Reznor SCE Installation Manual

Model SCE
Separated-Combustion
Packaged Furnace/Blower
NOTE: Model SCE units are not for residential use.
INSTALLATION/OPERATION/MAINTENANCE
Form I-SCE (12-14)
Obsoletes Form I-SCE (Version B.1)
TABLE OF CONTENTS Pa ges
Installation/Operation . ............. 1-30
Check Installation & Startup 30-31
Optional Equipment ................ 32-33
Service/Maintenance ............... 33-36
INDEX by Page No.
Belts ...... ................................................... 24
Blower ...................................................... 24
Blower Rotation ....................................... 24
Adjusting Blower Speed.......................... 24
Burner Air Shutters .................................. 30
Burner Carryover Systems ........................ 29
Burner
Burner Rack Removal .............................. 34
Burners..................................................... 29
Check Installation & Startup ................... 30
Cleaning the Heat Exchanger................... 35
Cleaning Pilot and Burners ..................... 34
Clearances .................................................. 4
Combustion Air .......................................... 7
Concentric Adapter Box............................ 10
Optional Condensation Drain.................... 6
Optional Dampers & Controls .................. 32
Dimensions ................................................ 3
Dirty Filter Switch (Option) .................... 33
Drives ........................................................ 24
Duct Connections...................................... 6
Ductstat (Optional)................................... 25
Electrical Supply & Connections ............ 20
Optional Electronic Modulation.............. 26
Fan Control ............................................. 23
Filter Rack & Filters ................................ 32
Gas Piping and Pressures......................... 18
Gas Valve ............................................ 24, 33
General ....................................................... 1
HAZARD Horizontal Vent Terminal/
Combustion Air Inlet .......................... 12
Ignition System....................................... 29
Installation Codes ...................................... 2
Limit Control .......................................... 23
Limit Control Check ............................... 35
MAINTENANCE .................................... 33
Manifold Pressure Setting........................ 19
Motor ........................................................ 23
Mounting................................................... 5
Optional Accessories ................................. 32
Pilot and Ignition Systems...................... 29
SERVICE................................................. 33
Startup ..................................................... 30
Support ....................................................... 9
Suspension ................................................. 5
Thermostat ............................................... 20
Troubleshooting...................................... 35
Optional Two-Stage Operation ................ 24
Uncrating................................................... 3
Valve ........................................................ 24
Vent/Combustion Air System............... 7, 33
Venting.................................................. 7-17
Vertical
Combustion Air Inlet .......................... 15
Warranty..................................................... 2
Wiring Diagram .................................. 21-22
REFERENCE
Replacement Parts....................... Form P-SC
Gas Conversion.......................... Form P-GC
s .............................. ........... 29
INTENSITY LEVELS ............. 2
Vent Terminal/
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open
.
4. Immediately call your gas supplier.
The use and storage of gasoline or other
ammable vapors and liquids in
open containers in the vicinity of this appliance is hazardous.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
WARNING: red appliances are not designed for use in hazardous atmospheres containing
ble vapors or combustible dust, in atmospheres containing chlorinated or halogenated hydrocarbons, or in applications with airborne silicone substances. See Hazard Levels, page
2.
Model Description
Separated-Combustion, Blower-Ty pe
GENERAL
The instructions in this manual apply to Model SCE blower-type unit heater with blower cabinet.
Installation should be done by a agency in accordance with the instructions in this manual and in compliance with all codes and requirements of authorities hav­ing jurisdiction.
Model SCE is Model SCE is available for use with either natural or propane gas. The type of gas, the
rate, and the electrical characteristics are on the unit rating plate.
This separated combustion unit is designed and manufactured in accordance with the ANSI
of separated combustion. That reads, "Separated Combustion System Appliance: A system consisting of an appliance and a vent cap(s) supplied by the manufac­turer, and (1) combustion air connections between the appliance and the outside atmo­sphere, and (2) gas connections between the appliance and vent cap, of a type(s)
by the manufacturer but supplied by the installer, constructed so that, when in­stalled in accordance with the manufacturer's instructions, air for combustion is obtained from the outside atmosphere and gases are discharged to the outside atmosphere."
Separated combustion units are designed to separate air for combustion and from the environment of the building in which the unit is installed. Separated combustion
by the Canadian Standards Association to ANSI Standards.
SCE
Unit Heater with Blower Cabinet
Front View
Rear View
products
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 1
General (cont'd)
appliances are recommended for use in dust laden and some corrosive fume environments or in buildings with negative pressure (up to .15" w.c.). As the definition states, all separated combustion, power-vented equipment must be equipped with both combustion air and ex­haust piping to the outdoors.
Definitions of Hazard Levels in this Manual
1. Installation Codes
Special Installations (Aircraft Hangars/ Garages)
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
These units must be installed in accordance with local building codes. In the absence of local codes, in the United States, the unit must be installed in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1 (latest edition). The code is available from CSA Information Services, 1-800-463-6727. Local authorities having jurisdiction should be consulted before installation is made to verify local codes and installation procedure requirements.
Installations in aircraft hangars should be in accordance with NFPA No. 409 (latest edition), Standard for Aircraft Hangars; in public garages in accordance with NFPA No. 88A (latest edition), Standard for Parking Structures; and for repair garages in accordance with NFPA No. 88B (latest edition), Standard for Repair Garages.
All Installations
2. Warranty
These gas-fired products are certified by ANSI Z83 family of standards governing the safe usage of heating equipment in the industrial/commercial marketplace. This includes using the heaters in makeup air applications to supply corridor pressurization in commercial build­ings such as office structures and apartment complexes.
The heaters are not certified as residential heating equipment and should not be used as such.
Clearances from the heater and vent to combustible construction or material in storage must conform with the National Fuel Gas Code ANSI Z223.1a (latest edition) pertaining to gas­burning devices, and such material must not attain a temperature over 160°F by continued operation of the heater.
Refer to the limited warranty information on the Warranty Card in the "Owner's Envelope".
Warranty is void if ...
a. Separated-combustion heaters are used in atmospheres containing flammable vapors or
atmospheres containing chlorinated or halogenated hydrocarbons or any contaminant (silicone, aluminum oxide, etc.) that adheres to the spark ignition flame sensing probe.
b. Wiring is not in accordance with the diagram furnished with the heater. c. Unit is installed without proper clearance to combustible materials.
Form RZ-NA I-SCE, Page 2
3. Dimensions
FIGURE 1 - Model SCE Dimensions - inches ±1/8 (mm ±3)
Standard Model SCE
Model SCE with Optional Horizontal Inlet with Duct Flanges
Size
Dimensions (inches±1/8)
125 150, 175 200, 225
250
300
350
400
Dimensions (mm±3)
125 150, 175 200, 225
250
300
350
400
A B D E F G H J K L
32-1/4 25-1/4 15-1/4 8-1/8 16-1/4717-3/4 17-3/8 17 1/2 40-1/4 27-3/4 32-1/4 30-3/4 20-3/4 8-1/8 21-3/4723-1/4 22-7/8 18-3/8 1/2 39 27-3/4 35-1/4 36-1/4 26-1/4 10-3/4 27-1/4 10 28-3/4 28-3/8 17 1/2 40-1/4 30-3/4 35-1/4 43-1/2 33-1/2 9-3/4 34-1/2 9 36 35-5/8 16 1/2 39-1/4 30-3/4 35-1/4 44-1/2 4-1/5 10-3/4 35-1/2 10 37 38-5/8 17 3/4 40-1/4 30-3/4 35-1/4 50 40 10-3/4 41 10 42-1/ 35-1/4 55-1/2 45-1/2 10-3/4 46-1/2 10 48 47-5/8 17 3/4 40-1/4 30-3/4
819 641 387 206 413 178 451 441 432 13 1022 705 819 781 527 206 552 178 591 581 467 13 991 705 895 921 667 273 692 254 730 721 432 13 1022 781 895 1105 851 248 876 229 914 905 406 13 997 781 895 1130 876 273 902 254 940 930 432 19 1022 781 895 1270 1016 273 1041 254 1080 1070 467 19 991 781 895 1410 1156 273 1181 254 1219 1210 432 19 1022 781
4. Uncrating
NM
2 42-1/8 18-3/8 3/4 39 30-3/4
The furnace is shipped completely assembled. Immediately upon uncrating, check the gas speci­cations and electrical characteristics of the unit to be sure that they agree with the gas and electric supply at the installation site. Check the unit for any damage that may have been incurred during shipment. If damage is found, document the damage with the transporting agency and immediately contact your Reznor dis­tributor. If you are an authorized Distributor, follow the FOB freight policy procedures.
The bottom corners are fastened to the crate with angle clips. Remove the lag screws from the shipping clips. Remove the clips and return the bolts to the heater legs to support the corner leg and the heater bottom. Putting the bolts back in the heater is required.
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 3
4. Uncrating (cont'd)
To protect the unit during shipping, blower models have special supports that must be removed before installation. Follow these instructions to remove:
Blower Support Legs - Remove the blower support legs and screws. Motor Shipping Block - Remove the wooden block located under the motor bracket. Find
the two rubber pads shipped in the instruction envelope. Place these pads on the ends of the motor bracket bolts.
Motor Shipping Plate - Units that are equipped with motors of
1-1/2 HP or less have a metal shipping plate attached between the motor and the blower housing. The shipping plate must be removed and the plate and screws discarded. On units factory equipped with an optional belt guard, the belt guard must be removed to reach the shipping plate.
Vent Terminal/Combustion Air Inlet Kit with Concentric Adapter Box -
Required for All Installations
Options
Some gas control options have parts either shipped loose with the heater or shipped separately. If your unit is equipped with any of the gas control options in the table, be sure these parts are available at the job site.
Before beginning installation, be sure that all other shipped-separate options ordered are available at the site, also. Shipped-separate options could include a shutoff valve, a condensate drain kit, a thermostat, a remote console, a disconnect switch, or high tempera­ture vent sealing tape.
5. Clearances and Location
For safety and convenience, provide clearances as shown in the following table. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object that is necessary to ensure that a surface temperature of 90°F above the surrounding ambient tempera­ture is not exceeded. Minimum clearances are also listed on the heater rating plate.
The concentric adapter assembly in the venting/combustion air kit (Option CC2 or CC6) is required on all separated combustion models. Be sure that the concentric adapter carton is at the installation site. (See parts lists in Para­graph 9.)
Application Option Shipped Separate Components Heati ng -- Gas Control Option
Makeup Air -- Gas Control Options AG9
AG7
AG3
AG15
AG16
AG39
Thermostat, P/N 48033
Control Switch, P/N 29054 Remot e T emp erat ure Selector, P/N 48042 Control Switch, P/N 29054 Remot e T emp erat ure Selector, P/N 115848 Stage Adder Module, P/N 115849 Control Switch, P/N 29054 Remot e T emp erat ure Selector, P/N 115848 Stage Adder Module, P/N 115849 Remote Disp lay Module, P/N 115852 Control Switch, P/N 29054 Remot e T emp erat ure Selector, P/N 174849
Minimum Clearances
- inches (mm)
Location
Form RZ-NA I-SCE, Page 4
Top
6"
(152mm)
For best results, the heater should be placed with certain rules in mind. In general, a unit should be located from 8 to 12 ft (2.6 to 3.6M) above the floor. Units should always be arranged to blow toward or along exposed wall surfaces, if possible. Where two or more units are installed in the same room, a general scheme of air circulation should be maintained. Suspended heaters are most effective when located as close to the working zone as possible, and this fact should be kept in mind when determining the mounting heights to be used. However, avoid directing the discharged air directly on the room occupants. Partitions, columns, counters, or other obstructions should be taken into consideration when locating the unit heater so that a minimum quantity of airflow will be deflected by such obstacles. When units are located in the center of the space to be heated, the air should be discharged toward the exposed walls. In large areas, units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the center of the area. At those points where infiltration of cold air is excessive, such as at entrance doors and shipping doors, it is desirable to locate the unit so that it will discharge directly toward the source of cold
air from a distance of 15 to 20 feet (4.5 to 6 M).
Control Side Side Oppos ite Controls To Combustibl es To Non-Combustibles
6" (152mm) plus
width of unit
6" (152mm) 6" (152mm) 0" (0mm)
BottomSides
CAUTION: Do not locate the heater where it may be exposed to water spray, rain, or dripping water.
6. Suspension and Mounting
Weights
Before installing, check the supporting structure to be sure that it has sucient load-carry­ing capacity to support the weight.
Net Weight (lbs and kg)
Size 125 150-175 200-225 250-300 350 400
lbs 313 358 382 482 498 560
kg 142 162 173 219 226 254
Suspension
WARNING: Units must be supported level for proper operation. Do not place or add additional weight to the suspended unit. See Hazard
Levels, page 2.
FIGURE 2 - Suspension Methods
Mounting Supports
FIGURE 3 - Model SCE Support Locations
FIGURE 4 - Corner Mount­ing Supports (NOTE: Sup­port is also required where furnace and blower cabinets meet. See FIGURE 3.)
Model SCE has four-point suspension. See hanger centerline dimensions in FIGURE 1 , Paragraph 3. At each suspension point, the unit is factory-equipped with a free-turning, female, 1" NPT pipe hanger. Suspend by connecting the pipe hanger to a 1" threaded pipe. See suspension method on the left in FIGURE 2 . As an alternative method, the factory-installed pipe hanger
may be removed and the heater suspended as illustrated on the right in FIGURE 2.
Model SCE requires six support locations. See FIGURE 3 . Supports available from the manufacturer (P/N 74487) or eld-fabricated legs as illustrated in FIGURE 4 may be used at the four corner support locations. Do not use this type of support at the center support locations (between the furnace and the blower section). At the center locations, a eld-fabricated, angle-iron brace support must extend horizontally, jointly sup­porting a portion of both the furnace and the blower cabinet. All supports must be non­combustible.
Field-supplied supports between the blower cabinet and the furnace
must extend horizontally support­ing both sections.
Support Locations
above - available as a part
right - eld fabricated
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 5
7. Optional Condensation Drain for Duct Furnaces
FIGURE 5 - Option CS1, P/N 31765, Optional Condensate Drain Connection
8. Duct Connections
FIGURE 6 - Duct Connection Dimensions ­inches (mm)
Model SCE furnaces are for installation upstream or downstream from a cooling coil. When installed downstream from a refrigeration system, condensation will form; and there­fore, adequate provision must be made to dispose of condensate. Periodic cleaning of the condensate collection and disposal system is required. Install drain connection, Option CS1, on the furnace casing as illustrated in FIGURE 5.
#10-32 x 1”Lg Machine Screw & Nut
Terminate drain outside of the building. Provide a trap to prevent air from entering the combustion zone. Periodic cleaning of the condensate collection and disposal system is required. NOTE: Requires a four-inch (102mm) minimum clearance under the furnace if a 90° street elbow is used.
RTV Sealant
Size G 125 15-1/4" (387mm) 150, 175 20-3/4" (527mm) 200, 225 26-1/4" (667mm) 250, 300 34-1/2" (876mm) 350 40" (1016mm) 400 45-1/2" (1156mm)
Seal holes in bottom pan with RTV sealant
Requirements and Suggestions for Connecting and Installing Ducts
Type of Ductwork - The type of duct installation to be used depends in part on the type of construction of the roof (whether wood joist, steelbar joist, steel truss, pre-cast concrete) and the ceiling (whether hung,
etc.).
Ductwork Material - Rectangular duct should be constructed of not lighter than No. 26 U.S. gauge galvanized iron or No. 24 B
& S gauge aluminum.
Ductwork Structure - All duct sections 24 inches (610mm) or wider, and over 48 inches (1219mm) in length, should be cross
broken on top and bottom and should have standing seams or angle-iron braces. Joints should be S and drive strip, or locked.
Through Masonry Walls - No warm air duct should come in contact with masonry walls. Insulate around all air duct through
masonry walls with not less than 1/2" (1" is recommended) of insulation.
Through Unheated Space - Insulate all exposed warm air ducts passing through an unheated space with at least 1/2" (1" is
recommended) of insulation.
Duct Supports - Suspend all ducts securely from adjacent buildings members. Do not support ducts from unit duct connections.
Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a satisfactory heating installation. The recognized
authority for such information is the Air Conditioning Contractors Association, 2800 Shirlington Road, Suite 300, Arlington, VA 22206 (www.acca.org). A manual covering duct sizing in detail may be purchased directly from them.
CAUTION: An external duct system static pressure not within the limits shown on the rating plate, or improper motor pulley or belt adjustment, may overload the motor. See Hazard Levels, page 2.
Removable Panels - The ducts should have removable access panels on both upstream and downstream sides of the furnace.
These openings must be accessible when the furnace is in service and should be a minimum of 6" x 10" (152mm x 254mm) in size so smoke or light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The covers for the openings must be attached in such a manner as to prevent leakage. See FIGURE 7A
Horizontal Discharge Duct Length - A minimum horizontal duct run of 24" (610mm) is recommended before turns or branches
are made in the duct system to reduce losses at the furnace outlet.
Supply Air Duct/Furnace Horizontal Connection - The seal between the furnace and the duct must be mechanical. Duct
connection should be made with "U" type of the heater giving an airtight Provide "U" type channels for the side to ensure tight joints. Use sheetmetal screws
to fasten ducts and "U" channels to the furnace
Form RZ-NA I-SCE, Page 6
on the top and bottom of the connecting duct. Slide the duct over the
See FIGURE 7B
CAUTION: Joint where supply air duct attaches to the furnace must be sealed securely to prevent air leakage into drafthood or burner rack area. Leakage can cause poor combustion, pilot problems, shorten heat exchanger life, and cause poor performance. See Hazard levels, page 2.
Return Air Duct/Furnace Connection - All return air ducts should be attached and
sealed to return air anges to provide airtight connection.
Return Air Duct/Grill Size - Make certain that return air ducting or grills have a free
area equal to the return duct size connection.
FIGURE 7A - Connecting Ductwork to the Furnace
(1) Flanges on the furnace (heat exchanger) turn out as shown. (2) Shape duct connection as shown -- "U" on top and bottom; "L" on sides. (3) Slide "U" channels over furnace top and bottom anges making connection. (4) Form "U" channels to seal sides. Drill and lock with
sheetmetal screws.
FIGURE 7B - Install "U" Channel on Sides of Duct Connection
9. Venting and Combustion Air
WARNING: Do not use an existing venting system. This heater requires installation of the combustion air/vent system ordered with the unit (either Option CC2 or Option CC6).
All separated combustion, power vented units MUST BE equipped with both combustion air and exhaust piping to the outdoors. The unique concentric adapter box designed for use with this heater allows for both combustion air and exhaust piping with only one horizontal or vertical penetration hole in the building.
These instructions apply to installation and use of the concentric adapter and vent/combus­tion air kit (Option CC2 or CC6) designed for use with all Reznor separated-combustion products. The systems illustrated in this manual are the only venting/combustion air sys­tems approved for these separated combustion units. Do not use this concentric adapter box with any other products.
Installation should be done by a qualied agency in accordance with these instructions. The qualied service agency installing this separated-combustion system is responsible for the installation.
Hazards of Chlorine - The presence of chlorine vapors in the combustion air of gas-red heating equipment presents a potential corrosion hazard. Chlorine found usually in the form of freon or degreaser vapors, when exposed to ame, will precipitate from the compound, and go into solution with any condensation that is present in the heat exchanger or associated parts. The result is hydrochloric acid which readily attacks all metals including 300 grade stainless steel. Care should be taken to separate these vapors from the combustion process. This may be done by wise location of unit vent terminal and combustion air inlet with regard to exhausters or prevailing wind directions. Remember, chlorine is heavier than air. This fact should be kept in mind when determining installation location of these heaters and building exhaust systems.
WARNING: SC Series separated combustion units are not designed or approved for use in atmospheres containing ammable vapors or atmospheres highly laden with chlorinated vapors. See Hazard Levels, page 2.
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 7
9. Venting and Combustion Air (cont'd)
1) Type of Pipe
Vent Pipe
Specific Venting Requirements
All pipe is field supplied. Requirements are listed for both the vent pipe and the combustion air inlet pipe.
• Vent pipe approved for a Category III appliance OR single-wall, 26-gauge or heavier galvanized (or a material of equivalent durability and corrosion resistance) vent pipe is
required between the heater and the concentric adapter box.
• Double-wall (Type B) vent pipe is required for vent terminal section. The length of vent pipe that extends through the box and runs concentric through the combustion air pipe must be one-piece with no joints.
Combustion Air Pipe
2) Venter Outlet and Combustion Air Inlet
NOTE: If using 7" pipe on Sizes 200-400 (see table below), use a taper-type 6" to 7" enlarger to attach the vent pipe and a 7" to 6" reducer to attach the combustion air pipe.
3) Pipe Length
and Diameter
Pipe Diameter and Maximum Pipe Length Between the Heater and the Concentric Adapter Box
Minimum length between the
heater and the concentric adapter box is 5 feet (1.5M).
Diameters of Outdoor Concentric Pipes
Model SCE - All Sizes Inl et Ai r P i pe Diameter
Vent Pipe Di ameter
8"
203mm
5"
127mm
• Sealed, single-wall galvanized pipe is recommended for combustion air.
Model SCE heaters have both an inlet air and a venter outlet connection. Both are 6" diam­eter for all sizes.
Taper-type Enlarger
Airflow
Taper-type Reducer
Airflow
Pipe diameter and length requirements listed for the indoor sections of pipe (between the heater and the concentric adapter box) are in the table below. Vent pipe diameters and maximum indoor vent lengths apply to both horizontal and vertical vents. Add all straight sections and equivalent lengths for elbows. The total length of the straight sections and
elbows must not exceed the Maximum Length.
Pipe Diameter and Maximum Pipe Length from Heater to Concentric Adapter
Pipe Diameter
SCE
125 150 175
200
225
250
300
350
400
The diameters of the outside (terminal) concentric pipes are shown in the concentric box connection illustrations in FIGURE 11, page 11. The outdoor lengths depend on the instal- lation. Outdoor vent length requirements are listed in the installation instructions for the horizontal and vertical vent/combustion air kits on pages 12-17.
Vent Pipe Inlet Air Pipe
inches mm inches mm feet M feet M feet M
6 152 6 152 50 15 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2 6 152 6 152 50 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2 6 152 6 152 30 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2 6 152 6 152 30 15 8 2.4 4 1.2 7 178 7 178 70 21 8 2.4 4 1.2
Venter Outlet Connection (diameter) SCE 125 150 175 200 225 250 300 350 400
inches666666666
mm 152 152 152 152 152 152 152 152 152
Combus tion Air Inlet Connection (diameter) SCE 125 150 175 200 225 250 300 350 400
inches666666666
mm 152 152 152 152 152 152 152 152 152
Maxi mum
Length 90° Elbow
Equivalent Straight Length for a
45° Elbow
4) Joints and Sealing
Form RZ-NA I-SCE, Page 8
Provide pipes as specified in Requirement No. 1 and seal joints as follows:
• If using Category III
joining and sealing Category III vent pipe sections.
• If using single-wall vent pipe run, secure slip-fit pipe connections using sheetmetal screws or rivets. Seal all joints with aluminum tape or silicone sealant.
vent pipe run, follow the pipe manufacturer’s instructions for
FIGURE 8 - Follow STEPS to join Double-Wall (Type B) Pipe and
the Vent Terminal
Cap (horizontal or vertical)
(NOTE: Pipes and vent caps may not look exactly as shown in the illustrations. Instructions apply to both horizontal and vertical vent kits.)
To seal joints in the single-wall combustion air pipe, secure slip t pipe connections using sheetmetal screws or rivets. Seal all joints with aluminum tape or silicone sealant.
To seal joint in the terminal section of double-wall vent pipe (allowed ONLY ABOVE
the concentric pipes on a VERTICAL vent, follow the pipe manufacturer’s instructions for joining and sealing double-wall vent pipe sections.
When joining the terminal section of
illustrated step-by-step instructions in FIGURE 8. When joining the terminal section of double-wall vent pipe to a single-wall or Cat­egory III vent pipe run, follow the illustrated step-by-step instructions in FIGURE 9.
Figure 8 -
Place a continual 3/8” bead of silicone sealant around the circumference of the vent cap col­lar. This will prevent any water inside the vent cap from running down the double-wall pipe.
Do STEP 2
STEP 1
immediately following STEP 1.
Figure 8 - STEP 2
Insert the collar on the vent cap inside the inner wall of the double-wall pipe. Insert as far as possible. Add additional silicone sealant to fully close any gaps between the vent cap and the double wall pipe. This is necessary to prevent water from entering the double wall pipe.
double-wall vent pipe to the vent cap, follow the
FIGURE 9 - Follow STEPS to join the Double-Wall (Type B) Pipe to the Taper-type Reducer that Joins it to the Single-Wall or Category III Vent Run
Figure 9 -
On the taper-type reducer, place a con­tinual 1/4” bead of silicone sealant around the circumference.
STEP 1
Do STEP 2 immediately following STEP 1.
5) Support
NOTE: The double-wall vent terminal pipe does not attach to the concentric adapter box and must be
supported during installation.
Figure 8 - STEP 3
Secure the vent cap to the double-wall pipe by drilling and inserting a 3/4” long sheetmetal screw into the vent cap collar. Do not overtighten screw.
Make this connection a maximum of 6" (152mm) from the concentric adapter box.
Figure 9 - STEP 2
Insert the collar of the reducer into the inner pipe of the double-wall pipe until the bead of sealant contacts the inner pipe creating a sealed joint.
5" I.D.
Double-
Wall Pipe
6" to 5" or
7" to 5"
Taper-
Type
Figure 9 - STEP 3
Spaced equally around the double-wall pipe, drill three small holes below the sealant ring. Insert 3/4 inch long sheetmetal screws to secure the joint. Do not overtighten screws.
Reducer
Support horizontal runs every six feet (1.8M). Support vertical runs of type "B" double-wall or Category III vent pipe in accordance with the requirements of the pipe manufacturer. Support single-wall vertical pipe in accordance with accepted industry practices. Do not rely on the heater or the adapter box for support of either horizontal or vertical pipes. Use non­combustible supports on vent pipe.
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 9
9. Venting and Combustion Air (cont'd)
Specific Venting Requirements (cont'd)
6) Clearance
7) Concentric Adapter Box
Do not enclose the vent pipe or place pipe closer than 6" (152mm) to combustible material.
All separated combustion installations require a concentric adapter box as illustrated in FIGURE 10. The concentric adapter box is included in the vent/combustion air kit. Installation instructions depend on whether the vent system is horizontal (Option CC6) or vertical (Option CC2).
FIGURE 10 - A Concentric Adapter Box is a Required Part of all Model SCE Installations
View of Heater Connection Side
Collar for connecting indoor portion of the combustion air pipe
Opening for double-wall vent pipe to pass through the box.
P/N 205885, Concentric Adapter Box
2 (51mm)
6-1/32
(153mm)
2 (51mm)
Top View
Heater Side View
6 Collar for Combustion Air Pipe
8 dia Collar for Combustion Air Pipe
View of Vent Terminal Connection Side
Collar for attaching outside concentric portion of the combustion air pipe
Concentric Adapter Box Airflow
Vent (exhaust gas) flows through field-supplied double-wall pipe that extends straight through the concentric adapter box.
14-1/4
(362mm)
End View
showing
Airflow
5
(127mm)
5-7/32
(133mm)
5-21/32
(144mm)
5-9/32
(134mm)
13-3/8 (340mm)
diameter
4
(102mm)
Opening for vent pipe to pass through the box
Gray Arrows show Flow of Combustion Air
Form RZ-NA I-SCE, Page 10
Pipe Connections at the Concentric Adapter Box
FIGURE 11 - Concentric Adapter Box Connections
If using 6” diameter pipes , Model SCE always require a 6” to 5” (152 to 127 mm) reducer in the vent pipe.
If using 7” diameter pipes (allowed on Sizes 200-400),
Model SCE always requires a 7” to 5” (178 to 127 mm) reducer in the vent pipe and a 6” to 7” (152 to 178 mm) enlarger for attaching the combustion air pipe.
When pipe diameters dier, depending on direction of airow, join the pipes with either a taper­type reducer or enlarger. Refer to illustrations in FIGURE 11 for pipe connection requirements at the concentric adapter box.
Do NOT make actual connections until after reading the instructions and length requirements for installing the vent/combustion air kit. The connection requirements are the same for both verti-
cal and horizontal systems, but the length of the double-wall pipe will vary.
HORIZONTAL OR VERTICAL?
Is the Separated Combustion Vent/ Combustion Air System Horizontal or Vertical?
instructions begin on page 12.
Horizontal, Option CC6,
Vertical, Option CC2,
instructions begin on page 15.
Form RZ-NA I-SCE, Mfg #207697 Rev 7, Page 11
Loading...
+ 25 hidden pages