 100 125 150 170 200 269948 269949 269950 269951 269952 269953 269957 269958 269959 269960
270464 270467 269924 269925 269929 266931 269933 269937 270398 270400 270401 270403
270399
270375 270389
270467
N/A
MODEL
VCT
U20 U40 U60 S20 S30 S40 S50 S60 S70
60
80
100
125
150
170
200*
* Nat Gas ONLY
MODEL
VCT
60
80
100
125
150
170
200
U Tube Straight Tube
Emitter Tube Type Material
Calcoat™ Mild Steel
Min. Distance to Bend
ft (m)
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 15 (4.6)
TUBE 1 REMAINDER 15 (4.6)
TUBE 1 REMAINDER 20 (6.1)
TUBE 1 & 2 REMAINDER 25 (7.6)
TUBE 1 & 2 REMAINDER 25 (7.6)
Doc No 700106 (06-15), Page 14
Page 15
2. Assembly Instructions.
PLEASE READ this section prior to
assembly to familiarize yourself with the components and tools you require at the various stages of assembly. Carefully open the packaging and check the contents against the parts and check list.
The manufacturer reserves the right to alter specifications without prior notice.
2.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Saw
Horses
Cordless Drill
Leather Faced Gloves
5/16” Drive
Please ensure that all packaging is
disposed of in a safe environmentally
friendly way.
For your own safety we recommend the
use of safety boots and leather faced gloves when handling sharp or heavy items. The use of protective eye wear is also recommended.
Suitable alternative tools may be used.
Phillips Screwdriver
3/16” (5mm) 5/32” (4mm) Allen wrench
Wrench Set
Tape Measure
2.2 Assembly Notes.
Please read these assembly notes in
conjunction with the correct assembly drawings (figs 9 to 17).
2.2.1 Emitter Tubes
Each heating unit has two types of emitter tube. For details of the tube types and position please refer to the table (page 14 of this instruction manual).
Identify and position emitter tubes on saw horses. For aesthetics it is advisable to position
all tube seams facing down. Position coupling
fastener so that these cannot be seen from beneath the heater.
Mark out the position of the bracket centers from the dimensions shown on the assembly drawings.
2.2.2 Turbulator Strips and Burner Inserts
Ensure that the correct turbulator or burner insert is fitted, as this could void your warranty if they are incorrectly fitted or omitted when necessary.
2.2.2.1 Turbulator Strips
Turbulator strips should be inserted (when required) into the correct emitter tube exactly as indicated in the assembly drawings.
Locate turbulator strip sections. Install the first turbulator strip into the open end of the last emitter tube (only after it has been suspended and connected to the previous emitter tube.)
Interlock the next section of turbulator strip as shown in the diagram below.
Doc No 700106 (06-15), Page 15
Page 16
Slide the connected sections into the emitter tube(s). Add further strips to form the correct length required.
2.2.2.2
Where a heater configuration requires more than three turbulator strips and has the exhaust heat exchanger tube adjacent to an “L” or “U” heat exchanger tube, refer to the diagram below for positions.
For specific configurations see detailed assembly diagrams on pages 21 to 29.
Vent
Model 200 S50 fan orifice plate
This model has a different fan orifice plate (Part No.269939) to all other models in the range. It is supplied with every burner as a loose item and should be discarded if not needed. This must be fitted to the 200 S50 model only.
Note: There should be 22 10mm x 10mm square holes in the replacement plate.
Remove the top cover of the burner to expose the combustion fan.
Remove the four screws (arrowed), three of which can not be seen in the photograph. Lift out the fan assembly to access the fan.
Remove the four fixing screws securing the existing orifice plate, then fit the replacement orifice plate with the correct air inlet hole orientation as shown in the picture opposite.
Fit three turbulator strips here
Vent
Fit the remaining turbulator strips here
Doc No 700106 (06-15), Page 16
Page 17
2.2.2.2 Burner Inserts
The burner insert (when required) is inserted into the first heat exchanger emitter tube from where it is joined to the second emitter tube.
2.2.3 Brackets
There can be various styles of brackets supplied with these heaters:
2.2.3.1 Suspension Brackets
2.2.3.1.1 Fixed suspension bracket assembly part #270126 & tube straps part #270572.
ONLY used as the first suspension bracket
positioned CLOSEST TO THE BURNER.
SUSPENSION BRACKET
SUSPENSION BRACKET
RADIANT
TUBE
PART #270126
2.2.3.2 Reflector Support Brackets
Reflectors are positioned above the emitter tube with a reflector support bracket part #270569.
RADIANT TUBE
TUBE
STRAP
SUPPLIED
NUT &
BOLT
SUPPLIED NUT & BOLT
RADIANT
TUBE
"A"
VIEW ON "A"
PARTS #270126 plus #270572
TUBE
STRAP
Slip the suspension first bracket assembly ­part #270126 onto the first section of emitter tube in the position as indicated on the assembly drawing.
Locate the tube strap assembly part #270572 and loosen the nut and bolt.
Position the strap over the emitter tube and hook the two straps onto the suspension bracket.
Finally tighten the nut and bolt to secure the bracket onto the emitter tube.
2.2.3.1.2 Suspension brackets #270126 with no tube straps. For
ALL other suspension
brackets
Once the emitter tubes have been assembled using the couplers (see section 2.2.4), position all other suspension brackets part #270126 onto the emitter tube(s) in their relevant positions as shown on the assembly drawing.
REFLECTOR BRACKET #270569
Locate a suspension support bracket and remove the bolt fixing the strap to the bracket.
Position the bracket over the emitter tube and loosely replace the bolt.
Roughly position the support brackets in place along the emitter tube assembly as indicated on the assembly drawing. The positioning may need to be adjusted when the reflector is added.
2.2.4 Couplers
The couplers are used for joining emitter tubes and U or L bends.
Slide the coupling onto the end of the existing emitter tube. Slide the end of the next emitter tube into the other side of the coupling.
Doc No 700106 (06-15), Page 17
Page 18
With both emitter tube ends pushed fully into the coupling and the bolts towards the bottom, using a 9/16” wrench, tighten the coupling bolts moving between each bolt in sequence to ensure equal pressure is applied to each bolt.
Complete assembly by drilling and screwing self tapping retention zip screws.
At this point raise the tube assembly into
position and suspend from previously fixed chains (Working Load 100lb). Longer tube assemblies may be raised in more than one sub-assembly with the final emitter tube connection made in the air.
2.2.5 Reflectors.
All reflectors must be positioned/ attached to the brackets exactly as detailed in the assembly drawings.
After removing the coloured protective plastic coating (where fitted), slip the reflectors through the suspension brackets until they overlap each other.
The first two reflectors are assembled and overlapped by a pre determined distance, as shown on the assembly drawing, and are fixed onto the emitter tube using the reflector support bracket part #270569.
Each reflector must OVERLAP the previous one as indicated by their individual assembly sheets.
(TWISTED LINK, PLATED)
NOTE. HOOKS ARE TO BE CLOSED UP AFTER ASSEMBLY
2/0 GA CHAIN
Reflectors. Note: each reflector must overlap the previous one
Reposition the reflector support bracket if necessary then tighten the clamp bolt.
These two reflectors are fixed in place by tightening the fixing screws/locknuts as below. These are known as ‘non-slip’ overlaps.
TIGHTEN SCREWS TO FIX REFLECTOR
The next reflector is assembled and overlapped by the pre determined distance. The reflector is fitted onto the emitter tube using another reflector support bracket part #270569.
Reposition the reflector support bracket if necessary, then tighten the clamp bolt.
These overlapped reflectors are allowed to ‘float’ within the support bracket by leaving a minimum of 1/8” gap of the fixing screws before tightening the locknuts. These are known as ‘slip’ overlaps.
1 8
" min
1
ALLOW REFLECTOR TO SLIDE
LEAVE
" MIN GAP TO
8
Further reflectors are assembled and overlapped onto the emitter tube by alternating ‘non-slip’ and ‘slip’ until complete length is covered.
Continue this method to the final reflector/ support bracket.
See stetch below for typical ‘slip’ and ‘non-slip’.
Further reflectors to be
overlapped in the same method
Burner
Suspension Bracket
part #270126
and fixing #270572
Doc No 700106 (06-15), Page 18
Support Bracket
part #270569
non-slip overlap
Support Bracket
part #270569
slip overlap
Support Bracket
part #270569
non-slip overlap
Page 19
2.2.6 End Caps (optional)
Position an end cap beneath the reflector profile (where required) with the end cap flanges facing inwards. Fasten to reflector using the four ’Z’ clips.
End
2.2.7 Bend(s) (where fitted)
The heater can be installed with 1 or 2 90° bends or a 180° U bend.
Slide the bend into the open end of the coupler ensuring that the screw stop has butted up to the emitter tube ends. Refer to 2.2.4 for fastening.
90° Elbow
Corner reflector
90° Bend
2.2.8 Burner/Fan Assembly.
Slide the burner assembly onto the open emitter tube end, ensuring it is fully engaged. Secure with set screws.
For the purpose of unvented applications, a 4” 90° elbow should be used on the terminating end of the emitter tube sections and completed using a vent cap.
Connect Gas and Electrical supplies as described in sections 1.4 and 1.5.
2.2.9 Detailed Assembly Drawings
The following pages show the technical dimensional details for the range of heaters available.
Please note the heater type, length and reference number from the delivery/advice note before identifying the correct model drawing.
Corner reflector kit
16” crs
U Bend
Doc No 700106 (06-15), Page 19
End Caps
End Caps
15”
Page 20
Figure 8. Possible Heater Orientations
S20
S30
S40
S50
S60
Bends must be fitted at a distance of at least 50% of the total heat exchanger
e.g. for a 60ft long heater, the closest to the burner a bend can be is 30ft.
S70
U20
U40
U60
Doc No 700106 (06-15), Page 20
Page 21
Figure 9. Heater Assembly: Model Linear 60-S20.
END CAPS
(OPTIONAL)
PART #270126
SUSPENSION BRACKET
6"-9" REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
TURBULATOR(S)
(SEE DETAIL)
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
L
C
PART #205546
QTY 1 REQUIRED
STANDARD 4" COUPLER
2" MINIMUM
REFLECTOR SUPPORT BRACKET
TURBULATOR SECTION
DETAIL
PART #116019
QTY 3 REQUIRED
21'6½" NOMINAL OVERALL ASSEMBLED LENGTH
SUSPENSION BRACKET
PART #270126
SUSPENSION BRACKET
DISTANCE BETWEEN
SUSPENSION POINTS
PART #270126 PLUS
STRAP PART #270572
COUPLER
(SEE DETAIL)
BURNER INSERT
NO TO EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 2
4"
END CAPS
(OPTIONAL)
BURNER
6"
ASSEMBLY OVERVIEW
DETAILS
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
QTY 2 REQUIRED
QTY 1 REQUIRED OF EACH
PART #270489 (5FT)
BURNER INSERT DETAIL
QTY 1 REQUIRED NAT GAS ONLY
PART #270569
QTY 2 REQUIRED
REFLECTOR SUPPORT BRACKET
Doc No 700106 (06-15), Page 21
Page 22
Figure 10. Heater Assembly: Model Linear 60-S30, 80-S30, 100-S30 and 125-S30.
END CAPS
(OPTIONAL)
SUSPENSION BRACKET
SUSPENSION BRACKET
PART #270126
PART #270126
6" REFLECTOR OVERLAP
6" REFLECTOR OVERLAP
TURBULATOR
COUPLER
(SEE DETAIL)
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
L
C
PART #205546
STANDARD 4" COUPLER
2" MINIMUM
DETAIL
REFLECTOR SUPPORT BRACKET
QTY 2 REQUIRED
PART #116019
TURBULATOR SECTION
QTY 3 REQUIRED SIZE 80/100 ONLY
QTY 4 REQUIRED SIZE 100 LPG ONLY
QTY 5 REQUIRED SIZE 125 ONLY
31'6½" NOMINAL OVERALL ASSEMBLED LENGTH
SUSPENSION BRACKET
PART #270126
SUSPENSION BRACKET
DISTANCE BETWEEN
SUSPENSION POINTS
PART #270126 PLUS
STRAP PART #270572
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
COUPLER
(SEE DETAIL)
BURNER INSERT
NO TO EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 3
4"
END CAPS
(OPTIONAL)
BURNER
6"
ASSEMBLY OVERVIEW
DETAILS
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
QTY 3 REQUIRED
QTY 1 REQUIRED OF EACH
BURNER INSERT DETAIL
REFLECTOR SUPPORT BRACKET
PART #270489 (5FT)
QTY 1 REQUIRED SIZE 60-100 NG ONLY
PART #270569
QTY 3 REQUIRED
PART #1005500 (3FT)
QTY 1 REQUIRED SIZE 125 NG ONLY
Doc No 700106 (06-15), Page 22
Page 23
Figure 11. Heater Assembly: Model Linear 60-S40, 80-S40, 100-S40, 125-S40 and 150-S40.
END CAPS
(OPTIONAL)
41'6½" NOMINAL OVERALL ASSEMBLED LENGTH
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
PART #270126
SUSPENSION BRACKET
6" REFLECTOR
PART #270126
SUSPENSION BRACKET
OVERLAP
OVERLAP
TURBULATOR
COUPLERCOUPLERCOUPLER
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
(SEE DETAIL)
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
L
C
PART #205546
QTY 3 REQUIRED
STANDARD 4" COUPLER
2" MINIMUM
DETAIL
REFLECTOR SUPPORT BRACKET
PART #116019
TURBULATOR SECTION
QTY 4 REQUIRED SIZE 125/150 ONLY
6" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
DISTANCE BETWEEN SUSPENSION POINTS NO TO EXCEED 12'
TYPICAL OF 4
10' 3" REFLECTORS
PART #270126 PLUS
STRAP PART #270572
SUSPENSION BRACKET
END CAPS
(OPTIONAL)
Doc No 700106 (06-15), Page 23
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
QTY 4 REQUIRED
QTY 1 REQUIRED OF EACH
BURNER INSERT DETAIL
REFLECTOR SUPPORT BRACKET
PART #270489 (5FT)
QTY 1 REQUIRED SIZE 60-100 NG ONLY
PART #270569
QTY 4 REQUIRED
PART #1005500 (3FT)
QTY 1 REQUIRED SIZE 125 NG ONLY
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
(SEE DETAIL)
BURNER INSERT
4"
6"
BURNER
ASSEMBLY OVERVIEW
DETAILS
Page 24
Figure 12. Heater Assembly: Model Linear 125-S50, 150-S50, 170-S50 and 200-S50
END CAPS
(OPTIONAL)
2" MINIMUM
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
REFLECTOR SUPPORT
BRACKET PART #270569
REFLECTOR SUPPORT
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
NOTE: The 200 S50 model
requires a different fan orifice
plate. See P16 for details.
L
C
DETAIL
REFLECTOR SUPPORT BRACKET
3" REFLECTOR
OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
PART #270126
SUSPENSION BRACKET
6" REFLECTOR
OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
51'6½" NOMINAL OVERALL ASSEMBLED LENGTH
SUSPENSION BRACKET
SUSPENSION BRACKET
PART #270126
PART #270126
6" REFLECTOR
OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
COUPLER COUPLER COUPLER COUPLER
PART #205546
QTY 4 REQUIRED
STANDARD 4" COUPLER
QTY 5 REQUIRED
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
TURBULATOR SECTION
BURNER INSERT DETAIL
PART #116019
QTY 4 REQUIRED SIZE 200 NG ONLY
PART #270489 (5FT)
QTY 1 REQUIRED SIZE 100 NG ONLY
QTY 2 REQUIRED SIZE 200 LPG ONLY
PART #1005500 (3FT)
QTY 1 REQUIRED SIZE 125 NG ONLY
TYPICAL OF 5
10' 3" REFLECTORS
DISTANCE BETWEEN SUSPENSION POINTS NO TO EXCEED 12'
PART #270126 PLUS
STRAP PART #270572
SUSPENSION BRACKET
END CAPS
(OPTIONAL)
BURNER
Doc No 700106 (06-15), Page 24
4"
6"
(SEE DETAIL)
BURNER INSERT
PART #270569
QTY 5 REQUIRED
QTY 1 REQUIRED OF EACH
REFLECTOR SUPPORT BRACKET
ASSEMBLY OVERVIEW
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
DETAILS
Page 25
Figure 13. Heater Assembly: Model Linear 150-S60, 170-S60 and 200-S60.
END CAPS
(OPTIONAL)
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
REFLECTOR SUPPORT
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
BRACKET PART #270569
2" MINIMUM
L
C
DETAIL
REFLECTOR SUPPORT BRACKET
NON-SLIP REFLECTOR OVERLAP
PART #205546
QTY 5 REQUIRED
STANDARD 4" COUPLER
NON-SLIP REFLECTOR OVERLAP
61'6½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN SUSPENSION POINTS NO TO EXCEED 12'
6" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
6" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
PART #270126 PLUS
STRAP PART #270572
SUSPENSION BRACKET
END CAPS
TYPICAL OF 6
10' 3" REFL'S
(OPTIONAL)
Doc No 700106 (06-15), Page 25
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
QTY 6 REQUIRED
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
REFLECTOR SUPPORT
BRACKET PART #270569
COUPLER COUPLER COUPLER COUPLER COUPLER
4"
6"
NON-SLIP REFLECTOR OVERLAP
PART #270569
QTY 6 REQUIRED
QTY 1 REQUIRED OF EACH
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
ASSEMBLY OVERVIEW
BURNER
DETAILS
REFLECTOR SUPPORT BRACKET
Page 26
Figure 14. Heater Assembly: Model Linear 170-S70 and 200-S70.
END CAPS
(OPTIONAL)
PART #270126
SUSPENSION BRACKET
PART #270126
SUSPENSION BRACKET
PART #270126
SUSPENSION BRACKET
PART #270126
SUSPENSION BRACKET
3" REFLECTOR
3" REFLECTOR
3" REFLECTOR
3" REFLECTOR
OVERLAP
OVERLAP
OVERLAP
OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
REFLECTOR SUPPORT
REFLECTOR SUPPORT
BRACKET PART #270569
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
SLIP REFLECTOR OVERLAP
L
C
PART #205546
QTY 6 REQUIRED
2" MINIMUM
DETAIL
REFLECTOR SUPPORT BRACKET
STANDARD 4" COUPLER
PART #270126
71'6½" NOMINAL OVERALL ASSEMBLED LENGTH
SUSPENSION BRACKET
6" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
6" REFLECTOR
OVERLAP
PART #270126
SUSPENSION BRACKET
DISTANCE BETWEEN SUSPENSIO N POINTS NO TO EXCEED 12'
PART #270126 PLUS
STRAP PART #270572
SUSPENSION BRACKET
END CAPS
TYPICAL OF 7
10' 3" REFL'S
(OPTIONAL)
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
SLIP REFLECTOR OVERLAP
QTY 7 REQUIRED
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
REFLECTOR SUPPORT
BRACKET PART #270569
COUPLER COUPLER COUPLER COUPLER COUPLER COUPLER
4"
6"
NON-SLIP REFLECTOR OVERLAP
PART #270569
QTY 7 REQUIRED
QTY 1 REQUIRED OF EACH
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
BURNER
ASSEMBLY OVERVIEW
DETAILS
REFLECTOR SUPPORT BRACKET
Doc No 700106 (06-15), Page 26
Page 27
Figure 15. Heater Assembly: Model U tube 60-U20.
2" MINIMUM
3' 3"
L
C
DETAIL
REFLECTOR SUPPORT BRACKET
REFLECTOR SUPPORT
BRACKET PART #270569
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
SUSPENSION BRACKET
PART #270126
COUPLERS
BURNER INSERT
NON-SLIP REFLECTOR OVERLAP
PART #270126
SUSPENSION BRACKET
(SEE DETAIL)
PART #205546
QTY 2 REQUIRED
STANDARD 4" COUPLER
PART #116019
TURBULATOR SECTION
QTY 1 REQUIRED SIZE 60 ONLY
SUSPENSION POINTS
DISTANCE BETWEEN
NO TO EXCEED 12'
12'1½" NOMINAL OVERALL ASSEMBLED LENGTH
TURBULATOR
(SEE DETAIL)
10' 3" REFLECTORS TYPICAL OF 2
PART #270126
SUSPENSION BRACKET
END CAPS
(OPTIONAL)
Doc No 700106 (06-15), Page 27
4"
BURNER
6"
PART #270126 PLUS
STRAP PART #270572
SUSPENSION BRACKET
QTY 3 REQUIRED
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
BURNER INSERT DETAIL
PART #270489 (5FT)
QTY 1 REQUIRED NAT GAS ONLY
PART #270569
QTY 2 REQUIRED
QTY 1 REQUIRED OF EACH
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
ASSEMBLY OVERVIEW
DETAILS
REFLECTOR SUPPORT BRACKET
Page 28
Figure 16. Heater Assembly: Model U tube 60-U40, 80-U40, 100-U40, 125-U40 and 150-U40.
3' 3"
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
REFLECTOR SUPPORT
PART #270126
SUSPENSION BRACKET
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
REFLECTOR SUPPORT
L
C
PART #270126
COUPLERS
6"-9" REFLECTOR OVERLAPS
SUSPENSION BRACKET
SUSPENSION POINTS
NO TO EXCEED 12'
DISTANCE BETWEEN
COUPLERS
PART #205546
QTY 4 REQUIRED
STANDARD 4" COUPLER
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
2" MINIMUM
DETAIL
REFLECTOR SUPPORT BRACKET
PART #116019
TURBULATOR SECTION
QTY 4 REQUIRED SIZE 150 ONLY
22'1½" NOMINAL OVERALL ASSEMBLED LENGTH
PART #270126
SUSPENSION BRACKET
TURBULATOR
PART #270126
SUSPENSION BRACKET
END CAPS
(SEE DETAIL)
(OPTIONAL)
10' 3" REFLECTORS TYPICAL OF 4
BURNER
BURNER INSERT
4"
6"
PART #270126
SUSPENSION BRACKET
(SEE DETAIL)
SUSPENSION BRACKET
STRAP PART #270572
PART #270126 PLUS
ASSEMBLY OVERVIEW
DETAILS
TUBE & REFLECTOR SUSPENSION
FIRST SUSPENSION POINT BRACKET
QTY 5 REQUIRED
BRACKET PART #270126
PART #270489 (5FT)
PART #1005500 (3FT)
BURNER INSERT DETAIL
QTY 1 REQUIRED SIZE 125 NG ONLY
QTY 1 REQUIRED SIZE 60-100 NG ONLY
PART #270569
QTY 4 REQUIRED
QTY 1 REQUIRED OF EACH
PART #270126 plus STRAP #270572
REFLECTOR SUPPORT BRACKET
Doc No 700106 (06-15), Page 28
Page 29
Figure 17. Heater Assembly: Model U tube 150-U60, 170-U60 and 200-U60.
3' 3"
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
REFLECTOR SUPPORT
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
L
C
2" MINIMUM
DETAIL
32'1½" NOMINAL OVERALL ASSEMBLED LENGTH
REFLECTOR SUPPORT
REFLECTOR SUPPORT
COUPLERS
COUPLERS
REFLECTOR SUPPORT
REFLECTOR SUPPORT
PART #270126
SUSPENSION BRACKET
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
PART #270126
PART #205546
SUSPENSION BRACKET
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
QTY 6 REQUIRED
STANDARD 4" COUPLER
REFLECTOR SUPPORT BRACKET
PART #270126
COUPLERS
SUSPENSION BRACKET
6" REFLECTOR OVERLAPS
SLIP REFLECTOR OVERLAP
BRACKET PART #270569
PART #270126
SUSPENSION BRACKET
6"-9" REFLECTOR OVERLAPS
BRACKET PART #270569
NON-SLIP REFLECTOR OVERLAP
PART #270126
SUSPENSION BRACKET
DISTANCE BETWEEN SUSPENSION
POINTS NO TO EXCEED 12'
PART #270126
SUSPENSION BRACKET
END CAPS
(OPTIONAL)
Doc No 700106 (06-15), Page 29
10' 3" REFLECTORS TYPICAL OF 6
BURNER
QTY 7 REQUIRED
BRACKET PART #270126
TUBE & REFLECTOR SUSPENSION
PART #270126
SUSPENSION BRACKET
(SEE DETAIL)
BURNER INSERT
SUSPENSION BRACKET
STRAP PART #270572
PART #270126 PLUS
4"
QTY 1 REQUIRED OF EACH
PART #270126 plus STRAP #270572
FIRST SUSPENSION POINT BRACKET
BURNER INSERT DETAIL
REFLECTOR SUPPORT BRACKET
PART #1005500 (3FT)
PART #270569
QTY 1 REQUIRED SIZE 125 NG ONLY
QTY 6 REQUIRED
6"
ASSEMBLY
OVERVIEW
DETAILS
Page 30
3. Start Up Instructions.
These appliances should be commissioned by a qualified mechanical contractor.
3.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Leather Faced Gloves
Phillips Screwdriver
Suitable alternative tools may be used.
Small Flat Head Screwdriver
Large Adjustable Wrenches for fitting Of Gas Flex.
½” Wrench
5/32” (4mm) Allen Wrench
3.2 Start Up Procedure
Inspect installation and ensure that it has been carried out in accordance with these instructions. Ensure that electrical and gas supplies are isolated.
The gas supply should be purged and tested for leaks in accordance with local and National Safety codes.
Open shut off gas valve and test gas connections for leaks using soap solution.
Open the control housing door by unscrewing the securing screw. Ensure all internal components are securely fixed and all connections securely made.
Switch on the electrical supply to start the heater and observe the correct start up sequence. Ensure that the setting of any time clock and thermostat are such that the heating system will be required to operate.
The fan will start to run and the ‘power on’ lamp will illuminate. Safe-start checks are carried out automatically.
After the fan has run up to full speed and a satisfactory vent pressure condition has been established, the ignition sequence will commence. The spark ignition will be energized producing a spark at the ignition electrode. The gas solenoid valve will energize at the same time and the ‘burner on’ lamp will illuminate. If the ignition is successful, the flame is detected by the flame sensing probe and the ‘burner on’ lamp will remain on.
If ignition is unsuccessful, after approximately 15 seconds the gas valve will close and the spark ignition will de-energize.
For approximately 30 seconds the fan will purge the system, then re-ignition will be attempted. After 2 further attempts at ignition the control unit will ‘lock-out’, the ‘power on’ lamp will remain illuminated and the fan will run for 120 seconds and then stop.
To reset after ‘lockout’ switch off the power supply to the system and wait 2 minutes. Then turn the power on. If repeated ‘lockout’ occurs, investigate the cause.
Set burner gas pressure as follows: Switch off the power supply to the heating system.
Connect a ‘U’ tube or digital manometer to the pressure test point provided on the combination gas control valve.
Remove the cover from the pressure regulator to reveal the adjusting screw.
Start the heater and using a suitable screwdriver adjust the pressure regulator, turning the screw clockwise to increase the pressure or counter-clockwise to decrease the pressure.
Set the pressure to appropriate inches w.c. from the table of gas pressures and orifice plate dimensions for correct heater description. (See section 1.8 page 13)
Manometer
Multimeter
Doc No 700106 (06-15), Page 30
Page 31
The high fire gas pressure should be set first followed by the low fire gas pressure. Re-check the high fire and re-adjust if necessary.
To enable post purge ensure that the setting of any time switch and thermostat are such that the heating system will be required to turn off.
Switch off the power supply to the heating system. Disconnect manometer, then secure screw in pressure test nipple.
Check the operation of the flame safeguard equipment as follows:
With the heater running normally, switch off the gas supply at the shut off valve. The heater should attempt to relight then ‘lock-out’ should occur. This is indicated by the ‘power on’ lamp being illuminated and fan running, but the ‘burner on’ lamp being off.
Check the operation of the pressure proving switch as follows:
With the heater running normally, pull off the silicone rubber tube connecting the vacuum switch to the combustion chamber. The burner should shut off within 4 seconds .
Replace the tube securely and observe that the heater proceeds to ignite in the normal way.
Close the controls door and secure with the screw.
Doc No 700106 (06-15), Page 31
Page 32
Commissioning chart
Check installation has
been carried out to these
instructions.
Remove burner from tube and inspect burner head.
Replace burner on tube
and secure.
Check thermostat is set to
maximum and is calling
for heat.
Ensure gas and electricity
supplies are isolated.
(See servicing instructions)
Reconnect gas hose.
Open Manual valve.
Check soundness.
Switch on electrical supply.
The red neon should now
be illuminated. If restarting
heater a delay of 15sec
should be allowed.
Disconnect gas hose from
burner
Open control housing and check that all components
are securely fastened.
The heater should now run through its start up
sequence and ignite.
Check gas pressure.
Leave the instructions
with a responsible person.
A successful ignition is indicated
by the amber light illuminating
and remaining illuminated.
Close control housing
Turn off power and check
that all components are
securely fastened.
NO
Has the
burner lit?
YES
Check operation on flame failure.
Check gas pressure.
Check operation of
air pressure switch.
Doc No 700106 (06-15), Page 32
Page 33
4. Servicing Instructions.
These appliances should be serviced annually by a competent person to ensure safe and efficient operation. In mildly dusty or polluted conditions more frequent servicing
may be required. Servicing work should be carried out by a qualified mechanical contractor.
4.1 Tools Required.
The following tools and equipment are advisable
Leather Faced Gloves
½” Wrench
4.2 Burner Description.
Figure 20. Burner breakdown
Flame Plates (Q)
269960 170 LP
269959 125/150 LP
F
Phillips Screwdriver
5/32” (4mm) Allen Wrench
P
to complete the tasks laid out in this manual.
Suitable alternative tools may be used.
Small Flat Head Screwdriver
Manometer
Multimeter
K
Large Adjustable wrenches for fitting of Gas Flex.
Note: Cables Omitted For Clarity
A
Soft Brush
L
N
I
Q
G
G
269958 80/100 LP
M
269957 60 LP
Part Number
A Ignition Controller 204955
B Gas Valve 270373 (NG) 270498 (LP)
C Power On Red Lamp 270474
D Low Fire Amber Lamp 270473
E High Fire Amber Lamp 270473
F Burner Tube 270424
G Burner head 270425
H Injector See section 1.8 P14
Doc No 700106 (06-15), Page 33
C
Part Number
I Igniter Assembly 270441
J Injector Carrier
K Combustion Fan
L Pressure Switch
M Gaskets
N Transformer
O 24V Relay 270472
P Burner Orifice Plate
Q Flame Plate (not shown)
E
D
H
J
O
B
See section 1.8 P14
See section 1.8 P14
See section 1.8 P14
2 off 270366
194808
See section 1.8 P14
See photos above
Page 34
4.3 Burner Removal
Step 1: Isolate power and gas supplies.
Step 2: Disconnect the external power/control
connections.
Step 3: Detach the gas supply as shown
below, taking care to support the burner connection.
Step 6: Remove the burner and position the
burner in a safe area to prevent the burner or components attached to the burner from falling to the ground.
4.4 Burner Gas Injector Servicing
Step 1:
Remove the 4 retaining screws, then
remove the burner support casting and gasket.
Step 4: If ducted air is connected, loosen hose
clip and remove the flexible hose from the burner.
Step 5: Loosen the set screw on the burner
support casting to enable the burner to be removed from the radiant tube.
Doc No 700106 (06-15), Page 34
Step 2: The burner head assembly can be
disconnected by separating the connectors of the ignition lead assembly and removing the earth lead and pressure switch silicon tube.
Page 35
Step 3: The gas injector can be inspected and
replaced if contaminated or blocked.
When replacing the gas injector ensure approved thread sealant is used.
Step 4: Reconnect ignition leads and silicone
tube to test nipple. Refit gasket and support casting.
4.5 Combustion Fan Servicing
Step 1: Remove the four top lid screws to
reveal the combustion fan shown below.
Step 2: Disconnect the fan cables after first
noting their positions, then pull cable through to fan compartment.
Step 4: Remove fan orifice plate.
Step 5: Inspect the impeller and remove any
dust with a soft brush.
Step 6: Remove any dust from fan scroll and
from around the motor.
Step 7: Ensure the impeller rotates freely.
Step 8: Refit components.
4.6 Burner Head and Electrode Servicing
Step 1:
Check the pepper pot burner head for contamination. If necessary this can be removed. See below.
Step 3: Remove the four fan fixing screws then
withdraw the fan complete with mounting bracket as shown below.
Doc No 700106 (06-15), Page 35
This can be cleaned together with the inside of the burner head.
Step 2: The pepper pot burner head can be
replaced ensuring the 5 holes on the outer ring are aligned alongside the probes.
Step 3: The condition of the igniter assembly
can be checked for deterioration. However, we advise replacement at each service to ensure
Page 36
continued reliability. Detach the electrode assembly from the burner head by removing the two screws as shown and separating the igniter assembly lead connectors.
Step 4: Refit the electrode assembly and
ensure the connections are secure to prevent incorrect sparking of the spark electrode.
Step 5:
Check the positions and spark gap as
shown in diagram below.
Step 6: The burner assembly is ready to refit
after servicing the combustion fan and the radiant tube assembly.
Step 7: Refit components.
4.7 Radiant Tube Servicing
Step 1:
Brush any dust from the exterior of the
tubes.
Step 2: Inspect the fan and burner tubes
visually. If the tubes appear clean, skip to servicing the reflector.
Step 3: If required the interior of the tubes can
then be cleaned using an industrial vacuum cleaner or by using long poles and a scraper.
4.8 Reflector Servicing
The condition of the reflectors should be noted. If necessary the reflectors can be cleaned with a mild detergent. This can significantly improve the efficiency of the appliance.
4.9 Cleaning of Vent
Inspect the fresh air inlet duct and vent to ensure they are free from any blockage or obstruction. The air inlet terminal and vent terminal should be inspected to ensure they are not liable to obstruction.
4.10 Re-commissioning After Service
After servicing of the heater has been undertaken, it will be necessary to re-commission the heater as detailed in the commissioning chart in these instructions.
Doc No 700106 (06-15), Page 36
Page 37
5. Troubleshooting Guide.
START
Ensure gas & electricity
supplies are enabled.
Turn any external timer
to call for heat (if fitted).
YES
Does the Power On
light illuminate?
NO
CHECK: -
1. Operation of any timer or control.
2. External fuses.
3. Supply Voltage is 120VAC 60Hz
Is there power to the
burner?
NO
CHECK: -
1. Transformer
YES
2. Integrity of wiring connections.
3. Light.
YES
Set two-stage thermostat to
call for heat at maximum
setting (High Fire).
Does the fan run? NO
CHECK: -
1. Relays is correctly fitted
2. Voltage across terminals A1 & A2 is 24VAC/60Hz(when calling for high fire).
3. Integrity of wiring connections.
4. Pressure switch operation.
5. Ignition controller.
6. Transformer.
Do the amber
lights illuminate after a
purge period?
Is there power to
NO
the fan?
NO
Does the Pressure
switch close?
CHECK: -
1. Voltage supply to fan terminal F2(F1on low fire is 120VAC 60Hz
YES
2. Integrity of wiring connections.
3. Fan.
CHECK: -
1. Pressure switch wiring connections.
YES
4. Integrity of wiring connections.
5. Amber lights.
6. Ignition controller.
5. Transformer
YES
Doc No 700106 (06-15), Page 37
NO
CHECK: -
1. Hose connection to vacuum switch.
2. Air inlet, outlet, and emitter tubes for obstructions.
3. Pressure switch operation.
4. Supply voltage 120VAC / 60Hz
5. Transformer.
6. Ignition Controller.
Page 38
To aid in the trouble shooting process the UT controller has an LED flash code diagnostic sequence:
Steady Off No control Power Steady On Power Applied, Control OK 1 Flash Combustion Pressure Switch Open With Blower On 2 Flashes Combustion Pressure Switch Closed With Blower Off 3 Flashes Lockout From The Three Ignition Trials 4 Flashes Lockout From Five Flame Losses 5 Flashes Control Hardware Fault Detected 6 Flashes Lockout From Five Pressure Switch Losses
Doc No 700106 (06-15), Page 38
Page 39
6. Replacing Parts.
Turn off gas and any electrical supplies to the heater before starting repair work.
6.1 Burner Controller Replacement
Step 1:
bottom access door.
Step 2: Disconnect burner controller from the
wiring harness.
Remove the four screws securing the
Step 2: Remove the two electrical chassis
retaining screws arrowed.
Step 3: Disconnect the Spark Lead from burner
controller.
Step 4: Remove burner controller from its
retaining screws and remove.
Step 5: Fit new burner controller.
Step 6: Refit spark lead and wiring harness
connector.
Step 7: Test product and close access door.
6.2 Air Pressure Switch Replacement
Step 1:
the pressure switch.
Disconnect the two silicone tubes from
Step 3:
It may be necessary to partially disconnect the chassis wiring to access the pressure switch mounting screws at the rear.
Disconnect pressure switch wiring.
Doc No 700106 (06-15), Page 39
Page 40
Step 4: Turn chassis over and remove the two
pressure switch retaining screws.
Step 5: Fit the new air pressure switch in
reverse order ensuring the silicone tubes are connected as shown below.
Step 4: Remove the gas valve wiring
connections, noting their positions.
Step 6: Re-connect wiring.
Step 7: Test product and close access door.
6.3 Gas Valve Replacement
Step 1:
Remove the burner assembly as
described in the Servicing section.
Step 2: Open the rear access door.
Step 3: Remove the two securing screws
(arrowed) from the base of the injector tube, noting earth terminal connection.
Doc No 700106 (06-15), Page 40
Step 5: Remove the four screws (arrowed)
securing the gas valve inlet plate to the burner housing and remove plate.
Step 6: Remove gas valve rearwards as shown.
Step 7: The jet carrier and gas inlet can now be
detached from the gas valve.
Step 8: Replace gas valve and Re-connect
wiring.
Step 9: Set burner pressure.
Step 10: Test product and close access door.
Page 41
Doc No 700106 (06-15), Page 41
Page 42
Doc No 700106 (06-15), Page 42
Page 43
Doc No 700106 (06-15), Page 43
Page 44
7. User & Operating Instructions.
Radiant tubular infrared heaters are designed for overhead heating of industrial and commercial buildings. Individual heating units are suspended from the roof.
1. This appliance must only be installed by qualified installer in accordance with the requirements of local and National Codes.
2. This appliance must be grounded in accordance with the National Electrical Code ANSI/NFPA No.70 or Canadian Codes.
3. Never rest anything, especially ladders, against the heaters.
7.1 To Start the Heater
1. First ensure that the gas supply to each heater is turned on by opening the main gas shut off valve.
2. Switch on the electrical supply to the heater. The ‘power on’ lamp will illuminate.
3. Ensure that the settings of the two stage thermostat and any time switch are set so that the heating system will be required to operate.
4. The fan will start and the ignition sequence will commence.
5. Ignition of the burner will occur and the ‘low fire’ light only will illuminate for low fire and both the ‘low fire’ and ‘high fire’ lights will illuminate for high fire.
6. If ignition is unsuccessful the gas valve will close and the spark ignition de-energize after approximately 15 seconds. For approximately 30 seconds the fan will purge the system then re-ignition will be
attempted. After 3 attempts at ignition the control unit will ‘lock-out’, the ‘power on’ lamp will remain illuminated and the fan will continue to run for 120 seconds then stop. To reset after ‘lockout’, switch off the power supply to the heater and wait 5 minutes. Then turn the power on. If repeated ‘lockout’ occurs investigate the cause.
7.2. To Switch Off Heater
Ensure that the setting of any time switch
and thermostat are such that the heating system will be required to turn off. Switch off electrical supply to the heater. The burner will stop and the fan will shut off.
7.3. Servicing
To ensure continued, efficient and safe
operation it is recommended that the heater be serviced regularly by a qualified person every year in normal working environments but in exceptionally dusty or polluted environments more frequent servicing may be needed.
Doc No 700106 (06-15), Page 44
Specifications & illustrations subject to change without notice or incurring obligations. © Nortek Global HVAC, LLC 2015, All rights reserved. Printed in U.S.A. (06-15) All trade marks are the property of their respective organizations.
Doc No. 700106
Loading...