Model VPS
Burner/Control Box
with 20 - 80 ft Tube/Reflector Length
Form I-VPS (Version C)Part No. 270683
Page 2
Introduction.
Welcome to the new range of powered infra-red
heaters. Local regulations may vary and it is the
installer’s responsibility to ensure that such regulations are satisfied.
All installation, assembly, commissioning and
service procedures must be carried out by
suitable qualified competent persons and
conform with local building codes, or in the
absence of local codes, with the National Fuel
Gas Code ANSI Z223.1/NFPA 54 or the
National Gas and Propane Installation Code
CSA B149.1
When assembling, installing, commissioning
and servicing is undertaken on radiant tube
Document Index.
heaters specified in these instructions, due care
and attention is required to ensure that working
at height regulations are adhered to.
PLEASE READ this document prior to
installation to familiarize yourself with the
components and tools you require at the various
stages of assembly.
All Dimensions shown are in inches unless
otherwise stated.
The manufacturer reserves the right to alter
specifications without prior notice.
1 Installation Requirements
1.1 Health & Safety
1.2 Heater Suspension
1.3 Clearance to Combustibles
1.4 Gas Connection & Supply Details
1.5 Electrical Connections
1.6 Ventilation Requirements
1.6.1 Unvented Units
1.6.2 Vertical Venting
1.6.3 Horizontal Venting
1.7 Fresh Air Intake
1.8 Technical Details
2 Assembly Instructions
2.1 Tools Required
2.2 Assembly Notes
2.2.1 Tubes
2.2.2 Turbulators
2.2.3 Brackets
2.2.4 Couplers
2.2.5 Reflectors
2.2.6 End Caps (optional)
2.2.7 Bends (where required)
2.2.8 Burner/Fan Assembly
2.2.9 Detailed Assembly Drawings
3 Start Up Instructions
3.1 Tools Required
3.2 Start up procedure
4 Servicing Instructions
4.1 Tools Required
4.2 Burner Description
4.3 Burner Removal
4.4 Burner Gas Injector Servicing
4.5 Burner Head and Electrode Servicing
4.6 Combustion Fan Assembly
4.7 Radiant Tube Servicing
4.8 Reflector Servicing
4.9 Cleaning of Vent
4.10 Re-commissioning after Service
5 Spare Parts
6 Troubleshooting Guide
7 Replacing Parts
7.1 Burner Controller Replacement
7.2 Air Pressure Switch Replacement
7.3 Gas Valve Replacement
7.4 Optional Extra Kits
8 User and Operating Instructions
8.1 To Start Heater
8.2 To Switch Off Heater
8.3 Servicing
1. Installation Requirements.
1.1 Health and Safety
A. Heater is intended for heating
non-residential indoor spaces and should
only be installed where flammable gases
or vapors are not generally present.
B. Heaters may be suspended either
horizontal or at any angle. See section
1.3 for clearance dimensions.
C. The installation must conform with local
building codes or, in the absence of local
codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the Natural
Gas and Propane Installation Code, CSA
B149.1.
D. The unit shall be electrically grounded in
accordance with National Electric Code
ANSI/NFPA 70 and Canadian Electrical
Code CSA C22.1.
E. The heater may be installed in aircraft
hangars in accordance with the Standard
for Aircraft Hangars, ANSI/NFPA 409
and in automotive garages when
2
Page 3
installed in accordance with the Standard
for Parking Structures, ANSI/NFPA 88A,
or the Standard for Repair Garages,
ANSI/NFPA 88B, or the Canadian
Natural Gas and Propane Installation
Code, CSA B149.1, and are so marked.
Ensure that minimum clearances will be
maintained to vehicles parked below the
heater.
F. The standard heaters are approved for
installations between 0 - 2000ft
(0 - 610m) for the US and 0 - 4500 ft
(1370m) for Canada. Conversion kits are
available on installations above these
heights in the USA.
1.2 Heater Suspension
Attachment to the heater support lugs should
be made by D shackle. The hanging
attachments to overhead steelwork etc. must
be purpose made to sound engineering
practice or supplied by others.
They must be adequately fixed and designed to
carry the whole weight of the heater. In the
event of suitable roof steelwork being
unavailable, additional steelwork should be fitted
to enable vertical hangers to be used for
suspending the heaters.
These methods are illustrated in Figure 1. If
there are any doubts as to the strength or
suitability of roof steelwork to which heaters are
to be suspended, please refer to a Consultant,
Architect or owner of the building.
It is recommended that the heater is raised to its
final position once the assembly of the tube/
bracket/reflector has been completed. Longer
tube assemblies may be raised in more than
one sub-assembly with final tube connection
made in the air.
The suggested mounting heights for heaters are
given in the chart next page.
WARNING:
If not installed, operated and maintained in accordance with the manufacturer’s instructions,
this product could expose you to substances in fuel or from fuel combustion which are
known to the state of California to cause cancer, birth defects or other reproductive harm.
Figure 1. Recommended Methods of Heater Suspension.
U TUBE VARIANTS
EYE HOOKS
NOTE.
HOOKS ARE TO
BE CLOSED UP
AFTER ASSEMBLY
Suitable Chain
2/0 GA CHAIN
Working Load Limit
(TWISTED LINK, PLATED)
100lb.
EXHAUST
END
CHAIN
55° SUSPENSION
3
BURNER
END
Page 4
ON U TUBE VARIANTS THE HEATER SHOULD SLOPE DOWNWARDS TOWARDS THE RETURN BEND AND
ON LINEAR VARIANTS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. ½” FOR
HORIZONTAL INSTALLATIONS AS SHOWN BELOW (DIAGRAMS EXAGGERATED FO R CLARITY)
1/2”
1/2”
Outlet
U Tube heater side view
U bend
Linear heater side view
1.3 Clearance to Combustibles.
Minimum clearance to combustibles are shown in Table 1 below.
IMPORTANT: The stated clearance to combustibles represents a surface temperature of 90°F (50° C) above room
temperature. Building material with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be
subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are
protected from degradation.
Minimum clearance from the heater must be maintained from vehicles
parked below heater. In all situations, clearances to combustibles must be
maintained. Signs should be posted in storage areas to specify maximum stacking height to
maintain required clearance to combustibles. Such signs must either be posted adjacent to
the heater thermostats or in the absence of such thermostats in a conspicuous location.
Refer to mounting clearance tables.
4
Page 5
Figure 2 Clearance to Combustibles.
The minimum clearances to combustible materials are given in the tables below. These
minimum distances MUST be adhered to at all times. Adequate clearance MUST be provided
around air openings into the combustion chamber and there MUST be suitable clearance for
accessibility and for combustion / ventilating air supplies.
D2
WARNING!
provision in the building for
Ensure that there is adequate
Angled view.
combustion and ventilation air supply.
Installation must meet minimum
applicable
requirements and appliciable codes.
A
.
0° to 55°
Outlet end.
D1
End
B1
Side
unvented
Above outlet
C3
unvented
Return end on
U tube heater
B
Below
A
B
Side
vented
End view.
heater
unvented
Above
Reflector
C2
Burner end.
C1
Above
Burner
5
E
Service
distance
Page 6
1.4 Gas Connection and Supply
WARNING: Before installation, check
that the local distribution conditions,
nature of gas and pressure, and adjustment
of the appliance are compatible.
The gas connection on the heater is ½” N.P.T
internal thread.
Injector sizes and manifold pressure for the
burners are shown in the table 4. The gas
supply piping and connections must be installed
so that the minimum pressure stated is
achieved.
A gas shut off valve and union should be fitted
in the gas supply line close to the heater and a
⅛” N.P.T plugged tapping, accessible for test
gauge connection, provided immediately
upstream of the appliance gas inlet.
It is essential to provide some flexibility in the
final gas connection by use of an approved
flexible gas connector. See Fig 4.
Take care when making a gas connection
to the heater not to apply excessive turning
force to the internal controls.
Care must be taken to observe the minimum
pipe bend diameter (minimum 10” - 250mm,
maximum 14” - 350mm) & pipe expansion
distance (minimum 1⅛” - 28mm, maximum
3¾”) - 95mm.
The correct installation as shown will allow
for approx 4” of movement due to expansion.
Figure 3. Correct orientation of Ball Valve
Gas Flow
Gas Flow
Figure 4. Correct Installation of Flexible
Gas Connection
WARNING: FIRE OR EXPLOSION HAZARD - Expansion of the radiant pipe occurs with
each firing cycle causing the burner to move with respect to the gas line. This can
result in a gas leak producing an unsafe condition. It is therefore essential to provide some
flexibility in the final gas line connection by use of an approved flexible connector as
shown in the drawings.
6
Page 7
* Connector must be certified for use on a radiant tube type
infrared heater and must comply with Standard for
Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 or
with the Standard for Elastomeric Composite Hose and
Hose Couplings for Conducting Propane and Natural Gas,
CAN/CGA 8.1.
For heaters up to 150,000Btu/h, ½” ID x 24” long
For heaters above 150,000Btu/h, ¾” ID x 36” long
NOTE: For Canada all heaters MUST use a hose 36” long
See Table 3
CONNECTOR MUST BE INSTALLED IN A “U” CONFIGURATION. FOR HEATERS
Table 3
HOSE SIZE USA CANADA
3/4” CE4
CONTACT
FACTORY
UPTO 150,000 BTU/H, A 24” LONG CONNECTOR OF AT LEAST ½” ID MUST BE
USED. FOR HEATERS ABOVE 150,000 BTU/H, A 36” LONG CONNECTOR OF AT
LEAST ¾” NOMINAL ID MUST BE USED.
Table 4 Gas Supply & Pressures
Gas Type Natural Gas LP/Propane Gas
Required Gas Pressure (in W.C) (60,000 TO
150,000 BTU)
Required Gas Pressure (in W.C) (170,000 TO
200,000 BTU)
Max Supply Pressure (in W.C)
Gas Supply
1.5 Electrical Connections
WARNING: Before making electrical
connections, switch OFF the main
electrical disconnect. There may be more
than one disconnect switch. Lock out
and tag switch with a suitable warning
label. Electrical shock can cause
personal injury or death.
This appliance must be electrically grounded
Supply 120V 60Hz single phase.
Standard heater 0.16HP.
Current rating 1.2 amp max (inductive).
Fuse: external 3 amp.
Important: All electrical work should be done by
a qualified electrician in strict accordance with
the National Electrical Code ANSI/NFPA 70 or
Canadian Codes CSA C22.1.
5.0 11.0
7.0 11.0
14.0 14.0
Connection ½” N.P.T thread
The electrical supply to the heater is by three
wires: live, neutral and ground connections.
Install in accordance with all state & local codes.
Where alternative manufacturers controls are
used, please refer to their instructions for their
installation details.
7
Page 8
Figure 5a. Single and Multiple Heater Installations 120V Control
KEY:
T
T
110V Thermostat
120V Thermostat
BK
W
W
G
BK
Burner 1
GND
L2
L1 (HOT)
120V 60Hz 1 Ph
Supply circuit
G-GREEN
W-WHITE
BK-BLACK
Other burners
BK
G
Figure 5b. Single Heater Installations 24V Control
BK
L1
Gas Control
IND
MV
PS1
PS0
W1
R
X
C
COM
R
R
Y
Y
K
K
BR
GR
BL
METHOD:Cut and strip pink cables linking terminals W1 and R
Attach thermostat wires using suitable wire nuts.
X
24V Thermostat
C
T
T
other burners
KEY:
BL - BLUE
BK - BLACK
BR - BROWN
GR - GREY
RW1
K - PINK
R - RED
Y - YELLOW
Figure 5c. Multiple Heater Installations 24V Control
C
T
T
R
RW1
BK
S-0700
R
G
24V Thermostat
Fan center relay
(Suppled by others)
KEY:
G - GREEN
W - WHITE
BK - BLACK
R - RED
8
40VA
30
Trans
Relay
BK
W
C
L2
L1
G
BK
GND
L2
L1 (HOT)
120V 60Hz 1 Ph
Supply circuit
Other burners
Burner 1
W
other burners
Page 9
Figure 6. Internal Burner Wiring Diagram.
120V AC Fan
G
R
W
BL
G
E
LN
120V/60Hz AC
Supply
KEY:
BK
G
W
BL - BLUE
BK - BLACK
BR - BROWN
GR - GREY
G - GREEN
K - PINK
G
BK
W
R - RED
W - WHITE
Y - YELLOW
YY
Pressure Switch
120v/24VAC 60Hz
Transformer
BR
Power ON (red)
BLBR
Burner ON (amber)
BK
Y
IND
R
MV
R
L1
K
PS1
PS0
K
W1
R
Gas Control
BR
BL
GR
X
C
COM
R
GR
G
M
C
E
Y
NOTES:Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected
to burner.
Additional wiring is required to install an optional extra thermostat and / or time clock.
If no thermostat is required then a jumper is fitted between terminals R and W1. In this
configuration the burner will continuously fire until the 120V power supply is disconnected.
Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
RGR
Gas Valve
If any of the original wire as supplied with the appliance must be replaced, it must be replaced
with wiring material having a temperature rating of at least 220°F/105°C
9
Page 10
1.6 Vent Requirements and Details
1.6.1 Unvented units
Heaters may be installed without a vent
providing the governing building codes are met
and consideration is properly given to
possibilities of condensation on cold surfaces.
Installation shall meet the following
requirements when unvented:
Natural or mechanical means shall be
provided to supply and exhaust at least 4
CFM per 1000 BTU per hour input of
installed heaters.
Combustion gasses shall not impinge on
combustible materials.
1.6.2 Vertical venting
The heater can be installed with a vertical vent.
All vent piping should be adequately supported
from the building structure and terminated with
an approved terminal. The maximum
recommended vent length is 25ft (7.6m) with
a maximum of two elbows. All connections
should be properly sealed. refer fig 7a
1.6.3 Horizontal venting
Individual units can be vented horizontally
through side walls. Recommended terminals
are Part Numbers 111848 for 4” and 111850 for
6”.
Distances from adjacent public walkways,
adjacent buildings, openable windows and
building openings, consistent with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the
Natural Gas and Propane Installation Code,
CSA B149.1.
Maximum length of vent is 25ft (7.6m) with two
- 90° elbows.
This protects the building material from
degradation by the vent gasses.
Vent joints should be sealed and secured
according to the vent manufacturers
instructions. Should condensation occur the
vent should be shortened or insulated.
The terminal should be at least 3ft (0.91m) away
from any air intake to the building.
If the heater is equipped with ducted combustion
air, the vent terminal must be at least 3ft
(0.91m) away from the air inlet and located
higher than the inlet.
The vent terminal must be installed at a suitable
height above the ground to prevent blockage by
snow.
1.7 Fresh Air Intake
Whenever the heater is installed in locations
where airborne dust or other pollutants are
present, a fresh air supply should be ducted to
the burner.
A fresh air duct of 4”(101mm) dia. should be
installed from the fresh air to the air intake
connection on the fan housing. A flexible
jointing piece should be installed at the fan
connection with hose clamps to facilitate
expansion and contraction.
The maximum recommended length air duct is
25ft (7.6m) and the maximum number of elbows
is two. The minimum length is 18” (456mm).
The location of the fresh air duct inlet must be
where it will receive dust free clean air. An inlet
cap with bird screen must be fitted at the inlet of
the duct. If the duct inlet is located above the
roof the underside of the inlet terminal must be
at least 2ft (0.61m) above roof level and at least
10” (254mm) above any projection on the roof
within 7ft (2.1m) of the inlet. Intake pipe, fittings
and sealant are not furnished by the
manufacturer. Refer fig 7c & d.
Runs of 12ft (3.6m) or shorter can use
4” (101mm) dia vent. Runs over 12ft (3.6m)
should use 6” (152mm) vent pipe.
Any portion of vent that passes through a
combustible wall must be insulated, or use an
approved insulating thimble.
Standard vent terminals must extend at least
6” (152mm) from the wall and at least
24” (609mm) from any combustible overhang.
10
Page 11
Figure 7.a Vertical Venting.
CODE APPROVED VENT
THROUGH ROOF
Figure 7.b Horizontal Venting.
SUPPLIED BY OTHERS
4" (101mm) TO 6" (152mm) DIA.ALUMINUM ADAPTER
REQUIRED ONLY FOR 6" (152mm) DIA. VENTS
APPROVED CAT III VENT PIPE
ALUMINUM
4" (101mm) O.D. OR
6" (152mm) O.D. FLUE
SEAL JOINTS WITH
HIGH TEMPERATURE SILICONE
END OF RADIANT TUBE
REFLECTOR
ENSURE ALL JOINTS ARE
HIGH TEMPERATURE
APPROVED CAT 3 VENT PIPE
ROOF
SEAL JOINTS WITH
SEALED
SILICONE
SEAL
12'-0" (3.66m)
12'-0" (3.66m)
(APPROXIMATE
MAXIMUM DIMENSIONS)
4" (101mm) TO 6" (152mm) DIA. ALUMINUMADAPTER
REQUIRED ONLY FOR 6" (152mm) DIA. VENT
VENT CAT III ELBOW
VENT ADAPTOR ELBOW
6" (152mm)
CAT III ADAPTER
COLLAR
TERMINAL
SUPPLIED BY OTHERS
COUPLER
END OF
REFLECTOR
RADIANT
TUBE
ALUMINUM 4" (101mm) O.D. MAX IMUM LENGTH = 12'-0" (3.66m)
ALUMINUM 6" (152mm ) O.D.MAX IMUM LENGTH = 25'-0" (7.62m)
(PLUS A MAXIMUM OF 2 x 90°BENDS
ELBOWS
Figure 7.c Fresh Air Ducted Intake.
ALUMINUM 4" (101 mm) O.D. PIPE
MAX LENGTH = 2 5'- 0" ( 7.62 m) WITH 2-90° LONG RADIUS BENDS
CLAMPS
WITH TWO– 90° ELBOW S
4.25” (108mm) O.D FLEXIBLE DUCT
4" (106mm) O.D.FLEXIBLE DUCT
WALL
TERMINAL
36" (914mm) MIN CENTERS
INLET WITH
BIRD SCREEN
36" (914mm) MIN CENTERS
Figure 7.d Wall Terminal Intake Kit.
INLET WITH
BIRD SCREEN
WALL
SEAL JOINTS WITH
SILICONE OR DUCT TAPE
NOTE: The vent
terminal should be
installed so as to be in
the same atmospheric
pressure zone as the
combustion air inlet of
the appliance
Appliances can be installed up to 10,000 ft in the USA. Altitude conversion kits are available on request.
USA Natural Gas 0- 2000 ft (0-610m)
Size
“WC
60 80 100 125 150 170 200
4.2 3.5 3.5 4.1 4.2 3.4 3.5
USA Natural Gas 2001- 4000 ft (611-1220m)
Size
“WC
60 80 100 125 150 170 200
4.0 3.3 3.3 3.9 4.0 3.2 3.3
CANADA Natural Gas 0- 2000 ft (0-610m)
Size
“WC
60 80 100 125 150 170 200
4.2 3.5 3.5 4.1 4.2 3.4 3.5
USA LP Gas 0- 2000 ft (0-610m)
Size
“WC
60 80 100 125 150 170 200
6.0 5.2 8.2 6.6 7.0 5.7 N/A
USA LP Gas 2001- 4000 ft (611-1220m)
Size
“WC
60 80 100 125 150 170 200
5.8 5.0 8.0 6.4 6.8 N/A
CANADA LP Gas 0- 2000 ft (0-610m)
Size
“WC
60 80 100 125 150 170 200
6.0 5.2 8.2 6.6 7.0 5.7 N/A
CANADA Natural Gas 2001- 4500 ft (611-1370m)
Size
“WC
60 80 100 125 150 170 200
4.0 3.3 3.3 3.9 4.0 3.2 3.3
12
CANADA LP Gas 2001- 4500 ft (611-1370m)
Size
“WC
60 80 100 125 150 170 200
N/A
5.8 5.0 8.0 6.4 6.8 N/A
Page 13
Technical Details continued
USA & CANADA Natural Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate
Part No.
Fan Type
Fan Orifice
Part No.
Injector
Part No.
Pressure Switch
Part No.
60 80 100 125 150 170 200
269954 269955 269943 269944 269945 269946 269946
270476
269923 269922 269923 269927 269926 266930 269938
270400 270402 270404 270406 270408 270409 270410
270386 270387
USA & CANADA LP Gas 0- 2000 ft (0-610m)
Size
Burner Orifice Plate
Part No.
Fan Type
Fan Orifice
Part No.
Injector
Part No.
Pressure Switch
Part No.
60 80 100 125 150 170 200
269948 269949 269950 269951 269952 269953
270476 270475
269925 269925 269928 266931 269933 269937
270398 270399 270399 270400 270401 270403
270386
270475
N/A
13
Page 14
Technical Details continued
U Tube Straight Tube
MODEL
U20 U40 U60 U80 S20 S30 S40 S50 S60 S70 S80
60
80
100
125
150
170
200
● ●
● ● ●
● ● ● ● ●
●● ● ●
●●
● ● ●
●●● ● ● ●
●●● ● ● ●
●●● ● ● ●
MODEL
60
80
100
125
150
170
Tube Type Material
Calcoat™ Mild Steel
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 10 (3.0)
TUBE 1 REMAINDER 15 (4.6)
TUBE 1 REMAINDER 20 (6.1)
TUBE 1 REMAINDER 20 (6.1)
TUBE 1 & 2 REMAINDER 25 (7.6)
Min. Distance to
Bend ft (m)
200
TUBE 1 & 2 REMAINDER 25 (7.6)
Options * Not available on LP Gas
1 All standard units fitted with unvented vent, natural gas and aluminized steel reflectors.
2 1 off 180° bend (U) or upto 2 off 90° bends (L) can be fitted at no less than 50% of the total heater length.
3 4” (101mm) or 6” (152mm) vent terminal.
4 Combustion air kit.
5 Reflector end caps.
6 Altitude conversion kit.
7 Propane and propane altitude conversion kit.
14
Page 15
2. Assembly Instructions.
PLEASE READ this section prior to
assembly to familiarize yourself with the
components and tools you require at the
various stages of assembly. Carefully open the
packaging and check the contents against the
parts and check list.
The manufacturer reserves the right to alter
specifications without prior notice.
2.1 Tools Required.
The following tools and equipment are advisable
to complete the tasks laid out in this manual.
Saw
Horses
Cordless
Drill
Leather
Faced
Gloves
5/16”
Drive
Please ensure that all packaging is
disposed of in a safe environmentally
friendly way.
For your own safety we recommend the
use of safety boots and leather faced
gloves when handling sharp or heavy items. The
use of protective eye wear is also
recommended.
Suitable alternative tools may be used.
Phillips
Screwdriver
3/16” (5mm)
5/32” (4mm)
Allen
wrench
Wrench
Set
Tape
Measure
2.2 Assembly Notes.
2.2.3 Brackets
Please read these assembly notes in
conjunction with the correct assembly
drawings (figs 9 to 19).
2.2.1 Tubes
There can be four types of brackets supplied
with these heaters:
Type ‘H’ are suspension brackets with
Each heating unit has two types of emitter tube.
For details of the tube types please refer to the
table (page 13 of this instruction manual).
Identify and position tubes on saw horses. For
aesthetics it is advisable to position all tube seams facing down. Position coupling
fastener so that these cannot be seen from
beneath the heater.
Mark out the position of the bracket centers
from the dimensions shown on the assemblers'
drawings.
Turbulators: Ensure that the correct
Type ‘G’ are suspension brackets with
turbulator or burner insert is fitted, as this could
void your warranty if they are incorrectly fitted
or omitted when necessary.
2.2.2 Turbulators (where fitted)
Insert turbulator into correct tube
as indicated in the assembly
drawings.
tube straps.
"A"
VIEW ON "A"
no tube straps.
15
Page 16
Type ‘F’ are fixed reflector brackets.
2 x SCREWS TIGHTENED TO FIX REFLECTOR
Type ‘S’ are sliding reflector brackets.
2.2.4 Couplers
The couplers are used for joining radiant tubes
and U or L bends.
Slide the coupler over the tube ensuring that the
screw stop has butted up to the tube ends.
Using the 9/16” wrench to tighten the bolts.
At this point raise the tube assembly into
position and suspend from previously fixed
chains (Working Load 100lb). Longer tube
assemblies may be raised in more than one
sub-assembly with final tube connection
made in the air.
LEAVE 1/8" MIN. GAP TO ALLOW REFLECTOR TO SLIDE
Slip the suspension brackets onto the tube
assembly. The fixed suspension point ’H’
shown on the drawings are adjacent to the
burner and secures the first suspension bracket
to the tube with a tube strap. All other
suspension brackets ’G’ shown on the
drawings, have floating suspension points.
Reflectors are fixed at point ’F’ with a reflector
support bracket and reflectors are held in
position with fixing screws. Fixed and sliding
joints alternate along the heater at the spacings
indicated on the individual heater assembly
sheets.
DO NOT OVERTIGHTEN.
Moving between the four bolts, tighten each
ensuring that equal pressure is applied to each
bolt in turn. Complete assembly by drilling and
screwing self tapping retention zip screws.
2.2.5 Reflectors.
After removing the protective plastic coating
(if fitted), slip the reflectors through the hanger
brackets until they overlap each other.
All reflectors must be positioned/
attached to the brackets exactly as
detailed in the assembly drawings.
The first and second reflector are fixed at the
point F by a type F reflector support bracket and
are held in place by tightening the fixing screws.
Each subsequent reflector must
OVERLAP the previous one as shown
below and to a distance as indicated by
their individual assembly sheets.
Alternate fixings of further reflectors by type S
and type F reflector brackets and space as
indicated by individual assembly sheets.
Reflector support bracket assemblies
are fitted at each reflector joint, with the
clamp screws adjusted so that reflectors
are fixed together.
16
Page 17
BURNER
ASSEMBLY
H
F
REFLECTORS
S
F
Typical usage of optional bend kits:
End Cap
2.2.6 End Caps (optional)
Position an end cap beneath the reflector
profile (where required) with the end cap
flanges facing inwards. Fasten to reflector
using the four ’Z’ clips.
2.2.7 Bend(s) (where fitted)
The heater can be installed with 1 or 2 90°
bends or a 180° U bend.
Slide the bend into the open end of the
coupler ensuring that the screw stop has butted
up to the tube ends. Refer to 2.2.4 for
fastening.
2.2.8 Burner/Fan Assembly.
Slide the burner assembly onto the open tube
end, ensuring it is fully engaged. Secure with
set screws.
For the purpose of unvented applications, a 4”
90° elbow should be used on the terminating
end of the radiant tube sections. This elbow
should be turned with the outlet facing either
side.
Connect Gas and Electrical supplies as
described in sections 1.4 and 1.5.
2.2.9 Detailed Assembly Drawings
The following pages show the technical
dimensional details of the range of heaters.
Please note the heater type, length and
reference number from the delivery/advice note
before identifying the correct model drawing.
Corner reflector
End Caps
Corner reflectors (optional)
16” crs
Corner reflectors kit
U Bend
End Caps
90° Bend
90° Elbow
15”
17
Page 18
S20
S30
S40
S50
S60
S70
S80
Figure . 8. Possible Heater Orientations
U20
U40
U60
Bends must be fitted at a distance of at
least 50% of the total heat exchanger
e.g. for a 60ft long heater, the closest to
the burner a bend can be is 30ft.
U80
18
Page 19
Figure 9. Heater Assembly: Model Linear 60-S20 and 80-S20.
END
CAPS
GH
(OPTIONAL)
6"-9" REFLECTOR OVERLAP
S
TURBULATOR
(SEE DETAIL)
TURBULATOR DETAIL PT. NO. 270495
NOTE: FOR MODEL 60/80 LP GAS ONLY
NOTE: FOR MODEL 80 NAT GAS ONLY
BURNER INSERT DETAIL PT. NO. 270489
2" MINIMUM
L
C
F
STANDARD 4" COUPLER
REFLECTOR OVERLAP
G
21'6½" NOMINAL OVERALL ASSEMBLED LENGTH
10' 3" REFLECTORS TYPICAL OF 2
SUSPENSION POINTS
DISTANCE BETWEEN
NO TO EXCEED 12'
CAPS
END
(OPTIONAL)
BURNER
COUPLER
SF
TUBE & REFLECTOR SUSPENSION BRACKET
DETAIL
2 x SCREWS MIN 1/8" GAP TO
BOLT
NUT &
SUPPLIED
REFLECTOR
HG
DETAIL
TUBE
RADIANT
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
4"
6"
SUSPENSION
12.6" ref
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
STRAP
2 x SCREWS TIGHTEN TO
ALLOW REFLECTOR TO SLIDE
FIX REFLECTOR
DETAIL
SLIDING REFLECTOR BRACKET
DETAIL
FIXED REFLECTOR BRACKET
19
Page 20
Figure 10. Heater Assembly: Model Linear 60-S30, 80-S30 and 100-S30.
END
CAPS
(OPTIONAL)
6" REFLECTOR OVERLAP
SF
GGH
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
COUPLER
2" MINIMUM
L
C
STANDARD 4" COUPLER
REFLECTOR OVERLAP
6" REFLECTOR OVERLAP
F
31'6½" NOMINAL OVERALL ASSEMBLED LENGTH
G
DISTANCE BETWEEN
COUPLER
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
TUBE
STRAP
SUSPENSION POINTS
10' 3" REFLECTORS TYPICAL OF 3
NO TO EXCEED 12'
REFLECTOR
VIEW ON "A"
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
G
DETAIL
H
S
DETAIL
ALLOW REFLECTOR TO SLIDE
2 x SCREWS MIN 1/8" GAP TO
SLIDING REFLECTOR BRACKET
BOLT
NUT &
SUPPLIED
REFLECTOR
F
CAPS
END
(OPTIONAL)
BURNER
DETAIL
4"
6"
12.6" ref
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
TUBE
STRAP
DETAIL
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
FIXED REFLECTOR BRACKET
20
Page 21
Figure 11. Heater Assembly: Model Linear 60-S40, 80-S40, 100-S40, 125-S40 and 150-S40.
END
CAPS
(OPTIONAL)
3" REFLECTOR
OVERLAP
F
G
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
41'6½" NOMINAL OVERALL ASSEMBLED LENGTH
GGH
G
DISTANCE BETWEEN
SUSPENSION POINTS
NO TO EXCEED 12'
6" REFLECTOR
OVERLAP
SS
L
C
STANDARD 4" COUPLER
2" MINIMUM
REFLECTOR OVERLAP
COUPLERCOUPLER
6" REFLECTOR
OVERLAP
TYPICAL OF 4
10' 3" REFLECTORS
F
DETAIL
2 x SCREWS MIN 1/8" GAP TO
*(HIGH TEMP COUPLER
COUPLER
MODEL 125/150 )
TUBE
STRAP
(SEE DETAIL)
BURNER INSERT
NAT GAS ONLY
4"
6"
REFLECTOR
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
REFLECTOR
HG
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
CAPS
END
(OPTIONAL)
BURNER
SUSPENSION
21
BRACKET
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
DETAIL
FIXED REFLECTOR BRACKET
DETAIL
TUBE
RADIANT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
SUPPLIED
NUT & BOLT
TUBE
STRAP
Page 22
Figure 12. Heater Assembly: Model Linear 100-S50, 125-S50, 150-S50, 170-S50, and 200-S50
END
CAPS
(OPTIONAL)
51'6½" NOMINAL OVERALL ASSEMBLED LENGTH
3" REFLECTOR
OVERLAP
G
S
COUPLERCOUPLER
F
3" REFLECTOR
OVERLAP
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODEL 100 NAT GAS ONLY
G
2" MINIMUM
L
C
SF
STANDARD 4" COUPLER
6" REFLECTOR
OVERLAP
REFLECTOR OVERLAP
GGH
*(HIGH TEMP
COUPLER
COUPLER
MODEL 170 & 200)
SF
F
6" REFLECTOR
OVERLAP
G
* (HIGH TEMP
COUPLER
COUPLER
MODELS 125,
150, 170 & 200)
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
POINTS NOT TO
EXCEED 12'
END
10' 3" REFLECTORS
CAPS
(OPTIONAL)
SUSPENSION
DISTANCE BETWEEN
TYPICAL OF 5
BURNER
TUBE
STRAP
4"
(SEE DETAIL)
BURNER INSERT
6"
NAT GAS ONLY
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
HG
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
DETAIL
2 x SCREWS TIGHTEN TO
TUBE
RADIANT
TUBE
STRAP
FIX REFLECTOR
FIXED REFLECTOR BRACKET
22
Page 23
Figure 13. Heater Assembly: Model Linear 125-S60, 150-S60, 170-S60 and 200-S60
END
CAPS
(OPTIONAL)
3" OVERLAP
S
F
GGH
COUPLERCOUPLER
3" OVERLAP
S
GGG
COUPLER
3" OVERLAP
F
L
C
2" MINIMUM
STANDARD 4" COUPLER
6" OVERLAP
61'6½" NOMINAL OVERALL ASSEMBLED LENGTH
S
REFLECTOR OVERLAP
SF
2 x SCREWS MIN 1/8" GAP TO
2 x SCREWS TIGHTE N TO
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
DETAIL
*(HIGH TEMP
COUPLER
COUPLER
MODELS 170 & 200)
6" OVERLAP
G
SUSPENSION
DISTANCE BETWEEN
POINTS NOT TO
EXCEED 12'
TYPICAL OF 6
10' 3" REFL'S
F
TUBE
STRAP
REFLECTOR
*HT COUPLER
4"
6"
"A"
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
REFLECTOR
HG
DETAIL
TUBE
RADIANT
CAPS
END
(OPTIONAL)
SUSPENSION
BRACKET
TUBE
BURNER
RADIANT
SUPPLIED
NUT & BOLT
FIRST SUSPENSION POINT TUBE STRAP
TUBE
STRAP
23
Page 24
Figure 14. Heater Assembly: Model Linear 150-S70, 170-S70 and 200-S70.
END
CAPS
(OPTIONAL)
F
3" OVERLAP
S
GGH
3" OVERLAP
F
G
3" OVERLAP
GGG
3" OVERLAP
S
2" MINIMUM
L
COUPLERCOUPLERCOUPLERCOUPLER
F
STANDARD 4" COUPLER
C
REFLECTOR OVERLAP
71'6½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
6" OVERLAP
6" OVERLAP
G
SUSPENSION
POINTS NOT TO
EXCEED 12'
TYPICAL OF 7
10' 3" REFL'S
CAPS
END
(OPTIONAL)
S
DETAIL
2 x SCREWS MIN 1/8" GAP TO
200)
*(HT COUPLERS
COUPLER
MODELS 170 &
F
TUBE
STRAP
REFLECTOR
HT COUPLER
4"
6"
SUSPENSION
BRACKET
BURNER
SUPPLIED
"A"
TUBE
RADIANT
NUT & BOLT
TUBE & REFLECTOR SUSPENSION BRACKET
BOLT
NUT &
SUPPLIED
VIEW ON "A"
FIRST SUSPENSION POINT TUBE STRAP
REFLECTOR
HG
DETAIL
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
24
Page 25
Figure 15. Heater Assembly: Model Linear 170-S80 and 200-S80
END
CAPS
(OPTIONAL)
S
3" OVERLAP
F
G
3" OVERLAP
S
G
3" OVERLAP
F
GGH
3" OVERLAP
GGG
S
L
C
STANDARD 4" COUPLER
2" MINIMUM
REFLECTOR OVERLAP
3" OVERLAP
F
81'6½" NOMINAL OVERALL ASSEMBLED LENGTH
COUPLER COUPLER COUPLER COUPLER COUPLER
6" OVERLAP
S
DETAIL
2 x SCREWS MIN 1/8" GAP TO
SF
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
TUBE & REFLECTOR SUSPENSION BRACKET
HT COUPLER
6" OVERLAP
F
TUBE
STRAP
NUT &
BOLT
SUPPLIED
REFLECTOR
G
HT COUPLER
4"
TYPICAL OF 8
SUSPENSION POINTS
DISTANCE BETWEEN
NO TO EXCEED 12'
10' 3" REFL'S
CAPS
END
(OPTIONAL)
6"
SUSPENSION
BRACKET
SUPPLIED
BURNER
NUT & BOLT
VIEW ON "A"
"A"
FIRST SUSPENSION POINT TUBE STRAP
TUBE
RADIANT
REFLECTOR
HG
2 x SCREWS TIGHTEN TO
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
DETAIL
TUBE
RADIANT
TUBE
STRAP
25
Page 26
Figure 16. Heater Assembly: Model U tube 60-U20 and 80-U20.
3' 3"
12'1½" NOMINAL OVERALL ASSEMBLED LENGTH
F
G
COUPLER
10' 3" REFLECTORS TYPICAL OF 2
F
GH
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODEL 80 NAT GAS ONLY
2" MINIMUM
BURNER INSERT
DISTANCE BETWEEN
(SEE DETAIL)
SUSPENSION POINTS
NAT GAS ONLY
STANDARD 4" COUPLER
DETAIL
NO TO EXCEED 12'
L
C
REFLECTOR OVERLAP
G
CAPS
END
(OPTIONAL)
BURNER
TUBE & REFLECTOR SUSPE NSION BRACKET
4"
6"
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
HG
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
F
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
26
Page 27
Figure 17. Heater Assembly: Model U tube 60-U40, 80-U40, 100-U40, 125-U40 and 150-U40.
3' 3"
S
GGG
COUPLER
FS
6"-9" REFLECTOR OVERLAPS
G
BURNER INSERT DETAIL PT. NO. 270489
NOTE: FOR MODELS 80/100 NAT GAS ONLY
2" MINIMUM
L
C
F
STANDARD 4" COUPLER
REFLECTOR OVERLAP
GH
22'1½" NOMINAL OVERALL ASSEMBLED LENGTH
SF
DISTANCE BETWEEN
END
SUSPENSION POINTS
CAPS
DETAIL
*(HIGH TEMP
COUPLER
COUPLER
MODEL 125/150 )
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFL ECTOR SUSPENSION BRACKET
(SEE DETAIL)
NAT GAS ONLY
BURNER INSERT
NO TO EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 4
4"
(OPTIONAL)
BURNER
6"
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
HG
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
ALLOW REFLECTOR TO SLIDE
FIX REFLECTOR
DETAIL
SLIDING REFLECTOR BRACKET
DETAIL
FIXED REFLECTOR BRACKET
27
Page 28
Figure 18. Heater Assembly: Model U tube 125-U60, 150-U60, 170-U60 and 200 -U60
3' 3"
F
G
S
6" REFLECTOR OVERLAPS
G
GGH
S
G
*(HIGH TEMP
COUPLER
COUPLER
MODELS 170 &
2" MINIMUM
200)
STANDARD 4" COUPLER
L
C
REFLECTOR OVERLAP
32'1½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
G
G
END
FF
SUSPENSION POINTS
CAPS
NO TO EXCEED 12'
(OPTIONAL)
6"-9" REFLECTOR OVERLAPS
10' 3" REFLECTORS TYPICAL OF 6
BURNER
F
SF
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
HT COUPLER
TUBE
STRAP
REFLECTOR
VIEW ON "A"
"A"
4"
6"
SUSPENSION
BRACKET
TUBE
RADIANT
SUPPLIED
NUT & BOLT
HG
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
BOLT
NUT &
SUPPLIED
REFLECTOR
TUBE
RADIANT
TUBE
STRAP
2 x SCREWS TIGHTEN TO
DETAIL
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
DETAIL
FIX REFLECTOR
FIXED REFLECTOR BRACKET
28
Page 29
Figure 19. Heater Assembly: Model U tube 170-U80 and 200-U80
3' 3"
S
GGG
F
3" REFLECTOR OVERLAPS
G
S
6" REFLECTOR OVERLAPS
G
GGH
F
G
COUPLER
S
2" MINIMUM
G
STANDARD 4" COUPLER
L
C
REFLECTOR OVERLAP
42'1½" NOMINAL OVERALL ASSEMBLED LENGTH
DISTANCE BETWEEN
END
SUSPENSION POINTS NO TO
FS
CAPS
HT COUPLER
6"-9" REFLECTOR OVERLAPS
EXCEED 12'
10' 3" REFLECTORS TYPICAL OF 8
(OPTIONAL)
BURNER
F
DETAIL
2 x SCREWS MIN 1/8" GAP TO
TUBE & REFLECTOR SUSPENSION BRACKET
TUBE
STRAP
REFLECTOR
HT COUPLER
SUSPENSION
4"
6"
BRACKET
SUPPLIED
NUT & BOLT
VIEW ON "A"
"A"
TUBE
RADIANT
HG
DETAIL
FIRST SUSPENSION POINT TUBE STRAP
REFLECTOR
RADIANT
SUPPLIED
TUBE
BOLT
NUT &
TUBE
STRAP
ALLOW REFLECTOR TO SLIDE
SLIDING REFLECTOR BRACKET
2 x SCREWS TIGHTEN TO
FIX REFLECTOR
FIXED REFLECTOR BRACKET
SF
DETAIL
DETAIL
29
Page 30
3. Start Up Instructions.
These appliances should be commissioned by a qualified mechanical contractor.
3.1 Tools Required.
The following tools and equipment are advisable
to complete the tasks laid out in this manual.
Leather
Faced
Gloves
Phillips
Screwdriver
Suitable alternative tools may be used.
Small Flat
Head
Screwdriver
Large Adjustable
Wrenches for fitting
Of Gas Flex.
½”
Wrench
5/32” (4mm)
Allen
Wrench
3.2 Start Up procedure
Inspect installation and ensure that it has been
carried out in accordance with these
instructions. Remove burner and inspect the
electrode assemblies ensuring these are
securely fixed and all electrical connections
securely made.
Re-fit the burner ensuring that it is correctly
positioned and the screws are fully tightened.
Ensure that electrical and gas supplies are
isolated.
The gas supply should be purged and tested for
soundness in accordance with local and
National Safety codes.
Open isolating gas valve and test gas
connections for soundness using soap solution.
Open the control housing door by unscrewing
the securing screw. Ensure all internal
components are securely fixed and all
connections securely made.
Open the manual gas valve outside the control
housing
Switch on the electrical supply to start the
heater and observe the correct start up
sequence. Ensure that the setting of any time
switch and thermostat are such that the heating
system will be required to operate.
The fan will start to run and the ‘power on’ lamp
will illuminate. Safe-start checks are carried out
automatically.
After the fan has run up to full speed and a satisfactory pressure condition has been
established, the ignition sequence will
commence. The spark ignition will be energized
producing a spark at the ignition electrode. The
gas solenoid valve will at the same time be
energized and the ‘burner on’ lamp will
illuminate. If the ignition is successful, the flame
is detected by the flame sensing probe and the
‘burner on’ lamp will remain on.
If ignition is unsuccessful the gas valve will close
and the spark ignition de-energized after
approximately 15 seconds.
For approximately 30 seconds the fan will purge
the system then re-ignition will be attempted.
After 2 further attempts at ignition the control
unit will ‘lock-out’, the ‘power on’ lamp will
remain illuminated and the fan will run for 120
seconds and then stop.
To reset after ‘lockout’ switch off the power
supply to the system and wait 2 minutes. Then
turn the power on. If repeated ‘lockout’ occurs,
investigate the cause.
Set burner gas pressure as follows:
Switch off the power supply to the heating
system.
Connect a ‘U’ tube manometer to the pressure
test point provided on the combination gas
control valve.
Remove the cover from the pressure regulator
revealing the adjustable screw.
Manometer
Multimeter
30
Page 31
Start the heater and using a suitable
screwdriver adjust the pressure regulator,
turning the screw clockwise to increase the
pressure or counter-clockwise to decrease the
pressure.
Set the pressure to appropriate inches w.c.
from the table of gas pressures and orifice plate
dimensions for correct heater description.
Switch off the power supply to the heating
system. Disconnect ‘U’ tube manometer, then
secure screw in pressure test nipple.
Check the operation of the flame safeguard
equipment as follows:
With the heater running normally, switch off the
gas supply at the shut off valve. The heater
should attempt to relight. If the gas valve has
been left off, ‘lock-out’ should occur. This is
indicated by the ‘power on’ lamp being
illuminated and fan running, but the ‘burner on’
lamp being off.
Check the operation of the pressure proving
switch as follows:
With the heater running normally, pull off the
silicone rubber tube connecting the vacuum
switch to the combustion chamber. Within 4
seconds the burner should shut off.
Then replace the tube securely and observe
that the heater proceeds to ignite in the normal
way.
Close the controls door securing it with the
screw.
31
Page 32
Commissioning chart
Check installation has
been carried out to these
instructions.
Remove burner from tube and inspect burner head.
Replace burner on tube
and secure.
Check thermostat is set to
maximum and is calling
for heat.
Ensure gas and electricity
supplies are isolated.
(See servicing instructions)
Reconnect gas hose.
Open manual valve.
Check soundness.
Switch on electrical supply.
The red lamp should now
be illuminated. If restarting
heater a delay of 15sec
should be allowed.
Disconnect gas hose from
burner
Open control housing and
check that all components
are securely fastened.
The heater should now
run through its start up
sequence and ignite.
Check gas pressure.
Leave the instructions
with a responsible person.
A successful ignition is indicated
by the amber light illuminating
and remaining illuminated.
Close control housing
Turn off power and check
that all components are
securely fastened.
NO
Has the
burner lit?
YES
Check operation on flame failure.
Check gas pressure.
Check operation of
air pressure switch.
32
Page 33
4. Servicing Instructions.
These appliances should be serviced annually by a competent person to ensure safe
and efficient operation. In mildly dusty or polluted conditions more frequent
servicing may be required. Servicing work should be carried out by a qualified
mechanical contractor.
4.1 Tools Required.
The following tools and equipment are advisable
to complete the tasks laid out in this manual.
Leather
Faced
Gloves
½”
Wrench
Phillips
Screwdriver
5/32”
(4mm)
Allen
4.2 Burner Description.
Figure 20. Burner breakdown
K
A
Suitable alternative tools may be used.
Small Flat
Head
Screwdriver
Manometer
Multimeter
J
H
Large Adjustable
wrenches for fitting
of Gas Flex.
Soft
Brush
L
F
G
I
A Ignition Controller
B Gas Valve
C Power On Red LED
D Burner On Yellow LED
F Burner Tube
G Burner head
H Injector
I Igniter Assembly
Q
P
M
J Jet Carrier
K Combustion Fan
L Pressure Switch
M Gaskets
N Transformer
P Burner Orifice Plate
Q Flame Plate (not shown)
D
C
N
Note: Cables Omitted
For Clarity
B
Page 34
4.3 Burner Removal
Step 1: Isolate power and gas supplies.
Step 2: Unplug the power connectors.
Step 3: Detach the gas supply as shown be-
low, taking care to support the burner
connection.
in a safe area to prevent the burner or
components attached to the burner from falling
to the ground.
4.4 Burner Gas Injector Servicing
Step 1.a: Remove the burner support casting
and gasket.
Step 4: If fresh air is connected, slacken
hose clip and remove the flexible hose from the
burner.
Step 5: loosen the set screw on the burner
support casting to enable the burner to be
removed from the radiant tube.
Step 6: Remove the burner and position
Step 1.b: The burner head assembly can be
disconnected by separating the connectors of
the ignition lead, ground lead assembly and
removing the pressure switch silicon tube.
Step 2: The gas injector can be inspected and
replaced if contaminated or blocked.
When replacing the gas injector ensure
approved thread sealant is used.
34
Page 35
Step 3: Reconnect ignition leads, ground lead
and silicone tube to test nipple. Refit gasket
and support casting.
4.5 Burner Head and Electrode Servicing
Step 1: Check the pepper pot burner head for
contamination. If necessary this can be
removed, see below. This can be cleaned
together with the Inside of the burner head.
the two screws and separating the igniter lead
connectors.
Step 4: Refit the electrode assembly and en-
sure the connections are secure to prevent incorrect sparking .
Step 5: Check the positions and spark gap as
shown below.
Step 6: The burner assembly is ready to refit
after servicing the combustion fan and the
radiant tube assembly.
4.6 Combustion Fan Assembly
Step 1: If ducted air is fitted, loosen hose clamp
and remove the flexible hose from the fan.
Step 2: The pepper pot burner head can be
replaced ensuring the 5 holes on the outer ring
are aligned alongside the probes.
Step 3: The condition of the igniter assembly
can be checked for deterioration. However, we
advise replacement at each service to ensure
continued reliability. Detach the electrode
assembly from the burner head by removing
35
Page 36
Step 2: Remove fan retaining screws and
unplug from burner box.
Step 3: The combustion fan can now be
detached.
4.8 Reflector Servicing
The condition of the reflectors should be
noted. If necessary the reflectors can be
cleaned with a mild detergent. This can
significantly improve the efficiency of the
appliance.
4.9 Cleaning of Vent
Inspect the fresh air inlet duct and vent to
ensure they are free from any blockage or
obstruction. The air inlet terminal and vent
terminal should be inspected to ensure they
are not liable to obstruction.
4.10 Re-commissioning After Service
After servicing has been undertaken, it will be
necessary to re-commission the heater as
detailed in Section 3 of these instructions.
2. Air inlet, outlet, and emitter tubes for obstructions.
3. Pressure switch operation.
4. Supply voltage 120VAC / 60Hz
5. Transformer.
6. Ignition Controller.
38
Page 39
To aid the troubleshooting process, the UT controller has a LED flash code diagnostic sequence:
Steady Off No control power
Steady On Power applied, control OK
1 Flash Combustion pressure switch open with blower on
2 Flashes Combustion pressure switch closed with blower off
3 Flashes Lockout from the three ignition trials
4 Flashes Lockout from five flame losses
5 Flashes Control hardware fault detected
6 Flashes Lockout from five pressure switch losses
39
Page 40
7. Replacing Parts.
Turn off gas and any electrical supplies to
the heater before starting repair work.
7.1 Burner Controller Replacement
Step 1: Loosen screw in right hand burner
access door and open.
Step 2: Disconnect burner controller from the
wiring harness.
Step 3: Disconnect the spark lead from burner
controller.
7.2 Air Pressure Switch Replacement
Step 1: Open left hand door. Disconnect the two
silicone tubes from the pressure switch.
Step 2: Remove the two screws shown below.
Step 4: Remove the two screws attaching the
controller to the burner door and remove.
Step 5: Attach new burner controller.
Step 6: Reattach leads.
Step 7: Test product and close access door.
Step 3: Remove electrical connections. The air
pressure switch can now be removed.
Step 4: Fit the new air pressure switch ensuring
the silicon tubes are connected as shown
below.
Step 5: Test product and close access doors.
Page 41
7.3 Gas Valve Replacement
Step 1: Remove the burner assembly as
described in the servicing section.
Step 2: Open the right hand access door and
detach the burner controller from the wiring
harness.
Step 3: Open the left hand access door and
detach the silicon hoses from the air pressure
switch.
Step 6: Detach the two screws securing the
front of the gas valve.
Step 7: Remove the four screws (arrowed),
holding the rear burner plate in position.
Step 4: Remove the 4 screws holding the
burner head onto the burner assembly.
Step 5: The burner head can now be detached
by disconnecting the silicon tube and the burner
head wiring.
Step 8: Remove the rear plate.
Step 9: The jet carrier, gas inlet, and wiring
harness can now be detached from the gas
valve.
Step 10: The two screws retaining the gas valve
can now be removed.
Step 11: The gas valve can now be replaced.
Step 12: Reattach all components.
Step 13: Set pressures and test for reliable
burner performance.
Step 14: Close access door.
Page 42
7.4 Optional Extra Kits.
180° U-Bend Kit
(1 Off)
90° Elbow Kit
Kit (1Pair)
Aluminized
Steel End Cap
Air inlet Kit
Combustion
Conversion Kit
Propane Gas &
Propane Altitude
270630 270619
Conversion Kit
Natural Gas Altitude
270613 270611 270277 270276
270630 270620
270631 270621
270632 270622
270633 270623
270634 270627*
270635 270628**
60
MODEL
42
80
100
125
150
170
200
* Burner de-rated when converted to propane
** Burner de-rated when converted to propane. Not for use at altitude.
Page 43
Notes.
43
Page 44
8. User & Operating Instructions.
Radiant tubular infrared heaters are designed for overhead heating of industrial and commercial
buildings. Individual heating units are suspended from the roof.
1. This appliance must only be installed by qualified installer in accordance with
the requirements of local and National Codes.
2. This appliance must be grounded in accordance with the National Electrical
Code ANSI/NFPA No.70 or Canadian Codes.
3. Never rest anything, especially ladders against the heaters.
8.1 To Start the Heater
1. First ensure that the gas supply to each
heater is turned on by opening the main
gas shut off valve.
2. Ensure that the setting of any time switch
and thermostat are such that the heating
system will be required to operate.
3. Switch on the electricity supply to the
heater. The fan will start, the ‘power on’
light on the burner will illuminate and
ignition commence.
4. Ignition will occur.
5. If ignition is unsuccessful the gas valve will
close and the spark ignition de-energize
after approximately 15 seconds. For
approximately 30 seconds the fan will
purge the system then re-ignition will be
attempted. After 3 attempts at ignition the
control unit will ‘lock-out’, the ‘power on’
lamp will remain illuminated and the fan will
continue to run. To reset after ‘lockout’,
switch off the power supply to the heater
and wait 5 minutes. Then turn the power on.
If repeated ‘lockout’ occurs investigate the
cause.
8.2. To Switch Off Heater
Switch off electrical supply to the heater.
The burner will stop and the fan will shut off.
8.3. Servicing
To ensure continued, efficient and safe
operation it is recommended that the heater
be serviced regularly by a qualified person
every year in normal working environments,
but in exceptionally dusty or polluted
environments more frequent servicing may
be needed.