Reznor RHC 4000(M) DJL, RHC 4000(M) RJL User Manual

®
1307RHC4DJL/RJL--EN
Gas-Fired, Balanced-Flue or Power-Vented Unit Heaters
RHC 4000(M) DJL for indoor use
RHC 4000(M) RJL for outdoor use
NSTRUCTION DOCUMENT APPLIES FOR:
Installation
Commissioning
Servicing
Applies to
Austria,Belarus, Bulgaria, China, Czech Republic, Croatia, Cyprus, Denmark,
England, Estonia, Finland, Germany, Greece, Hungary, Iceland, Latvia, Lithuania,
Montenegro, New Zealand, Norway, Poland, Romania, Russian Federation, Serbia,
Slovakia, Slovenia, Spain, Sweden, Turkey, Ukraine
These appliances meet the following EC Directives
Dir 2009/142/EC: GAD Dir 2004/108/EC: EMC Dir 2006/95/EC: LVD Dir 2006/42/EC: MD (annex II, sub B)
WARNING
Please read this document carefully before commencing installation commissioning and/or servicing. Leave it with the user or attached to the appliance or gas service meter after installation
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. All work must be carried out by appropriately qualified persons. The manufacturer does not take any responsibility in the event of non-observance of the regulations concerning the connection of the apparatus causing a harmful operation possibly resulting in damage to the apparatus and/or environment in which the unit is installed.
Reznor Europe N.V. – J&M Sabbestraat 130 – B 8930 Menen
Tel : +32 56/52 95 11 - Fax : +32 56/52 95 33
Subject to modifications
P 1/24-1307RHC4DJL/RJL—EN,
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Basic Information
1.2 Warranty
2.0 TECHNICAL DATA
3.0 GENERAL REQUIREMENTS
3.1 General
3.2 Specific heater location
3.3 Minimum airflow duty
3.4 Compartment dimensions
3.5 Maximum airflow conditi ons
3.6 Combustion air supply & flue system (applies only to DJL models)
3.7 Air Supply (applies only to DJL models)
3.8 Electrical supply
3.9 Gas supply
4.0 INSTALLATION
4.1 Uncrating and preparation
4.2 Fitting the combustion air inlet/flue system (applies only to DJL)
4.3 Electrical Connection
4.4 Room Thermostat Siting
5.0 COMMISSIONING AND TESTING
5.1 Electrical Check
5.2 Gas Connection
5.3 Lighting the Heater
5.3.1 To Turn the Heater ON
5.3.2 To Turn the Heater OFF for Short Periods
5.3.3 To Turn the Heater OFF for Long Periods
5.4 Heater Pipework
5.5 Adjustments
5.6 Options
5.6.1 2 stage burner control
5.6.2 Modureg V7335A 2000 series modulation system
5.7 Air heater controls & operation
5.8 Handing Over
6.0 SERVICING INSTRUCTIONS
7.0 REMOVAL AND REPLACEMENT OF PARTS
7.1 Main Burner Removal
7.2 Main Burner Injectors
7.3 Ignition System
7.4 Gas control valve
7.5 Limit Controls
7.6 Combustion Air Control Switch
7.7 Combustion Air Fan
8.0 FAULT FINDING
9.0 PARTS LIST
10.0.GAS CONVERSION
11.0 USERS INSTRUCTIONS
12.0 HEALTH & SAFETY STATEMENT
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WA RNING personal injury or death and/or property damage.
3. CAUTION personal injury and/or property damage.
: Failure to comply could resul t in severe
: Failure to comply could result in minor
WARNING:
The electrical isolator should only be used in an emergency and should not be used for closing down the main burner, as it switches off the fan prematurely and may damage the heat exchanger, invalidating the warranty.
This appliance is not intended for use by persons (including children) with reduced sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance
1.0 INTRODUCTION
1.1 BASIC INFORMATION
The instructions in this manual apply to the following gas­fired/fan-assisted warm air heaters:
RHC 4000(M) DJL
only (when installed where the height above floor level is greater than 1,8 meters measured to the underside of the appliance they may be used as a garage air heater).
Model RHC 4000(M) DJL heaters are approved for:
Type C12 - horizontal vent for balanced-flue heaters; Type C Type B
(through the wall)
RHC 4000(M) RJL
handlers built for outdoor Model RHC 4000 RJL heaters are approved for outdoor or
rooftop application.
Category : see table 2A.
All models & sizes are available for use with either natural, propane or butane gas with operating temperatures between
-15°C and 40°C.
These instructions are only valid for the country of use as indicated on the appliance. If these symbols are not shown, it is necessary to obtain appropriate technical instructions. Such instructions may be obtained upon request from your supplier. Check that the local distribution conditions of electricity supply, type of gas and pressure of the appliance are compatible with the data plate.
- vertical vent for balanced-flue heaters;
32
– vertical vent (through the roof) or horizontal vent
22
model suitable for indoor air handlers
model suitable for incorporation in air
installation only.
P 2/24-1307RHC4DJL/RJL—EN,
The installation
must comply with the requirements and recommendations of all relevant national and local standardisations.. The installation must also be in accordance with the relevant el ectrical and IEE regul ations.
When the external control calls for heat, an electronic control begins the ignition sequence to provide for a safe start. Under normal conditions the fan motor runs constantly and after a call for heat it switches the heater on thr ough a room or duct stat. However, in some applications, about 30 seconds after the call for heat, the fan control relay will activate the fan motor of the air ha ndler.
The electronic control will supervise the flame during the entire heating cycle to ensure safe operation.
When the required room temperature is reached, the main burner will shut down leaving the fan running to cool down the heat exchanger
In some applications, after approximately 45 seconds, the fan delay relay will turn off the fan (if wired).
2.0 TECHNICAL DATA
2.1 SPECIFICATIONS
Table 1 – Specifications
1.2 WARRANTY
Warranty is void if:
a) Model RHC 4000(M) DJL/RJL heaters are installed in
atmospheres containing flammable vapors or atmospheres containing chlorinated or halogenated hydrocarbons or atmospheres containing any silicone, aluminum oxide, etc., that adheres to spark ignition flame sensing probes.
b) The installation is not in accordance with these
instructions.
c) The maximum airflow through the heat exchanger tubes
is not respected (see section 3.5).
d) The required minimum air delivery is not respected (see
table 3a).
e) The duct dimensions do not comply with the prescribed
dimensions (see table 3b).
f) The inlet tem perature (meas ured at the heat exc hanger
inlet) is lower than the value st at ed o n t he ch a rt (s ee f ig. 5 : dew point occurrence chart).
Heat output
Model
4050 06 62.00 55.90 50.80 5.90 4.50 4.40 0.15 24.00 24.00 4060 07 74.60 67.20 61.20 7,10 5.40 5,20 0.15 28.60 28.60 4075 09 91.50 82.40 75.00 8,70 6.70 6,60 0.15 36.00 36.00 4100 12 120.00 108.40 100.00 11,40 8.80 8,60 0.15 47.00 47.00
4110M.13 136.60 123.00 112.30 13.00 -- 9.60 0.28 51.20 51.20 4125M.15 153.50 138.30 126.30 14.60 -- 10.80 0.28 51.00 51.00 4150M.18 182.90 164.80 151.30 17.40 -- 12.80 0.28 75.80 75.80 4175M.21 211.80 190.80 175.00 20.20 -- 14.90 0.28 99.40 99.40 4200M.24 240.60 216.80 198.70 22.90 -- 16.90 0.65 99.40 99.40
1. GCV (Hs) 3. Heat output depends on airflow – heat output H2 only for airflows above V2
2. NCV (Hi) 4. Natural gas G20 gross calorific value 10.48 kWh/m
Table 2A - Gas category
Heat input
kW gros1KW net
Butane gas G30 gross calorific value 13.7 kWh/kg Propane gas G31 gross calorific value 14.0 kWh/kg
2
H2
3
100%
kW m³/h kg/h kg/h kW kW kW
G20 G30 G31 2 sta ge
Gas rate
4
Pow er
Consumption
3
@ 15 °C, 1013.25 mbar
Heat output
50%
3
Minimum
modulating
output
Country Gas category Country Gas category
Austria II2H3P Belarus II2H3+ Germany I2ELL or I3P Bulgaria I2H or I3B/P Montenegro II2H3+ China II2H3+ New Zealand II2H3+ Czech republic II2H3+ Norway II2H3 B/P Croatia II2H3P Poland II2E3P Cyprus II2H3+ Portugal II2H3+ Denmark II2H3 B/P Romania II2H3P Estonia II2H3+ Russian Federation I2H or I3P England II2H3+ Serbia II2H3+ Finland II2H3 B/P Slovakia II2H3+ Greece II2H3+ Slovenia II2H3+ Hungary II2HS3P Spain II2H3+ Iceland II2H3+ Sweden II2H3 B/P Latvia II2H3+ Turkey II2H3+ Lithuania II2H3+ Ukraine I2H or I3P
P 3/24-1307RHC4DJL/RJL—EN,
Table 2B :Injector size and burner pressure
Belarus, China Croatia, Czech Republic, Cyprus, England, Estonia, Greece, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Portugal, Serbia, Slovenia, Slovakia, Spain , Turkey
Mo d el 4050 06 4060 07 4075 09 4100 12 4110M,13 4125M,15 4150M, 18 4175M,21 4200M,24
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G20
Burner pressure (1) mbar 7,00 7,50 7,50 7,50 7,70 7,40 7,50 7,70 7,70
Nat. Gas
Inlet pressure mbar
mm 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 marking 300 300 300 300 300 300 300 300 300
20
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G31
Burner pr essure (1) mbar 35,50 35, 50 33,90 33,60 35,20 34,80 34,90 35,30 34,40
Prop. Gas
Inlet pressure mbar
mm 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 marking 155 155 155 155 155 155 155 155 155
37
Romania, Poland
Mo d el 4050 06 4060 07 4075 09 4100 12 4110M,13 4125M,15 4150M, 18 4175M,21 4200M,24
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G20
Burner pressure (1) mbar 7,00 7,50 7,50 7,50 7,70 7,40 7,50 7,70 7,70
Nat. Gas
Inlet pressure mbar
mm 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 marking 300 300 300 300 300 300 300 300 300
20
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G31
Burner pr essure (1) mbar 28,90 28, 44 27,90 26,80 28,20 28,20 27,90 28,40 26,50
Prop. Gas
Inlet pressure mbar
mm 1,65 1,65 1,65 1,65 1,65 1,65 1,65 1,65 1,65 marking 165 165 165 165 165 165 165 165 165
30
Germany,Hungary, Russian Federation, Ukraine, Austria
Mo d el 4050 06 4060 07 4075 09 4100 12 4110M,13 4125M,15 4150M, 18 4175M,21 4200M,24
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G20
Burner pressure (1) mbar 7,00 7,50 7,50 7,50 7,70 7,40 7,50 7,70 7,70
Nat. Gas
mm 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 marking 300 300 300 300 300 300 300 300 300
Inlet pressure mbar Injector quantity 6 7 9 12 13 15 18 21 24
Injector size
G31
Burner pr essure (1) mbar 35,50 35, 50 33,90 33,60 35,20 34,80 34,90 35,30 34,40
Prop. Gas
mm 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 marking 155 155 155 155 155 155 155 155 155
Inlet pressure mbar (* ): Inlet pressure for Hungary = 25mbar
Bulgaria, Denmark, Finland, Norway, Sweden
Mo d el 4050 06 4060 07 4075 09 4100 12 4110M,13 4125M,15 4150M, 18 4175M,21 4200M,24
Injector quantity 6 7 9 12 13 15 18 21 24 Injector size
G20
Burner pressure (1) mbar 7,00 7,50 7,50 7,50 7,70 7,40 7,50 7,70 7,70
Nat. Gas
mm 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 3,00 marking 300 300 300 300 300 300 300 300 300
Inlet pressure mbar Injector quantity 6 7 9 12 13 15 18 21 24
Injector size
G31
Burner pr essure (1) mbar 27,60 27, 50 25,40 27,30 27,69 27,28 27,35 27,67 29,96
Prop. Gas
mm 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 1,55 marking 155 155 155 155 155 155 155 155 155
Inlet pressure mbar
(1) : with open service door
20(*)
50
20
30
P 4/24-1307RHC4DJL/RJL—EN,
2.2. MOUNTING FLANGE & MAIN DIMENSIONS
RHC 4000 DJL/RJL
1.Gas connection ¾”
2.Flue outlet
3.Electrical connection
Figure 1 : Side view
Figure 2 : Top view
RHC 4000(M) DJL/RJL
Figure 3 : Front view
TYPE A B B1 B2 A1 A2 C C1 E A1 A2 C C1 E
4050 06 531 800 613 187 85 466 224 268 118 85 446 291 268 118 4060 07 601 800 613 187 160 441 224 268 118 85 516 291 268 118 4075 09 741 800 613 187 160 581 224 268 118 85 656 291 268 118 4100 12 950 800 613 187 160 790 224 268 118 85 865 291 268 118
4110M.13 1132 930 778 152 190 942 361 348 188 190 942 364 351 191 4125M.15 1272 930 778 152 190 1082 361 348 188 190 1082 364 351 191 4150M.18 1481 930 778 152 190 1291 361 348 188 190 1291 364 351 191 4175M.21 1691 930 778 152 190 1501 361 348 188 190 1501 364 351 191 4200M.24 1900 930 831 99 139 1761 352 445 179 139 1761 354 447 181
DJL/RJL DJL RJL
P 5/24-1307RHC4DJL/RJL—EN,
2.3 W
/
/
EIGHTS
Weights (kg) 4050 06 4060 07 4075 09 4100 12 4110M.13 4125M.15 4150M.18 4175M.21 4200M.24 unit 90 100 120 149 200 220 250 279 313 packaging 292929295858585858 total 119 129 149 178 258 278 308 337 371
3.0 GENERAL REQUIREMENTS
3.1 GENERAL
It is important that all gas appliances are installed in accordance with the rules in force and by appropriately qualified persons. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure co mpli an ce wi th the law.
Caution : Air heaters should not be installed in corrosive atmospheres, i.e. near plating spray or de-greasing plants or in areas where there is a fire risk.
Care should be exercised when designing ducting systems especially with regard to the application of restriction and direction turning fittings, i.e. elbows directly on to the air heater, doing so can cause a n uneven and turbul ent air flo w across the heat exchanger resulting in heat exchanger spots and nuisance shut down of the gas burner due to localized overheating, thus activating thermal over-heat controls. The location must als o provide sufficient spa ce to allow the
Table 3a
Min. air volume required
With heat output
Model
4050 06 3900 1. 4060 07 4700 1.31 7150 1.99 4075 09 5700 1.
4100 12 7500 2.08 11700 3.25 4110M.13 --- --- 13600 3,80 4125M.15 --- --- 15600 4,30 4150M.18 --- --- 12300 3,40 4175M.21 --- --- 14100 4,00 4200M.24 --- --- 16300 4,50
(*) : cfr. table 1
H1 (*)
V1 V1 V2 V2
3
m
h
m³/s
08 5950 1.65
58
COMPARTMENT DIMENSIONS
3.4
Figure 4
With heat output
3
m
h
8800 2.
H2 (*)
m³/s
44
heater to be serviced.
Horizontal airflow
SPECIFIC HEATER LOCATIONS
3.2
DJL installation :
Do not locate the air heater where it may be e xposed to water spry, rain, etc.
The location chosen for the air heater must permit the provision of a satisfactory flue system venting to outdoor atmosphere and adequately ventilated to provide for combustion air.
Installation clearances (mm) (towards combustible materials)
Top 150 Flue connector 150 Access panel 600 Non-access side 150 Bottom 50
RJL installation :
A minimum distance of 1500mm must be maintained on the control side of the appliance. When installed at ground level a fence to guard against damage and to protect the public fro m possi ble injur y shoul d protect the entire installation. Ensure that the air heater is installed in a level plain and that the surface onto which it is installed is vibration free.
MINIMUM AIRFLOW REQUIREMENT
3.3
The minimum airflow duty through the heating section enclosure (see figure 4) must be observed as indicated in table 3a.
Table 3b (dim. expressed in mm)
Model
4050 06 531 461 1049 975 800 800 400 4060 07 601 531 1049 975 800 800 400 4075 09 741 671 1049 975 800 800 400
4100 12 950 880 1049 975 800 800 400 4110M.13 1132 1062 1049 975 930 930 420 4125M.15 1272 1202 1049 975 930 930 420 4150M.18 1481 1411 1049 975 930 930 420 4175M.21 1691 1621 1049 975 930 930 420
4200M. 24 1900 1830 1049 975 930 930 470
Duct channel & controls compartment
H1
H
YY2WW1E
P 6/24-1307RHC4DJL/RJL—EN,
3.5
MAXIMUM AIRFLOW CONDITION
Special attention must be given to ensure Figure 5 : Dew point occurrence chart (condensation zone) that the temperature rise of the a ir, passing through the enclosure (duct channel) around the heat exchanger tubes, is high enough to
20°C
T
avoid condensation forming within the tubes. This condensation forming could occur by super cooling of the products of combustion. Such condensation can be the source of severe corrosion and damage to tubes or part of the tubes.
Figure 5 indicates the probability of condensation forming within the tubes reference :
- the temperature rise of the air through the
20 C
0°C
E
R
R
E
U
G
T
N
A
A
R
H
C
X
E T
A
E
H E
H
T T
A
0 C
-20°C
-20 C 40K 20K 0K
30K
E
P
M
E
T R
I
A T
E
L
N
I
enclosure (around the tubes)
- the inlet air temperature passing over the heat exchanger
TEMPERATURE RISE OVER THE HEAT EXCHANGER
In function of the expected minimum inlet air temperature, the minimum required temperature rise (to avoid condensation) must be derived from the chart below (figure 5).
Example
expected minimum inlet temperature = -5°C minimum required temper ature rise sho wn on the chart
= +13°K
Table 1 indicates the heat output (kW) of the different models.
The maximum allowable airflow through the enclosure (duct channel) around the tubes can be calculated as follows :
V
max
(m³/h)
T
Δ
minimum
0.3423
1000(kW)outputheat
Example : T
= 13K (with min. inlet temp. = -5°C)
min
model 4075 09 at 100% heat output : 75.00kW results into V
= 16850m³/h
max
Remark
:
For air heaters with the option 2 stage gas valve (50% minimum heat input) or the option modulating gas valve (30% minimum heat input) attention must be given to determine the maximum allowable airflow in function of the appropriate heat input.
Example : T
= 13K (with min. inlet temp. = -5°C)
min
model 4075 09 at 50% modulation (see table 1 ‘output’) : 36W
results into :
V
max
3.6 COMBUSTION AIR SUPPLY & FLUE SYSTEM
ATTENTION : this section only applies to DJL models !
The air heater may be installed as a ba lanced flue (Type C) heater, requiring both a combustion air inlet duct and a combustion flue outlet duct (use a s eamless alumi nium pipe ) or as a power vented (Type B) heater flue pipe exhausting to outdoors and takes combustion air directly from the space to be heated.
The center distance between th e combustion air inlet soc ket and the flue outlet socket is 225mm for all models.
Each appliance requires it’s own individual flue system. When several appliances are installed, o ne common flue and combustion air system, thus combining several heaters, is not allowed.
, which requires only a
IMPORTANT:
The flue must be installed in accordance with national and local regulations. Failure to provide proper fluing could result in death, serious injury and/or property damage. The air heater must be installed with a flue to the outside of the building. Safe operation of any power vented gas apparatus requires a properly operating flue system, correct provision for combustion air, and regular maintenance and inspection.
Use of flue restriction rings (Only for 4000M units !!)
To ensure the efficiency of the units, eventually a flue restriction ring needs to be fitted in the outlet collar of the venter housing. The diameter of the restriction ring will be determined by the flue pipe length and the type of appliance (combustion air from environment (appliance B) or combustion air from outside (appliance C)).
CONDENSATION ZONE
10K
1000(kW)36
0.342313
T
h/³m8090
P 7/24-1307RHC4DJL/RJL—EN,
Table 5 : Diameter flue restrictors for DJL
Combustion out and inlet application 4110M.13 4125M,15 4150M.18 4175M.21 4200M.24
2X1m pipe length till 2X3m pipe length 99mm 95mm 93mm 95mm 102mm
C Appliance
B appliance
2X4m pipe length till 2X6m pipe length 107mm 107mm 99mm 107mm 114mm 2X7m pipe length till 2X9m pipe length open open open open open
1X1m pipe length till 1X3m pipe length 90mm 86mm 90mm 90mm 92mm 1X4m pipe length till 1X6m pipe length 93mm 90mm 93mm 95mm 97mm 1X7m pipe length till 1X9m pipe length 96mm 93mm 95mm 99mm 102mm
3.6.1 Flues for power vented instal lations (Type B appliances)
If the air heater is to be in stalled as a type B a ppliance, air for combustion will be taken from within the space where the heater is installed. Ensure that an adequate air supply for combustion and ventilation is provided within the building in accordance with the regulations & rules in force.
The combustion air inlet socket at the appliance must be foreseen with an inlet grill of class IP20 (dia 130 = PN 06
22786 134 (for all types))
Table 5 below shows flue pipe sizes and maximum vent lengths. The minimum flue length is 0.5 meters.
Model RHC 4000(M) DJL
Heater socket & pipe dia mm 130 Center distance B mm 225 Maximum straight length mm 9 Equivalent length of 90° elbow mm 1.5
To avoid leakage use single wall flue pipes of seamless aluminium. All joints must be seal ed to prevent products of combustion from leaki ng into th e building. A n approv ed flue terminal (installed through the roof or the wall) i s requ ired .
If the flue passes through a combustible element of the building it must be enclosed by a sleeve of non-combustible material and separated from the sleeve by at least a 25 mm air break.
The temperature of any combustible material near to the flue must not exceed 65 °C when the heater is in operation .
The flue must be at least 50 mm away from any combustible material.
Single wall flue pipe exposed to cold air or run through unheated areas must be insulated. Where condensation is unavoidable, provision must be made for the condensation to flow freely to a point to which it can be released, i.e. a drain or gully.
The condensation drain from the flue must be constructed from non-corrodible material not less than 20 mm diameter. Copper or copper-based alloys must not be used for condensation drains.
3.6.2 Combustion air inlet pipe & flue pipe for balanced flue installation (Type C appliances)
Balanced flue air heaters are designed to be fitted with a combustion air inlet duct that obtains outdoor air and a flue pipe that exhausts flue products to outdoors.
The heaters must be installed with an appropriate concentric vertical or horizontal vent terminal. The heaters are only approved for u se when installed with the appropriate approved co ncentric vent terminal (see
table 6.)
Both the flue and combustion air pipes must be sealed. Use seamless aluminum pipe.
The flue pipe may include a re-sealable test port to allow good average sampling of the fl ue gas mixture for testing, the port must be at least 450 mm away from the air heater flue connection socket.
Follow any flue pipe manufacturers installation instructions for making joints, includin g conn ections t o th e air heat er, fo r passing through a building element and for support requirements. If more than one air heater is being installed in the same place each heat er must have a separate flue system.
Table 6 Combustion air inlet & flue pipe requirements
Model RHC 4000(M) DJL
Heater socket & pipe dia mm
Max. straight length m
Equivalent length of 45 ° elbow m
Equivalent length of 90 ° elbow m
Concentric vertical/horizontal vent or wall terminal: types : Mugro or Burfix dia130
Flue pipe 130 Inlet pipe 130
Flue pipe 9 Inlet pipe 9
Flue pipe 0.75 Inlet pipe 0.50
Flue pipe 1.5 inlet pipe 1.5
P 8/24-1307RHC4DJL/RJL--EN
Loading...
+ 16 hidden pages