2) With the manual valve turned o to prevent ow to the gas valve, connect a
manometer to the 1/8ʺ outlet pressure tap in the valve. NOTE: A manometer (uidlled gauge) is recommended.
3) Turn the manual valve to the ON position and the heater OFF. Use your nger to
fully block the main burner orice for several seconds. Observe the manometer
with the orice blocked, and if any pressure is indicated, the gas valve is leak-
ing. A leaking gas valve must be replaced before the heater is put back in
operation.
See FIGURE 18, page 30, for location. (NOTE: Depending on date of manufacture and
size, pressure switch may not be in the location indicated. Check the control bracket
on the bottom of the compartment or further down on the compartment wall.) If it is
determined that the pressure switch needs replacing, use only the factory-authorized
replacement part that is designed for the model and size of heater being serviced.
NOTE: A unit operating above 6000 ft (1830M) elevation requires a high altitude pressure switch (see Paragraph 3.2).
If it is determined that the limit control needs replacing, use only a factory-authorized
replacement part that is designed for the size of heater.
For approximate limit location, see FIGURE 18, page 30.
The cause of a ame rollout switch activating must be determined. Activation of the
manually reset ame rollout switch could be caused by one or more of the following:
• Restricted or plugged heat
exchanger
• Too much building exhaust
• Manifold gas pressure too
high
• Restricted combustion air inlet or exhaust outlet
in combination with a defective pressure switch
• Electrical power interruption during operation
• Unit being operated with a line voltage
disconnect (a 24-volt thermostat is required)
If a ame rollout switch trips, inspect the burner/control compartment for signs of
excessive heat and burned wiring.
For location, see
FIGURE 18, page 30.
If the compartment appears normal, reset by depressing the red button on the
switch. 15 to 20 minutes are required for the switch to cool suciently for resetting. A distinct click will be felt when the switch resets. Operate the furnace. If the
ame rollout switch trips again, determine and correct the cause before resetting
the switch.
If there is damage to the control compartment, repairs must be made before
resetting the switch.
If it is determined that the ame rollout switch needs replacing, use only the factory-
authorized replacement part that is designed for that size of heater.
The disconnect switch is located in the sealed electrical box inside the control com-
partment with the toggle on the rear of the heater.
10.2.11 Door
Switch—Separated
Combustion Model
only
Page 34, D300519A (04-18) I-UDA&APD Series
If it is determined that the door switch needs replacing, use only a factory-
authorized replacement part that is designed for the heater.
For approximate switch location, see FIGURE 18, page 30.
10.2.12 Transformer
Trial for Ignition
Call for Heat
Is there a
spark across gap at
ignitor?
Does gas
ignite?
Is there minimum
flame current at the
flame sensor?
Is there
minimum flame current
at the control
module?
Replace control
module.
Check connections to flame
sensor and/or moisture in the
burner assembly.
Is the flame
sensor corroded?
Clean flame
sensor.
Is the sensor
located in flame
correctly?
Replace flame
sesnsor.
Reposition
flame sensor.
Is gas
flowing?
Is the ignitor
position correct in the
gas flow?
Check gas pressure
and supply voltage.
If either are low,
correct and repeat
startup.
Reposition
spark ignitor.
Is there
24VAC at the gas
valve?
Is there 24VAC
from gas valve output on
control module to
chassis?
Check wiring and
connections to
gas valve.
Replace
ignition
control
module.
Replace gas
valve.
Is there
spark voltage at
control?
Check high
voltage wire
continuity.
Is there 24V P1-2
to power control?
Replace
control
module.
Check wiring
and/or 24VAC
transformer output.
YESNO
YESNO
YESNO
YES
NO
YES
NO
YES
NO
YESNO
YES
NO
NO
YES
YESNO
YES
NO
YES
NO
10.2.13 Disconnect
Switch—Separated
Combustion model
only
10.2.14 Vent or Vent/
Combustion Air
System
10.3 Troubleshooting
Check the Lights on
the DSI Integrated
Control Module
(Circuit Board)
IMPORTANT: When using
a multimeter to troubleshoot
the 24 volt circuit, place the
meter’s test leads into the 5
or 9 pin connectors located
on the ignition control. Do
not remove connectors or
terminals from the electrical components. Doing so
can result in misinterpreted
readings due to the ignition
control board’s fault mode
monitoring circuits.
See FIGURE 18, page 30, for location. Use a voltmeter to verify that
there are 24 volts output from the transformer. If the transformer is not
functioning, it must be replaced. Use a replacement transformer identi-
cal to the factory-installed model.
If it is determined that the disconnect switch needs replacing, use only the
factory-authorized replacement part that is designed for the heater. Always
replace electrical box cover.
Check the complete system at least once a year. Inspection should include all joints,
seams, concentric adapter box (Separated Combustion), inlet air guard or inlet air cap
(Separated Combustion), and the vent terminal cap. Clean openings. Replace any
defective parts.
The integrated circuit board monitors the operation of the heater and includes two
LED signal lights that indicate normal operation and various abnormal conditions. If
the heater fails to operate properly, check this signal to determine the cause and/or
to eliminate certain causes. LED is visible through viewport on Separated Combustion models. Remove access panel on Standard Power Vent models. See operating
sequence in Paragraph 9.
Do not attempt to repair the DSI integrated control module (circuit board); the only eld
replaceable component is the fuse.
Control Status—Green LED Codes
Steady ONNormal Operation, No call for heat
Fast Flash . Normal Operation, Call for heat
1 Flash ...... System Lockout, Failed to detect or sustain ame
2 Flashes .. Pressure Switch Did Not Close within 30 Seconds of Venter Motor
3 Flashes .. High Limit or Flame Rollout Switch Open
4 Flashes ....Pressure Switch is Closed Before Venter Motor is Energized
Steady OFFBlown fuse, No Power, or Defective Board
Flame Status—Yellow LED Codes
Steady ON ..Flame is sensed
Slow Flash ..Weak ame (current below 1.0 microamps ± 50%)
Fast Flash ...Undesired Flame (valve open and no call for heat)
DSI Integrated Control Module (Circuit
Board) Trial Troubleshooting Flowchart
D300519A (04-18) I-UDA&APD Series, Page 35
10.3 Troubleshooting (cont’d)
General Troubleshooting
PROBLEMPROBABLE CAUSEREMEDY
Venter motor will not
start
Burner will not light1. Manual valve not open.1. Open manual valve.
Burner cycle on and o1. Gas pressure too high or too low.1. Supply pressure should be 5–14" w.c. for natural gas or 11–14" w.c. for pro
1. No power to unit.1. Turn on power, check supply fuses or circuit breaker.
2. No 24 volt power to integrated circuit board.2. Turn up thermostat; check control transformer output.