Please read this document carefully before commencing the installation & leave it
with the user or attached to the appliance after installation.
Reznor U.K. Limited – Park Farm Road – Folkestone – Kent CT19 5DT – Tel 01303-259141 – fax 01303-850002
INDEX
1.0Introduction
1.1General Information
1.2Quality Products
1.3CE Approved European Directives
1.4Product Information
1.5Warning
2.0Technical Specifications
2.1Data Sheets
2.2Dimensions
3.0Mechanical/Electrical Services
3.1Oil supply
3.2Oil pipework
3.3Electrical Connection
3.4Ventilation Requirement
3.5Electrical timer
4.0Installation
4.1Location
4.2Heater Clearances
4.3Flue
4.4Nozzled Heaters
4.5Ducted Heaters
4.6Filters
4.7Controls
5.0Commissioning
5.1Pre-Commissioning Checks
5.2Commissioning Procedure
5.3Commissioning Outlets
5.4User Instructions
6.0Instructions for Servicing
6.1Frequency
6.2Procedures
6.3Re-Commissioning
7.0Fault Finding
8.0Spare Parts
8.13D Drawing
8.2Parts List
9.0Reference Standards
2/31
1.0 Introduction
1.1 General
1.1.1Before installation check that the appliance as
described on the packaging label is in
accordance with the correct type and model
specified on the data plate and complies with
your customer order.
1.1.2The heater is delivered wrapped in heavy duty
polythene and should be checked to ensure
that it has been delivered undamaged.
1.1.3Please read this document before commencing
installation. The onus rests with the installer to
ensure that all relevant manuals are read and
understood, especially with regard to any
safety instructions stipulated by the
manufacturer.
1.1.4These instructions are only valid for the country
of use indicated on the appliance, i.e. GB - IE.
If these symbols are not shown it is necessary
to obtain appropriate technical instructions
which will provide information concerning the
necessary modification of the appliance for use
in the country concerned. Such instructions
may be obtained from your supplier upon
request.
1.1.5Check that the local distribution conditions of
electricity supply, type of oil and pressure and
adjustment of the appliance are compatible.
1.1.6When installed in Great Britain the total
installation must comply with the requirements
and recommendations of the relevant British
Standards & local laws. The installation must
also be in accordance with the relevant
electrical regulations and I.E.E. regulations.
1.1.7Warning! Unauthorised modification of this
appliance or departure from use in the manner
for which it was intended by the manufacturer,
or installation in a manner contrary to these
instructions may constitute a hazard and
jeopardise all warranties. Deviations should
only be carried out after formal consent has
been obtained from the manufacturer.
1.1.8Caution! Ensure that the environment in which
the air heater is to be installed will not create a
hazard, i.e. where excessive (volatile) dust,
flammable or corrosive substances and/or
vapours and combustible materials may be
present. Suitable protection should be given to
prevent damage to the appliance, for example
from fork lift trucks.
1.1.9These appliances have been tested and set
according to the data plate before leaving the
factory.
1.2Quality Products
1.2.1The Reznor range of oil fired floorstanding
heaters is manufactured in the EC and
supplied in accordance with BS EN 9002: 1994
Quality Assurance System.
1.2.2Certificates of conformity are available from the
Quality Control department at Reznor Limited.
1.3CE-Approval-European
Directives
1.3.1Reznor floorstanding heaters have been fully
assessed and tested and meet the following
EC Directives:
1.3.2In addition Reznor oil fired floorstanding
heaters are conform to the following
harmonised standards:
BS EN 292 - Part 1 :Safety of Machinery Basic Concepts, General Principles for
terminology, methodology
BS EN 292 - Part 2 :Safety of Machinery Basic Concepts, General Principles for Design
Technical Principles and Specifications.
BS EN 60204 - Part 1 :Safety of Machinery Electrical Equipment for Machine Specification
for General Requirements.
BS EN 60335 - Part 1 :Safety of Household
and Similar Electrical Appliances General
Requirements.
BS EN 55014 :Limits and methods of
measurement of radio disturbance
characteristics of electrical motor-operated and
thermal appliances for household and similar
purposes, electric tools and similar electric
apparatus.
prEN 50165 :Electrical equipment of nonelectric heating appliances for household and
similar purposes, safety requirements.
1.4.Product Information
1.4.1Reznor floorstanding heaters are available with
burner outputs from 30kW to 293kW and can
be floor mounted (FSV units) or suspended
(FSH units).
Floorstanding heaters can be used in free
blowing or ducted applications. Each heater
must have its own individual open flue.
1.4.2All floorstanding heaters are fitted with a pretested and set forced draught burner. A
sequential control box is fitted to each burner
to provide safety. Note: No asbestos or
soldered joints are present in the construction
of the heater.
1.4.3All the materials selected can withstand the
range of chemical, mechanical and thermal
demands expected during the foreseen and
normal use of the product, as stipulated by
manufacturers' instructions and
recommendations.
1.4.4Before final location of the product the following
criteria should always be considered in placing
the heater:-
• Flue outlet access
• Placing for efficient distribution of warm air
• Oil supply
• Electrical services
• Fresh air supply (when applicable)
• Service access and maintenance
requirements
1.5Warning
Heaters should not be installed in a corrosive
or solvent atmosphere
(i.e. near plating or degreasing plants), in areas
where there is a fire risk, or any other
environment which is detrimental to the heater
or its operation. Consult BS 6230 for further
information on hazardous areas.
(1) : unobstructed in still air with a terminal velocity of 50ft/min.
(2) : Condition R=5m; Q=2; A=160; louvres in neutral position
2.2 Dimensions
Figure 1a : unit with discharge nozzle
Vertical heater range
Front view
Figure 1b : unit with discharge plenum
Front view
6/31
Figure 1c – Side view
Figure 1d
Figure 1e
air inlet
Figure 1f : burner mounting flange
air inlet
7/31
Figure 2a – Side view
Horizontal heater range
Figure 2b – Front view
Remark :
The fixation eyes (4x dia 22.5) may only be used to put the unit into horizontal position after delivery. It is strictly forbidden
to use the fixation eyes for suspending the unit.
3.1.1Connection to an oil supply may only be
carried out by suitably qualified persons.
The oil installation must comply with the
rules in force using materials appropriate for
oil installations.
3.2.7All pipework must be adequately sealed
using approved sealing compounds suitable
for oil.
GALVANISED PIPEWORK AND FITTINGS
MUST NOT BE USED.
The pipework must be effectively sealed so
as to eliminate the ingress of air which will
ultimately stop the flow of oil.
3.1.2Check that the oil grade is in accordance
with the data described on the air heater.
3.1.3An adequate oil line sized to provide the
dynamic pressure for the volume required
by the air heater(s) is essential to maintain
the nominal heat input.
3.1.4A shut off tap and, to facilitate servicing, a
disconnect union fitting must be provided
adjacent to the appliance.
3.1.5Ensure that the installations a filter and has
been tested and purged in accordance with
prescribed practice prior to commissioning
and taking the air heater into service.
3.2Oil Pipework
3.2.1The burners fitted to the Reznor air heaters
are suitable for Class D (35 sec) oil via a
suitable oil pipeline and filter to a storage
tank installed externally to the building.
3.2.2The pipework can be constructed for use on
either a single pipe, or two-pipe system.
Whether a gravity feed or pumped system is
required is determined by the parameters of
the installation i.e. number of heaters and
length of pipeline.
3.2.3Please refer to the burner manual as to the
limitations of the oil line and most suitable
pipe diameters after deciding on which
pipework system to adopt.
3.2.4The storage tank and heater are to be
installed with the appropriate safety/service
components as shown by the following
figures.
Tank and single pipe system
Pressure ring main.
3.3Electrical connection
3.3.1The electrical installation may only be
carried out by suitably qualified persons
observing the rules in force.
3.3.2Check that the electrical specification is in
accordance with the specified data on the
air heater. A unique appliance wiring
diagram is supplied as a separate document
attached to this one, plus an additional copy
attached to the air heater.
3.3.3These appliances must be earthen.
3.3.4A lockable main switch must be installed
adjacent to each appliance and in view
when facing the service compartment. The
isolator must have a contact separation of at
least 3.0mm on all poles.
3.3.5Ancillary controls (option 910.2) may be
included with the heater to provide timed
heat cycles, room comfort temperature
level, frost protection, override air
circulation, etc.
3.3.6Ensure when planning the external
appliance control circuitry that power will be
supplied at all times to the air heater, even
when it is control switched in the ‘heat-off’
mode. This is necessary to ensure that the
fan can operate independently of the
heating control. Therefore never incorporate
automatic controls that electrically isolate
the appliance.
Figure 4 : Option 910.2
3.2.5Any external piping from the tank or filter
should be adequately lagged to avoid
waxing during the winter.
Always ensure the correct grade of fuel is
used and especially ensure winter grade is
used for the winter period, as this will be
suitable down to –12°C whereas summer
grade will wax and plug the filter at –4°C.
3.2.6When using a pumped ring main ensure that
correct pressure regulating valves are used
prior to each heater and a ring main
pressure below 0.4bar is used to avoid
aeration and consequential ‘air locks’.
Legend
1 frost stat 4fan control
2 room stat 5burner control
3 programmable clock 6fuse
10/31
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.