Reznor VCS100 Installation Manual

INSTALLATION / OPERATION / MAINTENANCE
Applies to: Model VCS/VCT 120V 60Hz
Low-Intensity Infrared Heater
Model VCS/VCT (Harsh Environment )
On/Off & High/Low Burner/Control Box
with 20 - 80 ft Tube/Reflector Length
Doc No 700102 (06-15), Page
Part No. 270685
Introduction.
Welcome to the new range of powered Harsh Environment infrared heaters. Local regulations may vary and it is the installer’s responsibility to ensure that such regulations are satisfied.
All installation, assembly, commissioning and service procedures must be carried out by suitable qualified competent persons and conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the National Gas and Propane Installation Code CSA B149.1.
When assembling, installing, commissioning
Document Index.
1 Installation Requirements
1.1 Health & Safety
1.2 Heater Suspension
1.3 Clearance to Combustibles
1.4 Gas Connection & Supply Details
1.5 Electrical Connections
1.5.1 Multiple Burner Detials
1.5.2 Multiple Burners via Ind Power Source
1.6 Ventilation Requirements
1.6.1 Unvented Units
1.6.2 Vertical Venting
1.6.3 Horizontal Venting
1.7 Fresh Air Intake
1.8 Technical Details
2 Assembly Instructions
2.1 Tools Required
2.2 Assembly Notes
2.2.1 Emitter Tubes
2.2.2 Turbulators
2.2.3 Brackets
2.2.4 Couplers
2.2.5 Reflectors
2.2.6 End Caps (optional)
2.2.7 Bends (where required)
2.2.8 Burner/Fan Assembly
and servicing is undertaken on radiant tube heaters specified in these instructions, due care and attention is required to ensure that working at height regulations are adhered to
PLEASE READ this document prior to
installation to familiarize yourself with the components and tools you require at the various stages of assembly.
All dimensions shown are in inches unless otherwise stated.
The manufacturer reserves the right to alter specifications without prior notice.
2.2.9 Detailed Assembly Drawings
3 Start Up Instructions
3.1 Tools Required
3.2 Start up procedure
4 Servicing Instructions
4.1 Tools Required
4.2 Burner Description
4.3 Burner Removal
4.4 Burner Gas Injector Servicing
4.5 Burner Head and Electrode Servicing
4.6 Combustion Fan Assembly
4.7 Emitter Tube Servicing
4.8 Reflector Servicing
4.9 Cleaning of Vent
4.10 Re-commissioning after Service
5 Troubleshooting Guide 6 Replacing Parts
6.1 Burner Controller Replacement
6.2 Air Pressure Switch Replacement
6.3 Gas Valve Replacement
7 User and Operating Instructions
7.1 To Start Heater
7.2 To Switch Off Heater
7.3 Servicing
1. Installation Requirements.
1.1 Health and Safety
A. Heater is intended for heating outdoor or
non-residential indoor spaces and should only be installed where flammable gases or vapours are not present.
B. Heaters can be suspended horizontally or at
any angle along the axis of the emitter tubes but can only be rotated about the burner head 0 to 55°. See section 1.3 for clearance dimensions.
Doc No 700102 (06-15), Page 2
C. The installation must conform with local
D. The unit shall be electrically grounded in
E. The heater may be installed in aircraft
building codes or, in the absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
accordance with National Electric Code ANSI/NFPA 70 and Canadian Electrical Code CSA C22.1.
hangars in accordance with the Standard for
Aircraft Hangars, ANSI/NFPA 409 and in automotive garages when installed in accordance with the Standard for Parking Structures, ANSI/NFPA 88A, or the Standard for Repair Garages, ANSI/NFPA
88B, or the Canadian Natural Gas and Propane Installation Code, CSA B149.1,
and are so marked.Ensure that minimum clearances will be maintained to vehicles parked below the heater.
F. The standard heaters are approved for installations between 0 - 2000ft (0 - 610m) above sea level for the US and 0 - 4500 ft (1370m) above sea level for Canada. Conversion kits are available on installations above these heights in the USA.
G. Massachusetts Requirement: If the heater is being installed in the Commonwealth of Massachusetts, this unit must be installed by a licensed plumber or licenced gas fitter.
Note: Any outdoor installations must be installed with a vent cap at the inlet and
the flue end.
1.2 Heater Suspension
Attachment to the heater support lugs should
be made by D shackle. The hanging attachments to overhead steelwork etc. have to be designed and produced in accordance with sound engineering practices. They must be adequately fixed and designed to carry the whole weight of the heater. In the event of suitable roof steelwork being unavailable, additional steelwork should be fitted to enable vertical hangers to be used for suspending the heaters.
These methods are illustrated in Figure 1. If there are any doubts as to the strength or suitability of roof steelwork to which heaters are to be suspended, please refer to a Consultant, Architect or owner of the building.
It is recommended that the heater is raised to its final position once the assembly of the emitter tube/bracket/reflector has been completed. Longer tube assemblies may be raised in more than one sub-assembly with final emitter tube connection made in the air.
Ensure that the installer uses the burner roof support mounting bracket when suspending the heater. This is situated on the front of the burner. When packed the bracket is reversed and must be turned to its correct state for mounting. (ref page 22.)
WARNING:
If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which are known to the state of California to cause cancer, birth defects or other reproductive harm.
U TUBE VARIANTS
NOTE. 'S' HOOKS ARE TO
BE CLOSED UP AFTER ASSEMBLY
SUITABLE CHAIN
WORKING LOAD
LIMIT 100LB
EXHAUST
END
CHAIN
55° SUSPENSION
Figure 1. Recommended Methods of Heater Suspension.
Doc No 700102 (06-15), Page 3
BURNER
END
ON VENTED HEATERS, THE HEATER SHOULD SLOPE DOWNWARDS AWAY FROM THE BURNER AND ON UNVENTED HEATERS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. ½” FOR HORIZONTAL INSTALLATIONS AS SHOWN BELOW (DIAGRAMS EXAGGERATED FOR CLARITY)
1/2”
VENTED
1/2”
UNVENTED
1.3 Clearance to Combustibles.
Minimum clearance to combustibles are shown in Table 1 below.
IMPORTANT:
The stated clearance to combustibles represents a surface temperature of 90°F (50° C) above room temperature. Building material with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
Table 1
MODEL A A1 / A2 B B1 C1 C2 C3 D1 D2 E
Clearance to Combustibles, inches (cm)
60
74
(188)
29
(74)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
12
(31)
12
(31)
80
74
(188)
29
(74)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
12
(31)
12
(31)
15° = 72 (183) 25° = 68 (173)
100
74
(188)
35° = 61 (155) 45° = 53 (135)
32
(82)
41
(105)
20 (51) /
10* (26)*
8
(21)
22
(56)
8
(21)
16
(41)
12
(31)
55° = 43 (110)
125
150
170
74
(188)
74
(188)
86
(219)
15° = 82 (209) 25° = 78 (199)
39
(99)
39
(99)
48
(122)
47
(120)
48
(122)
48
(122)
20 (51) /
10* (26)*
20 (51) /
10* (26)*
20 (51) /
10* (26)*
8
(21)
8
(21)
11
(28)
22
(56)
22
(56)
22
(56)
20
(51)
20
(51)
20
(51)
18
(46)
18
(46)
20
(51)
12
(31)
12
(31)
12
(31)
35° = 71 (181) 45° = 61 (155)
200
* distance with end caps fitted.
86
(219)
WARNING:
55° = 50 (127)
Minimum clearance from the heater must be maintained from vehicles parked below heater. In all situations, clearances to combustibles must be
48
(122)
48
(122)
20 (51) /
10* (26)*
11
(28)
22
(56)
20
(51)
20
(51)
12
(31)
maintained. Signs should be posted in storage areas to specify maximum stacking height to maintain required clearance to combustibles. Such signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location. Refer to mounting clearance tables.
Doc No 700102 (06-15), Page 4
Figure 2 Clearance to Combustibles (Standard indoor reflectors)..
The minimum clearances to combustible materials are given in Table 1 These minimum
distances MUST be adhered to at all times. Adequate clearance MUST be provided around air openings into the combustion chamber and there MUST be suitable clearance for accessibility and for combustion / ventilating air supplies.
D2
A2
.
0° to 55°
Angled view.
Return end on
U tube heater
A1
WARNING!
combustion and ventilation air supply.
provision in the building for
Ensure that there is adequate
Installation must meet minimum
B
requirements and applicable codes.
Below
Outlet end.
heater
D1
End
B1
Side
C3
unvented
unvented
unvented
Above outlet
Above
Reflector
C2
Burner end.
B
Side
vented
Doc No 700102 (06-15), Page 5
A
End view.
C1
Above
Burner
Above
C1
Burner
E
E
Service
distance
Service
distance
1.4 Gas Connection and Supply
WARNING: Before installation, check
that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The gas connection on the heater is ½” N.P.T internal thread.
Injector sizes and manifold pressure for the burners are shown in the table 4. The gas supply piping and connections must be installed so that the minimum pressure stated is achieved.
A gas shut off valve and union should be fitted in the gas supply line close to the heater and a ” N.P.T plugged tapping, accessible for test gauge connection, provided immediately upstream of the appliance gas inlet.
It is essential to provide some flexibility in the final gas connection by use of an approved flexible gas connector. (See Fig 4.)
Take care when making a gas connection to the heater not to apply excessive
turning force to the internal controls.
Care must be taken to observe the pipe bend diameter of 12” (30cm) and pipe displacement distance of 3” (7.62cm).
The correct installation as shown will allow for approx 4” of movement due to
expansion.
Figure 3. Correct orientation of Ball Valve
Gas Flow
Gas Flow
Figure 4. Correct Installation of Flexible Gas Connection
* Connector must be certified for use on a radiant tube type infrared heater and must comply with Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 or with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas, CAN/CGA 8.1.
For heaters up to 150,000Btu/h, ½” ID x 24” long For heaters 150,000Btu/h and above, ¾” ID x 36” long NOTE: For Canada all heaters MUST use a hose 36” long (See Table 3)
Table 3
HOSE SIZE USA CANADA
3/4” CE4
CONTACT FACTORY
WARNING: FIRE OR EXPLOSION HAZARD - It is essential to provide some flexibility in
the final gas line connection by use of an approved flexible connector as shown in the
drawings. Expansion of the radiant pipe occurs with each firing cycle causing the burner to move with respect to the gas line. This can result in a gas leak producing an unsafe condition.
Doc No 700102 (06-15), Page 6
CONNECTOR MUST BE INSTALLED IN A “U” CONFIGURATION. FOR HEATERS UP
TO 150,000 BTU/H, A 24” LONG CONNECTOR OF AT LEAST ½” ID MUST BE USED. FOR HEATERS ABOVE 150,000 BTU/H, A 36” LONG CONNECTOR OF AT LEAST ¾” NOMINAL ID MUST BE USED.
Table 4 Gas Supply Pressures
Gas Type
Natural Gas LP/Propane Gas
Model VCS VCT VCS/VCT
Min Required Gas Pressure (in W.C) (60,000 TO 150,000 BTU)
Min Required Gas Pressure (in W.C) (170,000 TO 200,000 BTU)
Max Supply Pressure (in W.C)
5.0 7.0 11.0
7.0 7.0 11.0
14.0 14.0 14.0
Gas Supply Connection ½” N.P.T thread
1.5 Electrical Connections
Important: All electrical work should be done by a qualified electrician in strict accordance with the
WARNING: Before making electrical
connections, switch OFF the main electrical disconnect. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
National Electrical Code ANSI/NFPA 70 or Canadian Codes CSA C22.1.
The electrical supply to the heater is by three wires: hot (Live), neutral and ground connections.
Install in accordance with
This appliance must be electrically grounded
Supply 120V 60Hz single phase. Standard heater 0.16HP. Current rating (inductive):
1.8 amp max (models 60 - 150)
1.0 amp max (models 170 & 200)
all state & local codes.
Where alternative manufacturers controls are used, please refer to their instructions for their installation details.
Fuse: external 3 amp.
Figure 5a. External Wiring Schematic (VCS)
24V AC Single Stage
Thermostat (Ext.)
Burner 1
24V AC
Terminals
(120V AC Fan
Terminals)
BK
G
W
Doc No 700102 (06-15), Page 7
W1
F1
F2
L
E
N
R
C
E
N
BK
BL
R
120V AC
Supply
W1
RC
KEY:
BK-BLACK
BL-BLUE
R-RED
G-GREEN
W-WHITE
Notes:
Use 18/4 class 2 thermostat cable between heater and thermostat.
Max. length @ 18 Awg (0.8mm²) = 100ft.
Only one burner can operate from one thermostat as supplied.
When servicing heaters ensure the electricity supply is isolated from the mains supply.
120V AC supply is still present at each burner when the thermostat is switched off.
Figure 5b. Single and Multiple Heater Installations 120V Control (VCS)
BK
T
T
120V Thermostat
110V Thermostat
KEY: G-GREEN W-WHITE BK-BLACK
G
W
BK
Burner 1
W
BK
G
If heaters are wired using the method
shown above, a link wire must be fitted to the burner terminals as shown in the diagram opposite.
GND L2 L1 (HOT)
120V 60Hz 1 Ph Supply circuit
Other burners
other burners
Burner
R
Link
C
W1
Figure 5c. External Wiring Schematic. (VCT)
24V AC 2-Stage
Thermostat (Ext.)
Burner 1
24V AC
Terminals
(120V AC Fan
Terminals)
BK
G
W
W1
W2
F1
F2
N
R
C
E
N
L
E
BK
BL R
O
120V AC
Supply
W1 W2
RC
KEY:
BK-BLACK
BL-BLUE
R-RED
O-ORANGE
G-GREEN
W-WHITE
Notes:
Use 18/4 class 2 thermostat cable between heater and thermostat.
Max. length @ 18 Awg (0.8mm²) = 100ft.
Only one burner can operate from one thermostat as supplied.
When servicing heaters ensure the electricity supply is isolated from the mains supply.
120V AC supply is still present at each burner when the thermostat is switched off.
Doc No 700102 (06-15), Page 8
Figure 6a. Internal Burner Wiring Diagram. (VCS)
Optional
24V single
stage
Thermostat
CW1R
O
BL
BR
G
R
BK
W
E
LN
G
BK
W
24V Stat
Terminals
BL
BR
YY
Pressure Switch
W
NE
120V AC
Supply
LNE
G
BK
W
BL - BLUE
KEY:
120V AC Fan
Terminals
CW1R
O
BK
F
G
BK - BLACK
BR - BROWN
E
GR - GREY
G - GREEN
W - WHITE
BK
W
Y - YELLOW
O - ORANGE
P - PURPLE
120v/24VAC 60Hz
Power ON (red)
Transformer
BR
BL BR
PGR
Burner On (amber)
Y
MV
PS1
Y
PS0
O
W1
BR
BR
R
Gas Control
BL
GR
X
C
COM
E
GR
P
M
C
G
E
Gas Valve
BK
BK
L1
P
IND
NOTES:-
Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner. Additional wiring is required to install an optional extra thermostat and / or time clock. If no thermostat is required then a jumper is fitted between terminals R and W1. In this configuration the burner will continuously fire until the 120V power supply is disconnected. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
Doc No 700102 (06-15), Page 9
Figure 6b. Internal Burner Wiring Diagram. (VCT)
24V Two stage
Thermostat
R
BR
24V AC Stat
Terminals
R
BR
YY
Pressure Switch
E
LN
W2W1
C
G
O
BL
120V AC Fan
W
BK
120V AC
G
R
K
Terminals
W2W1
C
O
BL
F1 NEF2
K
G
R
W
BK
BK
Supply
LNE
G
BK
W
KEY:
BL - BLUE
BK - BLACK
W
BR - BROWN
GR - GREY G - GREEN
E
E
K - PINK
R - RED
W - WHITE
Y - YELLOW
BK
120V/24VAC 60Hz
Transformer
BR
W
O - ORANGE
P - PURPLE
Power ON (red)
BL BR
High Fire
Low Fire
Relay
R
1222
A2
24V AC RELAY
21
NC
A1
COIL
1424
NO
11
COM
BL
BK
R
Y
Y
P
R
BK
L1
IND
MV
O
BR
R
W1
PS1
PS0
BR
BL
GR
X
C
COM
Gas Control
(amber)
High Fire
P
M
GR
C
K
HI
NOTES:­Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner.
Additional wiring is required to install an optional extra thermostat and / or time clock. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
PGR
KGR
Gas Valve
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
Doc No 700102 (06-15), Page 10
1.5.1 Multiple burner configurations (Master & Slave) via Optional Relay (VCT ONLY). Refer to figure 6c and 6e.
Multiple VCT burners can be controlled via one main burner. In this scenario the main burner is knows as the ‘Master’ and any additional burners are known as ‘Slaves’.
The external two stage thermostat is connected to the Master burner and powered via the inbuilt transformer. The total burner load for the Master is 20VA. Each additional ‘Slave’ burner is 1.6VA
The Thermostat chosen to control the multiple heaters must not have a power requirement exceeding the spare capacity as shown in the examples below.
CONFIGURATION TOTAL BURNER LOAD SPARE FOR THERMOSTAT
Master PLUS 1 Slave 21.6VA
Master PLUS 3 Slaves 24.8VA
Master PLUS 5 Slaves 28.0VA
Master PLUS 7 Slaves 31.3VA
18.4VA
15.2VA
12.0VA
8.8VA
Figure 6c. Wiring schematic. Multiple Burners Master and Slave. (VCT)
GND L2 L1 (HOT)
120V 60Hz 1 Ph
Supply circuit
THERMOSTAT
W1 W2
R C
R C W1 W2
MASTER
BURNER
LEN
SLAVE
BURNER
W1 W2
LENLENLEN
SLAVE
BURNER
W1 W2 W1 W2
SLAVE
BURNER
24VAC 60Hz 1 Ph Hi/Lo circuit
1.5.2 Multiple burner configuration via independently powered two stage thermostats. (VCT ONLY). Refer figs 6d & 6e
Note: If the thermostat has an independent power supply, all burners in the zone to be controlled MUST be Slave burners.
The maximum number of Slave burners per thermostat is dependent on the maximum power output of the thermostat selected.
Each ‘Slave’ burner is rated at 1.6VA 24VAC 60Hz.
The external two stage thermostat is powered via its own power supply and must output to each Slave burner - 24VAC for low fire to terminal W1 and 24VAC for hi fire to both terminals W1 and W2
Refer to thermostat manufactures literature for details.
Figure 6d. Wiring schematic. Multiple Burners via independently powered Relay. (VCT)
GND L2 L1 (HOT)
120V 60Hz 1 Ph Supply circuit
Low fire output
Hi fire output
THERMOSTAT
W1 W2
SLAVE
BURNER
LEN
SLAVE
BURNER
W1 W2
LENLENLEN
SLAVE
BURNER
W1 W2 W1 W2
SLAVE
BURNER
Supply Circuit
(by others)
Doc No 700102 (06-15), Page 11
24VAC 60Hz 1 Ph Hi/Lo circuit
Figure 6e. Internal Slave Burner Wiring/External Schematic Diagram with Optional Relay. (VCT)
1222
A2
24V AC
RELAY
21
R
A1
COIL
O
1424
NO
11
BL
OPTIONAL RELAY WIRING
COM
O
BR
BL
Relay mini harness leads
5A connector
24V Two stage
Thermostat
R
24V AC Stat
Terminals
R
BR
YY
Pressure Switch
W2W1
C
K
O
G
R
W
BK
120V AC Fan
Terminals
W2W1
C
BL
F1 NEF2
K
G
R
W
BK
E
E
L
G
BK
120V AC
Supply
LNE
G
BK
E
N
W
KEY:
BL - BLUE
BK - BLACK
W
BR - BROWN
GR - GREY
G - GREEN
K - PINK
R - RED
W - WHITE
Y - YELLOW
BK
120V/24VAC 60Hz
Transformer
BR
W
O - ORANGE
P - PURPLE
Power ON (red)
BL BR
PGR
High Fire
Relay
R
1222
A2
24V AC RELAY
21
NC
A1
COIL
1424
NO
11
COM
BL
BK
R
Y
Y
P
R
BK
L1
MV
IND
O
BR
R
W1
PS1
PS0
BL
BR
GR
X
C
COM
Gas Control
Low Fire
(amber)
High Fire
P
M
GR
C
K
HI
KGR
Gas Valve
NOTES:­Power On light is permanently illuminated when 120V / 60 Hz AC external supply is connected to burner. Additional wiring is required to install an optional extra thermostat and / or time clock. Wire specification:- 18 AWG (1.0mm²), Tri-rated, 105°C
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 220°F/105°C
Doc No 700102 (06-15), Page 12
1.6 Vent Requirements and Details
1.6.1 Unvented units
Heaters may be installed unvented providing the governing building codes are met and consideration is properly given to possibilities of condensation on cold surfaces.
Installation shall meet the following requirements when unvented:
Natural or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1000 BTU per hour input of installed heaters.
Combustion gases shall not impinge on combustible materials.
1.6.2 Vertical venting
The heater can be installed with a vertical vent.
All vent piping should be adequately supported from the building structure and terminated with an approved terminal.
recommended vent length is 25ft (7.6m) with a maximum of two elbows
should be properly sealed. refer fig 7a
1.6.3 Horizontal venting
Individual units can be vented horizontally through side walls. Recommended terminals are Part Numbers 111848 for 4” and 111850 for 6”.
Distances from adjacent public walkways, adjacent buildings, openable windows and building openings, consistent with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1.
The maximum recommended vent length is 25ft (7.6m) with a maximum of two 90° elbows.
However runs up to 12ft (3.6m) can use 4” (101mm) vent pipe. Runs over 12ft (3.6m) should always use 6” (152mm) vent pipe.
An approved clearance thimble is required when the flue pipe passes through combustible materials. Follow the requirements of the thimble manufacturer.
Standard vent terminals must extend at least 6” (152mm) from the wall and at least
The maximum
. All connections
24” (609mm) from any combustible overhang. This protects the building material from degradation by the vent gases.
Vent joints should be sealed and secured according to the vent manufacturers instructions. Should condensation occur the vent should be shortened or insulated.
The terminal should be at least 3ft (0.91m) from any air intake to the building.
The vent terminal must be installed at a suitable height above the ground to prevent blockage by snow.
1.7 Fresh Air Intake
Whenever the heater is installed in locations where airborne dust or other pollutants are present, a fresh air supply should be ducted to the burner.
If the heater is equipped with ducted combustion air, the vent terminal must be at least 3ft (0.91m) away from the air inlet and located higher than the inlet.
A fresh air duct of 4” (101mm) diameter should be installed from the fresh air to the air intake connection on the fan housing. A flexible jointing piece should be installed at the fan connection with hose clamps to facilitate expansion and contraction.
The maximum recommended length air duct is 25ft (7.6m) and the maximum number of elbows is two. The minimum length is 18” (456mm).
The location of the fresh air duct inlet must be where it will receive dust free clean air. An inlet cap with bird screen must be fitted at the inlet of the duct. If the duct inlet is located above the roof the underside of the inlet terminal must be at least 2ft (0.61m) above roof level (or above projected snow load) and at least 10” (254mm) above any projection on the roof within 7ft (2.1m) of the inlet. Intake pipe, fittings and sealant are not furnished by the manufacturer. Refer fig 7c & d.
Note the vent terminal must NOT be installed below the fresh air intake, and should have a minimum separation distance of 36” from the air intake.
Note The vent terminal should be installed so as to be in the same atmospheric pressure zone as the combustion air inlet of the appliance.
Doc No 700102 (06-15), Page 13
Figure 7.a Vertical Venting.
Approved clearance thimble is required when the flue pipe extends through combustible materials. Follow the requirements of the thimble and/or Category III vent pipe manufacturer.
Figure 7.b Horizontal Venting (plan view shown).
Approved clearance thimble is required when the flue pipe extends through combustible materials. Follow the requirements of the thimble and/or Category III vent pipe manufacturer.
Aluminum 4” (101mm) O.D. pipe.
Max length = 25’0” (7.62M) with 2
x 90° long radius bends.
Clamps
4” (101mm) O.D. flexible duct
Burner
Note The vent terminal should be installed so as to be in the same atmospheric pressure zone as the combustion air inlet of the appliance.
Note the vent terminal must NOT be installed below the fresh air intake, and should have a minimum separation distance of 36” from the air intake.
Figure 7.c Fresh Air Ducted Intake.
Doc No 700102 (06-15), Page 14
1.8.1 Technical Details - Table 5a (VCS)
No of Injectors
Gas Connection
Electrical Supply
Vent size (in)
Unitary Fan Motor Details
Current Rating
Ignition
Natural Gas LP Gas
MODEL
BTU/Hr BTU/Hr
60
60,000 60,000 20 40 20 40
120 volt 1 phase 60Hz
4” or 6” (101mm or 152mm)
120 volt, 1 phase 60Hz
1.8A MAX (models 60 - 150); 1.0A MAX (models 170 & 200) Electronic Program Start up with Spark Ignition
Min. Heater
Length
Max. Heater
Length
S ft S ft U ft U ft
1
½” N.P.T
Min. Heater
Length
Max. Heater
Length
80 80,000 80,000 30 40 20 40
100 100,000 100,000 30 50 40 40
125 123,500 125,000 30 60 40 60
150 150,000 150,000 40 70 40 60
170 169,000 169,000 50 80 60 80
200
Appliances can be installed up to 10,000ft above sea level in the USA. Altitude conversion kits are available on request.
200,000
N/A
50 80 60 80
USA 0- 2000 ft (0-610m) above sea level
Size
NG “WC
LP “WC
60 80 100 125 150 170 200
3.9 3.5 4.5 4.3 4.0 3.3 3.3
5.5 5.2 8.0 7.6 7.0 6.1 N/A
USA & CANADA Natural Gas 0- 2000 ft (0-610m) above sea level
Size
Burner Orifice Plate Part No.
60 80 100 125 150 170 200
269941 269942 269943 269944 1005513 269946 269946
Flame Plate Part No.
Fan Part No.
Fan Orifice Part No.
Injector Part No.
270476 270476 270476 270476 270476 269922 269925 269925 269930 269931 269935 269938 270400 270402 270403 270405 270407 270409 270410
Injector Carrier Part No.
Pressure Switch Part No.
USA & CANADA LP Gas 0- 2000 ft (0-610m) above sea level
Size
Burner Orifice Plate Part No.
Flame Plate Part No.
60 80 100 125 150 170 200 269948 269949 269950 269951 269952 269953 269957 269958 269960
Fan Part No.
Fan Orifice Part No.
Injector Part No.
269924 269925 269929 269931 269933 269937 270398 270399 270400 270401 270403
Injector Carrier Part No.
Pressure Switch Part No.
CANADA 0- 2000 ft (0-610m) above sea level
Size
NG “WC
LP “WC
270375 270376
270476 270475
60 80 100 125 150 170 200
3.9 3.5 4.5 4.3 4.0 3.3 3.3
5.5 5.2 8.0 7.6 7.0 6.1 N/A
N/A
270475
270389 270390
269959
N/A
270375 270389
Doc No 700102 (06-15), Page 15
Loading...
+ 33 hidden pages