IMPORTANT: Check, Test, and Startup MUST be followed, as documented in this manual.
A completed Condenser Startup Form (page 38) may be required for validation of any warranty
claims.
The factory reserves the right to deny warranty without completed Condenser Startup Form.
This booklet includes operation, maintenance, and service information. Before beginning any procedure, carefully
review the information, paying particular attention to the warnings. All installation procedures including handling of
refrigerant must be in compliance with all codes and requirements of authorities having jurisdiction.
Installer should complete information on page 40.
Condenser Startup Form on page 38 should be completed on initial startup.
Owner should keep this booklet for future reference.
There are warning labels on the condensing unit and throughout this manual.
For your safety, read the denitions below and comply with all boxes labeled
CAUTION, WARNING, and DANGER during installation, operation, maintenance, and service of this system.
Denitions of Hazard Intensity Levels in this Manual
HAZARD INTENSITY LEVELS
DANGER: Failure to comply will result in severe personal injury
or death and/or property damage.
WARNING: Failure to comply could result in severe personal
injury or death and/or property damage.
CAUTION: Failure to comply could result in minor personal
injury and/or property damage.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause property damage, personal injury, or
death. A qualied installer or service agency must perform
installation and service.
DANGER
This condensing unit is designed to use R-410A high pressure
refrigerant only. Hazards exist that could result in personal
injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-
410A refrigerant and using proper tools and equipment. Due
to much higher pressure of R-410A refrigerant, DO NOT USE
service equipment or tools designed for R22 refrigerant.
DANGER
Never use oxygen to pressurize a refrigeration system.
Oxygen can explode on contact with oil and result in
personal injury or death. When using high pressure gas
such as nitrogen for pressurizing a refrigeration system,
ALWAYS USE A PRESSURE REGULATOR that can control
the pressure down to 1 or 2 psig.
SAFETY WARNINGS
For your safety, wear eye protection, gloves, and protective
clothing when handling R-410A refrigerant or POE oil
and when brazing. Have a re extinguisher nearby when
brazing.
Form I-COND, P/N 220746R6, Page 3
1.0 General
(cont’d)
1.1 Hazard Labels
and Notices
(cont’d)
WARNING
Before installing or servicing, always turn off the main
power to the system and install a lock out on the disconnect
switch.
CAUTION
Do not leave system open to the atmosphere any longer than
minimum required for installation. Exposure for more than
ve minutes may contaminate the system. POE oil in the
compressors is extremely susceptible to moisture absorption.
Always keep ends of tubing sealed during installation.
1.2 General Information
This booklet includes operation, maintenance, and service information. Before
beginning any procedure, carefully review the information, paying particular
attention to the warnings. All installations must be in compliance with all codes
and requirements of authorities having jurisdiction.
A Model MASA outdoor condensing unit operates on R-410A refrigerant and
has two independent refrigeration circuits congured in an approximate 1/3-
2/3 arrangement. The Model MASA condensing unit is designed for use with a
Reznor PreevA
indoor Models are PDH or SDH; outdoor Model is RDH. The Model MASA condensing unit may also be matched to a eld-supplied 1/3-2/3 two-circuit evaporator coil. An air handler used with a Model MASA condensing unit must be
properly matched; the evaporator coil must have freeze protection and must
be equipped with properly sized thermostatic expansion valves.
®
air handler unit with a 1/3-2/3 two-circuit cooling coil. PreevA®
Form I-COND, P/N 220746R6, Page 4
CAUTION
The condensing unit must be matched to an approximate
1/3-2/3 two-circuit, R-410A refrigerant evaporator coil with
properly sized thermostatic expansion valves. Failure to
properly match and/or equip the split system components will
prevent the system from operating correctly and will void the
manufacturer’s warranty. See Hazard Levels, page 3.
1.3 Warranty
Refer to limited warranty information on the Warranty Form in the “Literature
Bag” shipped with this system.
A completed Condenser Startup Form on page 39 may be required for validation of any warranty claim. Proper Check, Test, and Startup procedures MUST
be followed, as documented in this manual. The factory reserves the right to
deny warranty without a completed Condenser Startup Form.
1.4 Installation Codes
All installations must be in compliance with the National Electric Code ANSI/
NFPA No. 70 (latest edition) or, in Canada, the Canadian Electrical Code,
Part I-C.S.A. Standard C 22.l. Check any local ordinances or utility company
requirements that apply. The installation must be in compliance with all authorities having jurisdiction. Local code requirements supersede national requirements.
Coil Side
(Inlet airflow through
the condenser coil
must be unrestricted.)
Control Side
(Service
Clearance)
Opposite
Control
Side
Electrical Entrance Side
NOTE: Suggested side for installing disconnect switch;
see FIGURE 2, page 6. If disconnect switch is installed
on this side, minimum clearance is 36” (914mm).
Airflow
Top discharge airflow must be unrestricted.
Top clearance is 60” (1524mm).
36”
(914mm)
6”
(152mm)
6” (152mm)
48”
(1219mm)
Top
View
2.0 Location
Model MASA condensing unit must be mounted outdoors on a level surface.
The supporting structure must be able to support the operating weight of the
unit and maintain a level plane during continued operation. Water should drain
away from the unit. Location must comply with free space clearances for unre-
stricted airow (See Paragraph 4.1) and the refrigerant piping requirements
(See Paragraph 6.1.3). Avoid facing condenser coils into the prevailing wind.
3.0 Receiving,
Moving, and
Uncrating
3.1 Receiving
Check for any damage that may have been incurred during shipment. If damage is found, document the damage with the transporting agency and immediately contact your Reznor distributor. If you are an authorized Distributor, follow
the FOB freight policy procedures as published by Reznor for Reznor products.
3.2 Moving
The heavy gauge base of the condensing unit has forklift openings in both
sides. To move a unit, use a forklift with forks that have a minimum length of
24” (610mm).
3.3 Uncrating
Immediately upon uncrating, check the electrical characteristics to verify that
the unit is suitable for the installation site. This condensing unit is designed for
R-410A refrigerant only; verify that the split system air handler is for use with
R-410A refrigerant.
3.3.1 Shipped-Separate Items
Before beginning installation, be sure that all shipped-separate options ordered
are available at the site. Shipped-separate options could have been ordered
with the condensing unit or the matching PreevA® air handler.
NOTE: Two liquid line lter driers are shipped loose with the condensing unit
for eld installation.
4.1 Clearances
The condensing unit must
have unrestricted airow
FIGURE 1 - Minimum
Clearances (Top
View)
4.0 Clearances and Dimensions
on the coil side and above the unit. A service clearance is required on the control side of the cabinet.
Form I-COND, P/N 220746R6, Page 5
61” (1549mm)
59” (1499mm)
9-5/32”
(233mm)
47”(1194mm)
50-1/4”
(1273mm)
5-1/8”
(130mm)
7” (178mm)
3” (76mm)
3” (76mm)
4” (102mm)
45-7/32” (1149mm)
44-13/32”
(1128mm)
1-25/32”
(45mm)
3”
(76mm)
Supply Voltage Entrance
Control Voltage Entrance
Electrical Box
and Compressor
Compartment
Access Panel
CIRCUIT B
Connections
Left - 1/2”
Liquid Line;
Right - 7/8”
Suction Line
Optional Hot Gas
Bypass Connections
Left - Circuit A, 1/2”
Right - Circuit B, 1/2”
CIRCUIT A
Connections
Left - 1/2” Liquid Line;
Right - 7/8” Suction Line
Front View
Right Side View
(side opposite coil)
Rear View
Top
View
MASA Sizes
60 and 90
Suggested location
for field-installed
disconnect switch
(See FIGURE 1, page 5.)
4.0 Clearances and
4.2 Dimensions
Dimensions cont’d)
FIGURE 2A - Model MASA 60 and 90 Dimensions
FIGURE 2B - Model MASA 120, 150, and 180 Dimensions
Before installing, check the supporting structure to be sure that it has sufcient
load-bearing capacity to support the operating weight of the unit. Mounting is
the responsibility of the installer.
TABLE 1 - Weights
Approximate Operating Weight of Condensing Unit
MASA Size 060090120150180240
lbs440461632699749771
kg200209287317340350
5.2 Lifting
The heavy gauge base of the condensing unit has fork lift holes and a pair of
lifting holes on each corner for rigging. If lifting with a forklift, forks must have
a minimum length of 24” (610mm). If attaching rigging, insert a clevis in each
set of holes for the rigging and lift using spreader bars. Lift the unit straight
up with vertical force.
Test lift the unit to be sure that it is secure and then lift slowly following safe
lifting procedures. Lifting and rigging are the responsibility of the installer.
5.3 Mounting
Condensing unit may be set directly on a roof or slab. Unit must be level. Be
sure to comply with clearances in FIGURE 1, page 5.
6.0 Mechanical
6.1 Refrigerant Piping
6.1.1 Location of Piping Connections at the Condensing Unit
Remove the control compartment door panel. Locate the refrigerant connections in the lower right corner. See FIGURE 3, page 8. Each circuit is shipped
with a nitrogen charge and has a shutoff valve. Do not open the valves until
after the lines are connected and the condenser circuits are leak tested.
The entrances for the two main refrigerant circuits are identied as Circuit A
and Circuit B (See FIGURE 3). Circuit A is the smaller (approximate 33%) con-
denser circuit; Circuit B is the larger (approximate 67%) circuit. Also indicated,
are the entrances for optional hot gas bypass circuits. If the condensing unit
is equipped with a hot gas bypass on only one circuit (Option CUG2), only
one entrance will be used. If equipped with a hot gas bypass on both circuits
(Option CUG3), both entrances will be used. When connecting refrigerant
lines to the condensing unit and the air handler, it is very important to
make all connections so that each individual circuit is maintained.
CAUTION
Do not remove seal caps from refrigerant connections or
open the service valves until ready to make permanent
connection. Exposure to the atmosphere for longer than
ve minutes may allow moisture and dirt to contaminate the
system. See Hazard Levels, page 3.
Form I-COND, P/N 220746R6, Page 7
6.0 Mechanical
Circuit A (1/3 circuit)
Piping Entrance Holes Liquid line on the left;
Suction line on the right
Electrical and
Compressor
Compartment
Access
Panel
Circuit B (2/3 circuit)
Piping Entrance Holes Liquid line on the left;
Suction line on the right
Entrances for Optional
Hot Gas Bypass Connections
Left - Circuit A;
Right - Circuit B
R-410A Compressors
(identified by
Circuit A & B)
B
A
Electrical
Compartment
(cont’d)
FIGURE 3 - Condensing
Unit Refrigerant Piping
Connection Locations
6.1.1 Location of Piping Connections at the Condensing Unit
(cont’d)
Form I-COND, P/N 220746R6, Page 8
6.1.2 Location of Piping Connections at the Split System
Evaporator Coil
It is important to identify the Circuit A and Circuit B connections at the evaporator coil before running the refrigerant lines.
Circuit A on the condenser (FIGURE 3) is the smaller (33%) circuit and should be connected to the 33% circuit of the evaporator coil. Circuit B on the condenser (FIGURE 3) is the larger (67%) circuit and should be connected to the
67% circuit of the evaporator coil.
On the evaporator coil, identify the liquid line connection at the distributor for
the smaller circuit (Circuit A). Force nitrogen into the Circuit A connection and
check which suction line connection corresponds to it. If the suction line connection is not identied, mark it as Circuit A. For verication, repeat the process with the larger circuit and mark the suction line connection as Circuit B.
Refer to FIGURE 4A or 4B for illustration of a split system refrigerant piping
system connecting a MASA condensing unit to a PreevA
FIGURE 4A, the condensing unit is higher than the evaporator coil. In FIGURE
4B, the condensing unit is lower than the evaporator coil.
®
evaporator coil. In
FIGURE 4A - Refrigerant Piping on a PreevA® Split System with the Condensing Unit
*Field-supplied per NEC.
**Field-supplied
SIGHT GLASS/
MOISTURE
INDICATOR **
CONDENSING UNIT INSTALLED ON THE ROOF
TO
CONDENSING
UNIT
FROM
AIR
HANDLER
Line Length NOTES:
1) MAXIMUM LIFT IS
45 FEET (13.7M).
2) MAXIMUM EQUIVALENT
LENGTH OF EACH
STANDARD LINE IS 60 FEET
(18.3M); SEE PARAGRAPH 6,
MECHANICAL.
3) CAUTION: MAXIMUM
EQUIVALENT LENGTH
OF AN OPTIONAL HOT GAS
BYPASS LINE IS 30 FT (9.1M).
TWO-CIRCUIT (1/3-2/3)
CONDENSING
UNIT FOR R-410A
REFRIGERANT
AIR HANDLER
UNIT WITH A
TWO-CIRCUIT (1/3-2/3)
COOLING COIL
FOR R-410A
REFRIGERANT
NOTES:
1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and
ASME Informational Standards for piping information. Comply with CSA Mechanical Refrigeration Code
CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or provincial requirements.
2. All wiring must comply with all applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply
to or include all details for a specific installation. Refer to ASHRAE Guide Section 15 for piping details.
4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have
properly sized thermal expansion valves.)
5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.
6. Evaporative coil must have freeze protection.
ROOF
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “A” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
DISCONNECT
SWITCH *
DISCONNECT
SWITCH *
LIQUID LINE
FILTER DRIER
LIQUID LINE
FILTER DRIER
POWER
WIRE
“B” CIRCUIT
LIQUID LINE
24V CONTROL
WIRE
“A” CIRCUIT
LIQUID LINE
OPTIONAL “A” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
“A” CIRCUIT
SUCTION LINE
“B” CIRCUIT
SUCTION LINE
LIQUID LINE
SOLENOID
VALVE **
LEGEND
NEC - National Electric Code
TXV - Thermostatic Expansion
Valve
Piping
Installed at a Higher Level than the Air Handler Unit
Form I-COND, P/N 220746R6, Page 9
6.0 Mechanical
CONDENSING UNIT INSTALLED AT GROUND LEVEL
FROM
AIR
HANDLER
REPRESENTATIVE
TRAPS
*Field-supplied
per NEC.
**Field-supplied
SIGHT GLASS/
MOISTURE
INDICATOR **
AIR HANDLER
UNIT WITH A
TWO-CIRCUIT (1/3-2/3)
COOLING COIL
FOR R-410A
REFRIGERAN
T
NOTES:
1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and ASME Informational Standards for
piping information. Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or
provincial requirements.
2. All wiring must comply with all applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply to or include all details for a specific
installation. Refer to ASHRAE Guide Section 15 for piping details.
4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have properly sized thermal expansion
valves.)
5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.
6. Evaporative coil must have freeze protection.
Line Length NOTES:
1) MAXIMUM LIFT IS 45 FEET (13.7M).
2) MAXIMUM EQUIVALENT LENGTH
OF EACH STANDARD LINE IS 60 FEET
(18.3M); SEE PARAGRAPH 6,
MECHANICAL.
3) CAUTION: MAXIMUM EQUIVALENT
LENGTH OF AN OPTIONAL HOT GAS
BYPASS LINE IS 30 FT (9.1M).
DISCONNECT
SWITCH *
OPTIONAL “A” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
“B” CIRCUIT
SUCTION LINE
“B” CIRCUIT
LIQUID LINE
24V CONTROL
WIRE
DISCONNECT SWITCH *
“A” CIRCUIT
SUCTION LINE
“A” CIRCUIT
LIQUID LINE
LIQUID LINE
FILTER DRIER
LIQUID LINE
FILTER DRIER
OPTIONAL “B” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
OPTIONAL “A” CIRCUIT HOT GAS
BYPASS (See Line Length NOTE 3)
POWER
LINE
LIQUID LINE
SOLENOID VALVE **
TWO-CIRCUIT (1/3-2/3)
CONDENSING UNIT
FOR R-410A
REFRIGERANT
GROUND
(PAD)
LEGEND
NEC - National Electric Code
TXV - Thermostatic Expansion Valve
- Piping
(cont’d)
FIGURE 4B - Refrigerant Piping on a PreevA® Split System with
the Condensing Unit Installed at a Lower Level than the Air
Handler Unit
The information in this section is a guideline and is not intended to provide
all of the instructions needed for designing and installing the R-410A refrigerant lines. The installer is responsible for designing the refrigerant connecting
system and for complying with standard refrigerant piping procedures. Refer
to ASHRAE Guide and ASME Informational Standards for piping information.
Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide
Section 15, all municipal codes, and state or provincial requirements.
Read all information in Section 6.1.3 before beginning installation of refrigerant
piping. In addition to the information in the following paragraphs, these general
requirements apply.
• IMPORTANT: Do not bury refrigeration lines.
• Pitch refrigerant lines in the direction of ow at approximately 1/2” per 10 ft
(12mm per 3 M).
• To prevent possible noise or line vibration, isolate refrigerant lines from
building structure and ductwork.
• Use long radius “L” for all 90° bends.
• Isolate suction and liquid lines from each other and from the unit cabinet.
CAUTION
Do not leave system open to the atmosphere any longer
than minimum time required for installation. POE oil in the
compressors is extremely susceptible to moisture absorption.
Keep ends of tubing sealed during installation. See Hazard
Levels, page 3.
6.1.3.1 Type of Refrigerant Piping
Refrigerant piping is eld supplied. Use only clean, dehydrated refrigeration
grade Type L scheduled or ACR Hard Drawn (ASTM B 280) copper tubing.
Size of refrigerant line segments depends on the condensing unit size and the
length and conguration of the lines. Do not determine the size of the piping
by the size of the connections at the condenser or evaporator; follow the line
sizing instructions in Section 6.1.3.2 below.
6.1.3.2 Refrigerant Piping Length and Size
Design the refrigerant circuit for a minimum pressure loss by keeping the actual
length to a minimum, with a minimum number of bends and ttings, and with
a minimum amount of line exposed to the outdoors. Excessive suction line
pressure drop will result in decreased thermal efciency and increased power
requirements. Excessive liquid line pressure drop can cause the refrigerant to
ash resulting in faulty expansion valve operation. Typically, each segment of
the refrigerant line should be sized for pressure loss of 2°F or less.
Lift must also be considered when determining location and piping length.
Maximum lift of the refrigerant circuit is 45 ft (13.7M).
Tubing size is determined separately for each of the four segments of the
refrigerant piping - Circuit A liquid line; Circuit A suction line; Circuit B liquid line;
and Circuit B suction line. The size of the tubing required for each segment is
determined by its equivalent length. The equivalent length is the actual length
of the line segment plus any ttings or accessories.
If accessories (see Paragraphs 6.1.3.3 and.4 for required accessories) have
equivalent lengths provided by the manufacturer, use that information. If
equivalent length is not provided and for ttings, use the equivalent lengths in
TABLE 2.
Form I-COND, P/N 220746R6, Page 11
6.0 Mechanical
(cont’d)
TABLE 2 - Fitting
Pressure Loss in
Equivalent Length
of Straight Copper
Tubing
NOTE: Liquid line lter
driers provided have 1/2”
connections. Add equil-
valent length for lter
driers plus, if liquid line is
not 1/2”, add equilvalent
6.1.3.2 Refrigerant Piping Length and Size (cont’d)
Equivalent Length of Fittings and Accessories
Globe /
Line
Solenoid
Size
OD
Valve
1/2"951.40.90.40.62.01.40.80.30.70.50.3
5/8"1261.51.00.50.82.51.81.10.40.80.70.4
3/4"1471.91.30.60.93.02.51.50.51.21.00.5
7/8"1582.31.50.71.03.53.22.00.71.61.20.7
1-1/8"22122.71.80.91.54.54.73.01.02.31.81.0
1-3/8"28153.62.41.21.86.05.83.62.92.92.21.2
1/2"2.71.50.40.30.10.20.60.40.20.10.20.20.1
5/8"3.71.80.50.30.20.20.80.60.30.10.20.20.1
3/4"4.32.10.60.40.20.30.90.80.50.20.40.30.2
7/8"4.62.40.70.50.20.31.11.00.60.20.50.40.2
1-1/8"6.73.70.80.60.30.51.41.40.90.30.70.60.3
1-3/8"8.54.61.10.70.40.61.81.81.10.90.90.70.4
Angle /
Check
Valve
90º SR
Elbow
45º
Tee Line
/ Sight
Glass
Tee
Branch
90º LR
Elbow
Elbow
Equivalent Length (in Feet of Pipe)
Equivalent Length (in Meters of Pipe)
Coupling to
Enlarge OD by
1/4"1/2"3/4"1/4"1/2"3/4"
Coupling to
Reduce OD by
TABLE 3 Recommended Size
of Refrigerant Piping
for each Segment
determined by the
Equivalent Length
Use the worksheet on page 13, and the information in TABLE 2 and TABLE 3
to determine the line segment and circuit equivalent lengths and the size
of tubing required for each line segment.
IF AN APPLICATION REQUIRES MORE THAN 60 FEET (18.3M) OF EQUIVALENT LENGTH OF TUBING (LIQUID LINE OR SUCTION LINE) BETWEEN
THE CONDENSER AND THE AIR HANDLER, CONTACT REZNOR FOR
APPROVAL.
*Minimum Recommended Refrigerant Piping Size
Suction Line Tubing Size (OD)Liquid Line Tubing Size (OD)
MASA
Model
60
90
120
150
180
240
*Based on copper tubing type L; a 2°F loss; and a maximum of 65ºF suction line (return gas) temperature and liquid line temperature of 105ºF.
**Equivalent Line Segment Length = length of eld-installed tubing in line segment plus equivalent length of all eld-installed ttings and
accessories in line segment. For both liquid line and suction line segments, maximum recommended equivalent length is 60 ft (18.3M).
CAUTION: Maximum equivalent length of a hot gas bypass line is 30 ft (9.1M).
Circuit
A 1/2 5/8 3/4 1/2 1/2 1/2
B 3/4 3/4 7/8 1/2 1/2 1/2
A 5/8 3/4 3/4 1/2 1/2 1/2
B 7/8 7/81 1/8 1/2 1/2 1/2
A 3/4 3/4 7/8 1/2 1/2 1/2
B 7/81 1/81 1/8 1/2 5/8 5/8
A 7/8 7/81 1/8 1/2 1/2 1/2
B1 1/81 1/81 3/8 1/2 5/8 5/8
A 7/8 7/81 1/8 1/2 1/2 1/2
B1 1/81 1/81 3/8 1/2 5/8 5/8
A 7/81 1/81 1/8 1/2 5/8 5/8
B1 1/81 3/81 3/8 5/8 3/4 3/4
**Equivalent Length of the Suction Line - Ft (M)**Equivalent Length of the Liquid Line - Ft (M)
Up to 25 Ft> 25 to 50 Ft> 50 to 60 FtUp to 25 Ft> 25 to 50 Ft> 50 to 60 Ft
(Up to 7.6M)(> 7.6 to 15.2M)(> 15.2 to 18.3M)(Up to 7.6M)(> 7.6 to 15.2M)(> 15.2 to 18.3M)
Form I-COND, P/N 220746R6, Page 12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.