Reznor UDAP, UDAS Installation Manual

Page 1
P
R
O
Y
C
C
N
E
G
A
C
C
U
S
T
O
M
E
CQS
R
Q
U
P
R
O
D
E
S
R
E
G
S
V
E
N
N
T
P
U
-
T
R
A
T
S
M
A
L
I
T
Y
U
C
T
Y
E
T
T
S
Y
S
N
A
R
R
A
W
Table of Contents
Page
Warnings ........................................ 1
Installation/Operation .............. 2-25
Check/Test/Startup ................. 26-28
Maintenance/Service .............. 28-36
Index (by page)
Burner .................................................. 16, 29
Burner Orifice............................................ 30
Burner Removal.......................................... 29
California W arning Label..............................3
Clearances ................................................... 7
Installation Codes ........................................ 2
Confined Space (UDAP) ..............................8
Dimensions ............................................... 4-5
Disconnect, Built-in (UDAS)................ 16, 34
Door Switch (UDAS) ........................... 19, 33
Downturn Nozzle (Option) ...........................4
Electrical Connections ............................... 16
Fan ............................................................. 32
Fan Motor ............................................. 22, 32
Flame Rollout Switch .......................... 19, 34
Gas Piping and Pressures ........................... 12
Gas Valve .............................................. 22, 33
General ........................................................ 2
Hanging the Heater ..................................... 10
Hazard Intensity Levels ............................... 2
Heat Exchanger Maintenance .....................29
High Altitude .......................................... 7, 14
Ignition System ..................................... 19, 31
Limit Control ........................................ 18, 33
Location (Heater).......................................... 9
Maintenance Schedule ............................... 28
Pressure Switch (Combustion Air)....... 18, 33
Replacement Parts ................ See Form P-UD
Sound Data .................................................. 6
Startup ........................................................26
Suspending Heater ....................................... 4
Technical Data ..............................................6
Thermostat (Option) .................................. 17
Throw (Heater) ............................................. 9
Transformer ................................................ 33
Troubleshooting ................................... 34-36
Uncrating and Preparation ........................... 3
Valve Outlet Pressure ..................................14
Vent System ............................................... 34
Venter Motor .............................................. 32
V enting UDAP .......... Use Form I-UD-V-PV
V enting UDAP-CV .......... Use Form I-V-CV
V enting UDAS........... Use Form I-UD-V-SC
Warranty ....................................................... 3
Wiring Diagrams .................................. 23-25
®
Series Fan-Type
Unit Heaters
Installation/Operation FORM RZ-NA I-UDA
APPLIES TO: Models UDAP and UDAS
FOR YOUR SAFETY
What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call your fire department.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
WARNING: Gas-fired appliances are not designed for use in hazardous atmospheres containing flammable vapors or combustible dust, in atmospheres containing chlorinated or halogenated hydrocarbons, or in applications with airborne silicone substances. See Hazard Levels, page 2.
WARNING: Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
WARNING: Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any gas control that has been under water.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 1
Page 2
Hazard Levels of W arnings in this Manual
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in sever e personal injury or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
1. General
BOTH this manual and the correct venting manual are REQUIRED for installation of this heater.
Model UDAP 30, 45, 60, 75, 100, and 125 and Model UDAS 30, 45, 60, 75, 100, and 125 are design certified by the Canadian Standards Association for use in residential, industrial, and commercial installations. Unit heaters certified for “resi­dential use” are intended to be used as supplementary heating devices in residen­tial areas such as workshops and garages. They are not intended to be the primary source of heat in residential applications or to be used in sleeping quarters.
Models UDAP 150, 175, 200, 225, 250, 300, 350, and 400 and UDAS 150, 175, 200, 225, 250, 300, 350, and 400 are design certified by the Canadian Standards Association for use in industrial and commercial installations only .
All models and sizes are available for use with either natural or propane gas. The type of gas, the input rate and the electrical supply requirement is shown on the heater’s rating plate. Check the rating plate to determine if the heater is appropri­ate for the intended installation.
Installation requires both this manual AND the venting manual.
V enting Manual by Model
Venting Instruction Look for Matching Label on
Model Manual by Form No. Venting Manual and Heater UDAP Standard Power Vent Label with
Installation (each heater Red Square has its own dedicated vent)
- Form RZ-NA I-UD-V-PV
UDAP-CV Optional Common Vent Label with with Installation (must be inverted Option equipped with Option AV6) Blue Triangle AV6 - Form RZ-NA I-V-CV
Model UDAP-CV is available in Sizes 30, 45, 60, 75, 100 only UDAS Separated Combustion Label with
- Form RZ-NA I-UD-V-SC Green Circle
2. Installation Codes
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 2
These units must be installed in accordance with local building codes. In the ab­sence of local codes, in the United States, the unit must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1. A Canadian installation must be in accordance with the CSA B149 Installation Codes. These codes are available from CSA Information Services, 1-800-463-6727. Local authorities having juris-
Both this installation manual and the appropriate venting manual are shipped with the heater. Verify that the literature is correct for the heater being installed. If either manual is missing or incorrect, contact your distributor before beginning installation.
The instructions in this manual apply only to the models listed. Installation should be done by a qualified agency in accordance with these in-
structions. The qualified service agency installing this heater is responsible for the installation.
Page 3
diction should be consulted before installation is made to verify local codes and installation procedure requirements.
Special Installations (Aircraft Hangars/ Repair Garages/ Parking Garages)
California Warning Label
Massachusetts Requirement
3. W arranty
Installations in aircraft hangars should be in accordance with ANSI/NFPA No. 409 (latest edition), Standard for Aircraft Hangars; in public garages in accordance with ANSI/NFPA No. 88A (latest edition), Standard for Parking Structures; and for repair garages in accordance with ANSI/NFPA No. 88B (latest edition), Stan­dard for Repair Garages. In Canada, installations in aircraft hangars should be in accordance with the requirements of the enforcing authorities, and in public ga­rages in accordance with CSA B149 codes.
If the heater is being installed in the state of California, the installer MUST attach a warning label on the outside of the access door. The California Warning label is shipped in the owner’s envelope along with this manual, the warranty form, and any other paperwork that applies.
If installation is in California, select a location on the heater access panel. Be sure the surface is clean and dry and adhere the label.
If the heater is being installed in the Commonwealth of Massachusetts, these units must be installed by a licensed plumber or licensed gas fitter .
Refer to the limited warranty information on the Warranty Card in the "Owner's Envelope".
Warranty is void if ...
a. Wiring is not in accordance with the diagram furnished with the heater. b. The unit is installed without proper clearance to combustible materials. c. A fan model is connected to a duct system or if the air delivery system is
modified.
4. Uncrating and Preparation
This unit was test operated and inspected at the factory prior to crating and was in operating condition. If the heater has incurred any damage in shipment, document the damage with the transporting agency and contact an authorized Reznor Dis­tributor. If you are an authorized Distributor, follow the FOB freight policy proce­dures as published by Thomas & Betts for Reznor products.
Check the rating plate for the gas specifications and electrical characteristics of the heater to be sure that they are compatible with the gas and electric supplies at the installation site.
Read this booklet and become familiar with the installation requirements of your particular heater. If you do not have knowledge of local requirements, check with the local gas company or any other local agencies who might have requirements concerning this installation.
Before beginning, make preparations for necessary supplies, tools, and manpower. If the installation includes optional vertical louvers, downturn nozzle, ceiling mount­ing bracket, hanger kit, high altitude kit, multiple heater control, and/or stepdown transformer, install these options before the heater is suspended. Follow the in­structions included in the option package; option packages are shipped separately .
Other shipped separate items could include a vent/combustion air kit, high tem­perature tape, a thermostat bracket kit, a thermostat, and/or a thermostat guard. Be sure all options ordered are at the installation site.
IMPORTANT: Shipping brackets are attached with cabinet screws. When removing shipping brackets, re-insert ALL screws into the cabinet.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 3
Page 4
5. Dimensions
M and N - Hanger Dimensions for both 2-pt and 4-pt Suspension
N
P and Q -
Hanger
for 4-pt
(4-pt is
P
Q
3/8-16 Female Thread
- all suspension points
Dimensions
Suspension
required if
installing
optional
nozzle.)
M
TOP VIEW
R - Hanger Dimension for 2-pt Suspension
R
(30-125 Ver tical;
150-400 Horizontal)
Thermostat Connection
G
J
FIGURE 1 - Model UDAP,
Combustion Air Inlet
REAR
Power Vented Fan Model
VIEW
Line Voltage
Inlet (connects
at circuit board)
B
D
FRONT
VIEW
C
A
1-1/4
(32)
K
External Gas
H
Connection
F
RIGHT SIDE
VIEW
(Access Panel)
E
Vent Collar
(see Technical Data for size)
REZNOR
MODEL UDAP DIMENSIONS (inches ± 1/16)
Size
30, 45
60
75 100 125
150, 175,
200
225, 250
300, 350,
400
MODEL UDAP DIMENSIONS (mm ± 2)
Size A B C D E F G H J K M N P Q R
30, 45
60
75 100 125
150, 175,
200
225, 250
300, 350,
400
FIGURE 2 ­With Optional Downturn Nozzle Dimension “U”
-- Applies to both UDAP and UDAS
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 4
ABC D EF G H J K MNPQ R
12-1/8 26-5/8 10 13-13/16 26 21-9/16 5-3/16 6-1/2 2-11/16 3-7/8 17-3/8 11/16 4-5/16 13 9-9/16 15-1/8 26-5/8 13 13-13/16 27 21-9/16 7-7/8 6-1/2 5 -1/2 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 15-1/8 26-5/8 13 13-13/16 27-5/8 21-9/16 7-7/8 6-1/2 5-1/2 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 23-1/8 26-5/8 21 13-13/16 28-5/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 23-1/8 26-5/8 21 13-13/16 29-3/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2
20-1/8 38-3/16 16 23 42 35-3/8 8-1/2 8-1/4 5-7/16 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 16-3/8 26-1/8 38-3/16 22 23 42 35-3/8 13-1/16 8-13/16 9 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 15-5/8 34-1/8 41 30 23 42 35-3/8 17-1/16 9 11-13/16 7-5/16 27-11/16 1-3/8 8-3/16 22-3/16 16-3/16
308 676 254 351 660 548 132 165 6 8 98 441 17 110 330 243 384 676 330 351 686 548 200 165 140 98 441 17 110 330 267 384 676 330 351 702 548 200 165 140 98 441 17 110 330 267 587 676 533 351 727 548 368 165 222 98 441 17 110 330 267 587 676 533 351 746 548 368 165 222 98 441 17 110 330 267
511 970 406 584 1067 899 216 210 138 165 652 35 208 564 416 664 970 559 584 1067 899 332 224 229 165 652 35 208 564 397 867 1041 762 584 1067 899 433 229 300 186 703 35 208 564 411
Downturn nozzles require 4-pt suspension.
With
UDAP or UDAS
Option CD2 or CD4
UDAP or UDAS
With
Option
CD3
U U
Size
30, 45 60, 75 100, 125 150, 175, 200 225, 250 300, 350, 400
Options CD2 and CD4
inch es mm inch es mm
7-1/8 181 12-3/8 314
8-5/8 219 15 381 12-5/8 321 21-7/8 556 11-1/2 292 19-7/8 505 14-1/2 368 25-1/8 638 18-1/2 470 32 813
Option CD3
Page 5
P and Q -
Hanger
Dimensions
for 4-pt
Suspension
(4-pt is
required if
installing
optional
nozzle.)
M and N - Hanger Dimensions
for both 2-pt and 4-pt Suspension
N
P
Q
3/8-16 Female Thread
- all suspension points
M
TOP VIEW
R - Hanger Dimension for 2-pt Suspension
Thermostat
R
Connection
(30-45, 150-400
Horizontal;
60-125 Vertical)
FIGURE 3 - Model UDAS,
Separated Combustion Fan
Model
Combustion Air Connection
(see Technical Data for size)
T
S
G
J
REAR
VIEW
Line Voltage
Inlet (connects in
sealed electrical box)
D
C
A
B
1-1/4
(32)
FRONT
VIEW
K
(Access Panel)
REZNOR
External Gas
H
Connection
E
F
RIGHT SIDE
VIEW
LED Viewport
Vent Connection
(see Technical Data for size)
MODEL UDAS DIMENSIONS (inches ± 1/16)
Size
30, 45
150, 175,
225,
300, 350,
ABCD EF GH J KMNPQ R S T
12-1/8 26-5/8 10 13-13/16 26 21-9/16 5-3/16 6-1/2 2-11/16 3-7/8 17-3/8 11/16 4-5/16 13 9-9/16 2-15/16 2-15/16
60
15-1/8 26-5/8 13 13-13/16 27 21-9/16 7-7/8 6-1/2 5-1/2 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 3-1/4 2-15/16
75
15-1/8 26-5/8 13 13-13/16 27-5/8 21-9/16 7-7/8 6-1/2 5-1/2 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 3-1/4 2-15/16
100
23-1/8 26-5/8 21 13-13/16 28-5/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 4-5/8 2-15/16
125
23-1/8 26-5/8 21 13-13/16 29-3/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13 10-1/2 4-5/8 2-15/16
20-1/8 38-3/16 16 23 42 35-3/8 8-1/2 8-1/4 5-7/16 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 16-3/8 4-1/8 8-5/16
200
26-1/8 38-3/16 22 23 42 35-3/8 13-1/16 8-13/16 9 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 15-5/8 5-9/16 8-5/16
250
34-1/8 41 30 23 42 35-3/8 17-1/16 9 11-13/16 7-5/16 27-11/16 1-3/8 8-3/16 22-3/16 16-3/16 9-1/16 8-9/16
400
MODEL UDAS DIMENSIONS (mm ± 2)
Size A B C D E F G H J K M N P Q R S T
30, 45
60
75 100 125 150, 175,
200
225,
250 300, 350,
400
308 676 254 351 660 548 132 165 68 98 441 17 110 330 243 384 676 330 351 686 548 200 165 140 98 441 17 110 330 267 384 676 330 351 702 548 200 165 140 98 441 17 110 330 267 587 676 533 351 727 548 368 165 222 98 441 17 110 330 267 587 676 533 351 746 548 368 165 222 98 441 17 110 330 267
511 970 406 584 1067 899 216 210 138 165 652 35 208 564 416
664 970 559 584 1067 899 332 224 229 165 652 35 208 564 397
867 1041 762 584 1067 899 433 229 300 186 703 35 208 564 411
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 5
75 75 89 75
89 75 117 75 117 75
105 211
141 211
230 217
Page 6
6. T echnical Dat a
TECHNICAL DATA - Sizes 30 - 125 (Data app li es to both Mod els UDAP and UDAS unless noted otherwise.)
Size 30 45 60 75 100 125
Inp ut Heating C apacity Thermal Efficiency (%) 828383838383 Output Heating Capacity
Gas Conne c t ion (inches) Vent Connection
C ombustion Air Inlet
A
B
C
(inches diam e t e r)
C
(inches diameter) ­Control Amps (24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 Full Load Amps (115 volt) 1.9 2.4 2.4 3.3 3.9 5.1
Maximum Ov er Cu rrent Protection
D E
Normal Power Consumption (watts) 109 155 155 217 276 354 Discharge Air Temperature Rise (°F) 50 55 60 60 60 60
Ai r Vol ume
Discharge Air Opening Area
Output Vel ocity
Fan Motor HP
E
Fan Motor RPM 1550 1550 1550 1550 1050 1050 Fan Diameter (inches) 10 10 12 12 16 16 Sound Level dba @ 15 ft 40 40 40 49 54 55
TECHNICAL DATA - Sizes 150 - 400
Size 150 175 200 225 250 300 350 400
In pu t Heating Capacity Thermal Efficiency (%) 8383838383838383 Output Heating Capacity
Gas C onnection (inches) Vent Connection
Combustion Ai r Inlet
A
B
C
(inches di a meter )
C
(inche s diameter) ­Control Amps (24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Full Load Amps (115 volt) 3.8 3.8 4.6 7.5 7.5 10.7 10.7 10.7
Maximum Ov er Current Protection
D E
Normal Power Consumption (watts) 392 392 491 747 747 1086 1086 1086 Discharge Air Temperature Rise (°F) 60 60 60 60 60 60 60 60
Ai r Volume
Discharge Air Opening Area
Output Velocity
Fan Motor HP
E
Fan Motor RPM 1050 1050 1050 1050 1050 1050 1050 1050 Fan Diameter (inches) 18 18 18 20 20 24 24 24 Sound Level dba @ 15 ft 51 52 53 56 56 59 61 62
A
CSA ratings for altitudes to 2000 ft.
B
Size shown is for gas connection to a single-stage gas valve, not supply line size.
C
Smaller and/or larger vent and combustion air pipe diameters may be permissible. For Model UDAS refer to the Venting
Installation Manual for Separated Combustion Units. For Model UDAP refer to the Venting Installation Manual for Power Vented units. For a Model UDAP with Option AV6, refer to the Venting Installation Manual for Common Venting.
D
MOCP = 2.25 x (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.
E
Except where indicated, information in this table is based on a heater equipped with a standard 115 volt open fan motor.
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 6
BTUH 30,000 45,000 60,000 75,000 105,000 120,000
kw 8.8 13.2 17.6 22.0 30.8 3 5.2
BTUH 24,600 37,350 49,800 62,250 87,150 99,600
kw 7.2 11.0 14.6 18.3 25.6 2 9.2
Natural 1/2 1/2 1/2 1/2 1/2 1/2
Pro pane 1/2 1/2 1/2 1/2 1/2 1/2
444444
UDAS only
444444
Standard 115V 15 15 15 15 15 15
Optional 208V or 230V 15 15 15 15 15 15
CFM 456 629 769 961 1345 1537
M
3
/minute
2
ft
2
M
12.9 17.8 21 .8 27.5 36.7 45.9
0.96 0.96 1.25 1.25 2.01 2.01
0.09 0.09 0.12 0.12 0.19 0.19
FPM 475 656 616 770 668 763
M/minute 145 200 188 238 196 245
Standard Open 0.02 0.03 0.03 0.06 1/30 1/20
Optional Enclosed N.A. N.A. N.A. N.A. 1/4 1/4
(Data applies to both Model s UDAP and UDAS unless noted otherwise.)
BTUH 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
kw 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1
BTUH 124,500 145,250 166,000 186,750 207,500 249,000 290,500 332,000
kw 36.4 42.5 48.6 54.7 60.8 72.9 85.1 97.2
Natural 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Propane 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
55555666
UDAS only
666666
66
Standard 115V 1515151515202020
Optional 208V or 230V 15 15 15 15 15 15 15 15
CFM 1921 2242 2562 2882 3202 3843 4483 5123
M
3
/minute
2
ft
2
M
54.4 63.5 72.5 81.6 90.7 108.8 126.9 145.1
2.56 2.56 2.56 3.51 3.51 4.79 4.79 4.79
0.24 0.24 0.24 0.33 0.33 0.45 0.45 0.45
FPM 752 877 1003 820 911 802 936 1069
M/minute 229 267 306 250 278 244 285
Standard Open 1/6 1/6 1/6 1/4 1/4 1/2 1/2 1/2
Optional Enclosed 1/4 1/4 1/4 1/4 1/4 1/2 1/2 1/2
Page 7
7. High Altitude
If the heater is being installed at an elevation above 2000 ft (610M), the input rate will have to be derated. This is done by adjusting the valve outlet pressure.
Operation
In addition, if the heater is being installed at an altitude above 6000 ft (1830M), the pressure switch will have to be changed. If ordered with the unit as Option DJ20 or DJ21, the pressure switch is shipped separately.
Gas valve adjustment for high altitude can only be done after heater is operating; see Paragraph 12.
Adjusting the valve outlet pressure is done after the heater is in operation; follow the instructions in Paragraph 12. Capacities and inputs for derated units are also listed in Paragraph 12.
If the pressure switch needs to be changed, do that before the heater is operated; follow the instructions in FIGURE 4.
FIGURE 4 - Installing High Altitude Pressure Switch required above 6000 ft (1830M) elevation
Model UDAP Size 30 45 60 75 100 125 150 175 200 225 250 300 350 400
High Altitude Switch P/N Negative Pressure OFF Setpoint "w.c. Label color
Model UDAP-CV with Option AV6 for Common Venting Size 30 45 60 75 100
Hig h Altitude Switch P/N 197029 197032 196388 Negative Pressure OFF Setpoint " w.c. 0.60 0.45 0.50 Label color Lt Blue Pink Orange
Model UDAS Size 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Hig h Altitude Switch P/N 196388 197030 Dif ferential Pressure OFF Setpoint "w.c. 0.50 0.40 Label c olor Orange Green
197031 197032
0.35 0.45
Purple Pink
196362
0.55
White
197029
0.60
Lt. Blue
197031
0.35
Purple
197031
Purple
0.35
201160
1.00
Brown
201160 201161
1.00 1.30
Brown
201161
1.30
White
White
Pressure Switch
8. Clearances
Clearances
Size
30 - 12 5
150 - 4 00
*Suspend t he heater so that the bot t om is a minimum of 5 feet (1 .5 M) above the floor.
Instructions for Changing Pressure Switch
1. In the control compartment, locate the pressure switch.
2. Mark and disconnect the two wires attached to the pressure switch.
3. Disconnect the sensing tube from the pressure switch.
4. Locate the two screws holding the switch mounting bracket. Remove the screws (save screws) and the pressure switch.
5. Using the same screws, install the high altitude pressure switch. Attach the sensing tube and wires.
Units must be installed so that the clearances in the table are provided for combus­tion air space, inspection and service, and for proper spacing from combustible construction. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object that is necessary to ensure that a surface tempera­ture of 90°F above the surrounding ambient temperature is not exceeded.
T op F lue Connector Access Panel Non- Access Sid e
inches mm inches mm in ches mm inches m m inches mm inches mm
125 6 152 4102 6 152
18 457 1 25 1 25 18 457 18 457 2 51 1 25 18 457
Bottom* Rear
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 7
Page 8
9. Combustion Air -
applies to Model UDAP and Model UDAP-CV
(Note: For Model UDAS, see V enting Manual for combustion air requirements.)
This heater must be supplied with the air that enters into the combustion process and is then vented to the outdoors. Sufficient air must enter the equipment location to replace that exhausted through the heater vent system. In the past, the infiltra­tion of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient. However , current construction methods using more insu­lation, vapor barriers, tighter fitting and gasketed doors and windows, weather­stripping, and/or mechanical exhaust fans may now require the introduction of outside air through wall openings or ducts.
The requirements for combustion and ventilation air depend upon whether the unit is located in a confined or unconfined space. An "unconfined space" is defined as a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance. Under ALL conditions, enough air must be provided to ensure there will not be a negative pressure condition within the equipment room or space.
WARNING: Model UDAP and UDAP-CV power-vented unit heaters are designed to take combustion air from the space in which the unit is installed and are not designed for connection to outside combustion air intake ducts. Connecting outside air ducts voids the warranty and could cause hazardous operation. See Hazard Levels, page 2.
Combustion Air Requirements for a Heater Located in a Confined Space - applies to Model UDAP and Model UDAP-CV
FIGURE 5 - Definition of Confined Space and Required Openings for Combustion Air
Do not install a unit in a confined space without providing wall openings leading
to and from the space. Provide openings near the floor and ceiling for ventilation and air for combustion as shown in FIGURE 5, depending on the combustion air source as noted in Items 1, 2, and 3 below.
Add total BTUH of all appliances in the confined space and divide by figures below for square inch free area size of each (top and bottom) opening.
Confined Space: A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating
1. Air from inside the building -- openings 1 square inch free area per 1000
BTUH. Never less than 100 square inches free area for each opening. See (1) in
FIGURE 5.
2. Air from outside through duct -- openings 1 square inch free area per 2000 BTUH. See (2) in FIGURE 5.
3. Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See (3) in FIGURE 5.
(3)
Confined
Space
(3)
(1)
(1)
(2)
(2)
NOTE: For further details on supplying combustion air to a confined space, see the National Fuel Gas Code ANSI Z223.1a (latest edition).
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 8
Page 9
10. Unit Heater
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
Location
Use the sound data in Paragraph 6, clearances in Paragraph 8; the combustion air requirements in Paragraph 9; the throw tables, mounting height requirements, and location recommendations below; the weights in Paragraph 11; and the venting requirements in the Venting Manual to determine where to suspend the heater.
Heater Throw
*Louver angle listed in the table is relative to the top of the heater.
FIGURE 6 - Throw for Fan Models UDAP and UDAS
NOTE: Throws listed are with
standard adjustable horizontal louvers at the angles listed (angle is relative to the top of the heater). Throw pattern changes with the addition of optional vertical louvers and/or downturn nozzles.
Dimensio ns X, Y, and Z (feet ) Mo del UDAP and Mo del U DAS with Standard Horizo nt al Louv ers at Mount ing Heights of 5 - 18 ft
H
5 ft 6 14 30 -21° 7 16 40 -20° 8 18 45 -16° 9 20 57 -14° 9 20 59 -18° 10 22 65 -14°
8 ft 7 13 26 -39° 9 16 37 -34° 10 18 42 -29° 12 22 54 -25° 11 21 56 -28° 12 23 63 -24° 10 ft 6 11 22 -52° 9 15 33 -43° 10 17 39 -37° 12 22 52 -32° 12 20 52 -36° 13 24 60 -30° 12 ft - - - - 8 12 27 -55° 10 16 34 -46° 12 21 48 -39° 11 19 47 -44° 14 23 57 -36° 14 ft - - - - - - - - 9 14 29 -56° 12 19 44 -46° 11 17 42 -51° 14 22 53 -43° 16 ft - - - - - - - - - - - - 11 17 38 -54° 10 14 34 -58° 13 20 47 -50° 18 ft------------------ --111740-57°
H
8 ft 13 24 73 -26 ° 15 28 90 -22° 16 30 93 -20° 14 27 86 -24° 16 29 93 -21° 15 28 9 4 -24° 17 31 105 -20° 1 8 34 113 -17° 10 ft 14 24 69 -32° 17 29 87 -27° 17 31 91 -25° 15 27 82 -30° 17 30 90 -26° 16 28 89 -29° 18 32 103 -25° 20 35 110 -21° 12 ft 14 24 64 -39° 18 29 84 -32° 18 31 88 -30° 16 27 78 -35° 18 30 87 -31° 17 28 85 -34° 19 32 98 -30° 21 36 108 -25° 14 ft 14 22 59 -45° 18 28 79 -37° 19 30 84 -34° 16 26 73 -41° 18 30 83 -36° 17 27 80 -40° 20 32 95 -34° 23 35 105 -29° 16 ft 13 20 53 -51° 18 27 74 -42° 19 29 79 -39° 16 24 67 -47° 19 28 78 -41° 17 25 74 -45° 21 31 90 -38° 23 35 101 -33° 18 ft 11 17 44 -58° 17 26 68 -48° 19 28 74 -44° 14 22 60 -53° 18 27 72 -46° 16 24 66 -51° 20 30 85 -43° 23 35 97 -37°
Dimensions X, Y, and Z (meters) Model UDAP and Model UDAS with Standard Horizontal Louv ers at Mounting Heights o f 1.5 - 5.5M
H
1.5 M 1.8 4.3 9.1 -21° 2.1 4.9 12.2 -20° 2.4 5.5 13.8 -16° 2.7 6.1 17.4 -14° 2.7 6.1 18.0 -18° 3.0 6.7 19.9 -14°
2.4 M 2.1 4.0 7.9 -39° 2.7 4.9 11.3 -34° 3.0 5.5 12.8 -29° 3.7 6.7 16.5 -25° 3.4 6.4 17.1 -28° 3.7 7.0 19.2 -24°
3.0 M 1.8 3.4 6.7 -52° 2.7 4.6 10.0 -43° 3.0 5.2 11.9 -37° 3.7 6.7 15.8 -32° 3.7 6.1 15.8 -36° 4.0 7.3 18.3 -30°
3.7 M - - - - 2.4 3.7 8.2 -55° 3.0 4.9 10.4 -46° 3.7 6.4 14.6 -39° 3.4 5.8 14.3 -44° 4.3 7.0 17.4 -36°
4.3 M - - - - - - - - 2.7 4.3 8.8 -56° 3.7 5.8 13.4 -46° 3.4 5.2 12.8 -51° 4.3 6.7 16.1 -43°
4.9 M - - - - - - - - - - - - 3.4 5.2 11.6 -54° 3.0 4.3 10.4 -58° 4.0 6.1 14.3 -50°
5.5 M------------------ --3.45.212.2-57°
H
2.4 M 4.0 7.3 22.3 -26° 4.6 8.5 27.4 -22° 4.9 9.1 28.0 -20° 4.3 8.2 26.2 -24° 4.9 8.8 28.3 -21° 4.6 8.5 28.7 -24° 5.2 9.4 32.0 -20° 5.5 11.3 34.4 -17°
3.0 M 4.3 7.3 21.0 -32° 5.2 8.8 26.6 -27° 5.2 9.4 27.7 -25° 4.6 8.2 25.0 -30° 5.2 9.1 27.4 -26° 4.9 8.5 27.1 -29° 5.5 9.8 31.4 -25° 6.1 10.7 33.5 -21°
3.7 M 4.3 7.3 19.5 -39° 5.5 8.8 25.6 -32° 5.5 9.4 26.8 -30° 4.9 8.2 23.8 -35° 5.5 9.1 26.5 -31° 5.2 8.5 25.9 -34° 5.8 9.8 29.9 -30° 6.4 11.0 32.9 -25°
4.3 M 4.3 6.7 18.0 -45° 5.5 8.5 24.1 -37° 5.8 9.1 25.6 -34° 4.9 7.9 22.3 -41° 5.5 9.1 25.3 -36° 5.2 8.2 24.4 -40° 6.1 9.8 29.0 -34° 7.0 10.7 32.0 -29°
4.9 M 4.0 6.1 16.2 -51° 5.5 8.2 22.6 -42° 5.8 8.8 24.1 -39° 4.9 7.3 20.4 -47° 5.8 8.5 23.8 -41° 5.2 7.6 22.6 -45° 6.4 9.4 27.4 -38° 7.0 10.7 30.8 -33°
5.5 M 3.4 5.2 13.4 -58° 5.2 7.9 20.7 -48° 5.8 8.5 22.6 -44° 4.3 6.7 18.3 -53° 5.5 8.2 21.9 -46° 4.9 7.3 20.1 -51° 6.1 9.1 25.9 -43° 7.0 10.7 26.9 -37°
30 45 125
XYZ
150 175 200 225 350 400
XYZ
30 45 60
XYZ
150 175 200
XYZ
le
XYZ
An
Louver
le*
XYZ
Louver
An
le
XYZ
An
Louver
le*
XYZ
Louver
An
le An
Louver
le*
Louver
An
le An
Louver
le*
Louver
An
H
X
Y
Z**
H = Distance from bottom of heater to the floor X = Distance from heater to start of floor coverage Y = Distance to end of floor coverage **Z = point when the air velocity drops below 50 ft (15.2M) per minute
60
XYZ
Louver
XYZ
Louver
XYZ
Louver
XYZ
Louver
75 100
le
XYZ
An
le*
XYZ
An
75 100 125
le
XYZ
An
le*
XYZ
An
le
XY Z
An
Louver
le*
XY Z
Louver
An
le
XY Z
An
Louver
le*
XY Z
Louver
An
250 300
le
XY Z
An
Louver
le*
XY Z
Louver
An
le
XY Z
An
Louver
le*
XY Z
Louver
An
le An
Louver
le*
XYZ
Louver
An
le An
Louver
le*
XYZ
Louver
An
le*
XYZ
Louver
An
le*
XYZ
Louver
An
400225 250 300 350
le*
Louver
An
le*
Louver
An
Location
Locate the heater so that it is a minimum of five feet (1.5M) above the floor and in compliance with the clearances in Paragraph 8.
Recommendations
W ARNING: If touched, the vent pipe and internal heater surfaces that are accessible from outside the heater will cause burns. Suspend the heater a minimum of 5 feet (1.5M) above the floor.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 9
Page 10
10. Unit Heater Location (cont’d)
NOTE: V enting requirements may affect location. Consult the V enting Manual for this heater before making final determination.
For best results, the heater should be placed with certain rules in mind. In general, a unit should be located from 8 to 12 feet (2.4-3.7M) above the floor . Units should always be arranged to blow toward or along exposed wall surfaces, if possible. Where two or more units are installed in the same room, a general scheme of air circulation should be maintained for best results.
Suspended heaters are most effective when located as close to the working zone as possible, and this fact should be kept in mind when determining the mounting heights to be used. However, care should be exercised to avoid directing the dis­charged air directly on the room occupants.
Partitions, columns, counters, or other obstructions should be taken into consider­ation when locating the unit heater so that a minimum quantity of airflow will be deflected by such obstacles.
When units are located in the center of the space to be heated, the air should be discharged toward the exposed walls. In large areas, units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the center of the area.
At those points where infiltration of cold air is excessive, such as at entrance doors and shipping doors, it is desirable to locate the unit so that it will discharge directly toward the source of cold air from a distance of 15 to 20 feet (4.6-6.1M).
CAUTION: Do not locate the heater where it may be exposed to water spray, rain, or dripping water.
Hazards of Chlorine ­applies to location of Model UDAS heater with regard to combustion air inlet
11. Hanging the Heater
WARNINGS: Check the supporting structure to be used to verify that it has sufficient load carry­ing capacity to support the weight of the unit. Suspend the heater only from the threaded nut retainers or with a man­ufacturer provided kit. Do NOT suspend from the heater cabinet.
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 10
The presence of chlorine vapors in the combustion air of gas-fired heating equip­ment presents a potential corrosion hazard. Chlorine found usually in the form of freon or degreaser vapors, when exposed to flame will precipitate from the com­pound, and go into solution with any condensation that is present in the heat ex­changer or associated parts. The result is hydrochloric acid which readily attacks all metals including 300 grade stainless steel. Care should be taken to separate these vapors from the combustion process. This may be done by wise location of the unit vent and combustion air terminals with regard to exhausters or prevailing wind directions. Chlorine is heavier than air. Keep these facts in mind when deter ­mining installation location of the heater in relation to building exhaust systems.
Before suspending the heater, check the supporting structure to be used to verify that it has sufficient load-carrying capacity to support the weight of the unit.
Model UDAP Size
lbs kg
Model UDAS Size
lbs 55 60 68 73 97 102 173 188 204 216 270 295 307 kg 25 27 31 33 44 46 78 85 93 98 122 134 138
When the heater is lifted for suspension, support the bottom of the heater with plywood or other appropriately placed material. If the bottom is not supported, damage could occur . Before hanging, verify that any screws used for holding ship­ping brackets were re-installed in the cabinet.
The heater is equipped for either two-point or four-point suspension. A 3/8"-16 threaded nut retainer is located at each suspension point. NOTE: Four-point sus­pension is required when installing an optional downturn nozzle. See Dimensions in Paragraph 5 and the illustration in FIGURE 7A.
30 45 60 75 100 125 150 175, 200 225 250 300 350 400
54 59 67 72 96 101 172 187 203 215 269 294 306 24 27 30 33 44 46 78 85 92 98 122 133 139
30 45 60 75 100 125 150 175, 200 225 250 300 350 400
Page 11
FIGURE 7A - Suspending
d
®
the Heater with Rods from the Threaded Nut Retainers (either two or four point suspension)
WARNING: Unit must be level for proper operation. Do not place or add additional weight to the suspended heater. Hazard Levels, page 2.
FIGURE 7B - Swivel Connectors to Suspend the Heater from 1” Pipe, Option CK8 (2-pt) or CK10 (4-pt)
Be sure the threaded hanger rods are locked to the heater as illustrated. Length of threaded rod extending into the heater MUST NOT exceed 1/2” (13mm).
Add a 3/8 nut and
washer to lock the
hanger rod to the heater.
3/8 threaded rod (field supplied)
Recommended maximum hanger rod length is 6 feet (1.8M).
If ordered with swivel connectors for 1” pipe, Option CK8 or CK10, attach the swivels at the threaded nut retainers. Suspend with 1” pipe. (See FIGURE 7B.)
Be sure the threaded swivel connectors are locked to the heater as illustrated.
Lock the swivel
connector to
the heater. The connector is threaded for
hanging from
a 1 pipe.
FIGURE 8 - Suspending the Heater using Option CK22, Ceiling Suspension Kit (no hanger rods)
FIGURE 9 - Model UDAS ­Plug the unused suspension points on the control side of the heater with the 1/2” long screws and flat washers. Find the screws and washers in the literature bag shipped inside the heater.
If ordered with a ceiling suspension kit, Option CK22, follow the illustrated in­structions in the kit. (See FIGURE 8.)
A vailable for Sizes 30-125. Allows the heater to be installed one inch from the ceiling.
NOR
Model UDAS - Whether using the suspension points or the hanger kit, when in­stalling a Model UDAS, the unused suspension points on the control side of the heater MUST be plugged. Plug these holes with the 1/2” long cap screws and flat washers shipped in the bag with the heater. (See FIGURE 9.)
Plug any unused suspension points on the control side with the 1/2long cap screws and flat washers provide
Control Side
Model UDAS
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 11
Page 12
12. Gas Piping and Pressures
W ARNING: This appliance is equipped for a maximum gas supply pressure of 1/2 psi, 3.5 kPa, or 14 inches water column. Supply pressure gr eater than 1/2 psi requir es installation of an additional lockup-type service regulator external to the unit.
WARNING: PRESSURE TESTING SUPPLY PIPING
Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve from the
gas supply line which is to be tested. Cap or plug the supply line. Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the
heater.
Sizing Gas Supply Line
WARNING: All components of a gas supply system must be leak tested prior to placing equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to comply could result in personal injury, property damage or death.
Length Diameter of Pipe
of 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
20' 92 56 190 116 350 214 730 445 1100 671 2100 1281 30' 73 45 152 93 285 174 590 360 890 543 1650 1007 40' 63 38 130 79 245 149 500 305 760 464 1450 885 50' 56 34 115 70 215 131 440 268 670 409 1270 775 60' 50 31 105 64 195 119 400 244 610 372 1105 674 70' 46 28 96 59 180 110 370 226 560 342 1050 641 80' 43 26 90 55 170 104 350 214 530 323 990 604
90' 40 24 84 51 160 98 320 195 490 299 930 567 100' 38 23 79 48 150 92 305 186 460 281 870 531 125' 34 21 72 44 130 79 275 168 410 250 780 476 150' 31 19 64 39 120 73 250 153 380 232 710 433 175' 28 17 59 36 110 67 225 137 350 214 650 397 200' 26 16 55 34 100 61 210 128 320 195 610 372
Note: When sizing supply lines, consider possibilities of future expansion and increa sed requirements.
Capacity of Piping
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Nat ural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Refer to National Fuel G as Code for addit ional information on line sizing.
All piping must be in accordance with requirements outlined in the National Fuel Gas Code ANSI/Z223.1a (latest edition) or CSA-B149.1 and B149.2 (See Para­graph 2). Gas supply piping installation should conform with good practice and with local codes. Support gas piping with pipe hangers, metal strapping, or other suitable material; do not rely on the heater to support the gas pipe.
The heater is orificed for operation with natural gas having a heating value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating value of 2500 (± 100) BTUH per cubic ft. If the gas at the installation does not meet these specifications, consult the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petro­leum gas or any other chemical constituents of the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the unit control system, as shown in FIGURE 10. Installation of a trap with a minimum 3" (76mm) drip leg is required.
The unit is equipped with a nipple that extends outside the cabinet. The gas con­nection is either 1/2” or 3/4”.
Gas Connection Size
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 12
Ga s Connection (inches) Size 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Natural 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 Propane 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Page 13
Leak-test all connections by brushing on a leak-detecting solution.
FIGURE 10 - Gas connection is at the pipe nipple that extends outside the cabinet
Illustration shows both a vertical and horizontal gas supply; requirements are the same.
Valve Outlet or Orifice Pressure Setting
NOTE: Gas Conversion Kits are available for changing from propane gas to natural gas or natural gas to propane gas. A factory­authorized conversion kit MUST be used.
Ground
Joint Union To Gas Valve (inside the cabinet)
Pipe nipple extending
outside the cabinet.
To Gas Valve (inside the cabinet)
Measuring valve outlet gas pressure cannot be done until the heater is in operation. It is included in the steps of the "Check-T est-Start" procedure in Paragraph 24. The following warnings and instructions apply .
Manual shutoff
Drip Leg
Ground
Joint
Union
From Gas Supply (horizontal or vertical)
Manual shutoff
Drip Leg
W ARNING: V alve outlet gas pr essure must never exceed 3.5" w .c. for natural gas and 10" w.c. for propane gas.
For Natural Gas: When the heater leaves the factory , the combination gas valve is
set so that the valve outlet gas pressure for a single stage valve or high fire of a two stage valve is regulated to 3.5" w.c. Inlet supply pressure to the valve for natural gas must be a minimum of 5" w .c. or as noted on the rating plate and a maximum of 14" w .c.
For Propane Gas: When the heater leaves the factory, the combination gas valve is set so that the valve outlet gas pressure for a single stage valve or high fire of a two stage valve is regulated to 10" w.c. Inlet supply pressure to the valve for pro­pane gas must be a minimum of 11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust valve outlet gas pressure, the inlet supply pressure must be within the specified range both when the heater is in operation and on standby . Incorrect inlet pressure could cause excessive valve outlet gas pressure immediately or at some future time. If natural gas supply pressure is too high, install a regulator in the supply line before it reaches the heater. If natural gas sup­ply pressure is too low, contact your gas supplier.
Check V alve Outlet Pressure (can only be done after heater is operating)
NOTE: If operating at high altitude, outlet pressure requires adjustment. Follow instructions on page 14.
Instructions
1) Locate the 1/8” output pressure tap on the valve (See FIGURE 11, page 14).
With the manual valve turned off to prevent flow to the gas valve, connect a manometer to the 1/8" pipe outlet pressure tap in the valve. NOTE: A manometer (fluid-filled gauge) is recommended rather than a spring type gauge due to the difficulty of maintaining calibration of a spring type gauge.
2) Open the manual valve and operate the heater. (NOTE: On Model UDAS, de-
press and hold the door safety switch.) Measure the outlet pressure of the gas valve. Normally when operating at sea level, adjustments should not be neces­sary to the factory setting. (For high altitude settings, see next paragraph.)
If adjustment is necessary, remove the cap from the adjustment screw(s). Set
pressure to correct settings by turning the regulator screw IN (clockwise) to increase pressure. Turn regulator screw OUT (counterclockwise) to decrease pressure.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 13
Page 14
12. Gas Piping
Instructions for High Altitude Derate
1. Determine the required valve outlet pressure for the elevation where the heater
and Pressures
Valve Outlet Pressure Settings by Elevation
(cont’d)
Derate by V alve Outlet Pressure Adjustment for High Altitude Operation
This adjustment can only be done after the heater is in operation. It is included in the startup procedures.
NOTE: If elevation is above 6000 ft (1830M), a high altitude pressure switch is required; see Paragraph 7.
FIGURE 11 - Top View of Valves showing Outlet Pressure Tap and Adjustment Locations
Single-Stage Valve
Output
Adjustment
Screw
Inlet
Pressure
Tap
1/8” Output
Pressure Tap
Two -Stage Valve
Adjust High
Pressure
Output
Inlet
Pressure
Tap
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 14
Adjust Low Pressure Output
1/8” Output
Pressure
Tap
2. Locate the 1/8” output pressure tap on the valve (See FIGURE 11). Turn the
3. Single Stage and Two Stage High Fire - Turn the knob on the top of the valve
4. Turn up the thermostat. (NOTE: On Model UDAS, depress and hold the door
5. With the heater operating determine that the inlet pressure to the heater for
6. Find the High Altitude Adjustment label in the plastic bag that contained these
will be operating. If unsure of the elevation, contact the local gas supplier.
Manifold Pressure Settings by Altitude for the UNI T ED STATE S
Alt itude Natural Gas (inches w.c.) Propane Gas (inches w.c.)
Feet Meters
0-2000 0-610 3.5 1 .8 10.0 5.0 2001-3000 611-915 3.1 1.6 8.8 4.4 3001-4000 916-1220 3.0 1.5 8.5 4.2 4001-5000 1221-1525 2.8 1.5 8.1 4.1 5001-6000 1526-1830 2.7 1.4 7.7 3.9 6001-7000 1831-2135 2.6 1.3 7.4 3.7 7001-8000 2136-2440 2.5 1.3 7.1 3.5 8001-9000 2441-2745 2.4 1.2 6.7 3.4
9001-10000 2746-3045 2.3 1.2 6.7 3.4
Ma nifold Pressure Settings by Altitude for CANADA
Alt itude Natural Gas (inches w.c.) Propane Gas (inches w.c.)
Feet Meters
0-2000 0-610 3.5 1.8 10.0 5.0 2001-4500 611-1373 2.8 1.5 8.1 4.1
Si ngl e Stage and
Two Stage High Fire
Si ngl e Stage and
Two Stage High Fire
Two Stage
Low Fire
Two Stage
Low Fire
Single St age and
Tw o Stage High Fir e
Single St age and
Tw o Stage High Fir e
Two Stage
Low Fire
Two Stage
Low Fire
knob on the top of the valve to “OFF”. Connect a manometer to the 1/8" pipe outlet pressure tap in the valve. Use a water column manometer that is readable to the nearest tenth of an inch.
to “ON”. Remove the cap from the pressure adjusting screw and adjust the gas train pressure to the pressure selected from the table above. Adjust pressure by turning the regulator screw IN (clockwise) to increase pressure or OUT (coun­terclockwise) to decrease pressure.
Two Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas valve and check the low fire pressure. Turn the regulator screw to adjust the low fire outlet pressure to the “Low Fire” pressure selected from the table. Re-con­nect the wire to the gas valve.
safety switch.) Cycle the burner once or twice to properly seat the adjustment spring in the valve.
Re-check the pressure(s). When the outlet pressure is right for the installation,
remove the manometer and replace the cap.
Check for leak at the pressure tap fitting.
natural gas is between 5 and 13.5 inches w.c. and for propane between 10 and
13.5 inches w .c. Take this reading as close as possible to the heater (Heaters are equipped with gas valves that have an inlet pressure tap.) If the inlet pressure is not within the specified range, the inlet pressure must be corrected and Steps 3 and 4 repeated.
instructions. Using a permanent marker, fill-in the appropriate information from the tables on page 15. Select a location for the label on the outside of the heater access panel so that it will be conspicuous to anyone operating or servicing the unit. Be sure the surface is clean and dry and adhere the label.
Page 15
High Altitude Capacity Changes
The input and/or the capacity of the heater changes with the derate. The tables below list inputs and capacities at altitudes from sea level to 10,000 ft (3045M).
BTUH Inputs and Capacities by Altitud e in the UNITE D STATES for Mod el UDAP and Model UDAS
Thermal
Output
Capacity
Siz e 75
Minimum
Input
ALTITUDE
Fe et Meters
Normal
Input
Input
Thermal
Output
Capacit y
Thermal
Output
Capacit y
Minimum
Input
Normal
Input
Thermal
Output
Capacit y
Minimum
Input
Normal
Siz e 30 Siz e 45 Siz e 60
Minimum
Input
Normal
Input
0-2000 0-610 30000 24600 30000 45000 37350 45000 60000 49800 42000 75000 62250 52500 2001-3000 611-915 28200 23124 28200 42300 35109 42300 56400 46812 39480 70500 58515 49350 3001-4000 916-1220 27600 22632 27600 41400 34362 41400 55200 45816 38640 69000 57270 48300 4001-5000 1221-1525 27000 22140 27000 40500 33615 40500 54000 44820 37800 67500 56025 47250 5001-6000 1526-1830 26400 21648 26400 39600 32868 39600 52800 43824 36960 66000 54780 46200 6001-7000 1831-2135 25800 21156 25800 38700 32121 38700 51600 42828 36120 64500 53535 45150 7001-8000 2136-2440 25200 20664 25200 37800 31374 37800 50400 41832 35280 63000 52290 44100 8001-9000 2441-2745 24600 20172 24600 36900 30627 36900 49200 40836 34440 61500 51045 43050
9001-10000 2746-3045 24000 19680 24000 36000 29880 36000 48000 39840 33600 60000 49800 42000
Fe et Meters
Size 100 Size 125
Size 150 Size 175
0-2000 0-610 105000 88200 73500 120000 100800 84000 150000 124500 105000 175000 145250 122500 2001-3000 611-915 98700 82908 69090 112800 94752 78960 141000 117030 98700 164500 136535 115150 3001-4000 916-1220 96600 81144 67620 110400 92736 77280 138000 114540 96600 161000 133630 112700 4001-5000 1221-1525 94500 79380 66150 108000 90720 75600 135000 112050 94500 157500 130725 110250 5001-6000 1526-1830 92400 77616 64680 105600 88704 73920 132000 109560 92400 154000 127820 107800 6001-7000 1831-2135 90300 75852 63210 103200 86688 72240 129000 107070 90300 150500 124915 105350 7001-8000 2136-2440 88200 74088 61740 100800 84672 70560 126000 104580 88200 147000 122010 102900 8001-9000 2441-2745 86100 72324 60270 98400 82656 68880 123000 102090 86100 143500 119105 100450
9001-10000 2746-3045 84000 70560 58800 96000 80640 67200 120000 99600 84000 140000 116200 98000
Fe et Meters
Size 200 Size 250 Size 300
Size 225
0-2000 0-610 200000 166000 140000 225000 186750 157500 250000 207500 175000 300000 249000 210000 2001-3000 611-915 188000 156040 131600 211500 175545 148050 235000 195050 164500 282000 234060 197400 3001-4000 916-1220 184000 152720 128800 207000 171810 144900 230000 190900 161000 276000 229080 193200 4001-5000 1221-1525 180000 149400 126000 202500 168075 141750 225000 186750 157500 270000 224100 189000 5001-6000 1526-1830 176000 146080 123200 198000 164340 138600 220000 182600 154000 264000 219120 184800 6001-7000 1831-2135 172000 142760 120400 193500 160605 135450 215000 178450 150500 258000 214140 180600 7001-8000 2136-2440 168000 139440 117600 189000 156870 132300 210000 174300 147000 252000 209160 176400 8001-9000 2441-2745 164000 136120 114800 184500 153135 129150 205000 170150 143500 246000 204180 172200
9001-10000 2746-3045 160000 132800 112000 180000 149400 126000 200000 166000 140000 240000 199200 168000
Fe et Meters
Size 400Size 350
0-2000 0-610 350000 290500 245000 400000 332000 280000 2001-3000 611-915 329000 273070 230300 376000 312080 263200 3001-4000 916-1220 322000 267260 225400 368000 305440 257600 4001-5000 1221-1525 315000 261450 220500 360000 298800 252000 5001-6000 1526-1830 308000 255640 215600 352000 292160 246400 6001-7000 1831-2135 301000 249830 210700 344000 285520 240800 7001-8000 2136-2440 294000 244020 205800 336000 278880 235200 8001-9000 2441-2745 287000 238210 200900 328000 272240 229600
9001-10000 2746-3045 280000 232400 196000 320000 265600 224000
BTUH Inp uts and Capacities b y A ltitude in CANADA for M o dels UD AP and UDAS
AL TITUDE
Feet Meters
Normal
Input
Thermal
Output
Capacity
Minimum
Input
Normal
Size 30 Size 45 Size 60
Input
Thermal
Output
Capacity
Minimum
Input
Normal
Input
Thermal
Outp ut
Capacity
Minimum
Input
Normal
Input
Thermal
Outp ut
Capacity
Size 75
Minimum
Input
0-2000 0-610 30000 24600 30000 45000 37350 45000 60000 49800 42000 75000 62250 52500 2001-4500 611-1373 27000 22140 27000 40500 33615 40500 54000 44820 37800 67500 56025 47250
Feet Meters
Size 150 Size 175Size 100 Size 125
0-2000 0-610 105000 88200 73500 120000 100800 84000 150000 124500 105000 175000 145250 122500 2001-4500 611-1373 94500 79380 66150 108000 90720 75600 135000 113400 94500 157500 132300 110250
Feet Meters
Size 200 Size 225 Size 250 Size 300
0-2000 0-610 200000 166000 140000 225000 186750 157500 250000 207500 175000 300000 249000 210000 2001-4500 611-1373 180000 151200 126000 202500 170100 141750 225000 189000 157500 270000 226800 189000
Feet Meters
Size 350 Size 400
0-2000 0-610 350000 290500 245000 400000 332000 280000 2001-4500 611-1373 315000 264600 220500 360000 302400 252000
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 15
Page 16
13. Burner
2
This heater has a one-piece TCORE
®
burner assembly (U.S. Patent No.
6,889,686) designed to provide controlled flame stability without lifting or flashback with either natural or propane gas.
The burner can be removed as a unit for inspection or service; see Maintenance Section for removal instructions.
14. Electrical Supply and Connections
CAUTION: Route wires so that they do not contact the flue wrapper or venter housing.
CAUTION: If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C, except for limit control, flame rollout, and sensor lead wires which must be 150°C. See Hazard Levels, page 2.
All electrical wiring and connections, including electrical grounding MUST be made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in Canada, with CSA Standard C22.1. In addition, the installer should be aware of any local ordinances or gas company requirements that might apply.
Check the rating plate on the heater for the supply voltage and current require­ments. A dedicated line voltage supply with disconnect switch should be run di­rectly from the main electrical panel to the heater. All external wiring must be
.
within approved conduit and have a minimum temperature rise rating of 60°C
Con­duit must be run so as not to interfere with the heater access panel. If the installation requires a stepdown transformer (Option CG), follow the instructions shipped with the option package for attaching the transformer to the heater.
The electrical supply enters at the rear of the heater (See FIGURE 13). Model UDAS includes a built-in disconnect switch (20A @ 115V; 10A @ 230V Rating). Model UDAS supply wiring connects to leads located inside a sealed electrical box. To maintain the sealing feature of the electrical box, always replace the cover plate. Model UDAP supply wiring connects directly to leads on the integrated cir ­cuit board.
The circuit board (See FIGURE 12) is located inside on the bottom of the control compartment. The circuit board is polarity sensitive. It is advisable to check the electrical supply to be certain that the black wire is the “hot” wire and that the white wire is the neutral wire. The supply connection made to “L1” on the circuit board must be the “hot” wire.
x
Spark
Transformer
Plug
Control
Fuse
FIGURE 12 - Supply Wiring Connections at the Circuit Board (DSI Integrated Control Module)
Connections
NOTE: Circuit board is polarity sensitive; “hot” wire MUST BE
connected to Terminal L1.
24V Control Wiring Connections
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 16
For all models, the terminal strip for 24 volt thermostat connections is located on the outside of the cabinet at the back of the heater (See FIGURE 13). Wires from the terminal strip are factory wired to the circuit board.
Supply
Wiring
Thermostat
Connections
Fan/Blower
Status Lights
Off
Delay
Page 17
15. Thermostat and Connections
Use either an optional thermostat available with the heater or a field-supplied 24­volt thermostat. Install according to the thermostat manufacturer's instructions, pay­ing particular attention to the requirements regarding the location of the thermostat.
Make sure that the heat anticipator setting on the thermostat is 0.6 amps (or in accordance with the amperage value noted on the wiring diagram of your heater).
Make thermostat connections at the terminal strip on the back of the heater. The strip has four terminals, R, G, W1, and W2; refer to the wiring diagram.
IMPORTANT: All units MUST be operated by a 24-volt thermostat. Never use a line voltage disconnect switch as a means of operating the heater . Operating Model Sizes 30-125 by means other than a 24-volt thermostat may result in the flame rollout switch tripping.
FIGURE 13 - Terminal Strip for 24-volt wiring is on the outside rear of the heater
NOTE: The size of heater illustrated has a vertical terminal strip. Some sizes have a horizontal terminal strip.
Rear View - Model UDAP
Terminal
Strip
Supply
Wiring
Entrance
Unit Mounted Thermostat ­Option CM3
Rear View - Model UDAS
Terminal
R
G W1 W2
Disconnect
If the heater was ordered with Option CM3, a kit for mounting the thermostat on the rear of the heater is shipped separately. Follow the instructions in the option package to attach the bracket.
Select a snap-action thermostat when using the unit mounted thermostat bracket. Do not use a mercury switch thermostat because the vibration may cause excessive unit cycling. Be careful with the thermostat leads; shorting the thermostat wires to a metal surface will cause the transformer to fail.
Strip
Built-in
Switch
Supply
Wiring
Entrance
R
G W1 W2
Multiple Heater Control - Option CL31 and Option CL32
If the heater was ordered with a multiple heater control option, one thermostat can be used to control up to six heaters. The option includes a 40VA transformer that replaces the standard transformer in the “master” unit and a relay assembly that attaches to the “slave” unit. Option CL31 provides for control of two heaters. If control of additional heaters is desired (up to six total), Option CL32 which is the relay assembly only must be added to each of the “slave” heaters.
The option packages are shipped separately and include complete instructions on installation and wiring.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 17
Page 18
16. Combustion Air Proving Switch (Pressure Switch)
DANGER: Safe operation of this unit requires proper venting flow. NEVER bypass combustion air proving switch or attempt to operate the unit without the venter running and the proper flow in the vent system. Hazardous conditions could result. See Hazard Intensity Levels, page 2.
The combustion air proving switch is a pressure sensitive switch that monitors air pressure to ensure that proper combustion airflow is available. On Model UDAP, the switch is a single pole/normally open device which closes when a negative pressure is sensed in the venter housing. On Model UDAS, the switch senses the differential pressure between the negative pressure in the venter housing and the pressure in the cabinet. (For switch location, see FIGURE 18, page 31.)
On startup when the heater is cold, the sensing pressure is at the most negative level, and as the heater and flue system warm up, the sensing pressure becomes less negative. After the system has reached equilibrium (about 20 minutes), the sensing pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pressure to be outside the switch setpoint, the pressure switch will function to shutoff the main burner. The main burner will remain off until the system has cooled and/or the flue system resistance is reduced.
The two T ables on the left below list the approximate water column negative pres­sure readings and switch setpoints for sea level operating conditions for Model UDAP and Model UDAP-CV heaters. The Table on the right lists the approximate water column differential pressure readings and switch setpoints for sea level op­erating conditions for Model UDAS heaters.
Pressure Switch Settings
Model
UDAP
150, 175 0.75 0.65 0.40 0.58 Green 197030 150, 175 0.75 0.60 0.40 0.58 Green 197030 200, 225 2.20 1.50 1.10 1.30 Blue 201158 200, 225 2.20 1.50 1.10 1.30 Blue 201158 250, 300 2.30 1.60 1.10 1.30 Blue 201158 250, 300 2.30 1.60 1.10 1.30 Blue 201158 350, 400 2.60 1.80 1.40 1.60 Red 201159 350, 400 2.60 1.80 1.40 1.60 Red 201159
Mo del UDA P-CV
with Opt AV6
17. Limit Control
Startup Equilibrium Setpoint Setpoint Startup Equilibrium Setpoint Setpoint
Cold Hot OFF ON Cold Hot OFF ON
Negative Pressure Measured in " w.c.
30 1.00 0.78 0.40 0.58 Green 197030 30 1.00 0.78 0.65 0.83 Yellow 197028 45 0.95 0.75 0.40 0.58 Green 197030 45 1.05 0.80 0.65 0.83 Yellow 197028 60 1.00 0.78 0.50 0.68 Orange 196388 60 1.10 0.85 0.65 0.83 Y ellow 197028
75 1.00 0.85 0.50 0.68 Orange 196388 75 1.10 0.85 0.65 0.83 Y ellow 197028 100 0.85 0.72 0.50 0.68 Orange 196388 100 0.85 0.72 0.55 0.73 White 196362 125 0.75 0.60 0.40 0.58 Green 197030 125 0.75 0.60 0.45 0.63 Pink 197032
Startup Equilibrium S etpoint Setpoint
Cold Hot OFF ON Negative Pressure Measured in " w.c.
30 45 60 75
100
1.10 0.84 0.65 0.83 Y ellow
1.10 0.81 0.50 0.68 Orange
0.92 0.75 0.60 0.78 Lt Blue
0.97 0.78 0.60 0.78 Lt Blue
0.88 0.71 0.55 0.73 White
All units are equipped with a temperature activated auto reset limit control. The
Label Color
Switch
P/N
Label
Color
Model
U DAS
Switch
P/N
197028 196388 197029 197029 196362
Differential Pressure Measured in " w.c.
control is factory set and is non-adjustable. If the setpoint is reached, the limit control will interrupt the electric supply to the gas valve. This safety device pro­vides protection in the case of motor failure or lack of airflow due to a restriction at the inlet or outlet. (For location, see FIGURE 18, page 31.)
Label
Color
Switch
P/N
CAUTION: The auto reset limit contr ol will continue to shut down the heater until the cause is corrected. Never bypass the limit control; hazardous conditions could result. See Hazard Intensity Levels, page 2.
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 18
Page 19
18. Flame Rollout Switch ­Sizes 30-125
only
Sizes 30-125 are equipped with a temperature activated manually reset flame rollout switch. The flame rollout switch is located at the top of the burner assembly. It is factory set and is non-adjustable. If the setpoint is reached, the flame rollout acts to interrupt the electric supply to the gas valve. If the flame rollout switch activates, identify and correct the cause before resetting the switch. Refer to the Mainte­nance Section for information on probable causes and instructions on resetting the flame rollout switch. (For location, see FIGURE 18, page 31.)
DANGER: If the manual reset flame rollout switch activates, identify and correct the cause before resetting the switch. Never bypass the flame rollout switch; hazardous conditions could result. See Hazard Intensity Levels, page 2.
19. Door Switch
- Model UDAS only
20. Ignition System
FIGURE 14 – DSI Integrated Control Module (circuit board)
x
Spark
Transformer
Plug
Control
All sizes of Model UDAS heaters are equipped with a door switch which prevents the heater from operating when the service door panel is open. The service panel of a Model UDAS is equipped with a pliable gasket material that fully seals the door to provide added protection from building air entering the combustion zone of the heater. (For switch location, see FIGURE 18, page 31.)
This heater is equipped with a direct spark integrated control module (circuit board). The module monitors the safety devices and controls the operation of the fan and venter motors and the gas valve between heat cycles.
Fuse
Thermostat
Connections
Fan/Blower
Off
Delay
LED lights are visible through viewport on Model UDAS. Remove door panel to view LED lights on Model UDAP.
Dip Switch
Status Lights
Control Status - Green LED Codes
Steady ON....... Normal Operation, No call for heat
Fast Flash........ Normal Operation, Call for heat
1 Flash ............ System Lockout, Failed to detect or sustain
flame
2 Flashes ......... Pressure Switch Did Not Close within 30
Seconds of Venter Motor
3 Flashes ......... High Limit or Flame Rollout Switch Open
4 Flashes ......... Pressure switch is closed before venter
motor is energized
Steady OFF ..... Blown Fuse, No Power, or Defective Board
LED Lights
Flame Status - Yellow LED Codes
Steady ON....... Flame is sensed
Slow Flash ...... Weak flame (current below 1.0
microamps ±50%)
Fast Flash........ Undesired Flame (valve open
and no call for heat)
Fan/Blower OFF Delay Settings (dip switches)
SW-1 SW-2 Time Off Off 120 seconds (factory setting) Off On 90 seconds On Off 160 seconds On On 180 seconds
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 19
Page 20
20. Ignition System (cont’d)
Normal Heat Cycle Operating Sequence
LED lights are visible through viewport on Model UDAS. Remove door panel to view LED lights on Model UDAP.
1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal. The control checks to see that the limit switch is closed and the pressure switch is open. If the limit switch is open, the control responds as defined in the “Abnormal Heat Cycle, Limit Switch Operation”. If the pressure switch is closed, the control will do four flashes on the green LED and wait indefinitely for the pressure switch to open. If the pressure switch is open, the control proceeds to prepurge.
2) Prepurge - The control energizes the venter motor and waits for the pressure switch to close. If the pressure switch does not close within 30 seconds of the venter motor energizing, the control will do two flashes on the green LED. The control will leave the venter motor energized indefinitely as long as the call for heat remains and the pressure switch is open.
When the pressure switch is proven closed, the control begins the prepurge time. If flame is present any time while in prepurge, the prepurge time is restarted. If flame is present long enough to cause lockout, the control responds as defined in “Fault Modes, Undesired Flame”.
The control runs the venter motor for a 20 second prepurge time, then proceeds to the ignition trial period.
3) Ignition Trial Period - The control energizes the spark and main gas valve. The venter remains energized. If flame is sensed during the first 16 seconds, the spark is de-energized and the control proceeds to heat fan/blower on delay. If flame has not been sensed during the first 16 seconds, the control de-energizes the spark output and keeps the gas valve energized for an additional one second flame proving period. If flame is not present after the flame proving period, the control de-energizes the gas valve and proceeds with ignition re-tries as specified in “Ab­normal Heat Cycle, Ignition Re-try”. If flame is present, the control proceeds to the fan/blower on delay.
4) Fan/Blower On Delay - The control waits for 30 seconds from the time the gas valve opened and then energizes the fan/blower motor. The gas valve and venter motor remain energized. The control proceeds to steady heat mode.
5) Steady Heat - Control inputs are continuously monitored to ensure limit and pressure switches are closed, flame is established, and the thermostat call for heat remains. When the thermostat call for heat is removed, the control de-energizes the gas valve and begins post-purge and fan/blower off delay timing.
6) Post Purge - The venter motor output remains on for a 45 second post-purge period after the thermostat is satisfied.
7) Fan/Blower Off Delay - The fan/blower motor is de-energized after a blower off delay as selected by the dip switches. Timing begins when the thermostat is satisfied. Delay times are as follows:
SW1 SW2 Time
OFF OFF 120 seconds (default when shipped) OFF ON 90 seconds ON OFF 160 seconds ON ON 180 seconds
Abnormal Heat Cycle Functions
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 20
Interrupted Thermostat Call for Heat - If the thermostat demand for heat is
removed before the flame is recognized, the control will run the venter motor for the post purge period and de-energize all outputs.
If the thermostat demand for heat is removed after successful ignition, the control will de-energize the gas valve, run the venter motor through post purge, and run the fan/blower motor on heat speed for the selected delay off time.
Page 21
Ignition Retry - If flame is not established on the first trial for ignition period, the control de-energizes the gas valve and the venter motor remains energized for an inter-purge period of 10 seconds. The spark and gas valve are then re-energized, and the control initiates another trial for ignition.
If flame is not established on the second trial for ignition, the control de-energizes the gas valve, energizes the fan/blower motor on heat speed, and venter motor remains energized. The fan/blower motor is shut off after the longest selectable fan delay time (180 seconds). When the fan/blower motor de-energizes, the spark and gas valve are re-energized and the control initiates another trial for ignition. (This fan delay is self-healing feature for an open auxiliary limit switch).
If flame is not established on the third trial for ignition period, the control de­energizes the gas valve, and the venter motor remains energized for an inter-purge period of 10 seconds. The control then re-energizes the gas valve and spark and initiates another trial for ignition.
If flame is not established on the fourth trial for ignition (initial try plus 3 re-tries), the control de-energizes the gas valve and goes into lockout. The control goes to one flash on the green LED to indicate ignition failure lockout.
Limit Switch Operation - The limit switch is ignored unless a call for heat is present (W energized). If the limit switch is open and a call for heat is present, the control de-energizes the gas valve and turns the fan/blower motor on heat speed and runs the venter motor.
When the switch re-closes or the call for heat is lost, the control runs the venter motor through post purge and runs the blower/fan motor through the selected fan off delay. The control will return to normal operation after fan off delay is com­pleted.
Pressure Switch - If the pressure switch opens before the trial for ignition period, the venter motor will run through the pressure switch recognition delay (2 sec­onds), the gas valve will be de-energized, and the venter motor will run through the postpurge time. The control will re-start the heat cycle at the pressure switch proving state if the call for heat still exists.
Pressure switch opening for less than 2 seconds during the trial for ignition period shall not interrupt the heat cycle. (Gas valve will de-energize while the pressure switch is open.)
If the pressure switch opens after a successful ignition, the control will de-energize the gas valve. If flame is lost before the end of the 2 second pressure switch recog­nition delay, the control will respond to the loss of flame. If the pressure switch remains open for 2 seconds and the flame remains, the control de-energizes the gas valve, the venter motor runs through post-purge, and the fan/blower motor runs on heat speed through the selected fan off delay. When the fan off delay is over, the fan/blower motor is de-energized, and a heat cycle is begun if the call for heat still exists.
Continuous Fan Operation
When the thermostat calls for continuous fan (G) without a call for heat, the fan motor is energized after a .25 second delay . NOTE: This brief on delay is to allow the “G” terminal to energize slightly before “Y” and an external changeover relay to switch from “G” to “W” without causing momentary glitches in the fan/blower output. The fan remains energized as long as the call for fan remains without a call for heat.
If a call for heat (W) occurs during continuous fan, the fan/blower will de-ener­gize.
A call for fan is ignored while in lockout.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 21
Page 22
20. Ignition System (cont’d)
Fault Modes
Undesired Flame - If flame is sensed longer than 20 seconds while the gas valve is de-energized, the control shall energize the venter motor and fan/blower motor on heat speed. When flame is no longer sensed, the venter motor will run through postpurge, and the fan/blower motor will run through the selected heat fan off delay time. The control will do a soft lockout, but will still respond to open limit and flame. The FLAME (yellow) LED shall flash rapidly when lockout is due to undesired flame.
Gas Valve Relay Fault - If the control senses the gas valve as energized for more than one second when the control is not attempting to energize the gas valve, or the gas valve is sensed as not energized when it is supposed to be energized, then the control will lockout with green LED off. The control assumes either the contacts of the relay driving the gas valve have welded shut, or the sensing circuit has failed. The venter motor is forced off to open the pressure switch to stop gas flow unless flame is present.
If the gas valve was sensed as closed when it should be open, and has not de­energized after the venter motor was shutoff for 15 seconds, then the venter motor is re-energized to vent the unburned gas.
Lockout
21. Gas V alve
Soft Lockout - The control shall not initiate a call for heat or call for continuous fan while in lockout. The control will still respond to an open limit and undesired flame. Lockout shall automatically reset after one hour. Lockout may be manually reset by removing power from the control for more than one second or removing the thermostat call for heat for more than one and less than 20 seconds.
Hard Lockout - If the control detects a fault on the control board, the status LED will be de-energized, and the control will lockout as long as the fault remains. A hard lockout will automatically reset if the hardware fault clears.
Power Interruption - During a momentary power interruption or at voltage levels below the minimum operating voltage (line voltage or low voltage) the system will self-recover without lockout when voltage returns to the operating range.
Power interruptions of less than 80mS shall not cause the control to change operat­ing states. Power interruptions greater than 80mS may cause the control to inter­rupt the current operating cycle and re-start.
The main operating gas valve is powered by the 24-volt control circuit through the thermostat and safety controls. The main control valve is of the diaphragm type providing regulated gas flow preset at the factory . (For location, see FIGURE 18, page 31.)
WARNING: The operating valve is the prime safety shutoff. All gas supply lines must be free of dirt or scale before connecting the unit to ensure positive closure. See Hazard Levels, page 2.
22. Fan Motor
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 22
The fan motor is equipped with thermal overload protection of the automatic reset type. Should the motor refuse to run, it may be because of improper current char­acteristics. Make certain that the correct voltage is available at the motor.
NOTE: If the unit is equipped with an optional totally enclosed motor or optional voltage, the horsepower may be larger than the standard motor . Refer to the motor nameplate to verify horsepower.
Page 23
23. Wiring Diagrams
FIGURE 15A - Typical Wiring Diagram for Model UDAP or Model UDAS, Single Stage
(OPT CL3) T874F OR (OPT CL1) W.R.
(OPT CL2) W.R. 1C30-341 THERMOSTAT
1C30-341 THERMOSTAT (SEE NOTE #8)
W-S23-6 SUBBASE (SEE NOTE #8)
SYSTEM TRANSFORMER
R
24V
BR
SW1
FUSE
3.0 AMP ATO OR ATC
LED FLASH CODES
GREEN LED
NORMAL OPERATION NO CALL FOR HEATSTEADY ON
FAST FLASH
1 FLASH
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
SLOW FLASH WEAK FLAME
NORMAL OPERATION CALL FOR HEAT
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS OF VENTER ENERGIZED
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED
INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
FLAME SENSEDSTEADY ON
UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)FAST FLASH
Y
LA
E
FF D
O
N
A
F
S W 1
E
TIM
1
2
FF
O
FF
O
N
O
N
O
DSI CONTROL
N
O
FF
O
FF
O
N
O
90
120
160
180
Y
VOLT
115/208/230
BK
L1 NEUTRAL NEUTRAL L1COMSEC
LED
TEST
OKFLAME
LED
GY
Y
Y
BL
BR
R
BR
FACTORY WIRING
FIELD WIRING
OPTIONAL FACTORY WIRING
WIRE NUT
P3-1
P3-2
P3-3
P3-4
R
P3-5
P1-8
P1-3
P1-6
P1-5
P1-4
P1-2
P1-7
P1-9
Y
G
W
R
C
W
R
TERMINAL STRIP
G
G
W1
W
R
R
W2
PR
Y
DOOR INTERLOCK
(UDAS ONLY)
R
LIMIT CONTROL
R R
R R
FLAME ROLLOUT
(MODELS 30-125 ONLY)
PRESSURE SWITCH
Y
GAS VALVE
BL
FLAME
ELECTRODE
FLAME
GROUND
LINE/1/60
W
(UDAS ONLY)
DISCONNECT SWITCH
BK BK
NEUTRAL
EAC/BLO
IND
NEUTRAL
SPARK
TRANSFORMER
W
BK
BK
W
G
GRD
SCREW
FAN MOTOR
BK
BR
CAPACITOR
(SEE NOTE #6)
W
(SEE NOTE #7)
SPARK GAP
G
G
W
G
BR/W
VENTER MOTOR
BR/W
CAPACITOR
BK
G
BR
1. SET THERMOSTAT AT LOWEST SETTING, (FAN SWITCH AT "AUTO" POSITION, OPTION CL2 ONLY).
2. TURN ON MANUAL GAS VALVE.
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).
9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION, OPTION CL2 ONLY.
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS 150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT ANTICIPATOR AT 0.6 AMPS.
OPERATING SEQUENCE
MOTOR IS ENERGIZED.
NOTES
FIELD CONTROL WIRING
TOTAL WIRE
LENGTH
150' 250' 350'
DISTANCE FROM UNIT TO CONTROL
WIRING CODE
BLACK - BK BROWN - BR RED - R ORANGE - O YELLOW - Y GREEN - G BLUE - BL PURPLE - PR WHITE - W
75' 125' 175'
UDAP & UDAS SERIES
WD# 185139 REV #2 AG1
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 23
MIN. RECOMMENDED
WIRE GAUGE
#18 GA. WIRE #16 GA. WIRE #14 GA. WIRE
Page 24
23. Wiring Diagrams (cont’d)
FIGURE 15B - Typical Wiring Diagram for Model UDAP or Model UDAS, Single Stage with Optional Air Recirculation
LINE/1/60
W
(UDAS ONLY)
DISCONNECT SWITCH
BK BK
NEUTRAL
EAC/BLO
IND
NEUTRAL
SPARK
TRANSFORMER
W
BK
BK
W
G
GRD
SCREW
FAN MOTOR
BK
BR
CAPACITOR
(SEE NOTE #6)
W
(SEE NOTE #7)
SPARK GAP
BR/W
CAPACITOR
W1
G
W2
(OPT CL18) T874F THERMOSTAT
RH
Q674C SUBBASE (SEE NOTES #8 AND #9)
RC
G
W1
R
W2
TERMINAL STRIP
PR
Y
DOOR INTERLOCK
(UDAS ONLY)
R R
LIMIT CONTROL
R R
R R
FLAME ROLLOUT
(MODELS 30-125 ONLY)
ELECTRODE
GROUND
PRESSURE SWITCH
Y
GAS VALVE
BL
FLAME
FLAME
BR
FACTORY WIRING
FIELD WIRING
OPTIONAL FACTORY WIRING
WIRE NUT
P3-1
P3-2
P3-3
P3-4
P3-5
P1-8
P1-3
P1-6
Y
P1-5
Y
P1-4
BL
P1-2
P1-7
R
P1-9
BR
SYSTEM TRANSFORMER
R
Y
G
W
R
C
3.0 AMP
FAST FLASH
1 FLASH
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
SLOW FLASH WEAK FLAME
FAN O
E
TIM
90
120
160
180
Y
24V
BR
SW1
FUSE
ATO OR ATC
LED FLASH CODES
GREEN LED
NORMAL OPERATION NO CALL FOR HEATSTEADY ON
NORMAL OPERATION CALL FOR HEAT
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS OF VENTER ENERGIZED
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED
INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
FLAME SENSEDSTEADY ON
UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)FAST FLASH
FF DELAY
FF
O
O
FF
O
O
N
O
O
N
O
O
DSI CONTROL
FF
FF
N
N
VOLT
115/208/230
BK
L1 NEUTRAL NEUTRAL L1COMSEC
LED
TEST
LED
OKFLAME
GY
G
W
VENTER
MOTOR
BR/W
G
G
BK
G
BR
1. SET THERMOSTAT AT LOWEST SETTING, FAN SWITCH AT "AUTO" POSITION.
2. TURN ON MANUAL GAS VALVE.
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE FAN MOTOR.
6. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
7. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
8. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION.
9. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS 150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT SECOND STAGE ANTICIPATOR AT 0.6 AMPS. AND FIRST STAGE ANTICIPATOR AT MINIMUM.
9. JUMPER THERMOSTAT TERMINALS G TO W1 AND RH TO RC IF FAN CONTROL FROM THERMOSTAT FAN SWITCH IS DESIRED.
OPERATING SEQUENCE
NOTES
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 24
FIELD CONTROL WIRING
TOTAL WIRE
LENGTH
150' 250' 350'
DISTANCE FROM UNIT TO CONTROL
WIRING CODE BLACK - BK BROWN - BR RED - R ORANGE - O YELLOW - Y GREEN - G BLUE - BL PURPLE - PR WHITE - W
75' 125' 175'
UDAP & UDAS SERIES WD# 185306 REV#3
MIN. RECOMMENDED
WIRE GAUGE
#18 GA. WIRE #16 GA. WIRE #14 GA. WIRE
Page 25
FIGURE 15C - Typical Wiring Diagram for Model UDAP or Model UDAS, Two Stage Gas Valve
W1
FACTORY WIRING
R
(OPT CL7) T874F THERMOSTAT
W2
Q674G SUBBASE (SEE NOTE #8)
G
W1
RH
(OPT CL18) T874F THERMOSTAT
RC
Q674C SUBBASE (SEE NOTE #8 AND #9)
W2
ALT. HONEYWELL TWO STAGE
GAS VALVE
BL
MV
STG
LOW
BR
C
STG
HIGH
O
HI
1. SET THERMOSTAT AT LOWEST SETTING, (FAN SWITCH AT "AUTO" POSITION, OPTION CL18 ONLY).
2. TURN ON MANUAL GAS VALVE.
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT LOW RATE.
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN
8. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT, FIRING UNIT AT FULL RATE.
9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION, OPTION CL18 ONLY.
10. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS
150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT FIRST STAGE ANTICIPATOR AT 0.6 AMPS AND SECOND STAGE ANTICIPATOR AT 0.2 AMPS.
9. JUMPER THERMOSTAT TERMINALS RH TO RC.
TERMINAL STRIP
G
PR
W1
R
W2
HONEYWELL
O
OPERATING SEQUENCE
Y
R R
O
TWO STAGE GAS VALVE
LO
STG
LOW
C
STG
HIGH
HI
NOTES
DOOR INTERLOCK
(UDAS ONLY)
LIMIT CONTROL
FLAME ROLLOUT
(MODELS 30-125 ONLY)
ELECTRODE
FIELD WIRING
OPTIONAL FACTORY WIRING
WIRE NUT
R R
R R
PRESSURE SWITCH
Y
BL
BR
FLAME
FLAME
GROUND
MOTOR IS ENERGIZED.
P3-1
P3-2
P3-3
P3-4
P3-5
P1-8
P1-3
P1-6
Y
P1-5
Y
P1-4
P1-2
P1-7
R
P1-9
BR
SYSTEM TRANSFORMER
Y
G
W
R
C
TIM
120
160
180
Y
R
24V
BR
VOLT
115/208/230
BK
W
SW1
L1 NEUTRAL NEUTRAL L1COMSEC
NEUTRAL
EAC/BLO
FUSE
3.0 AMP ATO OR ATC
LED FLASH CODES
GREEN LED
NORMAL OPERATION NO CALL FOR HEATSTEADY ON
FAST FLASH
1 FLASH
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
SLOW FLASH WEAK FLAME
FAST FLASH
FAN O
E
90
NORMAL OPERATION CALL FOR HEAT
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS OF VENTER ENERGIZED
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED
INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
FLAME SENSEDSTEADY ON
UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)
ELAY
FF D
S W
1
FF
O
FF
O
N
O
N
O
DSI CONTROL
2
N
O
FF
O
FF
O
N
O
LED
TOTAL WIRE
LENGTH
150' 250' 350'
TEST
OKFLAME
LED
GY
WIRING CODE
BLACK - BK BROWN - BR RED - R ORANGE - O YELLOW - Y GREEN - G BLUE - BL PURPLE - PR WHITE - W
NEUTRAL
SPARK
TRANSFORMER
FIELD CONTROL WIRING
DISTANCE FROM UNIT TO CONTROL
UDAP & UDAS SERIES WD# 185244 REV #4 AG2
LINE/1/60
G
GRD
(UDAS ONLY)
BK BK
BK
W
W
BK
SCREW
FAN MOTOR
BK
(SEE NOTE #6)
SPARK GAP
DISCONNECT SWITCH
IND
75' 125' 175'
G
G
W
G
BR
BR/W
CAPACITOR
VENTER
MOTOR
W
BR
BR/W
CAPACITOR
(SEE NOTE #7)
MIN. RECOMMENDED
WIRE GUAGE
#18 GA. WIRE #16 GA. WIRE #14 GA. WIRE
BK
G
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 25
Page 26
24. Check Installation and Startup
Check the installation prior to startup:
Check to be sure that all screws used to hold shipping brackets were re-
installed in the heater cabinet.
Check suspension. Unit must be secure and level.
 
Check clearances from combustibles. Requirements are in Paragraph 8.
Check vent system to be sure that it is installed according to the instructions
in the appropriate Vent Installation Manual as listed in Paragraph 1.
Check piping for leaks and proper gas line pressure. Bleed gas lines of
trapped air. See Paragraph 12.
Check electrical wiring. Be sure all wire gauges are as recommended. A
service disconnect switch should be used. Verify that fusing or circuit break­ers are adequate for the load use.
Check polarity. Verify that line voltage exists between the black “L1” and
earth ground.
If installed in California, verify that California Warning Label is displayed
Heater Startup:
WARNINGS: For your safety, read before operating. If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury, or loss of life.
• This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
• Before operating, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier fr om a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call your fire department.
• Use only your hand to turn the gas control ON/OFF knob on the gas valve. Never use tools. If the valve ON/OFF knob will not turn by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Operating Instructions and Operating Sequence
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 26
1. Set thermostat at lowest setting.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which automatically lights
• Should overheating occur, or the gas supply fail to shut off, turn off the manual gas valve to the appliance before shutting off the electrical supply.
• Do not use this appliance if any part has been under water. Imme­diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
the burner. Do not try to light the burner by hand. Open the access door and locate the gas control (ON/OFF) knob on the gas valve. (See FIGURE 16.)
Page 27
FIGURE 16 - Gas Valve ON/OFF Control Knob
Top View
Gas Control
Knob
(shown in the
ON position)
Gas Flow
Side View
Gas Flow
4. Turn the gas control knob clockwise to "OFF".
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near
the floor. If you smell gas, ST OP! and follow the steps in the WARNINGS printed above or on the Operating Label on the heater. If you do not smell gas, proceed to the next step.
6. Turn the gas control knob counterclockwise to "ON".
7. Close the access door.
8. Turn on the electric power to the heater.
9. Set the thermostat to the desired setting. NOTE: If the appliance does not operate, follow the instructions "To Turn Off
Gas to Appliance" printed below (and on the Operating Label on the heater) and call your service technician.
10. Thermostat calls for heat, energizing the venter motor.
11. Venter pressure switch closes, firing the unit.
12. Burner flame is sensed and in 30 seconds after the gas valve is energized, the fan motor is energized.
13. If the flame is extinguished during the main burner operation, the integrated control system closes the main valve and must be reset by interrupting power to the control circuit. (See lighting instructions on the heater.).
Check installation after startup:
TO TURN OFF GAS TO THE APPLIANCE
1) Set thermostat to lowest setting
2) If service is to be performed, turn off all electric power to the appliance.
3) Open the access door.
4) Turn the gas control knob clockwise to "OFF". Do not force.
5) Close the access door.
Vent System Testing Procedure - Model UDAP
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 or CSA B149.1 and B149.2, Installation Code for Gas Burning Appliances and Equipment, and the venting installation manual. Determine that there is no blockage or restric­tion, leakage, corrosion or other deficiencies that could cause an unsafe condition.
3. In so far as practical, close all building doors and windows and all doors between the space where the heater is and other spaces of the building. Turn on clothes dryers and exhaust fans, such as range hoods and bath­room exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Light the heater following the lighting instructions. Adjust the thermostat for continued operation. Verify that combustion products are venting properly. After determining that the heater vents properly, return doors, windows, exhaust fans, and fireplace dampers to their previous conditions. If improper venting is observed, the venting system must be corrected.
With the unit in operation, measure valve outlet gas pressure. If operated at
high altitude, adjust outlet gas pressure for altitude. See information and instructions in Paragraph 12.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 27
Page 28
Turn the unit off and on, pausing two minutes between each cycle. Observe
24. Startup
for smooth ignition.
(cont’d)
Place the "Owner's Envelope" containing the Limited Warranty, this booklet,
the venting manual, and any control or optional information in an accessible location near the heater. Follow the instructions on the envelope.
DANGER: The gas burner in this gas-fired equipment is designed and equipped to pr ovide safe controlled complete combustion. However, if the installation does not permit the burner to receive the proper supply of combustion air , complete combustion may not occur. The result is incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe operation of indirect-fired gas burning equipment requires a properly operating vent system that vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.
Always comply with the combustion air requirements in the installation codes and in Paragraph
9. Combustion air at the burner should be regulated only by manufactur er-provided equipment. NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER. Model UDAP units installed in a confined space must be supplied with air for combustion as required by Code and in Paragraph 9 of this heater installation manual. MAINTAIN THE VENT OR VENT/COMBUSTION AIR SYSTEM IN STRUCTURALLY SOUND AND PROPER OPERATING CONDITION.
MAINTENANCE AND SERVICE
25. Maintenance Schedule
NOTE: If replacement parts are required, use only factory-authorized parts.
WARNING: If you turn off the power supply, turn off the gas. See Hazard Levels, page 2.
The material contained in the MAINTENANCE AND SERVICE Section of this manual is designed to aid a qualified service person in maintaining and servicing this equipment. This heater will operate with a minimum of maintenance. To en­sure long life and satisfactory performance, a heater that is operated under normal conditions should be inspected and cleaned at the start of each heating season. If the heater is operating in an area where an unusual amount of dust or soot or other impurities are present in the air, more frequent maintenance is recommended. When any service is completed, be careful to reassemble correctly to ensure that no unsafe conditions are created. When re-lighting, always follow the lighting instructions on the heater.
Maintenance Schedule - The following procedures should be carried out at least annually (See FIGURE 18 and Paragraphs 26-39.):
• Clean all dirt, lint, and grease from the combustion air opening (UDAP) and venter assembly .
• Clean all dirt, lint, and grease from the fan blade, fan guard, and motor.
• Check the heat exchanger both internally and externally.
• Check the burner for scale, dust, or lint accumulation. Clean if needed.
• Check the vent or vent/combustion air system for soundness. Clean openings. Replace any parts that do not appear sound.
• Check the wiring for any damaged wire. Replace damaged wiring. (See Para­graph 14 for replacement wiring requirements.)
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 28
Page 29
26. Heat Exchanger Maintenance
27. Burner
Maintenance
Burner Removal Instructions (Refer to FIGURE 17.)
FIGURE 17 - Burner Removal (UDAP illustrated; same process for both UDAP and UDAS)
2
This heater is equipped with a TCORE
6,889,686). Remove any external dirt or dust accumulation. V isually check the heat exchanger
for cracks and holes. If a crack or hole is observed, replace the heat exchanger. NOTE: Inspection of the lower portion of the heat exchanger is done with the
burner removed. See the Burner Service section below for information on inspect­ing the lower portion of the heat exchanger.
This heater is equipped with a TCORE
Inspect the burner/control compartment annually to determine if cleaning is neces­sary. If there is an accumulation of dirt, dust, and/or lint, clean the compartment and follow the instructions below to remove and clean the burner.
®
heat exchanger (U.S. Patent No.
2
®
burner (U.S. Patent No. 6,889,686).
CAUTION: Use of eye protection is recommended.
1. Outside the cabinet, shut the gas supply off at the manual valve ahead of the
union.
2. Turn off electric supply.
3. Disconnect the gas supply at the union outside of the cabinet.
4. Remove the access panel.
5. Disconnect the Gas Train and Move Out of the Way - At the gas valve,
mark and disconnect the wires. Carefully remove the burner orifice and orifice adapter locking nut. Slide the orifice adapter out through the bracket on the burner pushing the gas train to the right. This will move the gas train out of the way.
6. Move the Control Assembly - Remove the two screws holding the control
assembly bracket. Being careful not to disconnect any wires, slide the control assembly to the right.
7. Remove Secondary Air Baffles (Sizes 60-400 only) - Vertical along the right
side of the burner, locate the flat plate(s) identified as the secondary air baffle(s). The quantity of baffles could be one to four depending on heater
Burner Assembly
Secondary Air Baffle (Qty varies per size.) Mark locations before removing.
Burner Body Support (at least two per unit) - Remove screw attaching to secondary air shield. Support remains attached to burner.
Secondary Air Shield
Burner
Orifice
Venturi Tube
Slide right; rotate inward; pull out
Slide Right
Control Bracket Screws ­Loosen bracket; slide right.
Gas Valve
Disconnect gas train at orifice and outside the heater; slide to the right.
Orifice Adapter Locking Nut
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 29
Page 30
27. Burner Maintenance (cont’d)
Burner Removal (cont’d)
size. Each baffle is held in place by one screw. For re-assembly, on the secondary air shield, mark the location (top and bottom) of each baffle.
Remove all baffles.
8. Remove Burner Assembly
a) Locate the burner body supports. Depending on the size, the burner will
have two or more supports. At each support, remove the one screw that attaches it to the secondary air shield
b) Holding the venturi tube, slide the entire burner assembly slightly to the
right to disengage the burner from the supports on the left. Then rotate the open end of the venturi tube inward toward the heater. Carefully pull the burner assembly out of the cabinet.
Inspect and Clean the Burner
Re-Install the Burner
With the burner assembly removed, shine a flashlight on the burner ribbons. Look for carbon buildup, scale, dust, lint, and/or anything that might restrict flow through the spaces between the burner ribbons. Holding the burner assembly so that any foreign material will fall away from the burner, use a stiff bristle brush to loosen and remove any foreign material(s). If the burner is excessively dirty, remove one of the burner end caps. Remove the four screws that hold the end cap to the burner housing. Lightly tap the end cap to remove it.
Clean all foreign material from the burner and venturi. After the burner is thor­oughly clean, replace the end cap making certain that it is tight against the burner housing. NOTE: If any of the burner components are damaged or deteriorated, replace the burner assembly.
Inspect the Lower Portion of the Heat Exchanger (with burner assembly removed)
At the burner flame entrance of each tube, shine a bright light into each heat exchanger section. With the light shining into the heat exchanger, observe the outside for visible light. Repeat this procedure with each heat exchanger section. If any light is observed, replace the heat exchanger.
Instructions to Re-Install the Burner (Refer to FIGURE 17)
1. Attach the Burner Assembly - Holding the venturi tube, slide the entire
burner assembly into position. Align the supports on the left side with the slots in the burner shield; sliding the supports into the slots. On the right, re­attach each burner body support to the secondary air shield.
2. Attach the Secondary Air Baffles (Sizes 60-400 only) - Re-attach the
secondary air baffles as marked. Baffles may be different sizes and each
must be attached in the correct location.
3. Attach the Control Assembly - Carefully slide the control assembly into
position. Re-attach with the same screws. Check to be sure all wire connec­tions are secure.
4. Attach the Gas Train - Slide the gas train so that the orifice adapter is
through the bracket. Fasten the gas train to the bracket with the locking nut. Install the gas orifice. Re-connect the wires to the gas valve.
5. Close the access panel.
6. Reconnect the gas supply at the union outside of the cabinet. Leak test the
connection with leak detecting solution.
7. Turn on the electric and the gas. Check for proper operation.
28. Burner Orifice
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 30
Burner orifice usually only needs to be replaced when installing a gas conversion kit. If ordering a replacement orifice only, give BTUH content and specific grav­ity of gas, as well as the model and serial number of the unit. When removing or replacing the burner orifice be careful not to damage the venturi tube and/or the bracket.
Page 31
FIGURE 18 - Location of Controls
Flame Rollout Switch
(Sizes 30-125)
Burner Assembly
Ignitor
Transformer
Circuit Board (DSI Integrated Control Module)
Flame Sensor
High Temperature Limit Control
Control Panel Assy
located on the
Control Compartment
Bottom
Sizes 30-125
Sizes 150-400
Optional Fan Motor Capacitor
Pressure Switch
Gas Valve
Transformer
Circuit Board (DSI Integrated Control Module)
Venter Motor (Size 30-75 illustrated. Venter motor is in the same location for all models, but appear­ance is different.)
Model UDAS has a collar for combustion air pipe (not illustrated)
Interlock Door Switch - UDAS only
Fan Motor
Terminal Board (24V)
Disconnect Switch
- UDAS only
Electrical Box - UDAS only Remove cover to connect supply and access disconnect switch wires . Always replace cover.
Venter Motor Capacitor
Fan Motor Capacitor
29. Ignition System
FIGURE 19 - DSI Integrated Control Module (Circuit Board)
DSI Integrated Control Module (circuit board) - See FIGURE 19. The module
monitors the operation of the heater including ignition. The only replaceable com­ponent is the 3 amp Type ATC or ATO fuse. If the fuse is blown, the problem is most likely an external overload. Correct the problem and replace the fuse.
Do not attempt to disassemble the control module. However, each heating season check the lead wires for insulation deterioration and good connections.
Proper operation of the direct spark ignition system requires a minimum flame signal of 1.0 microamps as measured by a microampmeter.
For further information and check out procedure on the direct spark ignition sys­tem, refer to Paragraph 20 and the Troubleshooting Flow Chart in Paragraph 40.
Only replaceable part is a Type ATC or ATO 3 amp fuse (Color Code Violet), P/N 201685
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 31
Page 32
29. Ignition System
Ignitor - Refer to FIGURE 18 and locate the ignitor. Disconnect the wire; re­move the screw and the ignitor. Clean the ignitor assembly with an emery cloth.
Spark gap must be maintained to 1/8". See FIGURE 20.
(cont’d)
Ignitor
Flame Sensor
30. Fan Motor , Fan Blades, and Guard
FIGURE 21 - Fan Blade Position on the Shaft
Dimension A
inches mm
Size
30 45 60
75 100 125 150 175 200
225, 250,
300 350 400
125
9/16 14 1-1/2 38 2-1/8 54 2-3/8 60
2-5/16 59
2-3/8 60 2-1/8 54 1-5/8 67
251
1-7/8 48 1-3/8 35
Fan Blade
FIGURE 20 - Ignitor showing required Spark Gap
1/8 inch
(3.2mm)
measurement
IMPORTANT: When re-assembling, the brown ground wire must remain attached
to the ignitor .
CAUTION: Due to high voltage on the spark wire and electrode, do not touch when energized. See Hazard Levels, page 2.
Flame Sensor - Refer to FIGURE 18 and locate the flame sensor. Disconnect the
wire; remove the screw and the flame sensor. Clean with an emery cloth.
Remove dirt and grease from the motor, the fan guard, and blades. Use care when cleaning the fan blades to prevent causing misalignment or imbalance. Check that the hub of the fan blades is secure to the shaft. Follow these instructions for replacement of the fan guard, fan motor and/or fan blades.
1. If the heater is installed, turn off the gas and disconnect the electric power.
2. Open the access door and disconnect the fan motor wires, capacitor wires at the capacitor, and ground screw.
3. Remove the assembled parts (the fan guard, the motor and the fan blade).
A
Fan
Motor
tioned properly.
5. Reconnect the fan motor wires according to the wiring diagram and close the access panel.
6. Restore power to the heater and turn on the gas. Light, following the instructions on the lighting instruction plate. Check for proper operation.
4. Disassemble and replace whatever parts are needed and reas­semble using whatever part(s) are being replaced and the original parts. Be sure the fan blade is in the proper position on the shaft; refer to the illustration and table in FIGURE 21. Position the assembly on the heater. Attach the fan guard. Rotate the fan blade to check for adequate clearance. If adjustment is required, loosen the mounting screws, re-position the fan guard, and tighten the screws. Rotate the fan blade and re-check for ad­equate clearance. Repeat this procedure until the assembly is posi-
31. V enter Motor and Wheel
Replacement Instructions
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 32
Remove dirt and grease from the motor casing, the venter housing, and the venter wheel. Venter motor bearings are permanently lubricated. Follow these instruc­tions for replacement of the venter motor and wheel assembly. Keep all hardware removed to be used in re-assembling and installing the replacement parts.
1. Turn off the gas and disconnect the electric power.
2. Open the burner/control compartment access panel.
3. Disconnect the three venter motor wires at the DSI control, capacitor wires at
4. Sizes 30 and 45 - Disconnect the gas train and move it out of the way. Discon-
the capacitor (if applicable), and ground screw (located on the control panel).
nect the gas supply at the union outside of the cabinet. At the gas valve, mark and disconnect the wires. Carefully remove the burner orifice and orifice adapter locking nut. Slide the orifice adapter out through the bracket on the burner push­ing the gas train to the right. This will move the gas train out of the way.
Page 33
FIGURE 22 - Venter Wheel Position on Shaft
5. Holding the venter motor, remove the three or four screws that attach the venter motor mounting plate to the venter housing. Remove the motor and wheel as­sembly from the heater.
6. Re-assemble with the replacement venter motor and wheel assembly. See FIG- URE 22.
7. Follow the wiring diagram to connect the venter wires.
8. Sizes 30 and 45 - Reconnect the gas supply at the union outside of the cabinet. Leak test the connection with leak detecting solution.
9. Replace the access panel. Restore power to the heater and turn on the gas. Light, following the instructions on the lighting instruction plate. Check for proper operation.
Venter Wheel, Sizes 30-75
32. Operating Gas V alve
Venter Motor Plate
Fan
Motor Mounting Bracket
Motor Sizes 30-75
5/16 (8mm) inside
The gas valve requires no field maintenance except careful removal of external dirt accumulation and checking of wiring connections. Instructions for testing pressure settings are in Paragraph 12.
WARNING: The operating valve is the prime safety shutoff. All gas supply lines must be free of dirt or scale before connecting to the unit to ensure positive closure. See Hazard Levels, page 2.
33. Combustion Air Pressure Switch
Venter Wheel, Sizes 100-175*
Single
Stage
Gas
Valve
Venter Motor Plate
Fan
Motor Mounting Bracket
Motor Sizes 100-400
*Venter wheel has different appearance on Sizes 200-400. Motor spacing is the same.
5/16 (8mm) inside
Optional
Two
Stage
Gas
Valve
See FIGURE 18, page 31, for location. (NOTE: Depending on date of manufacture and size, pressure switch may not be in the location indi­cated. Check the control bracket on the bottom of the compartment or further down on the compartment wall.) If it is determined that the pres­sure switch needs replacing, use only the factory-authorized replacement part that is designed for the model and size of heater being serviced.
NOTE: A unit operating above 6000 ft elevation requires a high altitude pressure switch. See Paragraph 7.
34. Limit Control
35. Door Switch
- UDAS only
36. T ransformer
If it is determined that the limit control needs replacing, use only a fac­tory-authorized replacement part that is designed for the size of heater.
For approximate limit location, see FIGURE 18, page 31.
If it is determined that the door switch needs replacing, use only a fac­tory-authorized replacement part that is designed for the heater.
For approximate switch location, see FIGURE 18, page 31.
See FIGURE 18, page 31, for location. Use a voltmeter to verify that there are 24 volts output from the transformer. If the transformer is not functioning, it must be replaced. Use a replacement transformer identi­cal to the factory-installed model.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 33
Page 34
37. Flame Rollout Switch ­Sizes 30-125
only
For location, see FIGURE 18, page 31.
The cause of a flame rollout switch activating must be determined. Activation of the manually reset flame rollout switch could be caused by one or more of the following:
• Restricted or plugged heat exchanger
• Too much building exhaust
• Manifold gas pressure too high
• Restricted combustion air inlet or exhaust outlet in combination with a defective pressure switch
• Electrical power interruption during operation
• Unit being operated with a line voltage disconnect (a 24-volt thermostat is required)
If a flame rollout switch trips, inspect the burner/control compartment for signs of excessive heat and burned wiring.
If the compartment appears normal, reset by depressing the red button on the switch. 15 to 20 minutes are required for the switch to cool sufficiently for resetting. A distinct click will be felt when the switch resets. Operate the fur­nace. If the flame rollout switch trips again, determine and correct the cause before resetting the switch. If there is damage to the control compartment, repairs must be made before
resetting the switch. If it is determined that the flame rollout switch needs replacing, use only the fac­tory-authorized replacement part that is designed for that size of heater.
38. Disconnect Switch ­UDAS only
39. V ent or V ent/ Combustion
Check the complete system at least once a year. Inspection should include all joints, seams, concentric adapter box (UDAS), inlet air guard or inlet air cap (UDAS), and the vent terminal cap. Clean openings. Replace any defective parts.
Air System
40. T roubleshooting
DSI Integrated Control Module (Circuit Board) T rial Troubleshooting
YES NO
Flowchart
Is there
minimum flame current
at the control
module?
NO
Check connections to flame
sensor and/or moisture in the
burner assembly.
YES
Is there minimum
flame current at the
flame sensor?
Replace control
module.
YES NO
Does gas
Is the flame
sensor corroded?
Is the sensor
located in flame
correctly?
Reposition
flame sensor.
The disconnect switch is located in the sealed electrical box inside the con­trol compartment with the toggle on the rear of the heater. If it is determined that the disconnect switch needs replacing, use only the factory-authorized replacement part that is designed for the heater. Always replace electrical box cover.
Trial for Ignition
Call for Heat
Is there a
spark across gap at
ignitor?
YES NO
Is gas
flowing?
Is there
spark voltage at
control?
NO
Is there 24V P1-2 to power control?
NO
Check wiring
and/or 24VAC
transformer output.
YES
YES
Check high voltage wire
continuity.
Replace control module.
ignite?
YES NO
YES
Clean flame
sensor.
NO
YES
Replace flame
sesnsor.
NO
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 34
Check gas pressure
and supply voltage.
If either are low,
correct and repeat
startup.
YES
Is the ignitor
position correct in the
gas flow?
NO
Reposition
spark ignitor.
Replace gas
valve.
Check wiring and
connections to
gas valve.
YES
YES NO
Is there
24VAC at the gas
valve?
NO
Is there 24VAC
from gas valve output on
control module to
chassis?
Replace ignition control module.
Page 35
Check the Lights on
b)
b)
the DSI Integrated Control Module (Circuit Board)
The integrated circuit board monitors the operation of the heater and includes two LED signal lights that indicate normal operation and various abnormal conditions. If the heater fails to operate properly , check this signal to determine the cause and/ or to eliminate certain causes. LED is visible through viewport on Model UDAS. Remove access panel on Model UDAP. See operating sequence in Paragraph 20.
Do not attempt to repair the DSI integrated control module (circuit board); the only
IMPORTANT: When using a
field replaceable component is the fuse.
multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or 9 pin connectors located on the ignition control. Do not remove connectors or terminals from the electrical components. Doing so can result in misinter­preted readings due to the ignition control board’s fault mode monitoring circuits.
Control Status - Green LED Codes
Steady ON..Normal Operation, No call
for heat
Fast Flash...Normal Operation, Call for
heat
1 Flash........System Lockout, Failed to
detect or sustain flame
2 Flashes ....Pressure Switch Did Not
Close within 30 Seconds of Venter Motor
3 Flashes ....High Limit or Flame
Rollout Switch Open
General T roubleshooting
PRO BLEM PROBABLE CAUSE REMEDY Venter moto r
will not start
1 . No power to unit. 1 . Turn on powe r; chec k supply fuses or main ci rcuit breaker. Turn on built-
in disconnect switch (Model UDAS only); replace switch if not operating.
4 Flashes ....Pressure Switch is Closed
Before Venter Motor is Energized
Steady OFF Blown fuse, No Power, or
Defective Board
Flame Status - Yellow LED Codes
Steady ON..Flame is sensed Slow Flash .Weak flame (current below
1.0 microamps ± 50%)
Fast Flash...Undesired Flame (valve
open and no call for heat)
Burner will not light
2. No 24 volt power to integrated circuit board. 2. Turn up thermostat; check control transformer output. 3 . Inte grated circuit boar d fuse blown. 3. Corre ct c a use. Re place f use (type ATC or AT O, 32VDC, 3A). 4 . No power to ve nt e r motor. 4 . Ti g hte n c onne c t ions at circ uit board and/ or m o tor ter mina ls.
5. Integrated circuit board defective. 5. Repl ace intergrated ci rcuit board.
6. Defecti ve venter motor. 6. Replace venter motor. S ee Paragraph 31. 1 . Manual valve not open. 1. Open manual valve.
2. Air in the gas line. 2. Bleed gas line (initial startup only). 3 . Gas pressure too high or too low. 3. Supply pre ssur e should be 5" - 14" w.c. for natur al ga s or 11" - 14 " w.c .
for propane gas.
4. No Spark: 4. a) L oose wir e connections. a) Be certain all wire c onn ections are solid. b) Transf ormer fai lure. b) B e sure 24 vol ts is avai lable. c) Incorrect spark gap. c) Maintain spark gap at 1/8". d) Spar k cable shorte d to ground. d) Replace worn or ground e d spark ca ble. e) Spark electrode shorted to ground. e) Repl ace if cer amic spark electrode is cracked or grounded. f) Burner not groun ded. f) Make certain integrate d circuit board is gr ou nded to ign itor. g) Cir c u it boar d not grounded. g) M a ke certai n integrat e d c ircuit board is ground e d to furnace chassi s. h.) Unit not properly grounde d . h.) Make certain unit is properly field grounded to earth ground and
prop e rly pha sed (L 1 to hot lea d L2 to neut ral ). i) Integrated cir cuit board fuse blown. i ) Correct cause. R eplace fuse (type ATC or ATO , 32VDC, 3A). j .) Faul ty intergr a t e d c ircuit board. j) If 24 volt is avail a ble to the i nte grated c irc uit board and all other causes
have been eli minated, replace board. 5 . L oc kout device inter rupti ng c ont rol c ircuit by above causes.
6. Interl ock door switch open (UDAS only). 6 . Close access door or r eplace switch.
7. Combustion air pr oving switc h 7. not closing. a) Make sure unit is properly vented.
8. Faulty combustion air proving switch. 8. Replace combustion air provi ng switch.
9. Mai n val ve not operating. 9. a) Defective valve. a) If 24 volt is measured at the valve connections and valve remains closed,
Loose wire c onnecti ons
5 . Reset lockout by interrupting control at the t hermostat or main power.
b) Rem ove obstructions from vent.
c) Replace faulty tubing to pressure switch.
repl ace valve.
C heck and tighten all w iring connections.
Form RZ-NA I-UDA, Mfg #195673 Rev 9, Page 35
Page 36
40. T roubleshooting (cont’d)
p
PROBLEM (cont'd) PROBABLE CAU SE (cont'd) REMEDY (cont'd) Burner will not light (cont'd )
Burner cycle on and of f
No heat (Heater Operati ng)
Fan or venter motor will not run
F an o r venter motor turns on and off while burner is operating F an o r venter motor cuts out on overload
9. Integra t ed circuit board does not power main valve. a) Loose wi re connections. a) Check and tighten all wi ring connecti ons. b) Flame sensor grounded. b) B e certain flame sensor lead is not grounded or insulation or ceramic
c) Incorrect gas pressure. c) Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14"
d) C r acked ceramic at sensor. d) Replace sensor. 1 . Gas pre ssure too hi gh o r too l ow. 1. Supply pr e ssur e should be 5" - 14" w. c. f or natural ga s or 11" - 14"
2. Bur ner not grounded 2. Make certa in integrated ci rcuit board is grounded to i gnitor.
3. Circuit board not grounded. 3 . Make cer tain integrated ci rcuit board is grounded to furnace chassis.
4. Faulty integrated circuit board 4. If 24 volt is available to the integrated circuit board and al l other
5. Combustion air proving switc h 5. not closing. a) Ma ke sure uni t is properly vented.
6. F a ul ty combustion air proving switch. 6. Replace combustion air pr ovi ng swi tch.
7. Flam e sensor gr ounded. 7 . B e c e rtai n flame sensor lead is not grounded or insulation or ceramic
8. Cracked ceramic at sensor. 8. R eplace sensor.
9. Incorr ec t polarity. 9. Reverse line volt leads to integrated cir cuit board.
10. Pi n ter minal l oose on 9 pin plug. 10. R eplace wire harness.
1. Incorrect valve outlet pressure or orifi ce. 1. Check valve outl e t pressure. See R ating plate for manifol d pressure.
2. Cycling on limit control. 2. Chec k air throughput.
3. Improper thermostat location or adjustment. 3. See thermostat manufactur er's instructions.
1. Circuit o
2. D e fective integrated ci r cuit board. 2. Replace board.
3. D e fective m otor or starter. 3. Replace motor or starter.
1. Motor overload device cycl ing on and off. 1. Check m otor load against m otor r a ting plate. Replace motor if needed.
1. Low or high voltage suppl y. 1. Correct e lectric supply.
2. D e fective m otor. 2. Replace motor.
3. Poor airflow. 3. C l ean motor, fan, fan guard, filter, and coils.
4. D e fective bearing or lubrication. 4. Lubricate bear ings (motor perm itting) or replace motor.
en. 1. Check wiring and connections.
9.
is not cracked. Replace as requir ed.
w. c. for propane gas.
w. c. for propane gas.
causes have been elim inated, replace board.
b) Remove obstr uct ions from vent. c) Replace faul ty tubing to pressure switch.
is not cracked. Replace as requir ed.
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:
FIRST: Contact the Installer
Name __________________________________________________________ Address_________________________________________________________
__________________________________________________________ __________________________________________________________
Phone _____________________________________
SECOND: Contact the nearest distributor (See Yellow Pages). If no listing,
contact Authorized Factory Representative, 1-800-695-1901 (Press 1).
®
THIRD: Contact REZNOR
/ Thomas & Betts Corporation 150 McKinley Avenue Mercer, PA 16137 Phone: (724) 662-4400
Date of
Model No. _______________Unit Serial No._____________________________ Installation _______________
(800) 695-1901; www.RezSpec.com
©2005 Thomas & Betts Corporation, All rights reserved. MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS
Trademark Note: Reznor®, TCORE2® , and ® are trademarks of Thomas & Betts.
Form RZ-NA I-UDA, P/N 195673 Rev 9, Page 36
5/05 Form RZ-NA I-UDA (Version .9)
Loading...