Reznor S5BP User Manual

Page 1
S5BP SERIES 11.2 EER
USER’S MANUAL / INSTALLATION INSTRUCTIONS
R410A SPLIT SYSTEM AIR CONDITIONER - 3 PHASE
IMPORTANT
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/ service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
2
Page 3
USER INFORMATION
Important Safety Information ....................................4
Operating Instructions ...............................................4
Cooling Operation .....................................................4
Heating Operation .....................................................4
Operating the Air Conditioner for Automatic
Cooling and Heating ..................................................4
Operating the Indoor Blower Continuously ................4
Turning the Air Conditioner Off ..................................4
Air Conditioner Maintenance .................................... 4
Troubleshooting ......................................................... 4
INSTALLER INFORMATION
Important Safety Information ....................................5
Air Conditioner Installation .......................................6
Before You Install this Unit .........................................6
Locating the Air conditioner .......................................6
Packaging Removal ...................................................6
Rigging & Hoisting .....................................................6
Rooftop ......................................................................6
Ground Level .............................................................7
Connecting Refrigerant Tubing Between the
Indoor & Outdoor Unit ...............................................7
Electrical Wiring ..........................................................8
Pre - Electrical Checklist ...........................................8
Line Voltage ...............................................................8
Grounding..................................................................8
Unbalanced 3-Phase Supply Voltage ........................9
Thermostat Connections ...........................................9
Optional Electric Heater Kits .....................................9
Startup & Adjustments ............................................10
Pre - Start Checklist ................................................10
Start-up Procedure ..................................................10
Air Circulation - Indoor Blower .............................10
Short Cycle Protection .........................................10
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the air conditioner. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
Correcting wiring problems in the electrical circuit supplying the air conditioner.
Resetting circuit breakers or other switches.
Adjusting or calibrating of thermostat.
System Cooling .................................................... 10
System Heating ....................................................10
Refrigerant Charging ............................................... 10
Charging R410A Units in AC Mode with
Outdoor Temperatures Above 55° F ..................... 11
Air Conditioner Maintenance ................................... 11
Replacement Parts ................................................... 11
Component Functions .............................................12
Figures & Tables ....................................................... 12
Figure 5. S5BP Air conditioner Dimensions ......... 12
Table 3. Unit Dimensions & Shipping Weights ..... 12
Electrical Information ............................................... 13
Table 4. Electrical Specs & Physical Data ............13
Figure 6. S5BP Wiring Diagram ........................... 14
Figure 7. Air conditioner T-stat Connections ......... 15
Cooling Charging Charts ......................................... 17
Figure 8. Charging Chart for 7.5 Ton Units ........... 17
Figure 9. Charging Chart for 10 Ton Units ............ 17
INSTALLATION / PERFORMANCE CHECKLIST ..... 20
3
Page 4
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
OPERATING INSTRUCTIONS
NOTE: Thermostat styles vary. Some models may not
include the AUTO mode and others will have the AUTO in place of the HEAT and COOL. Others may include all three. Please refer to the thermostat manufacturer’s User manual for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately 5 minutes following a previous operation or the interruption of the main electrical power.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The optional heating equipment (furnace or electric heat) will cycle on & off to maintain the indoor temperature at the desired heating level.
Operating the AC for Automatic Cooling & Heating
1. Set the thermostat system mode to AUTO and the thermostat fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired temperature level. The thermostat will maintain the desired temperature level by switching between either the outdoor cooling unit or the indoor heating unit (furnace or electric heat) automatically.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation. Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
Turning the Air conditioner Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO (See Figure 1). NOTE: The system will not operate, regardless of the temperature selector setting.
Fan
Mode
Figure 1. Digital Thermostat
AIR CONDITIONER MAINTENANCE
Proper maintenance is most important to achieve the best performance from the appliance and should be performed frequently at the beginning of each air conditioning season.
System
Mode
Temperature
Selector
WARNING:
Your Air Conditioner contains liquid and gaseous refrigerant under pressure. Installation and servicing should only be attempted by qualifi ed, trained personnel thoroughly familiar with the equipment and safe responsible refrigerant handling procedures. Failure to comply with this warning could result in equipment damage, personal injury, or death.
Keep the outdoor unit clean. Hose off periodically and keep unit fi ns clear of leaves and grass clippings.
• Keep the outdoor unit clear of obstructions. DO NOT obstruct airfl ow with tall plants or shrubs. DO NOT store gasoline or other fl ammable materials on or near the outdoor unit.
Never operate the appliance without a fi lter installed in the return air duct. Inspect fi lters frequently and replace when necessary with fi lter of same dimensional size.
TROUBLESHOOTING
Check the thermostat setting. Make sure the system mode and temperature settings are correct.
Check the electrical panel for tripped circuit breakers.
Check the fi lters for dust accumulation.
Check the outdoor unit and make sure it is clean and not covered with grass or leaves.
4
Page 5
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
WARNING:
Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage
WARNING:
S5BP Split System Air conditioners leave the factory with a 90 oz. (5.63 Lbs.) R410A refrigerant holding charge. Follow all charging instructions for maximum unit performance and effi ciency. Some local codes require licensed installation/ service personnel to service this type of equipment. Refrigerant charging must be done by qualifi ed personnel familiar with safe and environmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-410A. DO NOT use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
WARNING:
The information listed below must be followed during the installation, service, and operation of this unit. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
• All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
• This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
• Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
• Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fi re extinguisher, etc.) when performing brazing operations.
• This unit is designed for outdoor installations only and should be located in a position as shown on page 6.
• Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
.
sonal
5
Page 6
AIR CONDITIONER INSTALLATION
General Information
The S5BP series air conditioner is designed only for outdoor rooftop or ground level installations. This unit has been tested for capacity and effi ciency in accordance with A.R.I. Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
Before you install this unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the indoor unit's installation instructions for installation details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns. Claims for damage (apparent or concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all instructions before installing the unit.
Locating the Air Conditioner
• Survey the job site to determine the best location for mounting the outdoor unit.
• Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided.
• Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 2 for minimum clearances to obstructions.
• Consideration should be given to availability of electric power, service access, noise, and shade.
TOP OF UNIT
18"
18"
TO BE
UNOBSTRUCTED
18"
18"
Figure 2. Clearance Requirements
Packaging Removal
Locate and remove all screws securing the unit to the shipping skid. NOTE: To prevent damage to the tubing connections, carefully remove the carton and user’s manual from the equipment. Discard the shipping carton.
Rigging and Hoisting
WARNING:
To avoid the risk of property damage, personal injury, or death, it is the rigger’s responsibility to ensure that whatever means are used to hoist the unit are safe and adequate:
The lifting equipment must be adequate for the
load. Refer to Table 3 (page 12) for unit weights.
The unit must be lifted from the holes in the
base rails using cables or chains.
Spreader bars are required to protect the unit
and ensure even loading.
Keep the unit in an upright position at all times.
All panels must be securely in place during
rigging and hoisting.
Rooftop
Rooftop installations must be located according to local building codes or ordinances and these requirements:
• Units may be installed on Class A, B, or C roof covering material. The roof must be capable of handling the weight of the unit. For unit weights, see Table 3 (page
12). Reinforce the roof if necessary.
• Secure optional mounting pad or frame to roof using acceptable mechanical methods per local codes.
6
Page 7
Ground Level
Ground level installations must be located according to local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown in Figure 2 (page 6).
• A suitable mounting pad (Figure 3) must be provided and be separate from the building foundation. The pad must be level and strong enough to support the unit’s weight. The slab height must be a minimum of 2” (5 cm) above grade and with adequate drainage.
2”
Figure 3. Ground Level Installation
Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit
CAUTION:
This system uses R-410A refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.
After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is recommended that dry nitrogen be fl owing through the joints during brazing. This will prevent internal oxidation and scaling from occurring.
• Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing.
• Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
• Tubing should be kept clean of foreign debris during installation.
• Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
• The maximum recommended interconnecting refrigerant line lengths are listed in Table 4 (page 13) and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet.
• If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
• A fi lter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
• Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
7
Page 8
ELECTRICAL WIRING
WARNING:
To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation
• All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist:
Verify that the voltage, frequency, and phase of the
supply source match the specifi cations on the unit rating plate. Refer to Table 4 (page 13).
Verify that the service provided by the utility is suffi cient
to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper high and low voltage wiring.
Verify factory wiring is in accordance with the unit
wiring diagram (Figure 6, page 14). Inspect for loose connections.
Phase balance on 3 phase units must always be
checked. See Unbalanced 3-Phase Supply Voltage section (page 9).
Line Voltage
• A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.
An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
• Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming fi eld wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
• The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagram / schematic (Figures 6 & 7) for identifi cation and location of outdoor unit fi eld wiring interfaces. Make all electrical
connections in accordance with all applicable codes and ordinances.
• Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
• Use only copper wire for the line voltage power supply to this unit as listed in Table 1. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
• 208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V.
• Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not use gas piping as an electrical ground
This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Use the grounding lug provided in the control box for grounding the unit.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
200 150 100 50
6 8 10 14 15 46812 20 46810 25 44610 30 3468 35 3468 40 2346 45 2346 50 2346 55 1234 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
!
Supply Circuit
Ampacity
8
Page 9
Unbalanced 3-Phase Supply Voltage
Voltage unbalance occurs when the voltages of all phases of a 3-phase power supply are no longer equal. This unbalance reduces motor effi ciency and performance. Some underlying causes of voltage unbalance may include: Lack of symmetry in transmission lines, large single-phase loads, and unbalanced or overloaded transformers. A motor should never be operated when a phase imbalance in supply is greater than 2%.
Perform the following steps to determine the percentage of voltage imbalance:
1. Measure the line voltages of your 3-phase
Example:
power supply where it enters the building and at a location that will only be dedicated to the unit installation (at the
AB = 451V BC = 460V AC = 453V
units circuit protection or disconnect).
2. Determine the average voltage in the power supply.
In this example, the measured line voltages were 451, 460, and 453. The average would be 454 volts (451 + 460 + 453 = 1,364 / 3 = 454).
3. Determine the maximum deviation:
Thermostat Connections
• Ther mostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment.
• Single stage or two-stage thermostats can be used with this equipment depending on optional accessories (i.e. economizer) installed with the unit. Select a thermostat that operates in conjunction with the installed accessories. A typical commercial installation with an air conditioner thermostat and air handler (with & without an economizer) is shown in Figure 7 (page 15).
• The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/ NFPA 70) and with applicable local codes having jurisdiction.
• The low voltage wires must be properly connected to the units low voltage terminal block. Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2.
• The thermostat should be mounted about 5 feet above the fl oor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fi replaces, sunlight, or lighting fi xtures, and convective heat from warm air registers or electrical appliances. Refer to the thermostat manufacturer’s instruction sheet for detailed mounting and installation information.
Example:
From the values given in step 1, the BC voltage (460V) is the greatest difference in value from the average:
460 - 454 = 6
Highest Value
454 - 451 = 3 454 - 453 = 1
4. Determine percent of voltage imbalance by using the results from steps 2 & 3 in the following equation.
% Voltage Imbalance
=100x
Example:
100
x
= 1.32%
6
454
max voltage deviation from average voltage
average voltage
The amount of phase imbalance (1.32%) is satisfactory since the amount is lower than the maximum allowable 2%. Please contact your local electric utility company if your voltage imbalance is more than 2%.
Recommended T-Stat Wire
Thermostat Wire Gauge
Length (Unit to T-Stat)
2-Wire
(Heating)
(Heating/Cooling)
5-Wire
24 55 25
22 90 45
20 140 70
18 225 110
Table 2. Thermostat Wire Gauge
Optional Electric Heater Kits
Optional fi eld-installed electric heater kits are available in 10 kw through 36 kw heating capacities. Split System Air conditioners are designed to allow optional auxiliary electric heat to be fi eld installed as required by the building’s particular heating load. The options available for each unit are shown in the heater kit installation instructions.
Install the heater kits as directed by the instructions supplied with the heater kit. Follow all cautions and warnings as directed.
9
Page 10
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the indoor unit is level and allows proper
condensate drainage.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/ control panels are in place.
Verify that the duct work is sealed to prevent air leakage. Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
Verify that the low voltage wires are securely connected
to the correct leads on the low voltage terminal strip.
Verify that the power supply branch circuit overcurrent
protection is sized properly.
Verify that the thermostat is wired correctly.
Start-Up Procedures
WARNING:
This unit is equipped with a crankcase heater. Allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. This warning should be followed at initial start up and any time the power has been removed for 12 hours or longer.
The thermostat's function mode should be set to OFF and the fan mode should be set to AUTO. Close all electrical disconnects to energize the system.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan mode to ON.
2. Verify the blower runs continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. If insuffi cient air is detected, examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the blower stops running.
NOTE: On 3 phase air handler models only - If blower is spinning opposite of arrow direction, shut off the main power to the unit and switch any two fi eld wires at the disconnect. DO NOT alter unit wiring.
Anti-Short Cycle Timer Protection
1. Set the thermostat system mode to COOL. Note the temperature setting of the thermostat and gradually raise the set-point temperature until the unit de­energizes.
2. Immediately lower the set point temperature of the thermostat to its original setting and verify that the indoor blower is energized and outdoor unit remains de-energized.
3. After approximately 5 minutes, verify the compressor and fan energize and the temperature of the discharge air is cooler than the room temperature.
System Cooling
1. Set the thermostat’s system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated by arrow. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
3. Verify HI and LO refrigerant pressures.
NOTE: If refrigerant pressures are abnormal and
the compressor is rotating backwards, shut off main power to the unit and switch any two fi eld wires at the disconnect. DO NOT alter unit wiring.
4. Allow the system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower should also stop unless fan mode is set to the ON position.
System Heating (optional)
1. Set the thermostat's system mode to HEAT and the temperature mode above room temperature.
2. Verify the optional heating equipment (furnace or electric heat) and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
Refrigerant Charging
WARNING:
S5BP Split System Air Conditioners leave the factory with a 90 oz. (5.63 Lbs.) R410A refrigerant holding charge. Follow these charging instructions for maximum unit performance and effi ciency. Some local codes require licensed installation/service personnel to service this type of equipment. Refrigerant charging must be done by qualifi ed personnel familiar with safe and environmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
10
Page 11
After refrigerant line connections are completed, it is required that you leak check and evacuate the indoor section and all line connections (using proper methods) before fi nalizing the full system refrigerant charge. For fi nal charges based on matched systems and specifi ed line lengths, see physical and electrical specifi cations (Table 4, page 13).
• To achieve rated capacity and effi ciency the compressor must be exposed to refrigerant for at least 24 hours prior to running and then the compressor must be run for a minimum of 12 hours.
• Refrigerant charging charts (Figures 8 & 9) are applicable only to matched assemblies of NORDYNE equipment and listed airfl ows for the indoor coil. S5BP outdoor units with indoor coils not listed are not recommended and deviations from rated airfl ows or non-listed combinations may require modifi cation to the expansion device and refrigerant charging procedures for proper and effi cient system operation. See pages 16 - 17.
• The refrigerant charge can be checked and adjusted through the service ports provided external to the outdoor unit. Use only gage line sets which have a “Schrader” depression device present to actuate the valve.
Charging an R410A system in AC mode at outdoor temperatures above 55° F for optimized sub-cooling of 10° F - 12° F.
1. With the system operating at steady-state, measure
the liquid refrigerant pressure (in PSIG) at the outdoor unit service valve.
2. Measure the liquid refrigerant temperature (in
Fahrenheit) at the service valve.
3. Determine the required liquid refrigerant pressure
from the appropriate charging chart (Figures 8 or 9).
• If the pressure measured in Step 1 is greater than the required liquid refrigerant pressure determined in Step 3, then there is too much charge in the system. Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged.
• If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3, there is too little charge in the system. Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged.
AIR CONDITIONER MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Proper maintenance is important to achieve optimum performance from the air conditioner. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. Routine maintenance should include the following:
• Inspect and clean or replace air fi lters at the beginning of each heating and cooling season, or more frequently if required.
• Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
• Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
CAUTION:
The unit should never be operated without a fi lter in the return air system. Replace disposable fi lters with the same type and size.
• Do not attempt to add additional oil to motors unequipped with oil tubes. The compressor is hermetically sealed at the factory and does not require lubrication.
REPLACEMENT PARTS
Replacement parts are available through all Nordyne Please have the complete model and serial number of the unit when ordering replacement parts.
ELECTRICAL:
Capacitors Temperature Limit Switches
Compressors Thermostats
Contactors Time Delay Relays
Pressure Switches Transformers
Relays
MOTORS:
Blower Motor
Fan Motor
COMPONENTS:
Blower Assembly Fan Grille
Cabinet Panels Filter/Driers
Expansion Valves
distributors.
11
Page 12
COMPONENT FUNCTIONS
Anti-Short Cycle Timer (ASCT)
A protective short cycle timer is factory installed and located in the control panel of the outdoor section. If power to the compressor low voltage control circuit is interrupted, the outdoor unit will not energize for approximately 5 minutes.
High Pressure Switch (HPS)
A high-pressure switch is factory-installed and located in the liquid line internal to the outdoor unit. The switch is designed to protect the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the liquid pressure rises above 650 psig, then the switch will open and de­energize the outdoor unit. The switch will close again once the liquid pressure decreases to 460 psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
FIGURES & TABLES
DO NOT OBSTRUCT TOP OF UNIT
Allow 6' Minimum Clearance
Low Pressure Switch (LPS)
A low-pressure switch is factory-installed and located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
D
W
H
Figure 5. S5BP Air Conditioner Dimensions
Model
Number
S5BP-
090C 386 420 44 1/4 37 1/2 37 1/2 50 090D 386 420 44 1/4 37 1/2 37 1/2 50 120C 423 457 52 1/4 37 1/2 37 1/2 58 120D 423 457 52 1/4 37 1/2 37 1/2 58
Without Packaging Shipping Weight All dimensions in inches
Unit Weights (Lbs.) Height -H- Width -W- Depth -D- Shipping Height
12
Table 3. Unit Dimensions & Shipping Weights
Page 13
ELECTRICAL INFORMATION
Model Number
S5BP-
208-230V 460V 208-230V 460V
920888 920889 920890 920891
PERFORMANCE DATA
090C 090D 120C 120D
Gross Cooling Capacity (95
1
Net Cooling Capacity - Btuh 90,000 90,000 117,000 117,000
1
A.R.I. Rated Airfl ow - C.F.M. 3,000 3,000 4,000 4,000
2
Cooling - Effi ciency E.E.R. (Btu/Watt) 11.70 11.70 11.20 11.20
3
Cooling - Effi ciency I.E.E.R. 11.80 11.80 11.50 11.50
o
F) Btuh 92,400 92,400 121,700 121,700
ELECTRICAL RATINGS
Volts / Phase / Hz. 208-230 / 3 / 60 460 / 3 / 60 208-230 / 3 / 60 460 / 3 / 60
Operating Voltage 187-253 414-506 187-253 414-506
Unit Rated Ampacity 28.3 13.9 33.4 18.4
Minimum Circuit Ampacity (MCA) 34.6 17.0 40.9 22.6
4
Max. Overcurrent Protection (MOP) 50 25 70 35
Compressor Data:
1 ea. 1 ea. 1 ea. 1 ea.
Compressor (Scroll) ZP83KCE-TF5 ZP83KCE-TFD ZP103KCE-TF5 ZP103KCE-TFD
Volts / Phase /Hz. 208-230 / 3 / 60 460 / 3 / 60 208-230 / 3 / 60 460 / 3 / 60
Rated Load Amps (RLA) 25.0 12.2 30.1 16.7
Lock Rotor Amps (LRA) 164 100 225 114
Stages / Percent 1 / 100 1 / 100 1 / 100 1 / 100
Crankcase Heater - Qty. / Type 1 / Band 1 / Band 1 / Band 1 / Band
Outdoor Fan Assembly:
1 ea. 1 ea. 1 ea. 1 ea.
Volts / Phase /Hz. 208-230 / 1 / 60 460 / 1 / 60 208-230 / 1 / 60 460 / 1 / 60
Motor - HP / RPM 3/4 - 875 3/4 - 875 3/4 - 875 3/4 - 875
Motor Amps 3.3 1.7 3.3 1.7
Fan Blade - Diameter / Pitch / # Blades 30” / 22 / 3 30” / 22 / 3 30” / 26 / 3 30” / 26 / 3
RPM / CFM (Max. - Total) 850 - 7,200 850 - 7,200 850 - 8,000 850 - 8,000
PHYSICAL DATA & REFRIGERANT SPECS
Outdoor Coil Assembly:
2
Area (Ft.
) 31.94 31.94 38.33 38.33
1 ea. 1 ea. 1 ea. 1 ea.
Rows - FPI 2 - 16 2 - 16 2 - 18 2 - 18
Tube Diameter 3/8” OD 3/8” OD 3/8” OD 3/8” OD
Refrigerant Suction Line - Length / OD
0 - 75 Ft. / 1-1/8” 0 - 75 Ft. / 1-1/8” 0 - 100 Ft. / 1-3/8”
76 - 100 Ft. / 1-3/8”
(6)
76 - 100 Ft. / 1-3/8”
(6)
(6)
0 - 100 Ft. / 1-3/8”
Refrigerant Liquid Line - Length / OD All Lengths - 5/8” OD All Lengths - 5/8” OD All Lengths - 5/8” OD All Lengths - 5/8” OD
Refrigerant Charge. R410A R410A R410A R410A
Factory Holding Charge - oz 90 90 90 90
5
Total System with 25’ Line Set 416 416 520 520
High Pressure Switch (PSIG)
Loss of Charge Pressure Switch (PSIG)
Cut Out: 650 +/- 15
Cut In: 460 +/- 15
Cut Out: 5 +/- 5
Cut In: 20 +/- 5
Net Unit Weight - Lbs. (No Packaging) 386 386 423 423
Approximate Shipping Weight - Lbs. 420 420 457 457
Note: Net capacity includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.
1
Cetifi ed in accordance with A.R.I. Standard 340/360 at 95° F Outdoor DB and 80° F db/67° F wb evaporator entering air at minimum
external duct static pressures allowed by the standard.
2
E.E.R. - Energy Effi ciency Ratio. E.E.R. is determined @ 95° F Outdoor DB & 80° F DB / 67° F WB Air Indoor
3
I.E.E.R. - Integrated Energy Effi ciency Ratio. Cetifi ed in accordance with A.R.I. Standard 340/360.
4
Delay Fuse or HACR Type Curcuit Breakers can be used.
5
Add / Subtract 9.0 oz. of refrigerant per 5 feet change in length from original 25 Ft. lineset total system charge.
6
Requires a 1-3/8” to 1-1/8” reducer line to unit.
(6)
Table 4. Electrical Specifi cations & Physical Data - 11.2 E.E.R. - 3 Phase / 60 Hz
13
Page 14
Three Phase
1. Couper le courant avant de faire letretien.
2. Employez uniqement des conducteurs en cuivre.
RED
3 PHASE OUTDOOR MOTOR WIRING
TEST
T2
T1T3
TIMER
CYCLE
ANTI-SHORT
0610
711089A
BROWN
BLACK
T1 T2 T3
LPS
BROWN
BLACK
L3
YELLOW
L1
YELLOW
YELLOW
OR ORANGE
YELLOW
OR ORANGE
RED
BLACK
60 Hz
TRANSFORMER
HPS
L2
GREEN
CONTACTOR
GREEN
BLACK
24V
230V
SECONDARY
460V
WHITE
PRIMARY
208V
C
Y
R
SEE NOTE 7&8
24V
380V
415V
(Replaces 7110890)
¢711089?¤
PRIMARY
BLACK
WHITE
SEE NOTE 9
T1 T2 T3
ORANGE
AUX.
L3
BLACK
BLACK
YELLOW
T1
MOTOR
OUTDOOR FAN
SINGLE PHASE
CCH
T2
ORANGE
BLACK
PURPLE
R
S
SINGLE PHASE OUTDOOR FAN MOTOR
3. Furnace/Air Handler w/factory equipped 24 V control circuit transformers, should be
1. Disconnect all power before servicing.
NOTES:
Commercial Split System Air Conditioner (Outdoor section)
WIRING DIAGRAM
modified/rewired to ONLY use 24V transformer from outdoor section. See installation
2. For supply connections, use copper conductors only.
6. Wires connected to normally closed contacts.
4. For replacement wires, use conductors suitable for 105° C
instructions for typical modifications.
5. For ampacities and overcurrent protection, see unit rating plate.
C
L3
L2
L1
on 208V tap.
7. Transformer primary connection will match unit rated voltage.
8. For 208V operation remove white wire from 230V tap and place
place on 415V tap.
9. For 415/420V operation remove white wire from 380V tap and
CC
CC
CC
RED
MOTOR
L2
THREE PHASE
OUTDOOR FAN
L1
L1 L2 L3
SWITCH
SEE NOTE 6
T3
CCHCAS
C
S
BLACK
BLACK
COMPRESSOR
T3
T2
R
T1
BLACK
COMPRESSOR
L1
L3
GRD
L2
THREE PHASE
FIELD SUPPLY
ASCT
24V
CC
ASCT
50 Hz
CONNECTIONS
TRANSFORMER
C
LOW
SWITCH
PRESSURE
HIGH
SWITCH
PRESSURE
Y
R
LEGEND:
FIELD WIRING
HPS HIGH PRESSURE SWITCH WITH AUTO RESET
CAS CONTACTOR AUXILLIARY SWITCH (1NO/1NC)
CCH COMPRESSOR CRANKCASE HEATER
ASCT ANTI SHORT CYCLE TIMER
LOW VOLTAGE
CC COMPRESSOR CONTACTOR
HIGH VOLTAGE
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE
LPS LOW PRESSURE SWITCH
14
Figure 6. S5BP Wiring Diagram
Page 15
NOTE:
C &W2 to be connected to electric heat.
SINGLE STAGE
HEAT/COOL THERMOSTAT
RCG
YW
OPTIONAL
TO FIELD SUPPLIED DISCONNECT
GND
L1
L2
L3
BLOWER
MOTOR
FREEZESTAT
C
Y R
OUTDOOR
SECTION
C
Y R
OUTDOOR
SECTION
SINGLE STAGE
HEAT/COOL
THERMOSTAT
RCG
YW
OPTIONAL
FREEZESTAT
G
C W2 W1
O
Y
R
TERMINAL
BOARD
BROWN
G C
W2
GREEN
BLACK
See Note
W1
O Y
BLACK
R
TERMINAL
BOARD
SINGLE STAGE HEAT/COOL THERMOSTAT- NO ECONOMIZER
1. C & W2 to be connected to electric heat.
2. Remove BLACK wire from air handler low voltage terminal board Y terminal and connect to YELLOW wire from economizer.
3. 2nd Stage refrigerant cooling with optional economizer installed. A 2 stage thermostat is required for simultaneous operation of the economizer
TO FIELD SUPPLIED DISCONNECT
GND
BLACK
BLACK
GREEN
Note 1
Note 3
AIR HANDLER
SECTION
BLOWER
MOTER
Note 2
L2
L3
B
Y1
Y2
C7150 M.A.S.
L1
Note 4
GRY
YEL
GRN
BLK
WHITE
ORN BLUE
RED
RED
and refrigerant system. Connect Y2 from 2 stage thermostat to BLUE wire from economizer. If installing an economizer in this unit, refer to the Economizer installation instructions for proper set up and operation.
4. Heat Pump Economizer Relay. For heat pump applications only, connect B from thermostat to GREY wire from Economizer. Required for proper operation of an economizer (optional) in the heat pump Heating mode. If installing an economizer in this unit, refer to the Economizer installation instructions for proper set up and operation.
GRY-90”
AB
9
7
46 13
OPTIONAL
ECONOMIZER
AIR HANDLER
SECTION
NOTES:
GRN-18” GRN-18”
VIO-14”
s
BLU-14”
C7400A
YEL-18”
W7459A
TR
S
o
S
r
1
3
T
P
2
4
TR 1
JUMPER
5
2K
T1
P1
WIRE
1S
1S
TB-11 M7415A
BLK-12”
T
RED-12”
T1
GRY-12”
P1
BLK-12”
P
BLU-12”
TR
TR1
MA
MIN. POT.
SINGLE STAGE HEAT/COOL THERMOSTAT- WITH ECONOMIZER
Figure 7. Typical Air conditioner Thermostat Connections
15
Page 16
S5BP CHARGING CHARTS - COOLING ONLY
Application Notes on the Use of Charging Charts
This equipment’s cooling system contains refrigerant under high pressure. Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit. Review the factory literature and safety warnings prior to servicing.
• When repairing system leakages, always use a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before re-charging. Always replace the fi lter-dryers when performing any repair to the refrigeration system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns and weigh in the refrigerant to the amount specifi ed on the unit rating label.
• All S5BP-090/120 units are shipped from the factory with a 90 oz. holding charge refrigerant. Inspect the unit rating label to determine the units information prior to working on the system. DO NOT mix different refrigerants or charge the unit with a refrigerant not listed on the unit rating label.
• Charging charts are valid for a variety of indoor return air conditions and are most infl uenced by the outdoor ambient temperature, outdoor fan operation, and the unit operating voltage. Before using these charts, ensure the unit is in a stable operating mode. As shown in the charging charts (Figures 8 or 9, page 17), the ideal system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of sub­cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit effi ciency (EER) or rated Coeffi cient of Performance (COP) in heating mode.
• To inspect a systems operation, using quality instruments, match the measured liquid temperature to the units chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.
• For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase balance and the refrigeration system for leaks.
• Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more signifi cant deviation than the amount stated above.
DO NOT use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient kit instructions for more information. (If applicable)
16
Page 17
S5BP Charging Chart - Cooling
7.5 Ton Split System A.C. w/ B5SM-090* Indoor Air Handler
525
500
Remove refrigerant when above curve
475
450
425
400
375
350
325
300
Liquid Pressure (psig)
275
250
225
Add refrigerant when below curve
200
175
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (° F)
Figure 8. Charging Chart for 7.5 Ton Units
S5BP Charging Chart - Cooling
10 Ton Split System AC w/ B5SM-120* Indoor Air Handler
525
500
Remove refrigerant when above curve
475
450
425
400
375
350
325
300
Liquid Pressure (psig)
275
250
225
200
175
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (° F)
Add refrigerant when below curve
Figure 9. Charging Chart for 10 Ton Units
17
Page 18
18
Page 19
19
Page 20
INSTALLATION/PERFORMANCE CHECK LIST
INSTALLATION ADDRESS:
CITY ________________________ STATE ________________
UNIT MODEL # ________________________________________
UNIT SERIAL # _______________________________________
Unit Installed Minimum clearances per Figure 2 (page 6)?
INSTALLER NAME:
CITY _______________________ STATE ________________
ELECTRICAL SYSTEM:
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Rated Voltage: ___________________________________ VOLTS
L1-L2 Volts: _____________________________________ VOLTS
L1-L3 Volts: _____________________________________ VOLTS
YES NO
REFRIGERATION SYSTEM:
Was unit given 24 hr warm up period for crankcase heaters?
Stage-1 Liquid Pressure (high side) ________________________
Stage-1 Suction Pressure (low side) ________________________
Has the owner’s information been reviewed with the customer?
Has the Literature Package been left with the unit?
YES NO
YES NO
YES NO
L2-L3 Volts: _____________________________________ VOLTS
Avg. Volts: ______________________________________ VOLTS
Max. deviation of voltage from avg. volts: ___________________________________ VOLTS
% Volt imbalance: ________________________________ VOLTS
Blower Motor HP: ________ Sheave Setting ___________# Turns
Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
Is the heat anticipator setting correct? (If Applicable)
YES NO
IMPORTANT - This product has been designed and manufactured to meet ENERGY STAR criteria for energy effi ciency. However, proper refrigerant charge and proper air fl ow are critical to achieve rated capacity and effi ciency. Installation of this product should follow the manufacturer’s refrigerant charging and air fl ow instructions. Failure to confi rm proper charge and airfl ow may reduce energy effi ciency and shorten equipment life. This Applies only to 7.5 TON MODELS
Specifi cations & illustrations subject to change without notice or incurring obligations. O'Fallon, MO | Printed in U.S.A. (06/10)
¢7090936¤
709093A (Replaces 7090930)
Loading...