Reznor VPS, VPS 60, VPS 80, VPS 100, VPS 125 Installation & Operation Manual

...
Page 1
INSTALLATION / OPERATION / MAINTENANCE
Applies to: Model VPS 120V 60Hz
Gas-Fired, Tubular, Radiant,
Low-Intensity Infrared Heater
Model VPS Burner/Control Box with 20 - 80 ft Tube/Reflector Length
Page 2
Introduction.
Welcome to the new range of powered infra-red heaters. Local regulations may vary and it is the installer’s responsibility to ensure that such reg­ulations are satisfied.
All installation, assembly, commissioning and service procedures must be carried out by suitable qualified competent persons and conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the National Gas and Propane Installation Code CSA B149.1
When assembling, installing, commissioning and servicing is undertaken on radiant tube
Document Index.
heaters specified in these instructions, due care and attention is required to ensure that working at height regulations are adhered to.
PLEASE READ this document prior to
installation to familiarize yourself with the components and tools you require at the various stages of assembly.
All Dimensions shown are in inches unless otherwise stated.
The manufacturer reserves the right to alter specifications without prior notice.
1 Installation Requirements
1.1 Health & Safety
1.2 Heater Suspension
1.3 Clearance to Combustibles
1.4 Gas Connection & Supply Details
1.5 Electrical Connections
1.6 Ventilation Requirements
1.6.1 Unvented Units
1.6.2 Vertical Venting
1.6.3 Horizontal Venting
1.7 Fresh Air Intake
1.8 Technical Details
2 Assembly Instructions
2.1 Tools Required
2.2 Assembly Notes
2.2.1 Tubes
2.2.2 Turbulators
2.2.3 Brackets
2.2.4 Couplers
2.2.5 Reflectors
2.2.6 End Caps (optional)
2.2.7 Bends (where required)
2.2.8 Burner/Fan Assembly
2.2.9 Detailed Assembly Drawings
3 Start Up Instructions
3.1 Tools Required
3.2 Start up procedure
4 Servicing Instructions
4.1 Tools Required
4.2 Burner Description
4.3 Burner Removal
4.4 Burner Gas Injector Servicing
4.5 Burner Head and Electrode Servicing
4.6 Combustion Fan Assembly
4.7 Radiant Tube Servicing
4.8 Reflector Servicing
4.9 Cleaning of Vent
4.10 Re-commissioning after Service
5 Spare Parts 6 Troubleshooting Guide 7 Replacing Parts
7.1 Burner Controller Replacement
7.2 Air Pressure Switch Replacement
7.3 Gas Valve Replacement
7.4 Optional Extra Kits
8 User and Operating Instructions
8.1 To Start Heater
8.2 To Switch Off Heater
8.3 Servicing
1. Installation Requirements.
1.1 Health and Safety
A. Heater is intended for heating
non-residential indoor spaces and should only be installed where flammable gases or vapors are not generally present.
B. Heaters may be suspended either
horizontal or at any angle. See section
1.3 for clearance dimensions.
C. The installation must conform with local
building codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
D. The unit shall be electrically grounded in
accordance with National Electric Code ANSI/NFPA 70 and Canadian Electrical Code CSA C22.1.
E. The heater may be installed in aircraft
hangars in accordance with the Standard
for Aircraft Hangars, ANSI/NFPA 409
and in automotive garages when
2
Page 3
installed in accordance with the Standard
for Parking Structures, ANSI/NFPA 88A, or the Standard for Repair Garages,
ANSI/NFPA 88B, or the Canadian Natural Gas and Propane Installation Code, CSA B149.1, and are so marked.
Ensure that minimum clearances will be maintained to vehicles parked below the heater.
F. The standard heaters are approved for
installations between 0 - 2000ft (0 - 610m) for the US and 0 - 4500 ft (1370m) for Canada. Conversion kits are available on installations above these heights in the USA.
1.2 Heater Suspension
Attachment to the heater support lugs should be made by D shackle. The hanging attachments to overhead steelwork etc. must be purpose made to sound engineering practice or supplied by others.
They must be adequately fixed and designed to carry the whole weight of the heater. In the event of suitable roof steelwork being unavailable, additional steelwork should be fitted to enable vertical hangers to be used for suspending the heaters.
These methods are illustrated in Figure 1. If there are any doubts as to the strength or suitability of roof steelwork to which heaters are to be suspended, please refer to a Consultant, Architect or owner of the building.
It is recommended that the heater is raised to its final position once the assembly of the tube/ bracket/reflector has been completed. Longer tube assemblies may be raised in more than one sub-assembly with final tube connection made in the air.
The suggested mounting heights for heaters are given in the chart next page.
WARNING:
If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which are known to the state of California to cause cancer, birth defects or other reproductive harm.
Figure 1. Recommended Methods of Heater Suspension.
U TUBE VARIANTS
EYE HOOKS
NOTE. HOOKS ARE TO
BE CLOSED UP AFTER ASSEMBLY
Suitable Chain
2/0 GA CHAIN
Working Load Limit
(TWISTED LINK, PLATED)
100lb.
EXHAUST
END
CHAIN
55° SUSPENSION
3
BURNER
END
Page 4
ON U TUBE VARIANTS THE HEATER SHOULD SLOPE DOWNWARDS TOWARDS THE RETURN BEND AND ON LINEAR VARIANTS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. ½” FOR HORIZONTAL INSTALLATIONS AS SHOWN BELOW (DIAGRAMS EXAGGERATED FO R CLARITY)
1/2”
1/2”
Outlet
U Tube heater side view
U bend
Linear heater side view
1.3 Clearance to Combustibles.
Minimum clearance to combustibles are shown in Table 1 below. IMPORTANT: The stated clearance to combustibles represents a surface temperature of 90°F (50° C) above room temperature. Building material with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
Table 1
MODEL A B B1 C1 C2 C3 D1 D2 E
Clearance to Combustibles, inches (cm)
60
74 (188) 29 (74) 41 (105) 20 (51) / 10* (26)* 8 (21) 22 (56) 8 (21) 12 (31) 12 (31)
80
100
125
150
170
200
* distance with end caps fitted.
74 (188) 29 (74) 41 (105) 20 (51) / 10* (26)* 8 (21) 22 (56) 8 (21) 12 (31) 12 (31)
74 (188) 32 (82) 41 (105) 20 (51) / 10* (26)* 8 (21) 22 (56) 8 (21) 16 (41) 12 (31)
74 (188) 39 (99) 47 (120) 20 (51) / 10* (26)* 8 (21) 22 (56) 20 (51) 18 (46) 12 (31)
74 (188) 39 (99) 48 (122) 20 (51) / 10* (26)* 8 (21) 22 (56) 20 (51) 18 (46) 12 (31)
86 (219) 48 (122) 48 (122) 20 (51) / 10* (26)* 11 (28) 22 (56) 20 (51) 20 (51) 12 (31)
86 (219) 48 (122) 48 (122) 20 (51) / 10* (26)* 11 (28) 22 (56) 20 (51) 20 (51) 12 (31)
WARNING:
Minimum clearance from the heater must be maintained from vehicles
parked below heater. In all situations, clearances to combustibles must be maintained. Signs should be posted in storage areas to specify maximum stacking height to maintain required clearance to combustibles. Such signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location. Refer to mounting clearance tables.
4
Page 5
Figure 2 Clearance to Combustibles.
The minimum clearances to combustible materials are given in the tables below. These minimum distances MUST be adhered to at all times. Adequate clearance MUST be provided around air openings into the combustion chamber and there MUST be suitable clearance for
accessibility and for combustion / ventilating air supplies.
D2
WARNING!
provision in the building for
Ensure that there is adequate
Angled view.
combustion and ventilation air supply.
Installation must meet minimum
applicable
requirements and appliciable codes.
A
.
0° to 55°
Outlet end.
D1
End
B1
Side
unvented
Above outlet
C3
unvented
Return end on
U tube heater
B
Below
A
B
Side
vented
End view.
heater
unvented
Above
Reflector
C2
Burner end.
C1
Above
Burner
5
E
Service
distance
Page 6
1.4 Gas Connection and Supply
WARNING: Before installation, check
that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The gas connection on the heater is ½” N.P.T internal thread.
Injector sizes and manifold pressure for the burners are shown in the table 4. The gas supply piping and connections must be installed so that the minimum pressure stated is achieved.
A gas shut off valve and union should be fitted in the gas supply line close to the heater and a ” N.P.T plugged tapping, accessible for test gauge connection, provided immediately upstream of the appliance gas inlet.
It is essential to provide some flexibility in the final gas connection by use of an approved flexible gas connector. See Fig 4.
Take care when making a gas connection to the heater not to apply excessive turning
force to the internal controls.
Care must be taken to observe the minimum pipe bend diameter (minimum 10” - 250mm, maximum 14” - 350mm) & pipe expansion distance (minimum 1” - 28mm, maximum 3¾”) - 95mm.
The correct installation as shown will allow
for approx 4” of movement due to expansion.
Figure 3. Correct orientation of Ball Valve
Gas Flow
Gas Flow
Figure 4. Correct Installation of Flexible Gas Connection
WARNING: FIRE OR EXPLOSION HAZARD - Expansion of the radiant pipe occurs with
each firing cycle causing the burner to move with respect to the gas line. This can
result in a gas leak producing an unsafe condition. It is therefore essential to provide some flexibility in the final gas line connection by use of an approved flexible connector as shown in the drawings.
6
Page 7
* Connector must be certified for use on a radiant tube type infrared heater and must comply with Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 or with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas, CAN/CGA 8.1. For heaters up to 150,000Btu/h, ½” ID x 24” long For heaters above 150,000Btu/h, ¾” ID x 36” long NOTE: For Canada all heaters MUST use a hose 36” long See Table 3
CONNECTOR MUST BE INSTALLED IN A “U” CONFIGURATION. FOR HEATERS
Table 3
HOSE SIZE USA CANADA
3/4” CE4
CONTACT FACTORY
UPTO 150,000 BTU/H, A 24” LONG CONNECTOR OF AT LEAST ½” ID MUST BE USED. FOR HEATERS ABOVE 150,000 BTU/H, A 36” LONG CONNECTOR OF AT LEAST ¾” NOMINAL ID MUST BE USED.
Table 4 Gas Supply & Pressures
Gas Type Natural Gas LP/Propane Gas
Required Gas Pressure (in W.C) (60,000 TO 150,000 BTU)
Required Gas Pressure (in W.C) (170,000 TO 200,000 BTU)
Max Supply Pressure (in W.C)
Gas Supply
1.5 Electrical Connections
WARNING: Before making electrical
connections, switch OFF the main electrical disconnect. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
This appliance must be electrically grounded
Supply 120V 60Hz single phase. Standard heater 0.16HP. Current rating 1.2 amp max (inductive). Fuse: external 3 amp.
Important: All electrical work should be done by a qualified electrician in strict accordance with the National Electrical Code ANSI/NFPA 70 or Canadian Codes CSA C22.1.
5.0 11.0
7.0 11.0
14.0 14.0
Connection ½” N.P.T thread
The electrical supply to the heater is by three wires: live, neutral and ground connections. Install in accordance with all state & local codes.
Where alternative manufacturers controls are used, please refer to their instructions for their installation details.
7
Page 8
Figure 5a. Single and Multiple Heater Installations 120V Control
KEY:
T
T
110V Thermostat
120V Thermostat
BK
W
W
G
BK
Burner 1
GND L2 L1 (HOT)
120V 60Hz 1 Ph Supply circuit
G-GREEN W-WHITE BK-BLACK
Other burners
BK
G
Figure 5b. Single Heater Installations 24V Control
BK
L1
Gas Control
IND
MV
PS1
PS0
W1
R
X
C
COM
R
R
Y
Y
K
K
BR
GR
BL
METHOD:­Cut and strip pink cables linking terminals W1 and R Attach thermostat wires using suitable wire nuts.
X
24V Thermostat
C
T
T
other burners
KEY:
BL - BLUE
BK - BLACK
BR - BROWN
GR - GREY
RW1
K - PINK
R - RED
Y - YELLOW
Figure 5c. Multiple Heater Installations 24V Control
C
T
T
R
RW1
BK
S-0700
R
G
24V Thermostat
Fan center relay
(Suppled by others)
KEY: G - GREEN W - WHITE BK - BLACK R - RED
8
40VA
30
Trans
Relay
BK
W
C
L2
L1
G
BK
GND L2 L1 (HOT)
120V 60Hz 1 Ph Supply circuit
Other burners
Burner 1
W
other burners
Page 9
Figure 6. Internal Burner Wiring Diagram.
120V AC Fan
G
R
W
BL
G
E
LN
120V/60Hz AC
Supply
KEY:
BK
G
W
BL - BLUE
BK - BLACK
BR - BROWN
GR - GREY
G - GREEN
K - PINK
G
BK
W
R - RED
W - WHITE
Y - YELLOW
YY
Pressure Switch
120v/24VAC 60Hz
Transformer
BR
Power ON (red)
BL BR
Burner ON (amber)
BK
Y
IND
R
MV
R
L1
K
PS1
PS0
K
W1
R
Gas Control
BR
BL
GR
X
C
COM
R
GR
G
M
C
E
Y
NOTES:­Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner.
Additional wiring is required to install an optional extra thermostat and / or time clock. If no thermostat is required then a jumper is fitted between terminals R and W1. In this configuration the burner will continuously fire until the 120V power supply is disconnected. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
RGR
Gas Valve
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
9
Page 10
1.6 Vent Requirements and Details
1.6.1 Unvented units
Heaters may be installed without a vent providing the governing building codes are met and consideration is properly given to possibilities of condensation on cold surfaces.
Installation shall meet the following requirements when unvented:
 Natural or mechanical means shall be
provided to supply and exhaust at least 4 CFM per 1000 BTU per hour input of installed heaters.
 Combustion gasses shall not impinge on
combustible materials.
1.6.2 Vertical venting
The heater can be installed with a vertical vent.
All vent piping should be adequately supported from the building structure and terminated with
an approved terminal. The maximum
recommended vent length is 25ft (7.6m) with a maximum of two elbows. All connections
should be properly sealed. refer fig 7a
1.6.3 Horizontal venting
Individual units can be vented horizontally through side walls. Recommended terminals are Part Numbers 111848 for 4” and 111850 for 6”.
Distances from adjacent public walkways, adjacent buildings, openable windows and
building openings, consistent with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
Maximum length of vent is 25ft (7.6m) with two
- 90° elbows.
This protects the building material from degradation by the vent gasses.
Vent joints should be sealed and secured according to the vent manufacturers instructions. Should condensation occur the vent should be shortened or insulated.
The terminal should be at least 3ft (0.91m) away from any air intake to the building.
If the heater is equipped with ducted combustion air, the vent terminal must be at least 3ft (0.91m) away from the air inlet and located higher than the inlet.
The vent terminal must be installed at a suitable height above the ground to prevent blockage by snow.
1.7 Fresh Air Intake
Whenever the heater is installed in locations where airborne dust or other pollutants are present, a fresh air supply should be ducted to the burner.
A fresh air duct of 4”(101mm) dia. should be installed from the fresh air to the air intake connection on the fan housing. A flexible jointing piece should be installed at the fan connection with hose clamps to facilitate expansion and contraction.
The maximum recommended length air duct is 25ft (7.6m) and the maximum number of elbows is two. The minimum length is 18” (456mm).
The location of the fresh air duct inlet must be where it will receive dust free clean air. An inlet cap with bird screen must be fitted at the inlet of the duct. If the duct inlet is located above the roof the underside of the inlet terminal must be at least 2ft (0.61m) above roof level and at least 10” (254mm) above any projection on the roof within 7ft (2.1m) of the inlet. Intake pipe, fittings and sealant are not furnished by the manufacturer. Refer fig 7c & d.
Runs of 12ft (3.6m) or shorter can use 4” (101mm) dia vent. Runs over 12ft (3.6m) should use 6” (152mm) vent pipe.
Any portion of vent that passes through a combustible wall must be insulated, or use an approved insulating thimble.
Standard vent terminals must extend at least 6” (152mm) from the wall and at least 24” (609mm) from any combustible overhang.
10
Page 11
Figure 7.a Vertical Venting.
CODE APPROVED VENT THROUGH ROOF
Figure 7.b Horizontal Venting.
SUPPLIED BY OTHERS
4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAP TER
REQUIRED ONLY FOR 6" (152mm) DIA. VENTS
APPROVED CAT III VENT PIPE
ALUMINUM 4" (101mm) O.D. OR 6" (152mm) O.D. FLUE
SEAL JOINTS WITH
HIGH TEMPERATURE SILICONE
END OF RADIANT TUBE
REFLECTOR
ENSURE ALL JOINTS ARE
HIGH TEMPERATURE
APPROVED CAT 3 VENT PIPE
ROOF
SEAL JOINTS WITH
SEALED
SILICONE
SEAL
12'-0" (3.66m)
12'-0" (3.66m)
(APPROXIMATE
MAXIMUM DIMENSIONS)
4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAPTER
REQUIRED ONLY FOR 6" (152mm) DIA. VENT
VENT CAT III ELBOW
VENT ADAPTOR ELBOW
6" (152mm)
CAT III ADAPTER
COLLAR
TERMINAL
SUPPLIED BY OTHERS
COUPLER
END OF
REFLECTOR
RADIANT TUBE
ALUMINUM 4" (101mm) O.D. MAX IMUM LENGTH = 12'-0" (3.66m) ALUMINUM 6" (152mm ) O.D.MAX IMUM LENGTH = 25'-0" (7.62m) (PLUS A MAXIMUM OF 2 x 90° BENDS
ELBOWS
Figure 7.c Fresh Air Ducted Intake.
ALUMI NUM 4" (101 mm) O.D. PIPE
MAX LENGTH = 2 5'- 0" ( 7.62 m) WIT H 2-90° LONG RADIUS BENDS
CLAMPS
WITH TWO– 90° ELBOW S
4.25” (108mm) O.D FLEXIBLE DUCT
4" ( 106mm) O.D. FLEXI BLE DUCT
WALL
TERMINAL
36" (914mm) MIN CENTERS
INLET WITH BIRD SCREEN
36" (914mm) MIN CENTERS
Figure 7.d Wall Terminal Intake Kit.
INLET WITH BIRD SCREEN
WALL
SEAL JOINTS WITH
SILICONE OR DUCT TAPE
NOTE: The vent terminal should be installed so as to be in the same atmospheric pressure zone as the combustion air inlet of the appliance
BURNER
6" (152mm)
11
Page 12
1.8 Technical Details - Table 5
No of Injectors
Gas Connection
Electrical Supply
Vent size (in)
Unitary Fan Motor Details
Current Rating
Natural Gas LP Gas
MODEL
BTU/Hr BTU/Hr
60
80 100 125 150 170
60,000 60,000 20 (6.1) 40 (12.1) 20 (6.1) 40 (12.1)
80,000 80,000 20 (6.1) 40 (12.1) 20 (6.1) 40 (12.1)
100,000 100,000 30 (9.1) 50 (15.2) 40 (12.1) 40 (12.1)
123,500 125,000 40 (12.1) 60 (18.3) 40 (12.1) 60 (18.3)
150,000 150,000 40 (12.1) 70 (21.3) 40 (12.1) 60 (18.3)
169,000 169,000 50 (15.2) 80 (24.4) 60 (18.3) 80 (24.4)
200 200,000
Ignition
N/A
1
½” N.P.T
120 volt 1 phase 60Hz
4” or 6” (101mm or 152mm)
120 volt 1 phase 60Hz
1.2A MAX
Electronic Program Start up with Spark Ignition
Min. Heater
Length
Max. Heater
Length
Min. Heater
Length
Max. Heater
Length
S ft (m) S ft (m) U ft (m) U ft (m)
50 (15.2) 80 (24.4) 60 (18.3) 80 (24.4)
Appliances can be installed up to 10,000 ft in the USA. Altitude conversion kits are available on request.
USA Natural Gas 0- 2000 ft (0-610m)
Size “WC
60 80 100 125 150 170 200
4.2 3.5 3.5 4.1 4.2 3.4 3.5
USA Natural Gas 2001- 4000 ft (611-1220m)
Size “WC
60 80 100 125 150 170 200
4.0 3.3 3.3 3.9 4.0 3.2 3.3
CANADA Natural Gas 0- 2000 ft (0-610m)
Size “WC
60 80 100 125 150 170 200
4.2 3.5 3.5 4.1 4.2 3.4 3.5
USA LP Gas 0- 2000 ft (0-610m)
Size “WC
60 80 100 125 150 170 200
6.0 5.2 8.2 6.6 7.0 5.7 N/A
USA LP Gas 2001- 4000 ft (611-1220m)
Size “WC
60 80 100 125 150 170 200
5.8 5.0 8.0 6.4 6.8 N/A
CANADA LP Gas 0- 2000 ft (0-610m)
Size “WC
60 80 100 125 150 170 200
6.0 5.2 8.2 6.6 7.0 5.7 N/A
CANADA Natural Gas 2001- 4500 ft (611-1370m)
Size “WC
60 80 100 125 150 170 200
4.0 3.3 3.3 3.9 4.0 3.2 3.3
12
CANADA LP Gas 2001- 4500 ft (611-1370m)
Size “WC
60 80 100 125 150 170 200
N/A
5.8 5.0 8.0 6.4 6.8 N/A
Page 13
Technical Details continued
USA & CANADA Natural Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate
Part No.
Fan Type
Fan Orifice
Part No.
Injector
Part No.
Pressure Switch
Part No.
60 80 100 125 150 170 200
269954 269955 269943 269944 269945 269946 269946
270476
269923 269922 269923 269927 269926 266930 269938
270400 270402 270404 270406 270408 270409 270410
270386 270387
USA & CANADA LP Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate
Part No.
Fan Type
Fan Orifice
Part No.
Injector
Part No.
Pressure Switch
Part No.
60 80 100 125 150 170 200
269948 269949 269950 269951 269952 269953
270476 270475
269925 269925 269928 266931 269933 269937
270398 270399 270399 270400 270401 270403
270386
270475
N/A
13
Page 14
Technical Details continued
U Tube Straight Tube
MODEL
U20 U40 U60 U80 S20 S30 S40 S50 S60 S70 S80
60
80 100 125 150 170
200
MODEL
60
80 100 125 150 170
Tube Type Material
Calcoat™ Mild Steel
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 15 (4.6)
TUBE 1 REMAINDER 20 (6.1)
TUBE 1 REMAINDER 20 (6.1)
TUBE 1 & 2 REMAINDER 25 (7.6)
Min. Distance to
Bend ft (m)
200
TUBE 1 & 2 REMAINDER 25 (7.6)
Options * Not available on LP Gas
1 All standard units fitted with unvented vent, natural gas and aluminized steel reflectors. 2 1 off 180° bend (U) or upto 2 off 90° bends (L) can be fitted at no less than 50% of the total heater length.
3 4” (101mm) or 6” (152mm) vent terminal.
4 Combustion air kit. 5 Reflector end caps. 6 Altitude conversion kit. 7 Propane and propane altitude conversion kit.
14
Page 15
2. Assembly Instructions.
PLEASE READ this section prior to
assembly to familiarize yourself with the components and tools you require at the various stages of assembly. Carefully open the packaging and check the contents against the parts and check list.
The manufacturer reserves the right to alter specifications without prior notice.
2.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Saw
Horses
Cordless Drill
Leather Faced Gloves
5/16” Drive
Please ensure that all packaging is disposed of in a safe environmentally
friendly way.
For your own safety we recommend the
use of safety boots and leather faced gloves when handling sharp or heavy items. The use of protective eye wear is also recommended.
Suitable alternative tools may be used.
Phillips Screwdriver
3/16” (5mm) 5/32” (4mm) Allen wrench
Wrench Set
Tape Measure
2.2 Assembly Notes.
2.2.3 Brackets
Please read these assembly notes in
conjunction with the correct assembly drawings (figs 9 to 19).
2.2.1 Tubes
There can be four types of brackets supplied with these heaters:
 Type ‘H’ are suspension brackets with
Each heating unit has two types of emitter tube. For details of the tube types please refer to the table (page 13 of this instruction manual).
Identify and position tubes on saw horses. For
aesthetics it is advisable to position all tube seams facing down. Position coupling
fastener so that these cannot be seen from beneath the heater.
Mark out the position of the bracket centers from the dimensions shown on the assemblers' drawings.
Turbulators: Ensure that the correct
 Type ‘G’ are suspension brackets with
turbulator or burner insert is fitted, as this could void your warranty if they are incorrectly fitted or omitted when necessary.
2.2.2 Turbulators (where fitted)
Insert turbulator into correct tube as indicated in the assembly drawings.
tube straps.
"A"
VIEW ON "A"
no tube straps.
15
Page 16
 Type ‘F’ are fixed reflector brackets.
2 x SCREWS TIGHTENED TO FIX REFLECTOR
 Type ‘S’ are sliding reflector brackets.
2.2.4 Couplers
The couplers are used for joining radiant tubes and U or L bends.
Slide the coupler over the tube ensuring that the screw stop has butted up to the tube ends. Using the 9/16” wrench to tighten the bolts.
At this point raise the tube assembly into
position and suspend from previously fixed chains (Working Load 100lb). Longer tube assemblies may be raised in more than one sub-assembly with final tube connection made in the air.
LEAVE 1/8" MIN. GAP TO ALLOW REFLECTOR TO SLIDE
Slip the suspension brackets onto the tube assembly. The fixed suspension point ’H’ shown on the drawings are adjacent to the burner and secures the first suspension bracket to the tube with a tube strap. All other suspension brackets ’G’ shown on the drawings, have floating suspension points.
Reflectors are fixed at point ’F’ with a reflector support bracket and reflectors are held in position with fixing screws. Fixed and sliding joints alternate along the heater at the spacings indicated on the individual heater assembly sheets.
DO NOT OVERTIGHTEN.
Moving between the four bolts, tighten each ensuring that equal pressure is applied to each bolt in turn. Complete assembly by drilling and screwing self tapping retention zip screws.
2.2.5 Reflectors.
After removing the protective plastic coating (if fitted), slip the reflectors through the hanger brackets until they overlap each other.
All reflectors must be positioned/ attached to the brackets exactly as detailed in the assembly drawings.
The first and second reflector are fixed at the point F by a type F reflector support bracket and are held in place by tightening the fixing screws.
Each subsequent reflector must
OVERLAP the previous one as shown
below and to a distance as indicated by their individual assembly sheets.
Alternate fixings of further reflectors by type S and type F reflector brackets and space as indicated by individual assembly sheets.
Reflector support bracket assemblies are fitted at each reflector joint, with the clamp screws adjusted so that reflectors are fixed together.
16
Page 17
BURNER ASSEMBLY
H
F
REFLECTORS
S
F
Typical usage of optional bend kits:
End Cap
2.2.6 End Caps (optional)
Position an end cap beneath the reflector profile (where required) with the end cap flanges facing inwards. Fasten to reflector using the four ’Z’ clips.
2.2.7 Bend(s) (where fitted)
The heater can be installed with 1 or 2 90° bends or a 180° U bend.
Slide the bend into the open end of the coupler ensuring that the screw stop has butted up to the tube ends. Refer to 2.2.4 for fastening.
2.2.8 Burner/Fan Assembly.
Slide the burner assembly onto the open tube end, ensuring it is fully engaged. Secure with set screws.
For the purpose of unvented applications, a 4” 90° elbow should be used on the terminating end of the radiant tube sections. This elbow should be turned with the outlet facing either side.
Connect Gas and Electrical supplies as described in sections 1.4 and 1.5.
2.2.9 Detailed Assembly Drawings
The following pages show the technical dimensional details of the range of heaters.
Please note the heater type, length and reference number from the delivery/advice note before identifying the correct model drawing.
Corner reflector
End Caps
Corner reflectors (optional)
16” crs
Corner reflectors kit
U Bend
End Caps
90° Bend
90° Elbow
15”
17
Page 18
S20
S30
S40
S50
S60
S70
S80
Figure . 8. Possible Heater Orientations
U20
U40
U60
Bends must be fitted at a distance of at
least 50% of the total heat exchanger
e.g. for a 60ft long heater, the closest to
the burner a bend can be is 30ft.
U80
18
Page 19
Figure 9. Heater Assembly: Model Linear 60-S20 and 80-S20.
END
CAPS
GH
(OPTIONAL)
6"-9" REFLECTOR OVERLAP
S
TURBULATOR
(SEE DETAIL)
TURBULATOR DETAIL PT. NO. 270495
NOTE: FOR MODEL 60/80 LP GAS ONLY
NOTE: FOR MODEL 80 NAT GAS ONLY
BURNER INSERT DETAIL PT. NO. 270489
2" MINIMUM
L
C
F
STANDARD 4" COUPLER
REFLECTOR OVERLAP
G
21'6½" NOMINAL OVERALL ASSEMBLED LENGTH
10' 3" REFLECTORS TYPICAL OF 2
SUSPENSION POINTS
DISTANCE BETWEEN
NO TO EXCEED 12'
CAPS
END
(OPTIONAL)
BURNER
COUPLER
SF
TUBE & REFLECTOR SUSPENSION BRACKET
DETAIL
2 x SCREWS MIN 1/8" GAP TO
BOLT
NUT &
SUPPLIED
REFLECTOR
H G
DETAIL
TUBE
RADIANT
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
4"
6"
SUSPENSION
12.6" ref
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
STRAP
2 x SCREWS TIGHTEN TO
ALLOW REFLECTOR TO SLIDE
FIX REFLECTOR
DETAIL
SLIDING REFLECTOR BRACKET
DETAIL
FIXED REFLECTOR BRACKET
19
Page 20
Figure 10. Heater Assembly: Model Linear 60-S30, 80-S30 and 100-S30.
END
CAPS
(OPTIONAL)
6" REFLECTOR OVERLAP
S F
GGH
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
COUPLER
2" MINIMUM
L
C
STANDARD 4" COUPLER
REFLECTOR OVERLAP
6" REFLECTOR OVERLAP
F
31'6½" NOMINAL OVERALL ASSEMBLED LENGTH
G
DISTANCE BETWEEN
COUPLER
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
TUBE
STRAP
SUSPENSION POINTS
10' 3" REFLECTORS TYPICAL OF 3
NO TO EXCEED 12'
REFLECTOR
VIEW ON "A"
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
G
DETAIL
H
S
DETAIL
ALLOW REFLECTOR TO SLIDE
2 x SCREWS MIN 1/8" GAP TO
SLIDING REFLECTOR BRACKET
BOLT
NUT &
SUPPLIED
REFLECTOR
F
CAPS
END
(OPTIONAL)
BURNER
DETAIL
4"
6"
12.6" ref
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
TUBE
STRAP
DETAIL
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
FIXED REFLECTOR BRACKET
20
Page 21
Figure 11. Heater Assembly: Model Linear 60-S40, 80-S40, 100-S40, 125-S40 and 150-S40.
END
CAPS
(OPTIONAL)
3" REFLECTOR
OVERLAP
F
G
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
41'6½" NOMINAL OVERALL ASSEMBLED LENGTH
G GH
G
DISTANCE BETWEEN
SUSPENSION POINTS
NO TO EXCEED 12'
6" REFLECTOR
OVERLAP
S S
L
C
STANDARD 4" COUPLER
2" MINIMUM
REFLECTOR OVERLAP
COUPLER COUPLER
6" REFLECTOR
OVERLAP
TYPICAL OF 4
10' 3" REFLECTORS
F
DETAIL
2 x SCREWS MIN 1/8" GAP TO
*(HIGH TEMP COUPLER
COUPLER
MODEL 125/150 )
TUBE
STRAP
(SEE DETAIL)
BURNER INSERT
NAT GAS ONLY
4"
6"
REFLECTOR
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
REFLECTOR
H G
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
CAPS
END
(OPTIONAL)
BURNER
SUSPENSION
21
BRACKET
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
DETAIL
FIXED REFLECTOR BRACKET
DETAIL
TUBE
RADIANT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
SUPPLIED
NUT & BOLT
TUBE
STRAP
Page 22
Figure 12. Heater Assembly: Model Linear 100-S50, 125-S50, 150-S50, 170-S50, and 200-S50
END
CAPS
(OPTIONAL)
51'6½" NOMINAL OVERALL ASSEMBLED LENGTH
3" REFLECTOR
OVERLAP
G
S
COUPLERCOUPLER
F
3" REFLECTOR
OVERLAP
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODEL 100 NAT GAS ONLY
G
2" MINIMUM
L
C
S F
STANDARD 4" COUPLER
6" REFLECTOR
OVERLAP
REFLECTOR OVERLAP
G GH
*(HIGH TEMP
COUPLER
COUPLER
MODEL 170 & 200)
SF
F
6" REFLECTOR
OVERLAP
G
* (HIGH TEMP
COUPLER
COUPLER
MODELS 125,
150, 170 & 200)
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
POINTS NOT TO
EXCEED 12'
END
10' 3" REFLECTORS
CAPS
(OPTIONAL)
SUSPENSION
DISTANCE BETWEEN
TYPICAL OF 5
BURNER
TUBE
STRAP
4"
(SEE DETAIL)
BURNER INSERT
6"
NAT GAS ONLY
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
H G
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
DETAIL
2 x SCREWS TIGHTEN TO
TUBE
RADIANT
TUBE
STRAP
FIX REFLECTOR
FIXED REFLECTOR BRACKET
22
Page 23
Figure 13. Heater Assembly: Model Linear 125-S60, 150-S60, 170-S60 and 200-S60
END
CAPS
(OPTIONAL)
3" OVERLAP
S
F
G GH
COUPLERCOUPLER
3" OVERLAP
S
GGG
COUPLER
3" OVERLAP
F
L
C
2" MINIMUM
STANDARD 4" COUPLER
6" OVERLAP
61'6½" NOMINAL OVERALL ASSEMBLED LENGTH
S
REFLECTOR OVERLAP
SF
2 x SCREWS MIN 1/8" GAP TO
2 x SCREWS TIGHTE N TO
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
DETAIL
*(HIGH TEMP
COUPLER
COUPLER
MODELS 170 & 200)
6" OVERLAP
G
SUSPENSION
DISTANCE BETWEEN
POINTS NOT TO
EXCEED 12'
TYPICAL OF 6
10' 3" REFL'S
F
TUBE
STRAP
REFLECTOR
*HT COUPLER
4"
6"
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
REFLECTOR
H G
DETAIL
TUBE
RADIANT
CAPS
END
(OPTIONAL)
SUSPENSION
BRACKET
TUBE
BURNER
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
STRAP
23
Page 24
Figure 14. Heater Assembly: Model Linear 150-S70, 170-S70 and 200-S70.
END
CAPS
(OPTIONAL)
F
3" OVERLAP
S
G GH
3" OVERLAP
F
G
3" OVERLAP
GGG
3" OVERLAP
S
2" MINIMUM
L
COUPLER COUPLER COUPLERCOUPLER
F
STANDARD 4" COUPLER
C
REFLECTOR OVERLAP
71'6½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
6" OVERLAP
6" OVERLAP
G
SUSPENSION
POINTS NOT TO
EXCEED 12'
TYPICAL OF 7
10' 3" REFL'S
CAPS
END
(OPTIONAL)
S
DETAIL
2 x SCREWS MIN 1/8" GAP TO
200)
*(HT COUPLERS
COUPLER
MODELS 170 &
F
TUBE
STRAP
REFLECTOR
HT COUPLER
4"
6"
SUSPENSION
BRACKET
BURNER
SUPPLIED
"A"
TUBE
RADIANT
NUT & BOLT
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
FIRST SUSPENSION POINT TUBE STRAP
REFLECTOR
H G
DETAIL
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
24
Page 25
Figure 15. Heater Assembly: Model Linear 170-S80 and 200-S80
END
CAPS
(OPTIONAL)
S
3" OVERLAP
F
G
3" OVERLAP
S
G
3" OVERLAP
F
G GH
3" OVERLAP
GGG
S
L
C
STANDARD 4" COUPLER
2" MINIMUM
REFLECTOR OVERLAP
3" OVERLAP
F
81'6½" NOMINAL OVERALL ASSEMBLED LENGTH
COUPLER COUPLER COUPLER COUPLER COUPLER
6" OVERLAP
S
DETAIL
2 x SCREWS MIN 1/8" GAP TO
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
TUBE & REFLECTOR SUSPENSION BRACKET
HT COUPLER
6" OVERLAP
F
TUBE
STRAP
NUT &
BOLT
SUPPLIED
REFLECTOR
G
HT COUPLER
4"
TYPICAL OF 8
SUSPENSION POINTS
DISTANCE BETWEEN
NO TO EXCEED 12'
10' 3" REFL'S
CAPS
END
(OPTIONAL)
6"
SUSPENSION
BRACKET
SUPPLIED
BURNER
NUT & BOLT
VIEW ON "A"
"A"
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
REFLECTOR
H G
2 x SCREWS TIGHTEN TO
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
DETAIL
TUBE
RADIANT
TUBE
STRAP
25
Page 26
Figure 16. Heater Assembly: Model U tube 60-U20 and 80-U20.
3' 3"
12'1½" NOMINAL OVERALL ASSEMBLED LENGTH
F
G
COUPLER
10' 3" REFLECTORS TYPICAL OF 2
F
GH
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODEL 80 NAT GAS ONLY
2" MINIMUM
BURNER INSERT
DISTANCE BETWEEN
(SEE DETAIL)
SUSPENSION POINTS
NAT GAS ONLY
STANDARD 4" COUPLER
DETAIL
NO TO EXCEED 12'
L
C
REFLECTOR OVERLAP
G
CAPS
END
(OPTIONAL)
BURNER
TUBE & REFLECTOR SUSPE NSION BRACKET
4"
6"
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
H G
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
F
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
26
Page 27
Figure 17. Heater Assembly: Model U tube 60-U40, 80-U40, 100-U40, 125-U40 and 150-U40.
3' 3"
S
GGG
COUPLER
F S
6"-9" REFLECTOR OVERLAPS
G
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
2" MINIMUM
L
C
F
STANDARD 4" COUPLER
REFLECTOR OVERLAP
GH
22'1½" NOMINAL OVERALL ASSEMBLED LENGTH
SF
DISTANCE BETWEEN
END
SUSPENSION POINTS
CAPS
DETAIL
*(HIGH TEMP
COUPLER
COUPLER
MODEL 125/150 )
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFL ECTOR SUSPENSION BRACKET
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
NO TO EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 4
4"
(OPTIONAL)
BURNER
6"
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
H G
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
ALLOW REFLECTOR TO SLIDE
FIX REFLECTOR
DETAIL
SLIDING REFLECTOR BRACKET
DETAIL
FIXED REFLECTOR BRACKET
27
Page 28
Figure 18. Heater Assembly: Model U tube 125-U60, 150-U60, 170-U60 and 200 -U60
3' 3"
F
G
S
6" REFLECTOR OVERLAPS
G
GGH
S
G
*(HIGH TEMP
COUPLER
COUPLER
MODELS 170 &
2" MINIMUM
200)
STANDARD 4" COUPLER
L
C
REFLECTOR OVERLAP
32'1½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
G
G
END
F F
SUSPENSION POINTS
CAPS
NO TO EXCEED 12'
(OPTIONAL)
6"-9" REFLECTOR OVERLAPS
10' 3" REFLECTORS TYPICAL OF 6
BURNER
F
SF
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
HT COUPLER
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
4"
6"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
H G
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
28
Page 29
Figure 19. Heater Assembly: Model U tube 170-U80 and 200-U80
3' 3"
S
GGG
F
3" REFLECTOR OVERLAPS
G
S
6" REFLECTOR OVERLAPS
G
GGH
F
G
COUPLER
S
2" MINIMUM
G
STANDARD 4" COUPLER
L
C
REFLECTOR OVERLAP
42'1½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
END
SUSPENSION POINTS NO TO
F S
CAPS
HT COUPLER
6"-9" REFLECTOR OVERLAPS
EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 8
(OPTIONAL)
BURNER
F
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
TUBE
STRAP
REFLECTOR
HT COUPLER
SUSPENSION
4"
6"
BRACKET
SUPPLIED
NUT & BOLT
VIEW ON "A"
"A"
TUBE
RADIANT
H G
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
REFLECTOR
RADIANT
SUPPLIED
TUBE
BOLT
NUT &
TUBE
STRAP
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
FIXED REFLECTOR BRACKET
SF
DETAIL
DETAIL
29
Page 30
3. Start Up Instructions.
These appliances should be commissioned by a qualified mechanical contractor.
3.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Leather Faced Gloves
Phillips Screwdriver
Suitable alternative tools may be used.
Small Flat Head Screwdriver
Large Adjustable Wrenches for fitting Of Gas Flex.
½” Wrench
5/32” (4mm) Allen Wrench
3.2 Start Up procedure
Inspect installation and ensure that it has been carried out in accordance with these instructions. Remove burner and inspect the electrode assemblies ensuring these are securely fixed and all electrical connections securely made.
Re-fit the burner ensuring that it is correctly positioned and the screws are fully tightened. Ensure that electrical and gas supplies are isolated.
The gas supply should be purged and tested for soundness in accordance with local and National Safety codes.
Open isolating gas valve and test gas connections for soundness using soap solution.
Open the control housing door by unscrewing the securing screw. Ensure all internal components are securely fixed and all connections securely made.
Open the manual gas valve outside the control housing
Switch on the electrical supply to start the heater and observe the correct start up sequence. Ensure that the setting of any time switch and thermostat are such that the heating system will be required to operate.
The fan will start to run and the ‘power on’ lamp will illuminate. Safe-start checks are carried out automatically.
After the fan has run up to full speed and a sat­isfactory pressure condition has been established, the ignition sequence will commence. The spark ignition will be energized producing a spark at the ignition electrode. The gas solenoid valve will at the same time be energized and the ‘burner on’ lamp will illuminate. If the ignition is successful, the flame is detected by the flame sensing probe and the ‘burner on’ lamp will remain on.
If ignition is unsuccessful the gas valve will close and the spark ignition de-energized after approximately 15 seconds.
For approximately 30 seconds the fan will purge the system then re-ignition will be attempted. After 2 further attempts at ignition the control unit will ‘lock-out’, the ‘power on’ lamp will remain illuminated and the fan will run for 120 seconds and then stop.
To reset after ‘lockout’ switch off the power supply to the system and wait 2 minutes. Then turn the power on. If repeated ‘lockout’ occurs, investigate the cause.
Set burner gas pressure as follows: Switch off the power supply to the heating system.
Connect a ‘U’ tube manometer to the pressure test point provided on the combination gas control valve.
Remove the cover from the pressure regulator revealing the adjustable screw.
Manometer
Multimeter
30
Page 31
Start the heater and using a suitable screwdriver adjust the pressure regulator, turning the screw clockwise to increase the pressure or counter-clockwise to decrease the pressure.
Set the pressure to appropriate inches w.c. from the table of gas pressures and orifice plate dimensions for correct heater description.
Switch off the power supply to the heating system. Disconnect ‘U’ tube manometer, then secure screw in pressure test nipple.
Check the operation of the flame safeguard equipment as follows:
With the heater running normally, switch off the gas supply at the shut off valve. The heater should attempt to relight. If the gas valve has been left off, ‘lock-out’ should occur. This is indicated by the ‘power on’ lamp being illuminated and fan running, but the ‘burner on’ lamp being off.
Check the operation of the pressure proving switch as follows:
With the heater running normally, pull off the silicone rubber tube connecting the vacuum switch to the combustion chamber. Within 4 seconds the burner should shut off.
Then replace the tube securely and observe that the heater proceeds to ignite in the normal way.
Close the controls door securing it with the screw.
31
Page 32
Commissioning chart
Check installation has
been carried out to these
instructions.
Remove burner from tube and inspect burner head.
Replace burner on tube
and secure.
Check thermostat is set to
maximum and is calling
for heat.
Ensure gas and electricity
supplies are isolated.
(See servicing instructions)
Reconnect gas hose.
Open manual valve.
Check soundness.
Switch on electrical supply.
The red lamp should now
be illuminated. If restarting
heater a delay of 15sec
should be allowed.
Disconnect gas hose from
burner
Open control housing and check that all components
are securely fastened.
The heater should now
run through its start up
sequence and ignite.
Check gas pressure.
Leave the instructions
with a responsible person.
A successful ignition is indicated
by the amber light illuminating
and remaining illuminated.
Close control housing
Turn off power and check
that all components are
securely fastened.
NO
Has the
burner lit?
YES
Check operation on flame failure.
Check gas pressure.
Check operation of
air pressure switch.
32
Page 33
4. Servicing Instructions.
These appliances should be serviced annually by a competent person to ensure safe and efficient operation. In mildly dusty or polluted conditions more frequent servicing may be required. Servicing work should be carried out by a qualified mechanical contractor.
4.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Leather Faced Gloves
½” Wrench
Phillips Screwdriver
5/32” (4mm) Allen
4.2 Burner Description.
Figure 20. Burner breakdown
K
A
Suitable alternative tools may be used.
Small Flat Head Screwdriver
Manometer
Multimeter
J
H
Large Adjustable wrenches for fitting of Gas Flex.
Soft Brush
L
F
G
I
A Ignition Controller
B Gas Valve
C Power On Red LED
D Burner On Yellow LED
F Burner Tube
G Burner head
H Injector
I Igniter Assembly
Q
P
M
J Jet Carrier
K Combustion Fan
L Pressure Switch
M Gaskets
N Transformer
P Burner Orifice Plate
Q Flame Plate (not shown)
D
C
N
Note: Cables Omitted For Clarity
B
Page 34
4.3 Burner Removal Step 1: Isolate power and gas supplies.
Step 2: Unplug the power connectors.
Step 3: Detach the gas supply as shown be-
low, taking care to support the burner connection.
in a safe area to prevent the burner or components attached to the burner from falling to the ground.
4.4 Burner Gas Injector Servicing Step 1.a: Remove the burner support casting
and gasket.
Step 4: If fresh air is connected, slacken
hose clip and remove the flexible hose from the burner.
Step 5: loosen the set screw on the burner
support casting to enable the burner to be removed from the radiant tube.
Step 6: Remove the burner and position
Step 1.b: The burner head assembly can be
disconnected by separating the connectors of the ignition lead, ground lead assembly and
removing the pressure switch silicon tube.
Step 2: The gas injector can be inspected and
replaced if contaminated or blocked.
When replacing the gas injector ensure approved thread sealant is used.
34
Page 35
Step 3: Reconnect ignition leads, ground lead
and silicone tube to test nipple. Refit gasket and support casting.
4.5 Burner Head and Electrode Servicing
Step 1: Check the pepper pot burner head for
contamination. If necessary this can be removed, see below. This can be cleaned together with the Inside of the burner head.
the two screws and separating the igniter lead connectors.
Step 4: Refit the electrode assembly and en-
sure the connections are secure to prevent in­correct sparking .
Step 5: Check the positions and spark gap as
shown below.
Step 6: The burner assembly is ready to refit
after servicing the combustion fan and the radiant tube assembly.
4.6 Combustion Fan Assembly Step 1: If ducted air is fitted, loosen hose clamp
and remove the flexible hose from the fan.
Step 2: The pepper pot burner head can be
replaced ensuring the 5 holes on the outer ring are aligned alongside the probes.
Step 3: The condition of the igniter assembly
can be checked for deterioration. However, we advise replacement at each service to ensure continued reliability. Detach the electrode assembly from the burner head by removing
35
Page 36
Step 2: Remove fan retaining screws and
unplug from burner box.
Step 3: The combustion fan can now be
detached.
4.8 Reflector Servicing
The condition of the reflectors should be noted. If necessary the reflectors can be cleaned with a mild detergent. This can significantly improve the efficiency of the appliance.
4.9 Cleaning of Vent
Inspect the fresh air inlet duct and vent to ensure they are free from any blockage or obstruction. The air inlet terminal and vent terminal should be inspected to ensure they are not liable to obstruction.
4.10 Re-commissioning After Service
After servicing has been undertaken, it will be necessary to re-commission the heater as detailed in Section 3 of these instructions.
Step 4: Remove the fan orifice plate and
ducted air connection (If fitted).
Step 5: Inspect the impeller and remove any
dust with a soft brush.
Step 6: Remove any dust from fan scroll and
from around the motor.
Step 7: Ensure the impeller rotates freely. Step 8: Refit components.
4.7 Radiant Tube Servicing
Step 1: Brush any dust from the exterior of the
tubes.
Step 2: Visually inspect inside the tubes. If
they are clean, skip to servicing the reflector.
Step 3: If required the interior of the tubes
can then be cleaned using an industrial vacuum cleaner, or by using long poles and a scraper.
36
Page 37
5. Spare Parts.
Required Spares
In order to aid troubleshooting and servicing we recommend that the components shown in this section should be stocked.
Note: Any spare part components that are
not approved by the manufacturer could invalidate the approval of the appliance and the warranty.
Item
Transformer (30VA)
Gas Valve NG LPG
Flame Plates Models 60 NG & LPG 80 / 100 LPG 125 / 150 LPG 170 LPG
Jet Carriers Models 60 - 150 NG 60 - 170 LPG Model 170/200 NG
Part No. Description Part No. Description Item
175265
270378 270496
269957 269958 269959 269960
270375
270376
Pressure Switch Models 60 - 170 Model 200 NG
Single Probe Ignitor with Connector Lead
Amber Neon (Burner On)
Red Neon (Power On)
24V UT Ignition Controller
270386 270387
270441
270473
270474
204955
Burner Head
Burner Tube
Turbulators Models 60 / 80 LPG S20
Burner Insert Models 80 / 100 NG
270425
270424
270495
270489
Injector
Combustion Fans Models 60 - 170 NG, 60 - 150 LPG Models 200 NG, 170 LPG
See section 1.8
270464
270467
37
Page 38
6. Troubleshooting Guide.
START
Ensure gas & electricity
supplies are enabled.
Turn any external timer
to call for heat (if fitted).
YES
Does the Power On
light illuminate?
NO
CHECK: -
1. Operation of any timer or control.
2. External fuses.
3. Supply Voltage is 120VAC 60Hz
Is there power to the
burner?
NO
CHECK: -
1. Transformer
YES
2. Integrity of wiring connections.
3. Light.
YES
Set thermostat to call for
heat at maximum setting
Does the fan run?
CHECK: -
1. Integrity of wiring connections.
2. Pressure switch operation.
3. Ignition controller.
4. Transformer.
Do the amber
lights illuminate after a
purge period?
NO
NO
Is there power to
the fan?
NO
Does the Pressure
switch close?
YES
CHECK: -
1. Voltage supply to fan terminal 120VAC 60Hz
2. Integrity of wiring connections.
3. Fan.
CHECK: -
1. Pressure switch wiring connections.
4. Integrity of wiring connections.
YES
5. Amber lights.
6. Ignition controller.
5. Transformer
YES
NO
CHECK: -
1. Hose connection to Pressure switch.
2. Air inlet, outlet, and emitter tubes for obstructions.
3. Pressure switch operation.
4. Supply voltage 120VAC / 60Hz
5. Transformer.
6. Ignition Controller.
38
Page 39
To aid the troubleshooting process, the UT controller has a LED flash code diagnostic se­quence:
Steady Off No control power Steady On Power applied, control OK 1 Flash Combustion pressure switch open with blower on 2 Flashes Combustion pressure switch closed with blower off 3 Flashes Lockout from the three ignition trials 4 Flashes Lockout from five flame losses 5 Flashes Control hardware fault detected 6 Flashes Lockout from five pressure switch losses
39
Page 40
7. Replacing Parts.
Turn off gas and any electrical supplies to the heater before starting repair work.
7.1 Burner Controller Replacement Step 1: Loosen screw in right hand burner
access door and open.
Step 2: Disconnect burner controller from the
wiring harness.
Step 3: Disconnect the spark lead from burner
controller.
7.2 Air Pressure Switch Replacement Step 1: Open left hand door. Disconnect the two
silicone tubes from the pressure switch.
Step 2: Remove the two screws shown below.
Step 4: Remove the two screws attaching the
controller to the burner door and remove.
Step 5: Attach new burner controller. Step 6: Reattach leads. Step 7: Test product and close access door.
Step 3: Remove electrical connections. The air
pressure switch can now be removed.
Step 4: Fit the new air pressure switch ensuring
the silicon tubes are connected as shown below.
Step 5: Test product and close access doors.
Page 41
7.3 Gas Valve Replacement Step 1: Remove the burner assembly as
described in the servicing section.
Step 2: Open the right hand access door and
detach the burner controller from the wiring harness.
Step 3: Open the left hand access door and
detach the silicon hoses from the air pressure switch.
Step 6: Detach the two screws securing the
front of the gas valve.
Step 7: Remove the four screws (arrowed),
holding the rear burner plate in position.
Step 4: Remove the 4 screws holding the
burner head onto the burner assembly.
Step 5: The burner head can now be detached
by disconnecting the silicon tube and the burner head wiring.
Step 8: Remove the rear plate.
Step 9: The jet carrier, gas inlet, and wiring
harness can now be detached from the gas valve.
Step 10: The two screws retaining the gas valve
can now be removed.
Step 11: The gas valve can now be replaced. Step 12: Reattach all components.
Step 13: Set pressures and test for reliable
burner performance.
Step 14: Close access door.
Page 42
7.4 Optional Extra Kits.
180° U-Bend Kit
(1 Off)
90° Elbow Kit
Kit (1Pair)
Aluminized
Steel End Cap
Air inlet Kit
Combustion
Conversion Kit
Propane Gas &
Propane Altitude
270630 270619
Conversion Kit
Natural Gas Altitude
270613 270611 270277 270276
270630 270620
270631 270621
270632 270622
270633 270623
270634 270627*
270635 270628**
60
MODEL
42
80
100
125
150
170
200
* Burner de-rated when converted to propane
** Burner de-rated when converted to propane. Not for use at altitude.
Page 43
Notes.
43
Page 44
8. User & Operating Instructions.
Radiant tubular infrared heaters are designed for overhead heating of industrial and commercial buildings. Individual heating units are suspended from the roof.
1. This appliance must only be installed by qualified installer in accordance with the requirements of local and National Codes.
2. This appliance must be grounded in accordance with the National Electrical Code ANSI/NFPA No.70 or Canadian Codes.
3. Never rest anything, especially ladders against the heaters.
8.1 To Start the Heater
1. First ensure that the gas supply to each heater is turned on by opening the main gas shut off valve.
2. Ensure that the setting of any time switch and thermostat are such that the heating system will be required to operate.
3. Switch on the electricity supply to the heater. The fan will start, the ‘power on’ light on the burner will illuminate and ignition commence.
4. Ignition will occur.
5. If ignition is unsuccessful the gas valve will close and the spark ignition de-energize after approximately 15 seconds. For approximately 30 seconds the fan will purge the system then re-ignition will be attempted. After 3 attempts at ignition the control unit will ‘lock-out’, the ‘power on’
lamp will remain illuminated and the fan will continue to run. To reset after ‘lockout’, switch off the power supply to the heater and wait 5 minutes. Then turn the power on. If repeated ‘lockout’ occurs investigate the cause.
8.2. To Switch Off Heater
Switch off electrical supply to the heater.
The burner will stop and the fan will shut off.
8.3. Servicing
To ensure continued, efficient and safe
operation it is recommended that the heater be serviced regularly by a qualified person every year in normal working environments, but in exceptionally dusty or polluted environments more frequent servicing may be needed.
800-695-1901
www.RezSpec.com
©2014 Reznor, LLC. All rights reserved. Trademark note: Reznor is registered in at least the United States.
All other marks are the property of their respective organizations. 0114 OG POD Form I-VPS ( Version C.1)
700101
Loading...