Reznor MASA Unit User Manual

Form I-COND (Version C.2)
Obsoletes I-COND (Version C.1)
Installation/Operation/Maintenance
Applies to: Model MASA
Air Cooled Condensing Unit
Designed for Reznor Split Systems
P
R
O
Y
C
C
N
E
G
O
A
C
C
U
S
T
O
M
CQS
E
Q
R
U
A
P
R
O
D
U
E
S
R
E
G
V
N
L
I
T
C
S
E
N
T
P
U
-
T
R
A
T
S
M
Y
E
T
T
S
N
Y
Y
S
A
R
R
A
T
W
R-410A
Refrigerant
Only
IMPORTANT: Check, Test, and Startup MUST be followed, as documented in this manual.
A completed Condenser Startup Form (page 38) may be required for validation of any warranty claims.
The factory reserves the right to deny warranty without completed Condenser Startup Form.
This booklet includes operation, maintenance, and service information. Before beginning any procedure, carefully review the information, paying particular attention to the warnings. All installation procedures including handling of
refrigerant must be in compliance with all codes and requirements of authorities having jurisdiction.
Installer should complete information on page 40.
Condenser Startup Form on page 38 should be completed on initial startup.
Owner should keep this booklet for future reference.
Form I-COND, P/N 220746R6, Page 1
Table of Contents
1.0 General ..........................3
1.1 Hazard Labels and Notices ............3
1.2 General Information ..................4
1.3 Warranty ..........................4
1.4 Installation Codes ....................4
2.0 Location .........................5
3.0 Receiving, Moving, and Uncrating ....5
3.1 Receiving ..........................5
3.2 Moving ............................5
3.3 Uncrating ..........................5
3.3.1 Shipped-Separate Items ...........5
4.0 Clearances and Dimensions .........5
4.1 Clearances .........................5
4.2 Dimensions .........................6
5.0 Mounting .........................7
5.1 Weights............................7
5.2 Lifting .............................7
5.3 Mounting ..........................7
6.0 Mechanical .......................7
6.1 Refrigerant Piping ....................7
6.1.1 Location of Piping Connections at
the Condensing Unit ..............7
6.1.2 Location of Piping Connections at
the Split System Evaporator Coil.....8
6.1.3 Refrigerant Piping Guidelines
(R-410A Refrigerant) ............11
6.1.3.1 Type of Refrigerant Piping .....11
6.1.3.2 Refrigerant Piping Length
and Size ......................11
6.1.3.3 Liquid Line Piping ............13
6.1.3.4 Suction Line ................15
6.1.3.5 Optional Hot Gas Bypass Lines .15
6.1.3.6 Brazing Connections .........16
6.1.3.7 Piping Support and Insulation ...16
6.2 Leak Test the Refrigerant Circuits.......16
6.2.1 Leak Test the Condensing Unit ....16
6.2.2 Leak Test the Field-Installed Piping..17
6.3 Evacuate the Circuits ................17
6.4 Charge with R-410A Refrigerant .......17
7.0 Electrical and Wiring ..............18
7.1 General ...........................18
7.1.1 Wiring Diagram . . . . . . . . . . . . . . . . .18
7.2 Supply Wiring ......................18
7.2.1 Disconnect Switch...............18
7.2.2 Supply Voltage .................18
7.3 Unit Wiring Requirements ............19
7.4 Control Wiring ......................21
8.0 Controls and Operation ............21
8.1 Analog Control System ...............21
8.2 Digital Control System ...............21
8.3 Other Compressor and Refrigerant
Controls .........................22
8.3.1 High Pressure Cutoff .............22
8.3.2 Low Pressure Cutoff .............22
8.3.3 Hot Gas Bypass Valve (Option
CUG2 or CUG3) ................22
8.3.4 Compressor Protection (CUB1).....22
8.3.5 Crankcase Heaters ..............22
9.0 Final Checks and Start-Up.......... 23
9.1 General Comments ..................23
9.1.1 Checklist Prior to Start-up .........23
9.2 Start-up ...........................24
9.2.1 Power Supply Voltage Phasing .....24
9.2.2 Operating Sequence .............24
9.2.3 Refrigerant Charge ..............25
9.2.3.1 Check SUBCOOLING ........25
9.2.3.2 Determine SUPERHEAT .......25
9.2.4 Optional Hot Gas Bypass Valve ....26
10.0 Maintenance and Service..........26
10.1 General ..........................26
10.2 Maintenance Schedule ..............27
10.3 Condenser Fan(s) Maintenance .......27
10.4 Condenser Coil Maintenance .........28
10.5 Compressor Maintenance and
Replacement .....................28
10.6 Troubleshooting Chart...............34
APPENDIX
IMPORTANT Reminders about R-410A
Refrigerant and POE Oil ............36
Model MASA Technical Information ........36
Electrical Information....................37
Pressure/Temperature Chart for R-410A
Refrigerant for Checking Subcooling
and Superheat ....................37
CONDENSER STARTUP FORM ..........38
INDEX ..........................39
INSTALLATION RECORD - to be
completed by the installer .........40
Form I-COND, P/N 220746R6, Page 2
1.0 General
1.1 Hazard Labels and Notices
There are warning labels on the condensing unit and throughout this manual.
For your safety, read the denitions below and comply with all boxes labeled
CAUTION, WARNING, and DANGER during installation, operation, mainte­nance, and service of this system.
Denitions of Hazard Intensity Levels in this Manual
HAZARD INTENSITY LEVELS
DANGER: Failure to comply will result in severe personal injury
or death and/or property damage.
WARNING: Failure to comply could result in severe personal
injury or death and/or property damage.
CAUTION: Failure to comply could result in minor personal
injury and/or property damage.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or
death. A qualied installer or service agency must perform
installation and service.
DANGER
This condensing unit is designed to use R-410A high pressure refrigerant only. Hazards exist that could result in personal injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-
410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for R22 refrigerant.
DANGER
Never use oxygen to pressurize a refrigeration system. Oxygen can explode on contact with oil and result in personal injury or death. When using high pressure gas such as nitrogen for pressurizing a refrigeration system, ALWAYS USE A PRESSURE REGULATOR that can control the pressure down to 1 or 2 psig.
SAFETY WARNINGS
For your safety, wear eye protection, gloves, and protective clothing when handling R-410A refrigerant or POE oil
and when brazing. Have a re extinguisher nearby when
brazing.
Form I-COND, P/N 220746R6, Page 3
1.0 General (cont’d)
1.1 Hazard Labels and Notices (cont’d)
WARNING
Before installing or servicing, always turn off the main power to the system and install a lock out on the disconnect switch.
CAUTION
Do not leave system open to the atmosphere any longer than minimum required for installation. Exposure for more than
ve minutes may contaminate the system. POE oil in the
compressors is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
1.2 General Information
This booklet includes operation, maintenance, and service information. Before beginning any procedure, carefully review the information, paying particular attention to the warnings. All installations must be in compliance with all codes and requirements of authorities having jurisdiction.
A Model MASA outdoor condensing unit operates on R-410A refrigerant and
has two independent refrigeration circuits congured in an approximate 1/3-
2/3 arrangement. The Model MASA condensing unit is designed for use with a Reznor PreevA indoor Models are PDH or SDH; outdoor Model is RDH. The Model MASA con­densing unit may also be matched to a eld-supplied 1/3-2/3 two-circuit evapo­rator coil. An air handler used with a Model MASA condensing unit must be properly matched; the evaporator coil must have freeze protection and must
be equipped with properly sized thermostatic expansion valves.
®
air handler unit with a 1/3-2/3 two-circuit cooling coil. PreevA®
Form I-COND, P/N 220746R6, Page 4
CAUTION
The condensing unit must be matched to an approximate 1/3-2/3 two-circuit, R-410A refrigerant evaporator coil with properly sized thermostatic expansion valves. Failure to properly match and/or equip the split system components will prevent the system from operating correctly and will void the manufacturer’s warranty. See Hazard Levels, page 3.
1.3 Warranty
Refer to limited warranty information on the Warranty Form in the “Literature Bag” shipped with this system.
A completed Condenser Startup Form on page 39 may be required for valida­tion of any warranty claim. Proper Check, Test, and Startup procedures MUST be followed, as documented in this manual. The factory reserves the right to deny warranty without a completed Condenser Startup Form.
1.4 Installation Codes
All installations must be in compliance with the National Electric Code ANSI/ NFPA No. 70 (latest edition) or, in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C 22.l. Check any local ordinances or utility company requirements that apply. The installation must be in compliance with all authori­ties having jurisdiction. Local code requirements supersede national require­ments.
Coil Side
(Inlet airflow through
the condenser coil
must be unrestricted.)
Control Side
(Service
Clearance)
Opposite
Control
Side
Electrical Entrance Side
NOTE: Suggested side for installing disconnect switch; see FIGURE 2, page 6. If disconnect switch is installed on this side, minimum clearance is 36” (914mm).
Airflow
Top discharge airflow must be unrestricted.
Top clearance is 60” (1524mm).
36”
(914mm)
6”
(152mm)
6” (152mm)
48”
(1219mm)
Top
View
2.0 Location
Model MASA condensing unit must be mounted outdoors on a level surface. The supporting structure must be able to support the operating weight of the unit and maintain a level plane during continued operation. Water should drain away from the unit. Location must comply with free space clearances for unre-
stricted airow (See Paragraph 4.1) and the refrigerant piping requirements
(See Paragraph 6.1.3). Avoid facing condenser coils into the prevailing wind.
3.0 Receiving, Moving, and Uncrating
3.1 Receiving
Check for any damage that may have been incurred during shipment. If dam­age is found, document the damage with the transporting agency and immedi­ately contact your Reznor distributor. If you are an authorized Distributor, follow the FOB freight policy procedures as published by Reznor for Reznor products.
3.2 Moving
The heavy gauge base of the condensing unit has forklift openings in both sides. To move a unit, use a forklift with forks that have a minimum length of 24” (610mm).
3.3 Uncrating
Immediately upon uncrating, check the electrical characteristics to verify that the unit is suitable for the installation site. This condensing unit is designed for R-410A refrigerant only; verify that the split system air handler is for use with R-410A refrigerant.
3.3.1 Shipped-Separate Items
Before beginning installation, be sure that all shipped-separate options ordered are available at the site. Shipped-separate options could have been ordered with the condensing unit or the matching PreevA® air handler.
NOTE: Two liquid line lter driers are shipped loose with the condensing unit for eld installation.
4.1 Clearances
The condensing unit must
have unrestricted airow
FIGURE 1 - Minimum Clearances (Top View)
4.0 Clearances and Dimensions
on the coil side and above the unit. A service clearance is required on the con­trol side of the cabinet.
Form I-COND, P/N 220746R6, Page 5
61” (1549mm)
59” (1499mm)
9-5/32” (233mm)
47”(1194mm)
50-1/4”
(1273mm)
5-1/8” (130mm)
7” (178mm)
3” (76mm)
3” (76mm)
4” (102mm)
45-7/32” (1149mm)
44-13/32” (1128mm)
1-25/32” (45mm)
3” (76mm)
Supply Voltage Entrance Control Voltage Entrance
Electrical Box
and Compressor
Compartment Access Panel
CIRCUIT B Connections Left - 1/2” Liquid Line; Right - 7/8” Suction Line
Optional Hot Gas
Bypass Connections
Left - Circuit A, 1/2”
Right - Circuit B, 1/2”
CIRCUIT A
Connections
Left - 1/2” Liquid Line;
Right - 7/8” Suction Line
Front View
Right Side View
(side opposite coil)
Rear View
Top
View
MASA Sizes
60 and 90
Suggested location
for field-installed
disconnect switch
(See FIGURE 1, page 5.)
4.0 Clearances and
4.2 Dimensions
Dimensions cont’d)
FIGURE 2A - Model MASA 60 and 90 Dimensions
FIGURE 2B - Model MASA 120, 150, and 180 Dimensions
Optional Hot Gas
Bypass Connections
Left - Circuit A, 1/2”
Right - Circuit B, 1/2”
CIRCUIT A
Connections
Liquid Line;
Suction Line
Form I-COND, P/N 220746R6, Page 6
120, 150, 180, 240
Electrical Box
and Compressor
3” (76mm)
Left - 1/2”
Right - 7/8”
4” (102mm)
MASA Sizes
Front View
CIRCUIT B Connections
Compartment Access Panel
3” (76mm)
Left - Liquid Line, 1/2” Sizes 120, 150, 180; 5/8” Size 240 Right - Suction Line, 7/8” Size 120; 1-3/8” Sizes 150, 180, 240
9-5/32”
(233mm)
Suggested location
for field-installed
disconnect switch
(See FIGURE 1, page 5.)
1-25/32”
(45mm)
44-13/32” (1128mm)
7” (178mm)
Top
View
Supply Voltage Entrance
Control Voltage Entrance
B
3”
(76mm)
45-7/32”
(1149mm)
Right Side View
Rear View
(side opposite coil)
MASA
Sizes
120, 150 86 84 120, 150 2184 2134
A B
Dimensions (inches) Dimensions (mm)
180, 240 110 108 180, 240 2794 2743
A
5-1/8” (130mm)
MASA
Sizes
47” (1194mm)
A B
50-1/4”
(1273mm)
5.0 Mounting
5.1 Weights
Before installing, check the supporting structure to be sure that it has sufcient
load-bearing capacity to support the operating weight of the unit. Mounting is the responsibility of the installer.
TABLE 1 - Weights
Approximate Operating Weight of Condensing Unit
MASA Size 060 090 120 150 180 240
lbs 440 461 632 699 749 771
kg 200 209 287 317 340 350
5.2 Lifting
The heavy gauge base of the condensing unit has fork lift holes and a pair of lifting holes on each corner for rigging. If lifting with a forklift, forks must have a minimum length of 24” (610mm). If attaching rigging, insert a clevis in each set of holes for the rigging and lift using spreader bars. Lift the unit straight
up with vertical force.
Test lift the unit to be sure that it is secure and then lift slowly following safe lifting procedures. Lifting and rigging are the responsibility of the installer.
5.3 Mounting
Condensing unit may be set directly on a roof or slab. Unit must be level. Be sure to comply with clearances in FIGURE 1, page 5.
6.0 Mechanical
6.1 Refrigerant Piping
6.1.1 Location of Piping Connections at the Condensing Unit
Remove the control compartment door panel. Locate the refrigerant connec­tions in the lower right corner. See FIGURE 3, page 8. Each circuit is shipped with a nitrogen charge and has a shutoff valve. Do not open the valves until after the lines are connected and the condenser circuits are leak tested.
The entrances for the two main refrigerant circuits are identied as Circuit A and Circuit B (See FIGURE 3). Circuit A is the smaller (approximate 33%) con- denser circuit; Circuit B is the larger (approximate 67%) circuit. Also indicated,
are the entrances for optional hot gas bypass circuits. If the condensing unit is equipped with a hot gas bypass on only one circuit (Option CUG2), only one entrance will be used. If equipped with a hot gas bypass on both circuits (Option CUG3), both entrances will be used. When connecting refrigerant
lines to the condensing unit and the air handler, it is very important to make all connections so that each individual circuit is maintained.
CAUTION
Do not remove seal caps from refrigerant connections or open the service valves until ready to make permanent connection. Exposure to the atmosphere for longer than
ve minutes may allow moisture and dirt to contaminate the
system. See Hazard Levels, page 3.
Form I-COND, P/N 220746R6, Page 7
6.0 Mechanical
Circuit A (1/3 circuit) Piping Entrance Holes ­Liquid line on the left; Suction line on the right
Electrical and
Compressor
Compartment
Access
Panel
Circuit B (2/3 circuit) Piping Entrance Holes ­Liquid line on the left; Suction line on the right
Entrances for Optional Hot Gas Bypass Connections Left - Circuit A; Right - Circuit B
R-410A Compressors
(identified by
Circuit A & B)
B
A
Electrical
Compartment
(cont’d)
FIGURE 3 - Condensing Unit Refrigerant Piping Connection Locations
6.1.1 Location of Piping Connections at the Condensing Unit (cont’d)
Form I-COND, P/N 220746R6, Page 8
6.1.2 Location of Piping Connections at the Split System Evaporator Coil
It is important to identify the Circuit A and Circuit B connections at the evapora­tor coil before running the refrigerant lines.
Circuit A on the condenser (FIGURE 3) is the smaller (33%) circuit and should be connected to the 33% circuit of the evaporator coil. Circuit B on the con­denser (FIGURE 3) is the larger (67%) circuit and should be connected to the
67% circuit of the evaporator coil.
On the evaporator coil, identify the liquid line connection at the distributor for the smaller circuit (Circuit A). Force nitrogen into the Circuit A connection and check which suction line connection corresponds to it. If the suction line con­nection is not identied, mark it as Circuit A. For verication, repeat the pro­cess with the larger circuit and mark the suction line connection as Circuit B.
Refer to FIGURE 4A or 4B for illustration of a split system refrigerant piping system connecting a MASA condensing unit to a PreevA
FIGURE 4A, the condensing unit is higher than the evaporator coil. In FIGURE 4B, the condensing unit is lower than the evaporator coil.
®
evaporator coil. In
FIGURE 4A - Refrigerant Piping on a PreevA® Split System with the Condensing Unit
*Field-supplied per NEC. **Field-supplied
SIGHT GLASS/ MOISTURE INDICATOR **
CONDENSING UNIT INSTALLED ON THE ROOF
TO
CONDENSING
UNIT
FROM
AIR
HANDLER
Line Length NOTES:
1) MAXIMUM LIFT IS 45 FEET (13.7M).
2) MAXIMUM EQUIVALENT LENGTH OF EACH STANDARD LINE IS 60 FEET (18.3M); SEE PARAGRAPH 6, MECHANICAL.
3) CAUTION: MAXIMUM EQUIVALENT LENGTH OF AN OPTIONAL HOT GAS BYPASS LINE IS 30 FT (9.1M).
TWO-CIRCUIT (1/3-2/3) CONDENSING UNIT FOR R-410A REFRIGERANT
AIR HANDLER UNIT WITH A TWO-CIRCUIT (1/3-2/3) COOLING COIL FOR R-410A REFRIGERANT
NOTES:
1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and ASME Informational Standards for piping information. Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or provincial requirements.
2. All wiring must comply with all applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply to or include all details for a specific installation. Refer to ASHRAE Guide Section 15 for piping details.
4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have properly sized thermal expansion valves.)
5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.
6. Evaporative coil must have freeze protection.
ROOF
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “A” CIRCUIT HOT GAS BYPASS (See Line Length NOTE 3)
DISCONNECT SWITCH *
DISCONNECT
SWITCH *
LIQUID LINE FILTER DRIER
LIQUID LINE FILTER DRIER
POWER WIRE
“B” CIRCUIT LIQUID LINE
24V CONTROL WIRE
“A” CIRCUIT LIQUID LINE
OPTIONAL “A” CIRCUIT HOT GAS BYPASS (See Line Length NOTE 3)
OPTIONAL “B” CIRCUIT HOT GAS BYPASS (See Line Length NOTE 3)
“A” CIRCUIT SUCTION LINE
“B” CIRCUIT SUCTION LINE
LIQUID LINE
SOLENOID
VALVE ** LEGEND NEC - National Electric Code TXV - Thermostatic Expansion Valve
Piping
Installed at a Higher Level than the Air Handler Unit
Form I-COND, P/N 220746R6, Page 9
6.0 Mechanical
CONDENSING UNIT INSTALLED AT GROUND LEVEL
FROM
AIR
HANDLER
REPRESENTATIVE
TRAPS
*Field-supplied per NEC. **Field-supplied
SIGHT GLASS/ MOISTURE INDICATOR **
AIR HANDLER UNIT WITH A TWO-CIRCUIT (1/3-2/3) COOLING COIL FOR R-410A REFRIGERAN
T
NOTES:
1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and ASME Informational Standards for piping information. Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or provincial requirements.
2. All wiring must comply with all applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply to or include all details for a specific installation. Refer to ASHRAE Guide Section 15 for piping details.
4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have properly sized thermal expansion valves.)
5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.
6. Evaporative coil must have freeze protection.
Line Length NOTES:
1) MAXIMUM LIFT IS 45 FEET (13.7M).
2) MAXIMUM EQUIVALENT LENGTH OF EACH STANDARD LINE IS 60 FEET (18.3M); SEE PARAGRAPH 6, MECHANICAL.
3) CAUTION: MAXIMUM EQUIVALENT LENGTH OF AN OPTIONAL HOT GAS BYPASS LINE IS 30 FT (9.1M).
DISCONNECT
SWITCH *
OPTIONAL “A” CIRCUIT HOT GAS BYPASS (See Line Length NOTE 3)
OPTIONAL “B” CIRCUIT HOT GAS BYPASS (See Line Length NOTE 3)
“B” CIRCUIT SUCTION LINE
“B” CIRCUIT LIQUID LINE
24V CONTROL WIRE
DISCONNECT SWITCH *
“A” CIRCUIT SUCTION LINE
“A” CIRCUIT LIQUID LINE
LIQUID LINE FILTER DRIER
LIQUID LINE FILTER DRIER
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “A” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
POWER
LINE
LIQUID LINE
SOLENOID VALVE **
TWO-CIRCUIT (1/3-2/3)
CONDENSING UNIT
FOR R-410A
REFRIGERANT
GROUND
(PAD)
LEGEND NEC - National Electric Code TXV - Thermostatic Expansion Valve
- Piping
(cont’d)
FIGURE 4B - Refrigerant Piping on a PreevA® Split System with the Condensing Unit Installed at a Lower Level than the Air Handler Unit
Form I-COND, P/N 220746R6, Page 10
6.1.3 Refrigerant Piping Guidelines (R-410A Refrigerant)
The information in this section is a guideline and is not intended to provide all of the instructions needed for designing and installing the R-410A refriger­ant lines. The installer is responsible for designing the refrigerant connecting system and for complying with standard refrigerant piping procedures. Refer to ASHRAE Guide and ASME Informational Standards for piping information. Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or provincial requirements.
Read all information in Section 6.1.3 before beginning installation of refrigerant piping. In addition to the information in the following paragraphs, these general requirements apply.
IMPORTANT: Do not bury refrigeration lines.
Pitch refrigerant lines in the direction of ow at approximately 1/2” per 10 ft
(12mm per 3 M).
To prevent possible noise or line vibration, isolate refrigerant lines from
building structure and ductwork.
Use long radius “L” for all 90° bends.
Isolate suction and liquid lines from each other and from the unit cabinet.
CAUTION
Do not leave system open to the atmosphere any longer than minimum time required for installation. POE oil in the compressors is extremely susceptible to moisture absorption. Keep ends of tubing sealed during installation. See Hazard Levels, page 3.
6.1.3.1 Type of Refrigerant Piping
Refrigerant piping is eld supplied. Use only clean, dehydrated refrigeration
grade Type L scheduled or ACR Hard Drawn (ASTM B 280) copper tubing. Size of refrigerant line segments depends on the condensing unit size and the
length and conguration of the lines. Do not determine the size of the piping
by the size of the connections at the condenser or evaporator; follow the line sizing instructions in Section 6.1.3.2 below.
6.1.3.2 Refrigerant Piping Length and Size
Design the refrigerant circuit for a minimum pressure loss by keeping the actual
length to a minimum, with a minimum number of bends and ttings, and with a minimum amount of line exposed to the outdoors. Excessive suction line pressure drop will result in decreased thermal efciency and increased power requirements. Excessive liquid line pressure drop can cause the refrigerant to ash resulting in faulty expansion valve operation. Typically, each segment of
the refrigerant line should be sized for pressure loss of 2°F or less. Lift must also be considered when determining location and piping length.
Maximum lift of the refrigerant circuit is 45 ft (13.7M).
Tubing size is determined separately for each of the four segments of the refrigerant piping - Circuit A liquid line; Circuit A suction line; Circuit B liquid line; and Circuit B suction line. The size of the tubing required for each segment is determined by its equivalent length. The equivalent length is the actual length
of the line segment plus any ttings or accessories.
If accessories (see Paragraphs 6.1.3.3 and.4 for required accessories) have equivalent lengths provided by the manufacturer, use that information. If
equivalent length is not provided and for ttings, use the equivalent lengths in
TABLE 2.
Form I-COND, P/N 220746R6, Page 11
6.0 Mechanical (cont’d)
TABLE 2 - Fitting Pressure Loss in Equivalent Length of Straight Copper Tubing
NOTE: Liquid line lter
driers provided have 1/2” connections. Add equil-
valent length for lter
driers plus, if liquid line is not 1/2”, add equilvalent
for ttings.
6.1 Refrigerant Piping (cont’d)
6.1.3 Refrigerant Piping Guidelines (R-410A Refrigerant) (cont’d)
6.1.3.2 Refrigerant Piping Length and Size (cont’d)
Equivalent Length of Fittings and Accessories
Globe /
Line
Solenoid
Size
OD
Valve
1/2" 9 5 1.4 0.9 0.4 0.6 2.0 1.4 0.8 0.3 0.7 0.5 0.3
5/8" 12 6 1.5 1.0 0.5 0.8 2.5 1.8 1.1 0.4 0.8 0.7 0.4
3/4" 14 7 1.9 1.3 0.6 0.9 3.0 2.5 1.5 0.5 1.2 1.0 0.5
7/8" 15 8 2.3 1.5 0.7 1.0 3.5 3.2 2.0 0.7 1.6 1.2 0.7
1-1/8" 22 12 2.7 1.8 0.9 1.5 4.5 4.7 3.0 1.0 2.3 1.8 1.0
1-3/8" 28 15 3.6 2.4 1.2 1.8 6.0 5.8 3.6 2.9 2.9 2.2 1.2
1/2" 2.7 1.5 0.4 0.3 0.1 0.2 0.6 0.4 0.2 0.1 0.2 0.2 0.1
5/8" 3.7 1.8 0.5 0.3 0.2 0.2 0.8 0.6 0.3 0.1 0.2 0.2 0.1
3/4" 4.3 2.1 0.6 0.4 0.2 0.3 0.9 0.8 0.5 0.2 0.4 0.3 0.2
7/8" 4.6 2.4 0.7 0.5 0.2 0.3 1.1 1.0 0.6 0.2 0.5 0.4 0.2
1-1/8" 6.7 3.7 0.8 0.6 0.3 0.5 1.4 1.4 0.9 0.3 0.7 0.6 0.3
1-3/8" 8.5 4.6 1.1 0.7 0.4 0.6 1.8 1.8 1.1 0.9 0.9 0.7 0.4
Angle /
Check
Valve
90º SR
Elbow
45º
Tee Line
/ Sight
Glass
Tee
Branch
90º LR
Elbow
Elbow
Equivalent Length (in Feet of Pipe)
Equivalent Length (in Meters of Pipe)
Coupling to
Enlarge OD by
1/4" 1/2" 3/4" 1/4" 1/2" 3/4"
Coupling to
Reduce OD by
TABLE 3 ­Recommended Size of Refrigerant Piping for each Segment determined by the Equivalent Length
Use the worksheet on page 13, and the information in TABLE 2 and TABLE 3 to determine the line segment and circuit equivalent lengths and the size of tubing required for each line segment.
IF AN APPLICATION REQUIRES MORE THAN 60 FEET (18.3M) OF EQUIV­ALENT LENGTH OF TUBING (LIQUID LINE OR SUCTION LINE) BETWEEN THE CONDENSER AND THE AIR HANDLER, CONTACT REZNOR FOR APPROVAL.
*Minimum Recommended Refrigerant Piping Size
Suction Line Tubing Size (OD) Liquid Line Tubing Size (OD)
MASA
Model
60
90
120
150
180
240
*Based on copper tubing type L; a 2°F loss; and a maximum of 65ºF suction line (return gas) temperature and liquid line temperature of 105ºF.
**Equivalent Line Segment Length = length of eld-installed tubing in line segment plus equivalent length of all eld-installed ttings and
accessories in line segment. For both liquid line and suction line segments, maximum recommended equivalent length is 60 ft (18.3M).
CAUTION: Maximum equivalent length of a hot gas bypass line is 30 ft (9.1M).
Circuit
A 1/2 5/8 3/4 1/2 1/2 1/2
B 3/4 3/4 7/8 1/2 1/2 1/2
A 5/8 3/4 3/4 1/2 1/2 1/2
B 7/8 7/8 1 1/8 1/2 1/2 1/2
A 3/4 3/4 7/8 1/2 1/2 1/2
B 7/8 1 1/8 1 1/8 1/2 5/8 5/8
A 7/8 7/8 1 1/8 1/2 1/2 1/2
B 1 1/8 1 1/8 1 3/8 1/2 5/8 5/8
A 7/8 7/8 1 1/8 1/2 1/2 1/2
B 1 1/8 1 1/8 1 3/8 1/2 5/8 5/8
A 7/8 1 1/8 1 1/8 1/2 5/8 5/8
B 1 1/8 1 3/8 1 3/8 5/8 3/4 3/4
**Equivalent Length of the Suction Line - Ft (M) **Equivalent Length of the Liquid Line - Ft (M)
Up to 25 Ft > 25 to 50 Ft > 50 to 60 Ft Up to 25 Ft > 25 to 50 Ft > 50 to 60 Ft
(Up to 7.6M) (> 7.6 to 15.2M) (> 15.2 to 18.3M) (Up to 7.6M) (> 7.6 to 15.2M) (> 15.2 to 18.3M)
Form I-COND, P/N 220746R6, Page 12
Loading...
+ 28 hidden pages