Response SL5 Installation & Operating Manual

Page 1
1
45
6
7
ENTER
ESC
POWER ALARM
STATUS
ALARM MEM/
LINE
STATUS
!
9
2 3
8
?
0
36 Zone
Wireless Security System
SL5
Installation & Operating Manual
Page 2
FOREWORD
All devices in this wireless Alarm System are
designed and manufactured to provide long reliable service. The system is designed for ease of installation using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual and plans the system before proceeding with the installation.
During installation, it is important that the procedures described in this manual are followed in sequence.
This manual should be retained in a safe place
for future reference.
IMPORTANT: All devices, with the exception of the
External Siren are suitable for mounting in dry interior locations only.
DECLARATION
Novar ED&S hereby declares that this wireless alarm
system is in compliance with the essential requirements and other relevant provisions of the Radio and Telecommunications Terminal Equipment (R&TTE) directive, 1999/5/EC.
DEVICE RANGE
The quoted range of the system devices (see component
specification on rear cover) is measured in ideal conditions. Any solid object (e.g. walls, ceilings, reinforced PVC doors etc) placed between the transmitter and Receiver device will reduce the radio range.
The amount by which the range will be reduced is dependant upon the nature of the barrier.
For example:
Wall Type Range Reduction
Dry-lined partition wall: 10 - 30%
Single layer brick wall: 20 - 40% Double layer brick wall: 30 - 70% Metal panel/radiator: 90 - 100%
Note: The effect on the range of multiple walls is
cumulative, i.e. if there are 2 brick walls in the way, the range will be reduced by up to 40% by each wall.
SYSTEM SECURITY
This system has been designed to both detect
intruders and act as a strong deterrent to would-be intruders when installed correctly.
We recommend that your Alarm is used in conjunction with good physical protection such as security window and door locks.
All units in the system are encoded to operate together using a 20 bit House Code.
The system is operated from one or more Remote Control Units and/or Keypads - depending on which system and/or accessories purchased.
SAFETY
Always follow the manufacturers advice when using
power tools; steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes etc.
Before drilling holes in walls, check for hidden electricity cables and water pipes, the use of a cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned on a firm stable surface at the correct angle and suitably secured before use.
The use of ear defenders is advisable when working in close proximity to the Siren due to the high sound level produced by this device.
2
IMPORTANT:
LOCAL AUTHORITY REGULATIONS AND LEGISLATION
This alarm system should be installed and operated
in accordance with the requirements of any current local and/ or national regulations and legislation. We recommend that you contact your authority to obtain details of your area's requirements regarding intruder alarm installations.
For example in Belgium, the installation and use of an alarm system including notification by telephone (Voice Dialler) functionality and the optional use of an external siren is controlled by Belgium legislation "KB" of 19/06/2002.
Tools and Equipment Required:
No.0 Philips Screwdriver Bradawl
No.1 Philips Screwdriver Drill No.2 Philips Screwdriver 3mm Drill Bit Small Spirit Level 5 & 6mm Masonry Drill Bits
Page 3
3
CONTENTS
KIT CONTENTS 4
INTRODUCTION AND OVERVIEW 5
Multiple Users 5 User Access Code 5 System Arming 5 Entry/Exit Delay 5 Zones 6 Zone Lockout 6 Quick Set 6 Event Log 6 Chime 6 Monitoring 6 Latch Key 7 Remote System Control 7 Tamper Protection 7 Jamming Detection 7 Battery Monitoring 7
PLANNING AND EXTENDING YOUR
ALARM SYSTEM 8
Typical Installation 8
REMOTE CONTROL UNIT 9
General Information 9 Configuring the Remote Control 10 Testing the Remote Control 10
CONTROL PANEL 10
Positioning the Control Panel 10 Installing and Configuring the Control Panel 11 Linking a Remote Control or Remote Keypad
to the Control Panel 12
Testing the Control Panel and Remote Control 13
PASSIVE INFRA-RED (PIR) MOVEMENT
DETECTORS 14
Positioning the PIR Detectors 14 Installing and Configuring the PIR Detectors 15 Testing a PIR Detector Independently 15 Linking a PIR Detector to the Control Panel 16 Testing a PIR Detector with the Control Panel 17
MAGNETIC DOOR/ WINDOW DETECTORS 17
Positioning the Door/ Window Detectors 17 Installing and Configuring the Door/Window
Detectors 18 Testing a Door/Window Detector Independently 19 Linking a Door/Window Detector to
the Control Panel 19 Testing a Door/Window Detector
with the Control Panel 20
EXTERNAL SOLAR SIREN 21
General Information 21 Positioning the Solar Siren 21 Installing and Configuring the Solar Siren 21 Power-up of the Solar Siren 22 Testing the Wireless Solar Siren 23 Mounting the Solar Siren on to the wall 23
DUMMY SIREN 24
EXTERNAL CONNECTIONS 25
TESTING THE SYSTEM 26
FACTORY SETTINGS 31
Reset Factory Settings 31
PROGRAMMING INSTRUCTIONS 32
Navigating through the Programming Mode Menus 32 Telephone Application Setup 33 User Setup 33 System Setup 34 Learn Remote Controls and Keypads 35 Alarm Duration 36 Entry / Exit Delay Period 36 Entry Delay Beeps 37 Exit Delay Beeps 37 Wireless Siren 37 Wired Siren 37 Auxiliary Relay 37 Jamming Detection 37 Zone Lockout 38 Time & Date Setup 38 Dialler Operating Mode 38 Remote Phone Access and Control 38 Rings to Answer Phone 38 Zone Setup 39 Learn Detector Code 40 Monitoring Setup 42
-Remote Manager 42
-Voice Dialler 42 Latch Key Setup 45 Friedland Spectra Plus Lighting Setup 47
OPERATING INSTRUCTIONS 48
Voi ce Dialler 48 Arming the System 48 Part-Arming the System: Part-Arm 1 48 Part-Arming the System: Part-Arm 2 48 Disarming the System 48 Disarming the System with the Duress Code 49 Friedland Spectra Plus Lighting 49 Quick Set 49 Personal Attack (PA) Alarm 49 Latch Key 50 Zone Lockout 50 Device Tamper 50 Chime 50 Keyboard Beep Mute 50 Entry / Exit Beeps 50 Event Log 50 Remote Phone Access and Control 51 Monitoring 52
-Remote Manager 52
-Voice Dialler 53 Siren Service / Operating Mode 54 Battery Monitoring 54
MAINTENANCE 56
ALARM RECORD 57
TROUBLE SHOOTING 59
EXTENDING YOUR ALARM SYSTEM 62
COMPONENT SPECIFICATION 64
Page 4
4
KIT CONTENTS
The Alarm System should contain the following devices.
1xSolar Siren 1xDummy Siren 1xControl Panel 2xPIR Movement Detectors 2xMagnetic Door /Window Detectors
Also included:
Power Supply Adaptor
RJ11-BT Telephone Connection Lead Siren and Dummy Siren Mounting Template Installation & Operating Manual Installation DVD Fixing Pack Batteries
PLEASE READ BEFORE YOU INSTALL
The Solar Siren is supplied complete with a rechargeable 6V battery. However, before
installing this system, please ensure the battery is still fit for use by checking the date code label on it. Remove the battery cover on the rear of the Siren, you will see the label shown here. (Example of a date is
02/2009 meaning February 2009) MM = Month, YYYY = Year.
If the date you purchased this kit exceeds the install date but not the expiry date marked on this label, you will need to recharge the battery. You can use the Control Panel supplied with this kit to recharge this battery for 24 hours before you install the system. (See CONTROL PANEL section), but you will need to remove one of the supplied Control Panel batteries first.
If the battery has expired seek a replacement.
PIR Movement
Detector
Control Panel
1
45
6
7
ENTER
ESC
POWER ALARM
STATUS
ALARM MEM/
MESSAGE
LINE
STATUS
!
9
2 3
8
?
0
Solar Siren / Dummy Siren
Door/ Window
Detector
6V/1.2Ahr Sealed lead acid battery
(supplied 1 x fitted in Siren
and 2 x fitted in Control Panel)
3V CR2032 Lithium Coin Cell (for Door/
Window Detectors)
9V PP3 Alkaline battery
(for Siren and
PIR Detectors)
1.5V C Alkaline batteries (for
Dummy Siren)
Install battery before
MM/YYYY
or
else recharge after.
Battery expiry date
MM/YYYY
(Do not recharge after expiry date).
HEALTH WARNING:
Do not put the coin cell
battery in your mouth as this could impair your health. Keep this cell out of reach from young children as they could swallow it and choke.
Page 5
5
MULTIPLE USERS
The system allows for up to 6 Users, a Master and
a Duress User to be configured. This allows the system Event Log to maintain a record of which users have armed and disarmed the system. Each user will have a different User Access Code. In addition a 4 second voice recorder facility enables the user’s name to be recorded for use with the Latch Key facility.
Only the Master User has access to the programming functions and is able to configure the system.
Note: Any Remote Control Units on the system will
be recorded as User 6.
USER ACCESS CODE
The Control Panel is the brains of the system and is
where the system is programmed and operated from. A 4 digit code is used to ensure that only authorised people have access to the system. This is the User access code and can be set to a code of your choice that only you and other authorised system users know.
SYSTEM ARMING
The system has a ‘Full Arm’ and two ‘Part-Arm’
modes. ARM will ‘Arm’ all zones while the ‘Part-Arm’ modes will only arm the zones that are enabled for the particular Part-Arm mode.
For example:
The system could be configured so that during night
time, ‘Part-Arm 1’ would arm only zones protecting the lower floor and outbuildings leaving the upper floor free for movement without triggering the alarm.
During the day while the property is occupied ‘Part-Arm 2’ could arm only the zones protecting the outbuildings. However, when the property is left un-occupied, the ‘Full Arm’ mode will arm all zones to protect the entire property, (i.e. upper and lower floors and outbuildings).
ENTRY/EXIT DELAY
When the system is armed with the Exit-Delay
enabled, no signal from any detector on an active zone will be able to trigger an alarm until the Exit­Delay has expired. This enables the system to be armed from within the property and allows time for the user to exit the property without triggering an alarm. If the Exit-Delay is disabled then detectors on active zones will immediately be able to trigger an alarm once the system is armed.
The system Exit-Delay may be configured for between 10 to 250 seconds or disabled completely.
If a detector on a zone with its Entry-Delay enabled is triggered, then an alarm will not sound until the Entry-Delay period has expired. This allows time for the user to re-enter the property and disarm the system before an alarm occurs. Generally only the zones on the main entry route to the property will be configured with an Entry-Delay. The remaining zones would be configured with their Entry-Delay disabled allowing them to immediately initiate an alarm the instant a detector on the zone is triggered.
INTRODUCTION AND OVERVIEW
Full Arm
Part-Arm 1
Part-Arm 2
Page 6
The Entry-Delay for each zone may be configured for
between 10 to 250 seconds or disabled completely.
Note: To conserve power and maximise battery life
the PIR Detector will only detect movement if there has been no movement detected within the previous 2 minutes. Consequently the PIR Detector will not become active until the protected area has been free from movement for more than 3 minutes.
ZONES
The system incorporates 32 wireless alarm zones
for the connection of a detector per zone used to independently monitor different areas of the property. In addition to standard intruder protection, each zone can also be configured to operate in alternative modes.
For example:
‘Intruder’ mode provides standard intruder
monitoring.
– ‘24-hour Intruder’ mode provides 24 hour intruder
protection for areas where continuous monitoring is required, (e.g. gun lockers).
– ‘Fire’ mode provides 24 hour monitoring of any
Smoke detectors incorporated into the system.
–‘Test’ mode allows a zone to be monitored while
the system is armed. If a detector on a zone is triggered an entry will be recorded in the Event Log but an alarm will not occur.
In addition there is the facility to connect up to 4 hard wired zones to the Control Panel, each of which is configurable with most of the features of the wireless zones.
ZONE LOCKOUT
If a detector on an active zone is triggered while the
system is armed an alarm will sound. After the programmed alarm duration has expired the alarm will stop and the system will automatically reset. Subsequent detectors triggered will again trigger an alarm. If a single zone triggers an alarm more than 3 times then that zone will be ‘Locked Out’ and any further alarm signals from that zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled
if required.
QUICK SET
The system may be fully armed in 10 seconds using
the quick set facility, overriding the programmed exit­delay. This is useful for setting the system at night when the Exit-Delay warning beep will be silenced after just a few seconds.
EVENT LOG
The Control Panel incorporates a memory capable
of storing the last 99 system events. This enables the user to see which user has Armed/Disarmed the system and if and when any alarms occurred. The time, date and details of the event type will be recorded for each system event.
CHIME
Chime is a low security facility for use when the
system is in Standby mode. If the Chime feature is ON, and a detector on a zone that has its Chime function enabled is triggered, the internal sounder will produce a low volume warning tone. A typical use of the Chime function would be to warn that a door or particular area has been entered.
MONITORING (OPTIONAL)
This system incorporates a telephone dialler (Voice
Dialler) and monitoring service (Remote Manager).
The monitoring service enables the system to make a check call to the premises and generate text/email / telephone calls/ messages to up to 6 key holders. A monitoring service provider is required to make use of these features.
IMPORTANT: to set up monitoring follow REMOTE
MANAGER instructions.
The system telephone dialler can be set up as a
Voice Dialler that can be used to call for help and
or/ notify the user that the system has been triggered and an alarm has occurred.
In this mode the system will call for help using your recorded message and dial up to 4 telephone numbers and replay the corresponding alarm message for each number. Switching the system between
Remote Manager to Voice Dialler is
straightforward.
6
Page 7
7
LATCH KEY
When the system is Disarmed the Latch Key facility,
if enabled, will call the first Latch Key phone number and replay the user message (recorded under latch key setup) for the set ‘Play Time’. The recipient must acknowledge the message by pressing the button on their telephone keypad. If the call is unanswered or an acknowledgment is not received then the second Latch Key phone number will be called. The Voice Dialler will continue calling each number in turn until each number has been dialled the set number of times or the sequence is cancelled/acknowledged by the recipient.
For example, the Latch Key facility is useful to inform parents that a child has returned from school and Disarmed the system.
REMOTE PHONE ACCESS
AND CONTROL
It is possible to dial into the system via the connected
telephone line to interrogate the system status and to have basic control over the system, (e.g. to Arm and Disarm the system). You may also activate the microphone on the Control Panel to Listen-In to what is happening in the protected property.
TAMPER PROTECTION
All system devices (except any Remote Control
Units) incorporate Tamper protection features to protect against unauthorised attempts to interfere with the device.
Any attempt to remove the battery cover from any device (except a Remote Control) or to remove the Solar Siren or Control Panel from the wall will trigger the alarm even if the system is Disarmed (unless the system is in Test or Program modes).
JAMMING DETECTION
In order to detect any attempts to illegally jam the
radio channel used by your alarm system, a special jamming detection function is incorporated into the Control Panel. If this feature is enabled, an alarm will be triggered if the radio channel is jammed continuously for more than 30 seconds or if the system is jammed for more than 3 periods of 10 seconds in a 5 minute period. At full alarm it will beep for 3 seconds and will alarm after 10 seconds, at Part Arm it will beep for 3 seconds.
The jamming detection circuit will constantly scan for jamming signals. However, it will also detect and could in extreme cases be triggered by radio signals from other radio equipment within range operating on the same frequency which would not interfere with the normal operation of your alarm.
When activating jamming detection the system should be monitored carefully for false jamming alarms for at least 2 weeks before leaving the Jamming Detection function permanently enabled.
BATTERY MONITORING
All devices powered by non-rechargeable batteries
incorporate a battery level monitoring feature which will warn of a low battery status.
In addition the Control Panel will also indicate a low battery status on any PIR (Passive Infra-Red) or Magnetic Door/ Window Detector on the system.
The batteries on any device indicating a low battery status should be replaced immediately.
If you are planning to operate the Jamming Detection feature we recommend that you wait at least 30 days before activating this feature to allow time for you to become familiar with the operation of your system.
Page 8
PLANNING AND EXTENDING YOUR ALARM SYSTEM
Before attempting to install your Alarm System it is
important to study your security requirements and plan your installation accordingly.
PIR Movement Detectors are used to protect the main areas of the property, (e.g. lounge, study, hallway and landing). Magnetic Door /Window Detectors are typically used to protect the main access points to the property, (e.g. front door, back door, patio doors etc). However, they can also be used to protect other vulnerable doors/ windows or access doors to important rooms.
TYPICAL INSTALLATION
The following example below shows a typical property
incorporating the suggested positions for the External Siren, PIR and Magnetic Door/ Window Detectors. Use this as a guide for your installation in conjunction with the detailed positioning requirements for each device provided in the appropriate installation sections in this manual for planning your intruder alarm system.
Typical Installation using only the detectors
supplied:
1. Place the 1st
Door/ Window
Detector (configured
on zone 1) on the front door.
2. Place the 2nd
Door/ Window
Detector (configured
on zone 2) on the back or patio doors.
3. Place the 1st PIR Detector (set on zone 3) and
the 2nd PIR Detector (set on zone 4) in two of the following locations:
i) downstairs in the main living room containing
most valuables, or
ii) on the landing covering the access routes
between bedrooms and the stairs, or
iii) in the hall covering the Control Panel and
routes between downstairs rooms.
8
Control Panel
Magnetic
Door/ Window
Detector
Remote Control
PIR Movement
Detector
SHED
LOUNGE
GROUND FLOOR
GARAGE
KITCHEN
HALL
DINING
ROOM
A
B
C
D
E
External
Solar Siren
Back Door
A
B
E
C
C
C
C
C
A
D
D
D
D
D
D
D
1
45
6
7
ENTER
ESC
POWER ALARM
STATUS
ALARM MEM/ MESSAGE
LINE STATUS
!
9
2 3
8
?
0
F
Dummy Siren
F
Page 9
9
The system may be expanded with additional detectors, Remote Controls and Keypads to provide even greater protection. However, the following rules should be followed:
a. Any detectors covering the main door and the
route to the Control Panel should be set on zone 1 only.
b. Any detectors covering the remainder of the lower
floor should be set on zones 2 to 4 only.
c. Any detectors placed upstairs (which are not
required when activating Part-Arm1) should be set on zones 5 or 6 only.
The pre-configured system defaults provide a basic functional system, which will suit most installations, (i.e. a 2 floor house):
The systems factory settings are pre-configured to provide a basic functional system to suit most typical basic installations:
Detectors on zones 1 and 2 will have a 30 second
entry delay period. Detectors on all other zones are configured as INSTANT, (i.e. they have no entry delay).
The system has a 3 minute alarm duration.
The Zone Lockout feature is ON so that if any
single zone triggers an alarm more than 3 times they will be ignored until the system is next disarmed, (this feature helps protect against continuous false alarms).
PART-ARM 1 is configured with a 30 second exit
delay and operates with detectors on zones 1 to 4 only.
PART-ARM 2 is OFF.
All other system features, (e.g. telephone dialler,
Latch Key, Chime etc.) are OFF and not programmed.
Note: If you wish to change the system configuration
away from the above example and factory settings and customise it to your own unique requirements or activate any of the more advanced system features then refer to the Programming section on page 32.
REMOTE CONTROL UNIT
The Remote Control Unit(s) is used to Arm in either
Arm or Part-Arm and to Disarm the system.
The Remote Control Unit also incorporates a Personal Attack (PA) switch. Activating the PA switch on the side of the Remote Control will immediately trigger an Alarm (unless the Control Panel is in Test or Program Modes) even if the system is disarmed. The alarm can be cancelled using the Remote Control by pressing the ‘DISARM’ button.
Up to a total of 6 Remote Controls and/or Keypad Units can be used with your system, providing they are all operated within effective radio range of the Control Panel.
The Remote Control is powered by a CR2032 type Lithium cell which under normal conditions will have an expected life of approximately 1 year. Under normal battery conditions the Transmit LED on the Remote Control will only illuminate when a button is pressed.
However, under low-battery conditions this LED will continue to flash after the button has been released. When this occurs the battery should be replaced as soon as possible.
IMPORTANT:
As soon as installation is complete
The default Master User Access Code for the Control Panel should be changed to your own code that only you know.
User Access Codes 1-6 for the Control Panel should be changed to your own codes that only the relevant system user knows.
The system Time and Date must be configured.
Slide up to operate
Transmit LED
Personal Attack Switch
Arm
Part-Arm
Disarm
Page 10
10
CONFIGURING THE REMOTE CONTROL
1. Remove the rear cover by undoing the small
screw on the rear of the Remote Control and keeping it safe for later.
2. Insert the battery under the clip ensuring that
the +terminal faces upwards away from the Circuit Board.
3. Replace the rear cover and fixing screw. Do not
over tighten the screw as this could damage the thread.
TESTING THE REMOTE CONTROL
4. Press the button. The Transmit LED
should illuminate while the button is pressed and extinguish within 1 second of releasing the button.
5. Pressing any button on the Remote Control will
illuminate the Transmit LED as before to check that it is functioning correctly.
CONTROL PANEL
POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control
Panel, the following points should be considered.
1. The Control Panel should be located in a
position out of sight of potential intruders and in a safe location, but easily accessible for system operation and leaving and entering the house within the set time period.
2. The Control Panel should be mounted on a sound
flat surface to ensure that the rear tamper switch on the Control Panel is closed when the Panel is mounted. The Control Panel should be mounted at a convenient height of between 1.5 and 2 metres and in a position where it will be seen each day.
Note: If small children are in the household, a
further consideration should be given to keeping the unit out of their reach.
3. It is recommended that the Control Panel should
be positioned such that the Exit/Entry tone (emitted by the Control Panel) can be heard from outside the property.
4. The Control Panel should be mounted within a
protected area so that any intruder cannot reach the Control Panel without opening a protected door or passing through an area protected by a PIR Detector when the system is armed.
5. The Control Panel must be located within
reach of a mains socket.
6. If any of the telephone based functions are to be
used then the Control Panel will need connecting to a convenient telephone point.
1
45
6
7
ENTER
ESC
POWER ALARM
STATUS
ALARM MEM/
MESSAGE
LINE
STATUS
!
9
2 3
8
?
0
LCD Display Window
Status Indicator LEDs
Keypad
Battery Clip
Battery
Page 11
11
Note: It is recommended that the telephone
connection lead is not extended beyond 10 metres before connecting to a telephone master or secondary outlet.
7.
DO NOT fix the Control Panel onto or very close to metalwork (i.e. radiators, water pipes, etc) as this could affect the radio range of the device.
INSTALLING THE CONTROL PANEL
1. Undo the two cover fixing screws on top of the
panel and open the cover. The cover is hinged along the bottom edge.
2. Unclip and remove the two back-up batteries on
either side of the panel.
3. Hold the Control Panel in position on the wall
and mark the positions of the four fixing holes. Remove the panel, drill four 5mm holes and fit the 22mm wall plugs.
Note: The wall plugs supplied with the product
are not suitable for plasterboard walls. If mounting the Control Panel onto plasterboard use appropriate wall plugs.
4. Fit two 18mm No.4 screws into the top holes
until 3mm protrudes from the wall face and hang the Control Panel over these screws using the two keyhole slots in the top corners of the panel casing.
5. Route the cable from the Power Supply Adaptor
up behind and on the right hand side of the Control Panel and connect the plug to the DC power socket in the panel. Ensuring that the cable is not trapped between the panel and the wall.
6. Fix the Control Panel to the wall using two 18mm
No.4 screws in the lower two fixing holes in the Control Panel and tighten the upper fixing screws until they just grip the casing. Do not over-tighten the screws as this could damage or distort the casing.
Inside View of Control Panel
Upper Keyhole Fixing Hole
– ve Terminal (Black Lead)
+ ve Terminal (Red Lead)
Reset Jumper Link P1
Power Supply Jack Socket
Upper Keyhole
Fixing Hole
+ ve Terminal
(Red Lead)
– ve Terminal
(Black Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply Cable Access Hole
T1 T2 GND T3 T4 N.C. CN.O.GNDGND BUZ BUTTAMP GND B+ V+ OUT GND
Do not drill the fixing holes with the Control
Panel in position; as the resulting dust and vibration may damage the Control Panel’s internal components and invalidate the guarantee.
Page 12
12
7. Ensure that the Reset Jumper Link (P1) and the
External Tamper Switch Jumper Link (P51) are set in the OFF position.
8. Connect battery leads to both back-up batteries
and refit batteries.
LEFT Battery: Red lead to the Red (+) battery
terminal
Black lead to the Black (-) battery terminal
RIGHT Battery: Red lead to the Red (+) battery
terminal
Black lead to the Black (-) battery terminal
Note: The Power LED may flash to indicate that
the unit is being operated from the back-up batteries and that mains supply is not present.
9. If fitted, remove the plastic film covering the LCD
display and on the display window on the cover.
10. Close the lid of the Control Panel and fasten the
cover fixing screws.
11. Plug in and switch ON the Power Supply
Adaptor, (the Power LED should illuminate).
12. If required, connect the Control Panel to the
telephone line using the cable supplied by
inserting the small RJ11 plug into socket marked LINE located on the bottom edge of the Control Panel. If the cable supplied is not long enough to reach a suitable phone point then it will need extending using a coupler and extension lead (not supplied).
LINKING A REMOTE CONTROL OR
REMOTE KEYPAD TO THE CONTROL PANEL
If there are already 6 Remote Controls/Keypads
linked to the Control Panel then it will not be possible to link any more. Attempting to learn a 7th device will cause the panel to produce a single long beep and display ‘Cannot Learn - System Full’ message on screen for 3 seconds.
With unit in Standby mode (Power LED only illuminated).
1. Press
This puts the Control Panel into Programming Mode.
‘1. USER SETUP’ will be displayed.
2. Use the and buttons to scroll through
the menu until ‘2. SYSTEM SETUP’ is displayed and press . ‘2-1 Remotes’ will be displayed.
3. Press again.
The number of Remote Controls/Keypads already linked will be shown, (e.g. if there are two Remotes Controls and one Remote Keypad linked the display will show ‘2.1 Remotes = 3’).
The new Remote Control/Keypad can be programmed as follows:
4. Press .
OFF ON
Jumper
Link
O. GND V+ OUT GND
External Tamper Switch
Jumper Link P51
Reset Jumper
Link P1
Jumper
Link
Jumper
Link
IMPORTANT: Take care when connecting
battery leads to the batteries as connecting incorrectly could damage the batteries or the Control Panel.
ENTER
, ,
Master User Access Code
1423
Note: If the Control Panel Tamper alarm sounds
during the installation reset the alarm by pressing
on the Control Panel.
IMPORTANT: The keys must be pressed firmly
and within 5 seconds of each other. If you make a mistake, press and start the sequence again.
1423
ENTER
, ,
User Access Code
ESC
ENTER
ENTER
3
Page 13
13
The panel will now listen for a valid signal from a new Remote Control or Keypad.
The Panel will remain in Learn Mode for 30s.
If a valid signal is not received from a new device within 30s it will automatically exit Learn Mode and return to the top of level 2.0.
5. Press on the Remote Control, or
Press on
the Remote Keypad.
If the device is new and not already linked to the system the control panel will produce two short beeps and the display will show ‘New Device’
and the type or the detected device;
(e.g. Remote or Keypad).
6. Confirm the new device ID code from the same
new Remote Control or Remote Keypad within 15s as follows:
Press on the Remote Control, or
Press on
the Remote Keypad.
The panel will produce three short beeps and the LCD will show ‘Device Confirmed’.
The LCD will then show ‘Saving New Device’
while the ID code of the new detector is stored
into memory.
7. Press twice to return to standby.
TESTING THE CONTROL PANEL AND
REMOTE CONTROL
1. Press to put the
system into Test Mode.
Use the and buttons to scroll through the menu until ‘Detector Walk Test’ is displayed.
2. Press to activate Walk Test.
During the test the LCD will display:
3. Press the Arm, Part Arm, Disarm and Personal
Attack buttons in turn on the Remote Control.
Note: If no signal is received by the Control Panel
within 10 minutes, the display will return to ‘Detector
Walk Test’.
When signals are received from linked Remote Control, the appropriate messages will be displayed on the LCD screen:
Remote Control - ARM
Remote Control/Keypad - DISARM
Remote Control - PANIC/PA
4. Press to return to the top level menu of
TEST MODE.
Note: If the device is already linked to the
control panel then the panel will produce a single long beep and the received signal from the device will be ignored.
Note: If the confirmation signal is not
received within 15s the control panel will produce a single long beep and exit the learning process. The learning process will need to started again to learn the new device into memory.
,
Keypad User Access Code
? ? ? ?
,
Keypad User Access Code
? ? ? ?
1
ESC
ESC
1423
ENTER
, ,
User Access Code
ENTER
Walktest
Waiting...
Remote/Keypad
Arm
Remote/Keypad
Disarm
Remote/Keypad
Panic/PA
Page 14
14
PASSIVE INFRA-RED (PIR)
MOVEMENT DETECTORS
PIR Detectors detect movement in a protected area
by detecting changes in infra-red radiation levels caused for example when a person moves within or across the PIR’s detection pattern. If movement is detected an alarm will be triggered, (if the system is armed). PIR Detectors will also detect animals, so ensure that pets are not permitted access to areas fitted with PIR Movement Detectors when the system is armed.
The Detector incorporates an anti-tamper protection feature to protect against attempts to interfere with the device. If the battery cover is removed, an alarm will immediately occur at any time, (unless the system is in Program or Test Modes).
The PIR Detector also incorporates a sensitivity adjustment feature to compensate for situations where the detector may be triggered by environmental changes, (e.g. insects, air temperature, etc).
To conserve power and maximise battery life the PIR Detector will only detect movement if there has been no movement detected within the previous 2 minutes, (this is known as the detectors sleep period).
The PIR Detector is powered by a PP3 Alkaline battery which under normal conditions will have an expected life of approximately 1 year. When the battery level drops, with the PIR in normal operation mode and the battery cover fitted, the LED behind the detection window will flash. When this occurs the battery should be replaced as soon as possible. (Note: in normal operation, the LED behind the lens will not flash on detection of movement).
The system allows you to link one Detector to a zone, provided that the Detector is mounted within effective radio range of the Control Panel.
POSITIONING THE PIR DETECTORS
The recommended position for a PIR Detector is in
the corner of a room mounted at a height between 2 and 2.5 metres. At this height, the detector will have a maximum range of up to 12 metres with a field of view of 110°.
When deciding upon the mounting position for the detector the following points should be considered to ensure trouble free operation:
1. Do not position the Detector facing a window or
where it is exposed to or facing direct sunlight. PIR Detectors are not suitable for use in conservatories.
2. Do not position the Detector where it is exposed
to draughts.
3. Do not position the Detector directly above a
heat source, (e.g. fire, radiator, boiler, etc).
4. Where possible, mount the Detector in the
corner of the room so that the logical path of an intruder would cut across the fan detection pattern. PIR Detectors respond more effectively to movement across the device than to movement directly towards it.
5. Do not position the Detector in a position where
it is subject to excessive vibration.
6. Ensure that the position selected for the PIR
Detector is within effective range of the Control Panel.
7. Do not fix the PIR Detector onto or very close
to metalwork (i.e. radiators, water pipes, etc) as this could affect the radio range of the device.
Note: When the system is Armed, pets should not
be allowed into an area protected by a PIR Detector as their movement could be detected and trigger an alarm.
2m - 2.5m
2
3
416
78591
2
Detector Range (metres)
10 11
110°
180°
12m
Page 15
INSTALLING AND CONFIGURING THE
PIR DETECTORS
1. Undo and remove the fixing screw from the
bottom edge of the PIR Detector, (keep the screw safe for later). Carefully pull the bottom edge of the detector away from the rear cover and then slide down to release the top clips.
2. Carefully drill out the required mounting holes in
the rear cover using a 3mm drill according to whether the unit is being mounted in a corner or against a flat wall.
3. Using the rear cover as a template, mark the
positions of the fixing holes on the wall.
4. Fix the rear cover to the wall using the two
18mm No.4 screws and 22mm wall plugs, (a 5mm hole will be required for the wall plugs). Do not over-tighten the screws as this may distort or damage the cover.
Note: The wall plugs supplied with the product
are not suitable for plasterboard walls, if mounting the Detector onto plasterboard use appropriate wall plugs.
5. To select the required sensitivity, set switch SW3
as follows:
UP HIGH sensitivity DOWN LOW sensitivity
Note: The recommended setting is HIGH.
However, in cases of extreme environmental problems or if unexplained false alarms are experienced, it may be necessary to set the sensitivity to LOW. Setting the device to LOW sensitivity will require a greater amount of movement in order to trigger the device.
6. Connect the PP3 Alkaline battery to the battery
clip. The LED behind the lens will rapidly flash for approximately 2-3 minutes until the PIR has stabilised. The LED will then stop flashing and turn OFF.
TESTING A PIR DETECTOR
INDEPENDENTLY
7. Ensure that the LED indicator has stopped
flashing rapidly.
8. The ‘Test Mode’ button (SW1) is used to put
the PIR Detector into Walk Test Mode, which overrides the 2 minute sleep period and allows the operation of the detector to be checked during installation. Press and hold the button for 2 seconds to activate Test Mode for a fixed 5 minute after which it will automatically revert to normal operation.
15
Rear Cover
Fixing Screw
Rear Cover
Flat Wall Mounting
Corner Wall
Mounting
Fixing Screw
SW2 (Tamper)
SW1 (Test Mode)
SW3
S
e
n
s
it
iv
it
y
H
i
L
o
w
S
W
1
T
e
s
t
M
o
d
e
S
W
2
SW3 (Sensitivity)
SW3 up
High Sensitivity
SW3
Sensitivity Hi Low
SW3
Sensitivity Hi Low
SW3 down
Low Sensitivity
Page 16
On initial installation the detector should be
configured into Walk Test ready for testing, (i.e. Pressing down SW1 for 2 seconds).
9. Refit the PIR Detector to the rear cover by
offering the detector up to the rear cover and locate the clips in the top edge into the rear cover. Push the lower edge of the detector into place and refit the fixing screw in the bottom edge of the PIR to secure in position. Do not over-tighten the screws as this may damage the casing.
10. Walk into and move slowly around the protected
area within the 5 minutes of pressing SW1. Each time the detector senses movement the LED indicator behind the lens will flash.
LINKING A PIR DETECTOR TO THE
CONTROL PANEL
1. Remove the PIR Detector from its rear cover
after installing and configuring it.
2. With the system in Standby
Press
to enter Program Mode.
3. Scroll through the programming menu until
‘3. ZONE SETUP’ is displayed and press .
4. Enter the zone number to be configured (1 - 36)
and press .
‘3-1 ZX Empty’ will be displayed (X = Zone no.)
Note: Zones 33-36 the wired zones are the
same except there is no learn menu option as these are wired.
5. Press .
6. To learn a new detector ID code and link it to
the selected zone press .
The panel will now listen for a valid signal from a new detector to link to the zone.
The Panel will remain in Learn Mode for 30s.
If a valid signal is not received from a new device within 30s it will automatically exit Learn Mode and return to the top of level 2.0.
7. Activate the Tamper Switch on the PIR detector.
If the detector is new and not already linked on any security zone the panel will produce two short beeps and the display will show ‘New
Device’ and the type of device detected (PIR).
8. Confirm the new device ID code by activating
the Tamper Switch on the same new PIR detector within 15 seconds.
The panel will produce three short beeps and the LCD will show ‘Device Confirmed’.
The LCD will then show ‘Saving New Device’
while the ID code of the new detector is stored
into memory.
9. Refit the PIR to its rear cover.
10. After completing the Zone Setup press to
return to the top level of programming menu.
Note: Ensure that there is no movement in front of
the PIR for 3 minutes to allow it to stabilise before entering test mode.
SW1 (Test Mode)
Press for 2 seconds to activate Walk Test mode
SW3
Sensitivity Hi Low
SW1
Test Mode
SW2
16
????
ENTER
, ,
Installer Access Code
ENTER
ENTER
ENTER
3
Note: If the detector is already linked to the
control panel on any other zone then the panel will produce a single long beep and the received signal from the detector will be ignored.
Note: If the confirmation signal is not
received within 15s the control panel will produce a single long beep and exit the learning process. The learning process will need to be started again to learn the new device into memory.
ESC
Page 17
TESTING A PIR DETECTOR WITH THE
CONTROL PANEL
1. Ensure that the system is in Test Mode (see
page 13).
2.
Use the and buttons to scroll through
the menu until ‘Detector Walk Test’ is displayed and press .
will be displayed.
Note: If no signal is received by the Control Panel
within 10 minutes, the display will return to ‘Detector
Walk Test’
.
3.
Walk into and move slowly around the protected
area, each time the detector senses movement the LED indicator behind the lens will flash.
In addition, the Control Panel will beep to indicate that the alarm signal has been received and the identity of the zone that the detector is configured for will be displayed.
4.
Remove the back cover of the PIR detector. The
Control Panel should beep and display:
to show that the detector’s tamper switch has been activated.
5.
Refit the cover to the PIR Detector.
6.
Press to exit Test Mode and return to
standby.
MAGNETIC DOOR/WINDOW
DETECTORS
The Magnetic
Door/ Window Detector
comprises of two parts; a Detector and a Magnet. They are designed to be fitted to either doors or windows with the Magnet mounted on the opening part of the door/ window and the Detector mounted to the frame.
When the protected door or window is opened and the Magnet is moved away from the Detector an alarm will be triggered if the system is armed,
The Magnetic
Door/ Window
Detector has the facility to connect an additional wired Magnetic Contact. This must be of a normally closed contact type with the contact being opened in order to generate an alarm condition.
The Magnetic
Door/ Window
Detector is powered by two CR2032 type Lithium cells which under normal conditions will have an expected life of approximately 1 year. Under normal battery conditions the LED on the Detector will not illuminate when the Detector is triggered, (unless the detector is in Test Mode with the battery cover removed). However, under low battery conditions this LED will be illuminated for approximately 1 second when the detector is triggered. When this occurs the batteries should be replaced as soon as possible.
The system allows you to link one Detector to a zone, provided that the Detector mounted within effective radio range of the Control Panel.
POSITIONING THE MAGNETIC
DOOR/ WINDOW DETECTORS
The Door/ Window Detector is suitable for mounting in
dry interior locations only.
Decide which doors and windows are to be protected by fitting Door/ Window Detectors, (usually the front and back doors as a minimum will have Door/Window Detectors fitted). However additional detectors may be fitted where required to other more vulnerable doors or windows, (e.g. garage, patio/conservatory doors etc).
Ensure that the position selected for the Door/ Window Detector is within effective range of the Control Panel.
17
ENTER
Walktest
Waiting...
Zone X : PIR
Tamper
ESC
IMPORTANT: In normal operation, the LED
indicator behind the detector lens will not flash on movement detection, (unless the battery is low).
When the detector is fully installed i.e. battery cover fitted and in operating mode; in order to conserve power and maximise battery life the PIR Detector will only detect movement if there has been no movement detected within the previous 2 minutes.
Page 18
Do not fix the Detector onto or very close to
metalwork (i.e. radiators, water pipes, etc) as this could affect the radio range of the device.
On PVC door/window frames, it may be necessary to
space the Detector and Magnet away from the metal surface using a plastic or wooden spacer to achieve the necessary radio range.
INSTALLING AND CONFIGURING THE
MAGNETIC DOOR/WINDOW DETECTORS
The Detector and Magnet should be mounted
together along the opening edge of the window/door opposite the hinges. Ensure that the parallel gap between the Magnet and Detector is less than 10mm and that the arrow on the magnet is aligned with the mark on the detector.
1. Remove the battery cover by sliding and lifting it
off. (DO NOT use a screwdriver to lever it off).
2. Slide the two batteries supplied into the battery
holder, ensuring that the +side is uppermost on each battery as it is installed.
3. If necessary, refit the battery holder into the
detector ensuring that the spring clip connectors slide onto either side of the circuit board.
The Detector should be mounted on the fixed part of the frame and the magnet on the opening part.
The Detector and Magnet should be mounted using the double sided adhesive pads or screws provided.
Note: If mounting the device using the adhesive
pads, ensure that the mounting surfaces are clean and dry before mounting.
4.
If fixing the detector with screws first remove
the battery holder by carefully tilting up the end and pulling away from the printed circuit board (PCB).
The top of the Detector is secured by hanging the keyhole slot over the head of the 10mm pan head screw. The bottom of the Detector is secured using the 12mm counter-sunk head screw fitted within the battery compartment. Carefully drill out the centre of the fixing screw hole in the battery compartment using a 3mm drill. Fit the Magnet using the two 15mm fixing screws. Do not over- tighten the screws as this may distort or damage the casing.
5. If an additional wired Magnetic Contact is
required, this should be wired to the terminal block provided in the battery compartment.
The wired contact should be connected using a maximum length of 1.5 metres of any of the following:
6 core alarm cable
2 core bell wire (6 x 0.2mm minimum)
2 core 24AWG wire
A cable entry cut-out is provided beside the terminal block in the battery cover.
18
Double Sided Tape
OR Screw Fixin
g
Raised Head Screw,
Key-hole Slot Fixing
Small Counter-sunk Screw Fixing
Slide Open and Lift Off
Do Not Use A Screwdrive
r
Battery Connector
Tilt and Remove Battery Holder and Insert Two Batteries
Fit TWO
Batteries
Detector
Magnet
Alternative Mountings
Page 19
6. Switch SW3 is used to enable/ disable the
internal / external wired magnetic contact.
Position of SW3 Function
INT. Internal Contact ON
INT./EXT. Internal and External
Contacts ON
7. Set the Door/ Window Detector by setting the
position of the switch (SW3).
If setting to the INT. position, only the internal contact will be active. When two contacts are in use for internal and external connection simultaneously (INT./EXT. position), only one activation will be counted if one of the contacts is opened. If one contact is left open and the other closed contact is opened then an activation will be counted.
If using external contacts wired to the Detector, set to the INT./EXT. position.
8. Refit the battery cover.
TESTING A MAGNETIC DOOR/ WINDOW
DETECTOR INDEPENDENTLY
9.
Remove battery cover to activate the tamper switch.
As the button is released the LED indicator will illuminate for approximately 1 second to show that the tamper switch has been triggered and a signal is being transmitted.
10. Open the door/window to remove the Magnet
from the Detector.
As the Magnet is moved away from the Detector the LED indicator will illuminate for approximately 1 second to show that the Detector has been triggered and a signal is being transmitted.
Note: It does not matter if the LED indicator
illuminates as the magnet is brought towards the detector.
LINKING A MAGNETIC DOOR/ WINDOW
DETECTOR TO THE CONTROL PANEL
1. Remove the battery cover after installing and
configuring it.
2.
With the system in Standby
Press
to enter Program Mode.
3. Scroll through the programming menu until
‘3. ZONE SETUP’ is displayed and press .
4.
Enter the zone number to be configured (1 - 36)
and press .
Note: Zones 33-36 the wired zones are the
same except there is no learn menu option as these are wired.
5. To learn a new detector ID code and link it to the
selected zone
press .
The panel will now listen for a valid signal from a new detector to link to the zone.
The Panel will remain in Learn Mode for 30s.
If a valid signal is not received from a new detector within 30s it will automatically exit Learn Mode and return to the top of level 3.1
19
Location of
Key-hole Screw
(underside)
Hole for Mounting Screw
Terminal Block for
Additional Wired
Magnetic Contact
Tam per
Switch
8mm
11mm
SW3
Switch SW3
INT.
INT./EXT.
Switch SW3
INT./EXT. Position
Switch SW3
INT. Position
SW3
INT.
INT./EXT.
SW3
INT.
INT./EXT.
IMPORTANT:
If not using external contacts,
set to the INT. position for the Detector to operate correctly.
????
ENTER
, ,
Installer Access Code
ENTER
ENTER
3
Page 20
20
6. Activate the Tamper Switch on the MAG
detector.
If the detector is new and not already linked on any security zone the panel will produce two short beeps and the display will show ‘New
Device’ and the type of device detected (MAG).
7. Confirm the new device ID code by activating
the Tamper Switch on the same new MAG detector within 15 seconds.
The panel will produce three short beeps and the LCD will show ‘Device Confirmed’.
The LCD will then show ‘Saving New Device’
while the ID code of the new detector is stored
into memory.
8. Refit the battery cover.
9. After completing the Zone Setup press to
return to the top level of programming menu.
TESTING A MAGNETIC DOOR/ WINDOW
DETECTOR WITH THE CONTROL PANEL
1. Ensure that the system is in Test Mode (see
page 13).
2.
Use the and buttons to scroll through
the menu until ‘Detector Walk Test’ is displayed and press .
will be displayed.
Note: If no signal is received by the Control Panel
within 10 minutes, the display will return to ‘Detector
Walk Test’
.
3.
Open the door/window to remove the Magnet
from the Detector.
In addition, the Control Panel will beep to indicate that the alarm signal has been received and the identity of the zone that the detector is configured for will be displayed.
4.
Remove the battery cover. The Control Panel
should beep and display:
to show that the detector’s tamper switch has been activated.
5.
Refit the battery cover.
6.
Press to exit Test Mode and return to
standby.
IMPORTANT: With the battery cover fitted the
LED indicator will not flash when the door / window is opened, (unless the battery is low).
Note: If the detector is already linked to the
control panel on any other zone then the panel will produce a single long beep and the received signal from the detector will be ignored.
Note: If the confirmation signal is not
received within 15s the control panel will produce a single long beep and exit the learning process. The learning process will need to be started again to learn the new device into memory.
ESC
ENTER
Walktest
Waiting...
Zone X : MAG
Tamper
ESC
Page 21
The Siren is encapsulated within a tough
polycarbonate housing that also provides full protection against adverse weather conditions.
An LED indicator unit is built into the Siren to act as a visible deterrent and indication that the system is active. The LEDs will slowly and alternately flash whether the system is Armed or Disarmed. When an alarm occurs the LEDs will flash rapidly together.
An integral tamper switch provides additional security protection to the Siren and will immediately trigger an alarm should any unauthorised attempt be made to interfere with and remove the Siren cover.
The Siren is powered by a rechargeable sealed lead acid battery. A solar panel mounted on the top of the housing charges the battery during daylight hours. During darkness, only a small amount of energy is required to operate the Siren unit. A 9V Alkaline PP3 battery is supplied to boost the initial power to the unit when the system is first activated until the solar panel charges the main battery. (This battery is only designed to last for a short period until the main rechargeable battery has obtained sufficient charge). It does not need to be replaced.
POSITIONING THE SOLAR SIREN
The Siren should be located as high as possible in
a prominent position on an external wall so that it can be easily seen and heard. The Siren should be mounted on a sound flat surface so that the rear tamper switch is not activated when mounted.
In order to provide the maximum amount of daylight to the solar panel, the Siren should ideally be mounted on a south facing wall. However, an easterly or westerly position will suffice, but mounting the device on a north facing wall should be avoided due to the short dark days of winter months.
Shadows cast by neighbouring walls, trees and roof overhangs should also be avoided. If the Siren is to be mounted below the eaves, it should be positioned a distance of at least twice the depth of the eaves overhang below the eaves. Remember that in winter the sun is lower in the sky and you should avoid winter shadows where possible.
The Solar Siren contains a sophisticated radio receiver. However, reception of radio signals can be affected by the presence of metallic objects within the vicinity of the Siren. It is therefore important to mount the Siren a minimum distance of 1 metre away from any external or internal metalwork, (i.e. drainpipes, gutters, radiators, mirrors etc). Be especially aware of radiators mounted on the inside wall behind possible locations for the Siren.
Ensure that the position selected for the Siren is within effective range of the Keypad and all detectors.
INSTALLING AND CONFIGURING
THE SOLAR SIREN
Ensure that the system is in Test Mode.
Press
to put the system into Test Mode.
1. Working on a table, undo the two battery cover
fixing screws and remove the battery cover.
2. Under the cover you will also find a row of 5 DIP
Switches labelled SW3 and a
“LEARN” button.
3. Ensure that DIP switch 5 of SW3 on the main
board is set to
OFF (“SIREN”) for use with this
alarm system.
4. DIP switch 1 marked ALARM TIME” is used to
limit the maximum period for which the external siren will sound before it will be automatically shut down, (even if the Control Panel is still in alarm):
ON 10 minutes OFF 3 minutes
EXTERNAL SOLAR SIREN
21
Ensure that the tamper switch does not fall
into the recess between brick courses as this could prevent the switch from closing and give a permanent tamper signal.
1423
ENTER
, ,
User Access Code
C.U. OR SIREN
Set to 'OFF'
ON
1
2345
Switch SW3
Page 22
22
5. DIP switch 2 marked AJ” does not function for
this system and should be ignored.
6. DIP switch 3 marked ALARM SOUND” if OFF
will prevent the siren from sounding during an alarm, (this will not affect the warning beeps):
ON Siren enabled OFF Siren disabled
7. Switching between Service Mode and Operating
Mode generates a series of beeps. It is possible to disable these acknowledgement beeps with DIP switch 4 marked “BEEP SOUND”.
ON Beeps enabled OFF Beeps disabled
8. Now see Power-Up of the Solar Siren.
POWER-UP OF THE SOLAR SIREN
Note: The use of ear defenders is advisable when
working in close proximity to the Siren due to the high sound level produced by this device when triggered. Whenever the Siren is powered-up, it will automatically power-up in Service Mode. It cannot be switched out of Service Mode and into Operating Mode until the Control Panel is linked to it.
9. Connect the rechargeable battery to the battery
leads. Connect the Red lead to the Red (+ve) terminal and the Black lead to the Black (-ve) terminal.
Connect the 9V 6LR61 (PP3) power-up battery to the battery clip.
10. Press the tamper switch, both indicator LEDs will
flash together several times. The LEDs will then continue to flash alternately every 5 seconds thereafter to indicate that the Siren is functioning (still in Service Mode).
11. If fitted remove the protective film covering the
Solar Panel.
12. Press and hold the Learn button inside the
Sirens battery compartment for 5 seconds until the Siren enters Learn Mode and produces a single short low volume beep and both Learn and Indicator-LEDs start flashing together slowly (once every 2 seconds).
13. Use the and buttons to scroll through
the menu until ‘Link Panel to Wirefree Siren’ is displayed.
14. Press .
9 Volt startup
battery
Siren
7.5 Volt DC charging adaptor input
ALARM TIME
A J
C.U. OR SIREN
ALARM SOUND
BEEP SOUND
Learn
LED
ON
1
2345
ALARM TIME
A J
ALARM SOUND
BEEP SOUND
C.U. OR SIREN
ON
1
2345
ALARM TIME
AJ
ALARM SOUND
BEEP SOUND
C.U. OR SIREN
Tamper
Switch
Learn
Switch
Switch SW3
6 Volt 1.2Ah
rechargeable
battery
Wall mounting plate
The siren will remain in Learn Mode for 30s. If a valid signal is not received from a Control Panel within that period it will automatically exit Learn Mode. It will remain in Service mode.
The LCD will display ‘Sending ID Codes wait
15s…’ for 15s.
After 2 seconds the ‘Siren Stop’ signal will be transmitted by the panel to the siren to learn the panel’s code.
The siren will produce a single short beep and
ENTER
Page 23
15. Now scoll through the menu again until ‘Wirefree
Siren Service OFF’ is displayed and press .
The Siren will produce a single long beep followed by two short beeps.
16. Do not exit Test Mode at this stage. Now test the
Wireless Siren prior to installing it on the wall. (See step 17 below).
TESTING THE WIRELESS SOLAR SIREN
Enter Test Mode if not already in (see page 13).
17. Use the and buttons to scroll through
the menu until ‘Wirefree Siren Test’ is displayed and press .
During the test the LCD will display:
18. The Siren will activate for 5 seconds to show it is
working. Now follow the instructions below to mount the Solar Siren on to the wall.
MOUNTING THE SOLAR SIREN ON
TO THE WALL
Prior to mounting the Siren, the Siren needs to be
placed into Service mode again else pressing the Siren’s Tamper Switch against the wall will trigger the Siren.
19. Scroll through the Test Mode menu using the
and buttons until ‘Wirefree Siren
Service ON’ is displayed and press .
The Siren will produce two short beeps followed by one long beep.
20. Hold the clear plastic mounting template
supplied in position on the wall and mark the positions of the four mounting holes. A spirit level placed on the top edge will help ensure you get the unit level.
21. Undo the fixing screw securing the mounting
plate from the bottom edge of the siren and remove the plate.
22. Drill four 6mm holes and fit the wall plugs.
23. Fit the two 30mm fixing screws in the top holes
leaving approximately 9mm of the screw protruding
.
24. Fit the keyhole slots in the top of the siren over
these screws and check that they form a neat fit with minimal movement. If necessary remove the siren and adjust the screws as required.
25. Remove the siren and fit the wall mounting plate
in position using the two 25mm fixing screws.
26. Fit the siren to the wall ensuring that the keyhole
slots are correctly fitted over the heads of the two top fixing screws and the lower fixing hole lines up with the wall plate.
27. Secure the Siren in place by fitting the lower
fixing screw in the wall plate. Do not over-tighten the screw as this could damage the thread.
28. Now switch the Siren out of service mode. In
the Test Menu, select ‘Wirefree Service OFF’
again and press .
The Siren will produce a single long beep followed by two short beeps.
29. Press to exit Test Mode and return the
system to Operating Mode.
23
the Indicator/Learn LEDs will start flashing
together rapidly, (once every second).
After 10s the ‘Siren Stop’ signal will automatically
be retransmitted by the Control Panel for the siren to confirm the control panels ID code.
The siren will produce single long beep and
the Indicator/Learn LEDs will stop flashing and remain ON for 3 seconds after which it will go out to indicate that the Control Panel is now linked to the Siren and its ID code recorded in memory.
ENTER
ENTER
ENTER
ENTER
Siren ON for 5s
Stop->ESC
IMPORTANT:
The Siren must now be left in
position for a
t least 24 hours to fully
charge the Main Battery before
testing or operating the alarm.
ESC
Page 24
INSTALLATION
1.
Remove the two screws on the battery
compartment cover on the rear of the Dummy Siren and remove the cover.
2.
Insert the 4 batteries ensuring correct polarity
3.
Refit the battery cover.
Rear view of Dummy Siren Unit
Mounting Template
On the front face of the Dummy Siren behind the red
lens, you will now notice two red deterrent LEDs flashing alternately every 5 seconds.
4.
Use the clear plastic mounting template to mark
the positions of the four mounting holes shown. A spirit level placed on the top edge will help ensure you get the unit level.
5.
Undo the fixing screw securing the mounting
plate from the bottom edge of the Dummy Siren and remove the plate.
6.
Drill four 6mm holes and fit the wall plugs.
7.
Fit the two 30mm fixing screws in the top holes
leaving approximately 9mm of the screw protruding.
8.
Fit the keyhole slots in the top of the Dummy
Siren over these screws and check that they form a neat fit with minimal movement. If necessary remove the Dummy Siren and adjust the screws as required.
9.
Remove the Dummy Siren and fit the wall
mounting plate in position using the two 25mm fixing screws.
10. Fit t
he Dummy Siren to the wall ensuring that the keyhole slots are correctly fitted over the heads of the two top fixing screws and the lower fixing hole lines up with the wall plate.
11.
Secure the Dummy Siren in place by fitting the
lower fixing screw in the wall plate. Do not over tighten the screw as this could damage the thread.
24
DUMMY SIREN
Page 25
25
(Optional)
The Control Panel incorporates a terminal block for
connection of a Hard-wired Siren. The connection terminal block is located inside the Control Panel behind the front cover. To access the terminal block
you must first put the system into Test Mode to prevent an alarm occurring.
To do this:
Press
Undo the two fixing screws on the top edge of the Control Panel and open the front cover.
Before making any connections, ensure that the Reset Jumper Link P1 is in the ‘OFF’ position and then remove the DC power jack and disconnect 1 of the back-up batteries.
The signalling contacts on all hardwired alarm and tamper zones must be volt free. (i.e. they must only open and close and not apply any self generated voltage across the contacts).
The contacts on zones 33, 34, 35 and the tamper circuit should be normally closed. An alarm will be triggered when the contacts open. On zones 33, 34 and 35, additional Wired Magnetic Door/Window Contact Detectors can be hardwired to these terminals (by purchasing the Response Wired Door/Window Contact Accessory Pack (PW1).
The contacts on zone 36 should be normally open. An alarm will be triggered when the contacts close.
Note: The External Tamper Switch jumper link P51
should be fitted into the ON position only if the hardwired tamper circuit is used, otherwise it must be in the OFF position.
After making your external connections reconnect the power supply and back-up Battery. Then close the Control Panel cover and tighten the fixing screws on the top edge.
Press to leave Test Mode and return to Standby.
EXTERNAL CONNECTIONS
T1 T2 GND T3 T4 N.C. CN.O.GNDGND BUZ BUTTAMPGND B+ V+ OUT GND
Permanent
12Vdc power supply output (100mA max.)
Latching
relay contacts
(volt-free)
Hardwired Zone
Connections
(using normally
closed contacts)
Switched 12Vdc
output for
wired Siren
(300mA max.)
T1
T2
GND
T3
T4
N.C.
C
N.O.
GND
GND
TAM P
GND
B+
V+
OUT
GND
Tamper circuit
connections for
wired Siren
Not Used
Te rminal Block
External Tamper
Switch Jumper
Link P51
Reset Jumper
Link P1
TERMINAL BLOCK DETAIL
OFF ON
Jumper Link
Reset Jumper Link P1
Jumper Link
1423
ENTER
, ,
User Access Code
ESC
Page 26
26
TESTING THE SYSTEM
The Control Panel has a built in test facility to
enable you to test the system at any time. However it is recommended that the system is tested at regular intervals not exceeding 3 months.
With the system in Standby
Press
The Arm and Part-Arm LEDs will flash
The system is now in Test Mode.
Note: After completing all required test functions
press to exit Test Mode and return to Standby.
Use the and buttons to scroll through the menu options.
Press to select displayed test.
Press .
Note: There will be an automatic time-out period of
10 minutes while in the test mode menu and no test option has been selected. When a test option is selected, this time-out period will stop.
When a test is exited, the system returns to the test mode menu again and the time-out period will be reset to 10 minutes.
TEST FUNCTION SUMMARY
Detector Walk Test
Alarm Test – Wireless Siren
Alarm Test – Internal Siren
Alarm Test – Wired Siren
Alarm Test – Auxiliary Relay
Link Control Panel to Spectra Lighting
Spectra Lighting Test
Link Control Panel to Wireless Siren
Wireless Siren Service Mode ON
Wireless Siren Service Mode OFF
Voice Dialler Test – phone number 1
Voice Dialler Test – phone number 2
Voice Dialler Test – phone number 3
Voice Dialler Test – phone number 4
Remote Manager Test – phone number 1 (Optional)
Remote Manager Test – phone number 2 (Optional)
1423
ENTER
, ,
User Access Code
Detector
Walk Test
press ENTER
Wirefree Siren
Test
press ENTER
Internal Siren
Test
press ENTER
Wired Siren
Test
press ENTER
Auxiliary Relay
Test
press ENTER
Link Panel to
Spectra Lighting
press ENTER
Spectra Lighting
Test
press ENTER
Link Panel to
Wirefree Siren
press ENTER
Wirefree Siren
Service ON
press ENTER
Wirefree Siren
Service OFF
press ENTER
Voice Dialler
Test Phone No.1
press ENTER
Voice Dialler
Test Phone No.2
press ENTER
Voice Dialler
Test Phone No.3
press ENTER
Voice Dialler
Test Phone No.4
press ENTER
Remote Manager
Test Phone No.1
press ENTER
Remote Manager
Test Phone No.2
Remote Manager Test 2...Wait
press ENTER
Remote Manager Test 1...Wait
Test phone No.4 Stop->ESC
Test phone No.3 Stop->ESC
Test phone No.2 Stop->ESC
Test phone No.1 Stop->ESC
Sending ID Codes
Wait 15s...
Service ON
Wait for 5s
Service OFF Wait for 5s
Sending ID Code
Wait 5s...
Siren ON for 5s Stop->ESC
Siren ON for 5s Stop->ESC
Relay ON for 5s Stop->ESC
Siren ON for 5s Stop->ESC
Walk Test
Waiting...
Lights ON for 5s Stop->ESC
ESC
ENTER
ESC
Page 27
27
DETECTOR TEST
Before commencing testing please ensure that there
is no movement in any PIR protected area for at least 3 minutes, all doors/windows protected by Door/ Window Detectors are closed and that all battery covers are correctly fitted.
Note: It may be helpful to have a 2nd person to
assist with this test.
Scroll through the top level Test Mode menu until
‘Walk Test waiting…’ is displayed and press .
If your system includes Remote Controls:
For each Remote Control:
1. Activate each button on the Remote Control
in turn including the PA switch. As each button is pressed the Control panel will beep and the button name will be displayed,
e.g. ‘Remote Disarm’ will be displayed when the button is pressed.
If your system includes PIR Detectors:
For each Detector:
2. Ensure that the area protected by the PIR
has been free from movement for at least 3 minutes and then walk into the area to trigger the detector
Note: To conserve power the PIR will only
detect movement if there has been no movement detected within the previous 2 minutes.
When the detector is triggered the Control Panel will beep to indicate that a signal has been received and display the zone of the detector that was activated.
3. Remove the battery cover from the detector
to operate the anti-tamper switch.
The Control Panel will beep and ‘Zone x :
PIR Tamper’ will be displayed.
If your system includes Door/Window Detectors:
For each Detector:
4. Open the protected door/window to trigger
the detector.
When the detector is triggered the Control Panel will beep to indicate that a signal has been received and display the zone of the detector that was activated.
5. Remove the battery cover from the detector
to operate the anti-tamper switch.
The Control Panel will beep and ‘Zone x :
MAG Tamper’ will be displayed.
Press to exit Walk Test and return standby.
TEST FUNCTION SUMMARY
When signals are received from linked devices the
appropriate messages will be displayed on the LCD as follows:
Remote Control/Keypad - ARM
Remote Control/Keypad – PART-ARM 1
Remote Control/Keypad – PART-ARM 2
Remote Control/Keypad - DISARM
Remote Control/Keypad – PANIC/PA
PIR Detector – Alarm
PIR Detector – Tamper
ENTER
ESC
Remote/Keypad
Arm
Remote/Keypad
Part-Arm 1
Remote/Keypad
Part-Arm 2
Remote/Keypad
Disarm
Remote/Keypad
Panic/PA
Zone X : PIR
Alarm
Zone X : PIR
Tamper
Page 28
28
MAG Detector – Alarm
MAG Detector – Tamper
Smoke Detector – Alarm
Smoke Detector – Tamper
ALARM TEST – WIRELESS SIREN TEST
Scroll through the menu until Wirefree Siren Test’ is
displayed on the LCD.
Press to activate the wireless siren for 5s.
During the test the LCD will display:
Press to stop the test early.
ALARM TEST – INTERNAL/WIRED
SIREN TEST
Scroll through the menu until Internal Siren Test’ is
displayed on the LCD.
Press to activate the Control Panel siren for 5s.
During the test the LCD will display:
Press to stop the test early.
ALARM TEST – WIRED SIREN TEST
Scroll through the menu until Wired Siren Test’ is
displayed on the LCD.
Press to activate the wired siren for 5s.
During the test the LCD will display:
Press to stop the test early.
ALARM TEST – AUXILIARY RELAY TEST
Scroll through the menu until Auxiliary Relay Test’ is
displayed on the LCD.
Press to activate the Auxiliary Relay (n.o./n.c.) contacts for 5s.
During the test the LCD will display:
Press to stop the test early.
LINKING THE CONTROL PANEL TO
SPECTRA LIGHTING RECEIVER
In order for the Control Panel to be able to activate
the Spectra Lighting Receiver the panels code must be learnt into memory on the Receiver. To do this the panel must transmit a code to it.
To link the Control Panel to the Spectra Lighting
Switching Receiver…
1. Place the Spectra Receiver into Learn
Mode…
Send the ID codes from the panel to the Spectra Receiver…
2. Scroll through the system menu until ‘Link
Panel to Spectra Lighting’ is displayed.
3. Press
The LCD will display ‘Sending ID Code wait 5s” for 5s.
After 3 seconds a “lights on for 10s” signal will be transmitted by the control panel to the Spectra receiver to learn the panel’s code into memory.
The Receiver will automatically exit Learn mode. ‘lights on for 10s’ signal.
Zone X : MAG
Alarm
Zone X : MAG
Tamper
Zone X : Smoke
Alarm
Zone X : Smoke
Tamper
Siren ON for 5s
Stop->ESC
Siren ON for 5s
Stop->ESC
ENTER
ESC
Siren ON for 5s
Stop->ESC
ENTER
ESC
Siren ON for 5s
Stop->ESC
ENTER
ESC
ENTER
ESC
ENTER
Page 29
29
SPECTRA LIGHTING TESTS
Scroll through the menu until Spectra Lighting Test’ is displayed on the LCD.
Press to activate the linked Spectra lighting for 5s.
During the test the LCD will display:
Press to stop the test early.
WIRELESS SIREN SERVICE MODE
The Siren includes a Service Mode facility which
prevents the siren’s tamper switch from triggering an alarm when it is removed from the wall for maintenance or to change the batteries. After changing the batteries and refitting in position, the Siren must be put back into Operating Mode, otherwise the siren will not sound in the event of an alarm.
WIRELESS SIREN SERVICE MODE ON
Scroll through the menu until Wirefree Siren
Service ON’ is displayed on the LCD.
Press to switch the Solar Siren into Service Mode.
The LCD will display the following for 3s while the
‘Siren Service Mode ON’ signal is transmitted:
The siren will produce two short beeps followed 1 second later by a single long beep. The Siren LEDs will flash together in conjunction with the beeps.
WIRELESS SIREN SERVICE MODE OFF
Scroll through the menu until Wirefree Siren
Service OFF’ is displayed on the LCD.
Press to switch the Solar Siren into Service Mode.
The LCD will display the following for 3s while the
‘Siren Service Mode OFF’ signal is transmitted:
The siren will produce two short beeps followed 1 second later by a single long beep. The Siren LEDs will flash together in conjunction with the beeps.
REMOTE MANAGER TEST (OPTIONAL)
– PHONE NUMBER 1
Scroll through the menu until Remote Manager Test
Phone No.1’ is displayed on the LCD.
Press to activate the Remote Manager dialler to call phone number 1.
1. If the Remote Manager is disabled the
panel will beep and the LCD will display the following for 5s:
2. If phone number 1 is not programmed the
panel will beep and the LCD will display the following for 5s:
3. If phone number 1 is programmed the
Remote Manager dialler will be activated and a test call will be placed to the Alarm Monitoring Service provider using phone number 1. During the test the LCD will display:
If an acknowledgment signal is received from the Alarm Monitoring Service the panel will beep and the LCD will display:
Lights ON for 5s
Stop->ESC
ENTER
ESC
Service ON
Wait...
beep-beep …………….…… beeeeeeeeeep
1 second
ENTER
Service OFF
Wait...
beeeeeeeeeep …………….…… beep-beep
1 second
ENTER
ENTER
Remote Manager
Disabled
Phone Number 1:
Not Entered
Test Phone Number 1:
Stop->ESC
Remote Manager
Test....PASS
Page 30
30
If no acknowledgment signal is received form the Alarm Monitoring Service the panel will beep and the LCD will display:
To stop the test early at the panel press .
REMOTE MANAGER TEST (OPTIONAL)
– PHONE NUMBER 2
Scroll through the menu until Remote Manager
Test: Phone No.2’ is displayed on the LCD.
Press to activate the Remote Manager dialler to call phone number 2 following the same procedure as described above for phone number 1 with the LCD displays modified to show phone number 2.
VOICE DIALLER TEST
– PHONE NUMBER 1
Scroll through the menu until Voice Dialler Test:
Phone No.1’ is displayed on the LCD.
Press to activate the Voice Dialler to call phone number 1.
1. If the Voice Dialler is disabled the panel will
beep and the LCD will display the following for 5s:
2. If phone number 1 is not programmed the
panel will beep and the LCD will display the following for 5s:
3. If phone number 1 is programmed the voice
dialler will be activated and phone number 1 will be called. During the test the LCD will display:
When the call is answered the recorded main alarm message only will be repeatedly replayed for a minimum of 60s after which time the current replay cycle will be completed and the test will end.
The recipient of the call may acknowledge the call and stop the test by pressing the
button on the telephone keypad.
If this occurs the panel will beep and display the following for 5s:
To stop the test early at the panel press .
VOICE DIALLER TEST
– PHONE NUMBER 2
Scroll through the menu until Voice Dialler Test:
Phone No.2’ is displayed on the LCD.
Press to activate the Voice Dialler to call phone number 2 following the same procedure as described above for phone number 1 with the LCD displays modified to show phone number 2.
VOICE DIALLER TEST
– PHONE NUMBER 3
Scroll through the menu until Voice Dialler Test:
Phone No.3’ is displayed on the LCD.
Press to activate the Voice Dialler to call phone number 3 following the same procedure as described above for phone number 1 with the LCD displays modified to show phone number 3.
VOICE DIALLER TEST
– PHONE NUMBER 4
Scroll through the menu until Voice Dialler Test:
Phone No.4’ is displayed on the LCD.
Press to activate the Voice Dialler to call phone number 4 following the same procedure as described above for phone number 1 with the LCD displays modified to show phone number 4.
ENTER
ENTER
ENTER
Call
Acknowledged
ESC
ENTER
Remote Manager
Test....FAIL
ESC
Voice Dialler
Disabled
Phone Number 1:
Not Entered
Test Phone Number 1:
Stop->ESC
ENTER
Page 31
31
FACTORY SETTINGS
USER CODE SETUP
Master User: 1234
Users 1-6: Not programmed Duress Code: Not programmed
SYSTEM SETUP MENU
Alarm Duration: 3 minutes
Entry/Exit Delay period: 30s Entry Delay Beeps: On Exit Delay Beeps: On Wireless Siren: On Wired Siren: Off Auxiliary Relay: Off Jamming Detection: Off Zone Lockout: On Time: 12:00 Date: 01/01/07 Dial Mode: Off Remote Phone Access: Off Rings To Answer Phone: 6
REMOTE MANAGER SETUP
Phone Numbers 1 and 2: Not programmed
System ID Code: Not programmed
VOICE DIALLER SETUP MENU
Phone Numbers 1-4: Not programmed
Messages: Not programmed
ZONE SETUP MENU
Zone defaults set according to detector type
identified during learning process:
PIR/MAG Detectors
Zone Name: No name
Zone Type: Intruder Zone Mode: Zones 1-2: Delayed
Zones 3-36: Instant
Part-Arm 1: Zones 1-4: On
Zones 5-36: Off Part-Arm 2: Off Chime: Off
Smoke Detectors
Zone Name: No name
Zone Type: Fire Zone Mode: Instant Part-Arm 1: Off Part-Arm 2: Off Chime: Off
FACTORY SETTINGS
LATCH KEY SETUP
Status: OFF
Selected User Setup: OFF (all users) Phone Numbers: Not programmed
ANSWER PHONE SETUP
Status: OFF
User status: All Off User ID messages: Not recorded Phone Numbers: Not programmed
SPECTRA LIGHTING SETUP
Set Light-On Period: 3 Minutes
Spectra Mode: OFF Stop Time: 06:00 Start Time: 18:00
RESET FACTORY SETTINGS
1. Press
This puts the system into Test Mode.
2. Undo the Control Panel cover fixing screws and
open the cover.
3. Remove the DC power jack, then remove and
disconnect one of the back-up batteries.
4. Set jumper link P1 to the ON position.
5. Reconnect the power supply jack.
6. The Control Panel will now reset itself with all
factory settings.
‘EEPROM RESET’ will be displayed while the
factory settings are restored to memory. Once the memory reset has been completed ‘DISARM READY’ will be displayed.
7. Reconnect and replace the back-up battery.
8. Reset jumper link P1 into the OFF position.
9. Close the Control Panel cover and refit the fixing
screws.
????
ENTER
, ,
User Access Code
OFF ON
Jumper Link
Page 32
32
With the system in Standby (i.e. with the display showing ‘DISARM READY’).
Press
Note: To get to Standby Mode simply press
repeatedly until only the POWER LED is illuminated.
The system is now in Program Mode.
NAVIGATING THROUGH THE PROGRAMMING MODE MENUS
(Read carefully before you start).
The programmable system parameters are
arranged by group in a series of menus within programming mode.
Each menu (and sub-menu) will contain all programmable system parameters related to the particular function.
Note: Some basic system parameters will be
contained within the system menu because they relate to a number of different functions.
At each menu level use the and buttons to scroll through the available options.
Note: A menu item displayed in full capitals
(e.g. ‘USER SETUP’) indicates that there is another menu below that option. An option displayed in lower case (e.g. ‘1.0 Master User
Access Code’) indicates that this is a parameter
setting and no menu below, (although there may be setting options).
Press to:
a) select the displayed menu, or b) change the displayed parameter setting, or c) save the changed parameter setting and
revert to the previous level.
Press to:
a) exit to the previous menu level, or b) revert to the previous level without saving a
changed parameter setting.
Note: After programming all required functions,
press to leave Programming mode and return to Standby.
USER SETUP MENU
Master User Access Code
User 1 Access Code User 2 Access Code User 3 Access Code User 4 Access Code User 5 Access Code User 6 Access Code Duress Access Code
SYSTEM SETUP MENU
Alarm Duration
Entry/Exit Delay period Entry Delay Beeps Exit Delay Beeps Wireless Siren Wired Siren Auxiliary Relay Jamming Detection Zone Lockout Time Date Dial Mode Remote Phone Access Control Rings To Answer Phone
ZONE SETUP MENU
Learn Detector Code
Zone Name Zone Type Zone Mode Part-Arm 1 Part-Arm 2 Chime
LATCH KEY SETUP MENU
Status
User status Record User ID messages Replay User ID messages Phone Numbers
REMOTE MANAGER SETUP MENU
Phone Numbers
System ID Code
PROGRAMMING INSTRUCTIONS
????
ENTER
, ,
Master User Access Code
ESC
ESC
ESC
ENTER
Page 33
33
VOICE DIALLER SETUP MENU
Phone Numbers
Record Alarm Messages Replay Alarm Messages
SPECTRA LIGHTING SETUP
Set Light-On Period
Spectra Mode Stop Time Start Time
TELEPHONE APPLICATION SETUP
If using any of the telephone based functions,
(e.g. Answer Phone, Voice Dialler, Remote Phone Access and Control etc.) the Dial Method must be set as follows:
Remote Manager
1) set Dialler Mode = “Remote
Manager”
2) set Remote Manager Phone Numbers
3) set System ID Code
Voice Dialler
1) set Dialler Mode = “Voice Dialler”
2) set Voice Dialler Phone Numbers
3) set Dial Sequence
4) record Alarm Messages
Answer Phone
1) set Rings to Answer Phone
Latch Key
1) set Latch Key Status =
“ON” or “OFF”
2) enable users if “ON” chosen
3) set Latch Key Phone Numbers
4) record User ID Message(s)
USER SETUP
This menu allows the 4 digit User Access Codes
to be configured for each user. The general users (1- 6) may also record a 4 second message to be used with the Latch Key feature in the Latch Key Setup menu.
Scroll through the top level programming menu until
‘1. USER SETUP’ is displayed and press .
Note: After configuring all required users, press
to return to the top level of programming menu.
MASTER USER
Default setting: 1234
Scroll through the menu until ‘1.0 Master User
Code:’ and the current access code is displayed.
To change the access code press .
Enter the new 4 digit User Access Code which will be displayed on the LCD.
Press to save new setting and exit, or
Press to exit without saving.
Note: User must enter a 4 digit code, 1,2 or 3
digit codes are not acceptable.
USERS 1-6 and DURESS CODES:
To change User 1 access code, select ‘1.1 User 1 Code’ from the menu and follow the procedure above.
To c hange User 2 access code, select ‘1.2 User 2 Code’
from the menu and follow the procedure above.
To c hange User 3 access code, select ‘1.3 User 3 Code’
from the menu and follow the procedure above.
To c hange User 4 access code, select ‘1.4 User 4 Code’
from the menu and follow the procedure above.
To c hange User 5 access code, select ‘1.5 User 5 Code’
from the menu and follow the procedure above.
To c hange User 6 access code, select ‘1.6 User 6 Code’
from the menu and follow the procedure above.
To c hange the Duress access code, select ‘1.7 U Duress
Code’
from the menu and follow the procedure above.
Page 45
see SYSTEM
SETUP menu
see REMOTE MANAGER SETUP menu
Page 42
see SYSTEM
SETUP menu
see VOICE DIALLER SETUP menu
Page 38
see SYSTEM
SETUP menu
Page 44
see
LATCH KEY SETUP menu
ENTER
ENTER
Enter new code xxxx
Enter new code xxxx
Enter new code xxxx
enter 4 digit code
press ENTER
enter 4 digit code
press ENTER
enter 4 digit code
press ENTER
1.0 Master User Code: xxxx
1.7 Duress Code: xxxx
1. USER SETUP
press ENTER
1.1 User 1 Code: xxxx
Similar for Users 2-6
press ENTER press ENTER press ENTER
ESC
ENTER
ESC
Page 34
34
System Setup Diagram
Enter (10-250s)
enter time
press ENTER
2.3 Entry/Exit
Delay: xxxs
press ENTER
Send Disarm
Waiting 30s...
display for 3s
enter time
press ENTER
2.5 Exit Delay
Beeps: xxx
press ENTER
Select
ON->1 OFF->3
2.6 Wirefree
Siren: xxx
press ENTER
Select
ON->1 OFF->3
OFF2s30s
60s
180s
300s
ON until Disarm
2.8 Aux Relay
xxxxxxxxxxxxxx
press ENTER
Select
ON->1 OFF->3
2.7 Wired Siren
xxx
press ENTER
DD/MM/YY
2.10 Zn Lockout
xxx
press ENTER
Select
ON->1 OFF->3
2.9 RF Jamming
Detection: xxx
press ENTER
select menu item
press ENTER
enter date
press ENTER
OFF
Voice Dialler
Remote Manager
Select
ON->1 OFF->3
enter time
press ENTER
PROGRAM MODE
Code:
enter Master User Access Code and press ENTER
2.4 Entry Delay
Beeps: xxx
press ENTER
2. SYSTEM SETUP
press ENTER
2.1 Remotes = x
Edit->Enter
Enter 1-60(x10)s
enter time
press ENTER
2.2 Alarm Time
xxxs
press ENTER
2.1 Remotes = x
1->Del Learn->3
Confirm Delete
YES->1 3->NO
press 1 to delete press 3 to learn device
New Device
xxxxxx
Send PartArm
Waiting 15s...
Remotes/Keypads
Deleted
press 1 to confirm delete
press 3 to cancel
15s time-out or auto cancel
Device Confirmed
xxxxxx
display for 3s
Saving
New Device
display for 3s
display for 3s
HH:MM
enter time
press ENTER
2.11 Time
HH:MM
press ENTER
DD/MM/YY
enter date
press ENTER
2.12 Date
DD/MM/YY
press ENTER
select menu item
press ENTER
2.13 Dialler Mode
xxxxxxxxxxxxxx
press ENTER
Select
ON->1 OFF->3
2.14 Phone
Control: xxx
press ENTER
2.15 Rings to
Answer Phone: xx
press ENTER
Enter 1-9:
enter no of rings
press ENTER
Page 35
35
SYSTEM SETUP
The parameters in this menu allow the configuration of
general system parameters, such as Alarm Duration and control of any hardwired or output relay alarm contacts. This section also contains the basic setup information for the systems telephone dialler interface which must be configured appropriately if any of the telephone based functionality is to be used.
Refer to System Setup diagram on page 34.
Scroll through the top level programming menu until ‘2. SYSTEM SETUP’ is displayed and press .
Note: After completing the system setup press
to return to the top level programming menu.
Scroll through the menu until ‘2. SYSTEM SETUP’ is displayed on the LCD and press .
After configuring the system parameters press to return to the top level programming menu.
LEARN REMOTE CONTROLS
AND KEYPADS
Allows up to 6 Remote Controls or Remote keypads to
be linked to the system and their ID codes learnt into memory.
Scroll through the Zone menu until option ‘2.1 Remotes’
is displayed. The number of Remote Controls/ Keypads
already linked will be shown, (e.g. if there are two Remotes Controls and one Remote Keypad linked the display will show ‘2.1 Remotes = 3’).
Linking a Remote Control or Remote Keypad to
the Control Panel:
Note: If there are already 6 Remote
Controls/ Keypads linked to the Control Panel then it will not be possible to link any more. Attempting to learn a 7th device will cause the panel to produce a single long beep and display
‘Cannot Learn - System Full’ message on
screen for 3s.
To learn a new Remote or Keypad ID code and link it to the selected zone press .
The panel will now listen for a valid signal from a new Remote Control or Keypad.
The Panel will remain in Learn Mode for
30s. If a valid signal is not received from a new device within 30s it will automatically exit Learn Mode and return to the top of level 2.0.
Send DISARM from the new Remote Control or
Remote Keypad as follows…
Press on the Remote Control, or
Press
on the Remote Keypad.
If the device is new and not already linked to the system the control panel will produce two short beeps and the display will show ‘New Device’ and the type or the detected device; (e.g. Remote or Keypad).
ENTER
ESC
ENTER
ESC
3
x = No of remotes/keypads linked
2.1 Remotes = x Edit->Enter
2.1 Remotes = x 1->Del Learn->3
1 = Delete or
3 = Learn
Confirm Delete
YES->1 3->NO
6
devices already
linked?
Delete confirmed
within 15s?
Send Disarm
waiting 30s...
Device Deleted
Wait...
1 = Delete
press 1 to confirm delete press 3 to cancel 15s time-out or auto cancel
display for 3s
YES
NO
Send Disarm
waiting 30s...
NO
Signal
received within 30s
from Remote/Keypad not
yet linked?
YES
New Device
xxxxxx
Send Part-Arm
waiting 15s...
NO
Remote/Keypad
code confirmed within
15s?
Device Confirmed
xxxxxx
Saving
New Device
display for 3s
display for 3s
YES
display for 3s
3 = Learn
NO
,
Keypad User Access Code
? ? ? ?
Note: If the device is already linked
to the control panel then the panel will produce a single long beep and the received signal from the device will be ignored.
Page 36
36
Confirm the new device ID code by sending the Disarm signal from the same new Remote Control or Remote Keypad within 15s as follows…
Press on the Remote Control, or
Press
on the Remote Keypad.
The panel will produce three short beeps and the LCD will show ‘Device Confirmed’.
The LCD will then show ‘Saving New Device’
while the ID code of the new detector is
stored into memory.
Deleting Linked Devices:
Scroll through the Zone menu until option ‘2.1
Remotes’ is displayed. The number of Remote
Controls/Keypads already linked will be shown, (e.g. if there are two Remotes Controls and one Remote Keypad linked the display will show
‘2.1 Remotes = 3’).
To delete all linked Remote Controls and Remote Keypads press .
Press again within 15s to confirm and actually delete all devices.
The display will now show ‘2.1 Remotes = 0’.
ALARM DURATION
Controls the alarm duration of the wireless, internal
control panel and wired sirens in the event of an alarm, subject to the On / Off status of the wireless and hard wired sirens which can be independently controlled and disabled.
Scroll through the system menu until ‘2.2 Alarm
Time’ (and the current setting) is displayed.
Siren Duration
Default setting: 180 seconds
To change the setting press .
Enter the required Alarm Duration in units of 10 seconds (0 - 60).
e.g. enter 6 for a 60 seconds alarm duration.
minimum setting = 0. (i.e. 0 seconds / no
alarm).
maximum setting = 60 . (i.e. 600 seconds
or 10 minutes).
Press to save new setting and exit, or
Press to exit without saving.
Note: Following an alarm, the Siren will continue
to sound until either the system is Disarmed; or the Alarm Duration time expires. If the ‘3 minute
alarm time limit’ of the Siren is enabled, then the
Siren will shut down after 3 minutes even if the Control Panel siren is still sounding.
ENTRY/EXIT DELAY PERIOD
This sets the time entry and exit delay time period for
the system. The exit delay is the period between arming the alarm and any detectors being allowed to initiate an alarm (either instant or delayed). On entering the property it sets the period between triggering a detector configured as “delayed” and the alarm occurring.
Default setting: 30 seconds
Scroll through the system menu until ‘2.3 Entry/Exit
Delay’ (and the current setting) is displayed.
Note: If the confirmation signal is not
received within 15s the control panel will produce a single long beep and exit the learning process. The learning process will need to started again to learn the new device into memory.
Note: If delete all is not confirmed within
15s then the action will be cancelled and the Remote Controls/Keypads will not be deleted and the display will revert to its original setting.
,
Keypad User Access Code
? ? ? ?
1
1
1
ENTER
ENTER
ESC
Page 37
37
To change the setting press .
Enter the required delay period (10 - 240s).
Press to save new setting and exit, or
Press to exit without saving.
ENTRY DELAY BEEPS
Allows the systems Entry-Delay warning beeps when
arming the system to be switched ON or OFF.
Scroll through the system menu until ‘2.4 Entry
Delay Beeps’ (and the current setting) is displayed.
To change the setting press .
Press to enable the entry delay beeps, or
Press to disable the entry delay beeps.
EXIT DELAY BEEPS
Allows the systems Entry-Delay warning beeps when
arming the system to be switched ON or OFF. .
Scroll through the system menu until ‘2.5 Exit Delay
Beeps’ (and the current setting) is displayed.
To change the setting press .
Press to enable the exit delay beeps, or
Press to disable the exit delay beeps.
WIRELESS SIREN
Allows the wireless siren to be enabled or disabled.
If disabled it will not sound in the event of any alarm.
Default setting: ON
Scroll through the system menu until ‘2.6 Wirefree
Siren’ (and the current setting) is displayed.
To change the setting press .
Press to enable the wireless siren, or
Press to disable the wireless siren.
WIRED SIREN
Allows the hard wired siren to be enabled or disabled.
If disabled it will not sound in the event of any alarm. (This does not affect the control panels internal siren
which cannot be de-activated unless the alarm duration is set to 0).
Scroll through the system menu until ‘2.7 Wired
Siren’ (and the current setting) is displayed.
To change the setting press .
Press to enable the wired siren, or
Press to disable the wired siren.
AUXILIARY RELAY
Controls the operation of the auxiliary relay in the
event of an alarm occurring.
Scroll through the system menu until ‘2.8 Aux Relay’
(and the current setting) is displayed.
To change the setting press .
Scroll through the menu options, until the required setting is displayed.
Options: OFF / 2s / 30s / 60s / 180s / 300s /
On-until-disarm
Press to save the new setting, or
Press to exit without saving.
JAMMING DETECTION
This controls the systems anti-jamming detection
facility. It is recommended that the jamming
detection is not activated for at least the first 30 days to allow time for you to become familiar with the operation of your systems first.
Allows the control panels internal jamming detection
feature to be enabled or disabled. (The jamming detection in the wireless siren cannot be enabled with SK5 Platinum systems).
Default setting: OFF
Scroll through the system menu until ‘2.9 RF Jamming
Detection(and the current setting) is displayed.
To change the setting press .
Press to enable jamming detection, or
Press to disable jamming detection.
ENTER
ENTER
ENTER
ESC
1
3
ENTER
1
3
ENTER
ENTER
ESC
ENTER
1
3
ENTER
1
3
ENTER
1
3
Page 38
38
ZONE LOCKOUT
Prevents a single zone from triggering an alarm
more than 3 times before the system is disarmed. (Zone lockout is effective on all zones except 24-HOUR-INTRUDER and FIRE zones which cannot be locked out).
Default setting: ON
Scroll through the system menu until ‘2.10 Zn
Lockout’ (and the current setting) is displayed.
To change the setting press .
Press to enable zone lockout, or
Press to disable zone lockout.
TIME & DATE SETUP
These parameters allow the systems clock and
calendar (required for the Event Log) to be configured.
Note: The clock will require updating to reflect any
time changes due spring/ autumn daylight saving.
DATE
To change the system date scroll through the menu
until ‘2.12 Date’ (and current setting) is displayed and press .
Press to save new setting and exit, or
Press to exit without saving.
TIME
To change the system date scroll through the menu
until ‘2.11 Time’ (and current setting) is displayed and press .
Enter the new time in the format “hh:mm” using the 24 hour clock format.
Press to save new setting and exit, or
Press to exit without saving.
REMOTE PHONE ACCESS AND CONTROL
If enabled, this allows the system to be remotely
controlled via the telephone.
Default setting: OFF
Scroll through the system menu until ‘2.14 Remote
Phone Control’ (and the current setting) is displayed.
To change the setting press .
Press to enable remote phone control, or
Press to disable remote phone control.
DIALLER OPERATING MODE
Controls whether the telephone dialler is activated
and whether it operates with the Remote Manager or Voice Dialler features.
Scroll through the system menu until ‘2.13 Dialler
Mode’ (and the current setting) is displayed.
To change the setting press .
Scroll through the menu options, until the required setting is displayed.
Options: OFF / Voice Dialler / Remote Manager
Press to save the new setting, or
Press to exit without saving.
RINGS TO ANSWER PHONE
This sets the number of rings which occur before the
Control Panel will “pick up” an incoming call to operate with the Remote Phone Access and Control feature.
Default setting: 6
Scroll through the system menu until ‘2.15 Rings To
Answer Phone’ (and the current setting) is displayed.
To change the setting press .
Enter the required number of rings (options 1-9).
Press to save the new setting, or
Press to exit without saving.
ENTER
ENTER
ENTER
1
3
1
3
ENTER
ESC
ENTER
ESC
ENTER
ENTER
ENTER
ENTER
ESC
ENTER
ESC
Page 39
39
Send Code
Waiting 30s...
display for 3s
3.1 Znn
Wire Zone
press ENTER
No name
Front door
Back door
Side Door
Patio door
Dining room
Living room
Lounge
Study
Play Room
Kitchen
Utility Room
Hall
Landing
Bedroom 1
Bedroom 2
Bedroom 3
Bedroom 4
Bedroom 5
Shed
Garage
PIR
MAG
SMOKE 1
SMOKE 2
SMOKE 3
3.2 Znn Name xxxxxxxxxxxxxx
press ENTER
3.3 Znn Type xxxxxxxxxxxxxx
press ENTER
select menu item
press ENTER
Menus 3.2 - 3.7 repeated
Intruder
24 hour Intruder
Fire
Test
select menu item
press ENTER
Instant
Delayed
select menu item
press ENTER
PROGRAM MODE Code:
enter Master User Access Code and press ENTER
Enter Zone(1-36)
nn
press ENTER
Following structure is repeated for each zone
3.1 Znn: xxxxx Edit->Enter
3.1 Znn: xxxxx 1->Del Learn->3
Confirm Delete YES->1 3->NO
press 1 to delete press 3 to learn device
New Device
xxxxx
Resend Code
Waiting 15s...
Device Code
Deleted
press 1 to confirm delete
press 3 to cancel
15s time-out or auto cancel
Device Confirmed
xxxxx
display for 3s
Saving
New Device
display for 3s
display for 3s
3.4 Znn Mode xxxxxxx
press ENTER
Select
ON->1 OFF->3
enter date
press ENTER
3.5 Znn Part-Arm 1: xxx
press ENTER
3.6 Znn Part-Arm 2: xxx
press ENTER
Select
ON->1 OFF->3
3.7 Znn Chime xxx
press ENTER
only for wirefree zones 1-32
empty PIR MAG Smoke
only for wired zones 33-36
Select
ON->1 OFF->3
3. ZONE SETUP
press ENTER
The parameters in this menu allow each zones specific function to be configured.
Scroll through the programming menu until
‘3. ZONE
SETUP’ is displayed and press .
Enter the zone number to be configured (1 - 36) and press .
The following configuration options are based upon setting zone 1. Options for all other zones (2-10) are identical except the zone number reference will change according to the zone being configured.
Zones 33-36, the wired zones are the same except there is no learn menu option as these are wired.
Note: After completing the Zone Setup press to
return to the top level programming menu.
ZONE SETUP
ENTER
ESC
ESC
Page 40
40
LEARN DETECTOR CODE
(zones 1-32 only).
Allows a wireless detectors ID code to be learnt and
linked to the selected wireless zone.
Linking a New Detector to the Zone:
Note: There can only be one detector on each
zone so if a detector is already linked then linking a new detector will replace the existing one.
To learn a new detector ID code and link it to the selected zone press .
The panel will now listen for a valid signal from a new detector to link to the zone.
The Panel will remain in Learn Mode for
30s. If a valid signal is not received from a new detector within 30s it will automatically exit Learn Mode and return to the top of level 3.1.
Activate the Tamper Switch on the PIR/MAG
detector or trigger a smoke detector via its test button.
If the detector is new and not already linked on any security zone the panel will produce two short beeps and the display will show
‘New Device’ and the type or the detected
device; (e.g. PIR, MAG or Smoke).
Confirm the new device ID code by activating the Tamper Switch on the same new PIR/MAG detector or triggering the same smoke detector with its test button within 15s.
The panel will produce three short beeps and the LCD will show ‘Device Confirmed’.
The LCD will then show ‘Saving New Device’ while the ID code of the new detector is stored into memory.
Deleting an Existing Device:
If a detector is already linked then the display
will show the detector type, for example:
‘3.1 Zxx: PIR’. The detector can be removed
from the system and its ID code erased from memory without replacing it as follows:
To delete the current detector from the zone press .
Press again within 15s to confirm and actually delete the device.
The display will now show ‘3.1 Zxx: empty’.
xxxxx = PIR, MAG or Smoke, empty
3.1 Znn: xxxxx Edit->Enter
3.1 Znn: xxxxx 1->Del Learn->3
1 = Delete or
3 = Learn
Confirm Delete
YES->1 3->NO
Delete confirmed
within 15s?
Device Deleted
Wait...
1 = Delete
press 1 to confirm delete press 3 to cancel 15s time-out or auto cancel
display for 3s
YES
NO
Send Code
waiting 30s...
NO
Signal
received within 30s
from detector not
yet linked to
any zone?
New Device
xxxxx
Resend Code
waiting 15s...
NO
Detector code
confirmed within
15s?
Device Confirmed
xxxxx
Saving
New Device
display for 3s
display for 3s
YES
display for 3s
Note: If the detector is already linked
to the control panel on any other zone then the panel will produce a single long beep and the received signal from the detector will be ignored.
Note: If the confirmation signal is not
received within 15s the control panel will produce a single long beep and exit the learning process. The learning process will need to be started again to learn the new device into memory.
Note:
If delete all is not confirmed within
15s then the action will be cancelled and the device will not be deleted and the display will revert to level 3.1 as before.
3
1
1
Page 41
41
NAME
This enables a name to be allocated to the zone so it
can be identified by its location.
Available for all zones 1- 36. Only available for wireless zones 1-32 if a detector is linked.
Default setting: No Name
Scroll through the Zone menu until ‘3.2 Zxx Name’ (and the current setting) is displayed.
To change the setting press .
Scroll through the menu options, until the required setting is displayed.
Options: No name, Front Door, Back Door,
Side Door, Patio Door, Dining Room, Living Room, Lounge, Study, Play Room, Kitchen, Utility Room, Hall, Landing, Bedroom 1, Bedroom 2, Bedroom 3, Bedroom 4, Bedroom 5, Shed, Garage, PIR, MAG or SMOKE.
Press to save the new setting, or
Press to exit without saving.
TYPE
Each zone may be programmed to operate in 1 of 4
different modes dependant upon the type of alarm function required. The following types are available:
Intruder - provides standard intruder monitoring.
24 Hour Intruder - used to provide 24 hour
monitoring of areas requiring continuous security protection even while the system is Disarmed, (e.g. gun lockers). Activation of any detector on a security zone will immediately initiate an Alarm.
Fire - used to provide 24 hour monitoring of any
Fire/ Smoke detectors fitted to the system. Activation of any detector will immediately initiate an Alarm.
Test - when the system is armed, any detector on
the zone will generate an entry in the Event Log without initiating an alarm.
Default setting: Intruder
Scroll through the Zone menu until ‘3.3 Zxx Type’ (and the current setting) is displayed.
To change the setting press .
Scroll through the menu options, until the required setting is displayed.
Press to save new setting and exit, or
Press to exit without saving.
ZONE MODE
Each zone may be selected to operate with or
without a entry/exit delay period (see System Setup menu). This is selected in zone mode.
Default setting: Zones 1- 2: Delayed
Zones 3- 36: Instant
Available for all zones 1- 36. Only available for
wireless zones 1-32 if a detector is linked
Scroll through the Zone menu until ‘3.4 Zxx Mode’ (and the current setting) is displayed.
To change the setting press .
Scroll through the menu options, until the required setting is displayed.
Options: Instant / Delayed
Notes: Smoke detectors can only be
set as Instant
Press to save new setting, or
Press to exit without saving.
PART-ARM 1
This controls whether the zone is active when
Part-Arm 1 is armed.
Default setting: Zones 1- 4: ON
Zones 5-36: OFF
Scroll through the Zone menu until ‘3.5 Zxx Part-Arm 1’ (and the current setting) is displayed.
To change the setting press .
Press to enable the zone in part arm 1, or
Press to disable the zone in part arm 1.
ENTER
ESC
ENTER
ESC
ENTER
ESC
ENTER
ENTER
ENTER
1
3
ENTER
Page 42
42
PART-ARM 2
This controls whether the zone is active when
Part-Arm 2 is armed.
Default setting: OFF (all zones)
Scroll through the Zone menu until ‘3.6 Zxx Part-Arm 2’ (and the current setting) is displayed.
To change the setting press .
Press to enable the zone in part arm 2, or
Press to disable the zone in part arm 2.
CHIME
This controls whether the zone will operate with
Chime Mode.
Default setting: OFF
Available for all zones 1- 36 only if detector is a
PIR/ MAG. Only available for wireless zones 1-32 if a detector is linked. Smoke detectors automatically disabled in Chime Mode.
Scroll through the Zone menu until ‘3.7 Zxx Chime’
(and the current setting) is displayed.
To change the setting press .
Press to enable the zone in chime mode, or
Press to disable the zone in chime mode..
MONITORING SETUP
REMOTE MANAGER
The parameters in this menu configure the system
telephone dialler to interface to the Alarm Monitoring Service following the occurrence of an appropriate alarm or system event.
Scroll through the menu until ‘6. REMOTE
MANAGER SETUP’ is displayed and press .
Note: After completing the Remote Manager Setup
press to return to the top level programming menu.
PHONE NUMBER 1
Scroll through the menu until ‘6.1 Phone No.1:’ is
displayed and press .
Enter phone number 1 (see the Monitoring welcome leaflet enclosed).
Press to save new setting and exit, or
Press to exit without saving.
PHONE NUMBER 2
To setup Remote Manager phone number 2 select ‘6.2 Phone No.2:’ from the menu and follow the
procedure above.
UNIT ID CODE
Scroll through the menu until ‘6.3 Unit ID:’ is displayed
and press .
Enter the 4 digit System ID Code obtained from the Alarm Monitoring Service provider (see the Monitoring welcome leaflet enclosed).
This is not to be confused with the System Access Code or any User Access Codes.
1
3
ENTER
1
3
ENTER
ESC
ENTER
Note: For the telephone dialler to operate
correctly with the Alarm Monitoring Service the ‘Dialler Mode’ (see System Setup) must be correctly set and programmed.
PROGRAM MODE Code:
enter Master User Access Code and press ENTER
6. REMOTE MANAGER
press ENTER
Enter Phone No: Enter Unit ID:Enter Phone No:
(32 digits max) (32 digits max) (4 digits max)
6.1 Phone No.1 xxxxxxxxxxxxxx
6.3 Unit ID: xxxx
6.2 Phone No.2 xxxxxxxxxxxxxx
press ENTER press ENTER press ENTER
ENTER
Notes:
Press to insert a 3.5 seconds pause in
the dialling sequence.
Press to move the cursor left.
Press to move the cursor right.
Press to delete the number under the cursor.
Press (and hold) to erase the entire number.
ENTER
ESC
ENTER
Page 43
43
Press to save new setting and exit, or
Press to exit without saving.
VOICE DIALLER
The parameters in this menu allow the setting of
the systems Voice Dialler. It allows up to 4 phone numbers to be entered and called in sequence. The alarm voice messages are also recorded here.
Refer to Voice Dialler Setup diagram on page 44.
Scroll through the programming menu until ‘5. VOICE
DIALER SETUP’ is displayed and press .
Note: After completing the Voice Dialler Setup press
to return to the top level programming menu.
PHONE NUMBERS
Scroll through the menu until ‘5-1 PHONE NUMBERS’ is displayed and press .
Scroll through the menu until the required ‘Phone
No._’ (and the current setting) is displayed.
To change the setting press .
Enter the new phone number (32 digits max.)
Press to save and exit, or
Press to exit without saving.
After programming all required phone numbers press
to return to the top level Voice Dialler menu.
RECORD ALARM MESSAGES
Scroll through the menu until ‘5.2 RECORD ALARM
MESSAGES’ is displayed and press .
Scroll through the available menu options until the required message to be recorded is displayed.
a) Main message (12 seconds max.). b) Intruder Alarm message (5 seconds max.). c) Fire Alarm message (5 seconds max.). d) Panic/PA Alarm message (5 seconds max.). e) Duress alarm message (5 seconds max.).
To change the setting press .
Press to start the voice recorder.
Press to exit without saving
Press to return to the top level Voice Dialler Setup menu.
REPLAY ALARM MESSAGES
Scroll through the menu until ‘5.2 RECORD ALARM
MESSAGES’ is displayed and press .
Scroll through the menu options until the required message is displayed and press to replay the message.
Press to return to the top level Voice Dialler menu.
ENTER
ESC
ENTER
ENTER
ENTER
ENTER
Notes:
Press to insert a 3.5 seconds pause in
the dialling sequence.
Press to move the cursor left.
ENTER
ESC
ESC
1
After recording, press to stop the recorder and cancel any remaining recording time. The new message will then be replayed.
ESC
3
ESC
ESC
ENTER
ENTER
Note: For the Voice Dialler to operate correctly
the ‘Dialler Mode’ (see system setup) must be correctly set and programmed.
Ensure all Alarm Messages are recorded (see Record Alarm Messages, right).
Notes:
To enter code B, press ,
To enter code C, press ,
To enter code D, press ,
To enter code E, press ,
To enter code F, press ,
1
2
3
4
5
ENTER
ESC
Press to move the cursor right.
Press to delete the number under the cursor.
Press (and hold) to erase the entire number.
Page 44
44
Voice Dialler Setup Diagram
While recording the
LCD should show...
5.2.3 Fire
Alarm Message
press ENTER
Playing
5.3.2 Intruder
Alarm Message
press ENTER
Select
YES->1 NO->3
Playing
Playing
5.3.1 Main
Alarm Message
press ENTER
Playing
5.3.3 Fire
Alarm Message
press ENTER
Playing
5.3.4 Panic/PA
Alarm Message
press ENTER
Playing
5.3.5 Duress
Alarm Message
press ENTER
Enter Phone No:
enter Tel No (32)...
press ENTER
5.1.2 Phone No.2
xxxxxxxxxxxxxx
press ENTER
Enter Phone No:
enter Tel No (32)...
press ENTER
5.1.4 Phone No.4
xxxxxxxxxxxxxx
press ENTER
Enter Phone No:
enter Tel No (32)...
press ENTER
5.1.3 Phone No.3
xxxxxxxxxxxxxx
press ENTER
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
PROGRAM MODE
Code:
enter Master User Access Code and press ENTER
5. VOICE DIALLER
SETUP
press ENTER
Enter Phone No:
enter Tel No (32)...
press ENTER
5.1.1 Phone No.1
xxxxxxxxxxxxxx
press ENTER
5.2 RECORD ALARM
MESSAGES
press ENTER
5.3 REPLAY ALARM
MESSAGES
press ENTER
While recording the
LCD should show...
5.2.2 Intruder
Alarm Message
press ENTER
Select
YES->1 NO->3
Playing
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
While recording the
LCD should show...
5.2.1 Main
Alarm Message
press ENTER
Select
YES->1 NO->3
Playing
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
While recording the
LCD should show...
5.2.4 MPaniv/PA
Alarm Message
press ENTER
Select
YES->1 NO->3
Playing
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
While recording the
LCD should show...
5.2.5 Duress
Alarm Message
press ENTER
Select
YES->1 NO->3
Playing
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
5.1 PHONE
NUMBERS
press ENTER
Page 45
45
LATCH KEY SETUP
The parameters in this menu configures which
users the Latch Key feature operates with and the telephone numbers that the system dials when the Latch Key is activated.
Note: To allow the Latch Key to operate before the
system is disarmed, the User Access Code must be programmed (see page 33).
Scroll through the top level programming menu until
‘4. LATCH KEY SETUP’ is displayed and press .
Note: After completing the Latch Key Setup press
to return to the top level programming menu.
STATUS
This controls which users the Latch Key facility will
operate with.
Default setting: OFF
Scroll through the Zone menu until ‘4.0 Status’ (and the
current setting) is displayed.
To change the setting press .
Press to enable Latch Key, or
Press to disable Latch Key.
LATCH KEY USER SETUP
This configures the individual users that the Latch
Key operates with when set to ‘Selected-Users’.
Default setting: OFF
Scroll through the menu until the required user number
is displayed (e.g. ‘4.1 User 1 Setup’) and press
.
ESC
ENTER
Note: For Latch Key to operate correctly, the
User Access Code, Latch Key Status, User Status, Latch Key Message and Phone number must be correctly set and programmed.
1
3
ENTER
4.1 User 1 Setup xxx
press ENTER
Enter Phone No.1
4.7 Phone No.1 xxxxxxxxxxxxxx
press ENTER
Enter Phone No.2
4.8 Phone No.1 xxxxxxxxxxxxxx
press ENTER
PROGRAM MODE Code:
enter Master User Access Code and press ENTER
4. LATCH KEY SETUP
press ENTER
Select
ON->1 OFF->3
4.0 Status xxx
press ENTER
During replay the LCD
should show...
4.1.2 Record User 1 Msg
press ENTER
Select
YES->1 NO->3
Playing
Recording
Stop->ESC
press 1
The recording will
then be replayed.
During replay the LCD
should show...
4.1.1 User 1 Status: xxx
press ENTER
Select
YES->1 NO->3
4.1.3 Replay User 1 Msg
press ENTER
Playing
While recording the
LCD should show...
Users 2 to 6
Structure similar to User 1
enter Tel No(32)
press ENTER
enter Tel No(32)
press ENTER
ENTER
Page 46
46
After configuring required users press to return to the top level Latch Key menu.
User Status
Scroll through the system menu until ‘User x
Status’ (and the current setting) is displayed.
To change the setting press .
Press to enable user x with Latch Key, or
Press to disable user x with Latch Key.
After configuring all users as required press to return to the top level Latch Key Setup menu.
RECORDING USER ID MESSAGES
Scroll through the menu until ‘Record User x Msg’ is
displayed and
press .
To record the selected alarm message press .
Press to exit without saving.
Press to start the voice recorder and record a new message.
To stop recording before the maximum message length has expired press . This ends the recording and cancels any remaining recording time.
After recording the new message will
automatically be replayed.
REPLAYING USER ID MESSAGES
Scroll through the menu until ‘Replay User x Msg’ is
displayed and press .
Press to stop the message playback early.
PHONE NUMBERS
Scroll through the menu until ‘4.7 PHONE NUMBERS’ is displayed and press .
Scroll through the menu until the required ‘Phone
No._’ (and the current setting) is displayed.
To change the setting press .
Enter the new phone number (32 digits max.)
Press to save and exit, or
Press to exit without saving.
After programming all required phone numbers press
to return to the top level Latch Key Setup menu.
ESC
ESC
ENTER
3
1
ESC
ESC
ESC
1
3
ENTER
ENTER
ENTER
ENTER
ENTER
Notes:
Press to insert a 3.5 seconds pause in
the dialling sequence.
Press to move the cursor left.
Press to move the cursor right.
Press to delete the number under the cursor.
Press (and hold) to erase the entire number.
ENTER
ESC
Page 47
47
FRIEDLAND SPECTRA PLUS
LIGHTING SETUP
Scroll through the menu until ‘7. SPECTRA
LIGHTING SETUP’ is displayed on the LCD and
press .
After configuring the Spectra Plus lighting press to return to the top level programming menu.
SET LIGHT-ON PERIOD
This controls the time period for which any linked
Spectra lighting is switched on for following an alarm condition.
Scroll through the system menu until ‘7.1 Lamp On
Time’ (and the current setting) is displayed.
To change the setting press .
Enter the required light-on period (1 to 20 minutes).
Press to save the new setting, or
Press to exit without saving.
SET LIGHTING OPERATING MODE
This controls whether the Spectra Lighting is active
and if it operates on a 24 hours basis or is time controlled. If time controlled it means that the user can set the time in the morning after which an alarm will no longer cause the lights to activate and the time in the evening after which an alarm will allow the lights to be activated again. This prevents the lights from being triggered during the day.
Scroll through the system menu until ‘7.2 Spectra
Mode’ (and the current setting) is displayed.
To change the setting press .
Options: OFF / 24-Hour / Time-Controlled
Press to save the new setting, or
Press to exit without saving.
STOP TIME
This controls the time of day after which triggering
an alarm will no longer be able to activate the Spectra Lighting.
Scroll through the system menu until ‘7.3 Stop Time’
(and the current setting) is displayed and press .
Enter the new time in the format ‘hh:mm’ using the 24 hour clock format.
Press to save the new setting, or
Press to exit without saving.
START TIME
This controls the time of day after which triggering
an alarm will be able to activate the Spectra Lighting.
Scroll through the system menu until ‘7.4 Start Time’
(and the current setting) is displayed and press .
Enter the new time in the format ‘hh:mm’ using the 24 hour clock format.
Press to save the new setting, or
Press to exit without saving.
PROGRAM MODE Code:
enter Master User Access Code and press ENTER
7. SPECTRA LIGHTING SETUP
press ENTER
Enter (1-20 mins) stop: HH:MMstop: HH:MM
enter time
press ENTER
enter time
press ENTER
enter time
press ENTER
7.1 Lamp On Time xx minutes
7.4 Start Time HH:MM
7.3 Stop Time HH:MM
press ENTER press ENTER press ENTER
off
24-hour
Time-Controlled
select menu item
press ENTER
7.2 Lamp On Time xxxxxxxxxxxxxx
press ENTER
ENTER
ENTER
ESC
ENTER
ENTER
ESC
ENTER
ESC
ENTER
ENTER
ENTER
ESC
ENTER
ESC
Page 48
48
When leaving the premises, the system must be Armed. However, before doing so, check that all windows are closed and locked, all protected doors are closed and PIR Detectors are not obstructed. Ensure that pets are restricted to areas not protected by PIR Detectors.
The system has 3 arming modes, ARM, Part-Arm 1 and Part-Arm 2. The Part-Arm modes allow for selected zones to be left in a Disarmed state whilst the remainder of the system is Armed.
When the system is Armed the mode being activated will be displayed on the screen followed by the status of the Latch Key feature. The programmed system exit-delay will be displayed and counted down on the screen. If exit-delay beeps are enabled the panel will beep with the beep rate increasing in steps as the exit-delay expires. At the end of the Exit period all active zones will be fully Armed. By this time the user must have left the property and closed the final protected door.
If while the system is armed a detector on an active zone is triggered the programmed entry-delay for that zone will be displayed and counted down on the screen. If entry-delay beeps are enabled the panel will beep with the beep rate increasing in steps as the entry-delay expires. If the system has not been Disarmed when the entry-delay expires a Full Alarm will occur. (Note: if the entry-delay for the zone triggering the alarm is disabled then an alarm will occur immediately the detector is triggered instead). Details of the zone event that triggered the alarm will be recorded in the Event Log.
At the end of the set alarm duration the Siren and Control Panel alarms will stop and the system will automatically re-Arm itself, (subject to the conditions of the Zone Lockout feature).
Notes:
To conserve power and maximise battery life the
PIR detector will only detect movement if there has been no movement detected within the previous 2 minutes.
–Ifthe Solar Siren is fitted and the 3 minute limit is
enabled then the siren will stop when the programmed alarm duration expires or after 3 minutes, whichever occurs first.
ARMING THE SYSTEM
The system can be set in FULL ARM mode using
either the Remote Control or the Control Panel as follows:
a. Press on the Remote Control, or
b. Press
on the Control Panel.
PART-ARMING THE SYSTEM:
PART-ARM 1
The system can be set in PART-ARM 1 mode using
either the Remote Control or the Control Panel as follows:
a. Press on the Remote Control, or
b. Press
on the Control Panel.
PART-ARMING THE SYSTEM:
PART-ARM 2
The system can be set in PART-ARM 2 mode using
either the Remote Control or the Control Panel as follows:
a. Press , on the Remote
Control, or
b. Press
on the Control Panel.
DISARMING THE SYSTEM
The system can be Disarmed using either the
Remote Control or the Control Panel as follows:
a. Press on the Remote Control, or
b. Press
on the Control Panel.
OPERATING INSTRUCTIONS
????
ENTER
, ,
User Access Code
????
ENTER
, ,
User Access Code
????
ENTER
, ,
User Access Code
????
ENTER
, ,
User Access Code
Page 49
49
Note: If the system is Disarmed with the Remote
Control the Siren will beep twice, (unless the warning beeps have been disabled on the Siren).
DISARMING THE SYSTEM WITH THE
DURESS CODE
If the system is disarmed at the Control Panel using
the Duress Access code the system will Disarm as normal. However, the Voice Dialler or Remote Manager dialler will be activated (after the 30s dialler delay) and the appropriate duress message sent.
The dialler Line LED will not be illuminated during this call.
FRIEDLAND SPECTRA PLUS LIGHTING
If the control panel is liked to a Spectra plus Lighting
Receiver and the Spectra lighting Control is enabled then any alarm condition (except Fire alarms) will cause the linked lighting to be switched on for the set light-on duration.
If the spectra lighting is configured as 24-hour then the lights will be triggered at any time an alarm occurs. However, if it is configured as time controlled then the lights will only be triggered if the alarm occurs either before the programmed stop time or after the start time. If the alarm occurs between the stop and start times the lights will not be triggered.
Notes:
1. Spectra lighting signal to be sent (subject to
mode and timed programmed settings) each
time a Tamper or PA switch is triggered and each time a detector on an enabled zone is triggered when the panel is armed.
2.
Spectra lighting will not be triggered by Smoke
Alarm events.
Spectra Manual-On/Auto switching:
Press switch the linked Spectra lighting ON.
Press to switch the linked Spectra lighting OFF and back to automatic operation.
QUICK SET
The Quick Set function fully arms the system with a
10s second exit delay:
Press
on the Control Panel.
Alternatively, pressing during the exit-delay period of any armed mode (including Part-Arm 1 and Part-Arm 2) will reset the remaining exit-delay period to 5 seconds.
PERSONAL ATTACK (PA) ALARM
An alarm can be immediately triggered at any time
(whether the system is Armed or Disarmed) in the event of threat or danger by activating a Personal Attack (PA) switch on either the Remote Control or the Control Panel as follows:
a. Slide the Personal Attack switch on the
Remote Control upwards, or
b. Press and hold the button for
approximately 3 seconds on the Control Panel.
The alarm will continue either for the alarm duration when the system will automatically reset or until the system is disarmed.
If the system has been triggered the ‘ALARM MEM’ LED will flash and the panel will beep every 10 seconds.
To stop the LED flashing and panel beeping either
a. Press or
b. Inspect the Event Log to find out the cause
of the alarm.
ESC
00.00 24.00
Stop Time
Start
Time
Spectra Enabled
Alarm conditions
will trigger
Spectra lighting
Spectra Disabled
Alarm conditions
will not trigger
Spectra lighting
Spectra Enabled
Alarm conditions
will trigger
Spectra lighting
????
ENTER
, ,
User Access Code
0
0
!
9
Page 50
50
LATCH KEY
If the Latch Key function is enabled and the
system is disarmed by a user that is enabled for Latch Key then…
1. The first Latch key phone number will be called
(if entered).
2.
10s after the number is dialled the appropriate
User ID message will be replayed.
The appropriate user ID message will be repeated continuously for 60s. After 60s has elapsed the current message play cycle will be completed and then the call will be terminated. This ensures the message is not cut off part way through.
3.
There is a 10s delay before the second latch
Key phone number is dialled (if entered).
4.
After both entered numbers have been dialled
once. There will be a 30s delay before the next call sequence is started again from the first entered number.
The dialler sequence can be stopped early by either…
a. All numbers have been dialled three times
b. A call is acknowledged by the recipient
pressing the button on the telephone keypad.
ZONE LOCKOUT
If while the system is armed a single alarm zone
triggers an alarm more than three times and zone lockout is enable then the particular zone will be “locked out” and any further alarm signals from that zone will be ignored by the siren and an alarm will not be triggered again during that armed session. The zone lockout will be cancelled when the siren is disarmed.
If zone lockout is disabled then there is no limit to the number of alarms that any single zone can initiate. Zone lockout is applicable to Alarm zones only. It does not operate with the Fire zone.
DEVICE TAMPER
The Tamper zone operates on a 24 hour basis.
(i.e. Receipt of a Tamper signal form any device will immediately trigger an alarm irrespective of systems armed/disarmed status unless the system is in program or Test modes).
If the battery cover of any device (except a Remote Control) is removed or if the Siren or Control Panel are removed from the wall then an alarm will immediately occur (unless the system is in Test or Program modes), even if the system is Disarmed.
The Alarm will sound until the set alarm duration time expires or the system is Disarmed from the Remote Control or Keypad. The ‘ALARM MEM’ LED on the Control Panel will flash and the panel will beep every few seconds to indicate an alarm has occurred.
CHIME
The Chime facility can only be operated with the
system in Standby mode.
Press to toggle the Chime facility between ON and OFF.
Also see page 39 in Zone Setup menu, 3.7 Znn Chime to enable the required zone.
KEYBOARD BEEP MUTE
The keyboard beeps can be temporarily switch
on/off by pressing
.
ENTRY/EXIT BEEPS
If the entry/exit delay beeps are enabled then they
may be temporarily switched OFF during the active delay period only by pressing
.
When the next entry/exit delay periods starts the beeps will follow the main system setting as normal.
EVENT LOG
Any new event entered into the event log will be
indicated by the ‘Alarm Msg’ LED flashing every 5 seconds.
Note: Alarm events only will cause the panel to
beep every 10s, other system events entered into the event log (e.g. low battery) will not initiate the warning beeps.
Message replay starts
Message play time
expires
10s
60s Message Play Time
Dialler delay expires number called
Message replay complete
Call ended and line hung up
2
3
3
Page 51
51
To stop the LED flashing press or access the Event Log to read the event message.
To read the event log press from Standby.
Use and to manually scroll through the events. Events are displayed starting with event 1 which is the most recent through to event 99.
Note: The Event Log will not automatically scroll
through the display as before.
Press to return to Standby.
Event Log Message Structure:
The event log messages are to be structured as
follows. This allows each event to be displayed on a single screen and not split across two screens. The top line being the event header detailing the event number and when the event occurred and the second line detailing the actual event:
e.g. Event 74 occurred on 13th March at 2:23pm,
Zone 12 – smoke detector – low battery
Header:
‘Enn: DD/MM hh:mm’
Where: nn = event number, 01 through to 99
DD = event date MM = event month hh = event hour mm = event minute
Event Messages:
Zone Event Messages:
Zxx PIR Alarm
Zxx PIR Tamper Zxx PIR LowBat Zxx MAG Alarm Zxx MAG Tamper Zxx MAG LowBat Zxx Smoke Alarm Zxx Smoke Tamper Zxx Smoke LowBat
User Event Messages:
User x Arm
User x Disarm User x PartArm 1 User x PartArm 2 User x Disarm Master Arm Master Disarm Master PartArm 1 Master PartArm 2 Master Disarm Duress Disarm
System Event Messages:
AC Power Fail
System Low-bat Remote Low-Bat Keypad Low-Bat Panic/PA System Tamper RF Jamming Tel Line Error V-Dialler Fail V-Dialler SendOK R-Manager Fail
REMOTE PHONE ACCESS
AND CONTROL
The Remote Phone Access and Control facility, if
enabled, allows you to dial into the system and monitor/ control the basic alarm system functions.
The Control Panel will answer the call after the set number of rings and emit 3 beeps on the phone line.
Enter a User Access Code on the telephone keypad.
A valid User Access Code will be acknowledged with 1 long beep.
An incorrect code will be acknowledged by 2 short beeps.
If a User Access Code is not entered within 30 seconds or is entered incorrectly 3 times then the Control Panel will automatically disconnect the line.
ESC
ESC
E74: 13/03 14:23
Z12 Smoke LowBat
8
Page 52
52
Double Dial-In for Operation with an External
Answer Phone:
If the Remote Access and Control feature is to be
used and the system is operating in conjunction with an external Answer Phone then
1. Remote Phone Access and Control must be
enabled.
2. The number of ‘rings to answer’ for the Control
Panel must be greater than that of the external answerphone.
To access the Remote System Control facility the Control panel has a ‘double dial-in’ feature to enable the Control Panel to pick-up the phone call before the external answerphone cuts in. The ‘double dial-in’ procedure operates as follows:
1. Dial up the system and hang up after 1 or 2 rings.
2. Wait a few seconds and then redial up the system
within 20 seconds, the system will answer the phone after 1 ring.
3. Enter the User Access Code as described above.
Remote Access and Control Functions:
The following functions may be access via the
remote telephone. The system will acknowledge each signal with a single long beep over the phone.
Press to interrogate the system status. The status will be indicated by the following tones which are generated once.
1 long beep system Disarmed 1 short beep system Armed 2 short beeps system Part-Armed (1 or 2) 3 short beeps Alarm has occurred
Press to initiate FULL ARM mode.
Press to initiate Part-Arm 1 mode.
Press to initiate Part-Arm 2 mode.
Press to Disarm the system.
Press to turn the Siren OFF.
Press to turn the Siren ON.
Press to activate listen in.
Press to stop Listen-In.
Press to end the session and disconnect the Control Panel line.
MONITORING (OPTIONAL)
REMOTE MANAGER
Refer to Remote Manager diagram on page 53.
If an alarm occurs and the Remote Manager dialler
is enabled…
1. The Remote Manager dialler will activate after
fixed 30s dialler delay has expired provided the system has not been disarmed in that period.
2. The first Remote Manager phone number will be
dialled and the appropriate alarm signal transmitted.
3. If an acknowledgement signal is received from
the Alarm Monitoring Service the dialler will stop and an ‘R-Manager Send OK’ message will be entered into the event log.
However…
4. If an acknowledgement signal is not received
from the Alarm Monitoring Service the call will be ended and the next number will be dialled.
There will be a 10s pause between consecutive calls in the same sequence and a 30s pause between consecutive sequences.
5. If an acknowledgement signal is not received after
each entered number has been called three times then the dialler will shut down and an ‘R-Manager
Fail’ message will be entered into the event log.
Notes:
1. If system disarmed while dialler is operating the
current call should be completed. After a further 10s the dialler will operate and send a Cancel signal to the alarm monitoring service using the same dialler process described above.
2. The same alarm event signal must not be re-
transmitted until there has been at least 10 minutes of inactivity of that event. Alarm events on different zones are treated separately.
For example:
If an alarm event is triggered by a detector
on zone 1, the AMS will be contacted with a “zone 1 intruder signal”.
If another zone 1 alarm event occurs within 10 minutes the AMS will not be contacted with this event. The 10 minute period should restart at this point.
Page 53
53
VOICE DIALLER
If an alarm is triggered and the Voice dialler is
activated then the first enabled phone number in the dialling sequence will be called and the recorded alarm message will be played. The recipient should acknowledge the message by pressing the button on their telephone keypad to shut down the call sequence. If an acknowledgment signal is not received, then the next enabled number in the call sequence will be called. The dialler will continue calling each enabled number in turn until either all numbers in the sequence have been dialled or is cancelled by an acknowledged signal from a recipient.
If an alarm occurs and the Voice Dialler is enabled…
1. The dialler will only activate after the fixed 30s
dialler delay has expired provided the system has not been disarmed in that period.
2. Each entered phone number will be called in the
order 1 - 2 - 3 - 4
If a number is not entered it will not be dialled.
3. 10s after the number is dialled the appropriate
alarm message will be replayed followed immediately by the main message.
The alarm and main messages will be repeated continuously for 60s. After 60s has elapsed the current message play cycle will be completed and then the call will be terminated. This ensures the message is not cut off part way through.
4. 10s delay before next entered number is dialled.
5. After all entered numbers have been dialled
once. There will be a 30s delay before the next call sequence is started again from the first entered number.
If a further zone 1 alarm event occurs after more than 10 minutes then this event will be transmitted to the AMS.
Remote Manager Diagram
System Armed
0m 5m 10m 15m
Zn 1 Alarm event
Zn 1 Alarm event
Zn 2 Alarm event
Zn 1 Alarm event
Initial Zone 1
event...
Zone 1 alarm
event sent
to AMS
2nd Zone 1
event...
occurs within
10 minutes
of last Zn 1
event...
NO
communication
to AMS
Initial Zone 2
event...
Zone 2 alarm
event sent
to AMS
3rd Zone 1
event...
occurs within
10 minutes
of last Zn 1
event...
AMS
Zone 1 alarm
AMS
Zone 2 alarm
AMS
Zone 1 alarm
Message replay starts
Message play time expires
10s
60s Message Play Time
Dialler delay expires number called
Message replay
complete
Call ended and
line hung up
30s Dialler
Delay
Alarm Activated
Page 54
54
The dialler sequence can be stopped early by either…
a. All numbers have been dialled three times
b. The system is disarmed
c. A call is acknowledged by the recipient
pressing the button on the telephone keypad.
Note: The line status warning will not operate if the
voice dialler is disabled.
The ‘Cancel/Abort’ signal must only be sent if
a. the dialler has successfully communicated
the alarm event to the AMS, or
b. the system is disarmed within 10 minutes
of the last alarm event being successfully communicated to the AMS.
SIREN SERVICE/ OPERATING MODE
In order to remove the Solar Siren from the wall to
change the batteries, it is necessary to place the Siren into Service mode to prevent the Tamper switch on the Siren operating and triggering an Alarm. When you have completed any alterations to the system you must remember to switch the Siren back into Operating Mode.
The Siren can be switched between Service and Operating modes using either the Remote Control or Control Panel as follows:
Remote Control:
Press and hold the button on the Remote
Control for approx. 6 seconds.
Control Panel:
With the system in Standby with the Power LED ON:
Press
to enter Test Mode.
Use and buttons to scroll through the available options until ‘Wirefree Siren Service ON/OFF’ is displayed.
Press .
The mode into which the Siren is switching will be indicated as follows:
Service Mode: The siren will produce two short
beeps followed 1 second later by a single long beep. The Siren LEDs will flash together in conjunction with the beeps.
Operating Mode: The siren will produce a
single long beep followed 1 second later by two short beeps. The Siren LEDs will flash together in conjunction with the beeps.
Press to return to Standby mode.
BATTERY MONITORING
Low battery condition
All system devices continuously monitor their battery
condition. When a low battery indicator is activated, the battery for that device should be replaced as soon as possible.
In addition if any PIR or Door /Window Detector has a low battery status it will be recorded by the Control Panel and a message stored in the Event Log.
In addition a low battery status on any PIR or Door/ Window Detector will be recorded by the Control Panel and stored in the Event Log.
Note: Before removing the battery cover on any
device to replace the battery ensure that the system is put into Test mode to avoid initiating a Full Alarm.
The low battery indication built into each system device is as follows:
Control Panel:
During a period of mains supply interruption
the Control Panel will be powered by the rechargeable backup batteries.
Under normal battery conditions the Power LED on the panel will flash at 1 second intervals. However, under low battery conditions the Power LED will flash at 3 second intervals
Remote Control:
When the Remote Control is operated under low
battery conditions the transmit LED will continue to flash after the button has been released.
Under normal battery conditions the LED will extinguish within 2 seconds of the button being released.
????
ENTER
, ,
User Access Code
ESC
ENTER
Page 55
55
PIR Movement Detector:
Under low battery conditions the LED behind the
detector lens will flash when movement is detected to indicate that the battery needs to be replaced.
Under normal battery conditions the LED does not illuminate unless the PIR Detector is in Walk Test mode.
Door/Window Detector:
When the Detector is activated, under low-
battery conditions the Transmit LED will be illuminated for approx. 1 second as the door/window is opened.
Under normal battery conditions the LED does not illuminate as the Detector is operated, (unless the Detector is in Test Mode with the battery cover removed).
Page 56
56
MAINTENANCE
Your Alarm System requires very little maintenance.
However, a few simple tasks will ensure its continued reliability and operation.
SOLAR SIREN
1.
It is recommended that the solar panel on the top
of the siren housing should be cleaned at least twice a year, preferably in the Spring and Autumn, using a soft damp cloth. Do not use abrasive, solvent based or aerosol cleaners. Do not attempt to clean inside the unit or allow water to enter the unit.
This will ensure that the solar panel does not become affected by the build up of excessive dirt and receives all the available light.
2. The Siren should not be left for long periods with
the batteries connected, unless the unit is able to receive sufficient light to maintain the battery charge. Failure to maintain charge to the unit will result in the rechargeable battery running unacceptably low. Should this occur, the unit must be recharged from a 7.5Vdc/ 100mA supply (e.g. from a mains adaptor power supply). When re-powering the Siren, fit a new 9V PP3 leak­proof Alkaline power-up battery to ensure that the Siren receives sufficient power until the solar panel can recharge the main battery.
3. The main rechargeable battery has a typical life
of 3 - 4 years and needs no maintenance during this period, provided the battery is kept charged. The battery will be damaged if it is stored in a discharged state for long periods.
CONTROL PANEL
The rechargeable batteries have a typical life in
excess of 3 to 4 years and need no maintenance
during this period, provided they are kept charged. The batteries will be damaged if they are stored in a discharged state for long periods.
DETECTORS, REMOTE CONTROL
AND KEYPAD
The Detectors and Remote Control require very little
maintenance. The batteries should be replaced once a year or when a low battery status is indicated.
DUMMY SIREN
The batteries in the siren should be replaced once
every year to ensure the siren continues to act as a visual deterrent during both the day and night
.
BATTERIES
Note: Before removing the battery cover on any
device to replace the battery ensure that the system is switched into Test Mode to avoid triggering an alarm.
The specifications for replacement batteries are:
Note: Rechargeable batteries should NOT be fitted
to any detector.
DISPOSAL AND RECYCLING
Batteries and waste electrical
products should not be disposed of with household waste. Please recycle where these facilities exist. Check with your local authority or retailer for recycling advice.
The Rechargeable Batteries contain Sulphuric Acid
– DO NOT ATTEMPT TO OPEN THE CASING.
Remote Control:
1 x 3V CR2032 Lithium Cell (or equivalent)
Door/Window Detector:
2 x 3V CR2032 Lithium Cells (or equivalent)
PIR Movement Detector:
1 x 9V PP3 Alkaline Battery
Keypad:
1 x 9V PP3 Alkaline Battery
Dummy Siren:
4 x 1.5V C Alkaline Batteries
IMPORTANT: Before removing the Siren from the
wall ensure that the Siren is first switched into Service Mode to prevent the Tamper switch operating and triggering an alarm.
First, place the Control Panel into Test Mode (see page 26) and then switch the Siren into Service Mode (see page 29).
The Siren must be switched back into Operating Mode, otherwise the system cannot be Armed.
Page 57
57
1
2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Entry
Delay
ALARM RECORD
Complete the following information during installation for future reference, when adding to your system and to assist
trouble shooting.
Zone
Detector
Type(s)
Location Type Chime Arm
Part-
Arm 1
Part-
Arm 2
Page 58
58
NOTES
You may make a note of your System information below.
Remote Manager Phone Numbers (Optional)
Phone No.1: Phone No. 2:
System ID No:
Voice Dialler Phone Numbers
Phone No.1: Phone No. 2:
Phone No. 3: Phone No. 4:
Latch Key Phone Numbers
Phone No.1: Phone No. 2:
User Access Codes
User 1: User 2: User 3:
User 4: User 5: User 6:
Master User:
This information is confidential and should be kept in a safe location.
Page 59
59
Control Unit not working - Power LED OFF
or flashing.
1. Mains power failure - check if other electrical
circuits are operable.
2. Check that mains adaptor is plugged in and
socket is switched ON.
3. Check that DC jack plug from mains adaptor is
connected in Control Panel.
4. Check fuse /MCB in Consumer Unit on the
circuit serving the Control Panel.
Note: Before replacing any fuses or resetting
the MCB, the cause of the failure should be investigated and rectified.
Control Unit “Low Battery” LED flashing.
1. Check all PIR,
Door/ Window
,Remote, Keypad and Smoke Detectors for low battery indication, (i.e. LED behind detection lens flashes when movement detected). Renew batteries as required.
Control Unit not accepting User Access Code.
1. Pause between key depressions too long. Do
not pause for more than 5 seconds between pressing keys.
2. Incorrect code entered. Press before
re-entering correct code.
3. Reset to factory defaults and reprogram system.
Detection Zone triggered (LED flashing) but
no alarm is sounding.
1. Entry/Exit delay still running and not yet
expired.
2. Alarm duration period has already expired and
system has reset.
3. Alarm duration programmed to ‘no alarm’.
Siren and Indicator LEDs operating but no
alarm at Control Panel.
1. Siren’s Tamper switch activated. Check security
of Siren fixing to wall and adjustment of anti­tamper switch to ensure switch is fully depressed.
Siren not responding to Control Panel.
1. Ensure ‘ID Code’ of the Siren is learnt by the
Control Panel.
2. Ensure main Siren configuration switch is set to
SIREN.
3. Incorrect User Access Code being entered at
Control Panel.
4. Ensure Siren is within effective radio range of
Control Panel and equipment is not mounted close to metal objects.
5. Siren rechargeable battery discharged
a. Clean Solar Panel.
b. Check age of rechargeable battery - replace if
at end of useful life.
c. Fit new initial power-up battery and re-power
up Siren.
Full Alarm sounds when system has not
been triggered by an intruder or is disarmed.
1. Tamper switch activation
a. Check all detector battery covers to ensure
correctly fitted.
b. Check Control Panel and Siren are securely
mounted to the wall and Tamper switch is closed.
2. Personal Attack Alarm operated from a Remote
Control or Control Panel.
3. Jamming Detection circuit operated.
TROUBLE SHOOTING
Symptom / Recommendation
ESC
Page 60
60
LED on Remote Control not illuminating, or
is dim when unit is operated.
1. Ensure battery is fitted with correct polarity.
2. Ensure battery holder connections are making
good contact with the battery.
3. Battery flat - replace battery.
PIR Detector false alarming.
1. Ensure that the detector is not pointing at a
source of heat or a moving object.
2. Ensure that the detector is not mounted above a
radiator or heater.
3. Ensure that the detector is not facing a window
or in direct sunlight.
4. Ensure that the detector is not in a draughty area.
5. Sensitivity set too HIGH - reset to LOW
sensitivity. (i.e. SW3 to down position).
PIR Detector not detecting a person’s
movement.
1. Ensure the battery clip is securely connected.
2. Ensure ‘ID Code’ of the detector is learnt for a
particular zone.
3. Sensitivity set too LOW - reset to HIGH
sensitivity. (i.e. SW3 to up position).
4. Ensure that detector is mounted the correct way
up, (i.e. with detection window at the bottom).
5. Ensure that the detector is mounted at the
correct height, (i.e. 2- 2.5 metres).
6. Allow up to 3 minutes for detector to stabilize
and become fully operational. Leave the area for this period.
7. Ensure detector is within effective radio range of
the Control Panel and is not mounted close to metal objects which may interfere with Radio transmission.
PIR Detector LED flashes on detection of
movement, (device in normal operation mode).
1. PIR still in Walk Test Mode for fixed 5 minutes
after the PCB button was activated.
2. Low battery - replace battery.
Door/Window Detector not working.
1. Ensure that Magnet is correctly positioned in
relation to Detector and that the gap between Magnet and Detector is less than 10mm.
2. Ensure batteries are fitted with correct polarity
(correct way around).
3. Ensure battery holder connections are making
good contact with the batteries and Circuit Board.
4. Ensure ‘ID Code’ of the detector is learnt for a
particular zone.
5. If an additional wired Magnetic Contact is
connected:
a. Check that both contacts are closed.
b. Check that additional contact is correctly
wired and switch SW3 set to the INT./EXT. position.
6. Ensure detector is within effective radio range
of Control Panel and is not mounted close to metal objects which may interfere with Radio transmission.
Door/Window Detector false alarming.
1. Ensure that magnet is correctly positioned in
relation to detector.
2. Ensure that gap between magnet and detector
is less than 10mm.
3. Tamper switch below battery cover is not
depressed - check battery cover is fitted correctly and that fixing lugs are not broken.
Page 61
61
LED on Door/ Window Detector illuminating
when door or window is opened.
1. Low battery - replace batteries.
Control Unit Not Contacting Remote
Manager Service on Alarm.
1. Telephone line not connected or faulty - check
phone line with another phone.
2. Dialer Mode incorrectly programmed.
3. Incorrect phone number for Remote Security
Manager Service programmed.
4. Incorrect system ID number for Remote Security
Manager Service programmed.
5. Remote Security Manager Service not
commissioned or signed up.
Remote Phone Access and Control facility
not functioning.
1. Telephone line not connected or faulty - check
phone line with another phone.
2. Remote Access disabled.
3. Incorrect User Access Code entered.
Voice-Dialler Not Responding to Alarm.
1. Telephone line not connected or faulty - check
phone line with another phone.
2. Incorrect phone numbers programmed.
3. Phone numbers disabled in dialling sequence.
4. Alarm messages not recorded.
Latch Key Not Responding when system
Disarmed.
1. Telephone line not connected or faulty - check
phone line with another phone.
2. Dialer Mode incorrectly programmed.
3. Latch Key disabled.
4. Latch Key set to Selected-Users and not
enabled for User that is Disarming the system.
5. No Latch Key phone numbers programmed.
CUSTOMER HELPLINE
Most issues can be solved over the phone in a few minutes.
Please contact our Helpline Team on the number below for any
installation and general advice regarding our products:
0844 736 9149
Lines open 9.00am to 5.00pm, Monday to Friday.
Calls charged at service providers national rate.
Page 62
62
The following additional accessories are available to enhance your system and provide further protection and a higher level of security where required.
ACCESSORIES
EXTENDING YOUR ALARM SYSTEM
GUARANTEE
Novar ED&S undertakes to replace or repair at its discretion goods (excluding non rechargeable batteries)
should they become defective within 1 year solely as a result of faulty materials and workmanship.
Understandably if the product has not been installed, operated or maintained in accordance with the instructions, has not been used appropriately or if any attempt has been made to rectify, dismantle or alter the product in any way the guarantee will be invalidated.
The guarantee states Novar ED&S entire liability. It does not extend to cover consequential loss or damage or installation costs arising from the defective product. This guarantee does not in any way affect the statutory or other rights of a consumer and applies to products installed within UK and Eire only.
If an item develops a fault, the product must be returned to the point of sale with:
1. Proof of purchase.
2. A full description of the fault.
3. All relevant batteries (disconnected).
Response is a trademark of Novar ED&S.
HW0
Response Dummy Siren
Accessory
HW2
Response PIR
Accessory
HW3
Response Remote
Control Accessory
HW4
Response Door/Window
Detector Accessory
0
1 2 3
4 5 6
7 8 9
2
1
HW5
Response Keypad
Accessory
HW10
Response 6V
Rechargeable Battery
Accessory
PW1
Response Wired
Door/ Window Contact
Accessory Pack
HW12
Response External
Lighting Control
Accessory
Page 63
NOTES
63
Page 64
External Solar Siren
RF operating frequency: 868MHz
Sealed lead acid battery 6V /1.2Ahr
Solar Panel 7.5V - Charge Rate
typically 60mA
Operation time in complete darkness
- up to 25 days
95dB Piezo Siren
10 minutes alarm duration limiter
(optional)
Siren Disable (selectable)
Rear anti-tamper protection
Jamming Detection
Audible confirmation
PIR Infra-Red Movement
Detector
RF operating frequency: 868MHz
Range: 150 metre max.
Detection range: 12 metres at 110°
Walk test facility
LOW/HIGH Detection Sensitivity
Anti-tamper protected
Corner or surface mount
Battery life >1 year
Low battery indicator
Magnetic Door/ Window
Detector(s)
RF operating frequency: 868MHz
Range: 150 metre max.
Test Mode
Anti-tamper protection
Facility to connect additional
wired Magnetic Contact
Battery life >1 year
Low battery indicator
Control Panel
RF operating frequency: 868MHz
Range: 125 metre max.
Battery back-up
Detector Low-Battery Status Indication
RF Jamming Detection
90dB Piezo Siren
Dual front and rear anti-tamper
6 Users + Master User + Duress
4 digit User Access Code
6 Wireless Zones + 4 Wired zones
2 Part-Arm Facilities
Independently programmable Entry
and Exit delays
Entry/Exit Delay Warning (selectable)
Programmable Alarm Duration
Quick Set
Zone lockout
Chime
Event Log (99 events)
Latch Key
Remote Phone Access and Control
System Control
Listen-In facility.
Front & Rear Anti-Tamper protection
Personal Attack (PA) facility
Telephone Voice Dialler
Remote Security Manager interface
Connections for Hardwired Siren
External Lighting Control
(Optional)
Power supply: 230Vac~50Hz
Load switching capacity
- Tungsten Filament: 1200W
- Tungsten Halogen: 1200W
-Fluorescent: 250W Note: Not suitable for compact
fluorescent lamps
Protection: IP54
Operatingtemperature:-20°C to +50°C
Operating Frequency: 868MHz
RF range: see transmitter device spec.
No of linkable devices: 10
Remote Control (Optional)
RF operating frequency: 868MHz
Range: 80 metre max.
Personal Attack (PA) switch
Operates all ARM, PART-ARM,
and DISARM functions
Transmission indicator
Battery life >1 year
Low battery indicator
Keypad (Optional)
RF operating frequency: 868MHz
Range: 125 metre max.
Changeable 4 digit User Access Code
Anti-tamper protected
Personal Attack (PA) facility
Battery life >1 year
Low battery indicator
COMPONENT SPECIFICATION
50042380Rev.A
100
mm
32
mm
148
mm
71
mm
13
mm
36
mm
112
mm
38
mm
140
mm
0
1 2 3
4 5 6
7 8 9
2
1
125
mm
26
mm
15
mm
12
mm
10
mm
52
mm
60
mm
187
mm
235
mm
1 45
6
7
ENTER
ESC
POWER ALARM
STATUS
ALARM MEM/
MESSAGE
LINE STATUS
!
9
2 3
8
?
0
95
mm
65
mm
40
mm
218
mm
300
mm
94
mm
CUSTOMER HELPLINE
Most issues can be solved over the
phone in a few minutes. Please contact our Helpline Team on
the number below for any installation and general advice regarding our products:
0844 736 9149
Lines open 9.00am to 5.00pm,
Monday to Friday. Calls charged at service providers national rate.
RESEARCH & DEVELOPMENT
Our R & D Department is constantly
developing new products. We practice
a policy of continued improvement
and reserve the right to change
specifications without prior notice.
Novar Electrical Devices and Systems
are Quality Assurance Registered to
BS EN ISO9001 2000, by Asta.
Novar Electrical Devices and Systems Limited. (A Honeywell Company)
The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA. UK
www.friedland.co.uk
.
© Novar Electrical Devices and Systems Limited. 2009
Loading...