Reznor LCSC-3E 30, LCSC-3E 45, LCSC-3E 60, LCSC-3E Series, LCSC-3E 20 Installation, Commissioning, Servicing And User Instructions

...
1801LCSC-3EE--EN
Gas-Fired, Balanced-Flue or Power-Vented Unit Heater
LCSC-3E
Installation, commissioning, servicing & user instructions
These appliances meet the following EC Directives
DIR 2009/142/EC : GAD
DIR 2014/30/EC : EMC
DIR 2014/35/EC : LVD
DIR 2006/42/EC : MD
Applies to
Austria, Belarus, Bulgaria, China, Czech Republic, Croatia, Cyprus, Denmark, England, Estonia, Finland,
Germany, Greece, Hungary, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Norway, Poland, Romania,
Russian Federation, Serbia, Slovakia, Slovenia, South Africa, Spain, Sweden, Turkey, Ukraine
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. All work must be carried out by appropriately qualified persons. The manufacturer does not take any responsibility in the event of non-observance of the regulations concerning the connection of the apparatus causing a dangerous operation of the apparatus, possibly resulting in damage to the apparatus and/or environment in which the unit is installed.
Please read this document carefully before commencing installation commissioning and/or servicing. Leave it with the user or attached to the appliance or gas service meter after installation.
LCSC-3E--EN 1/40
TABLE OF CONTENTS
r
1.0 INTRODUCTION
1.1 Basic Information
1.2 Warranty
2.0 SPECIFICATIONS
2.1 Technical data
2.2 Burner pressure
2.3 Blower curves
2.4 Blower options
2.5 Dimensions
3.0 GENERAL REQUIREMENTS
3.1 Related Documents
3.2 Heater Location
3.3 Combustion Air Inlet Pipe and Flue Pipe
3.4 Air Supply
3.5 Air Distribution System
3.6 Electrical Supply
3.7 Gas Supply
4.0 INSTALLATION
4.1 Uncrating and Preparation
4.2 Suspending the Heater
4.3 Fitting the Combustion Air Inlet/Flue Pipe System
4.4 Gas Connection
4.5 Electrical Connections
4.6 Room Thermostat Siting
5.0 AIR DISTRIBUTION
6.0 COMMISSIONING AND TESTING
6.1 Electrical Check
6.2 Gas Connection
6.3 Suspension and Support
6.4 Lighting the Heater
6.5 Heater pipe work
6.6 Adjustments
6.6.1 Burner Gas Adjustment
6.7 Air Distribution System
6.8 Heater Controls
6.9 Handing Over
7.0 SERVICING INSTRUCTIONS
7.1 Servicing Procedure
8.0 REMOVAL AND REPLACEMENT OF PARTS
8.1 Main Burner Removal
8.2 Main Burner Injectors
8.3 Ignition System
8.4 Operating Gas Valve
8.5 Limit Controls
8.6 Combustion Air Pressure Switch
8.7 Combustion Air Fan
9.0 FAULT FINDING
10.0 PARTS LIST
11.0 GAS CONVERSION
12.0 USERS INSTRUCTIONS
13.0 HEALTH & SAFETY STATEMENT
HAZARD INTENSITY LEVELS
DANGER Failure to comply will
result in severe
dange
WARNING Failure to comply could
CAUTION Failure to comply
WARNING: The electrical isolator should only be used in an emergency and should not be used for closing down the main burner, as it switches off the fan prematurely and may damage the heat exchanger, invalidating the warranty.
ATTENTION: This appliance is not intended for use by persons (including children) with reduced sensory or mental capacities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
personal injury or death and/or property damage.
result in severe personal injury or death and/or property damage
could result in minor personal injury and/or property damage.
INTRODUCTION
1
1.1 Basic Information
The instructions in this manual apply to Model LCSC-3E gas-fired/fan-assisted warm air heaters. These models have an axial fan for air delivery. These heaters are designed for overhead suspension and are suitable for indoor installation only installed at an operation ambient temperature between -15°C and 45°C. When installed as a type C12/C32 and where
LCSC-3E--EN 2/40
the height above floor level is greater than 1.8 meters measured to the underside of the appliance they may be used as a garage air heater. This appliance must be installed in accordance with the rules in force. Before installation, check that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible. A permanent electricity supply of 230 volts, 50 Hz,
single phase is required.
Heaters are approved for: Type C12 horizontal vent for balanced-flue heaters; Type C32 vertical vent for balanced-flue heaters; Type B 22 vertical vent;
When the external control calls for heat, an electronic control begins the ignition sequence to provide for a safe start..
About 30 seconds after the call for heat, the fan will begin circulating warm air. The electronic control will supervise the flame during the entire heating cycle to ensure safe operation. When the required room temperature is reached, the main burner will shut down leaving the fan running to cool down the heat exchanger. After approximately 45 seconds, the fan delay relay will turn off the fan.
1.2 Warranty: Warranty is void if:
a) LCSC-3E heaters are installed in atmospheres containing flammable vapors or atmospheres
containing chlorinated or halogenated hydrocarbons or atmospheres containing any silicone, aluminum oxide, etc., that adheres to spark ignition flame sensing probes.
b) The installation is not in accordance with these instructions.
TECHNICAL DATA
2
2.1 Specifications
Table 1a : Technical data
LCSC-3E
20 30 45 60 75 100
Comb. Air & Flue Type B (1) Comb. Air & Flue Type C (1)
C12, C32, C42, C82
B22P
Connection colars mm 100 100 130 130 130 130 Heat inputs Hs kW 26,42 31,63 54,38 73,25 87,85 114,87 Heat inputs Hi kW 23,80 28,50 49,00 66,00 79,15 103,50 Heat output kW 21,82 25,99 44,64 60,92 73,13 94,50 Thermal efficiency % 91,70 91,20 91,10 92,30 92,39 91,30
Gas consumption G20 m3/h 2,52 3,02 5,19 6,98 8,38 11,19 Gas consumption G31 kg/h 1,86 2,22 3,82 5,15 6,17 8,24 Gas pipe connection (2) inch
½" ¾"
ESP MIN Press Pa 50 50 50 100 150 100 ESP MAX Press Pa 200 300 200 200 350 300 Air flow measured m3/h 2248 2741 4023 5573 7079 8068 Temperature rise (3) K 28 28 32 32 30 34
Electrical service (protection IP20)
230/240V 1N 50Hz 230/240V 1N 50Hz
400V 3P
50Hz Blower electrical rating W 660 1250 1410 1700 3070 3200 Total electrical rating W 770 1370 1530 1810 3180 3320 Blower Weight kg 14,5 20,5 27 26 41 45 Unit Weight kg 54 55,8 87 99 109 155 Total Weight kg 68,5 76,3 114 125 150 200
(1) Gas appliance Classifications for approved venting methods based on CEN report CR 1749:2001. (2) There is a difference between the gas connection diameter and the diameter of the supply line. Always use the most
adequate diameter of the supply line to minimize the pressure drop through the gas pipes – if necessary, reduce the diameter of the supply line at the inlet of the unit.
(3) Figure for isothermal conditions.
LCSC-3E--EN 3/40
Table 1b : Gas categories
Country Gas category Country Gas category
Austria II2H3P Montenegro II2H3+
Belarus II2H3+ New Zealand II2H3+
Bulgaria I2H or I3P Norway II2H3 B/P
China II2H3+ Poland II2E3P
Czech republic II2H3+ Portugal II2H3+
Croatia II2H3P Romania II2H3 B/P
Cyprus II2H3+ Russian Federation I2H or I3P
Denmark II2H3 B/P Serbia II2H3+
England II2H3+ Slovakia II2H3+
Estonia II2H3+ Slovenia II2H3+
Finland II2H3 B/P South Africa II2H3+
Germany I2ELL Spain II2H3+
Greece II2H3+ Sweden II2H3 B/P
Hungary II2HS3P Turkey II2H3+
Iceland II2H3+ Ukraine I2H or I3P
Latvia II2H3+
Lithuania II2H3+
2.2 Burner pressure & injector size
Table 2:
Belarus, China, Croatia, Czech Republic, Cyprus, England, Estonia, Greece, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Portugal, Serbia, Slovenia, Slovakia, South Africa, Spain , Turkey, Poland
LCSC-3E
Special Poland
LCSC-3E
Burner pressures & injector sizes
Injector quantity 5 6 10 8 10 12
Injector size
G20
Nat. Gas
Prop. Gas
Burner pressure (1) mbar 8,00 7,25 6,90 8,50 8,30 7,50
Inlet pressure mbar
Injector quantity
Injector size
G31
Burner pressure (1) mbar
Inlet pressure mbar
Injector quantity
Injector size
G27
Burner pressure (1) mbar
Inlet pressure mbar
Injector quantity
Injector size
G2,350
Burner pressure (1) mbar
Inlet pressure mbar
(1) with open service door
Model2030 456075100
mm 2,10 2,10 2,20 2,70 2,70 2,90
marking 210 210 220 270 270 290
20
561081012
mm
marking
Model2030 456075100
mm
marking
mm
marking
1,15 1,15 1,15 1,50 1,45 1,50
115 115 115 150 145 150
34,20 34,40 35,90 35,20 35,40 34,40
37
5610-10-
2,40 2,40 2,40 - 3,00 -
240 240 240 - 300 -
8,30 8,20 8,25 - 9,25 -
20
5610-10-
2,60 2,60
260 260
8,25 8,45
2,60
260
8,40
13
-
-
-
3,90
390
5,25
-
-
-
LCSC-3E--EN 4/40
Austria, Germany, Hungary, Russian Federation, Ukraine
LCSC-3E
Injector quantity
Injector size
G20
Nat. Gas
Prop. Gas
Bulgaria, Denmark, Finland, Norway, Sweden
LCSC-3E
Nat. Gas
Prop. Gas
Burner pressure (1) mbar 8,00 7,25 6,90 8,50 8,30 7,50
Inlet pressure mbar
Injector quantity
Injector size
G31
Burner pressure (1) mbar
Inlet pressure mbar
(* ): Inlet pressure for Hungary = 25mbar
(**): no nat gas for Germany
Injector quantity 5 6 10 8 10 12
Injector size
G20
Burner pressure (1) mbar 8,00 7,25 6,90 8,50 8,30 7,50
Inlet pressure mbar
Injector quantity
Injector size
G31
Burner pressure (1) mbar
Inlet pressure mbar
Model2030 456075100
561081012
mm 2,10 2,10 2,20 2,70 2,70 2,90
marking 210 210 220 270 270 290
561081012
mm
marking
Model2030 456075100
mm 2,10 2,10 2,20 2,70 2,70 2,90
marking 210 210 220 270 270 290
mm
marking
1,15 1,15 1,15 1,50 1,45 1,50
115 115 115 150 145 150
34,20 34,40 35,90 35,20 35,40 34,40
561081012
1,15 1,15 1,15 1,50 1,45 1,50
115 115 115 150 145 150
34,20 34,40 35,90 35,20 35,40 34,40
20(*)
50
20
30
Romania
LCSC-3E
Injector quantity 5 6 10 8 10 12
Injector size
G20
Nat. Gas
Prop. Gas
(1) : with open service door
Burner pressure (1) mbar 8,00 7,25 6,90 8,50 8,30 7,50
Inlet pressure mbar
Injector quantity
Injector size
G31
Burner pressure (1) mbar
Inlet pressure mbar
Model2030 456075100
mm 2,10 2,10 2,20 2,70 2,70 2,90
marking 210 210 220 270 270 290
20
561081012
mm
marking
1,15 1,15 1,15 1,50 1,45 1,50
115 115 115 150 145 150
34,20 34,40 35,90 35,20 35,40 34,40
30
LCSC-3E--EN 5/40
2.3 Blower curves LCSC-3E
LCSC-3E--EN 6/40
LCSC-3E--EN 7/40
LCSC-3E--EN 8/40
2.4 Blower options LCSC-3E
2.4.1 Mixing cabinet LCSC-3E
Damperposition
Bottomexit Rearexit
closed open
open closed
half half
LCSC-3E--EN 9/40
LCSC-3E--EN 10/40
LCSC-3E--EN 11/40
2.4.2 Mixing cabinet and filters LCSC-3E
LCSC-3E--EN 12/40
LCSC-3E--EN 13/40
LCSC-3E--EN 14/40
2.4.3 Free blowing
Freeblowing Dimensions[mm]
LCSC3E Restriction
partno 20 ‐‐ 30 1002436 58 70 240 45 1002437 154 154 320 60 1002438 130 154 320 75 1002439 130 154 396 100 1002440 166 178 396
A B C
LCSC-3E--EN 15/40
2.5 Dimensions standard unit
LCSC-3E--EN 16/40
Dimensions unit with mixing cabinet (option 526)
LCSC-3E--EN 17/40
GENERAL REQUIREMENTS
d
3
3.1 Related documents
It is important that all gas appliances are installed in accordance with the rules in force and by appropriately qualified persons. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure compliance with the law.
3.2 Heater location
The location chosen for the air heater must permit the provision of a satisfactory flue system venting to outdoor atmosphere and adequately ventilated to provide for combustion air. The location must also provide sufficient space to allow the heater to be serviced.
Table 3 Minimum installation clearances (mm)
LCSC-3E 100
Top 150 Flue connector 150 Access panel 500 Non access si Bottom 150 Rear* 250
* Measure rear clearance from the back of the blower
Table 4 Recommended mounting heights to underside (m) (*)
LCSC-3E 20
Mounting height 3 4 5
* Height from floor to bottom surface of heater. These
are recommendations only. Positioning of heaters depends on application.
150
3045
others
Where air heaters are located in the center of the space to be heated, the air should be discharged toward outside walls. In large areas, they should be located to discharge air along outside walls with additional heaters provided to blow air into the center of the area.
In places where infiltration of cold is excessive, such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the source of cold air from a distance of 4,5 - 6,0m
Air heaters should not be installed in corrosive atmospheres, i.e. near plating or degreasing plants or in areas where there is a fire risk.
Do not locate the air heater where it may be exposed to water spray, rain, etc.
3.3 Combustion air supply & flue system
The air heater may be installed as a balanced flue (Type C) heater requiring both a combustion air inlet duct and a flue pipe or as a power vented (Type B) heater, which requires only a flue pipe exhausting to outdoors. All products of combustion must be flued to outdoor atmosphere.
Figure 2a: Combustion air and flue pipe sockets
Air heaters should, where ever possible always be installed to blow toward or along external wall surfaces. Where two or more air heaters are installed in the same room, a general scheme to ensure continuous air circulation should be maintained for best results. Suspended heaters are most effective when located as close to the occupancy zone as possible, this fact should be born in mind when determining the mounting heights to be used. Care should be exercised to avoid directing warm air directly onto the occupants. Partitions, columns, counters, storage racking, etc. should be taken into account when choosing the location so that an unobstructed path for the
Legend :
1 Flue outlet socket
2 Combustion air inlet opening 3 Gas connection inlet with sealing ring
4 Electrical connections
air circulation can be maintained.
LCSC-3E--EN 18/40
Each heater installed as a type B appliance must be fitted with an individual flue pipe and the combustion air inlet opening must be provided with a protection grill (ask your distributor for the appropriate protection grill (IP20) (dia130 = PN 02 25094 ). Each heater installed as a type C appliance must be fitted with an individual combustion air/flue pipe system. Only systems specified by the air heater manufacturer may be used.
Common flue and combustion air systems must not be used
IMPORTANT: The flue must be installed in accordance with national and local regulations. Failure to provide proper flueing could result in death, serious injury and/or property damage. The air heater must be installed with a flue to the outside of the building. Safe operation of any power vented gas apparatus requires a properly operating flue system, correct provision for combustion air, and regular maintenance and inspection.
3.3.1 Flues for power vented installations (Type B appliances)
If the air heater is to be installed as a type B appliance, air for combustion will be taken from within the space where the heater is installed. Ensure that an adequate air supply for combustion and ventilation is provided within the building in accordance with the regulations & rules in force.
Table 5 shows flue pipe sizes and maximum pipe lengths. The minimum flue length is 0.5 meters.
Table 5 Flue pipe diameters & maximum lengths
LCSC-3E other sizes
Heater socket & mm pipe dia Maximum straight m
length
Equivalent length m of 45° elbow Equivalent length m of 90° elbow
20 & 30
100
130
9
0.75
1.5
Single wall flue pipes are required. All joints must be sealed to prevent products of combustion from leaking into the building. An approved flue terminal is required.
If the flue passes through a combustible element of the building it must be enclosed by a sleeve of non-combustible material and separated from the sleeve by at least a 25 mm air break.
The temperature of any combustible material near to the flue must not exceed 65°C when the heater is in operation. The flue must be at least 50 mm away from any combustible material.
Single wall flue pipe exposed to cold air or run through unheated areas must be insulated. Where condensation is unavoidable, provision must be made for the condensation to flow freely to a point to which it can be released, i.e. a drain or gully. The condensation drain from the flue must be constructed from non-corrodible material not less than 20 mm diameter. Copper or copper based alloys must not be used for condensation drains.
3.3.2 Combustion air inlet pipe & flue pipe for balanced flue installation (Type C appliances)
Balanced flue air heaters are designed to be fitted with a combustion air inlet pipe that obtains outdoor air and a flue pipe that exhausts flue products to outdoors.
Air heaters if fitted with a power venter permitting either a vertical or horizontal combustion air inlet/flue pipe system. The
heaters must be installed with a concentric vertical or horizontal flue/combustion air inlet. The heaters are only approved for use when installed with the appropriate approved concentric vent terminal. See table 6.
Both the flue and combustion air pipes must be sealed. Use gasket sealed seamless aluminum pipe or equivalent. The flue pipe must include a re-sealable test port to allow good average sampling of the flue gas mixture for testing, the port must be at least 450 mm away from the air heater flue connection socket.
Follow any flue pipe manufacturers’ installation instructions for making joints, including connections to the air heater, for passing through a building element and for support requirements. If more than one air heater is being installed in the same place each heater must have a separate flue system. Where condensation is unavoidable, provision must be made for the condensation to flow freely to a point to which it can be released, i.e. a drain or gully. The condensation drain from the flue must be constructed from non-corrodible material not less than 20 mm diameter. Copper or copper based alloys must not be used for condensation drains.
LCSC-3E--EN 19/40
Figure 2b : Combustion air and flue pipe sockets, Type C
1 Flue pipe outlet collar
2 Combustion air pipe inlet collar
Table 6 Combustion air inlet & flue pipe requirements
LCSC3E
Heatersocket&pipedia
1
2
2030 Othersizes
mm Fluepipe/Inletpipe 100 130
Maxstraightlength
Equivalentlengthof45° elbow
Equivalentlengthof90° elbow
90°elbow
mFluepipe/Inletpipe 9 9
mFluepipe/Inletpipe 0,75 0,75
mFluepipe/Inletpipe 1,5 1,5
mFluepipe/Inletpipe 1,5 1,5EquivalentLengthof
LCSC-3E--EN 20/40
3.4 Air supply
Figure 2c: Combustion air and flue pipe sockets, Type B
It is important to ensure that there is an adequate air supply at all times for both combustion and heating requirements. Modern constructions involve the greater use of insulation, improved vapor barriers, and weather proofing. This practice means that buildings are sealed much tighter than in the past.
1 Flue pipe outlet collar
2 combustion air inlet opening
The combustion air supply for a power vented gas fired air heater (Type B installation) can be affected by lack of air supply. Natural infiltration may not be adequate. Use of extract fans aggravates this situation. It is important to ensure that there is an adequate air supply at all times. Reliance on doors and windows is not allowed. Always ensure that an adequate inlet for fresh air for combustion is provided sized to suit the total installation of any combustion apparatus. Fit an access guard to the combustion air inlet on the back of the heater and take appropriate action to ensure that it remains unblocked. See figure 2c.
WARNING: This model air heater is installed as a type B application and is designed to take air for combustion from the space in which it is installed. Do not restrict the combustion air intake.
3.5 Air distribution
Follow recommended practice for building air distribution. The following notes are of particular importance:
"Where free blowing air heaters are installed it
must be taken into account that heated air is buoyant when it leaves the appliance, therefore, air patterns within the space being heated will modify the air throw pattern achieved.
having low heat loss where single heaters are required to cover a large floor area and in buildings with high ceiling heights, air re-circulation fans e.g. Maximizors may be fitted to ensure even heat distribution and minimize stratification. Care should be taken to avoid impeding air flow with storage racking, partitions, etc."
In building
3.6 Electrical supply
Wiring external to the air heater must be carried out in accordance with the rules if force and by appropriately qualified persons. A constant 230 Volt 50 Hertz single phase fused electricity supply with neutral link is required. All heaters and controls must be earthed. A lockable isolator with contact separation of at least 3.0 mm on all poles should be installed adjacent to the appliance and within reach of any person working on the heater. When a number of heaters are to be connected as part of a single installation each heater must be provided with a separate isolator. The electrical connection to the air heater is at the back of the appliance. The final connection must be made in the terminals provided in the control compartment. Follow the wiring diagram provided with the air heater. Electrical supply cable conductor size should be 1.5 mm. Fit the cord grip supplied with the heater. The length of conductors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor.
3.7 Gas supply
LCSC-3E air heaters are designed to operate on either natural gas (G20) or propane gas (G31). Refer to the specifications in section 2 of this document and to the data plate for details of supply pressures. The gas meter and gas service must be checked by the supply undertaking to ensure that they are adequate to deal with the total
1
2
LCSC-3E--EN 21/40
load of all gas fired apparatus installed.
INSTALLATION
4
4.1 Unpacking and preparation
Prior to dispatch, the air heater was operated and tested at the factory. If the heater has incurred any damage in shipment, file a report claim within 2 working days from receipt. Check the shipping label and data plate to ensure the specification of gas and electrical supplies are compatible. Read this document and become familiar with the installation requirements and the appliance before commencing installation.
4.2 Suspending the air heater
Before installing the appliance, check to ensure that the supporting structure is adequate to carry the weight of the appliance and its ancillaries i.e. flue system. Please check weighs specified in table 1 When the heater is lifted for suspension, support the bottom of the heater with plywood or other appropriately placed material. If the bottom is not supported, damage could occur.The heater is supplied with four point suspension. All points must be used. Two threaded nut retainers are provided on each side of the top of the heater. See dimensions in section 2.2 and figure 3.Be sure that the threaded hanger rods are locked to the heater as illustrated in figure 3. Recommended maximum hanger rod length is 1.8m.
Figure 3 Suspension detail
4.3 Fitting the Combustion air inlet/Flue system
Flue pipe runs may be horizontal or vertical and terminate either through the wall or roof. See table 5 for maximum pipe length for an appliance installed as type B or table 6 for maximum lengths and approved supplied concentric terminals for a heater installed as a type C appliance. All pipe runs must be independently supported so that the heater does not carry any of the weight of the flue system.
4.3.1 Fitting the flue pipe
The flue pipe socket is located on the back of the air heater. Flue pipes must be sealed. Use seamless, aluminum pipe or equivalent. Follow pipe manufacturer's instructions (see figures 4 & 5).
Table 7 Flue pipe socket size (dia mm)
LCSC-3E 20 & 30 other sizes
Socket 100 130
4.3.2 Installing a guard on the combustion air inlet pipe for power vent (Type B installations)
The combustion air inlet socket is located at the back of the heater. When installed as a type B appliance, protect the inlet by fitting an access guard on the socket. Do not block this socket as it supplies combustion air for the burner (see figure 4).
Figure 4
Add a nut to lock the M10x1.5
hanger rod to the heater
4.3.3 Fitting the combustion air inlet pipe for balanced flue (Type C installations)
The combustion air pipe attaches directly to
IMPORTANT: Suspend the heater from the threaded nut retainers. Do not suspend from the heater cabinet panels. Do not place or add additional weight to the suspended air heater. See hazard levels, page 2.The heater must be installed in a level plane to ensure proper operation.
LCSC-3E--EN 22/40
the inlet socket at the back of the heater. Air inlet pipes must be sealed. Use seamless aluminum or equivalent. Follow the pipe manufacturer's installation instructions. See typical installations in figure 5.
Table 8 Air inlet socket size (dia mm)
LCSC-3E 20 & 30 other sizes
Socket 100 130
Figure 5
4.4 Gas connection
Connection to a gas network may only be carried out by appropriately qualified persons. The gas installation must comply with the rules in force using materials appropriate for gas installation. To facilitate servicing, the air heater must be fitted with an approved gas service tap and union fitting or union tap adjacent to the appliance. The inlet gas supply line must be installed so as to permit the access door to be opened and to allow removal of the slide out burner assembly. Air heaters suspended by flexible suspension materials or drop rods must be connected to the gas supply using an approved flexible connector. Sufficient slack must be provided in the connection to allow for movement of the appliance. Use a flexible connector of suitable size to reduce the pressure drop and the possibility of gas flow noise.
Do not use the appliance gas supply to balance or support any part of the
appliance.
Figure 6
1 Gas tube inlet sealing ring 2 Inlet gas pipe 3 Union fitting 4 Gas service tap
5 Gas pipe : Sizes 20 & 30 : Other sizes
½”
: ¾”
4.5 Electrical connections
The electrical installation may only be carried out by appropriately qualified persons observing the rules in force. All electrical connections should be made in the heater control compartment (refer to figure 9). Screw type terminals are provided. Connections should be in accordance with the terminal markings and the wiring diagram affixed to the air heater or included with this document.
THIS APPLIANCE MUST BE EARTHED!
danger
The minimum external controls required for the air heater are a room thermostat. It is essential the main input line and neutral to terminals L and N remains live at all times even when the appliance is switched off this is to ensure correct operation of the unit. An indicator light and burner reset button are fitted inside the appliance. To add a remote reset button, make connections to the terminals in the electric box as indicated on the wiring diagram.
IMPORTANT: If the reset button requires activating for any reason the cause should be identified before resetting. After resetting stay with the appliance for long enough to ensure that lock-out does not reoccur (suggest 5 minutes).Fix all electric cables and installer’s wiring to the control panel and ensure they do not touch the combustion collector box.
4.6 Room thermostat location
Do not attempt to control more than 1 air heater from a room thermostat or control panel unless a properly wired relay is fitted. Follow instructions supplied with such panels. The location of the room thermostat is important. It should not be fitted on an outside wall. Avoid location in draughty areas or where it may be influenced by heat sources e.g. the sun, process plant, etc. The thermostat or temperature sensor should be mounted on a vibration free surface and mounted about 1,5 meters above floor level. Follow the thermostat manufacturers fitting instructions. The thermostat must be suitable for switching 230 volts.
LCSC-3E--EN 23/40
AIR DISTRIBUTION
5
The LCSC-3E air heaters are fitted with adjustable horizontal louvers over the range 0
- 45 degrees from the horizontal so as to be able to direct the airflow downwards.
COMMISIONING/TESTING
6
The commissioning and testing may only be carried out by appropriately qualified persons. This section should be read and fully understood before commencing commissioning and testing.
6.1 Electrical check
After completion of the installation and before switching on the electrical supply to the appliance, a preliminary check must be carried out by a qualified electrician. The following must be checked: * Ensure that all cables & installer’s wiring
are fixed to the gas pipe & that they do not touch the combustion collector box
* Check that all wiring is connected in
accordance with the appliance circuit diagram;
* Ascertain that the correct fuse value and
cable size has been provided;
* Check to ensure that the appliance is
earthed by conducting an earth continuity test. Connect a test meter, one lead to the appliance earth terminal and the other to the mains incoming earth point at the electrical isolator. A resistance reading of 1,0 ohm or less must be indicated. If a higher reading is obtained, check all cable connections to ensure adequate security and cleanliness..If problem still exists, it may be necessary to consult the electricity supply undertaking;
* Carry out a polarity test. Connect one lead
of a suitable AC voltmeter to earth and connect the other lead to the live supply terminal (L) at the air heater. Switch ON the power to the air heater and check for correct voltage.
The same result should be obtained by
connecting the test leads between live and neutral.
Connect the voltmeter test leads to N and
E. A reading of  0V should be obtained. If these tests do not conform to the above, there is a fault which must be rectified before proceeding further with the commissioning;
* Check that a suitable thermostat or control
panel has been fitted;
LCSC-3E--EN 24/40
DO NOT ADJUST THE LOUVRES BEYOND THEIR STOPS.
* Ensure that an electrical isolator with two
pole separation with a minimum air break between poles of 3.0 mm has been fitted adjacent to the air heater.
6.2 Gas connection
Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing.
The whole of the gas service installation including the meter must be inspected, tested for soundness and purged in accordance with appropriate requirements by a qualified person.
Never use a flame for checking gas soundness.
6.3 Suspension and support
Check to ensure that the air heater is adequately suspended or supported and that no other parts have been fitted that are not independently supported and secured. For safe and correct operation, check the heater is level in both planes.
6.4 Lighting the air heater
LCSC-3E air heaters are all fitted with automatic spark ignition systems. When adequate airflow for combustion is proven by an air proving control and a pre-purge period has elapsed, the integral ignitor and multi­functional gas control operate. The ignition spark ignites the gas creating the burner flame which is detected by a flame rod sensor. If a burner flame is not detected, the ignition controller proceeds to lock-out and requires manually resetting. Lock-out is indicated by the red warning light on the air heater.
If the first reset is not successful, wait 15 seconds before attempting reset.
6.4.1 To turn the air heater "ON" The following checks should be carried out
before attempting to light the air heater. * Ensure that the gas supply to the air heater
is turned ON;
* Ensure that the electrical supply to the air
heater is switched ON;
* If fitted ensure that a time switch is set to
an ON period
* Set room thermostat to call for heat e.g. to
above room ambient temperature. The burner will now light.
The burners can be seen through the
viewing port.
* Adjust the room thermostat to the required
operating comfort temperature. The air heater will now start automatically when heat is called for by the room thermostat.
Note:
If the air heater will not start on initial start-up, the ignition controller may be in lock-out position and require resetting. This may occur especially if the appliance has been on stand-by for a prolonged period.
6.4.2 To turn the air heater "OFF" for short periods
Adjust the room thermostat to its lowest setting or 'OFF'. The fan will continue to run to cool the heater and then switch OFF automatically.
6.4.3 To turn the air heater "OFF" for long periods
Adjust the room thermostat to OFF or its lowest setting. When the fan has stopped, turn OFF the gas supply and then switch OFF the electricity supply to the air heater.
6.5 Air heater gas pipe work
The soundness of the air heater pipe work has been checked prior to leaving the factory. However during installation, connections may have been loosened. Check the soundness of the appliance pipe work using a soapy solution. If any leaks are found they must be rectified immediately.
Never use a flame for checking gas soundness.
6.6 Adjustments
Gas valve
Fig 7a : Types 20- 45 Fig 7b : Types 60-100
2b
2a
2a
6
7
3
4
8
1) Shut off solenoid valve EV1 2a)Adjustment low fire 2b)Adjustment high fire
3)Inlet pressure test point (not visible on fig 7b)
4)Outlet pressure test point (not visible on fig 7b)
1
4
1
3
6
81
5
5
7
5)Shut off solenoid valve EV2
6)Pilot outlet
7)Main gas outlet
8)Holes (M5) for fixing flanges
LCSC-3E--EN 25/40
6.6.1 Burner gas pressure adjustment
The gas pressure is set for the required heat input before the appliance leaves the factory. Provided the gas supply to the air heater is in accordance with the supply pressure described on the appliance data plate the operating pressure will not require adjustment. To check the pressure, the following procedure should be carried out:
* Ascertain from section 1 of this document
and the appliance data plate the correct operating gas pressure for the air heater;
* Turn the room thermostat control to its
lowest setting;
* Remove the screw from the burner
pressure test point of the multi-functional control valve. Connect a manometer to the test point (see figure 7);
* Adjust the room thermostat to call for heat
e.g. above room ambient temperature;
* Observe the burner gas pressure on the
manometer and compare to the required pressure;
* If necessary, adjust the burner gas
pressure (only for natural gas). Remove the cover screw. Turn the regulator screw anti-clockwise to decrease pressure or clockwise to increase pressure (see figure
7);
* Set room thermostat to lowest setting to
turn the burners OFF. Replace the test point screw (if removed) and with the main burner alight, test for gas soundness using a soapy solution. Reset temperature control/room thermostat to comfort operating level.
6.7 Air distribution system
Adjust the air outlet discharge louvres to provide a satisfactory spread of the warm air. Direct the air towards the floor avoiding blowing directly on people who may be in the vicinity of the appliance.
If louvre adjustment is carried out whilst the appliance is hot wear gloves to avoid being burnt.
6.8 Air heater controls and operation
Check air heater operation after all adjustments have been carried out. Set the temperature control above ambient temperature.
LCSC-3E air heaters are fitted with a pressure sensitive, combustion air safety control that monitors the combustion airflow. When the combustion air safety control closes, verifying airflow, the gas control valve will open and the burner will light. When insufficient airflow, the burner will extinguish until the airflow returns to the acceptable level. Wait approximately 30 seconds after the burner has lit, the time delay relay will activate the thermal fan control which will energize the fan motor. Continue to operate the air heater for several minutes to ensure correct operation. Turn room thermostat to its lowest setting The main burners should extinguish while the fan continues to run to cool the air heater. The fan delay relay will normally be de­energized and stop the fan motor in approximately 45 seconds.
6.9 Handing over
Upon satisfactory completion of commissioning and testing, hand the instructions to the user or their representative. Advise the appropriate person how to safely use and operate the air heater and describe the use of appropriate external controls. Ensure that the person understands how to start the heater and how to turn it OFF. Suggest that the instructions are placed close to the air heater for future reference. In the absence of an appropriate location fix them to the gas service meter. Ensure they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface. Advise the person who is resuming responsibility that for continued safe operation the air heater should be serviced at least once a year.
LCSC-3E--EN 26/40
7
SERVICING INSTRUCTIONS
IMPORTANT: Only appropriately qualified persons may carry out servicing and fault finding on this gas fired equipment. Before commencing service ensure that both the gas and the electricity are turned and switched "OFF" and that the air heater has cooled down. Inadvertent substitution or replacement of components similar to those specified or replacement in a manner contrary to the method herein described could constitute a hazard and lead to prosecution.
When cleaning air heaters, wearing of eye protection and a dust face mask is recommended.
LCSC-3E air heaters will operate with a minimum of maintenance. To ensure long life and satisfactory and safe performance, an air heater that is operated under normal conditions should be inspected and cleaned at the start of each heating season. If the air heater is operated in an area where unusual amounts of dust, etc. are present in the air, more frequent servicing is recommended. When any service is completed, be sure that components are reassembled correctly to ensure that no unsafe condition exists. Upon completion of the service carry out the commissioning instructions outlined in section 6 of this document.
WARNING: Excessive dirt build-up on the inside of the burner ports could cause unburnt gas to spill out of the back of the burner tube causing a fire or explosion. To prevent this occurring, clean all of the burner ports at least annually.
Service procedure
The following procedures should be carried out at least annually:
1. Remove the burner assembly as in section
8.1. Clean thoroughly, (cleaning the burners requires an emery cloth, wire brush and a cleaning cloth -stubborn deposits on burners are best cleaned using "acetone" as a solvent) * Check the condition of the ignitor and clean
to remove all deposits. Check the spark gap (3.0 mm).
* Check the sensor - clean as necessary.
LCSC-3E--EN 27/40
* Remove any soot deposits from the burner
with a wire brush. Clean the ports with a degreaser or acetone. A vacuum cleaner or compressed air may assist in this cleaning
operation Wipe the inside of the burner tube clean (cleaning thoroughly with a degreaser as recommended will retard future build-up of dirt). Inspect the burner for any damage or deterioration. If the burner is damaged or corroded, replace it.
2. The heat exchanger should remain clean unless a problem has developed due to poor combustion. Examine the heat exchanger tubes internally and externally for any sign of deterioration. The outside of the tubular heat exchanger can be cleaned from the front of the heater with an air jet and/or a flexible brush. Remove any dust and grease deposits. The inner surfaces of the heat exchanger can be reached for cleaning with the burner and combustion air fan (venter) assemblies removed. Clean with a flue brush or a heavy wire to which wire wool has been attached.
Brush inside each heat exchanger tube until
all foreign material has been removed. The use of a flashlight is necessary to carry out this operation.
3. Clean the axial fan blades, fan guard, and fan motor to remove all external dirt Check the security of the fan on the motor.
Note: Fan motors are lubricated for life and do not require lubricating.
4. Remove any dirt and/or grease that may have
accumulated on the venter fan motor and its housing. NOTE: The combustion air fan motors are lubricated for life and do not require oiling or greasing.
5. The gas multi-functional control valve
requires no field maintenance except cleaning of its exterior and checking the condition of the wire connections. Instructions for testing pressure are given in section 6.6.
6. Check the flue/combustion air system for
soundness. Reseal/replace any parts that are not sound.
7. Check all wiring connections. Check wiring for any signs of damage. Replace any suspect wiring with an equivalent specification.
8. Check operation of thermal fan control and control relay.
9. When service is complete carry out full commissioning procedure as per section 6 of this document.
Removal & replacement of parts
8
LCSC-3E air heaters must only be fitted with authorized replacement parts. These heaters must use certificated spare parts to comply with legislation.
8.1 Main burner removal
Instructions for burner removal (see figure 8):
1. Turn OFF the gas supply to the air heater.
2. Switch OFF the electricity supply to the air heater.
3. Open the access door.
4. Disconnect the union in the gas supply outside of the appliance.
5. Remove gas supply pipe from multi­functional gas control valve.
6. At the burner rack assembly, remove the nuts that secure the burner manifold to the burner rack. Lift the burner rack/manifold assembly upward and pull the assembly out of the air heater.
Instructions for re-assembly:
1. Reverse the procedure for removal making sure that all parts are installed correctly. Check that all components are secure.
2 When lighting, always follow the lighting
instructions on the air heater.
Remember! After any service work has been carried out, the air heater must be fully commissioned. See section 6 of this document
Figure 8 (for clarity, the heater cabinet & other
parts are not illustrated)
8.2 Burner injectors
1. Carry out steps 1 to 6 of section 8.1.
2. Unscrew the main burner injectors.
3. Re-fit new injectors.
4. Re-assemble in reverse order.
8.3 Ignition system
To access the ignition system, follow steps 1 to 3 in section 8.1.
Ignitor- refer to figure 9 and locate the ignitor (on the side of the burner rack). Disconnect the wire, remove the screw and the ignitor. Clean with an emery cloth. Note: Spark gap must be maintained to 3.0 mm (see figure 10b) Re-fit the ignitor as per figure 10a.
Flame sensor - Refer to figure 9 and locate the flame sensor. Disconnect the wire, remove the screw and the flame sensor. Clean with an emery cloth.
Ignition controller - The enclosed integrated circuit monitors the operation of the burner including ignition. Do not attempt to dismantle the ignition controller. Each heating season ignition cables should be checked for insulation deterioration and good connections.
Proper operation of the direct spark ignition system requires a minimum flame current of 1,0 μA when measured with a micro-ammeter.
For further information and checkout procedure of the direct spark ignition system, refer to the manufacturers control operating instructions a copy of which is supplied with the air heater.
Fig. 10a: Fitting the ignitor
Due to high voltage on the spark wire and electrode, do not touch when energized. See hazard levels.
LCSC-3E--EN 28/40
Fig. 10b - Ignitor assembly
When replacing a capillary control be careful not to damage the capillary tube by kinking. Make bends with a generous radius (approx. 25 mm).
8.6 Combustion air control/switch
If it is determined that the air differential pressure switch needs replacing, use only parts approved by the manufacturer designed for the air heater
8.4 Multi-functional gas control valve
1. Ensure gas supply to the air heater is turned OFF.
2. After the air circulation fan has stopped, switch OFF the electricity supply to the air heater.
3. Mark for future identification and disconnect the wires connected to the valve.
4. Disconnect the gas service union between the control valve and the gas service tap. Remove the gas control valve.
5. Re-fit a replacement valve making all of the required connections.
6 Carry out complete commissioning
procedure prior to placing the appliance back into service as outlined in section
6.0
The gas control operating valve is the prime safety shut-off. All gas supply lines must be free of
dirt, scale, etc. before connecting to the air heater thus ensuring positive closure of the control valve.
being serviced. These switches are calibrated to operate at the designed combustion air flow duty for each appliance size in the product range.
8.7 Combustion air fan (venter)
1. Ensure gas supply to the air heater is turned OFF
2. After the air circulation fan has stopped, switch OFF the electricity supply to the air heater
3. To gain access to the fan open the hinged controls compartment access door. Refer to figure 9 for location
4. Mark for future identification and disconnect the wires connecting the fan motor at the terminals on the main wiring junction.
5. Remove combustion air fan and clean as necessary using a wire brush and solvent to remove sticky residues.
6. Re-assemble and check for free rotation before proceeding to test the appliance.
Note: The combustion air fan motor is lubricated for life. Do not oil or grease.
8.5 Thermal overheat (limit) controls
If it is determined that the thermal overheat control needs replacing, use only replacement parts approved by the manufacturer. To gain access to the control, open the controls compartment access door. Refer to figure 9 for control locations. The control near the top of the air heater is a disc type control. Both controls are capillary types with a capillary tube that extends into the heat exchanger area. To remove the controls, disconnect the wires leading to them, remove the fixing screws and lift clear of the inner casing panel.
Note: The capillary control is fitted to a bracket. With the bracket removed from the air heater, remove the control from the bracket.
LCSC-3E--EN 29/40
C
6
Figure 9 : View of the control compartment
Burner
LC1 limit control
LC3 limit controls
Burner
lamp H
Reset
switch S3
Spark igniter ER
Flame sensor
Fan control relayKF
Reset LC3
Gas valve V1
Control
panel
LCSC-3E--EN 30/40
9
FAULT FINDING
Fault finding may only be carried out by appropriately qualified persons
9.1 Air heater does not operate and lock-out indicator light is off
Is the thermostat above room temperature and if
used is the time clock on?
Correct fault.
Limit control LC1 closed ?
YES
Check connection line
voltage.
NO
YES
Faulty burner
controller fuse ?
YES
Replace fuse
YES
NO
NO
Set thermostat above room
temperature & if used make certain
the time clock is on
NO
Let appliance cool down so
that LC1 can return to
closed position.
Faulty burner
controller : replace
LCSC-3E--EN 31/40
9.2 Air heater does not operate and lockout indicator light is on
Does venter motor
operate ?
YES
Breakdown of appliance -
signal lamp H3 burns
See 2A
NO
Breakdown of appliance
- s ignal lamp H3 burns
Reset appliance
Is differential air press ure
switch (S3) active ?
NO
Overheat control LC3
in open pos ition ?
NO
Do you observe
flame failure :
consult 2B
YES
Reset appliance -Check if there is 230V at
term inals (5) J2 & (2) J1.
YES
YES
See 2C
NO
Check venter motor.
Check burner
controller.
2A :Faulty differential air
pressure switch
Check flue pipe s ystem (s ee table 5) - Flue blocked or too
Reference tube to differential air
pressure s witch is not airtight or
Check differential air press ure
switch (S3). Check switch point
eltaP. Does burner ignite?
long ?
YES
blocked ?
YES
NO
NO
Corre ct i f neces sary.
Check connection (2)+(3)
J2 at burner controller (E).
If n eces s ary correct. Doe s
burner ignite?
YES
NO
Faulty burner control ler (E).
Faulty differential air pressure s witch S3 :
replace.
LCSC-3E--EN 32/40
2B : Flame failure
Correct gas supply pressure
Check spark igniter - check spark gap, spark wire and connector.
Check burner relay
NO
Is po la ri ty of m ains corre ct?
NO
Does inlet gas pressure agree with the data badge?
Is a spark vis ible ?
NO
During 5 sec trial for ig nition is a spark vis ible?
Spark visible, still no flam e.
YES
YES
NO
YES
NO
Correct polarity
Wait 20 sec. and press reset button
Wait 25 sec and check if a flame is visible in the view port ?
YES
Check flame s ignal using m icro amp m eter. Is signal greater than 0,2microA?
NO
Check electronic igniton control - if neces sary clean
Check burner relay
YES
(E)
Is signal greater than 0,2microA?
YES
Replace burner relay (E)
Is there 230V on burner relay at termi nals (1 )+(2) J6 ?
NO
NO
Re pos iti on fl am e sensor.
Correct if
NO
necessary.
YES
Check multi functional gas valve & wiring
NO
Check burner relay (E)
Is s ensor lo cate d in fl am e ?
YES
Is the heater grounded?
YES
Replace flame sensor.
LCSC-3E--EN 33/40
2C : Limit controls LC1 (auto reset) & LC3 (manual reset) switch burner off
Does the fan operate?
YESA
Louvres correctly adjusted ?
YES
Check if fan rotational direction is correct.
YES
Check for excessive injector press ure
NO
Check if fan operates ca 10 sec after starting-up of burner?
YES
Check if fan continues to run ca 3min after burner switched off?
NO
NO
YES
Is there 230V at terminals
J1?
(1)+(2)
Correct fau lt
Correct fault (see table 8a)
NO
Replace burner relay (E)
NO
YES
Faulty motor ­replace
NO
YES
Line voltage dis connected?
NO
Check if swtich-point LC1 (=90\ ) is OK?
YES
Check if switch-point LC3 (=110\) is OK?
YES
NO
NO
Detect cause and repair
Replace limit control LC1
Replace limit control LC3
LCSC-3E--EN 34/40
PARTS LISTING
10
Description Part number
DeltaPswitchS3:LCSC203E 3060617185 DeltaPswitchS3:LCSC303E,453E,603E,753E 3060621175
185(+12)Pa out 203Pa(-20) in
175(+12)Pa out 203Pa(-20) in
Settings
DeltaPswitchS3:LCSC1003E 3060617130 135(+/5)Paout 147(+/5)Pain OverheatcontroldeviceLC1 032495904 90°Cout 85°Cin Ventermotor 114342604 Gasvalvemodureg453E/603E/753E/1003E 0325136M Gasvalvemodureg203E/303E 0325141M BurnerrelayE0325321 IgnitionelectrodeER 03400US42 Flame
sensorelectrodeIS 03401US195292 ERPblowerLCSC203E 0127200 ERPblowerLCSC303E 0127201 ERPblowerLCSC453E 0127202 ERPblowerLCSC603E 0127203 ERPblowerLCSC753E 0127204 ERPblowerLCSC1003E 0127205
GAS CONVERSION
11
LCSC-3E air heaters are designed to operate on natural, propane or butane gas and will be supplied fitted for the gas type ordered. In the event of site conversion to a different gas type it is necessary to convert the gas burner and burner controls.
Affix new data plate and gas type over­sticker.
Upon completion of conversion re­commission the air heater in accordance with section 6 of this document.
Changes to carry out: To adapt gas injectors, burner pressures and gas inlet pressures, we refer to table 2A/2B
.
LCSC-3E--EN 35/40
12
USER INSTRUCTIONS
Operating: Gas is burned by an atmospheric
burner which fires into a heat exchanger. The gas burner is controlled by a double gas valve via an electronic burner control, which is actuated automatically via external controls i.e. a room thermostat and/or a time switch. The burner is ignited by a spark igniter. When the burner fires and warms the heat exchanger, the heat is sensed by a thermally actuated fan control which switches on the fan when the air temperature has reached its preset operating level. At the end of a heating cycle the burner is switched off, the air circulation fan will continue to run until the air heater has cooled to a safe condition. Thereafter the fan will remain off until the next cycle is initiated.
Safety:
1. Flame failure is detected by the ionization probe which is the sensor and will immediately result in gas valve shut down.
2. Safety against overheating is assured by two overheat controls. The first is an automatic recycle control which protects against low air flow i.e. clogged air ways, fan failure etc. The second, which is set to a higher level than the first one, is a control which locks out and switches off the burner in the event of gross overheating for any reason. Manual intervention is necessary to reset this control device. Resetting of the automatic burner control may also be required.
3. The location of the air heater should be maintained at normal atmospheric pressure. Changes to the building after air heater installation, should have regard to the heating installation, i.e. structural changes causing excessive draughts from doors, windows etc. Other air handlers and installation of air extraction equipment which may cause a negative pressure environment, can seriously affect the operation of this type of air heater, especially if combustion air supply is not ducted.
To light the heater:
1. Turn on the gas supply to the air heater.
2. Switch on the electricity supply to the air heater.
3. Ensure time switch (if fitted) is set to an 'ON' cycle.
4. Adjust control/room thermostat to desired temperature.
5. Air heater will light automatically when the room thermostat calls for heat after about 30 sec.
6. If the appliance does not light:
a) Check that the burner control does not
require resetting. An indicator light glows at the inside panel of the appliance and on a remote control if fitted. Reset by pushing reset/button inside the appliance or the remote control.
b) Check if thermal overheat control requires resetting
7. If the thermal overheat control requires resetting and doing so restarts the air heater, wait until the appliance warms to thermal equilibrium, to ensure the overheat control does not lock out again. If it does and the temperature near the heater is less than 30°C, then switch off the appliance and call for service. If the temperature is over 30°C, take appropriate action to reduce the ambient temperature near the air heater.
Air circulation:
1. The space heating process is for air to be circulated through the appliance whereby it gains heat from a heat exchanger. The air is directly discharged into the space to be heated. The air is eventually re-circulated. Therefore it is very important that an unobstructed path for the circulation of the air will be maintained. This is particularly important if the air heater has been installed to blow through the wall between two rooms.
2. Sometimes the air circulation fan of the appliance is connected to a remote over­ride switch. This enables air to be used for circulation purposes when the air heater is not used for heating purposes e.g. in summer. To use this feature:
a) Switch ON electricity
b) Switch ON manual override switch, this
may be fitted as a feature on a remote composite control.
Maintenance:
1. Maintenance and service must only be carried out by appropriately qualified persons e.g. "Corgi" registered undertakings.
2. It is in your interest to ensure proper service and maintenance is carried out at a regular basis. Periods between services are dependent upon the local environment where the heater is installed. All gas appliances should be serviced at least once a year.
3. In case of any damage to the appliance, it must be shut down completely and checked by an appropriately qualified person.
4. In the event of difficulties in resolving any of these matters, please do not hesitate to contact the manufacturer or their official distributor.
NEVER SWITCH OFF ELECTRICTY SUPPLY TO THE AIR HEATER WITHOUT FIRST CLOSING THE GAS ISOLATING TAP
LCSC-3E--EN 36/40
13
HEALTH & SAFETY STATEMENT
13.1 General
Under the Consumer Protection Act 1987 and Section 6 of the Health and Safety at Work Act 1974 we hereby provide the following information on substances hazardous to health. Product range reference LCSC-3E air
heaters.
13.2 Cautionary note
During first firing some smoking may occur, this is due to the burning off of protective/lubricating oils used during appliance production. Most of this will have been removed during the production testing process. It is a wise precaution to ensure that adequate ventilation is provided during the initial firing and throughout the commissioning period, this is particularly important if the discharge air is to blow into a confined space. This smoking does not constitute a poison hazard.
13.3 Declaration
LCSC-3E heaters contain no asbestos; copper is not employed in gas carrying components; solder which has a melting point below 450°C is not used; paints for corrosion protection and decoration are heat cured and contain no lead. The above appliances meet the Electrical Safety requirements of EN60 335 Pt 1 1988.
13.4 Miscellaneous
Small quantities of adhesives and sealants used in the product are dried and cured and present no known hazard.
13.5 Insulation and seals.
Material: Alumino - silicon fiber - crane glass
Precautions: Wear protective gloves when handling. People with a history of skin complaints may be susceptible to irritation. Dust levels are only likely when the material is abraded. In general normal handling and use for this purpose will not present discomfort. Follow good hygiene practices, wash hands before consuming food or using the toilet. First Aid: Medical attention must be sought following eye contact or prolonged reddening of the skin.
13.6 Thermostat.
Material: Illuminating Kerosene. Description: Sealed phial contains a small quantity in liquid form. Recognition: Colorless liquid, paraffin oil/petroleum hydrocarbon odor. Characteristics: Non-corrosive, flammable with no poisonous reference-CH poison Class 3 Precautions: Avoid handling. This product can irritate and defat the skin. Prolonged contact may cause dermatitis. Avoid breathing vapor. Avoid eye contact. Do not ingest. First Aid: Skin. Wash thoroughly with soap and water. Eyes. Rinse immediately with copious amounts of clean water. Ingestion: Seek medical advice. Note: If skin irritation persists seek medical advice.
13.7 Electrolytic capacitor
Two types are used by random selection: Recognition: 1. Plastic enclosure 2. Aluminium enclosure Material: Contained liquid electrolyte Known hazards: Electric shock possible if charged. Precautions: Discharge to ground/earth. Do not incinerate. First Aid: Treat for electric shock if affected.
Description: Tapes Known hazards: Some people can suffer reddening and itching of the skin. Fiber entry into the eyes will cause foreign body irritation. Inhalation will cause irritation to the respiratory tract.
LCSC-3E--EN 37/40
CERTIFICATE
EC DECLARATION OF CONFORMITY OF MACHINERY
(Annex II 1 A of EC Machinery Directive 2006/42/EC)
Nortek Global HVAC Belgium nv
J&M Sabbestraat 130/A000 B-8930 Menen, Belgium
Hereby declares that the following gas-fired unit heaters:
LCSC-3E Types 20, 30, 45, 60, 75, 100
Complies with the requirements of the above mentioned machinery directive Complies with the requirements of further directives, namely
GAD 2009/142/EC - EMC 2014/30/EC – LVD 2014/35/EC the following harmonized standards have been applied:
EN 1020: Non-domestic gas-fired forced convection air heaters for space heating not exceeding a net heat input of 300 kW, incorporating a fan to assist transportation of combustion air and/or combustion products.
The following notified body Technigas Chaussée de Vilvorde 156 BE 1120 Brussels Has been involved with regarding to the EC type examination number E1058/5521
Menen, 18.01.2018
J. Dubus Engineering Team Leader
LCSC-3E--EN 38/40
InformationrequirementsforwarmairheatersCommissionRegulation(EU)2016/2281
Informationtoidentifythemodel(s)towhichtheinformationrelatesto:LCSC3E B1warmairheater: C2warmairheater: C4warmairheater:
[NO] [NO]
[NO] Typeoffuel: [GAS:G20/G25] Model: Item: Symbol:
Unit: Capacity:
Ratedheatingcapacity:
Minimumcapacity:
P
rated,h
P
min
[kW] 21,65 25,56 44,48 59,55 71,99 94,17
[kW] 10,26 12,06 21,11 27,93 34,20 44,64 Electricpowerconsumption*: Atratedheatingcapacity:
Atminimalcapacity:
Instandbymode:
el
el
el
max
min
sb
[kW] 0,08 0,08 0,08 0,08 0,08 0,08
[kW] 0,08 0,08 0,08 0,08 0,08 0,08
[kW] 0,02 0,02 0,02 0,02 0,02 0,02 Usefulefficiency: Usefulefficiencyatratedheatingcapacity*:
Usefulefficiencyatminimumcapacity*:
η
nom
η
[%] 81,9 80,8 81,7 81,3 81,9 81,9
pl
[%] 77,7 76,2 77,6 76,2 77,8 77,7
Otheritems:
NO
η
F
env
P
ign
s,flow
η
s,h
η
th
[%] 000000
[kW] 0,02 0,02 0,02 0,02 0,02 0,02
x
[mg/kWh] ‐ ‐ ‐ ‐ ‐ ‐
[%] 94,8 95,2 94,7 95,2 94,5 94,0
[%] 72,1 72,2 72,2 72,1 72,5 72,1
[%] 91,0 89,7 90,8 90,2 91,0 91,0
Envelopelossfactor:
Ignitionburnerpowerconsumption*:
Emissionsofnitrogenoxides[inputenergy(GCV)]*:
Emissionefficiency:
ErPseasonalspaceheatingenergyefficiency:
Thermalefficiencyatratedheatingcapacity[NCV]: *notrequiredforelectricwarmairheaters Contactdetails:
NortekGlobalHVACBelgiumNV;+32(0)56529511;J&MSabbestraat130/A000;
203E 303E 453E 603E 753E 1003E
B8930
LCSC-3E--EN 39/40
NORTEK GLOBAL HVAC Belgium nv
J&M Sabbestraat 130/A000
B-8930 Menen, Belgium
Tel. +32(0) 56 52 95 11
www.reznor.eu
LCSC-3E--EN
40/40
Loading...