This unit contains R-410A high pressure refrigerant. Hazards exist that could
result in personal injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-410A refrigerant and
using proper tools and equipment. Due to much higher pressure of R-410A
refrigerant, DO NOT USE service equipment or tools designed for R22
refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service
procedures include the adding or removing of refrigerant, the service technician
must comply with all federal, state and local laws. The procedures discussed
in this manual should only be performed by a qualied HVAC technician.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 1
Table of Contents
1.0 General ................................................................2
3.8 Dampers and Damper Controls .........................19
3.9 Other Controls ...................................................19
1.0 General
This booklet includes operation, maintenance, and service information on the MAPS®III
Cabinet D Size systems. Before beginning any procedure, carefully review the information, paying particular attention to the warnings. Handling of refrigerant should only
be performed by a certied HVAC technician with knowledge of the requirements of
R-410A refrigerant and in compliance with all codes and requirements of authorities
having jurisdiction.
The instructions in this manual apply to the following MAPS®III models.
4.0 Gas Heat Section Maintenance - Models
RDCB and RDDB ........................................ 21-33
booklet is applicable, see
list of D Cabinet Sizes in
Paragraph 2.3, page 5.
Denitions of Hazard
Intensity Levels used
in this Manual
ModelDescription
RCB
RDCB
RECB
RDB
RDDB
REDB
There are warning labels on the unit and throughout this manual. For your safety,
comply with all warnings during installation, operation, and service of this system. See
denitions of Hazard Intensity Levels of warnings below.
Makeup Air Cooling Packaged System, 5200-13000CFM
Makeup Air Cooling Packaged System, 5200-13000 CFM, with Gas
Heat Section (500-1600 MBH)
Makeup Air Cooling Packaged System, 5200-13000 CFM, with
Electric Heat Section (120 & 180 kw)
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged
System, 5200-13000 CFM
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged
System, 5200-13000 CFM, with a Gas Heat Section (500-1600 MBH)
Makeup Air Cooling and Re-heat Pump Reheat Cycle Packaged
System, 5200-13000 CFM, with Electric Heat Section (120 & 180 kw)
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or
death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury
or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury
and/or property damage.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 2
2.0 Maintenance
Requirements
This unit will operate with a minimum of maintenance. To ensure long life and satisfactory performance, a system that is operating under normal conditions should be
inspected according to the Maintenance Schedule. If in an area where an unusual
amount of dust or soot or other impurities are present in the air, more frequent inspection is recommended.
Refer to the illustration in FIGURE 1, page 4, and follow the instructions in the referenced paragraphs to maintain this equipment. Maintenance requirements and procedures apply to all Models unless noted.
NOTE: If replacement parts are required, use only factory-authorized parts.
For information, go to www.ReznorHVAC.com or call 800-695-1901
WARNING
Lock power OFF before performing all maintenance procedures (except where power is
required such as checking refrigerant pressure and temperature). Lock disconnect switch
in OFF position. If the system has a heat section, when you turn off the power supply, turn
off the gas. See Hazard Levels, page 2.
2.1 Maintenance
Schedule
Monthly
□ Inspect lters; clean or replace as needed. See Paragraph 3.1. □ Inspect the condensate drain; clean as needed. For information, see Form
I-MAPSIII&IV, Paragraph 6.2.
Semi-Annually
□ Inspect the unit blower plenum fan and belt. Check belt for tension, wear, and
alignment. Adjust or replace as needed. Clean dirt from blower and motor. See
Paragraph 3.2.
Annually
NOTE: Redo the cooling startup procedures when the cooling season begins. Refer
to Startup instructions in the installation manual, Form I-MAPSIII&IV, Paragraph 10.0.
Beginning of the cooling season or more frequently in year-round
cooling climate (applies to all Models):
□ Inspect the wiring for any damaged wire. Replace damaged wiring.□ Inspect the condensate drain pan. Clean the coil cabinet, the drain pan, and ll the
trap.
□ Inspect/clean condenser fans. See Paragraph 3.3.□ Inspect/clean all coils. See Paragraph 3.4.□ Check compressor operation. See Paragraph 3.6.□ Check refrigerant pressure and temperatures (superheat and subcool). These
checks are done when the system is operating. See Paragraph 3.5.
Models RDCB & RDDB with a gas heat section (beginning of the heating
season) - See Section 4.0.
□ Clean all dirt and grease from the combustion air openings and the venter
assembly.
□ Check the heat exchanger, burner, and venter for scale, dust, or lint accumulation.
Clean as needed.
□ Check the gas valves to ensure that gas ow is being shutoff completely.
Models RECB & REDB with an electric heat section (beginning of the
heating season) - See Section 5.0.
□ Check the wiring connections.□ Check the heat section and electric elements for dust or lint accumulation.
Carefully clean as needed.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 3
2.0 Maintenance Requirements (cont'd)
High Voltage Panel
Control
Transformer
Distribution
Block
Distribution Block
Distribution Block
Distribution Block
Distribution Block
Grounding
Lug
Terminal Blocks
Phase Loss
Monitor
Contactor (Condenser
Fan B & C)
Contactor (Condenser Fan A & D)
Contactor (Reheat Compressor E)
Contactor (Compressor D)
Contactor (Compressor C)
Contactor (Compressor B)
Contactor (Compressor A)
Motor Starter
Rear
View
Side View
Front
View
75VA
transformers
Optional Dirty
Filter Switch
Digital
Controller
Controller
Display
Wire Harness
Assembly
Optional
Relays
and Bases
Low Voltage Panel
Control Compartment
Access Door
Heater Controls
Access Door
Filter Access
Coil Access
Fan and Motor
Access
Condenser Section
A
B
C
D
2.2 Control Locations
FIGURE 1 - Access Panels and High and Low Voltage Control Locations
Door Hinge
Locked Unlocked
The lter, coil, and fan/motor cabinet
doors can be opened from the left or
right. On the side of the door to be
opened, unlock the two hinges with
an allen key. Pull out unlocked "fronts"
of hinges to 90 degrees to expose
handles needed to open the door.
Re-lock hinges when door is closed.
High Voltage Panel
(behind low voltage
panel; post is removed
for less restricted view)
Low Voltage Panel
(hinged; swings out
to access rear side and
high voltage panel behind)
Gas Heat
Section
Control Panel
(See Para 4.2.1.)
NOTE: Electric heat
Models RECB and
REDB have additional
electrical panels in
the heat section; see
Paragraph 5.0, page
33.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 4
(2) P/N 104102,
16x16x1
(2) P/N 104102,
16x16x1
(2) P/N 104102,
16x16x1
(2) P/N 104102,
16x16x1
(2) P/N 104102,
16x16x1
(2) P/N 104102,
16x16x1
(2) P/N 101609,
16x25x1
(2) P/N 101609,
16x25x1
(2) P/N 101609,
16x25x1
1) Loosen wing nuts and
slide clamp.
2) Remove filters.
3) Repeat for all filters.
4) Wash and dry filters.
5) Re-install filters in hood.
Be sure wing nuts are tight
and filters secure.
Filters in Hood - Cabinet D
2.3 MAPSIII D
Cabinet Sizes
Model
RCB
360
480
600
720
Model
RDB
418
444
484
538
564
602
658
684
722
804
842
Cabinet
Size
D
Cabinet
Size
D
Model
RDCB
360
480
600
720
Model
RDDB
418
444
484
538
564
602
658
684
722
804
842
Gas Heat Section Size
-500 -600 -700 -800 -1000 -1200 -1400 -1600
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
Gas Heat Section Size
-500 -600 -700 -800 -1000 -1200 -1400 -1600
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
DDDDDDDD
Electric Heat Section
RECB120 RECB180
DD
DD
DD
DD
Electric Heat Section
REDB120 REDB180
DD
DD
DD
DD
DD
DD
DD
DD
DD
DD
DD
3.0 Maintenance/
Service
Procedures
3.1 Filters
The lter section is equipped with 4 inches of pleated disposable or permanent aluminum lters. To remove lters, open the door and slide lters out.
If equipped with permanent aluminum lters, there are sixteen 2"x20"x24" lters.
Remove the lters, wash, rinse, allow to dry, and slide them back in the cabinet. The
P/N for replacement or extra lter is 223065; quantity is 16.
If equipped with pleated disposable lters, there are eight 4"x20"x24" lters, either
MERV8 or MERV13.. Replace dirty lters. Exposure to humid makeup air can accelerate lter degradation. Systems with disposable lters require more frequent lter
inspection. The P/N for one replacement or extra MERV8 lter is 222480; quantity
required is 8. The P/N for one replacement or extra MERV13 lter is 260828; quantity
required is 8.
Dirty Filter Switch - If equipped with a dirty lter switch, check the condition of the
sensing tubes to be sure that they are not blocked. Check the wiring connections. To
set a new switch, see Installation Form I-MAPSIII&IV, Paragraph 8.1, Replacement
switch is P/N 105507.
Permanent Filters in
the Outside Air Hood
If equipped with an outside air hood, there are 1" permanent, aluminum lters at the
entrance of the hood. The lters act as a moisture eliminator and bird screen.
When inspecting the inlet air lters, inspect the outside air hood lters. If cleaning is
needed, remove the lters, clean, rinse, dry and re-install. NOTE: If it is more conve-
nient to keep an extra clean set of lters, lter sizes and part numbers are shown in
the illustration.
FIGURE 2 - Removing Filters
from Outside Air Hood
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 5
3.0 Maintenance/
2-1/2” (63.5mm)
Fan and Motor Assembly
showing Fan Blade Position
Cross-section of Installed Fan and Motor
Assembly showing Cabinet Top
1.76” (44.7mm)
Top of Fan Blade
to Top of the
Cabinet Top Panel
Service
Procedures
(cont'd)
3.2 Drive Components
Bearings - Bearings with a grease tting should be lubricated twice a year with a high
temperature, moisture-resistant grease. (Type NLGI-1 or -2 standard grease is recommended.) Be sure to clean the grease tting before adding grease. Add grease with a
handgun until a slight bead of grease forms at the seal. Be careful not to unseat the
seal by over lubricating. NOTE: If unusual environmental conditions exist (tempera-
tures below 32°F or above 200°F; moisture; or contaminants), more frequent lubrication is required.
CAUTION: If the blower is unused for more than three months,
bearings with a grease tting should be purged with new grease
prior to start-up.
Setscrews - Check all of the setscrews (bearing/blower hubs and pulleys). Torque pul-
ley setscrews a minimum of 110 in-lb to 130 in-lb maximum.
A bearing hub setscrew for a 1-3/8" to 1-3/4" shaft requires a 5/16" socket and a tightening torque of 165 in-lbs.
Belts - Check belt for proper tension and wear. Adjust belt tension as needed. Replace
worn belts.
Blower systems are equipped with either Power Twist Plus
belt. The linked belts are designed in sections allowing for easy sizing and adjustment.
The belt is sized at the factory for the proper tension. If the belt needs adjustment, the
recommended method of shortening the belt length is to count the number of links and
remove one link for every 24. (A link is made up of two joining sections of belt. For easier removal of links, turn the belt inside out. But be sure to turn it back before installing.)
If equipped with a solid belt, adjust the belt tension by turning the adjusting screw on
the motor base until the belt can be depressed 1/2" (13mm) on each side. After correct
tension is achieved, re-tighten the locknut on the adjustment screw.
Proper belt tension is important to the long life of the belt and motor.
Be sure belts are aligned in the pulleys. If a belt is removed or replaced, be sure to align
directional arrows on the belt to the proper drive rotation.
Motor and Blower - Inspect the motor mounts periodically. Remove dust and dirt accumulation from the motor and wheel.
The blower has cast iron, pillowblock, sealed bearings. Under most operating conditions, re-lubrication is unnecessary. If lubrication is required, use a lubricant compatible to Shell Alvania #2 (lithium base - Grade 2). Operating temperature range is -30
to 230°F.
"D" size cabinets have plenum fan blowers which have an extension to the grease tting on the side of the fan assembly.
If any drive parts need to be replaced, use only factory-authorized replacements
designed for the application.
®
linked blower belt or a solid
3.3 Condenser Fans
FIGURE 3 -
Condenser
Fan Assembly
Dimensions
and Rotation
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 6
Depending on the size, there are two, three, or four fans in the condenser section. If
parts need to be replaced, use only factory authorized replacement parts.
See FIGURE 3 for assembled dimensions and proper fan rotation direction.
Fan rotation
is clockwise
3.4 Coil
Condenser Coils by Circuit
D
A
B
C
5 ton MC Coil
10 ton MC Coil
Inlet 1
Ø 0.879
Inlet 2
Ø 0.879
Outlet
Ø 0.879
Discharge
Line Ø 0.500
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Liquid Line
Ø 0.875
Liquid Line
Ø 0.875
Liquid Line
Ø 0.500
Filter Drier
Filter Drier
Filter Drier
(See compressor locations on page 12.)
A
C
D
A
C
D
Suction Line Ø 1.375
Suction Line Ø 0.875
Suction Line Ø 1.375
RCB/RDCB/RECB 360 and
RDB/RDDB/REDB 418, 444, and 484
(To TXV valves and
Distributors on
Evaporator Coils)
15 ton MC Coil
Inlet
Ø 0.506
Outlet Ø 0.506
Inlet
Ø 0.879
Outlet Ø 0.879
Outlet Ø1.380
Outlet Ø1.380
Outlet Ø 0.879
Maintenance
Inspect all cooling system coils at the beginning of the cooling season or more often if
needed. Follow the cleaning instructions below. If additional cleaning is required or if a
coil must be removed for any reason, consult the factory. Be prepared to provide rating
plate and installation information.
Condenser Coil Access - The bank of condensing coils is located on top of the unit.
Condenser Coil Cleaning Instructions:
1) Verify that the electrical power has been turned off and the disconnect switch
locked.
2) Use a soft brush to remove any dirt and debris from the coils.
3) Spray with cold or warm (not hot) water and a cleaning solution (non-acid based
coil cleaner is recommended). Due to possible damage to the coil, do not use high pressure spray.
4) When clean, rinse with cool, clean water.
Evaporator Coil Access - The evaporative coils can be accessed by opening the coil
cabinet door.
Inspect coils for debris, dirt, grease, lint, pollen, mold, or any element which would
obstruct heat transfer or airow. Inspect coils and tubing for physical damage. Inspect
feeders, piping connections, coil headers, and return bends for signs of fatigue, rubbing, and physical damage.
Clean the coils annually, or more often if needed. Use the proper tools and follow the
instructions carefully to avoid damaging the coil. Use of a non-acid based coil cleaner
is recommended. Due to possible damage to the coil, high pressure spray is not recommended.
FIGURE 4 - Coil Circuits (Views are from the control side of the system.)
Evaporator Coil Cleaning Instructions:
1) Verify that the electrical power has been turned off and the disconnect switch
locked.
2) Open the access panels.
3) Use a soft brush to remove any dirt and debris from both sides of a coil.
4) Spray with cold or warm (not hot) water and a cleaning solution (non-acid based
coil cleaner is recommended). Due to possible damage to the coil, high pressure
spray is not recommended. First spray the leaving airow side, then the inlet
airow side.
As much as possible, spray the solution perpendicular to the face of the coil.
Follow the instructions on the cleaning solution. When cleaning process is
complete, rinse both sides with cool, clean water.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 7
3.0 Maintenance/Service Procedures (cont'd)
Condenser Coils by Circuit
Condenser Coils by Circuit
ADA
B
C
D
A
B
C
10 ton MC Coil
5 ton MC Coil
10 ton MC Coil
15 ton MC Coil
15 ton MC Coil
Inlet 1
Ø 0.881
Inlet 1Ø 0.879
Inlet
Ø 0.881
Inlet 2
Ø 0.881
Inlet 2Ø 0.879
Inlet 1
Ø 0.881
Inlet 2
Ø 0.881
Outlet
Ø 0.881
Outlet
Ø 0.881
Outlet Ø 0.879
Outlet
Ø 0.881
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Discharge
Line Ø 0.500
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Liquid Line Ø 0.875
Liquid Line
Ø 0.875
Liquid Line Ø 0.875 Liquid Line Ø 0.875
Liquid Line Ø 0.500
Liquid Line Ø 0.875
Filter Drier
Filter Drier
Filter Drier
Filter Drier
Filter Drier
Filter Drier
A
D
B
C
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Discharge
Line Ø 0.875
Liquid Line
Ø 0.875
Liquid Line
Ø 0.875
Liquid Line Ø 0.875
Liquid Line Ø 0.875
Filter Drier
Filter Drier
Filter Drier
Filter Drier
Outlet
Ø 0.881
Outlet
Ø 0.881
Outlet
Ø 0.881
Outlet
Ø 0.881
Inlet
Ø 0.881
Inlet 2
Ø 0.881
Inlet 1
Ø 0.881
Inlet 2
Ø 0.881
Inlet 1
Ø 0.881
Inlet
Ø 0.881
10 ton MC Coil
10 ton MC Coil
15 ton MC Coil
15 ton MC Coil
(See compressor locations on page 12.)
(See compressor locations on page 12.)
(See compressor
locations on page 12.)
Evaporator Coils by
Circuit (interlaced)
Evaporator Coils by
Circuit (interlaced)
A
C
D
A
C
D
A
C
D
All three
outlets
Ø 1.380
All four
outlets
Ø 1.380
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 0.875
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 1.375
RCB/RDCB/RECB 480 and
RDB/RDDB/REDB 538, 564, and 602
RCB/RDCB/RECB 360 and RDB/RDDB/REDB 418, 444, and 484
RCB/RDCB/RECB 600 and
RDB/RDDB/REDB 658, 684, and 722
A
B
D
C
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 1.375
(To TXV valves and
Distributors on
Evaporator Coils)
(To TXV valves and
Distributors on
Evaporator Coils)
(To TXV valves and Distributors
on Evaporator Coils)
Condenser Coils by Circuit
15 ton MC Coil
Inlet
Ø 0.506
Outlet Ø 0.506
Inlet
Ø 0.879
Outlet Ø 0.879
Outlet Ø1.380
Outlet Ø1.380
Outlet Ø 0.879
3.4 Coil Maintenance (cont'd)
FIGURE 4 (cont'd) - Coil Circuits (Views are from the control side of the system.)
RCB/RDCB/RECB 720 and
RDB/RDDB/REDB 722, 804, and 842
Evaporator Coils by
Circuit (interlaced)
A
C
D
B
All four
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 8
outlets
Ø 1.380
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 1.375
Suction Line Ø 1.375
Filter Drier
Filter Drier
Filter Drier
Filter Drier
on Evaporator Coils)
(To TXV valves and Distributors
A
15 ton MC Coil
Inlet 2
Ø 0.881
Inlet 1
Ø 0.881
Liquid Line
Ø 0.875
Liquid Line
Ø 0.875
(See compressor locations on page 12.)
Condenser Coils by Circuit
Inlet 1
D
Ø 0.881
15 ton
Inlet 2
Outlet
Ø 0.881
Discharge
Line Ø 0.875
Liquid Line Ø 0.875
Liquid Line Ø 0.875
MC Coil
Outlet
Ø 0.881
Ø 0.881
Discharge
Line Ø 0.875
Inlet 1
Ø 0.881
15 ton
MC Coil
Inlet 2
Ø 0.881
Discharge
Outlet
Ø 0.881
Line Ø 0.875
B
15 ton MC Coil
Outlet
Ø 0.881
C
Inlet 2
Ø 0.881
Inlet 1
Ø 0.881
Discharge
Line Ø 0.875
3.5 Check
Refrigerant
Pressure and
Temperatures
(subcooling and
superheat)
DANGER
The refrigeration circuits are high pressure systems. Hazards
exist that could result in personal injury or death. Removal,
installation, and service of this scroll compressor must be
performed by a technician qualied in R-410A refrigerant.
DO NOT USE tools or service equipment designed for R22
refrigerant. See Hazard Levels, page 2.
Check SUBCOOLING
Measure and record temperature and pressure of the liquid line at the condenser coil
outlet.
STEP 1) Record Measurements: Temperature = ________°F (°C) and
Pressure = ________ psig
STEP 2) From Temperature/Pressure Conversion Chart (page 10), convert
Measured Pressure (STEP 1) to ________°F (°C)
STEP 3) Subtract Measured Temperature (STEP 1) from Temperature from
Recommended superheat at is 8 to 12 degrees F (4.5 to 6.7
degrees C).
Typically, too much superheat indicates that the evaporator coil is undercharged.
Too little superheat typically indicates that the evaporator coil is overcharged and
may potentially ood liquid refrigerant to the compressor. To reduce the superheat,
adjust the thermal expansion valve by turning the adjusting stem counterclockwise.
To increase the superheat, adjust the thermal expansion valve by turning the adjusting stem clockwise.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 9
3.0 Maintenance/Service Procedures (cont'd)
3.5 Check Refrigerant Pressure and Temperatures (subcooling and superheat)
(cont'd)
The refrigeration circuits are high pressure systems.
Hazards exist that could result in personal injury or death. It
is therefore required that the removal and installation of this
scroll compressor be performed by a technician qualied in
R-410A refrigerant. See Hazard Levels, page 2.
Never use oxygen to pressurize a refrigeration system. Oxygen
can explode on contact with oil and could result in personal injury
or death. When using high pressure gas such as nitrogen for
this purpose, ALWAYS USE A PRESSURE REGULATOR that can
control the pressure down to 1 or 2 psig. Failure to use a regulator
will result in extremely high pressure which could exceed the
burst pressure of the compressor or other system components
and result in personal injury or death. See Hazard Levels, page 2.
DANGER
DANGER
WARNINGS
For your safety, wear eye protection, gloves, and protective clothing
when handling refrigerant and oil and when brazing. Have a re
extinguisher nearby. See Hazard Levels, page 2.
Compressor Handling
Do not lift compressor by copper tubing. To prevent internal damage, compressors
must ALWAYS be held upright.
The following instructions include major points of consideration that will ensure proper
installation and protect you from potential personal injury. Please use the following 13
steps as a checklist, taking each item in order before proceeding to the next. If more
information is required, contact the Reznor Service Department for Reznor® products.
WARNING
To avoid electrical shock, power to the com-pressor(s) MUST REMAIN
OFF during performance of Steps 1 through 9 below. LOCK DISCONNECT
SWITCH OFF (open).
Step 1. Verify Proper Application
Verify that the replacement compressor is identical to the model being replaced.
All system components are matched to the compressor. Replacing a compressor
with a model other than the one specied for replacement will void the product
warranty. See part numbers for R-410A compressors on page 13.
Step 2. Determine Cause of Initial Failure and Remove the
Compressor
In order to prevent a second failure, the cause of the original failure must be
determined. Identify the cause and make the necessary repairs.
CAUTION: DO NOT LIFT compressor by copper tubing; damage will
occur. Compressor must remain upright.
WARNING
Wear eye protection and gloves when handling refrigerant or oil and
when brazing.
a) BEFORE REMOVING THE FAULTY COMPRESSOR, remove refrigerant charge
using proper recovery procedures. Call 1-800-441-9450 for the name of the nearest
Dupont authorized distributor or 1-800-ASK-KLEA (IGI) for information on their refrigerant reclaim programs.
b) Disconnect wires. All compressor wiring is connected using a black molded
plastic plug. Remove the plug from the compressor.
c) Open access ports so that pressure does not build up in the system. Before
unbrazing stubs from the compressor, cut suction and discharge tubing with a
tubing cutter.
WARNING
Have a re extinguisher near. The compressor contains oil. There is a
risk of re when unbrazing stubs.
Use a high temperature torch to disconnect the suction line and the discharge line from
the compressor.
d) Remove the mounting bolts and the compressor. Save the mounting hardware
to attach the grommets and sleeves shipped with the replacement compressor.
e) To test for acid and to assure excess oil does not remain in the circuit, remove
oil from the failed compressor. Measure the amount of oil.
CAUTION: In addition to the required eye protection and gloves, care
should be taken in handling POE oil because it may cause damage to
certain plastics and roong materials. See Hazard Levels, page 2.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 11
3.0 Maintenance/
Reheat compressor in
Models RDB and RDDB
A
C
B
DH or E
D
Condenser
Bank B & C
Condenser
Bank A & D
Service
Procedures
(cont'd)
3.6 Compressor Maintenance (cont'd)
Step 2. Determine Cause of Initial Failure (cont'd)
Compressor Oil Charge (POE Oil)
Compressor
Model
ZP57K3E153852
ZP83KCE165656
ZP120KCE3135106
ZP182KCE3135106
ccoz
Important NOTES: These R-410A compressors use a polyolester (POE)
lubricant. Types of recommended POE oil are Copeland Ultra 22 CC, Copeland Ultra
32 CC, Copeland Ultra 32-3MAF, Mobil EAL™, Arctic 22 CC, Uniqema Emkarate RL32CF,
or Uniqema RL32-3MAF.
POE oil absorbs moisture much quicker and to a greater degree than standard
mineral oil. The compressor must not be left open longer than 15 minutes
during replacement. During installation the system must be swept with an inert
gas such as dry nitrogen to keep moisture from entering the compressor and
prevent the formation of oxides.
If the oil taken from the compressor and measured is found to be signicantly
lower than listed in the table above, clean the excess oil through use of suction
and liquid line lter driers. Beginning in Step 4, follow the same procedure
as for burnout cleanup.
Use an acid test kit to check the oil for acid. If acid is found, beginning in
Step 4, follow procedures indicated for burnout cleanup.
Dispose of oil and compressor using an approved environmentally safe
disposal method.
□ Step 3. Mount the Replacement Compressor
Do not remove the dust cover or rubber shipping plugs until all other system
connections are complete (i.e. new liquid line lter drier(s) installed and all tubing
changes made - see Steps 4 and 5). The amount of time the compressor is open
to the atmosphere must be kept to a minimum.
Use the new mounting grommets and sleeves that are shipped with the
compressor to mount it. The sleeves will prevent over compression of the
grommets. Re-use the mounting bolts from the compressor that was removed. The
mounting bolts will bottom out when tight.
FIGURE 5 - Identication of Compressors by Location
Compressor
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 12
Compressor Staging for Cooling (applies to Models RCB, RDB, RDCB, RDDB RECB, REDB)
MAPSIII
Cabinet D
360
418
444
484
480
538
564
602
600
658
684
722
720
804
842
DH or E (RDB/RDDB/REDB 418)5
DH or E (RDB/RDDB/REDB 444)7
DH or E (RDB/RDDB/REDB 484)10
DH or E (RDB/RDDB/REDB 538)5
DH or E (RDB/RDDB/REDB 564)7
DH or E (RDB/RDDB/REDB 602)10
DH or E (RDB/RDDB/REDB 658)5
DH or E (RDB/RDDB/REDB 684)7
DH or E (RDB/RDDB/REDB 722)10
DH or E (RDB/RDDB/REDB 804)7
DH or E (RDB/RDDB/REDB 842)10
CompressorCooling Staging
CircuitTonnage12345678
A10
C5
D15
A10
C15
D15
A10
B10
C15
D15
A15
B15
C15
D15
CAA+CDC+DA+C+D
ADA+DC+DA+C+D
BDA+BA+DC+DA+B+D B+C+D A+B+C+D
BB+CB+C+D A+B+C+D
Compressor Model
and P/N by Tonnage
and Voltage
Compressor
Model
ZP57K3E5216686216686216687216688
ZP83KCE7216689216689216690216691
ZP120KCE10216695216695216696216697
ZP182KCE
Wiring Harness
Crankcase HeaterP/N 216402P/N 216404 P/N 216405
ARI Tonnage
15216454216454216455216456
One each for each
compressor
208V230V460V575V
P/N 223028P/N 223029 P/N 223030
Compressor P/N
□ Step 4. Install New Filter Driers (Select procedure that applies.)
IF the oil measured in Step 2 was not signicantly less than the amount shown
in the table on page 12 or the test for acid in Step 2 did NOT indicate burnout ,
install a new R-410A refrigerant liquid line lter drier. The lter drier must be rated
for no less than 600 psig and be the proper size for the circuit. Because R-410A
refrigerant requires POE oil which absorbs moisture quickly, it is important to
change the lter drier any time the circuit is opened.
It is recommended to use a tubing cutter when cutting out a lter drier as the
desiccant absorbs and holds moisture better when it is cool. Heat from a torch may
cause moisture to leave the lter and be absorbed in the oil. Be careful to keep
dirt, lings, and other contaminants out of the system.
Continue to Step 5.
IF the oil measured in Step 2 was signicantly less than shown in the table on
page 12 or the test for acid in Step 2 did indicate compressor burnout, do the
following:
a) Install a liquid line lter drier. If there is acid, install an acid removing lter drier.
Size the acid-removing lter drier at least one capacity size larger than normally
required for the circuit.
b) Install a temporary lter drier in the suction line. When there is acid, a 100%
activated alumina suction lter drier is recommended. The suction line drier
should be sized properly for the circuit and have a service access tting to
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 13
3.0 Maintenance/
Service
Procedures
(cont'd)
3.6 Compressor
Maintenance
(cont'd)
□ Step 4. Install New Filter Driers (cont'd)
monitor pressure drop across the drier. (NOTE: Suction line lter drier must be
removed after 72 hours of operation.)
Step 12 includes the remaining procedures required for cleanup of a burnout. Continue to Step 5.
□ Step 5. Braze on Suction and Discharge Lines
CAUTION; Do not leave system open to the atmosphere any
longer than minimum required for installation. POE oil in the
compressors is extremely susceptible to moisture absorption.
Always keep ends of tubing sealed during installation. See Hazard
Levels, page 2.
Brazing materials must be able to withstand the high pressure of R-410A refrigerant.
A high temperature, silver phosphate type brazing with 5% or greater alloy is recommended.
To prevent oxidation, purge tubing with 2-3 psig of regulated dry nitrogen while it is
being brazed. Open the service valve as needed to release the nitrogen. Do not allow
moisture to enter the system.
The installer is responsible for brazing and for complying with appropriate standard
refrigerant piping procedures.
CAUTION:All brazing should be done using a 2 to 3 psig dry
nitrogen purge owing through the pipe being brazed. See Hazard
Levels, pg 2.
CAUTION: When brazing, protect all painted surfaces and
components from excessive heat. Wet wrap all valves but do not
allow moisture to enter the tubing. See Hazard Levels, page 2.
□ Step 6. Check System for Leaks
After installation is complete, pressurize the circuit to approximately 75 psig using
nitrogen and a few ounces of refrigerant. Check for leaks using soap bubbles or
other leak-detecting methods.
□ Step 7. Evacuate the Circuit
Evacuate one circuit at a time. Use a vacuum pump and micron gauge. Each
circuit must be evacuated to hold a 500 micron vacuum. Vacuum must be pulled
on both the discharge (high) and suction (low) side. Do the suction side rst; and
the compressor discharge side second. To establish that a circuit is leak-free
and moisture-free, a standing vacuum test is recommended. Close off the valve
to the vacuum pump and observe the micron gauge. If the vacuum gauge does
not rise above 500 microns in one minute, the evacuation should be complete.
If the vacuum gauge does rise above 500 microns in one minute, evacuation
is incomplete or the circuit has a leak. Repeat as needed until evacuation is
complete. The evacuation process must be done on each circuit.
NOTE: Evacuation will not remove moisture from POE oil. Moisture must be
prevented from getting in the oil.
Continue and/or repeat Steps 6 and 7 until evacuation is complete.
CAUTION: Do not use the replacement compressor as an
evacuation assist and never apply voltage to a compressor while
it is in a vacuum. See Hazard Levels, page 2.
Moisture and air are harmful to the system because they increase the condensing
temperature, raise the discharge gas temperature, cause formation of acids, and
cause oil breakdown.
Form O-MAPSIII Cabinet D, P/N 222918R9, Page 14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.