Reznor RCB060 Service Manual

Form O-MAPSIII&IV Cabinets A/B/C (Version B.4)
CQS
Obsoletes O-MAPSIII Cabinets A/B/C (Version B.3)
®
Operation / Maintenance / Service
Applies to: Cabinet Sizes A, B, and C
®
of MAPS®III Models RCB, RDB,
RDCB, RDDB, RECB, REDB and
MAPS®IV Models RCC, RDC,
RDCC, RDDC, RECC, REDC
P
R
O
Y
C
C
E
G
C
C
U
S
T
O
M
CQS
E
Q
R
U
P
R
O
D
E
S
R
E
G
S
V
E
N
N
O
T
P
U
-
T
R
A
T
S
M
Y
E
A
L
I
T
U
C
T
T
S
N
Y
Y
S
A
R
R
A
T
W
MAPS® Cabinet
Sizes A, B, and C
R-410A
Refrigerant
DANGER
This unit contains R-410A high pressure refrigerant. Hazards exist that could result in personal injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-410A refrigerant and
using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for R22 refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed
in this manual should only be performed by a qualied HVAC technician.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 1
Table of Contents
1.0 General ....................................................2-3
2.0 Maintenance Requirements ..................3-6
2.1 Maintenance Schedule.....................................4
2.2 Control Locations ............................................. 5
2.3 Cross-Reference of Models and
Cabinet Sizes A, B, and C ..............................6
3.0 Maintenance & Service Procedures ...6-21
3.1 Filters ..............................................................6
3.2 Drive Components ...........................................7
3.3 Condenser Fans...............................................8
3.4 Coil Maintenance .............................................8
3.5 Check Refrigerant Pressure & Temperatures
(subcooling and superheat) ............................. 9
3.6 Compressor Operation, Maintenance, and
Replacement.................................................. 11
3.7 Thermostatic Expansion Valves ..................... 19
3.9 Other Controls ................................................ 20
3.8 Optional Dampers and Damper Controls ....... 20
1.0 General
This booklet includes operation, maintenance, and service information for Cabinet Sizes A, B, and C of the MAPS® III and MAPS® IV Models listed below. Before begin­ning any procedure, carefully review the information, paying particular attention to the warnings. Handling of refrigerant should only be performed by a certied HVAC techni­cian with knowledge of the requirements of R-410A refrigerant and in compliance with all codes and requirements of authorities having jurisdiction.
The instructions in this manual apply to the following MAPS® Models in Cabinet A, B, and C Sizes and Model JHUP 250 and 300 duct furnace curb option.
4.0 Gas Heat Section Maintenance -
RDCB, RDCC, RDDB, RDDC .............21-30
4.1 Heat Exchanger, Burner, and Venter..............21
4.2 Heat Section Controls .................................... 25
4.3 Gas Train........................................................26
4.4 Other Gas Heat Section Controls / Sensors ..30
5.0 Electric Heat Section Maintenance -
RECB, RECC, REDB, REDC ..............30-31
6.0 Energy Recovery Module,
Option ER1 ..............................................31
7.0 Troubleshooting .................................32-39
7.1 Troubleshooting - Refrigeration (All Models) ..32
7.2 Compressor Digital Controller
Troubleshooting - all MAPS® IV Models.........33
7.3 Troubleshooting the Heat Section .................34
INDEX .............................................................40
NOTE: To conrm that this
booklet is applicable, see list of Model and Cabinet Sizes in Paragraph 2.3, page 6.
Form O-MAPSIII&IV Cabinets A/B/C, Page 2
MAPS
Model
®
III MAPS®IV
RCB RCC
RDCB RDCC
RECB RECC
RDB RDC
RDDB RDDC
REDB REDC
JHUP
System Description (MAPS®III models have staged cooling; MAPS®IV models have modulating cooling.)
Makeup Air Cooling Packaged System, 1500-9000 CFM
Makeup Air Cooling Packaged System, 1500-9000 CFM, with Gas Heat Section (100-700 MBH)
Makeup Air Cooling Packaged System, 1500-9000 CFM, with Electric Heat Section (10- 88 kw)
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged System, 1500-9000 CFM
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged System, 1500-9000 CFM, with a Gas Heat Section (100-700 MBH)
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged System, 1500-9000 CFM, with Electric Heat Section (10 - 88 kw)
Optional Curb Section with 250 or 300 MBH Gas-Fired Duct Furnace installed with a Model RDCB, RDCC, RDDB or RDDC with a Size 250 or 700 Heat Section to provide 500 or 1000 MBH heating
Denitions of Hazard
Intensity Levels used in this Manual
There are warning labels on the unit and throughout this manual. For your safety, comply with all warnings during installation, operation, and service of this system. See
denitions of Hazard Intensity Levels of warnings below.
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
2.0 Maintenance Requirements
To ensure long life and satisfactory performance, a system that is operating under nor­mal conditions should be inspected according to the Maintenance Schedule in Para­graph 2.1. If in an area where an unusual amount of dust or soot or other impurities are present in the air, more frequent inspection is recommended.
Refer to the illustration in FIGURE 1 and follow the instructions in the referenced para­graphs to maintain this equipment. Maintenance requirements apply to all Models and Sizes unless noted.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be
performed by a qualied HVAC technician familiar with
R-410A refrigerant.
WARNING
Lock power OFF before performing any maintenance procedure (except where power is required such as checking refrigerant pressure and temperature). Lock disconnect switch in OFF position. If the system has a gas heat section, when you turn off the power supply, turn off the gas. See Hazard Levels above.
If replacement parts are required, use only factory-
authorized parts. For information, go to
www.ReznorHVAC.com or call (800)-695-1901.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 3
2.0 Maintenance Requirements (cont'd)
2.1 Maintenance
Schedule
Important NOTE:
If equipped with an optional energy recovery module, refer to Form I-MAPSIII&IV-ER for enthalpy wheel maintenance instructions
Monthly
Inspect lters; clean or replace as needed. See Paragraph 3.1.
Inspect the condensate drain; clean as needed. For information, see the
installation manual, Form I-MAPSIII&IV, Paragraph 6.2.
Semi-Annually
Inspect the unit blower and belts. Check belts for tension, wear, and alignment.
Adjust or replace as needed. Clean dirt from blower and motor. See Paragraph
3.2.
Annually
NOTE: Redo the cooling startup procedures when the cooling season begins. Refer
to Startup instructions in the installation manual, Form I-MAPSIII&IV, Paragraph 10.0.
All Models - Beginning of the cooling season or more frequently in year-round cooling climate:
Inspect the wiring for any damaged wire. Replace damaged wiring.
Inspect the condensate drain pan. Clean the coil cabinet, clean the drain pan,
and ll the trap.
Inspect/clean condenser fans. See Paragraph 3.3.
Inspect/clean all coils. See Paragraph 3.4.
Check compressor operation. See Paragraph 3.6.
Check refrigerant pressure and temperatures (superheat and subcool). These
checks are done when the system is operating. See Paragraph 3.5.
Models RDCB, RDCC, RDDB, & RDDC with a gas heat section (beginning of the heating season) - See Paragraph 4.0:
NOTE: A MAPS® B cabinet with 500 MBH of heat is a Size 250 gas heat section plus an optional Model JHUP curb duct furnace. A MAPS® C cabinet with 1000 MBH of heat is a Size 700 gas heat section plus an optional Model JHUP curb duct furnace. The same maintenance procedures apply to the duct furnaces.
Clean all dirt and grease from the combustion air openings and the venter
assembly.
Check the heat exchanger, burner, and venter for scale, dust, or lint
accumulation. Clean as needed.
Check the gas valves to ensure that gas ow is being shutoff completely.
Models RECB, RECC, REDB, & REDC with an electric heat section (beginning of the heating season) - See Paragraph 5.0:
Form O-MAPSIII&IV Cabinets A/B/C, Page 4
Check wiring connections.
Check the heat section and elements for dust or lint accumulation. Carefully
clean as needed.
2.2 Control Locations
Controller
Display
(BacView)
IQ
Controller
Reheat
Board
Combustion
Air Proving
Switch
(RDCB/RDCC/
RDDB/RDDC)
Air Proving Switch
Power Supply
Ignition
Board
(RDCB/RDCC/
RDDB/RDDC)
Relay or Sequencer (RDCB/RDCC/ RDDB/RDDC)
Control
Expander
Option BHB6
Dirty Filter Switch or Differential Pressure Gauge
Low Voltage Panel - Cabinet C
Optional Control Block(s)
FIGURE 1 - Showing Access (panels removed) and High and Low Voltage Control Locations (including control options)
Condenser Section
Compressors
Tubing Access
Heat Section
(Gas illustrated)
High Voltage Panels
Cabinets A & B
Digital Controller
- MAPS IV only
Control
Transformers
Contactor,
Condenser Fan
Contactor,
Compressor A
Fuse & Fuse
Holder
Contactor,
Compressor B Contactor, Compressor C (below “B”, behind the transformer)
Cabinet C
Contactor,
Compressor B
Optional
Transformer
Control
Transformers
Digital Controller
- MAPS IV only
Fuse & Fuse
Holder
Contactor, Compressor DH
Phase Monitor or Motor Saver
Dampers
Blower Section with Bottom Discharge
Two Low Voltage Panels ­A&B Cabinets (top right)
or Low Voltage Panel -
C Cabinet (bottom right)
Phase Monitor or Motor Saver
Distribution Blocks
Grounding Lug
Contactor or Starter and Overload, Blower Motor
Contactor, Compressor DH
Optional Transformer
Contactor, Compressor A
Contactor, Condenser Fan
Contactor, Compressor C
Contactor or Starter and Overload, Blower Motor Distribution Blocks Grounding Lug
Optional Transformer
Slide-out Filter Rack
Reheat
Compressor
Evaporator Coil Section (with slide out drain pan)
Primary Low Voltage Layout - Cabinets A & B
Controller
Display
(BacView)
IQ
Controller
Optional
Plugin Card
Optional
Differential
Pressure
Switch
Combustion
Air Proving
Switch
(RDCB/RDCC/
RDDB/RDDC)
Air Proving
Switch
Venter Motor
Capacitor
(RDCB/RDCC/
RDDB/RDDC)
Secondary Low Voltage Layout -
Cabinets A & B
Optional
Control
Expander
Optional
Reheat
Board
Sequencer (RDCB/RDCC/ RDDB/RDDC)
Ignition Board (RDCB/RDCC/ RDDB/RDDC)
Optional Control Block(s)
Power Supply
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 5
2.0 Maintenance Requirements (cont'd)
2.3 Cross-Reference of Models and Cabinet Sizes A, B, and C
DX Cooling Models RCB and RCC and DX with Reheat Models RDB and RDC
Model
Model
RCB
RCC
060
078 --
090
118 120
136 --
160
186 --
200
190
216 --
298
410
Model
Model
RDB
RDC
084
102 --
114
142 144
162 --
184
-- 196
210 --
222 --
224 --
236
-- 257
248
262
272 --
288 --
354
370
468
482
3.0 Maintenance and Service Procedures
Cabinet Size A B C
Model Sizes 060/078/084/102 090/114/11//120/136/142/144/162 All Cabinet B All Cabinet C
Filter Description Opt Qty Size P/N Qty Size P/N Qty Size P/N Qty Size P/N
2” Pleated Disposable AW 11 1 20x25x2 104113
4” Pleated Disposable, MERV 8
4” Pleated Disposable, MERV 13
2” Permanent Aluminum AW9 1 20x25x2 101623
4” Permanent Aluminum AW20 2 20x25x2 101623
Model RDCB, RDDB, RDCC, and RDDC by Cabinet Size and Gas Heat Section Size
Model
Model
RDCB
RDCC
-100 -150 -200 -250 -300 -400 -500 -600 -700 -800 -1000
060
Cabinet
Cabinet
078 --
Size
118 120
136 --
186 --
A
216 --
B
Model
RDDB
C
102 --
142 144
Size
162 --
-- 196
A
210 -­222 --
224 --
-- 257
B
272 -­288 --
* A MAPS® B Cabinet with 500 mbh of gas heat is a Size 250 mbh heat section plus an Option JH25 curb with a 250 mbh
C
duct furnace.
A A A -- -- -- -- -- -- -- --
A A A B B B* -- -- -- --
090
A A A B B B* -- -- -- --
A A A B B B* -- -- -- --
A A A B B B* -- -- -- --
160
-- -- -- B B B* -- -- -- --
-- -- -- B B B* -- -- -- --
200
-- -- -- B B B* -- -- -- --
190
-- -- -- -- -- C C C C -- C**
-- -- -- -- -- C C C C -- C**
298
-- -- -- -- -- C C C C -- C**
410
-- -- -- -- -- C C C C -- C**
Model
RDDC
-100 -150 -200 -250 -300 -400 -500 -600 -700 -800 -1000
084
A A A -- -- -- -- -- -- -- -­A A A B B -- -- -- -- -- --
114
A A A B B -- -- -- -- -- --
A A A B B -- -- -- -- -- --
-- A A B B -- -- -- -- -- --
184
-- -- -- B B -- -- -- -- -- --
-- -- -- B B -- -- -- -- -- --
-- -- -- B B -- -- -- -- -- --
-- -- -- B B -- -- -- -- -- --
-- -- -- B B -- -- -- -- -- --
236
-- -- -- B B -- -- -- -- -- --
-- -- -- B B -- -- -- -- -- --
248
-- -- -- -- -- C C C C -- C**
262
-- -- -- -- -- C C C C -- C**
-- -- -- -- -- C C C C -- C**
-- -- -- -- -- C C C C -- C**
354
-- -- -- -- -- C C C C -- C**
370
-- -- -- -- -- C C C C -- C**
468
-- -- -- -- -- C C C C -- C**
482
-- -- -- -- -- C C C C -- C**
Gas Heat Section Size
Gas Heat Section Size
Model RECB, REDB, RECC, and REDC by Electric Heat Module and Cabinet Size
Model RECB
060
078 --
090 118 120 136 --
160 186 --
200
190 216 --
298
410
Model REDB
084 102 --
114 142 144 162 --
184
-- 196 210 -­222 -­224 --
236
-- 257
248
262 272 -­288 --
354
370
468
482
Model RECC
-10S -15S -20S -24S -15 -20 -25 -30 -35 -39 -50 -60 -75 -88 A A A A A A A A A A -- -- -- --
-- A A A A B A A B A B B B --
-- A A A A B A A B A B B B B
-- A A A A B A A B A B B B B
-- A A A A B A A B A B B B B
-- -- -- -- B B B B B B B B B B
-- -- -- -- B B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
Model REDC
-10S -15S -20S -24S -15 -20 -25 -30 -35 -39 -50 -60 -75 -88 A A A A A B A A B A B B B --
-- A A A A B A A B A B B B B
-- A A A A B A A B A B B B B
-- A A A A B A A B A B B B B
-- -- -- -- A B A A B A B B B B
-- -- -- -- B B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- B B B B B B B B B
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
-- -- -- -- -- -- -- -- -- C C C C C
Electric Heat Section
Electric Heat Section
** A MAPS® C Cabinet with 1000 mbh of gas heat is a Size 700 mbh heat section plus an Option JH30 curb with a 300 mbh duct furnace.
3.1 Filters
The lter section is equipped with a slide out lter rack and 2 or 4 inch, pleated dispos­able or permanent aluminum lters. To remove lters, open the door and slide lters out. Replacement lters are listed in the table below. Do not use any other type of lters.
AW21 1 20x25x4 205791
AW24 1 20x25x4 256663
If equipped with permanent aluminum lters, remove the lters, wash, rinse, allow to
dry, and slide them back in the cabinet.
If equipped with pleated disposable lters, replace dirty lters. Exposure to humid makeup air can accelerate lter degradation. Systems with disposable lters require more frequent lter inspection.
2 16x20x2 104110 2 20x20x2 104111 2 16x20x4 211127 2 20x20x4 205790 2 16x20x4 256665 2 20x20x4 256662 2 16x20x2 101620 2 20x20x2 101621 4 16x20x2 101620 4 20x20x2 101621
4 20x25x2 104113 6 20x25x2 104113
4 20x25x4 205791 6 20x25x4 205791
4 20x25x4 256663 6 20x25x4 256663
4 20x25x4 101623 6 20x25x2 101623
8 20x25x2 101623 12 20x25x2 101623
Dirty Filter Switch (Options BE16 and BE18)
If equipped with a dirty lter switch or gauge, check the condition of the sensing tubes
to be sure that they are not blocked. Check the wiring connections. To set a new switch (Option BE18), see Installation Form I-MAPSIII&IV, Paragraph 8.3, Replacement switch is P/N 105507.
Form O-MAPSIII&IV Cabinets A/B/C, Page 6
Filter
Clamp
Filter
Filter
Wing Screw,
P/N 205707,
and Retainer,
P/N 205709
(2 each)
Filter
Filter
Filter Clamps attach with Wing Screws P/N 205707
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Filter
16x25x1
Filter
16x25x1
Filter
16x25x1
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Inlet View
  
 
   
Permanent Filters in the Outside Air Hood
If equipped with an outside air hood, there are 1" permanent, aluminum lters at the entrance of the hood. The lters act as a moisture eliminator and bird screen. See FIG- URE 2A or 2B. When inspecting the inlet air lters, inspect the outside air hood lters. If cleaning is needed, remove the lters, clean, rinse, dry and re-install.
NOTE: If it is more convenient to keep an extra clean set of lters, lter sizes and part numbers are shown in the illustration.
FIGURE 2A - Removing Filters from Outside Air Hood
1" Permanent Aluminum Filters for Outside Air
Cabinet Sizes A and B with Option AS16 Outside Air Hood
(Does not apply if system includes Option PE power exhaust; see below.)
All Cabinet Size C with either Outside Air Hood Option AS16 or AS19
Hood are listed by Cabinet Size A, B, or C (see cross-reference, page 6)
*A - (4) 16 x 20, P/N 101607 *B - (4) 16 x 25, P/N 101609
C - (3) 16 x 25, P/N 101609;
(6) 16 x 20, P/N 101607
* Apply only to Cabinet Size A and B with outside
air hood Option AS16
.
Instructions: Remove lters by loosening the wing screws and sliding the lter
clamp(s). Clean with soap and water, allow to dry, and replace. If it is more convenient
to keep an extra clean set of lters, quantities, lter sizes, and part numbers are listed.
FIGURE 2B - Removing Filters from Option AS19 Outside Air Hood Installed on a Cabinet Size A or B with power exhaust Option PE1 or PE2
Instructions: 1) Remove the four screws as illustrated. Lower the tray.; 2) Pull out lters. Clean with soap and water. Allow to dry.; 3) Slide clean dry lters into tray.;
4) Re-position tray and replace screws. 1" Aluminum Filters: **A - (4) 18 x 20, P/N 194903; **B - (4) 20 x 25, P/N 101610
** Apply only to Cabinet Size A and B with outside air hood Option AS19.
Filters in an Optional Energy Recovery Module
*See cross-reference of MAPS® Models by Cabinet Size A, B, or C on page 6.
3.2 Drive Components
CAUTION: If the blower is unused for more than three months, bearings
with a grease tting
should be purged with new grease
prior to startup.
If equipped with an energy recovery module (Option ER1A, ER1B, or ER1C), check
both inlet and exhaust lters. Replace as needed.
Cabinet
Size *
A Pleated 20x25x2 2 104113 Pleated 20x25x2 2 104113
B
C
Inlet Air Filters (Merv 8) Exhaust Air Filters (Merv 8)
Filter Type & Size Qty P/N Filter Type & Size Qty P/N
Pleated 16x25x2 2 104112 Pleated 16x25x2 2 104112 Pleated 12x25x2 2 114320 Pleated 12x25x2 2 114320 Pleated 16x25x2 2 104112 Pleated 16x25x2 2 104112 Pleated 20x25x2 2 104113 Pleated 20x25x2 2 104113 Pleated 16x16x2 1 104109 Pleated 16x16x2 1 104109 Pleated 16x20x2 1 104110 Pleated 16x20x2 1 104110
Bearings - Bearings with a grease tting should be lubricated twice a year with a high
temperature, moisture-resistant grease. (Type NLGI-1 or -2 standard grease is recom-
mended.) Be sure to clean the grease tting before adding grease. Add grease with a
handgun until a slight bead of grease forms at the seal. Be careful not to unseat the seal by over lubricating. NOTE: If unusual environmental conditions exist (tempera­tures below 32°F or above 200°F; moisture; or contaminants), more frequent lubrica­tion is required.
Setscrews - Check all of the setscrews (bearing/blower hubs and pulleys). Torque pul­ley setscrews a minimum of 110 in-lb to 130 in-lb maximum.
A bearing hub setscrew for a 1-3/8" to 1-3/4" shaft requires a 5/16" socket and a tight­ening torque of 165 in-lbs.
Belts - Check belt for proper tension and wear. If needed, follow instructions to adjust belt tension. Replace worn belts.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 7
2-1/2” (63.5mm)
Fan and Motor Assembly showing Fan Blade Position
Cross-section of Installed Fan and Motor Assembly showing Cabinet Top
1.76” (44.7mm)
Top of Fan Blade
to Top of the
Cabinet Top Panel
Fan rotation is clockwise.
3.0 Maintenance and Service Procedures (cont'd)
3.2 Drive Components Cont'd)
Belts (cont'd) - Blower systems are equipped with either Power Twist Plus
blower belt or a solid belt. The linked belts are designed in sections allowing for easy sizing and adjustment. The belt is sized at the factory for the proper tension. If the belt needs adjustment, the recommended method of shortening the belt length is to count the number of links and remove one link for every 24. (A link is made up of two joining sections of belt. For easier removal of links, turn the belt inside out. But be sure to turn it back before installing.)
If equipped with a solid belt, adjust the belt tension by turning the adjusting screw on the motor base until the belt can be depressed 1/2" (13mm) on each side. After correct tension is achieved, re-tighten the locknut on the adjustment screw.
Proper belt tension is important to the long life of the belt and motor. Be sure belts are aligned in the pulleys. If a belt is removed or replaced, be sure the
directional arrows on the belt match the drive rotation. Motor and Blower - Inspect the motor mounts periodically. Remove dust and dirt accu-
mulation from the motor and wheel. The blower has cast iron, pillowblock, sealed bearings. Under most operating condi-
tions, re-lubrication is unnecessary. If lubrication is required, use a lubricant compat­ible to Shell Alvania #2 (lithium base - Grade 2). Operating temperature range is -30 to 230°F.
If any drive parts need to be replaced, use only factory-authorized replacements designed for the application.
®
linked
3.3 Condenser Fans
FIGURE 3 - Condenser Fan Assembly Dimensions and Rotation
3.4 Coil Maintenance
Condenser Coil Cleaning Instructions:
Form O-MAPSIII&IV Cabinets A/B/C, Page 8
Depending on the size, there are two, three, or four fans in the condenser section. If parts need to be replaced, use only factory authorized replacement parts. See FIGURE 3 for assembled dimensions and proper fan rotation.
The MAPS® cooling system is equipped with space-saving MACROCHANNEL Inspect all cooling system coils at the beginning of the cooling season or more often if needed. Follow the cleaning instructions below. If additional cleaning is required or if a coil must be removed for any reason, consult the factory. Be prepared to provide rating
plate and specic installation information.
Condensing Coil Access - The condensing coils are visible on the side of the unit (below the condenser fans). For additional access for inspection and maintenance, remove the tubing access panel (See FIGURE 1, page 5.).
1. Verify that the electrical power has been turned off and the disconnect switch locked.
2. Use a soft brush to remove any dirt and debris from the coils.
3. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based coil
4. When clean, rinse with cool, clean water.
Evaporator Coil Access - The evaporative coils can be accessed by opening the coil cabinet door.
Inspect coils for debris, dirt, grease, lint, pollen, mold, or any element which would
obstruct heat transfer or airow. Inspect coils and tubing for physical damage. Inspect
®
coils.
cleaner is recommended). Due to possible damage to the coil, DO NOT use high pressure spray.
feeders, piping connections, coil headers, and return bends for signs of fatigue, rub­bing, and physical damage.
Clean the coils annually, or more often if needed. Use the proper tools and follow the instructions carefully to avoid damaging the coil. Use of a non-acid based coil cleaner is recommended. Due to possible damage to the coil, DO NOT use high pressure spray.
Evaporator Coil Cleaning Instructions:
3.5 Check Refrigerant Pressure and Temperatures (subcooling and superheat)
1. Verify that the electrical power has been turned off and the disconnect switch locked.
2. Open the access panels.
3. Use a soft brush to remove any dirt and debris from both sides of a coil.
4. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based coil cleaner is recommended). Due to possible damage to the coil, DO NOT use
high pressure spray. First spray the leaving airow side, then the inlet airow side.
As much as possible, spray the solution perpendicular to the face of the coil. Follow the instructions on the cleaning solution. When cleaning process is
complete, rinse both sides with cool, clean water.
DANGER
These refrigeration circuits are high pressure systems. Hazards exist that could result in personal injury or death. Removal, installation, and service of this scroll compressor
must be performed by a technician qualied in R-410A
refrigerant. DO NOT USE service equipment or tools designed for R22 refrigerant. See Hazard Levels, page 3.
Two important requirements before checking superheat and subcooling:
1) This unit has fully intertwined refrigerant circuits and each circuit MUST be isolated before measuring its
temperature. Another active circuit will inuence the reading and make it impossible to determine accurate superheat
and subcooling.
2) If the circuit is equipped with an optional hot gas bypass valve, the valve must be disabled before measuring superheat and subcooling. Method of disabling depends on the model and date of manufacture.
All MAPS®IV Models & any MAPS®III Models with a shutoff valve in the line between the compressor discharge and the hot gas bypass valve - Locate the shutoff valve. Disable the hot gas bypass valve by closing the shutoff valve. When measurements are complete, be sure to open the valve.
MAPS®III Models without a shutoff valve in the line between the compressor discharge and the hot gas bypass valve
- Disable the hot gas bypass valve by removing the cover and adjusting the spring tension counterclockwise until the spring tension is relieved. Count and record the number of turns required so that you can return the bypass valve to its original setting. To check setting, refer to Paragraph 3.9.5.
Check SUBCOOLING
Measure and record temperature and pressure of the liquid line at the condenser coil outlet.
STEP 1) Record Measurements: Temperature = ________°F (°C) and Pressure = ________ psig
STEP 2) From Temperature/Pressure Conversion Chart (page 10), convert Measured Pressure (STEP 1) to
________°F (°C)
STEP 3) Subtract Measured Temperature (STEP 1) from Temperature from Conversion Chart (STEP 2)
________°F (°C) - ________°F (°C) = ________°F (°C) degrees of Subcooling
Recommended subcooling with outdoor temperature range of 70 to 95°F (21 to 35°C)
is 10 to 12 degrees F (5.6 to 6.7 degrees C).
Too much subcooling indicates a refrigerant overcharge. To reduce the subcooling, remove excess refriger-
ant. Too little subcooling indicates a refrigerant undercharge. To increase subcooling, slowly add R-410A refrigerant.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 9
3.0 Maintenance and Service Procedures (cont'd)
3.5 Check Refrigerant Pressure and Temperatures (cont'd)
WARNING
Do not release refrigerant to the atmosphere. When adding or
removing refrigerant, the qualied technician must comply
with all national, state/province, and local laws.
Determine SUPERHEAT
Measure and record temperature (insulate probe from surrounding air temperature) and pressure in the suction line at the compressor inlet.
STEP 1) Record Measurements: Temperature = _______°F (°C) and
Pressure = _______ psig
STEP 2) From Temperature/Pressure Conversion Chart (below), convert
Measured Pressure (STEP 1) to ________°F (°C)
STEP 3) Subtract Measured Temperature (STEP 1) from Temperature from
Conversion Table (STEP 2)
________°F (°C) - ________°F (°C) = ________°F (°C) degrees of
Superheat
Recommended superheat range is 8 to 12 degrees F (4.5 to 6.7 degrees C).
Typically, too much superheat indicates that the evaporator coil is undercharged. Too little superheat typically indicates that the evaporator coil is overcharged and
may potentially ood liquid refrigerant to the compressor. To reduce the superheat,
adjust the thermal expansion valve by turning the adjusting stem counterclock­wise. To increase the superheat, adjust the thermal expansion valve by turning the adjusting stem clockwise.
Temperature/Pressure Conversion Chart
R-410A Refrigerant R-410A Refrigerant R-410A Refrigerant R-410A Refrigerant R-410A Refrigerant
Pressure Temperature Pressure Temperature Pressure Temperature Pressure Temperature Pressure Temperature
PSI °F °C PSI °F °C PSI °F °C PSI °F °C PSI °F °C
1.8 -55 -48.3 49.5 1 -17.2 77.0 19 -7.2 112.2 37 2.8 218.2 75 23.9
4.3 -50 -45.6 50.9 2 -16.7 78.7 20 -6.7 114.4 38 3.3 235.9 80 26.7
7.0 -45 -42.8 52.2 3 -16.1 80.5 21 -6.1 116.7 39 3.9 254.6 85 29.4
10.1 -40 -40.0 53.6 4 -15.6 82.3 22 -5.6 118.9 40 4.4 274.3 90 32.2
13.5 -35 -37.2 55.0 5 -15.0 84.1 23 -5.0 121.2 41 5.0 295.0 95 35.0
17.2 -30 -34.4 56.4 6 -14.4 85.9 24 -4.4 123.6 42 5.6 316.9 100 37.8
21.4 -25 -31.7 57.9 7 -13.9 87.8 25 -3.9 125.9 43 6.1 339.9 105 40.6
25.9 -20 -28.9 59.3 8 -13.3 89.7 26 -3.3 128.3 44 6.7 364.1 11 0 43.3
27.8 -18 -27.8 60.8 9 -12.8 91.6 27 -2.8 130.7 45 7.2 389.6 11 5 46.1
29.7 -16 -26.7 62.3 10 -12.2 93.5 28 -2.2 133.2 46 7.8 416.4 120 48.9
31.8 -14 -25.6 63.9 11 -11.7 95.5 29 -1.7 135.6 47 8.3 444.5 125 51.7
33.9 -12 -24.4 65.4 12 -11.1 97.5 30 -1.1 138.2 48 8.9 474.0 130 54.4
36.1 -10 -23.3 67.0 13 -10.6 99.5 31 -0.6 140.7 49 9.4 505.0 135 57.2
38.4 -8 -22.2 68.6 14 -10.0 101.6 32 0.0 143.3 50 10.0 537.6 140 60.0
40.7 -6 -21.1 70.2 15 -9.4 103.6 33 0.6 156.6 55 12.8 571.7 145 62.8
43.1 -4 -20.0 71.9 16 -8.9 105.7 34 1.1 170.7 60 15.6 607.6 150 65.6
45.6 -2 -18.9 73.5 17 -8.3 107.9 35 1.7 185.7 65 18.3 645.2 155 68.3
48.2 0 -17.8 75.2 18 -7.8 110.0 36 2.2 201.5 70 21.1
Form O-MAPSIII&IV Cabinets A/B/C, Page 10
3.6 Compressor
Compressor B
Compressor C
Compressor A
Compressor
Dh (Reheat)
Operation, Maintenance, and Replacement
DANGER
The refrigeration circuits are high pressure systems. Hazards exist that could result in personal injury or death. It is therefore required that the removal and installation of this
scroll compressor be performed by a technician qualied in
R-410A refrigerant. See Hazard Levels, page 3.
DANGER
Never use oxygen to pressurize a refrigeration system. Oxygen can explode on contact with oil and could result in personal injury or death. When using high pressure gas such as nitrogen for this purpose, ALWAYS USE A PRESSURE REGULATOR that can control the pressure down to 1 or 2 psig. Failure to use a regulator will result in extremely high pressure which could exceed the burst pressure of the compressor or other system components and result in personal injury or death. See Hazard Levels, page 3.
WARNINGS
For your safety, wear eye protection, gloves, and protective clothing when handling refrigerant and oil and when brazing.
Have a re extinguisher nearby. See Hazard Levels, page 3.
Compressor Staging (Cooling) - applies to all MAPS®III Models
Each MAPS®III system leaves the factory with the compressor staging sequence shown here for that Model and Size. The compressor will start based upon a call for cooling to maintain the discharge air temperature setpoint. There is a minimum 240 second ON and OFF time for each stage (not compressor).
FIGURE 4 - Identication of
Compressors by Circuit and Staging for MAPS®III Models
Cabinet
Size
A
A or B
B
C
Cooling
Size
(RCB)
060 078 090
118
136
160 184 B A A+B A+B+C --
186
200
190
216
298
410
Cooling/
Reheat Size
(RDB)
084 B A A+B -- -­102 B A A+B -- -­114 B A A+B -- -­142 B A A+B -- -­162 B A A+B -- --
210 A B A+C A+B A+B+C 222 A B A+C A+B A+B+C 224 A B A+B B+C A+B+C 236 A B A+B B+C A+B+C 248 A B A+B -- -­262 A B A+B -- -­272 B B+C A+B+C -- -­288 B B+C A+B+C -- -­354 B A+B B+C A+B+C -­370 B A+B B+C A+B+C -­468 B A+B A+B+C -- -­482 B A+B A+B+C -- --
Cooling Staging by Compressor
Circuit
1st 2nd 3rd 4th 5th
Compressor
NOTE: Staging listed by cooling only Models RCB/RDB also
applies to Models RDCB /RDDB with gas heat and Models RECB/ REDB with electric heat.
Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 11
3.0 Maintenance/Service Procedures (cont'd)
Alarm Light (Red LED) - See Paragraph 7.2.
Compressor Modualting Solenoid Valve Energized Light (Yellow LED)
Power Light (Green LED)
3.6 Compressor Operation, Maintenance, and Replacement (cont'd)
Compressors and Crankcase Heater P/N's by Voltage on MAPS®III Models
208-240/3/60 480/3/60 575/3/60
Compressor
Model P/N Model P/N Model P/N
ZP24K5E 235095 216434 ZP24K5E 235097 216436 ZP24K5E 235099 216437 ZP36K5E 235096 216398 ZP36K5E 235098 216400 ZP36K5E 235100 216401 ZP54K5E 235008 216398 ZP54K5E 235012 216400 ZP54K5E 235016 216401 ZP57K3E 216686 216398 ZP57K3E 216687 216400 ZP57K3E 216688 216401 ZP72KCE 235009 216398 ZP72KCE 235013 216400 ZP72KCE 235018 216401 ZP83KCE 216689 216398 ZP83KCE 216690 216400 ZP83KCE 216691 216401 ZP137KCE 235010 216398 ZP137KCE 235014 216404 ZP137KCE 235019 216405 ZPT144KCE 235011 216398 ZPT144KCE 235015 216400 ZPT144KCE 235020 216401 ZP154KCE 220260 216402 ZP154KCE 220261 216404 ZP154KCE 220262 216405
Crankcase Heater P/N
Compressor
Crankcase Heater P/N
Compressor
Crankcase Heater P/N
Modulating Cooling -
®
MAPS
IV Models
MAPS®IV units are equipped with a modulating capacity compressor and a digital con-
troller to provide cooling modulation. The digital controller in the control compartment (See FIGURE 1, page 5) is the electronic interface between the compressor and the
NOTE: To identify MAPS®IV Models, see Paragraph 1.0.
system controller. The compressor controller is connected to the unit controller to pro­vide protection and diagnostics for modulating compressor operation.
After a compressor shutdown, a two-minute anti-short cycle timer in the compressor
controller delays the compressor restart. The unit controller has a ve-minute compres­sor on/off time. The delay times are concurrent so total delay time is ve minutes.
FIGURE 5 - Compressor Digital Controller located in the control compartment interfaces the modulating capacity compressor with the unit controller.
LED Color
Green Solid
Green Flashing Anti-short cycle timer is active
Yellow Solid
Red Not lit No abnormal operation alerts
NOTE: See Troubleshooting, Paragraph 7.2.
LED State
Indicates
Power (24VAC present at power terminals)
Unloader (Solenoid valve is
energized; compressor capacity is 0.)
Compressor and Crankcase Heater P/N's by Voltage on MAPS®IV Models
208-240/3/60 480/3/60 575/3/60
Compressor
Model P/N Model P/N Model P/N
ZP24K5E 235095 216434 ZP24K5E 235097 216436 ZP24K5E 235099 216437 ZP36K5E 235096 216394 ZP36K5E 235098 216396 ZP36K5E 235100 216397 ZP54K5E 235008 216394 ZP54K5E 235012 216396 ZP54K5E 235016 216397 ZP57K3E 216686 216398 ZP57K3E 216687 216400 ZP57K3E 216688 216401 ZP61KCE 261235 216398 ZP61KCE 261236 216400 ZP72KCE 235018 216401 *ZPD61KCE 261145 216398 *ZPD61KCE 261146 216400 ZP83KCE 216691 216401 ZP72KCE 235009 216398 ZP72KCE 235013 216400 *ZPD83KCE 261149 216401 ZP83KCE 216689 216398 ZP83KCE 216690 216400 ZP137KCE 235019 216405 *ZPD83KCE 261147 216398 *ZPD83KCE 261148 216400 *ZPD137KCE 261155 216405 ZP137KCE 235010 216402 ZP137KCE 235014 216404 *ZPD61KCE 268531 216401 *ZPD137KCE 261153 216402 *ZPD137KCE 261154 216404 ZP61KCE 268532 216401 ZP154KCE 220260 216402 ZP154KCE 220261 216404 *ZPDT14MCE 268533 216401 *ZPDT14MCE 262656 (2)216398 *ZPDT14MCE 262657 (2)216400 * Modulating capacity compressor
Form O-MAPSIII&IV Cabinets A/B/C, Page 12
Crankcase Heater P/N
Compressor
Crankcase Heater P/N
Compressor
Crankcase Heater P/N
Loading...
+ 28 hidden pages