This unit contains R-410A high pressure refrigerant. Hazards exist that could
result in personal injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-410A refrigerant and
using proper tools and equipment. Due to much higher pressure of R-410A
refrigerant, DO NOT USE service equipment or tools designed for R22
refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service
procedures include the adding or removing of refrigerant, the service technician
must comply with all federal, state and local laws. The procedures discussed
in this manual should only be performed by a qualied HVAC technician.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 1
Page 2
Table of Contents
1.0 General ....................................................2-3
3.9 Other Controls ................................................ 20
3.8 Optional Dampers and Damper Controls ....... 20
1.0 General
This booklet includes operation, maintenance, and service information for Cabinet
Sizes A, B, and C of the MAPS® III and MAPS® IV Models listed below. Before beginning any procedure, carefully review the information, paying particular attention to the
warnings. Handling of refrigerant should only be performed by a certied HVAC technician with knowledge of the requirements of R-410A refrigerant and in compliance with
all codes and requirements of authorities having jurisdiction.
The instructions in this manual apply to the following MAPS® Models in Cabinet A, B,
and C Sizes and Model JHUP 250 and 300 duct furnace curb option.
4.0 Gas Heat Section Maintenance -
RDCB, RDCC, RDDB, RDDC .............21-30
4.1 Heat Exchanger, Burner, and Venter..............21
7.3 Troubleshooting the Heat Section .................34
INDEX .............................................................40
NOTE: To conrm that this
booklet is applicable, see
list of Model and Cabinet
Sizes in Paragraph 2.3,
page 6.
Form O-MAPSIII&IV Cabinets A/B/C, Page 2
MAPS
Model
®
III MAPS®IV
RCBRCC
RDCB RDCC
RECBRECC
RDBRDC
RDDBRDDC
REDBREDC
JHUP
System Description (MAPS®III models have
staged cooling; MAPS®IV models have modulating
cooling.)
Makeup Air Cooling Packaged System, 1500-9000
CFM
Makeup Air Cooling Packaged System, 1500-9000
CFM, with Gas Heat Section (100-700 MBH)
Makeup Air Cooling Packaged System, 1500-9000
CFM, with Electric Heat Section (10- 88 kw)
Makeup Air Cooling and Re-heat Pump Reheat Cycle
Packaged System, 1500-9000 CFM
Makeup Air Cooling and Re-heat Pump Reheat Cycle
Packaged System, 1500-9000 CFM, with a Gas Heat
Section (100-700 MBH)
Makeup Air Cooling and Re-heat Pump Reheat Cycle
Packaged System, 1500-9000 CFM, with Electric Heat
Section (10 - 88 kw)
Optional Curb Section with 250 or 300 MBH Gas-Fired
Duct Furnace installed with a Model RDCB, RDCC,
RDDB or RDDC with a Size 250 or 700 Heat Section to
provide 500 or 1000 MBH heating
Page 3
Denitions of Hazard
Intensity Levels used
in this Manual
There are warning labels on the unit and throughout this manual. For your safety,
comply with all warnings during installation, operation, and service of this system. See
denitions of Hazard Intensity Levels of warnings below.
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal
injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe
personal injury or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal
injury and/or property damage.
2.0 Maintenance
Requirements
To ensure long life and satisfactory performance, a system that is operating under normal conditions should be inspected according to the Maintenance Schedule in Paragraph 2.1. If in an area where an unusual amount of dust or soot or other impurities are
present in the air, more frequent inspection is recommended.
Refer to the illustration in FIGURE 1 and follow the instructions in the referenced paragraphs to maintain this equipment. Maintenance requirements apply to all Models and
Sizes unless noted.
IMPORTANT: Do not release refrigerant to the
atmosphere! If required service procedures include the
adding or removing of refrigerant, the service technician
must comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualied HVAC technician familiar with
R-410A refrigerant.
WARNING
Lock power OFF before performing any maintenance
procedure (except where power is required such as
checking refrigerant pressure and temperature). Lock
disconnect switch in OFF position. If the system has a
gas heat section, when you turn off the power supply,
turn off the gas. See Hazard Levels above.
If replacement parts are required, use only factory-
authorized parts. For information, go to
www.ReznorHVAC.com or call (800)-695-1901.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 3
Page 4
2.0 Maintenance
Requirements
(cont'd)
2.1 Maintenance
Schedule
Important NOTE:
If equipped with an
optional energy recovery
module, refer to Form
I-MAPSIII&IV-ER
for enthalpy wheel
maintenance instructions
Monthly
□Inspect lters; clean or replace as needed. See Paragraph 3.1.
□Inspect the condensate drain; clean as needed. For information, see the
installation manual, Form I-MAPSIII&IV, Paragraph 6.2.
Semi-Annually
□Inspect the unit blower and belts. Check belts for tension, wear, and alignment.
Adjust or replace as needed. Clean dirt from blower and motor. See Paragraph
3.2.
Annually
NOTE: Redo the cooling startup procedures when the cooling season begins. Refer
to Startup instructions in the installation manual, Form I-MAPSIII&IV, Paragraph 10.0.
All Models - Beginning of the cooling season or more frequently
in year-round cooling climate:
□Inspect the wiring for any damaged wire. Replace damaged wiring.
□Inspect the condensate drain pan. Clean the coil cabinet, clean the drain pan,
and ll the trap.
□Inspect/clean condenser fans. See Paragraph 3.3.
□Inspect/clean all coils. See Paragraph 3.4.
□Check compressor operation. See Paragraph 3.6.
□Check refrigerant pressure and temperatures (superheat and subcool). These
checks are done when the system is operating. See Paragraph 3.5.
Models RDCB, RDCC, RDDB, & RDDC with a gas heat section
(beginning of the heating season) - See Paragraph 4.0:
NOTE: A MAPS® B cabinet with 500 MBH of heat is a Size 250 gas heat section
plus an optional Model JHUP curb duct furnace. A MAPS® C cabinet with 1000
MBH of heat is a Size 700 gas heat section plus an optional Model JHUP curb duct
furnace. The same maintenance procedures apply to the duct furnaces.
□Clean all dirt and grease from the combustion air openings and the venter
assembly.
□Check the heat exchanger, burner, and venter for scale, dust, or lint
accumulation. Clean as needed.
□Check the gas valves to ensure that gas ow is being shutoff completely.
Models RECB, RECC, REDB, & REDC with an electric heat section
(beginning of the heating season) - See Paragraph 5.0:
Form O-MAPSIII&IV Cabinets A/B/C, Page 4
□Check wiring connections.
□Check the heat section and elements for dust or lint accumulation. Carefully
clean as needed.
Page 5
2.2 Control Locations
Controller
Display
(BacView)
IQ
Controller
Reheat
Board
Combustion
Air Proving
Switch
(RDCB/RDCC/
RDDB/RDDC)
Air
Proving
Switch
Power Supply
Ignition
Board
(RDCB/RDCC/
RDDB/RDDC)
Relay or
Sequencer
(RDCB/RDCC/
RDDB/RDDC)
Control
Expander
Option BHB6
Dirty Filter
Switch or
Differential
Pressure
Gauge
Low Voltage Panel - Cabinet C
Optional
Control
Block(s)
FIGURE 1 - Showing Access (panels removed) and High and Low Voltage Control Locations
(including control options)
Condenser Section
Compressors
Tubing
Access
Heat Section
(Gas illustrated)
High Voltage Panels
Cabinets A & B
Digital Controller
- MAPS IV only
Control
Transformers
Contactor,
Condenser Fan
Contactor,
Compressor A
Fuse & Fuse
Holder
Contactor,
Compressor B
Contactor, Compressor C
(below “B”, behind the transformer)
Cabinet C
Contactor,
Compressor B
Optional
Transformer
Control
Transformers
Digital Controller
- MAPS IV only
Fuse & Fuse
Holder
Contactor, Compressor DH
Phase Monitor or Motor Saver
Dampers
Blower Section
with Bottom Discharge
Two Low Voltage Panels A&B Cabinets (top right)
or Low Voltage Panel -
C Cabinet (bottom right)
Phase Monitor
or Motor Saver
Distribution
Blocks
Grounding
Lug
Contactor or
Starter and
Overload,
Blower Motor
Contactor,
Compressor DH
Optional Transformer
Contactor, Compressor A
Contactor,
Condenser Fan
Contactor,
Compressor C
Contactor or
Starter and
Overload,
Blower Motor
Distribution
Blocks
Grounding
Lug
Optional Transformer
Slide-out
Filter Rack
Reheat
Compressor
Evaporator Coil
Section (with slide
out drain pan)
Primary Low Voltage Layout - Cabinets A & B
Controller
Display
(BacView)
IQ
Controller
Optional
Plugin Card
Optional
Differential
Pressure
Switch
Combustion
Air Proving
Switch
(RDCB/RDCC/
RDDB/RDDC)
Air Proving
Switch
Venter Motor
Capacitor
(RDCB/RDCC/
RDDB/RDDC)
Secondary Low
Voltage Layout -
Cabinets A & B
Optional
Control
Expander
Optional
Reheat
Board
Sequencer
(RDCB/RDCC/
RDDB/RDDC)
Ignition
Board
(RDCB/RDCC/
RDDB/RDDC)
Optional
Control
Block(s)
Power
Supply
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 5
Page 6
2.0 Maintenance Requirements (cont'd)
2.3 Cross-Reference of Models and Cabinet Sizes A, B, and C
DX Cooling
Models RCB
and RCC and
DX with Reheat
Models RDB
and RDC
Model
Model
RCB
RCC
060
078--
090
118 120
136--
160
186--
200
190
216--
298
410
Model
Model
RDB
RDC
084
102--
114
142 144
162--
184
--196
210--
222--
224--
236
--257
248
262
272--
288--
354
370
468
482
3.0 Maintenance
and Service
Procedures
Cabinet SizeABC
Model Sizes060/078/084/102090/114/11//120/136/142/144/162All Cabinet BAll Cabinet C
Model RECB, REDB, RECC, and REDC by Electric Heat Module
and Cabinet Size
Model
RECB
060
078--
090
118120
136--
160
186--
200
190
216--
298
410
Model
REDB
084
102--
114
142144
162--
184
--196
210-222-224--
236
--257
248
262
272-288--
354
370
468
482
Model
RECC
-10S -15S -20S -24S -15 -20 -25 -30 -35 -39 -50 -60 -75 -88
AAAAA A A A A A-- -- -- --
--AAAA B A A B A B B B --
--AAAA B A A B A B B B B
--AAAA B A A B A B B B B
--AAAA B A A B A B B B B
--------B B B B B B B B B B
--------B B B B B B B B B B
---------- B B B B B B B B B
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
Model
REDC
-10S -15S -20S -24S -15 -20 -25 -30 -35 -39 -50 -60 -75 -88
AAAAA B A A B A B B B--
--AAAA B A A B A B B B B
--AAAA B A A B A B B B B
--AAAA B A A B A B B B B
--------A B A A B A B B B B
--------B B B B B B B B B B
---------- B B B B B B B B B
---------- B B B B B B B B B
---------- B B B B B B B B B
---------- B B B B B B B B B
---------- B B B B B B B B B
---------- B B B B B B B B B
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
---------- ---- -- -- C C C C C
Electric Heat Section
Electric Heat Section
** A MAPS® C Cabinet with 1000 mbh of gas heat is a Size 700 mbh heat section plus an Option JH30 curb with a 300
mbh duct furnace.
3.1 Filters
The lter section is equipped with a slide out lter rack and 2 or 4 inch, pleated disposable or permanent aluminum lters. To remove lters, open the door and slide lters
out. Replacement lters are listed in the table below. Do not use any other type of
lters.
AW21120x25x4 205791
AW24120x25x4 256663
If equipped with permanent aluminum lters, remove the lters, wash, rinse, allow to
dry, and slide them back in the cabinet.
If equipped with pleated disposable lters, replace dirty lters. Exposure to humid
makeup air can accelerate lter degradation. Systems with disposable lters require
more frequent lter inspection.
If equipped with a dirty lter switch or gauge, check the condition of the sensing tubes
to be sure that they are not blocked. Check the wiring connections. To set a new switch
(Option BE18), see Installation Form I-MAPSIII&IV, Paragraph 8.3, Replacement
switch is P/N 105507.
Form O-MAPSIII&IV Cabinets A/B/C, Page 6
Page 7
Filter
Clamp
Filter
Filter
Wing Screw,
P/N 205707,
and Retainer,
P/N 205709
(2 each)
Filter
Filter
Filter Clamps attach
with Wing Screws
P/N 205707
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Filter
16x25x1
Filter
16x25x1
Filter
16x25x1
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Inlet View
Permanent Filters in
the Outside Air Hood
If equipped with an outside air hood, there are 1" permanent, aluminum lters at the
entrance of the hood. The lters act as a moisture eliminator and bird screen. See FIG-URE 2A or 2B. When inspecting the inlet air lters, inspect the outside air hood lters.
If cleaning is needed, remove the lters, clean, rinse, dry and re-install.
NOTE: If it is more convenient to keep an extra clean set of lters, lter sizes and part numbers are shown in the illustration.
FIGURE 2A -
Removing Filters
from Outside
Air Hood
1" Permanent
Aluminum Filters
for Outside Air
Cabinet Sizes A and B with Option AS16
Outside Air Hood
(Does not apply if
system includes
Option PE
power exhaust;
see below.)
All Cabinet Size C with
either Outside Air Hood
Option AS16 or AS19
Hood are listed by
Cabinet Size A, B, or C
(see cross-reference, page 6)
*A - (4) 16 x 20, P/N 101607
*B - (4) 16 x 25, P/N 101609
C - (3) 16 x 25, P/N 101609;
(6) 16 x 20, P/N 101607
* Apply only to Cabinet
Size A and B with outside
air hood Option AS16
.
Instructions: Remove lters by loosening the wing screws and sliding the lter
clamp(s). Clean with soap and water, allow to dry, and replace. If it is more convenient
to keep an extra clean set of lters, quantities, lter sizes, and part numbers are listed.
FIGURE 2B - Removing Filters from Option AS19 Outside Air
Hood Installed on a Cabinet Size A or B with power exhaust
Option PE1 or PE2
Instructions: 1) Remove the four screws as illustrated. Lower the tray.; 2) Pull out
lters. Clean with soap and water. Allow to dry.; 3) Slide clean dry lters into tray.;
4) Re-position tray and replace screws.
1" Aluminum Filters: **A - (4) 18 x 20, P/N 194903; **B - (4) 20 x 25, P/N 101610
** Apply only to Cabinet Size A and B with outside air hood Option AS19.
Filters in an Optional
Energy Recovery
Module
*See cross-reference of
MAPS® Models by Cabinet
Size A, B, or C on page 6.
3.2 Drive
Components
CAUTION: If the
blower is unused
for more than three
months, bearings
with a grease tting
should be purged
with new grease
prior to startup.
If equipped with an energy recovery module (Option ER1A, ER1B, or ER1C), check
both inlet and exhaust lters. Replace as needed.
Cabinet
Size *
APleated 20x25x22104113Pleated 20x25x22104113
B
C
Inlet Air Filters (Merv 8)Exhaust Air Filters (Merv 8)
Bearings - Bearings with a grease tting should be lubricated twice a year with a high
temperature, moisture-resistant grease. (Type NLGI-1 or -2 standard grease is recom-
mended.) Be sure to clean the grease tting before adding grease. Add grease with a
handgun until a slight bead of grease forms at the seal. Be careful not to unseat the
seal by over lubricating. NOTE: If unusual environmental conditions exist (temperatures below 32°F or above 200°F; moisture; or contaminants), more frequent lubrication is required.
Setscrews - Check all of the setscrews (bearing/blower hubs and pulleys). Torque pulley setscrews a minimum of 110 in-lb to 130 in-lb maximum.
A bearing hub setscrew for a 1-3/8" to 1-3/4" shaft requires a 5/16" socket and a tightening torque of 165 in-lbs.
Belts - Check belt for proper tension and wear. If needed, follow instructions to adjust
belt tension. Replace worn belts.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 7
Page 8
2-1/2” (63.5mm)
Fan and Motor Assembly
showing Fan Blade Position
Cross-section of Installed Fan and Motor
Assembly showing Cabinet Top
1.76” (44.7mm)
Top of Fan Blade
to Top of the
Cabinet Top Panel
Fan rotation is
clockwise.
3.0 Maintenance
and Service
Procedures
(cont'd)
3.2 Drive
Components
Cont'd)
Belts (cont'd) - Blower systems are equipped with either Power Twist Plus
blower belt or a solid belt. The linked belts are designed in sections allowing for easy
sizing and adjustment. The belt is sized at the factory for the proper tension. If the belt
needs adjustment, the recommended method of shortening the belt length is to count
the number of links and remove one link for every 24. (A link is made up of two joining
sections of belt. For easier removal of links, turn the belt inside out. But be sure to turn
it back before installing.)
If equipped with a solid belt, adjust the belt tension by turning the adjusting screw on
the motor base until the belt can be depressed 1/2" (13mm) on each side. After correct
tension is achieved, re-tighten the locknut on the adjustment screw.
Proper belt tension is important to the long life of the belt and motor.
Be sure belts are aligned in the pulleys. If a belt is removed or replaced, be sure the
directional arrows on the belt match the drive rotation.
Motor and Blower - Inspect the motor mounts periodically. Remove dust and dirt accu-
mulation from the motor and wheel.
The blower has cast iron, pillowblock, sealed bearings. Under most operating condi-
tions, re-lubrication is unnecessary. If lubrication is required, use a lubricant compatible to Shell Alvania #2 (lithium base - Grade 2). Operating temperature range is -30
to 230°F.
If any drive parts need to be replaced, use only factory-authorized replacements
designed for the application.
®
linked
3.3 Condenser Fans
FIGURE 3 -
Condenser
Fan Assembly
Dimensions
and Rotation
3.4 Coil
Maintenance
Condenser
Coil Cleaning
Instructions:
Form O-MAPSIII&IV Cabinets A/B/C, Page 8
Depending on the size, there are two, three, or four fans in the condenser section. If
parts need to be replaced, use only factory authorized replacement parts. See FIGURE 3 for assembled dimensions and proper fan rotation.
The MAPS® cooling system is equipped with space-saving MACROCHANNEL
Inspect all cooling system coils at the beginning of the cooling season or more often if
needed. Follow the cleaning instructions below. If additional cleaning is required or if a
coil must be removed for any reason, consult the factory. Be prepared to provide rating
plate and specic installation information.
Condensing Coil Access - The condensing coils are visible on the side of the unit
(below the condenser fans). For additional access for inspection and maintenance,
remove the tubing access panel (See FIGURE 1, page 5.).
1. Verify that the electrical power has been turned off and the disconnect switch locked.
2. Use a soft brush to remove any dirt and debris from the coils.
3. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based coil
4. When clean, rinse with cool, clean water.
Evaporator Coil Access - The evaporative coils can be accessed by opening the coil
cabinet door.
Inspect coils for debris, dirt, grease, lint, pollen, mold, or any element which would
obstruct heat transfer or airow. Inspect coils and tubing for physical damage. Inspect
®
coils.
cleaner is recommended). Due to possible damage to the coil, DO NOT use high
pressure spray.
Page 9
feeders, piping connections, coil headers, and return bends for signs of fatigue, rubbing, and physical damage.
Clean the coils annually, or more often if needed. Use the proper tools and follow the
instructions carefully to avoid damaging the coil. Use of a non-acid based coil cleaner is
recommended. Due to possible damage to the coil, DO NOT use high pressure spray.
Evaporator
Coil Cleaning
Instructions:
3.5 Check
Refrigerant
Pressure and
Temperatures
(subcooling
and superheat)
1. Verify that the electrical power has been turned off and the disconnect switch
locked.
2. Open the access panels.
3. Use a soft brush to remove any dirt and debris from both sides of a coil.
4. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based
coil cleaner is recommended). Due to possible damage to the coil, DO NOT use
high pressure spray. First spray the leaving airow side, then the inlet airow side.
As much as possible, spray the solution perpendicular to the face of the coil.
Follow the instructions on the cleaning solution. When cleaning process is
complete, rinse both sides with cool, clean water.
DANGER
These refrigeration circuits are high pressure systems.
Hazards exist that could result in personal injury or death.
Removal, installation, and service of this scroll compressor
must be performed by a technician qualied in R-410A
refrigerant. DO NOT USE service equipment or tools designed
for R22 refrigerant. See Hazard Levels, page 3.
Two important requirements before checking superheat and subcooling:
1) This unit has fully intertwined refrigerant circuits and each circuit MUST be isolated before measuring its
temperature. Another active circuit will inuence the reading and make it impossible to determine accurate superheat
and subcooling.
2) If the circuit is equipped with an optional hot gas bypass valve, the valve must be disabled before measuring
superheat and subcooling. Method of disabling depends on the model and date of manufacture.
All MAPS®IV Models & any MAPS®III Models with a shutoff valve in the line between the compressor discharge and
the hot gas bypass valve - Locate the shutoff valve. Disable the hot gas bypass valve by closing the shutoff valve.
When measurements are complete, be sure to open the valve.
MAPS®III Models without a shutoff valve in the line between the compressor discharge and the hot gas bypass valve
- Disable the hot gas bypass valve by removing the cover and adjusting the spring tension counterclockwise until the
spring tension is relieved. Count and record the number of turns required so that you can return the bypass valve
to its original setting. To check setting, refer to Paragraph 3.9.5.
Check SUBCOOLING
Measure and record temperature and pressure of the liquid line at the condenser coil outlet.
STEP 1) Record Measurements: Temperature = ________°F (°C) and Pressure = ________ psig
STEP 2) From Temperature/Pressure Conversion Chart (page 10), convert Measured Pressure (STEP 1) to
________°F (°C)
STEP 3) Subtract Measured Temperature (STEP 1) from Temperature from Conversion Chart (STEP 2)
Recommended subcooling with outdoor temperature range of 70 to 95°F (21 to 35°C)
is 10 to 12 degrees F (5.6 to 6.7 degrees C).
Too much subcooling indicates a refrigerant overcharge. To reduce the subcooling, remove excess refriger-
ant. Too little subcooling indicates a refrigerant undercharge. To increase subcooling, slowly add R-410A
refrigerant.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 9
Page 10
3.0 Maintenance and Service Procedures (cont'd)
3.5 Check
Refrigerant
Pressure and
Temperatures
(cont'd)
WARNING
Do not release refrigerant to the atmosphere. When adding or
removing refrigerant, the qualied technician must comply
with all national, state/province, and local laws.
Determine SUPERHEAT
Measure and record temperature (insulate probe from surrounding air temperature)
and pressure in the suction line at the compressor inlet.
STEP 1) Record Measurements: Temperature = _______°F (°C) and
Pressure = _______ psig
STEP 2) From Temperature/Pressure Conversion Chart (below), convert
Measured Pressure (STEP 1) to ________°F (°C)
STEP 3) Subtract Measured Temperature (STEP 1) from Temperature from
Conversion Table (STEP 2)
________°F (°C) - ________°F (°C) = ________°F (°C) degrees of
Superheat
Recommended superheat range is 8 to 12 degrees F (4.5 to 6.7
degrees C).
Typically, too much superheat indicates that the evaporator coil is undercharged.
Too little superheat typically indicates that the evaporator coil is overcharged and
may potentially ood liquid refrigerant to the compressor. To reduce the superheat,
adjust the thermal expansion valve by turning the adjusting stem counterclockwise. To increase the superheat, adjust the thermal expansion valve by turning the
adjusting stem clockwise.
The refrigeration circuits are high pressure systems.
Hazards exist that could result in personal injury or death. It
is therefore required that the removal and installation of this
scroll compressor be performed by a technician qualied in
R-410A refrigerant. See Hazard Levels, page 3.
DANGER
Never use oxygen to pressurize a refrigeration system. Oxygen
can explode on contact with oil and could result in personal injury
or death. When using high pressure gas such as nitrogen for
this purpose, ALWAYS USE A PRESSURE REGULATOR that can
control the pressure down to 1 or 2 psig. Failure to use a regulator
will result in extremely high pressure which could exceed the
burst pressure of the compressor or other system components
and result in personal injury or death. See Hazard Levels, page 3.
WARNINGS
For your safety, wear eye protection, gloves, and protective
clothing when handling refrigerant and oil and when brazing.
Have a re extinguisher nearby. See Hazard Levels, page 3.
Compressor Staging
(Cooling) - applies to
all MAPS®III Models
Each MAPS®III system leaves the factory with the compressor staging sequence
shown here for that Model and Size. The compressor will start based upon a call for
cooling to maintain the discharge air temperature setpoint. There is a minimum 240
second ON and OFF time for each stage (not compressor).
FIGURE 4 - Identication of
Compressors by Circuit and
Staging for MAPS®III Models
MAPS®IV units are equipped with a modulating capacity compressor and a digital con-
troller to provide cooling modulation. The digital controller in the control compartment
(See FIGURE 1, page 5) is the electronic interface between the compressor and the
NOTE: To identify MAPS®IV
Models, see Paragraph 1.0.
system controller. The compressor controller is connected to the unit controller to provide protection and diagnostics for modulating compressor operation.
After a compressor shutdown, a two-minute anti-short cycle timer in the compressor
controller delays the compressor restart. The unit controller has a ve-minute compressor on/off time. The delay times are concurrent so total delay time is ve minutes.
FIGURE 5 - Compressor Digital Controller
located in the control compartment
interfaces the modulating capacity
compressor with the unit controller.
LED
Color
Green Solid
Green Flashing Anti-short cycle timer is active
Yellow Solid
RedNot litNo abnormal operation alerts
NOTE: See Troubleshooting, Paragraph 7.2.
LED
State
Indicates
Power (24VAC present at power
terminals)
Unloader (Solenoid valve is
energized; compressor capacity is 0.)
Compressor and Crankcase Heater P/N's by Voltage on MAPS®IV Models
For your safety, wear eye protection, gloves, and protective clothing
when handling refrigerant and oil and when brazing. Have a re
extinguisher nearby. See Hazard Levels, page 2.
Compressor
Handling
Do not lift compressor by copper tubing. To prevent internal damage, compressors
must ALWAYS be held upright.
The following instructions include major points of consideration that will ensure proper
installation and protect you from potential personal injury. Please use the following 13
steps as a checklist, taking each item in order before proceeding to the next. If more
information is required, contact the Reznor HVAC Service Department for Reznor
products.
®
WARNING
To avoid electrical shock, power to the compressor(s) MUST REMAIN
OFF during performance of Steps 1 through 9 below. LOCK DISCONNECT
SWITCH OFF (open).
□ Step 1. Verify Proper Application
Verify that the replacement compressor is identical to the model being replaced.
All system components are matched to the compressor. Replacing a compressor
with a model other than the Reznor® specied replacement will void the product
warranty. See part numbers for R-410A compressors in the tables on page 12.
□ Step 2. Determine Cause of Initial Failure and Remove the Compressor
In order to prevent a second failure, the cause of the original failure must be
determined. Identify the cause and make the necessary repairs.
CAUTION: DO NOT LIFT compressor by copper tubing; damage will
occur. Compressor must remain upright.
WARNING
Wear eye protection and gloves when handling refrigerant or oil and
when brazing.
a) BEFORE REMOVING THE FAULTY COMPRESSOR, remove refrigerant
charge using proper recovery procedures. Call 1-800-441-9450 for the name
of the nearest Dupont authorized distributor or 1-800-ASK-KLEA (IGI) for
information on their refrigerant reclaim programs.
b) Disconnect wires. All compressor wiring is connected using a black molded
plastic plug. Remove the plug from the compressor.
c) Open access ports so that pressure does not build up in the system. Before
unbrazing stubs from the compressor, cut suction and discharge tubing with a
tubing cutter.
WARNING
Have a re extinguisher near. The compressor contains oil. There is a
risk of re when unbrazing stubs.
Use a high temperature torch to disconnect the suction line and the discharge line from
the compressor.
d) Remove the mounting bolts and the compressor. Save the mounting hardware
to attach the grommets and sleeves shipped with the replacement compressor.
e) To test for acid and to assure excess oil does not remain in the circuit, remove
oil from the failed compressor. Measure the amount of oil.
CAUTION: In addition to the required eye protection and gloves, care
should be taken in handling POE oil because it may cause damage to
certain plastics and roong materials. See Hazard Levels, page 3.
If the oil taken from the compressor and measured is found to be signicantly
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 13
Page 14
3.0 Maintenance/
Service
Procedures
(cont'd)
3.6 Compressor
Maintenance
(cont'd)
lower than listed in the table on page 14, clean the excess oil through use
of suction and liquid line lter driers. Beginning in Step 4, follow the same
procedure as for burnout cleanup.
Use an acid test kit to check the oil for acid. If acid is found, beginning in Step
Compressor Oil Charge (POE Oil)
Compressor Model ccoz
ZP24K5E62121
ZP36K5E112438
ZP54KCE124242
ZP57K3E171558
ZP61KCE153852
ZPD61KCE177460
ZP72KCE177460
ZP83KCE165656
ZPD83KCE165656
ZP137KCE3253110
ZPD137KCE3135106
ZPT144KCE3312112
ZP154KCE3253110
ZPDT14MCE3135106
4, follow procedures indicated for burnout cleanup.
Dispose of oil and compressor using an approved environmentally safe
disposal method.
Important NOTES: These R-410A
compressors use a polyolester (POE)
lubricant. Types of recommended POE
oil are Copeland Ultra 22 CC, Copeland Ultra
32 CC, Copeland Ultra 32-3MAF, Mobil EAL,
Arctic 22 CC, Uniqema Emkarate RL32CF, or
Uniqema RL32-3MAF.
POE oil absorbs moisture much quicker
and to a greater degree than standard
mineral oil. The compressor must not
be left open longer than 15 minutes
during replacement. During installation
the system must be swept with an
inert gas such as dry nitrogen to keep
moisture from entering the compressor
and prevent the formation of oxides.
• Step 3. Mount the Replacement Compressor
• Step 4. Install New Filter Driers (Select procedure that applies.)
Form O-MAPSIII&IV Cabinets A/B/C, Page 14
Do not remove the dust cover or rubber shipping plugs until all other system
connections are complete (i.e. new liquid line lter drier(s) installed and all tubing
changes made - see Steps 4 and 5). The amount of time the compressor is open
to the atmosphere must be kept to a minimum.
Use the new mounting grommets and sleeves that are shipped with the
compressor to mount it. The sleeves will prevent over compression of the
grommets. Re-use the mounting bolts from the compressor that was removed. The
mounting bolts will bottom out when tight.
IF the oil measured in Step 2 was not signicantly less than the amount shown in
the table above or the test for acid in Step 2did NOT indicate burnout , install
a new R-410A refrigerant liquid line lter drier. The lter drier must be rated for
no less than 600 psig and be the proper size for the circuit. Because R-410A
refrigerant requires POE oil which absorbs moisture quickly, it is important to
change the lter drier any time the circuit is opened.
It is recommended to use a tubing cutter when cutting out a lter drier as the
desiccant absorbs and holds moisture better when it is cool. Heat from a torch
may cause moisture to leave the lter and be absorbed in the oil. Be careful to
keep dirt, lings, and other contaminants out of the system.
Continue to Step 5.
IF the oil measured in Step 2 was signicantly less than shown in the table above
or the test for acid in Step 2 did indicate compressor burnout, do the following:
a) Install a liquid line lter drier. If there is acid, install an acid removing lter
drier. Size the acid-removing lter drier at least one capacity size larger than
normally required for the circuit.
b) Install a temporary lter drier in the suction line. When there is acid, a 100%
activated alumina suction lter drier is recommended. The suction line drier
should be sized properly for the circuit and have a service access tting to
monitor pressure drop across the drier. (NOTE: Suction line lter drier must be
removed after 72 hours of operation.)
Page 15
Step 12 includes the remaining procedures required for cleanup of a burnout.
Continue to Step 5.
• Step 5. Braze on Suction and Discharge Lines
CAUTION: Do not leave system open to the atmosphere any longer
than minimum required for installation. POE oil in the compressors
is extremely susceptible to moisture absorption. Always keep ends
of tubing sealed during installation. See Hazard Levels, page 3.
Brazing materials must be able to withstand the high pressure of R-410A
refrigerant. A high temperature, silver phosphate type brazing with 5% or greater
alloy is recommended.
To prevent oxidation, purge tubing with 2-3 psig of regulated dry nitrogen while it
is being brazed. Open the service valve as needed to release the nitrogen. Do not
allow moisture to enter the system.
The installer is responsible for brazing and for complying with appropriate standard
refrigerant piping procedures.
CAUTION: All brazing should be done using a 2-3 psig dry nitrogen
purge owing through the pipe being brazed.
CAUTION: When brazing, protect all painted surfaces and
components from excessive heat. Wet wrap all valves but do not
allow moisture to enter the tubing. See Hazard Levels, page 3.
• Step 6. Check System for Leaks
After installation is complete, pressurize the circuit with helium or dry nitrogen to
approximately 150 psi (maximum pressure is 450 psi). Check for leaks using soap
bubbles or other leak-detecting methods.
• Step 7. Evacuate the Circuit
Evacuate one circuit at a time. Use a vacuum pump and micron gauge. Each
circuit must be evacuated to hold a 500 micron vacuum. Vacuum must be pulled
on both the discharge (high) and suction (low) side. Do the suction side rst; and
the compressor discharge side second. To establish that a circuit is leak-free
and moisture-free, a standing vacuum test is recommended. Close off the valve
to the vacuum pump and observe the micron gauge. If the vacuum gauge does
not rise above 500 microns in one minute, the evacuation should be complete.
If the vacuum gauge does rise above 500 microns in one minute, evacuation
is incomplete or the circuit has a leak. Repeat as needed until evacuation is
complete. The evacuation process must be done on each circuit.
NOTE: Evacuation will not remove moisture from POE oil. Moisture must be
prevented from getting in the oil.
Continue and/or repeat Steps 6 and 7 until evacuation is complete.
CAUTION: Do not use the replacement compressor as an
evacuation assist and never apply voltage to a compressor while
it is in a vacuum. See Hazard Levels, page 3.
Moisture and air are harmful to the system because they increase the condensing
temperature, raise the discharge gas temperature, cause formation of acids, and
cause oil breakdown.
CAUTION: Do not leave a circuit open to the atmosphere any longer
than minimum required for installation. POE oil in the compressor
is extremely susceptible to moisture absorption. Evacuation will
not remove moisture from POE oil.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 15
Page 16
Compressor B
Compressor C
Compressor A
Compressor
Dh (Reheat)
3.0 Maintenance/
Service
Procedures
(cont'd)
3.6 Compressor
Maintenance
(cont'd)
CAUTION:
Crankcase heaters
must be allowed
to warm up for
at least 24 hours
prior to startup.
Disable cooling
controls before
turning on power
to warm up
crankcase heaters.
• Step 8. Check the Electrical System
After the system has been evacuated, reconnect the electrical plug to the
compressor or the wires to the compressor terminals. It is a normal practice to
replace all starting components any time a compressor is changed.
WARNING
Do not apply voltage to the compressor when the plug is
removed or terminals disconnected.
Crankcase Heater - Connect the crankcase heater. The crankcase heater is
energized continuously and is extremely important to proper compressor operation
and long life. NOTE: See crankcase heater P/N's on page 12.
The crankcase heater must be energized for at least 24 hours before starting
the unit or after a power outage of more than 8 hours. Be sure to disable cooling
controls before turning on power to warm up crankcase heaters.
• Step 9. Charge the System (Use R-410A refrigerant only.)
Refer to the applicable table (either MAPS®III or MAPS®IV) for the approximate
amount of refrigerant required. Follow the instructions below to charge the circuit.
R-410A refrigerant MUST BE charged as a LIQUID.
NOTE: Outdoor temperature must be between 70-95°F (21-35°C) for verifying
superheat and subcooling. If temperature is not within this range, consult the
factory service department before charging.
If equipped with an optional hot gas bypass, disable the hot gas bypass valve
before charging. Method of disabling depends on the model and date of
manufacture.
All MAPS®IV Models & any MAPS®III Models with a shutoff valve in the line
between the compressor discharge and the hot gas bypass valve - Locate the
shutoff valve. Disable the hot gas bypass valve by closing the shutoff valve.
When measurements are complete, be sure to open the valve.
MAPS®III Models without a shutoff valve in the line between the compressor
discharge and the hot gas bypass valve - Disable the hot gas bypass valve by
removing the cover and adjusting the spring tension counterclockwise until the
spring tension is relieved. Count and record the number of turns required so
that you can return the bypass valve to its original setting. To check setting, refer
to Paragraph 3.9.5.
Liquid charge the high side to 80%. With the system running, add the balance of
the charge to the correct superheat and subcooling values. Refer to Step 11, page
17, and the instructions in Paragraph 3.5, page 9.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service
procedures include the adding or removing of refrigerant, the qualied HVAC service
technician must comply with all federal, state or provincial, and local laws.
Approximate R410-A Refrigerant Charge
(lbs) for MAPS®IV Models by Size and
Compressor for Each Circuit
Form O-MAPSIII&IV Cabinets A/B/C, Page 16
Cabinet
A060084N/A8.0N/A4.2
A or B
B
C
RCC/
RDCC/
RECC
090114N/A10.5N/A4.2
1201448.08.0N/A4.2
160
200
190
298
410
RDC/
RDDC/
REDC
R410-A Charge (lbs) by Compressor Circuit
ABC
184
1964.2
236
2576.0
248
26210.0
354
37010.0
468
48210.0
9.59.5N/A
5.56.05.5
9.010.5N/A
11.011.0
10.510.510.5
DH
(Reheat)
4.2
6.0
10.0
10.0
10.0
Page 17
Approximate R410-A Refrigerant
Compressor B
Compressor C
Compressor A
Compressor
Dh (Reheat)
Charge (lbs) for MAPS
®
III Models
by Size and Compressor for Each
Circuit
• Step 10. System Startup
Assure voltage to compressor does not drop below minimum allowable voltage
(e.g. 187 volts for 230/208-3-60, 415 volts for 460/3/60, 518 volts for 575/3/60)
during the period the compressor is trying to start. If a low voltage or voltage
imbalance condition exists, the electrical problem must be determined and
corrected prior to operating the unit.
Voltage Imbalance - Voltage imbalance is becoming a more common problem.
In a 3-phase system, excessive voltage imbalance between phases will cause
motors to overheat and compressors to fail. Maximum allowable imbalance is
2%. To determine voltage imbalance, measure and record the voltage of all three
phases. Take the measurements at the compressor terminals with the compressor
operating.
Voltage Imbalance Formula:
Key:
Formula:
If the imbalance is within the 2% tolerance, voltage imbalance is not a problem and
the system may be operated. If the imbalance exceeds the 2% tolerance, follow
the procedures below.
Solutions to Voltage Imbalance:
The cause for a voltage imbalance problem can originate at the power company or
can be caused inside the building. Try the following on-site solution to determine if
the problem can be easily resolved.
Roll the connections at the compressor terminals one forward. Connect the wire
now on Terminal 1 to Terminal 2, 2 to 3, and 3 to 1. Re-measure and re-calculate
the voltage imbalance. If the imbalance is within 2%, the system may be operated.
If the imbalance is not within tolerance, roll the connections one more forward.
Re-measure and re-calculate the voltage imbalance. If the imbalance is within
2%, the system may be operated. If the voltage imbalance still exceeds 2%, do
not start the system. Contact the building owner or person responsible to have an
electrician analyze the buildings's power supply and load distribution.
Power Supply Voltage Phasing - Connect refrigerant pressure gauges to the
suction and discharge lines of the compressors and an electric meter to the power
supply.
VD = Line Voltage (V1, V2, or V3 that deviates farthest from average (VA)
% of Voltage Imbalance = [100 (VA - VD)] / VA
CAUTION: Be sure to connect pressure gauges to the suction and discharge lines before
system startup so that compressor rotation can be checked immediately. Scroll compressors
will be destroyed if allowed to operate in the wrong direction. See Hazard Levels, page 3.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 17
Page 18
3.0 Maintenance/
Service
Procedures
(cont'd)
3.6 Compressor
Maintenance
(cont'd)
• Step 10. System
Startup (cont'd)
NOTE: To identify MAPS
and MAPS®IV Models, see
Paragraph 1.0.
IMPORTANT: Do not
release refrigerant
to the atmosphere!
If required service
procedures
include the adding
or removing of
refrigerant, the
qualied HVAC
service technician
must comply with
all federal, state or
provincial, and local
laws.
®
Record the ambient temperature. Adjust the system controller so that a call for
cooling exists.
NOTE: Outdoor ambient lockouts may prevent mechanical cooling. Temporarily
override lockouts by lowering the cooling setpoint. When testing is complete, reset
the controller.
Because it is possible to unknowingly connect 3-phase power in such a way
as to cause the scroll compressor or blower to rotate in reverse, it is very
important to check this on startup.
Check Compressors - Immediately at startup, observe the gauges. If the
suction pressure rises and discharge pressure drops, the compressor is
operating in reverse and must be shut down. Turn off the power and switch
the 3-phase line voltage wiring connections before restarting the unit.
Important: If allowed to operate for several minutes in reverse, the compressor’s
internal protector will trip. If a compressor is repeatedly allowed to restart and run
in reverse, the compressor will be permanently damaged.
• Step 11. Check Subcooling and Superheat
Superheat is the verication that the evaporator coil is properly using the
refrigerant supplied. Too much superheat indicates that the coil is undercharged.
Too little superheat indicates that the coil is overcharged and potentially ooding
liquid refrigerant to the compressor.
Subcooling is the measurement of liquid refrigerant stored in the condenser
coil. Too much subcooling indicates a system overcharge. Too little subcooling
indicates a system undercharge and may not provide the thermal expansion valve
with a full column of liquid refrigerant for proper operation.
Two important requirements before checking superheat and subcooling:
1) This unit has fully intertwined refrigerant circuits and each circuit MUST be
isolated before measuring its temperature. Another active circuit will inuence the
reading and make it impossible to determine accurate superheat and subcooling.
2) If the circuit is equipped with an optional hot gas bypass valve, the valve must
be disabled before measuring superheat and subcooling. Method of disabling
depends on the model and date of manufacture.
III
All MAPS®IV Models & any MAPS®III Models with a shutoff valve in the line
between the compressor discharge and the hot gas bypass valve - Locate the
shutoff valve. Disable the hot gas bypass valve by closing the shutoff valve. When
measurements are complete, be sure to open the valve.
MAPS®III Models without a shutoff valve in the line between the compressor
discharge and the hot gas bypass valve - Disable the hot gas bypass valve by
removing the cover and adjusting the spring tension counterclockwise until the
spring tension is relieved. Count and record the number of turns required so
that you can return the bypass valve to its original setting. To check setting, refer
to Paragraph 3.9.5.
Follow the procedures in Paragraph 3.5 to check subcooling and superheat.
• Step 12. (Select the procedure that applies.)
IF the oil measured in Step 2 was signicantly less than in the table on
page 14 or the acid test in Step 2 indicated a burnout, do the following:
a) Operate the unit for several hours. Check the pressure drop through the
temporary suction line lter drier. If the pressure drop exceeds 8 psig, recover
the refrigerant, replace the suction line lter drier with the same type as
removed, replace the liquid line lter drier, evacuate the circuit, and re-charge
with the recovered refrigerant.
Continue to monitor the pressure drop through the suction line lter drier and
repeat the process above until the pressure does not exceed 8 psig after
several hours of operation. (NOTE: System must be allowed to run no more
than 72 hours with a suction line lter drier.)
b) Allow the system to operate for 4-8 hours. Recover the refrigerant and take an
oil sample. Retest the oil for acid.
Form O-MAPSIII&IV Cabinets A/B/C, Page 18
Page 19
c) If the test for acid is negative, remove the suction line lter drier, replace
Compressor B
Compressor C
Compressor A
Compressor
Dh (Reheat)
the liquid line drier, evacuate, and re-charge the system with the recovered
refrigerant.
If the test indicates acid, replace both the liquid line lter drier and the suction
line lter drier and repeat b) and c).
CAUTION: After cleanup is complete, remove the suction line lter
drier. See Hazard Levels, page 3.
d) Verify subcooling and superheat (refer to Step 11).
e) When the system is operating properly, remove the gauges.
Or, IF the oil measured in Step 2 was not signicantly less than that
shown in the table on page 14 or the acid test in Step 2 did not indicate
a compressor burnout, continue to the review in Step 13.
• Step 13 . Review ALL Steps to ensure that nothing was overlooked.
3.7 Thermostatic
Expansion
Valves
All refrigeration circuits have a thermostatic expansion valve. Thermostatic expansion
valves do not have replaceable parts. If a replacement valve is required, it must be
for R410-A refrigerant and must be sized correctly for the application. All refrigerant
service should be performed by a service technician qualied in R410-A refrigerant.
Replacement valve P/N's by Model, size, and circuit are listed in the following tables.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 19
Thermostatic Expansion Valve P/N's by
Compressor Circuit
ABCDH (Reheat)
220554220555220554
220554220555220555
234987220558N/A
220558220555
220558220558
220558220558220558
Thermostatic Expansion Valve P/N's
by Compressor Circuit
ABCDH (Reheat)
220555220555N/A
220554220556220554
234967261175N/A
261175261175
261175261175261175
220552
220552
234987
234987
234987
234987
234987
234987
234987
234987
220552
220553
234987
234987
234987
Page 20
3.0 Maintenance/
Service
Procedures
(cont'd)
FIGURE 7 - Damper
Motor
3.8 Optional Dampers and Damper Controls
Inlet Air Dampers
Location: Dampers and damper motors are located in the inlet air opening.
Function: Dampers operate in response to a variety of controls (GF Options).
Service: Clean dampers and controls of dust and dirt.
2-Position Damper Motor (Options AR8, AR2D, AR2L)
Function: The 2-position damper motor opens and closes the dampers in response to
unit operation or a eld-supplied time clock. The motor closes the dampers on heater
shutdown.
Modulating Motor (Options AR25, AR2G, AR2H, AR2K)
Function: The modulating damper motor actuates the dampers in response to the
selected control with actuation from input switch settings.
The motor closes the inlet dampers on heater shutdown.
Service: Other than external cleaning, there is no service required on the dampers or
the damper motor. If the damper, control, or motor need to be replaced, replace with a
factory-authorized replacement.
For additional information on damper controls (Options GF 1-9), see the system installation manual Form I-MAPSIII&IV.
3.9 Other Controls
FIGURE 8 - I/Q
System Programmable Controller
and Unit Module
Interface with Display
Refer to Control
Instruction Form
CP-MAPS D15/16/17/18
for information on the
programmable controller.
3.9.2 Air Proving
Switch
3.9.1 Programmable Digital Controller and Sensors
All MAPS® systems have a unit-mounted,
BACview
Display
I/Q System
Controller
Some sensors are standard and others will depend on option selection.
Service: If a sensor needs to be replaced, use only a factory authorized replacement
part designed for the purpose. Refer to the digital wiring requirements in Paragraph 7.4
of Installation Form I-MAPSIII&IV.
If a controller needs to be replaced, it must be replaced with the same controller and
software.
Function: The airow proving switch is a pressure switch that veries
to the main controller that the blower is operating.
Service: If the switch needs to be replaced, use a factory-authorized
replacement designed for the application.
24-volt I/Q programmable controller.
Depending on how it was ordered, the
system is equipped for either neutral air/
discharge air control (Option D15) or
space control with discharge air reset
(Option D16). In addition, MAPS®IV electric heat Model RECC for process applications may have neutral air/discharge
air control (Option D17) or space control
with discharge air reset (Option D18). The
controller is factory programmed to match
the selection. See the control instruction
manual, Form CP-MAPS D15/16/17/18, for
more details.
3.9.3 Motor Starter
(Option AN10) or
Variable Frequency
Drive (Option VFD2)
Form O-MAPSIII&IV Cabinets A/B/C, Page 20
Function: When the main controller calls for blower operation, either an IEC type
starter with a contactor or a variable frequency drive (VFD) module responds to operate the motor.
The starter is in the high voltage control compartment. The VFD was eld installed in
a location that is no more than 50 feet (15M) away where the minimum temperature
is 18°F (-9°C). Control of the variable frequency drive module is coordinated with the
main controller, and depending on what was ordered, can function in response to temperature, CO2, or pressure controls.
Service: If a starter or contactor need replaced, use only the identical replacements
that are designed to match the motor and voltage of the system.
Page 21
If a VFD needs to be replaced, contact the factory service department. Be prepared to
provide the model, serial, and wiring diagram number.
Function: Phase loss and low or high voltage can cause damage to electrical com-
ponents. This safety control monitors phase loss and voltage and shuts down the unit
when its limits are exceeded. The device is auto reset and allows the unit to restart
when the power conditions are corrected.
Function: The hot gas bypass valve allows some of the refrigerant gas from the suction line to be re-routed directly to the evaporator coil providing for expanded compressor modulation at low outside air temperatures.
Service: To check the hot gas bypass valve setting, connect a pressure gauge to the
suction line and block the entering air to the evaporator coil. Suction pressure will drop,
and the hot gas bypass valve should begin to open at a approximately 115 psi and will
be fully open at 95 psi. When the valve begins to open it will be hot to the touch (see
caution below).
CAUTION: Touching the operating hot gas bypass valve can cause
a burn. Use caution when checking and adjusting the valve. See
Hazard Levels, page 3.
If a hot gas bypass valve needs to be replaced, use only a factory-authorized replace-
ment for R410-A refrigerant. All refrigerant service should be done by a qualied R410-A
service technician.
Function: Units with modulating reheat control (Option AUR1) have a temperature
control board with a potentiometer, an air temperature sensor, and an electric discharge bypass valve. When reheat is active, the sensor monitors the air temperature
as it leaves the reheat coil. Based on the potentiometer setpoint, the board will open
or close the bypass valve. If the leaving air temperature is higher than the setpoint, the
board will open the valve adding refrigerant hot gas to the refrigerant liquid before it
enters the pre-cool coil. This reduces the coil's ability to absorb the heat, and thus, the
reheat coil's ability to reject. If the leaving air temperature is lower than the setpoint,
the opposite occurs.
Service: Check the wiring connections at the board. The board is polarity sensitive;
positive connects to terminal 1 and negative to terminal 2.
The valve may be tested by measuring the resistance of the leads. Remove the power
and the leads from the board before testing. Resistance between the black and white
leads should be about 75 Ohms. Resistance between the green and red leads should
be within 5% of the white and black.
Use only factory-authorized replacement parts.
4.0 Gas Heat
Section
Maintenance Models RDCB,
RDCC, RDDB,
and RDDC
This gas heater will operate with a minimum of maintenance. To ensure long life and
satisfactory performance, a heater that is operated under normal conditions should be
inspected and cleaned at the start of each heating season. If the heater is operating in
an area where an unusual amount of dust or soot or other impurities are present in the
air, more frequent maintenance is recommended.
When any service is completed, be careful to reassemble correctly to ensure that no
unsafe conditions are created. When re-lighting, always follow the lighting instructions
on the furnace.
WARNING
Turn off the power before performing maintenance procedures. Lock disconnect switch in
OFF position. When you turn off the power supply, turn off the gas at the external manual
valve. See Hazard Levels, page 2.
2
4.1 Heat Exchanger,
Burner,
and Venter
This gas heat section is equipped with a
Inspect the gas heat section annually to determine if cleaning is necessary. If there is
an accumulation of dirt, dust, and/or lint, clean the compartment.
TCORE
®
style heat exchanger and burner.
Maintenance
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 21
Page 22
Venter Motor
and Wheel
Assembly
Venter Side Supports
Venter
Housing
and Support
Flue Collection
Box Assembly
Venter Support
Venter
Housing
Venter
Housing
Gasket
Motor and
Wheel Assy
OR, depending on the Cabinet size
and date of manufacture, venter
components may look more like
the one shown below.
4.0 Gas Heat Section Maintenance - RDCB, RDDC, RDDB and RDDC (cont'd)
4.1 Heat Exchanger, Burner, and Venter Maintenance (cont'd)
4.1.1 Instructions for
Inspecting/Cleaning
the Heat Exchanger
and Burner
CAUTION: Use of
eye protection is
recommended.
NOTE: If the installation includes a Model JHUP
curb duct furnace, the
inspection and cleaning
procedures described in
Paragraph 4.1 also apply
to the duct furnace. For
illustration of a curb duct
furnace, see the installation
manual, Form I-MAPSIII&IV
Cabinet, Paragraph 5.4.3,
Heat Exchanger Maintenance -
The outside of the heat exchanger is
accessible by opening the blower section door and sliding the blower out of the
unit. Remove any external dirt or dust accumulation. Visually check the heat
exchanger for cracks or holes. If a crack or hole is observed, replace the heat
exchanger.
NOTE: Inspection of the lower portion of the heat exchanger is done with the burner
removed. See the Burner Service section below for information on inspecting the lower
portion of the heat exchanger.
2
Burner Maintenance - This furnace is equipped with a TCORE
®
style
burner.
Inspect the gas heat section annually to determine if cleaning is necessary. If there is
an accumulation of dirt, dust, and/or lint, clean the compartment and follow the instructions below to remove and clean the burner.
CAUTION: Use of eye protection is recommended.
Burner Removal Instructions (Refer to FIGURES 10 and 11.)
1. Shut off the gas supply.
2. Turn off electric supply.
3. Remove the gas heat section access panel.
4. Remove the venter assembly. Disconnect the tubing. Mark and discon-
nect the three venter motor wires at the control board, capacitor wires at the
capacitor (if applicable), and ground screw (located on the control panel).
The venter motor and wheel assembly only can be removed. To remove the entire
venter, also remove the side supports and venter housing.
5. Disconnect the Gas Train - At the gas valves, mark and disconnect the wires. Discon-
nect the gas supply line at the connection outside the furnace. Carefully remove the
burner orices and orice adapter locking nuts. Remove the manifold brackets. Slide
the complete gas train including valves and optional pressure switches out of the unit.
6. Remove Burner Assembly - Remove the screws above and below the burner as-
sembly. Carefully pull the burner assembly out of the cabinet.
Appearance will vary by Cabinet and size.
Maintenance requirements apply to all heat
sections including an optional curb duct furnace
(JHUP 250 or 300).
Inspect and
Clean the Burner
NOTE: If any of the
burner components
are damaged or
deteriorated, replace
the burner assembly.
Inspect the Lower
Portion of the Heat
Exchanger (with
burner assembly
removed)
Burner Orice
Check the Ignitor and
Flame Sensor
CAUTION: Due
to high voltage
on the spark wire
and electrode, do
not touch when
energized. See
Hazard Levels,
page 3.
With the burner assembly removed, shine a ashlight on the burner ribbons. Look for
carbon buildup, scale, dust, lint, and/or anything that might restrict ow through the
spaces between the burner ribbons. Holding the burner assembly so that any foreign
material will fall away from the burner, use a stiff bristle brush to loosen and remove
any foreign material(s). If the burner is excessively dirty, remove both of the burner end
caps. Remove the screws that hold the end caps to the burner housing and lightly tap
end caps to remove.
Clean all foreign material from the burner and venturi. After the burner is thoroughly
cleaned, replace the end caps making certain that they are tight against the burner
housing.
At the burner ame entrance of each tube, shine a bright light into each heat exchanger
section. With the light shining into the heat exchanger, observe the outside for visible
light. Repeat this procedure with each heat exchanger section. If any light is observed,
replace the heat exchanger.
The burner orice usually will not need to be replaced. If ordering a replacement orice
only, give BTUH content and specic gravity of gas, as well as the model and serial
number of the unit and the orice size. When removing or replacing the burner orice
be careful not to damage the venturi tube and/or the bracket.
Ignitor - Locate the ignitor. Disconnect the wire; remove the
screw and the ignitor. Clean the ignitor assembly with an
emery cloth.
Spark gap must be maintained to 1/8". See FIGURE 12.
IMPORTANT: When re-assembling, the brown ground wire
must remain attached to the ignitor.
Flame Sensor - Locate the ame sensor on the burner. Disconnect the wires; remove the screws and the ame sensor.
Clean with an emery cloth.
Ignitor
Flame Sensor
FIGURE 12 - Ignitor
showing required Spark
Gap Measurement
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 23
Page 24
1/2” (13mm) from motor
plate to wheel
NOTE: Measure from
plate and not the gasket.
Venter
Motor
Motor Plate
with Gasket
Venter Wheel
4.0 Gas Heat
Section
Maintenance
(cont'd)
4.1 Heat Exchanger,
Burner,
and Venter
Maintenance
(cont'd)
FIGURE 13 - Venter
Wheel Position on
the Shaft
4.1.2 Maintenance Instructions for the Venter Motor and Wheel
Follow the instructions below to remove the venter assembly. Keep all hardware
removed to be used in re-assembling and installing the replacement parts.
Note that during normal operation of this deep modulation control system, the current draw of the venter motor can exceed the full load amp rating on its nameplate.
This condition is common when employing electronic wave-chopping technology to
reduce the running speed of a single-phase type PSC alternating current motor. The
technology reduces energy to the main winding by momentarily interrupting current for
a variable amount of time, resulting in a reduction of the motor speed. The increased
current is a result of increased slip, which is the difference between the rotation speeds
of the rotor and stator elds. All motors used in MAPS
and built for this unique modulating application and cannot be replaced with a nonapproved motor. All prototype motors have been thoroughly tested with regards to temperature of the windings and bearings at all operating points and ambient conditions
and approved by the manufacturer to assure the elevated current does not affect the
normal motor life expectancy.
®
systems are custom designed
Instructions:
1. Turn off the gas and disconnect the electric power.
2. Open the gas heat section access panel and the electrical compartment.
3. Disconnect the three venter motor wires at the control board, capacitor wires at the
capacitor (if applicable), and ground screw (located on the control panel).
4. Holding the venter motor, remove the three or four screws that attach the venter
motor and wheel assembly. Remove the motor and wheel assembly.
5. Re-assemble with the replacement venter motor and wheel assembly. See
FIGURE 13, for proper spacing.
6. Follow the wiring diagram to re-connect the venter wires.
7. Close the access panels. Restore power to the gas heater and turn on the gas.
Check for proper operation.
NOTE: Manufacturer
recommends replacing
venter motor capacitor
when replacing venter
motor. Use only factoryauthorized replacement
parts.
4.1.3 Re-Assemble
the Heat Exchanger
Panel, Burner, Gas
Train, and Venter
Form O-MAPSIII&IV Cabinets A/B/C, Page 24
If replacing venter parts, see FIGURE 3 for proper spacing. If the motor plate gasket
is damaged or deteriorated, replace it with P/N 222856.
Remove dirt and grease from the venter housing, the motor casing, and the venter
wheel. Venter motor bearings are permanently lubricated.
Instructions to Re-Assemble the Gas Heat Section (Refer back to
FIGURES 10 and 11.)
1. Re-attach the Burner Assembly - Slide the entire burner assembly into position.
Insert all of the screws along the top and the bottom.
2. Re-attach the Gas Train - Position the gas train so that the orice adapter(s) are
through the brackets. Attach the manifold to the manifold brackets. Install the
orice adapter nuts and the gas orice(s) being careful not to damage the venturi
tubes and/or the brackets. Re-connect the wires to the gas valve.
3. Re-attach the venter assembly. (If replacing venter parts, follow the instructions
above.) Re-connect the tubing and the wires.
4. Close the access panel.
5. Reconnect the gas supply at the union outside of the cabinet. Leak test the
connection with leak detecting solution. Turn on the electric. Turn on the gas.
Check for proper operation.
Page 25
4.2 Heat Section
Controls
4.2.1 General
The heat section controls are in the low voltage compartment. See FIGURE 1, page 5.
4.2.2 Ignition System
for Modulating Gas
Control
FIGURE 14A -
Ignition Control
Module (Deep
Modulation Board)
in the Electrical
Compartment
IMPORTANT: The control module is P/N 257246 for
all sizes of MAPS®III&IV
Cabinet C heat sections and P/N 258319 on all
MAPS®III&IV Cabinet
A and B heat sections.
However, the ID plug on
each board is unique for
each size of heat section.
A replacement board will
require either a new ID plug
or reuse of the ID plug from
the board being replaced.
NOTE: Operating and
Lockout Error Codes
displayed on ignition
controller 3-character
display (FIGURE 14A) are
listed in Troubleshooting
Paragraph 7.3.3.
FIGURE 14B - Spark
Ignition Board,
P/N 257975
The control module is located in the control compartment with an additional board to
control spark that is attached directly to the side of the burner. Do not attempt to disassemble either board. However, each heating season check the lead wires for insulation
deterioration and good connections.
If replacement is required, these boards must be replaced with identical parts.
ID
Plug
3-Character Display
The control has a built-in, self-diagnostic capability. The control continuously monitors
its own operation and the operation of the heat section including direct spark ignition,
safety and modulating valves, and venter motor speed. The 3-digit display on the control indicates the current system state, warnings, failures, and test modes.
Controller LED Information (displayed on power up)
Display Info (example only) Description
C CAbFurnace series or model name, for example, "C cabinet
series"
400Heat Section Size
nAt or LPFuel type
1.01Software version
Normal Furnace Operation (LED 3-Character Display in FIGURE 14A)
LED Display Heat ModeDescription
OFF Mode (OFF) System Idle - Control board has power, no faults found, no call for heat.
PURGE Mode
(Pur)
IGNITION Mode
(Ign)
WARM-UP Mode
(HEA)
RUN Mode (run) Normal modulating operation.
Ignition Retry (rEt)
System is purging the heat exchanger – No gas on, no ame, inducer runs for
the specied purge timings. Purge cycles occur immediately before and after
each burner operation.
System is initiating burner operation – Igniter energized, modulating valve
moved to ignition setting, gas on. Maintained for the trial-for-ignition period
and the ve second ame stabilization period.
Period between Ignition and Run – System checks completed before
modulation control begins.
System has had a failed ignition attempt or has lost ame during burner
operation and is beginning another ignition cycle.
Spark Board is attached
CAUTION: Due to high
to the side of the burner.
voltage on the spark wire
and electrode, do not
touch when energized. See
Hazard Levels, page 3.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 25
Page 26
Orifice
Adapter
Ball Valve
Optional High Gas
Pressure Switch
Transducer
Ball Valve
Actuator
Gas
Valve
Optional Low Gas
Pressure Switch
Manifold Pressure Tap
4.0 Gas Heat
Section
Maintenance
(cont'd)
4.2 Heat Section
Controls
(cont'd)
4.2.2 Ignition System
for Modulating Gas
Control (cont'd)
Modulating Gas Control Sequence of Operation
1) Call for Heat - The IQ controller calls for heat (there is a closure between "R" and
"W" and at least 2 VDC to the analog input). The ignition system circuit board will check
the modulating valve position and move to lightoff position. It checks to see that the
limit switch is closed and the pressure switch is open. If the pressure switch is closed,
the circuit board will wait indenitely for the switch to open. If the switch is open, the
circuit board proceeds to prepurge.
2) Prepurge - After the actuator moves to its lightoff position, the circuit board energizes the venter motor and waits for the pressure switch to close. If the pressure switch
does not close at the beginning of a heat cycle, the venter motor will run for two min-
utes, then cycle off for 30 seconds, then on for two minutes, and so forth indenitely.
When the pressure switch is proven closed, the venter motor ramps up to the appropri-
ate lightoff speed and the circuit board begins the prepurge time. If ame is present any
time while in prepurge, the prepurge time is restarted. If ame is present long enough
to cause lockout, refer to the Troubleshooting Guide in Paragraph 7.3.2. The ignition
system circuit board runs the venter motor for a 30-second prepurge time, then proceeds to the ignition trial period.
3) Ignition Trial Period - The ignition system circuit board energizes the spark and
main gas valve. The venter remains energized. If ame is sensed during the rst 6
seconds, the spark is de-energized. If ame has not been sensed during the rst 6 sec-
onds, the control de-energizes the spark output and keeps the gas valve energized for
an additional one second ame proving period. If ame is not present after the ame
proving period, the control de-energizes the gas valve and proceeds with three ignition
re-tries as specied in “Abnormal Heat Cycle, Ignition Retry”. If ame is present, the
circuit board proceeds to steady heat. After three re-tries, the board will lockout for one
hour. It will require a cycling of power to reset before the one-hour limit.
4) Modulating Heat - As long as the call for heat exists, the circuit board not only
modulates the gas to precisely meet varying load conditions, but also modulates the
combustion air to maintain stable performance and optimize thermal efciency across
the entire modulating range. Circuit board inputs are continuously monitored to ensure
limit switch is closed and ame is established. When the call for heat is removed, the
ignition system circuit board de-energizes the gas valve and begins postpurge timing.
5) Post Purge - The venter motor output remains on for a 45 second postpurge period
after the system controller is satised.
4.3 Gas Train
See component
identication in
FIGURE 15A, 15B, or
15C.
FIGURE 15A Components in the
Heat Section Gas
Train - MAPS®III&IV
Cabinet A (Heat
Section Sizes 100,
150, 200)
Form O-MAPSIII&IV Cabinets A/B/C, Page 26
Location: The gas train is visible with the heat section door open.
Service: Carefully remove external dirt from the valves and check the wiring connec-
tions. Annually, in preparation for the heating season, check the single-stage operating
valve to be sure that it shuts gas ow off completely.
If any gas valves or other gas train components need to be replaced, they must be
replaced with identical part or factory-authorized replacement.
Page 27
Optional High Gas
Pressure Switch
Optional Low
Gas Pressure
Switch
Dual, Single-Stage Gas Valve
Ball Valve
Transducer
From Gas
Supply
To
Burner
Manifold Pressure Tap
Ball Valve
Actuator
Orifice
Adapter
Orifice Adapter
Optional High Gas
Pressure Switch
Transducer
Ball
Valve
Single-Stage
Gas Valve
Ball Valve
Actuator
Optional Low Gas
Pressure Switch
Manifold Pressure Tap
FIGURE 15B Components in the
Heat Section Gas
Train - MAPS®III&IV
Cabinet B (Heat
Section Sizes 250
and 300)
FIGURE 15C Components in the
Heat Section Gas
Train - MAPS®III&IV
Cabinet C (Heat
Section Sizes 400,
500, 600, 700)
Single-Stage Operating Gas Valve - All gas trains have either a single-stage or a dual single-stage safety gas valve.
The gas valve must be checked annually to ensure that it is shutting off gas ow completely; follow the instructions in
box below.
FIGURE 16A - Top View of Single-Stage Gas
Valves used on Cabinet A or B Sizes
Adjust Outlet
Pressure
1/8” Output
Pressure Tap
FIGURE 16B - Top View of Dual Single-Stage
Gas Valve used on Cabinet C Heat Section
Pressure
Adjustment
1/8” Outlet
Pressure
Tap
Inlet
Pressure Tap
Adjust Outlet
Pressure
Inlet Pressure
Tap
Instructions:
1. Locate the 1/8" NPT pressure tap or taps on the
combination valve.
2. Turn the knob(s) or switch to the OFF position to
Modulating Valve
prevent ow to the manifold. Connect a manometer to
each of the 1/8” outlet pressure taps (1 on the single-
stage valve; 2 on the dual single-stage valve). NOTE:
Manometers (uid-lled gauges) with inches water
The gas train also has a ball valve with an actuator to control gas ow. The ball valve
and actuator are located downstream of the regular or dual single-stage valve as
shown in FIGURE 17A.
Carefully clean external dirt accumulation from the actuator.
1/8”
Output
Pressure
Tap
3. Use nger(s) to fully block the burner orice(s).
Pressure
Adjustment
column scale are recommended. Turn the heater off.
On the valve, turn the knob(s) or switch to the ON
position.
Continue blocking for several seconds and observe
the manometers. If any pressure is indicated, the gas
valve is leaking. A leaking gas valve must be replaced
before the heater is put back in operation.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 27
1/8” Outlet
Pressure
Tap
Page 28
4.0 Gas Heat
Section
Maintenance
(cont'd)
4.3 Gas Train
FIGURE 17A -
Ball Valve and
Actuator in Gas
Control Option
AG70
(cont'd)
FIGURE 17B - Ball Valve with Actuator in Modulating Gas Control (Option AG70) Manifold
Ball Valve with actuator removed
Modulating System
Gas Valve (Ball
Inspect the position of the ball valve shaft.
□ In the fully open position, the dash marks on the top of the shaft should be aligned
Valve and Actuator)
Adjustment
□ In the fully closed position, the dash marks on the top of the shaft should be
If the ball valve shaft is not properly aligned or if the manifold pressure does not match
the settings in the chart below, the ball valve will need to be adjusted.
Manifold Pressures
for MAPS®III&IV Gas
Modulation System
Ball Valve Shaft
Ball Valve Actuator
Modulates the Gas Flow
Actuator
Set Screw
(shown on the
right or closed
position)
with the gas piping.
aligned at a 90° angle across the gas piping.
Manifold Pressure (" w.c.) Measured
at the Pressure Tap by the Gas Transducer
Cabinet and Heat
Section Size
A-Cab 100Nat3.4" w.c.0.15" w.c.
A-Cab 150Nat3.4" w.c.0.15" w.c.
A-Cab 200Nat3.4" w.c.0.15" w.c.
A-Cab 100LP10.0" w.c.0.5" w.c.
A-Cab 150LP10.0" w.c.0.5" w.c.
A-Cab 200LP10.0" w.c.0.5" w.c.
B-Cab 250Nat3.4" w.c.0.15" w.c.
B-Cab 300Nat3.4" w.c.0.15" w.c.
B-Cab 250LP10.0" w.c.0.45" w.c.
B-Cab 300LP10.0" w.c.0.45" w.c.
C-Cab 400Nat3.4" w.c.0.2" w.c.
C-Cab 500Nat3.4" w.c.0.2" w.c.
C-Cab 600Nat3.4" w.c.0.2" w.c.
C-Cab 700Nat3.4" w.c.0.2" w.c.
Gas
Type
High Setting
100% on ModHeat
Low Setting
0% on ModHeat
To adjust gas modulation follow instructions below:
1. Checking modulation requires a manometer capable of reading to 0.10" w.c. Connect the manometer as
instructed in Step 1.f) below.
To check and adjust the modulation system, the IQ controller must be in Test Mode. On the control display in the
electrical compartment, follow the steps below to enter Test Mode.
Form O-MAPSIII&IV Cabinets A/B/C, Page 28
Page 29
a) Scroll down to Menus and press Enter.
b) Enter password (0000) using the INC button and the right arrow button and press Enter.
c) Scroll down to the Service Menu and press Enter.
d) Scroll down to Test Mode and press Enter.
e) Scroll down to Manual Test; press Enter; press the INC button to change the command from OFF to ON; and
press Enter.
f) After the system has completed the shutdown sequence, connect the gas manometer to the manifold pressure
tap next to the transducer (See FIGURE 15 and illustration below).
g) On the display, scroll down to Heat Stg 1 and press Enter.
h) Scroll down to ModHeat which has a default setting of 100%.
2. With the ModHeat set at 100%, measure the manifold pressure. If the manifold pressure matches the High
Setting value in the chart (page 28), continue to Step No. 3. If the manifold pressure does not match the value
in the chart and the ball valve is fully or close to fully open, adjust the pressure screw(s) on the Honeywell
valve (See FIGURE 16) until the pressure matches the chart. Note, if the manifold has a dual valve, adjust both
pressure screws so that they are the same. When the manifold pressure measured at the manometer matches
the pressure listed in the chart, make a note for future reference of the position of the ball valve stem in relation
to the dash marks on the actuator.
3. On the display, change the ModHeat setting to 0% modulation and allow the ball valve to go to its lowest setting.
Check the manifold pressure on the manometer. If the manifold pressure matches the Low Setting value in the
chart, skip to Step No. 4. If the manifold pressure does not match the low (0%) value on the chart, the ball valve
will need to be adjusted. Follow these steps:
a) While the unit is still ring at 0% modulation, remove the ball valve actuator. To do this, locate the screw on the
rear of the actuator and remove it. Loosen the actuator set screw (See FIGURE 17B), and carefully remove
the actuator by lifting it straight up. Do not disconnect any wires.
b) Using adjustable pliers, slowly turn the ball valve stem until the manifold pressure on the manometer matches
the low setting on the chart.
Important NOTE: If the valve is adjusted too far closed and the ame goes out, let the unit recycle and then
manually open the ball valve to the 100% open position noted in Step No. 2. When the unit is ring at full re,
re-attach the actuator to the ball valve, and repeat the procedure beginning with Step No. 2.
c) When the manometer readings match the values in the chart and before re-installing the actuator, the burr
left on the ball valve stem from the previous set screw setting needs to be removed. Either lightly le the burr
on the valve stem to prevent the set screw from returning to the previous position or remove the valve stem,
rotate it 180° so that the set screw contacts the opposite side of the stem, and re-install the valve stem.
d) Re-install the actuator making sure it is level on the ball valve mounting plate.
e) Re-check the setting by going to full re (Set ModHeat at 100%) and returning to 0% modulation (Set
ModHeat at 0%). Measure the manifold pressure. The adjusted gas pressure should be close to the value in
the chart on page 28. If not, repeat the procedure.
4. When the settings are in agreement with the chart and testing is complete, remove the manometer. Set ModHeat
to 100%. Scroll the display back to Test Mode and press Enter. Disable Test Mode by pressing the INC button
to change the command from ON to OFF; and press Enter.
Gas Manifold
Transducer
Optional Gas
Pressure Switches
Location: See FIGURE 15.
Function: The transducer reads the manifold pressure and sets the venter motor
speed to precisely match the designed combustion settings.
Service: If the transducer needs to be replaced, use only a factory-authorized replace-
ment part designed for the purpose.
Location: Low pressure switch is at the entrance to the gas train. The high pressure
switch is at the burner end. See FIGURE 15.
Function: Monitors gas pressure and shuts down the heat section if gas pressure
becomes too low or too high. The low pressure switch is an auto reset type and is set
at 50% of the maximum manifold pressure. The high pressure switch requires manual
reset and is set at 125% of manifold pressure.
Service: There are no replaceable parts and the settings are non-adjustable. If replacement is required, use identical factory-authorized safety switches.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 29
Page 30
4.0 Gas Heat
Section
Maintenance
(cont'd)
4.4 Other Gas Heat Section Controls / Sensors
Combustion Air Proving Switch
Location: See FIGURE 1, page 5, for location.
Function: The function of the pressure switch is to verify the cali-
bration of the air pressure sensor mounted on the ignition control
board. If the air pressure is not as required, the controller will shut
down operation of the heat section.
Service: If it is determined that the pressure switch needs replacing, use only the
factory-authorized replacement part that is designed for the model and size of gas
heater being serviced.
The ignition board controls the entire combustion process by modulating both the gas
and the combustion air supply. Combustion air pressure switches used are listed below.
□ *A "B" Cabinet with 500
mbh of gas heat is a Size
250 heat section plus
a Model JHUP-25 curb
section duct furnace.
Both furnaces have an
air proving switch.
□ ** A "C" Cabinet with
1000 mbh of gas heat is
a Size 700 heat section
plus a Model JHUP-30
curb section duct furnace. Both furnaces
have a combustion air
proving switch.
Heat Section
Size
100Nat & Pro1.301.300.80Gray197078
150Nat & Pro1.301.300.80Gray197078
200Nat & Pro1.301.300.80Gray197078
250 and
JHUP-250
300Nat & Pro1.401.401.15Brown201160
400Natural2.702.701.40Red201159
500Natural2.902.901.40Red201159
600Natural3.353.352.00White234054
700*Natural3.403.402.00White234054
JHUP-300*Natural0.700.700.50Orange 196388
Gas
Natural1.151.150.80Gray197078
Propane1.301.301.05Brown 201160
Light Off (Cold) Equilibrium (Hot)
Full Rate
Setpoint
OFF
Label
Color
Switch
P/N
DANGER
Safe operation requires proper venting ow. Never bypass the combustion air
proving switch or attempt to operate the heat section without the venter running
and proper ow in the vent system. Hazardous condition could result. See Hazard
Levels, page 3.
Limit Control
Location: The limit control is located in the farthest downstream heater compartment
with the capillary sensor extending across the discharge side of the heat exchanger.
NOTE: If the installation includes an Option JHUP-30 curb section duct furnace, it also
has a limit control. See location in installation Form I-MAPSIII&IV, Paragraph 5.4.3
Function: The limit control is a temperature sensitive safety device. If the temperature
setting of the limit control is exceeded, the controller will shut down heat section operation.
Service: The limit switch will automatically reset when the temperature drops below
the setpoint. However, the cause for the limit activating should be found and corrected.
If it is determined that the limit control needs replacing, use only a factory-authorized
replacement part that is designed for that heat section.
5.0 Electric Heat
Section
Maintenance -
Turn off the power locking the disconnect switch. Allow the
heating elements to cool.
Models RECB,
RECC, REDB
and REDC
Form O-MAPSIII&IV Cabinets A/B/C, Page 30
WARNING
CAUTION: Wearing eye protection is recommended when
cleaning the heating elements and cabinet.
Page 31
Electric Heating
Elements and
Controls
Service: Check the heating elements at the beginning of the heating season. The ele-
ments are assembled and attached to the electrical panel that is visible on the inner
side of the electric heat section. Slide the panel out to access the elements. Carefully
clean all dust and dirt from the heating elements using a brush or steel wool. With a
vacuum or air hose, clean the inside of the cabinet especially the bottom and sides
where dirt and dust will accumulate.
If a replacement is needed, order a complete heat section assembly.
Location: See the control location illustration in FIGURE 1, page 5, and FIGURE 18,
below, the additional high voltage panel in the electric heat section. Quantities and
types of distribution blocks, fuses, and contactors depend on the size of the unit.
If replacement parts are required, check with your distributor and use only factoryauthorized replacements.
FIGURE 18 - High
Voltage Panel in the
Electric Heat Section
- Models RECB,
RECC, REDB, and
REDC
Distributor Blocks
are on this panel.
(qty varies by size
and voltage)
6.0 Energy
Recovery
Module,
Option ER1
Grounding Lug
High Voltage Panel in Electric Heat Section
If the MAPS® unit is equipped with an optional energy recovery module (Option ER1A,
ER1B, or ER1C), there are additional maintenance and service procedures unique to
the energy recovery wheel.
Refer to the energy recovery module manual, Form I-MAPSIII&IV-ER, for required
maintenance instructions and service information.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 31
Page 32
7.0 Troubleshooting
7.1 Troubleshooting
- Refrigeration
(All Models)
IMPORTANT: Do not release refrigerant to the atmosphere!
If required service procedures include the adding or removing of
refrigerant, the service technician must comply with all federal,
state and local laws. The procedures discussed in this manual
should only be performed by a qualied HVAC technician.
See Control
Instructions, Form
CP-MAPSD15/16/17/18,
for information on the unit
controller.
General Refrigeration Circuit - applies to all Models
SYMPTOMPOSSIBLE CAUSEREMEDY
A. Compressor
will not start.
B. Compressor
starts but cuts out
on low pressure
(low pressure
switch activates
at 35 psig.)
C. Compressor
starts but cuts out
on high pressure
switch.
D. Compressor
cuts out on
thermal overload.
E. Noisy
compressor.
F. Noisy unit
operation.
G. High suction
pressure
1. Power off, loose electrical connections or fuse
open.
2. Compressor contactor not closing.2. Check voltage to contactor coil, transformer, slave relay, system. Replace
3. Internal compressor thermal overload open.3. If compressor is hot, allow 2 hours to cool. See D. below.
4. Compressor defective.4. Check compressor for electrical failure. Compressor may be seized; check
5. High or low pressure switch open or defective.5. If manual reset (high pressure), reset switch. (Switch opens at 600 psi and will
1. Low refrigerant charge.1. Check subcooling; see Paragraph 3.5.
2. Thermal expansion valve setting2. Check superheat and adjust valve as needed.
3. Blower running backward.3. Interchange any two wires from 3 phase disconnect.
4. Loose blower, pulley, or belts.4. Check drive pulley alignment and belt tension.
5. Dirty lter.5. Check lter and evaporator coil.
6. Too little air ow or low entering air temperature. 6. Check airow and entering air wet bulb conditions.
7. Restriction in suction or liquid line.7. Check refrigerant circuit for restriction.
1. Insufcient refrigerant charge.1. Check subcooling (Paragraph 3.5). Check for leak. Repair and add refrigerant.
2. Defective or improperly adjusted expansion valve. 2. Check superheat (Paragraph 3.5) and adjust thermal expansion valve.
3. Low suction pressure.3. See “I. Suction pressure too low” above.
4. Defective compressor.4. See "G. High suction pressure” above.
1. Improper refrigerant charge.1. Check subcooling and superheat. (Paragraph 3.5)
2. Defective high or low pressure control.2. Check high or low pressure switch.
3. Liquid oodback.3. Possible tight bearings, see above.
4. Defective expansion valve.4. Check superheat and thermal expansion valve.
5. Poor air distribution.5. Check ductwork for recirculating.
6. High discharge pressure.6. See “H. High discharge pressure” above.
7. Leaking discharge valves in compressor.7. See “G. High suction pressure” above.
1. Refrigeration undercharged.1. Check subcooling (Paragraph 3.5) and add refrigerant.
2. Dirty lter or evaporator coil.2. Check lter, coil, and airow. Clean and/or replace.
3. Dirty or clogged condenser coil.3. Check coil and airow. Clean.
4. Air or other non-condensables in system.4. Check equalized high side pressure with equivalent outdoor temperature.
5. Defective compressor.5. See “G. High suction pressure” above.
6. Restriction in suction and liquid line.6. Check for restrictions in refrigerant circuit.
7. Control contacts stuck.7. Check wiring.
1. Refrigerant undercharge or leak in system.1. Check subcooling(Paragraph 3.5). Check for leak. Repair and add refrigerant.
2. Evaporator plugged with dirt or ice.2. Check evaporator, airow, and lter. Clean.
3. Improperly adjusted or defective expansion valve. 3. Check superheat (Paragraph 3.5) and adjust thermal expansion valve. Check
expansion valve bulb placement and insulation.
4. Defective compressor.4. Check compressor for proper operation.
5. High discharge pressure.5. See “H. High discharge pressure” above.
6. Airow is too high.6. Check external static pressure.
1. Airow is too low.1. Check evaporator coil; check lters; check for closed dampers or grills; check
drive for loose parts, belts, or misalignment; and check external static pressure.
2. Return air temperature too low.2. Check entering air wet bulb conditions.
1. Refrigerant undercharge.1. Check subcooling.
2. High discharge pressure.2. See H. above.
7.2 Compressor
Digital
Controller
Troubleshooting
®
- all MAPS
IV
Models
NOTE: To identify MAPS®IV
Models, see Paragraph 1.0.
General - The digital controller is located in the electrical compartment and acts as the
interface between the digital compressor and the unit controller. If the unit interface display indicates critical Alarm Code 17, Modulating Capacity Compressor Failure, check
the LED lights on the digital controller.
The alert code (red LED ashes) on the digital controller remains active and the compressor de-energized until the reset conditions have been met or the 24VAC power
is cycled off and on. All Codes except 6 result in compressor (contactor and unloader
valve) being de-energized.
Compressor Digital Controller LED’s
LED State
ColorCODE
GreenSolidPower (24VAC present at
Green. FlashingAnti-short cycle timer is
YellowSolidUnloader (Solenoid valve
RedNot litNo abnormal operation
Red2 Flashes High Discharge
IndicatesAdditional Information
power terminals)
active
is energized; compressor
capacity is 0.)
alerts
Temperature Alert
(thermistor temperature
above 268°F or
thermistor is short
circuited)
Modulating capacity compressor starts only when
demand signal input is above 1.45 VDC and no
ALERTS (red LED ashes) are active.
Modulating capacity compressor always unloads for 0.1
second at startup.
Modulating capacity compressor will be allowed to
restart after a 30-minute delay and after the thermistor
temperature is below 250°F. Compressor will lockout
after 5 alerts within 4 hours and can only be reset by
cycling the 24VAC power off and on.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 33
(continued)
Page 34
7.2 Compressor
Digital
Controller
Troubleshooting
®
- all MAPS
IV
Models (cont'd)
Compressor Digital Controller LED’s (cont'd)
Red3 Flashes Compressor Protector
Trip (demand signal
>1.44VDC & no
compressor current)
Red4 Flashes Locked Rotor AlertLocked rotor sensed by controller on four consecutive
Red5 Flashes Demand Signal Loss
(below .5VDC)
Red6 Flashes Discharge Thermistor
Fault (no signal being
received)
Red7 Flashes Unloader Solenoid Valve
Fault
Red8 Flashes Compressor Contactor
Fault (compressor
running on less than
1.44VDC demand signal)
Red9 Flashes Low 24VAC supply
to controller (below
18.5VAC)
AllSolidDigital compressor
controller failure
AllFlashing24VAC Supply too low for
operation
Possible causes - internal overload, fuse or breaker,
compressor wiring. After 2-minute anti-short cycle timer
the controller will attempt to restart the compressor as
long as demand is above 1.44VDC. No lockout feature.
start-ups. Lockout occurs and can only be reset by
cycling 24VAC power off and on.
When demand signal input rises above 0.5VDC, alarm
code will reset. When demand reaches above 1.44VDC
and anti-short cycle timer has timed out, modulating
capacity compressor will restart.
Modulating compressor capacity limited to 50%.
Re-connect or replace thermistor.
Modulating compressor will run unloaded. Alarm will be
reset when current is no longer detected while system
demand signal is below 1.44VDC.
Alarm will reset when supply voltage to controller rises
above 19.5VAC.
The installed digital compressor controller can be tested
to verify that it is working properly. In each test, 24VAC
must be supplied to 24VAC and 24COM. For output
test, 24-250VAC must be supplied to L1 and L2.
Input Tests - 1) Thermistor Input - Disconnect thermistor
(T1 & T2); LED should display Code 6.; and 2) Demand
Input - Disconnect unit controller (C1 & C2); LED
should display Code 5 unless a previous alert code was
present.
Output Tests - 1) Contactor Output - while the controller
is powered off (no supply voltage to 24VAC and
24COM), disconnect signal wire from C1 & C2; add
jumper wires from P3 to C2 and from P1 to C1; re-apply
power to 24VAC and 24COM. If functioning normally,
same voltage should be read across M1 and M2 as
across L1 and L2, unless an LED ALERT code is
present.; and 2) Unloader Output - while controller is
modulating the unloader solenoid (whenever the yellow
LED is lit), voltage across U1 and U2 should be the
same as L1 and L2.
7.3 Troubleshooting the Heat Section
7.3.1 General Troubleshooting - Electric Heat Section - RECB, RECC, REDB, & REDC
PROBLEMPROBABLE CAUSEREMEDY
Unit does not
operate
Fan operates
but element
does not heat
Insufcient
heat
Form O-MAPSIII&IV Cabinets A/B/C, Page 34
1. No power to unit1. Turn on power; check supply fuses or main circuit breaker.
2. Blown fuses2. Check and replace if necessary.
3. Defective or incorrect wiring.3. Check wiring and connections. Refer to wiring diagram provided with unit.
4. Defective or burned out control transformer 4. Check secondary voltage with voltmeter. Replace if necessary.
1. Dirty lters1. Check lters and clean or replace if necessary.
2. Defective air proving switch2. Check and replace if necessary.
3. Blown element fuses3. Check and replace element fuses if necessary.
1. Burned out element1. Turn off power and check element resistance with ohmmeter. Replace if open.
2. Blown fuses2. Check and replace if necessary.
3. Cycling on limit control3.
a) Check air throughput (temperature rise).
b) Check motor rpm against nameplate rating. Replace motor if speed is too slow.
c) Defective limit control. Check wiring and connections. Check continuity through
control and replace if necessary.
4. Defective or incorrect wiring.4. Check wiring and connections. Refer to wiring diagram provided with unit.
Page 35
7.3.2 General Troubleshooting - Gas Heat Section - Models RDCB, RDCC, RDDB & RDDC
PROBLEMPROBABLE CAUSEREMEDY
Venter motor
will not start
Burner will
not light
Burner cycles
on and off
No heat
(Heater
Operating)
Venter motor
will not run
Venter motor
cuts out on
overload
1. No power to unit.1. Turn on power; check supply fuses or main circuit breaker.
2. No 24 volt power to ignition system circuit board. 2. Turn up thermostat; check control transformer output.
6. Defective venter motor or capacitor6. Replace defective parts. Recommend replacing capacitor when replacing
1. Manual valve not open.1. Open manual valve.
2. Air in the gas line.2. Bleed gas line (initial startup only).
3. Gas pressure too high or too low.3. See installation manual, Form I-MAPSIII&IV, Paragraph 9.2.1.
4. No Spark:4.
a) Loose wire connections.a) Be certain all wire connections are solid.
b) Transformer failure.b) Be sure 24 volts is available.
c) Incorrect spark gap.c) Maintain spark gap at 1/8".
d) Spark cable shorted to ground.d) Replace worn or grounded spark cable.
e) Spark electrode shorted to ground.e) Replace if ceramic spark electrode is cracked or grounded.
f) Burner not grounded.f) Make certain circuit board is grounded to ignitor.
g) Ignition system circuit board not grounded.g) Make certain circuit board is grounded to furnace chassis.
h) Unit not properly grounded.h) Make certain unit is properly eld grounded to earth ground and properly
i) Ignition system circuit board fuse blown.i) Correct cause; replace fuse.
j) Modulation system out of acceptance rangej) Review error codes on board; refer to pages 36-39.
j) Faulty circuit board.j) If 24 volt is available to the circuit board and all other causes have been
5. Lockout device interrupting control circuit by
above causes.
6. Combustion air proving switch not closing6.
7. Faulty combustion air proving switch.7. Replace combustion air proving switch.
8. Valve not operating.8.
a) Defective valve.a) If 24 volt is measured at the valve connections and valve remains closed,
b) Loose wire connectionsb) Check and tighten all wiring connections.
9. Circuit board does not power valves.9.
a) Loose wire connections.a) Check and tighten all wiring connections.
b) Flame sensor grounded.b) Be certain ame sensor lead is not grounded or insulation or ceramic is
c) Incorrect gas pressure.c) See installation manual, Form I-MAPSIII&IV, Paragraph 9.2.1.
d) Cracked ceramic at sensor.d) Replace sensor.
1. Gas pressure too high or too low.1. See installation manual, Form I-MAPSIII&IV, Paragraph 9.2.1.
2. Burner not grounded2. Make certain integrated circuit board is grounded to ignitor.
3. Circuit board not grounded.3. Make certain integrated circuit board is grounded to furnace chassis.
4. Faulty integrated circuit board4. If 24 volt is available to the circuit board and all other causes have been
5. Combustion air proving switch not closing.5.
6. Faulty combustion air proving switch.6. Replace combustion air proving switch.
7. Flame sensor grounded.7. Be certain ame sensor lead is not grounded or insulation or ceramic is
8. Cracked ceramic at sensor.8. Replace sensor.
9. Incorrect polarity.9. Reverse line volt leads to integrated circuit board.
1. Incorrect valve outlet pressure.1. Check valve outlet pressure. See Installation Form I-MAPSIII&IV,
2. Cycling on limit control.2. Check air throughput.
1. Low or high voltage supply.1. Correct electric supply.
2. Defective motor or capacitor.2. Replace defective parts. Recommend replacing capacitor when replacing
motor. See Paragraph 4.1.2.
phased (L1 to hot lead L2 to neutral).
eliminated, replace board.
5. Reset lockout by interrupting control.
a) Remove obstructions from vent.
b) Replace faulty tubing to pressure switch.
replace valve.
not cracked. Replace as required.
eliminated, replace board.
a) Make sure unit is properly vented.
b) Remove obstructions from vent.
c) Replace faulty tubing to pressure switch.
not cracked. Replace as required.
Paragraph 9.2.1.
motor. See Paragraph 4.1.2.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 35
Page 36
7.3 Troubleshooting the Heat Section (cont'd)
7.3.3 Troubleshooting - Modulating Control Module used on Cabinet A, B, and C Gas Heat
Sections
The control that operates the furnace in a MAPS®III Cabinet A, B, and C has a built-in, self-diagnostic capability. The
control continuously monitors its own operation and the operation of the system. The LED on the control indicates the
current state, warnings, failures, and test modes.
Normal Furnace Operation Display
LED Display Heat ModeDescription
OFF Mode (OFF)System Idle - Control board has power, no faults found, no call for heat.
PURGE Mode (Pur)
IGNITION Mode (Ign)
WARM-UP Mode (HEA)
(Board Self Check)
RUN Mode (run)Normal modulating operation.
Ignition Retry (rEt)
System is purging the heat exchanger – No gas on, no ame, venter motor runs for the specied purge
timings. Purge cycles occur immediately before and after each burner operation.
System is initiating burner operation – Ignitor energized, modulating valve moved to ignition setting, gas
on. Maintained for the trial-for-ignition period and the ve-second ame stabilization period.
Period between Ignition and Run – System checks completed before modulation control begins.
System has had a failed ignition attempt or has lost ame during burner operation and is beginning
another ignition cycle.
Deep Modulation (Option AG70) Ignition Board is in
the Control Compartment (See FIGURE 1, page 5.)
IQ Controller Signal
Input Terminals (J4)
Main Board Supply Power Input
Spades (L1 T1 and L2 T5)
Board Status
Voltage Output
to IQ (J7)
Board Power
and Signal (J6)
Control Board
Fuse (3A)
Plug Connection for Board
Control Points
(J8)
• Ball Valve
Actuator Power,
Drive Voltage,
and Feedback
Signal
• Off Board
Digital Venter
Air Pressure
Switch and Unit
Primary Limit
Switch
Gas Manifold PSI Transducer
Plug 3-wire (red, black, and green)
Wiring Connection (J13)
On board Air Pressure Sensor for Monitoring Inducer Pressure.
Venter Sensing Tubing is connected from Venter housing to
J9, J10, J3, and J2 are
not currently used.
"LO" pressure input point on air sensing transducer.
Inducer Motor Main Power
Connection Spades
(IND-L2 T3 and IND-L1 T2)
Inducer
Motor
Capacitor
Spade
Connection
(AUX-L2 T6)
Flame
Sensor
Spade
Connection
(T8)
ID Plug
(unique by
heat section
size)
3 Character LED
Display used to show
deep modulation
board codes for
status, alarm, and
error information.
Form O-MAPSIII&IV Cabinets A/B/C, Page 36
Page 37
Gas Heat Section Modulating Control FUNCTIONAL ALERTS
CodeAlertDescriptionProbable CausesSolutions
Failed ignition
attempt (AO1)
Maximum
number of
allowed retries
not met
Lost Flame
(AO2)
Insufcient
Combustion Air
(AO3)
Furnace
functional
Limited Low
Fire (AO4)
Weak Flame
Signal (AO5)
The ame could not be
established during the trial
for ignition period. This alert
indicates the maximum
number of retries has not
been exceeded and furnace
operation will continue with
another ignition attempt.
The ame sensor signal
has been lost after ame is
established during a call for
heat. This alert is displayed
during the RECYCLE period
prior to the next ignition
attempt.
Furnace cannot achieve
desired combustion air ow
due to blockage or high
altitude operation resulting in
a de-rate of the furnace.
Automatic adaptive program
is currently limiting the lower
range of modulation at avoid
ame loss at minimum re
conditions. The alert is
displayed during the run
cycle once a ame-out
condition has triggered the
Limited Low Fire function.
This function is reset by
cycling power to the board.
The ame signal level is
less than optimal for this
furnace. Maintenance of the
ame sensing components
is advised.
See
LOCKOUT ERRORS
section, pages 38-39.
A. Flame sensor coated1. Clean ame rod sensor.
B. Flame sensor
improperly mounted or
grounded
C. Unstable ame pattern 1. Verify that the spacing between the burner body and the burner shield
D. Insufcient intermediate
gas manifold pressure
through main gas safety
valve
E. Insufcient gas manifold
pressure to burner through
modulating ball valve
assembly
A. High altitude operation 1. Normal operation. Furnace automatically de-rates for high altitude
B. Partially blocked vent1 Check air inlet and outlet for blockage.
C. Leak in sensing hose1. Check sensing hose for cracks, crimps, or loose connections.
D. Low Line Voltage1. Check the line voltage to the control board. Voltage should be within
E. Faulty venter assembly 1. Verify that the venter assembly is functioning properly by referring to
A. Low gas line pressure1. Ensure gas supply is connected to furnace and check for proper line
B. Insufcient intermediate
gas manifold pressure
through gas safety valve
C. Faulty burner operation 1. Check burner orice for proper size and blockage.
D. Faulty ame sensor1. Check ame rod wiring and connections.
E. Improper alignment of
the modulating actuator
and the gas ball valve.
F. Blocked or improper
venting
G. Improper jumper
connection on IQ UI-12
causing AO-4 to show on
BacView as alarm and
disables heat sequence.
A. Flame sensor coated1. Clean ame rod sensor.
B. Flame sensor
improperly mounted or
grounded
C. Unstable ame pattern 1. Verify that the spacing between the burner body and the burner shield
in the
See in the LOCKOUT ERRORS section, pages 38-39.
1. Check ame sensor wiring integrity and ceramic for cracks.
2. Re-install / replace ame sensor.
is equal across the entire length of the burner.
2. Check that the seals between the heat exchanger header and heat
exchanger tubes are sound; refer to Paragraph 4.1.1.
3. Ensure that the heat section door gasket is in place and the doors are
properly aligned
1. Check for faulty gas valve wiring.
2. Check 24 VAC to gas valve assembly.
3. Check inlet pressure to safety gas valve.
4. Check outlet pressure from the safety gas valve.
5. Replace safety gas valve if faulty.
1. Check voltage to gas valve actuator. (2-10 VDC depending on model)
2. Check alignment and set screw connection between ball valve and
actuator. See Paragraph 4.3.
conditions.
2. Check venting conguration for excessive venting length, improper
sizing, etc.
10% of nameplate.
the sensing pressure chart on page 30.
pressure.
1. Check for faulty gas valve wiring.
2. Check 24 VAC to gas valve assembly.
3. Check inlet pressure to safety gas valve.
4. Check outlet pressure from the safety gas valve – adjust as needed.
5. Replace safety gas valve if faulty.
2. Check for proper alignment of ame rod.
3. Clean ame rod sensor.
1. Check that the alignment of the actuator to the ball valve is correct.
The valve must be in the fully open position when the actuator is
energized (ACTUATOR DRIVE = 9.6 VDC or greater).
2. Ensure that the setscrew on the actuator is tightened to the ball valve
stem.
1. Check air inlet and outlet for blockage.
2. Check venting conguration for excessive venting length, improper
sizing, etc.
1. Verify that the IQ heating feedback input is set to receive the ignition
board voltage output of 0-10VDC from terminals J7 by making sure
jumpers are set to receive 0-10VDC signal on UI-12 of the IQ controller.
1. Check ame sensor wiring integrity and ceramic for cracks.
2. Re-install / replace ame sensor.
is equal across the entire length of the burner.
2. Check that the seals between the heat exchanger header and heat
exchanger tubes are sound; refer to Paragraph 4.1.1.
3. Ensure that the heat section door gasket is in place and the door is
properly aligned.
(continued)
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 37
Page 38
7.3 Troubleshooting the Heat Section (cont'd)
7.3.3 Modulating Control Module on Cabinet A, B, C Gas Heat Sections (cont'd)
Gas Heat Section Modulating Control LOCKOUT ERRORS
CodeAlertDescriptionProbable CausesSolutions
Ignition
Board
Failure
(888)
Failed
Ignition
(EO1)
Maximum
Retries (3)
Exceeded
Primary
Limit /
Fuse
Failure
(EO2)
Modulation
Valve
Failure
(EO3)
Air Sensor
Failure
(EO4)
Pressure
Sensor
Reading
Low
Ignition board start-up
checks have detected
an error.
The ame could
not be established
during multiple trialfor-ignition periods
(3). The maximum
number of retries
has been exceeded
and the furnace is in
a lockout condition.
System Shutdown
alarm lockout will need
to be reset through
BacView interface or
IQ controller will need
to be power cycled.
The control board
safety fuse has
blown or the primary
temperature limit has
opened indicating
safe operating
temperatures for this
furnace have been
exceeded.
The control lost the
position feedback from
the modulating gas
valve actuator.
The air sensor reading
is too low for operating
conditions or the air
pressure switch closed
when the sensor
indicates low ow
The pressure switch
MUST be open prior to
venter activation.
A. Faulty transformer1. Check 24-volt transformer for correct output.
2. Check connections and wiring to control board and other
components connected to the 24 volt source.
3. Replace if necessary.
B. Faulty control board1. Turn off power to the furnace, wait 30 seconds and turn power
A. Insufcient gas line pressure1. Insure gas supply is connected to furnace and check for proper
B Gas valve control turned “OFF” 1. Turn gas valve to the “ON” position
C. No spark from direct spark
ignition
D. Insufcient intermediate gas
manifold pressure through gas
safety valve
D. (cont'd)4. Check outlet pressure from the safety gas valve – adjust as
E. Insufcient gas manifold
pressure to burner through
modulating ball valve assembly
F. Burners do not light1. Check spark rod assembly for proper location, spark gap, etc.
G. Burners light and remain lit for
about 5 seconds
A. Improper circulating airow1. Check lter / replace if dirty.
B. Primary limit switch failure1. Check for an open primary limit switch at ambient temperature.
C. Fuse is blown1. Check and replace fuse on the board.
D. Faulty primary limit switch
wiring
A. Faulty modulation valve
actuator wiring
B. Modulation valve actuator
failure
A. Faulty wiring or connections1. Check pressure switch wiring.
B. Faulty pressure switch1. Replace pressure switch.
C. Faulty pressure sensor,
located on the board
back on. Re-try ignition sequence and see if the system responds.
2. Replace control board if necessary.
line pressure.
1. Check ignition voltage (115 VAC from board to transformer) and
wiring.
2. Check 24 VAC transformer for DSI board.
1. Check for faulty gas valve wiring.
2. Check 24 VAC to gas valve assembly.
3. Check inlet pressure to safety gas valve.
needed.
5. Replace safety gas valve if faulty.
1. Check voltage to gas valve actuator. (7 – 10 VDC depending on
model)
2. Check alignment and setscrew connection between ball valve and
actuator (See procedure in Paragraph 4.3.).
2. Verify that the spacing between the burner body and the burner
shield is equal across the entire length of the burner.
3. Check burner orice for proper size and blockage.
1. Check ame rod wiring and connections.
2. Check for proper alignment of ame rod.
3. Clean ame rod sensor.
2. Check for improperly sized duct system.
3. Check for faulty blower motor.
4. Check for faulty blower motor wiring.
2. Make sure fuse socket is tight, crimp fuse terminals if necessary.
1. Check primary limit wiring continuity from the switch to the control
board.
1. Ensure wiring is connected per unit wiring diagram.
2. Check for loose pins or bad connections.
3. Check for frayed wiring or shorts to ground.
1. Ensure actuator has 24 V power.
2. Ensure actuator is receiving signal from the control board (2-10
VDC).
3. Check for actuator feedback to the control board (2-10 VDC)
2. Check inducer wiring.
3. Check for plugged or disconnected vacuum hoses.
1. Replace board.
Air Sensor
Failure
(EO5)
Pressure
Sensor
Reading
High
Form O-MAPSIII&IV Cabinets A/B/C, Page 38
The air sensor reading
is too high when the
venter is off or the
air pressure switch
open when the sensor
indicates high ow.
The pressure switch
MUST close to initiate
an ignition sequence.
A. Faulty wiring or hose
connections
B. Blocked or improper venting1. Check air inlet and outlet for blockage.
C. Faulty pressure switch1. Replace pressure switch.
1. Check pressure switch wiring.
2. Check venter motor wiring.
3. Check for broken or disconnected vacuum hoses.
2. Check venting conguration for excessive venting length,
improper sizing, etc.
Page 39
Gas Heat Section Modulating Control LOCKOUT ERRORS (cont'd)
CodeAlertDescriptionProbable CausesSolutions
Gas
Sensor
Failure
(EO6)
Pressure
Sensor
Reading
Low
Gas
Sensor
Failure
(EO7)
Pressure
Sensor
Reading
High
Improper
Flame
Signal
(EO8)
No Firing
Rate Input
(EO9)
Invalid I.D.
Plug (Eid)
The gas transducer
reading is too low
compared to the
expected value for the
modulating gas valve
actuator position.
When the furnace is
operating at 75% or
higher -- greater than
8 VDC analog input
voltage - the manifold
pressure sensor must
read 1.4" w.c. or
higher
The gas transducer
reading is too high
compared to the
expected value for the
modulating gas valve
actuator position.
When the furnace
is operating at 75%
or lower - less than
8 VDC analog input
voltage -- the manifold
pressure sensor must
read 2.8" w.c. or lower.
Control senses ame
present when the gas
valve is commanded
off.
Call for heat is sensed
(R & W closed) but
ring rate is below
dened voltage
threshold for furnace
operation.
The installed I.D. plug
is not valid for this
control board.
A. Modulating actuator/ball valve
not properly aligned
B. Line pressure too low1. Ensure line pressure is properly adjusted for the gas and
C. Intermediate regulated
pressure to low
D. Wrong gas pressure sensor
installed.
E. Gas pressure sensor faulty1. Ensure gas manifold transducer is installed properly and wired
A. Modulating actuator / ball
valve not properly aligned
B. Line pressure too high1. Ensure the line pressure is properly adjusted for the gas and
C. Intermediate regulated
pressure too high
D. Wrong gas pressure sensor
installed
E. Gas pressure sensor faulty1. Ensure gas sensor is installed properly and wired per the unit
A. Flame remains lit in “Off” cycle 1. Gas valve leaks - check wiring to remove continuous 24V to gas
A. Faulty wiring into the “Analog
+” and “Analog –“ terminals
B. No signal from source.1. Check ring rate input voltage – must be greater than 1.5 VDC.
A. Incorrect I.D. plug installed1. Ensure I.D. plug is correct for the furnace – check label.
1 Perform modulating system gas valve alignment procedure; see
Paragraph 4.3.
application. Correct as needed.
1. Ensure the safety gas valve(s) are properly adjusted to the
specied outlet pressure. Adjust per the installation instructions as
necessary.
1. Ensure the proper gas transducer - either natural gas or propane
- is installed. Replace as needed.
per the unit wiring diagram. Replace as necessary.
1. Perform modulating system gas valve alignment procedure; see
Paragraph 4.3.
application. Correct as necessary.
1. Ensure the safety gas valve(s) are properly adjusted to the
specied outlet pressure. Adjust per the installation instructions as
necessary.
1. Ensure gas sensor -- either natural or propane -- is installed.
Replace as necessary.
wiring diagram. Replace as necessary.
valve.
2. Gas valve is stuck open – remove, repair, or replace gas valve.
1. Ensure wiring is connected per unit wiring diagram.
2. Check for loose pins or bad connections.
3. Check for frayed wiring or shorts to ground.
2. Troubleshoot controller providing ring rate input to the deep
modulation ignition control board.
2. Ensure I.D. plug is properly inserted into the mating connector on
the control board.
3. With the I.D. plug installed, cycle power to the furnace. The board
will display the I.D. plug identity upon power-up.
4. Install correct I.D. plug as needed.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 39
Page 40
INDEX
A
Air Proving Switch 20
B
Ball Valve and Actuator in Gas
Control Option AG70 28
Bearings 7
Belts 7
Braze 15
Burner 21
Burner Assembly and Gas Train
23
Burner Maintenance 22
Burner Orices 23
Burner Removal Instructions 22
C
Charge the System 16
Coil Maintenance 8
Combustion Air Proving Switch 30
Compressor 12
Mount the Replacement