Reznor EWHB Installation Manual

EWHB Unit Heaters
Washdown / Corrosion Resistant
Industrial / Commercial Electric Unit Heater
Owner’s Manual
install, operate or service the EWHB Series Unit Heater.
IMPORTANT INSTRUCTIONS
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Reznor, LLC
O’Fallon, MO 63368 USA
800-695-1901
www.reznorhvac.com
23-2180-83-5REZ
IMPORTANT INSTRUCTIONS
Installation and maintenance personnel should familiarize themselves with this manual and all the IMPORTANT INSTRUCTIONS before installing or working on this heater to avoid potential unsafe conditions, severe property damage, personal injury or death.
1. Read all instructions before installing and operating this heater.
2. Verify that the supply voltage and phase to the heater matches the nameplate rating before energizing.
3. Potentially lethal voltages are present. Be sure to lock the branch circuit disconnect switch in the OFF position and tag the
circuit “Out for Maintenance” before
working on this equipment.
4. Keep electrical enclosure cover tightly closed while in operation.
5. Hazard of Electric Shock. Heater must be grounded in accordance with both local and national codes.
6. This heater should be installed by a licensed electrician familiar with all applicable national and local codes having jurisdiction. It is the responsibility of the installer to verify the safety and suitability of the installation.
7. Disassembly of the unit for installation is not required or authorized.
8. Replacement electrical components must be obtained from the factory in order to maintain any applicable Agency Listings.
9. Use this heater only as described in this manual. Any other use is not recommended
by the manufacturer and may result in fire,
electric shock or personal injury.
10. The heater and discharge air are hot when in use. To avoid burns, do not let bare skin touch hot surfaces.
11. To prevent a possible fire, do not block or allow foreign objects to enter air intakes or exhaust in any manner.
WARRANTY WILL BE VOID IF INSTRUCTIONS ARE NOT FOLLOWED.
12. Risk of fire due to high temperatures. Keep electrical cords, drapery, furnishings, insulation and other combustibles at least 3 feet (0.9m) from the front of the heater and away from the sides, rear and top.
13. Installation minimum mounting clearances specified both on heater nameplate and in this owner’s manual must be maintained.
14. Use copper wire rated 90°C min. for supply connections.
15. This heater should not be used in potentially explosive atmospheres. Do not use in areas where gasoline, paint, or flammable liquids are used or stored.
16. Do not use outdoors. Heater may be washed down with water for cleaning. Do not use high pressure cleaning systems.
17. Risk of fire. Do not use as a residential or household heater.
18. Heater is designed to be controlled by a room thermostat located within the operating space that will control the room temperature below 80°F (26.7°C). Do not allow heater to cycle on the built-on limit controls.
19. The heaters are designed for permanent wall or ceiling mounting in a horizontal position only.
20. Do not operate heater after it malfunctions. Disconnect power at service panel and have heater inspected by a reputable electrician before reusing.
21. SAVE THESE INSTRUCTIONS.
EWHB Series Industrial / Commercial Electric Unit Heater /Warnings, Page 1 23-2180-83-5REZ
INSTALLATION INSTRUCTIONS
FIGURE 1
EXPOSED WALL
FIGURE 2
RISK OF FIRE / EXPLOSION
This heater should not be used in potentially explosive atmospheres. Do not use in areas where gasoline, paint or flammable liquids are used or stored.
 Keep electrical cords, drapery, furnishings, insulation and other combustibles at least 3 feet (0.9m) from the
front of the heater and away from the sides, rear and top.
 Installation minimum clearances specified both on the heater nameplate and in the owner’s manual must be
maintained.
 Do not use as a residential or household heater.
These air heaters are designed for comfort heating and should not be used in ambient temperatures exceeding 80ºF (26.7ºC). They are to be permanently mounted to the wall or ceiling for horizontal discharge. The unit is designed to give years of safe, trouble-free operation when properly installed and maintained.
A. Site Selection:
The heaters are intended for elevated mounting locations so that they blow warm air down to the floor area. A mounting height should be selected so that the heater is out of the way of possible moving equipment or personnel, yet low enough to deliver warm air to the selected area. See the mechanical installation section for recommended installation heights. Heater airflow should be directed to areas of greatest heat loss. In general, greater numbers of small heaters will provide more uniform and even heat distributions than a few large ones. In order to help move heated air around the room, multiple heaters should be spaced out and direct air in a circular pattern around the room perimeter such that each heater supports the next heater’s airstreams. See Figures 1 & 2 for some typical airflow pattern arrangements:
Large room with exposed walls and roof :
Small room with one exposed wall:
EWHB Series Industrial / Commercial Electric Unit Heater /Installation Instructions, Page 1 of 4 23-2180-83-5REZ