Reznor BE-200 Service Manual

NOTICE:
The information contained on the following page(s) was produced
prior to May 1, 2014. On that date Reznor became part of
Nortek, Inc.
References to any other company afliations are no longer valid.
©2014 Reznor, LLC. All Rights Reserved.
Trademark notice: Reznor is registered in at least the United States.
0514 PDF Form Cover1
Model FE and BE
Gas-Fired, Power-Vented
Unit Heaters
®
Installation and Operation ........................ Paragraph 1-24 ...... Pages 1-19
Check Installation and Start-Up ................. Paragraph 25 ........... Page 20
Optional Equipment .................................. Paragraph 26-32 .... Pages 21-23
Service/Maintenance/Troubleshooting ...Paragraph 33-43 ....Pages 23-28
Index by Page
Belt Tension............................................. 17
Blower/Filter Cabinet (Optional) ............ 23
Blower Motor .......................................... 17
Blower Rotation ...................................... 18
Blower Speed Adjustment ....................... 17
Bottom Access......................................... 24
Burners .............................................. 19, 24
Burner Air Adjustment ............................ 19
Burner Rack Removal .............................. 24
Carryover, Flash ...................................... 25
Check Installation and Start-Up .............. 20
Clearances .................................................. 6
Combustion Air Proving Switch .............. 19
Combustion Air ......................................... 6
Confined Space Installation ....................... 6
Dimensions ................................................ 3
Disconnect Switch ................................... 12
Duct Flange (Blower Model Option) ...... 21
Electrical Supply and Connections.......... 12
Fan Blade ................................................. 25
APPLIES TO: Installation/Operation/Service
Table of Contents
Index by Page
Fan Control........................................ 18, 26
Fan Motor ............................................... 17
Gas Piping and Pressures ........................ 10
Guard Options (Blower Model).............. 22
Hanger Kits (Optional).............................. 7
Hazard Intensity Levels ............................ 2
Heat Exchanger ........................................ 25
High Altitude Combustion Air
Pressure Switch .......................... 5, 11
High Altitude Operation ............................ 5
Ignition System.................................. 19, 25
Installation Codes ...................................... 2
Limit Control ..................................... 18, 26
Location (Heater)....................................... 5
Louvers, V ertical (Optional) .................... 21
Maintenance ............................................ 23
Maintenance Schedule ............................. 23
Manifold Pressure ................................... 11
Multiple Heater Control Option ............. 23
REFERENCES: Replacement Parts, Form RZ-NA 726
Gas Conversion, Form RZ-NA 434/436-GC
INSTALLA TION FORM RZ-NA-I-FE/BE
Obsoletes RGM 436 (Version B)
Index by Page
Nozzles, Downturn Air (Optional) ......... 21
Optional Equipment ................................ 20
Operating Sequence ................................. 19
Orifices, Burner and Pilot ........................ 25
Pilot ................................................... 19, 25
Polytube Adapter (Blower Model
Option) .......................................... 21
Service ...................................................... 23
Spark Gap................................................ 25
Suspending the Heater ............................... 6
Thermostat and Connections................... 12
Troubleshooting....................................... 27
Uncrating and Preparation ......................... 2
V alve, Gas .......................................... 19, 26
Venter Motor and Relay .......................... 26
Venting ................................................. 8, 25
Warranty .................................................... 2
Wiring Diagrams .................................13-16
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier . FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
WARNING: Gas-fired appliances are not designed for use in hazardous atmospheres containing flammable vapors or combustible dust, in atmospheres containing chlorinated or halogenated hydrocarbons, or in appli­cations with airborne silicone substances. See Hazard Levels, Page 2.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
GENERAL
Installation should be done by a
qualified agency in accordance with the instructions in this manual and in compliance with all codes and re­quirements of authorities having ju­risdiction. The instructions in this manual apply to the unit heater mod­els listed below .
Model Fuel Vent Air Delivery
FE
BE
G as-Fired Power Propeller Fan Gas -Fired Po wer
C e ntrifugal Bl ower (heater may be attached to ductwork)
Model
FE
Model
BE
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in se­vere personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or death and/or prop­erty damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
1. Installation Codes
The gas-fired unit heaters covered in this manual are design-certified by the Canadian Standards Association (CSA) to ANSI Z83.8a and CGA
2.6a for industrial/commercial installations in the United States and Canada. All heaters are available for use with either natural or propane gas. The type of gas, the firing rate, and the electrical characteristics are on the unit rating plate.
These units must be installed in accordance with local building codes. In the absence of local codes, in the United States, the unit must be in­stalled in accordance with the National Fuel Gas Code (latest edition). A Canadian installation must be in accordance with the CAN/CGA B149.1 and B149.2 Installation Code for Gas Burning Appliances and Equipment. These codes are available from CSA Information Services, 1-800-463-6727. Local authorities having jurisdiction should be con­sulted before installation to verify local codes and installation proce­dure requirements.
Special Installations (Aircraft Hangars/ Garages)
Installations in aircraft hangars should be in accordance with ANSI/ NFP A No. 409 (latest edition), Standard for Aircraft Hangars; in public garages in accordance with ANSI/NFPA No. 88A (latest edition), Stan­dard for Parking Structures; and for repair garages in accordance with ANSI/NFPA No. 88B (latest edition), Standard for Repair Garages. ANSI/NFPA-88 (latest edition) specifies overhead heaters must be installed at least eight feet above the floor. In Canada, installations in aircraft hangars should be in accordance with the requirements of the enforcing authorities, and in public garages in accordance with CAN/ CGA B149 codes.
ANSI/NFP A 409 (latest edition) specifies a clearance of ten feet to the bottom of the heater from the highest surface of the top of the wing or engine enclosure of whatever aircraft would be the highest to be housed in the hangar, and a minimum clearance of eight feet from the floor in other sections of aircraft hangars, such as the offices, and shops which communicate with areas used for servicing or storage. The heaters must be located so as to be protected from damage by aircraft or other objects such as cranes and movable scaffolding. In addition, the heaters must be located so as to be accessible for servicing, adjustment, etc.
2. Warranty
Refer to limited warranty information on the warranty card in the "Owner's Envelope".
W ARRANTY: W arranty is void if......
a. Unit Heaters are used in atmospheres containing flammable
vapors or atmospheres containing chlorinated or halogenated hydrocarbons or airborne silicone substances.
b. Wiring is not in accordance with the diagram furnished with
the heater.
c. Unit is installed without proper clearances to combustible ma-
terials or located in a confined space without proper ventila­tion and air for combustion. (See Paragraphs 7 and 8.)
d. Fan-type unit heater is connected to a duct system.
3. Uncrating and Preparation
This unit was test operated and inspected at the factory prior to crating and was in operating condition. If the heater has incurred any damage in shipment, document the damage with the transporting agency and im­mediately contact your Reznor Distributor.
Check the rating plate for the gas specifications and electrical character­istics of the heater to be sure that they are compatible with the gas and electric supplies at the installation site. Read this booklet and become familiar with the installation requirements of your particular heater. If you do not have knowledge of local requirements, check with the local gas company or any other local agencies who might have requirements concerning this installation. Before beginning, make preparations for necessary supplies, tools, and manpower.
Check to see if there are any field-installed options that need to be assembled to the heater prior to installation. Each of the option pack­ages includes a list of components and step-by-step instructions. For a brief description of optional hanger kits, refer to Paragraph 9. For a brief explanation of other frequently specified field-installed options, see Paragraphs 26-32. After becoming familiar with the instructions, assemble and install the options that are required for your heater.
If the heater was ordered with a vent cap, it will be shipped in a separate carton.
Unless the crate bottom has been removed for option installation, leave it attached until after the heater has been suspended. If the crate bottom has been removed, the bottom of the heater must be supported with plywood or appropriately placed boards. Without adequate support, the bottom access panel could be damaged.
To protect the unit during shipping, the blower model has special supports that must be removed before installation. Follow these in­structions to remove:

Blower Support Legs -- Remove the two blower support legs and

screws.

Motor Shipping Block - Remove the wooden block located under the

motor bracket. Find the two rubber pads shipped in the instruction envelope. Place these pads on the ends of the motor bracket bolts.

Motor Shipping Plate -- Blower models that are equipped with mo-

tors of 3/4 HP or less have a metal shipping plate attached between the motor and the blower housing. Remove and discard the shipping plate. Note: On units factory equipped with an optional belt guard, the belt guard must be removed in order to reach the shipping plate.
Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 2
4. Dimensions
Fan-Type, Power-Vented Unit Heater
Figure 1A - Model FE Dimensions - inches (mm)
Female Thread - See Note at bottom of page
Suspension Points (2) or (4) 3/8-16
B
13/16
(21)
13/16
(21)
FRONT
A
Optional
Vertical
Louvers
C
E
K
2-1/4 (57)
F
G
D
RIGHT SIDE
1-11/16 (43)
1/8 (3)
4-1/4 (108)
Electrical Supply Connection
B
M
3/4 (19)
N
J
REAR
H = O.D. Venter Outlet
L = Gas connection (not supply line size)
Dimensions (inches)
SizeABCDEFGHJKLMN
Nat Pro
29-25/32 13-9/16 27-1/16 31-7/16 5-27/32 14-7/16 14-1/32 4 10-9/32 16 1/2 1/2 9-13/16 3
25
29-25/32 13-9/16 27-1/16 31-7/16 5-27/32 14-7/16 14-1/32 4 10-9/32 16 1/2 1/2 9-13/16 3
50
29-25/32 15-9/16 27-1/16 31-7/16 5-27/32 14-7/16 14-1/32 4 10-17/32 16 1/2 1/2 10-7/16 3
75
29-25/32 17-9/16 30-7/16 31-7/16 5-27/32 14-7/16 14-1/32 4 12-29/32 16 1/2 1/2 10-7/16 3
100
29-25/32 23-5/16 30-7/16 31-7/16 5-27/32 14-7/16 14-1/32 5 14-7/16 16 1/2 1/2 11-9/16 2-5/8
125
39-15/16 20-5/16 35-7/16 35-15/16 4-7/8 19-15/32 15-23/32 5 14-9/32 24 1/2 1/2 11-11/16 4-19/32
165
39-15/16 23-5/16 36-3/16 35-15/16 4-7/8 19-15/32 15-23/32 5 14-13/32 2 4 1/2 1/2 11-11/16 4- 19/32
200
39-15/16 28-13/16 36-3/16 35-15/16 4-7/8 19-15/32 15-23/32 5 12-11/32 24 1/2 1/2 11-11/16 4-19/32
250
39-15/16 28 -13/16 36-11/16 35-15/16 4-7/8 19-15/32 15-23/32 6 12-11/32 24 3/4 1/2 11-11/16 3-19/32
300
39-15/16 37-1/16 37-5/16 35-15/16 4-7/8 19-15/32 15-23/32 6 13 24 3/4 1/2 11-11/16 3-19/32
400
Dimensions (mm)
SizeABCDEFGHJKLMN
Nat Pro
25 50
75 100 125 165 200 250 300 400
Suspension Notes: Use Dimension "G" for two-point suspension and "E" and "F" for four-
756 344 687 799 148 367 356 102 261 406 13 13 249 76 756 344 687 799 148 367 356 102 261 406 13 13 249 76 756 395 687 799 148 367 356 102 267 406 13 13 265 76 756 446 773 799 148 367 356 102 328 406 13 13 265 76 756 592 773 799 148 367 356 127 367 406 13 13 294 67
1014 516 900 913 124 498 399 127 363 610 13 13 297 117
756 592 919 913 124 498 399 127 366 610 13 13 297 117 756 732 919 913 124 498 399 127 314 610 13 13 297 117 756 732 932 913 124 498 399 152 314 610 19 13 297 91 756 941 948 913 124 498 399 152 330 610 19 13 297 91
point suspension. (Two-point suspension is standard; four-point is op­tional. Four-point suspension is available either factory or field installed.)
4. Dimensions (cont'd)
Blower-Type, Power-Vented Unit Heater
Figure 1B - Model BE Dimensions - inches (mm)
(4) Suspension Points
3/8-16 Female Thread
N
13/16 (21)
FRONT
B
13/16 (21)
S
T
K
Optional
Duct
Flange
2 (61)
E
3/4 (19)
F
D
RIGHT SIDE
M
R
A
P
Optional Blower Cabinet
X
2-1/4
(57)
1/8 (3)
C
G
10
(254)
4-1/4 (108)
Cabinet Hanger Location
6
Electrical Supply
Connection
7
Optional
Blower
Cabinet
1-11/16
(43)
3/4
(19)
Y
J
REAR
B
U
Gas connection
L =
(not supply line size)
H
= O.D.
Venter Outlet
Z
W
K
Dimensions (inches)
Size
25 50
75 100 125 165 200 250 300 400
Size
25
50
75 100 125 165 200 250 300 400
ABCHDEFDG
29-25/32 13-9/16 43-3/8 31-7/16 5-27/32 14-7/16 61-3/8 4 10-9/32 16 1/2 1/2 29-25/32 13-9/16 50 31-7/16 5-27/32 14-7/16 61-3/8 4 10-9/32 16 1/2 1/2 29-25/32 15-9/16 50 31-7/16 5-27/32 14-7/16 61-3/8 4 10-17/32 16 1/2 1/2 29-25/32 17-9/16 50 31-7/16 5-27/32 14-7/16 61-3/8 4 12-29/32 16 1/2 1/2 29-25/32 23-5/16 47-1/2 31-7/16 5-27/32 14-7/16 65-29/32 5 14-7/16 16 1/2 1/2 39-15/16 20-5/16 61 35-15/16 4-7/8 19-15/32 76-1/8 5 14-9/32 24 1/2 1/2 39-15/16 23-5/16 66-1/2 35-15/16 4-7/8 19-15/32 76-1/8 5 14-13/32 24 1/2 1/2 39-15/16 28-13/16 66-1/2 35-15/16 4-7/8 19-15/32 76-1/8 5 12-11/32 24 1/2 1/2 39-15/16 28-13/16 66-1/2 35-15/16 4-7/8 19-15/32 76-1/8 6 12-11/32 24 3/4 1/2 39-15/16 37-1/16 66-1/2 35-15/16 4-7/8 19-15/32 76-1/8 6 13 24 3/4 1/2
A
M
3-23/32 20-15/16 17-3/4 5-1/4 10-3/4 8-7/16 14-3/4 6-3/16 31-7/32 9-13/16 3 3-23/32 20-15/16 17-3/4 5-1/4 10-3/4 8-7/16 14-3/4 6-3/16 31-7/32 9-13/16 3 2-23/32 20-15/16 17-3/4 5-1/4 12-3/4 8-7/16 14-3/4 6-3/16 31-7/32 10-7/16 3 1-23/32 20-15/16 17-3/4 5-1/4 14-3/4 8-7/16 14-3/4 6-3/16 31-7/32 10-7/16 3 1-11/32 20-15/16 17-3/4 5-1/4 20-1/2 8-7/16 20-1/2 6-3/16 35-3/4 11-9/16 2-5/8 2-27/32 25-15/16 25-1/4 7-1/4 17-1/2 11-7/16 20-1/2 7-15/16 36-11/16 11-11/16 4-19/32 1-11/32 25-15/16 25-1/4 7-1/4 20-1/2 11-7/16 20-1/2 7-15/16 36-11/16 11-11/16 4-19/32 5-29/32 40-9/16 25-1/4 7-1/4 26 11-7/16 26 7-15/16 36-11/16 11-11/16 4-19/32 5-29/32 40-9/16 25-1/4 7-1/4 26 11-7/16 26 7-15/16 36-11/16 11-11/16 3-19/32 6-25/32 50-9/16 25-1/4 7-1/4 34-1/4 11-7/16 34-1/4 7-15/16 36-11/16 11-11/16 3-19/32
N
A
P
A
R
A
Dimensions (mm)
Size
25 50
75 100 125 165 200 250 300 400
Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 4
ABCHDEFDG
756 344 1102 799 148 367 1559 102 261 406 13 13 756 344 1270 799 148 367 1559 102 261 406 13 13 756 395 1270 799 148 367 1559 102 267 406 13 13 756 446 1270 799 148 367 1559 102 328 406 13 13
756 592 1207 799 148 367 1674 127 367 406 13 13 1014 516 1549 913 124 495 1934 127 363 610 13 13 1014 592 1689 913 124 495 1934 127 366 610 13 13 1014 732 1689 913 124 495 1934 127 314 610 13 13 1014 732 1689 913 124 495 1934 152 314 610 19 13 1014 941 1689 913 124 495 1934 152 330 610 19 13
S
A C
HJ K
Hanger
B
B
T
A
U
W
A
A B
E
X
L
Nat Pro
YZ
Hanger
Hanger
A C
HJ K
A B
L
Nat Pro
Size
25 50
75 100 125 165 200 250 300 400
NOTES
M
A
N
A
P
A
R
A
S
B
B
T
A
U
W
A
E
X
YZ
Hanger
94 532 481 133 273 214 375 157 793 249 76 94 532 481 133 273 214 375 157 793 249 76 69 532 481 133 324 214 375 157 793 265 76 44 532 481 133 375 214 375 157 793 265 76 34 532 481 133 521 214 521 157 908 294 67 72 659 641 184 445 291 521 202 932 297 117
34 659 641 184 521 291 521 202 932 297 117 150 1030 641 184 660 291 660 202 932 297 117 150 1030 641 184 660 291 660 202 932 297 91 172 1284 641 184 870 291 870 202 932 297 91
A
When equipped with optional blower cabinet.
B
When equipped with optional duct flange.
C
Dimension includes a 3/4" flange on the rear of the blower cabinet.
D
Use with 4-point suspension without blower cabinet. If installing hanger kit Option CK19, suspension points change; see Paragraph 9.
E
Use with 4-point suspension with blower cabinet.
F
Contactor is standard on Models 300 and 400; optional on other sizes.
G
Contactor location with optional three phase motors on Sizes 50, 75, 100 and 125.
H
Deduct 6-5/8" (168mm) on Sizes 50, 75, and 100 when equipped with direct drive motor.
5. High Altitude Operation
If the heater is being installed in an altitude above 2000 ft (610M), check the rating plate to determine what must be done to prepare the heater for high altitude operation.
NOTE: A heater equipped with a two-stage valve must be factory­built for high altitude installation.
Check the rating plate, determine which circumstance below applies, and follow the instructions.
If the altitude range on the rating plate agrees with the altitude
at the site, no further action is required. Proceed with the instal­lation.
If the altitude range on the rating plate reads "Sea Level" and
the altitude at the site is between 2000 ft and 6000 ft (610M to 1830M) and the heater has a single-stage gas valve, install
the heater and follow the instructions in Paragraph 11 to derate by manifold gas pressure adjustment.
If the altitude range on the rating plate reads "Sea Level" and
the altitude at the site is above 6000 ft (1830M) and the heater has a single-stage gas valve, in addition to adjusting the
manifold pressure, it will be necessary to replace the combustion air pressure switch. Order the listed below and replace the switch before suspending the heater.
After the heater is installed, follow the instructions in Paragraph 11 to derate by adjusting the manifold gas pressure.
High Altitude Combustion Air Pressure Switch
P/N Description 159180 #PPS10027-2733
Figure 2­Pressure Switch Location (above 6000 ft, replace with a pressure switch set for high altitude operation)
6. Unit Heater Location
CAUTION: Avoid installing a unit heater in extremely drafty areas. Extreme drafts can shorten the life of the heat exchanger and/or cause safety problems.
For best results, the heater should be placed with certain rules in mind. In general, a unit should be located from 8 to 12 feet (2.4-3.7M) above the floor. Units should always be arranged to blow toward or along exposed wall surfaces, if possible. Where two or more units are installed in the same room, a general scheme of air circulation should be maintained for best results.
Suspended heaters are most effective when located as close to the work­ing zone as possible, and this fact should be kept in mind when determin­ing the mounting heights to be used. However, care should be exercised to avoid directing the discharged air directly on the room occupants.
Partitions, columns, counters, or other obstructions should be taken into consideration when locating the unit heater so that a minimum quantity of airflow will be deflected by such obstacles.
When units are located in the center of the space to be heated, the air should be discharged toward the exposed walls. In large areas, units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the center of the area.
At those points where infiltration of cold air is excessive, such as at entrance doors and shipping doors, it is desirable to locate the unit so that it will discharge directly toward the source of cold air from a distance of 15 to 20 feet (4.6-6.1M).
Units should not be installed closer than 18 inches (457mm) from any wall.
CAUTION: Do not locate the heater where it may be exposed to water spray , rain or dripping water .
Pressure Switch
7. Clearances and Combustion Air
Units must be installed so that the following clearances are provided for combustion air space, service and inspection, and for proper spacing from combustible construction. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object that is necessary to ensure that a surface temperature of 90°F above the sur­rounding ambient temperature is not exceeded.
Model Required Clearances (inches and mm) Size Top Flue Sides Bottom Rear
Collector
25-400 6"(152) 6"(152) 18"(457) 12"(305) * 24" (610)**
* When supplied with optional downturn nozzle, bottom clearance is
42"(1067mm). For service purposes, on standard units, bottom clearance exceeding minimum (12" or 305mm) is not required but may be desirable.
** For servicing purposes only, rear must remain full open. All fuel-burning equipment must be supplied with the air that enters
into the combustion process and is then vented to the outdoors. Suffi­cient air must enter the equipment location to replace that exhausted through the heater vent system. In the past, the infiltration of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient. However, current construction methods uti­lizing more insulation, vapor barriers, tighter fitting and gasketed doors and windows or weather-stripping, and mechanical exhaust fans may now require the introduction of outside air through wall openings or ducts.
The requirements for combustion and ventilation air depend upon whether the unit is located in a confined or unconfined space. An "un­confined space" is defined as a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance. Under all condi- tions, enough air must be provided to ensure there will not be a negative pressure condition within the equipment room or space. For specific requirements for confined space installation, see Paragraph 8.
W ARNING: These power -vented unit heaters are designed to take combustion air from the space in which the unit is installed and are not designed for connection to outside combustion air intake ducts. Connecting outside air ducts voids the warranty and could cause hazardous operation. See Hazard Levels, Page 2.
8. Combustion Air Requirement s for a Heater Located in a Confined Space
Do not install a unit in a confined space without providing wall open­ings leading to and from the space. Provide openings near the floor and ceiling for ventilation and air for combustion as shown in Figure 3, depending on the combustion air source as noted in Items 1, 2, and 3 below the illustration.
Figure 3 ­Confined Space: A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating
Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 6
Add total BTUH of all appliances in the confined space and divide by figures below for square inch free area size of each (top and bottom) opening.
1. Air fr om inside the building -- openings 1 square inch free area per 1000 BTUH. Never less than 100 square inches free area for each opening. See (1) in Figure 3.
2. Air fr om outside thr ough duct -- openings 1 square inch free area per 2000 BTUH. See (2) in Figure 3.
3. Air dir ect from outside -- openings 1 square inch free area per 4000 BTUH. See (3) in Figure 3.
NOTE: For further details on supplying combustion air to a confined space, see the National Fuel Gas Code ANSI Z223.1a (latest edition ).
9. Suspending the Heater
Before suspending the heater, check the supporting structure to be used to verify that it has sufficient load-carrying capacity to support the weight of the unit.
Net Weight (lbs and kg) Model Size Type 25 50 75 100 125 165 200 250 300 400
Fan lbs 7 6 83 9 2 101 132 154 175 209 226 281
kg 34 38 42 46 60 70 79 95 103 127
Blower lbs 9 7 104 118 130 180 206 240 278 301 395
kg 44 47 54 59 82 93 109 126 137 179
NOTE: If the installation includes an optional stepdown transformer kit (Option CF or CG), the stepdown transformer bracket is part of the heater suspension and must be installed prior to hanging the heater. Follow the instructions on the installation sheet included with the op­tion kit.
A fan-type unit heater is equipped with standard two-point suspen- sion. A 3/8-16 threaded hanger bracket assembly is located on each side of the heater. If a fan-type unit has been ordered with optional, factory­installed, four-point suspension (Option BJ6), it will have two threaded hanger brackets on each side.
A blower-type heater is equipped with standard four-point suspen- sion. Two 3/8-16 threaded hanger bracket assemblies are located on each side of the unit. Each hanger bracket assembly is designed for threaded rod attachment.
For both "standard" and "optional" suspension point dimensions, see Dimension Tables in Paragraph 3. (Note: If installing Option CK19 hanger kit, suspension points change; see Figure 7.)
WARNING: Suspend the heater only from the threaded hanger brackets. Do not suspend from the heater side panel.
Figure 4 -
Suspension
When the heater is lifted for suspension, the bottom must be protected. If the wooden crate bottom has been removed, the bottom of the heater will have to be supported with plywood or other appropriately placed material. If the bottom is not supported, the bottom access panel could be damaged. Also, when lifting a blower unit, support the blower and motor to prevent the unit from tipping.
All blower models have legs that support the blower assembly dur­ing shipping. After the unit is suspended, these legs should be re­moved.
Be sure that the threaded hanger rods are locked to the heater as shown in Figure 4.
WARNING: Unit must be level for proper operation. Do not place or add additional weight to the suspended heater. See Hazard Levels, page
2.
If an optional downturn air nozzle is used, the unit must be sus­pended from four points to ensure level suspension. Two hanger brackets are included in the downturn option package and must be field-installed on fan-type units with standard two-point suspen­sion. For additional information, refer to Paragraph 27 and the in­structions that are furnished with the option package. When blower-type units are equipped with an optional blower/ filter cabinet, there are two suspension points on the blower cabi­net hanger bar. Suspend a unit equipped with a blower/filter cabinet from four points, using the two heater hanger bracket assemblies closest to the front of the heater and the two suspension points on the blower/filter cabinet. If one of the optional, field-installed hanger kits has been ordered for your heater, it will have been shipped separately. Each option pack­age includes a list of components and complete, step-by-step assem­bly instructions.
Optional, Field-Installed Hanger Kits:
1) Four-Point Suspension (fan models only) - Option CK7
This option kit is designed to convert a fan-type heater from stan­dard two-point suspension to four-point suspension. The kit con­tains two additional hanger brackets.
2) Two-Point Swivel Connectors (fan models only) - Option CK8 (See Figure 5)
The purpose of this option kit is to adapt the standard hanger bracket so that the heater can be suspended from 1", threaded, stationary pipe. The swivel connector screws "into" the threaded hanger bracket on the heater and "onto" the 1" threaded pipe used for hanging the heater. The kit includes two swivel hanger connector assemblies and two lock washers.
Figure 5 - T wo­Point Suspension with Swivel Connections (fan models only)
3) Four-Point with Swivel Connectors (fan-models only) - Option CK9 (See Figure 6)
This option package is designed to convert a fan-type heater from stan­dard two-point suspension to four-point suspension with swivel con­nectors. By installing this kit the standard fan-type heater can be hung from four 1", threaded, stationary pipes. The kit includes two hanger bracket assemblies, four swivel hanger connector assemblies and four lock washers.
4) Four-Point Swivel Connectors - Option CK10 (See Figure 6)
This option package is used on a heater that is already equipped with four-point suspension to adapt it for suspension from four 1", threaded, stationary pipes. The kit includes four swivel hanger connector assem­blies and four lock washers.
Figure 6 - Four-Point Suspension with Swivel Connections (Applies to both fan and blower models)
5) Special Four-Point Suspension with Nearly Equal Loading (applies to blower models only) - Option CK19
This suspension option is designed for special applications when a sus­pension system is needed that has nearly equal loading at all four suspen­sion points. Use this option in installations with spring isolation de­signed for seismic protection or when threaded rod hangers are longer than twelve inches. Suspension points change with the addition of hanger kit Option CK19; see Figure 7.
(See Figure 7)
A (Standard suspension points/hanger bars)
1-3/8 (35)
B (Suspension points with Option CK19)
Front View of Model B with Option CK19
Dimensions (inches) Size A B
25-50 11-7/8 9-1/8 75 13-7/8 11-1/8 100 15-7/8 13-1/8 125 21-5/8 18-7/8 165 18-5/8 15-7/8 200 21-5/8 18-7/8 250 27-1/8 24-3/8 300 27-1/8 24-3/8 400 35-3/8 32-5/8
Dimensions (mm) Size A B
25-50 302 232 75 352 283 100 403 333 125 549 479 165 473 403 200 549 479 250 689 619 300 689 619 400 899 829
1-3/8 (35)
Figure 7 - Suspension Dimensions for Model B Heater
with Hanger Kit Option CK19
18-3/4 (476)
4-7/8
(124)
17-3/8 (441)
19-15/32 (495)
Side View of Model B with Option Ck19
Airflow
10. V enting
These power-vented unit heaters are designed to operate safely and efficiently with either a horizontal or vertical vent. (Horizontal vent run is recommended for maximum fuel savings.)
W ARNING: Units installed in multiples r equire individual vent pipe runs and vent caps. Manifolding of vent runs is not permitted due to possible recirculation of combustion products into the building and possible back pressure effects on the combustion air proving switch.
Specific Venting Requirements (read all before installing)
1. Venter (Flue) Outlet Venter Outlet Size:
Model Size Outlet Diameter
25-100 4" 125-250 5" 300-400 6"
Venter Outlet Attachment Requirements:
• If the pipe used in the vent run is larger than the diameter of the venter outlet (See Vent Length Table 2), Make the transition at the venter outlet.
• A minimum of 12" (305mm) of straight pipe is required at the venter outlet (or transition fitting) before installing an elbow in the vent system. An elbow should never be attached directly to the venter. An elbow attached to the straight pipe can be in any position at or above horizontal. See Figure 8.
Figure 8 - Alternate V ent Dir ections (vent in any position above horizontal; minimum of 12" (305mm) of straight pipe is required before an elbow)
2. Vent Pipe
If installed with a horizontal vent run, use either vent pipe ap­proved for a Category III heater or appropriately sealed 26-gauge galvanized steel or equivalent single-wall pipe. If at least half of the equivalent length of the vent system is verti­cal, vent pipe approved for a Category I heater may be used. Single-wall pipe or double-wall (Type B) vent pipe are suitable for use with a Category I heater. Use only one of the flue pipe diameters listed in the Vent Length Tables for the furnace size being installed.
2A. Vent Pipe Diameter Reduction
If at least half of the equivalent length of the vent system is verti­cal, the vent pipe diameter may be reduced one inch from the standard diameter listed in Vent Length Table 1. Only single-wall pipe is suitable for use when reducing the pipe diameter. A taper­type reducer must be used. The maximum allowable vent length remains the same. If required, double-wall pipe may be used at the terminal end as shown in Figures 9 and 10. (Use the equivalent length for elbows as shown in V ent Length T able 1 for the standard vent pipe diameter. All elbows used in the vent system must be considered.)
Form RZ-NA-I-FE/BE, Mfg P/N 98807, Rev 10, Page 8
3. Vent Length Tables
Table 1: Maximum Permissible Vent Lengths
Vent Maximum Equivalent Straight
Model Pipe Vent Length* Length** - ft (M)
Diameter ft (M ) 90° Elbows 45° Elbows
25 4" 30 ft (9.1 M) 3.5' (1 M) 1.8' (.5 M) 50 4" 40 ft (12.2 M) 5' (1.5 M) 2.5' (.8 M)
75 4" 50 ft (15.2 M) 7' (2.1 M) 3.5' (1.1 M) 100 4" 50 ft (15.2 M) 7' (2.1 M) 3.5' (1.1 M) 125 5" 50 ft (15.2 M) 5' (1.5 M) .5' (.8 M) 165 5" 50 ft (15.2 M) 9' (2.7 M) 4.5' (1.4 M) 200 5" 50 ft (15.2 M) 8' (2.4 M) 4.0' (1.2 M) 250 5" 50 ft (15.2 M) 10' (3.0 M) 5' (1.5 M) 300 6" 50 ft (15.2 M) 11' (3.4 M) 5.5' (1.7 M) 400 6" 50 ft (15.2 M) 15' (4.6 M) 7.5' (2.3 M)
Table 2: Optional Maximum Permissible Vent Lengths
(Requires an increase in vent pipe diameter.)
Vent Maximum Equivalent Straight
Model Pipe Vent Length* Length** - ft (M)
Diameter ft (M) 90° Elbows 45° Elbows
100 5" 60 ft (18.3 M) 8' (2.4 M) 4.0' (1.2 M) 165 6" 60 ft (18.3 M) 10' (3.0 M) 5.0' (1.5 M) 200 6" 60 ft (18.3 M) 12' (3.7 M) 6.0' (1.8 M) 250 6" 70 ft (21.3 M) 8' (2.4 M) 4.0' (1.2 M) 300 7" 70 ft (21.3 M) 13' (4.0M) 6.5' (2.0 M) 400 7" 90 ft (27.4 M) 14' (4.3M) 7.0' (2.1M)
*Note 1: If the system contains all vertical pipe or a combination of horizontal and vertical vent pipe, the Maximum Permissible Vent Length shown in Tables 1 and 2 may be increased one foot for each foot vertical rise up to a maximum increase of 10 feet for Model sizes 25 thru 100 and up to 20 feet for Model sizes 125 thru 400.
**Reduce the maximum vent length by the amount indicated for each elbow.
4. Vent System Joints
Vent system joints depend on the installation and the type of pipe being used.
• If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit connections using sheet metal screws or rivets. Seal pipe joints either with tape suitable for 550°F (such as Option FA1, P/N 98266) or high­temperature silicone sealant.
• If using Category III vent pipe, follow pipe manufacturer's instructions for joining pipe sections. When attaching Category III pipe to the venter outlet or the vent cap, make secure, sealed joints following a procedure that best suits the style of Category III pipe being used.
• If using double-wall (Type B) vent pipe (allowed only if 1/2 of the equivalent vent length is vertical), follow pipe manufacturer's instruc­tions for joining pipe sections. For joining double-wall pipe to the venter outlet collar, single-wall pipe, and/or the vent cap, follow the instruc­tions below.
Loading...
+ 20 hidden pages