Response Protector P500S Installation & Operating Manual

Page 1
Installation & Operating
Manual
Protector P500S
Solar Wirefree Alarm System
Page 2
FOREWORD
Your decision to purchase a Protector P500S Wirefree Alarm System represents a major and sensible step towards total protection of your premises, its contents and its occupants.
The Protector P500S Wirefree Alarm System complies with the requirements of BS6799 Class 1, 2 & 3 for Wire-free Alarms. All components are designed and manufactured to provide a high standard of security protection and long, reliable service. In addition, the radio devices are tested and approved by the Radio Regulatory division of the Department of Trade and Industry (DTI) to ensure that they will not interfere with other radio equipment. No radio licence is required, however, the approved radio frequency is not protected from interference and may be withdrawn from use at any time subject to the DTI giving users an appropriate notice period.
The Protector P500S Wirefree Alarm System is purposely designed for installation by non-experienced people using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual before proceeding with the installation. This manual should be retained for future reference.
During installation, it is also important that the procedures are followed in sequence.
IMPORTANT NOTE
All components, with the exception of the External Solar Siren are only suitable for internal use.
SYSTEM SECURITY
This system has been designed to both detect intruders and act as a strong deterrent to would-be intruders. Please remember that given adequate knowledge and time it is possible to overcome any alarm system and we therefore recommend that an Intruder Alarm is used in conjunction with good physical protection such as security windows and door locks.
The system is operated by entering an Access Code at the Control Unit keypad. Protection is provided within the system to prevent anyone trying to establish your Access Code by randomly pressing keys on the keypad. If 16 random keys are pressed the Control Unit will lock out and ‘Bleep’ for 15 seconds. If this occurs 3 times without a valid code being entered, a Full Alarm will occur.
CONTENTS
Page No.
INTRODUCTION 1
PLANNING AND EXTENDING YOUR PROTECTOR ALARM SYSTEM 2
CONTROL UNIT
Indicators and Keypad 3 Indicator Lights 3 Location 3 Installation 4 Settings 4 Jamming Detection 5
INITIAL POWER UP
Mains Adaptor 5 Optional Back-up Battery 5
SETTING YOUR ACCESS CODE 6
SETTING THE CONTROL UNIT TO TEST MODE 6
SETTING THE EXIT, ENTRY AND AUTO STOP TIMERS 6
WIREFREE PASSIVE INFRA RED DETECTORS (PIR’S)
Installation 8 Setting 9
WIREFREE MAGNETIC CONTACT DETECTOR(S)
Installation 10
EXTERNAL SOLAR SIREN
Location 11 Installation 12 Settings 12 Initial Power-up 12
SETTING THE SOLAR SIREN TRANSMITTER MODULE 13
OPERATING INSTRUCTIONS 13
BATTERY MONITORING 14
MAINTENANCE 15
TESTING THE SYSTEM 15
ALARM RECORD 16
TROUBLE SHOOTING 17
EXTENDING YOUR SYSTEM 19
SPECIFICATIONS Back Cover
Response
Protector P500S Wirefree Alarm System
Page 3
INTRODUCTION
The Protector P500S Alarm System contains all components necessary to install a complete system.
Items included are:
1 x Control Unit 1 x D.C. Mains Adaptor 2 x Wirefree Passive Infra Red Detectors 2 x Wirefree Magnetic Contact Detectors 1 x External Solar Siren
1Protector P500S
WP1.2-6
Wirefree Passive Infra
Red Detectors (PIR’s)
DC Mains Adaptor
Control Unit
(optional back-up battery NOT included).
Wirefree Magnetic Contact Detectors
Rechargeable Battery
(supplied fitted in the External Siren)
Detector Batteries
External Solar Siren
Also included:
Installation & Operating Manual All necessary fixings Window stickers
EXTENDING YOUR SYSTEM
Having selected a Protector Wirefree Alarm System, you can increase your protection by adding additional Wirefree Passive Infra Red Detectors (PIR’s) or Wirefree Magnetic Contact Detectors, either at the time of initial installation or at a future date. Full details of other accessories to extend your system are given on page 19. You may also wish to purchase Remote Control Unit(s) to enable you to operate your Control Unit from in or around your premises.
Page 4
For even greater protection you can install as many PIR’s and Magnetic Contact Detectors as and when your require. The Protector P500S Alarm
System is designed to give you protection for a three bedroomed house. Just add additional detectors where further protection is needed.
PLANNING AND EXTENDING YOUR PROTECTOR P500S ALARM SYSTEM
2 Protector P500S
PART ARM
Protect either all of your home or just the areas you choose. For example, for night time protection you can have downstairs plus the garage and shed Part Armed whilst upstairs is Disarmed. This allows you to occupy upstairs areas without activating your alarm.
PLANNING YOUR INSTALLATION
Before attempting to install your Protector P500S Alarm System it is important to study your security requirements and plan your installation.
External Solar Siren
Magnetic Contact Detector
Magnetic Contact Detector
PIR
Remote Control (Optional)
PIR
PIR PIR
PIR
LOUNGE
GROUND FLOOR
GARAGE
KITCHEN
HALL
DINNING
ROOM
Back Door
SHED
Magnetic Contact Detector
Control Unit
Each property will have its own layout, the diagram shown is intended as a guide.
Page 5
LOCATION
When choosing a suitable location for the Control Unit, the following points should be considered.
1. Ensure that the Control Unit is within a protected area with the system Armed, ie: an intruder cannot reach the Control Unit without opening a protected door or being detected by a movement detector.
2. The position selected must be within reach of a 13A socket.
3. The Control Unit should be close to the entry/exit door but not visible from the door or windows.
4. Do not locate the Control Unit closer than 1 metre to any large metallic object eg: mirrors, radiators, fridge­freezers, etc.
5. Locate the Control Unit in an easily accessible position, between 1.5 and 2 metres above floor level and in a position where it will be seen each day.
INDICATORS AND KEYPAD
INDICATOR LIGHTS
GREEN On System Fully Armed
Flashing System Part Armed Off Disarmed
RED On Instant/Full Armed Zone Activated
Slow flashing Delay/Part Armed Zone Activated Rapid flashing Tamper/Personal Attack Zone Activated Off Normal
YELLOW Slow Flashing Detector Low Battery
Rapid Flashing Low Battery in Test Mode On Test Mode On Off Normal
GREEN On Adaptor Power (Normal)
Flashing Back-up Battery Power Only Off System Off
IMPORTANT: THE CONTROL UNIT INDICATOR LIGHTS HAVE NO RELATION TO THE PUSH BUTTONS THEY ARE ADJACENT TO.
CLEARING WARNING INDICATORS
The RED Alarm Activated and YELLOW Low Battery Indicators are cleared by entering on the Control Unit. (See page 6 for Setting your Access Code).
Protector P500S
3
CONTROL UNIT
Part Arm Button
Full Arm Button
Disarm Button
Te st Button
Indicator Lights
Access Code
Keypad
Buttons 0-9
1
3
2
4
5
6
7
8
9
0
Access Code
? ???
Page 6
Protector P500S
INSTALLATION
1. Undo the two front cover retaining screws and hinge the Control Unit cover down.
2. Using the paper template mark the four fixing holes, ensuring that the template is level. Note that the bottom fixings are keyhole type, so the holes should be marked through the top of the keyhole and that the bottom left hand fixing is behind the siren transmitter module.
3. Drill the four fixing holes & fully insert the plastic wall plugs supplied.
IMPORTANT NOTE:
Do not drill the fixing holes with the Control Unit in position, as the resulting dust could seriously affect the system electronics and invalidate the guarantee.
4. Insert the two lower screws almost fully in, slide the Control Unit lower keyhole slots over the screws & push down into position. Insert the top two screws & tighten all screws fully ensuring that the unit is fitted flush & firmly to the wall.
Be careful when fitting the bottom right-hand screw not to damage the ribbon cable and ensure that the
control unit sounder plug is plugged into the socket at the bottom right.
SETTING THE SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to activate or disarm your system, you must set your system to accept encrypted radio signals only from your own Detectors. This is done by setting a series of miniature switches in the Control Unit and Detectors to a special combination selected by yourself. (Similar to setting a combination lock).
IMPORTANT NOTE:
In order for all detectors to communicate with the Control Unit, it is essential that the same House Code
4
Control Unit
Anti Tamper Switch
Power Jack Socket
Fuse
J.D. Link
House Code
Miniature
Switches 1-8
Entry/Exit Delay
To ne Switch 9
OFF
ON
Siren Code
Miniature
Switches 1-8
Solar Siren
Transmitter Module
Main PCB Protection Cover
Control Unit Siren Plug
Ribbon Cable
Entry/Exit Delay Tone
Selection Switch 9
(Always change from the factory setting)
House Code
ON
1 2 3 4 5 6 7 8 9
View of inside
of Control Unit
Page 7
is used for all components (except the Solar Siren). To set the system House Code proceed as follows.
Using a small screw driver or ball-point pen, set the first eight miniature switches (numbered 1-8) on the House Code switch block in any random combination of either ‘ON’ or ‘OFF’. Take note of the combination selected, as it will be required when setting the Detectors, (and other accessories, when purchased).
DO NOT set or adjust the miniature switches on the Solar Siren transmitter at this stage.
SETTING THE ENTRY/EXIT DELAY TONE
Your alarm system has an adjustable delay timer which delays activation of the system after you have Armed it to allow time to close the exit door on leaving, and to Disarm the system on entry. Setting of the entry/exit delay timer is explained later in this manual. During the entry/exit delay time, the Control Unit sounder will emit either a continuous tone or two short ‘bleep' tones at the beginning of the delay time and two at the end (Semi­Silent) depending on the setting of the miniature switch number 9 on the Control Unit House Code switch block. Set switch number 9 to ‘ON’ for the ‘Semi-Silent’ short ‘Bleep’ tone, or to ‘OFF’ for a continuous tone.
JAMMING DETECTION
In order to detect any attempts to illegally jam the radio channel used with your alarm system a special jamming detection circuit is incorporated into the Control Unit. If this feature is selected, and the radio channel is jammed continuously for 30 seconds, when the system is Armed or Part Armed, the Control Unit will emit a pre-alarm series of rapid bleeps for 5 seconds. If the jamming continues for a further 10 seconds or more a Full Alarm condition will occur on the Tamper Zone.
The jamming detection circuit is designed to permanently scan for jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detect function ‘ON’ permanently. To select the Jamming Detect function simply set the J.D. Link on the Control Unit PCB to ‘ON’
INITIAL POWER UP
MAINS ADAPTOR
A DC Mains Adaptor and Cable is supplied with the equipment. To fit the Mains Adaptor, proceed as follows:
1. Lead the cable along the cable track or pass the cable through the knockout in the rear of the casing.
2. Plug the jack plug into the jack socket on the printed circuit board as shown below. Close the Control Unit cover and hold it firmly closed whilst securing the two retaining screws.
Note: Leave the cover open if the optional back-up battery is to be fitted.
3. Plug the adaptor into a 13A socket.
4. The Control Unit will emit a continuous bleep while the four indicator lights illuminate sequentially for 2 seconds.
5. The green power indicator will now illuminate steady, indicating that the Control Unit is powered from the mains supply. (It is normal for the adaptor to appear warm to the touch when in use).
OPTIONAL BACK-UP BATTERY
The Control Unit has provision for an optional 1.2Ahr rechargeable back-up battery. The purpose of the battery is to supply emergency power to the Control Unit in the event of a failure of the mains supply. The back­up battery is capable of providing emergency power to the Control Unit for a period of approx. 8 hours and will automatically recharge on restoration of the supply. The system will operate normally under mains supply only. However, for additional protection we recommend that the optional back-up battery is fitted.
Protector P500S 5
W
P
1.2
-
12
Alternative Cable
Entry (knockout)
Power Supply
Jack Socket
Cable Track
OPTIONAL
Back-up Battery
Page 8
1. To fit the optional back-up battery, place the battery in the compartment provided and connect the battery leads red to red (+) and black to black (-).
2. In the event of mains failure the green power indicator will now flash, showing that the Control Unit is powered by battery only.
3. Close the Control Unit cover and hold it firmly closed whilst securing the two retaining screws.
SETTING YOUR ACCESS CODE
The Control Unit is supplied with a preset Access Code of .
However, for security reasons, it is essential that you immediately change the Access Code to another four­digit number which only you and other occupants of the premises know (usually a number with a personal significance is easier to remember).
IMPORTANT NOTE
If the Control Unit is powered down, (eg no mains or battery) the Access Code will return to
and you will have to re-programme
it again to your own Access Code. If you should forget your Access Code, you will need to completely power down the control unit and then re-apply power to the Control Unit. However, you may change the Access Code at any time using the following procedure (except when in Test mode).
To change your Access Code, open the hinged keypad cover.
1. Press
2. Enter
or your current Access
Code if applicable.
3. Press
4. Enter new Access Code
5. Press
6. The Control Unit Siren will emit two rapid ‘bleeps’ to indicate acknowledgment of new Access Code.
7. From now on, only the new Access Code will operate the system.
Note: Do not pause more than 5 seconds between pressing keys, otherwise the code change will not be accepted and you will need to start the programming sequence again from the beginning.
SETTING THE CONTROL UNIT TO TEST MODE
Before installing the Passive Infra Red or Magnetic Contact Detectors you should set the Control Unit to Test mode. This will help to ensure that the correct House Code is used and to establish the radio range.
1. Enter at the keypad.
2. The system is now in Test mode.
3. The yellow indicator light will be illuminated.
4. When a Detector is operated, the Control Unit will sound for 3 seconds and the red Alarm Activated light will illuminate and indicate the zone of operation.
The Control Unit should be left in Test mode whilst the detectors and other accessories are set up and installed. However, if you wish to exit the Test mode,
enter at the Control Unit to
revert to normal, Disarmed mode.
SETTING THE EXIT, ENTRY AND AUTO STOP TIMERS
EXIT TIME
When you arm the system, by entering your Access Code at the Control Unit keypad, the system will ignore Detectors for a preset delay time to allow you to leave the premises. During the delay period (Full Arm or Part Arm), the Control Unit sounder will emit either two short bleeps at the beginning and two short bleeps at the end of the delay period (Semi-Silent Mode) or a continuous tone throughout the delay period, depending on the setting of miniature switch 9 in the Control Unit as previously described.
6 Protector P500S
1 2 3 4
Access Code
? ???
Access Code
? ??? 1 2 3 4
? ???
1 2 3 4
Page 9
Your Control Unit is supplied with the exit time preset to 30 seconds. However, you may change the exit time if required, as follows:
With the Control Unit still in the Test mode,
press then either = 10 sec
or = 20 sec
or = 30 sec
or = 40 sec
or = 50 sec
ENTRY TIME
When entering the premises with the system Armed, or entering a protected area with the system Part Armed, all Detectors set to give an entry delay will be inactive for a preset time delay to allow you to disarm the system by entering your Access Code at the Control Unit keypad. During the entry delay period (Full or Part Arm), the Control Unit sounder will emit either two short bleeps at the beginning of the delay period (Semi-Silent Mode) or a continuous intermittent bleep tone throughout the delay period, depending on the setting of miniature switch 9 in the Control Unit, as previously described. Your Control Unit is supplied with the entry time preset to 30 seconds. However, you may change the entry time if required, as follows:
With the Control Unit still in Test mode,
press then either = 10 sec
or = 20 sec
or = 30 sec
or = 40 sec
or = 50 sec
ALARM AUTO STOP TIME
The Control Unit is supplied with the ‘Auto Stop’ time (the length of time that the Control Unit Siren and External Siren will sound for when activated) set at 3 minutes. This time can be adjusted if necessary between 1 minute and 10 minutes as follows:
With the Control Unit still in the Test mode,
press then either = 1 mins
or = 2 mins
or = 3 mins
or = 5 mins
or = 10 mins
(If accidentally triggered, the alarm can be stopped at any time by disarming at the Control Unit keypad).
NOTE:
The maximum length of time that the External Solar Siren will sound for when activated is set within the Solar Siren to either 3 or 15 minutes - refer to “Installing & Setting the External Solar Siren” for details.
LEAVE THE CONTROL UNIT IN THE TEST MODE WHILST YOU INSTALL ALL YOUR DETECTORS.
Protector P500S 7
12345
followed by
67890
followed by
12345
followed by
Page 10
WIREFREE PASSIVE INFRA RED DETECTORS(PIR's)
Two Passive Infra Red Detectors are supplied in the standard package. However, additional Passive Infra Red Detectors can be purchased separately, if required. Passive Infra Red Detectors are designed to detect movement within a protected area. The Detector element detects differences in Infra Red radiation when a person moves within the protected area. If movement is detected, a radio signal is transmitted to the Control Unit to activate the alarm.
The recommended position for a Passive Infra Red Detector is in the corner of a room mounted between 2 and 2.5 metres from the floor. At this height, the detector will detect movement up to 6 metres at 110° and 12 metres at 60° depending on adjustment. Also, in this position, the 110°/60° fan-shaped detection patterns can normally offer greater protection than mounting on a flat wall. Before selecting a position for a Passive Infra Red detector the following points should be noted:
1. Do not position Detector facing a window or direct sunlight. Passive Infra Red Detectors are not suitable for use in conservatories or draughty areas.
2. Do not position Detector directly above any source of heat, eg. fire, radiators, boiler etc.
3. Where possible, keep pets out of areas protected by Passive Infra Red Detectors. If this is not possible, alternative mounting arrangements or a special Pet Lens may be required.
4. Where possible, mount the Detector so that the logical path of an intruder would cut across the fan patterns rather than directly towards the Detector.
Any number of Passive Infra Red Detectors can be used with your system, providing they are all coded with the system House Code and are within the radio range of the Control Unit. To install and set the Passive Infra Red Detectors, proceed as follows.
INSTALLING THE WIREFREE PASSIVE INFRA RED DETECTORS (PIR’s)
1. Remove the battery cover by inserting a coin under the cover lip and twisting open. Remove the fixings pack.
2. Remove the screw (in the battery compartment) holding the wall bracket to the Detector.
3. Slide the bracket up and remove the wall bracket from the Detector as shown.
4. Hold the wall bracket in position and mark the two mounting holes. (If corner mounting, drill pilot holes in the chamfers as shown). Drill two 4mm diameter holes and insert the plastic wall plugs and screw the bracket to the wall using the screws supplied.
8 Protector P500S
Pulse Count Detection Switch on Side
UP = 2 pulse detection
DOWN = 1 pulse detection
TOP
TOP
Fixings for Corner Mounting
Fixings for
Surface Mounting
Normal Lens
11
0° angle
60° angle
Pet Lens
Up to 6m at 110° and 12m at 60°
1m clearance at 7m with pet lens fitted
2-2.5m
2.5m
7m
1m
Page 11
5. Offer the Detector up to the wall bracket and locate it into one of the bracket slots to angle the Detector down slightly. Fix the Detector in position on the bracket using the fixing screw at the rear of the battery compartment.
Note: A special Pet Lens (order code PL1) is available direct from Response Electronics PLC (Tel 01372 848586) for installation into the Detector at 2.5 metres mounting height to allow for pet movement. Alternatively, mount the Detector upside down, ie. with the battery compartment upwards, at a height of 1 metre from the floor. This will shorten the detection range but allow pets to move about the floor area without activating the Detector.
View inside PIR Detector battery compartment
SETTING THE WIREFREE PASSIVE INFRA RED DETECTORS (PIR’s)
ENSURE THAT THE CONTROL UNIT IS STILL IN TEST MODE.
1. Using a small screwdriver or ball-point pen, set the miniature switches 1-8 to the same combination of ‘ON’ and ‘OFF’ as the House Code switches in the Control Unit.
2. If the passive Infra-Red detector has to be active in the ‘Part Armed’ mode or if activation of the detector has to be delayed during entry (Part or Full Armed) set miniature switches 9 and 10 to ‘ON’. Otherwise set switch 9 ‘ON’ and switch 10 ‘OFF’.
Note: Any other combination of switches 9 and 10 will not operate with your P500S Control Unit.
3. The PIR incorporates an anti false-alarm feature designed to compensate where the Detector may be
affected by environmental changes, eg. insects, air temperature, etc. This feature is called ‘Pulse Count’ and may be selected for one or two pulses.
The recommended Pulse Count is one. In cases of extreme environmental problems or if unattributable false alarms are experienced, it may be necessary to select Two Pulse Count detection.
Note: The higher the Pulse Count, the more paces an intruder will have to move before triggering the alarm.
To select the required pulse count move the switch on the side of the detector:
UP = Two Pulse Detection
DOWN = One Pulse Detection.
4. Fit the 9 Volt Alkaline battery supplied to the battery terminals, but do not replace the battery cover.
Note: As soon as the battery is connected, a two tone Alarm will be emitted from the Control Unit siren for 3 seconds and the Tamper/PA Zone LED will illuminate. This confirms that the House Code is correct and that the Detector is within radio range of the Control Unit.
5. After the battery has been connected for approximately 40 seconds, the Infra Red Detector will become active causing the LED above the detector window to flash every time movement is detected. Where Two Pulse Count detection has been selected, the LED will be dim on the first detection and brighter on the second.
The Control Unit will also emit a 3 second alarm tone each time the Detector senses movement and the appropriate Zone LED indication will be given to confirm the Zone selected (instant or delay).
6. By walking into the protected area the Detector will now be triggered each time the Detector senses movement. If necessary re-adjust the detection distance by angling the Detector up or down on its wall bracket.
7. Replace the battery cover on the Detector.
Note: When the Detector is fully installed, ie. battery cover is refitted, the Unit will not detect movement for approx. 40 seconds after each activation. In normal operation, with the battery cover on, the red LED, above the detector window, will NOT illuminate upon detection of movement.
Leave the Control Unit in Test mode and proceed to install your remaining Detectors.
Protector P500S 9
House Code
ON
1 2 3 4 5 6 7 8 9 10
PART ARM/ENTRY DELAY
SWITCHES 9 AND 10
Anti
Ta mper
Switch
Backplate Fixing Screw
ON
1 2 3 4 5 6 7 8 9 10
SW9 SW10 OPERATION
ON
ON
OFF
OFF
ON
OFF
ON
OFF
DELAY/PART ARM
INSTANT FULL ARM
NOT USED
NOT USED
Page 12
WIREFREE MAGNETIC CONTACT DETECTOR(S)
INSTALLATION
Two Magnetic Contact Detectors are supplied in the standard package. However, additional Contact Detectors can be purchased separately if required. Any number of Magnetic Contact Detectors can be used with your system, providing they are all coded with the system House Code and are within radio range of the Control Unit. Magnetic Contact Detectors can be fitted to protect doors or windows as required.
To set the House Code and fit the batteries, proceed as follows:
ENSURE THAT THE CONTROL UNIT IS STILL IN THE TEST MODE
1. Remove the battery cover by sliding and lifting off.
DO NOT use a screw driver to lever off.
2. Remove the battery holder by carefully tilting up the end and sliding the connectors off of the printed circuit board.
3 Slide the batteries supplied into the battery holder
ensuring that the positive (+) side is uppermost on each battery as it is installed.
4. Carefully refit the battery holder into the Detector ensuring that the spring connectors slide onto either side of the circuit board.
5 Using a small screwdriver or ball-point pen, set the
miniature switches 1-8 to the same combination of ‘ON’ and ‘OFF’ as the House Code switches in the Control Unit.
Note: Once the House Code is set, press and release the detector anti-tamper switch. A 3 second, two tone alarm will be emitted from the Control Unit Siren. This confirms that the House Code is correct.
6. If the Magnetic Contact Detector has to be
active in the Part Armed mode, or if activation of the detector has to be delayed during entry (Part or Full Armed) set the miniature switches 9 and 10 ‘ON’. Otherwise set switch 9 ‘ON’ and switch 10 ‘OFF’.
Note: Any other combination of switches 9 and 10 will not operate with your P500S Control Unit.
7. Hold the Contact Detector at the correct position on the door or window then press and release the anti-tamper switch. Providing the Detector is within radio range of the Control Unit, the two tone alarm will be repeated for another 3 seconds. When fixing the Detector to a metal door/window under exceptional circumstances it may be
10 Protector P500S
ON
1 2 3 4 5 6 7 8 9 10 11
Tilt and remove
battery holder and insert both
batteries
Double Sided Tape
OR Screw Fixing
Raised Head Screw, Key-hole Slot Fixing
Small Counter-sunk
Screw Fixing
Battery
Connector
Slide Open and Lift Off
Do Not Use A Screwdriver
(Ensure back
surfaces are flush)
Detector
Magnet
Alternative Mounting
House Code
Location of Key-hole Screw (underside)
Hole for Mounting Screw
Printed Circuit Board
Anti-Tamper Switch
ON
1 2 3 4 5 6 7 8 9 10
8mm
11m m
SW9 SW10 OPERATION
ON
ON
OFF
OFF
ON
OFF
ON
OFF
DELAY/PART ARM
INSTANT FULL ARM
NOT USED
NOT USED
PART ARM/ENTRY DELAY
SWITCHES 9 AND 10
Page 13
necessary to space the Magnet/Detector off the metal surface using a plastic or wooden spacer to achieve the necessary radio range.
8. Remove the battery holder, then using the double
sided tape OR the screws provided, mount the Magnet to the door and the Detector to the door frame (or vice-versa, if necessary). Ensure that the arrows on the Magnet and Detector are pointing towards each other and that the gap between the Detector and Magnet is less than 5 mm. When using the screws for mounting the Detector, ensure that the small countersunk screw is used within the battery compartment and that the screw is driven flush with the inside of the casing.
9. Refit the battery holder (the Control Unit will emit a 3 second Tamper Alarm).
10 .Refit the battery cover by placing it over the
batteries and sliding it on.
11 .Test the operation by opening the door/window.
The LED on the Detector will light for approximately 1 second and then extinguish each time the Magnet is moved away from the Detector, and the Control Unit will emit a 3 second alarm tone each time the Detector is operated.
When you have completed installing all your Detectors, take the Control Unit out of Test mode
by entering
at the Control Unit.
EXTERNAL SOLAR SIREN
The Solar Siren incorporates a solar panel which will maintain a charge to the integral 6 Volt 1.2Ahr sealed lead acid rechargeable battery during daylight hours. During the night, a negligible amount of energy is released by the rechargeable battery to operate the Siren. The Solar Siren is self maintainable during darkness and long winter periods.
LOCATION
To provide the optimum amount on daylight to the Solar Panel, you should ideally mount the Solar Siren on a south facing wall. However, an easterly or westerly position will suffice.
Although the Solar Siren is designed to work on any aspect wall, for optimum performance you should refrain from siting the Unit on a north facing wall where possible. Shadows cast by neighbouring walls, trees and roof overhangs should also be avoided. Where applicable, the Solar Siren should be positioned a minimum of twice the width of the eaves overhang below the eaves. Remember that in winter the sun is lower in the sky and you should avoid winter shadows where possible.
The Solar Siren contains a sophisticated radio receiver. However, reception of radio signals can be affected by the presence of metallic objects within the vicinity of
Access Code
? ???
Protector P500S 11
NORTH
WEST
EAST
SOUTH
Avoid if possible
Page 14
Ta mper
switch
6V 1.2Ahr
rechargeable
battery
9V PP3 initial
power up battery
Siren
Printed circuit board enclosure
Receiver
Aerial
Miniature switch cover
Alarm duration miniature switch 9
Siren Code miniature switches 1-8
7.5 V DC charging adaptor input
Front cover locating tabs
Optional Strobe Upgrade PCB
Solar Panel
ON
1 2 3 4 5 6 7 8 9
View of inside
Solar Siren
the Solar Siren. It is therefore important to mount the Solar Siren a minimum distance of 1m radius away from any external or internal metalwork, ie. external drain pipes, gutters and internal radiators, mirrors etc.
INSTALLATION
Remove the holding screw from the base of the housing and carefully hinge off the front cover. All electronic components are housed within the front cover.
Use the rear back-plate as a template to mark the position of the four fixing holes on the external wall. Drill four 5mm diameter holes and insert the plastic wall plugs. Mount the back-plate using the four screws provided.
SETTINGS
Undo the three screws holding the miniature switch cover in place and remove the cover.
SIREN CODE
Under the cover you will find a series of two position miniature dip switches.
Using a ball-point pen set the miniature dip switches 1-8 to a random sequence of ‘ON’s’ and ‘OFF’s’. Make a note of the Siren Code miniature switch settings as this will be needed when setting the siren transmitter in the Control Unit.
DO NOT SET THE “SIREN CODE” TO THE “HOUSE CODE” USED IN THE DETECTORS.
Note: When the Solar Siren is viewed as shown above
the miniature switches are ‘upside down’.
ALARM DURATION
This is the maximum length of time that the Solar Siren alarm will sound for, following activation. Alarm duration can be set for either 3 or 15 minutes. Set
miniature
switch 9 ‘OFF’ for 3 minutes or ‘ON’ for 15 minutes.
Refit the miniature switch cover securely.
Note: Following activation into alarm condition the Solar Siren will continue to sound until either the Control Unit is Disarmed, or the Control Unit Auto Stop time expires, or until the Solar Siren Alarm Duration Time expires; whichever occurs first.
INITIAL POWER-UP
Once you have completed setting your Siren Code and Alarm Duration Time, connect the 9 Volt PP3 initial Power-up Battery to the clip-on connectors. Connect the Rechargeable Battery to the charging leads red to red (+) and black to black (-).
Hinge the front cover locating tabs over the top edge of the back-plate, push the base of the Siren cover into place and secure with the lower fixing screw.
12 Protector P500S
Alarm Duration DIP Switch 9
(Always change from the factory setting)
Siren Code
ON
1 2 3 4 5 6 7 8 9
Page 15
The installation of your Solar Siren is now complete.
Note: Once the batteries have been connected, the Unit will be operational and it is important that the Solar Panel receives sufficient light to maintain the battery charge. Also, the Unit should not be repeatedly set into alarm during installation/testing as this could rapidly drain the battery.
SETTING THE SOLAR SIREN TRANSMITTER MODULE
A small radio transmitter is incorporated within the Control Unit to operate and control the external Solar Siren.
To set the transmitter and operate the Solar Siren proceed as follows:
1. Turn the Control Unit ‘OFF’ by entering
at the Control Unit keypad. The green Power indicator light will extinguish.
2. With the Control Unit in ‘OFF’ mode, undo the cover retaining screws and hinge the Control Unit front cover down.
3. Set the miniature dip switches 1-8 on the Siren transmitter module (at the bottom of the Control Unit) to the same sequence of ‘ON’s and ‘OFF’s as set in the Solar Siren (the “Siren Code”).
DO NOT SET TO THE “HOUSE CODE” USED IN THE DETECTORS
4. Close the Control Unit front cover and secure the two retaining screws.
5. Turn the Control back ‘ON’ by entering
at the Control Unit keypad.
Note: Once the system has been installed, setting the Control Unit to the ‘Test Mode’ will prevent the external Siren from activating during testing. This will allow you to test the system without causing unnecessary disturbance.
OPERATING INSTRUCTIONS
FULLY ARMING THE SYSTEM
When leaving the premises, the system must be Fully Armed. However, before doing so, check that all windows are closed and locked, all protected doors are closed, and Passive Infra-Red Detectors are not obstructed. Ensure that pets are restricted to areas not protected by Passive Infra-Red Detectors, or that suitable precautions have been taken to allow for pets. To Fully Arm the system, hinge open the keypad cover,
and enter on the keypad
then close the keypad cover. If the system exit tone has been set for ‘continuous’ the Control Unit Sounder will emit a continuous tone for the duration of the preset exit time, arming automatically when the exit time expires.
If the system exit tone has been set for ‘Semi Silent’, the control unit sounder will emit two short bleep tones when the button is pressed and two short bleep tones on expiry of the exit time.
All occupants must leave the premises before the exit time has expired. If for any reason you are unable to leave the premises before the exit time has expired, you will need to Disarm the system, then re-arm.
Failure to do so will cause a Full Alarm if any protected door is opened or movement is detected by a Passive Infra-Red Detector.
Note: When Fully Armed, the Control Unit top green light will be constantly illuminated. (Refer to page 3).
Protector P500S 13
Access Code
? ???
Access Code
? ???
Access Code
? ???
Siren Code
ON
1 2 3 4 5 6 7 8
Solar Siren
RED
BLACK
YELLOW
N.O. C N.C. POWER () POWER (+) SIREN COM CHARGE TAM PER
2
1
3 4 5 6 7 8 9
Page 16
PART ARMING THE SYSTEM
If you are remaining in the premises, you may Arm only the PIR Detectors, and Magnetic Contact Detectors with miniature switches 9 and 10 set to ‘ON’, by selecting ‘Part Arm’. This will permit free access to areas where the Detectors are NOT set to operate on Part Arm.
To Part Arm the system hinge open the keypad cover, and enter on the keypad,
then close the keypad cover.
The exit tone emitted when the button is pressed will be the same as when fully arming the system and is dependant on the setting of miniature switch number 9 in the Control Unit. The system will set on ‘Part Arm’ on expiry of the preset exit time.
All occupants must leave any protected areas before expiry of the exit time. If for any reason you are unable to leave the protected areas within the exit time, you will need to disarm the system then re-arm. Failure to do so will cause a Full Alarm if any protected door is opened or movement is detected by a Passive Infra Red Detector set to operate in Part Arm.
Note: When set on ‘Part Arm’ the Control Unit top green light will be flashing. (See page 3).
DISARMING THE SYSTEM
Upon entering the premises or protected area, the entry tone will be emitted from the control unit sounder (Continuous or Semi-Silent).
You should proceed immediately to the Control Unit and enter to disarm the system.
DISARMING AFTER AN ALARM ACTIVATION
A Full Alarm condition (Control Unit Siren and External Siren operating), will be initiated following any intrusion or Tamper/Personal Attack Activation. This condition will continue until expiry of the preset alarm ‘Auto Stop’ time, whereby the External Siren and Control Unit Siren will cease. The Control Unit will now immediately re-arm itself. In the event of a further intrusion/activation the control unit will once again initiate a Full Alarm condition, and the above process is repeated.
If a Full Alarm condition is initiated accidently,
the alarm can by stopped immediately by entering at the Control Unit.
CONTROL UNIT OFF/ON MODE
To prevent the alarm from being activated when either opening the Control Unit or removing a battery cover from a Detector, it is necessary to first enter the Control Unit
OFF/ON code:
The green ‘Power On’ indicator will now extinguish. When you have completed your alterations, turn the control unit back ‘ON’ by re-entering the OFF/ON code as above. The green ‘Power On’ indicator will now illuminate and the system is ready for operation.
PERSONAL ATTACK ALARM
A Full Alarm condition can be initiated by the user at any time (system armed or disarmed) in the event of threat or danger. To initiate an alarm press and hold
and buttons on the Control Unit keypad
for more than 2 seconds.
The Control Unit Siren will emit a two tone ‘Tamper’ warning and the External Siren will operate. To cancel the alarm enter
at the Control Unit.
BATTERY MONITORING
The system will continuously monitor the battery condition of all PIR & Magnetic Contact Detectors. If the voltage level of any battery falls unacceptably low a radio signal will automatically be transmitted to the Control Unit and the yellow ‘Low Battery’ light will flash.
To identify a PIR Detector with a low battery, leave each protected area for at least 40 seconds. If, when you re­enter the area the PIR LED flashes on detection of movement, this indicates a low battery.
The batteries in the Magnetic Contact Detectors can be checked by operating the Detector (opening and closing the protected door/window) and observing the LED on the detector. If the LED is dim or does not illuminate the battery needs to be replaced.
Access Code
? ???
14 Protector P500S
Access Code
? ???
Access Code
? ???
Access Code
? ???
Access Code
? ???
Page 17
Protector P500S 15
In the event of a low battery condition, turn the Control Unit ‘OFF’ using the OFF/ON code. Replace the battery as required and turn the Control Unit back ‘ON’.
Note: When replacing PIR Detector batteries, fit a PP3 alkaline type. Rechargeable batteries should NOT be fitted.
For areas subject to seasonal low ambient temperatures (eg garages, sheds etc) we recommend the use of PP3 Lithium batteries (Response Electronics Plc order code 3005B) in PIR Detectors.
TESTING THE SYSTEM
You may test your system at any time, however, it is recommended that the system is tested at regular intervals not exceeding three months. To set the Control Unit to Test mode enter
at the Control Unit keypad.
The yellow ‘Test’ light will now illuminate.
Before testing areas protected by Passive Infra Red Detectors, ensure that the area is completely clear of occupants, including pets. Wait 40 seconds before testing areas protected by Passive Infra Red Detectors and also allow 40 seconds between tests. Where Two Pulse Detection has been selected, ensure you take two or three paces within the area to trigger the Detector.
When a Passive Infra Red Detector is activated, or a protected door or window is opened the Control Unit will emit a 3 second alarm tone and the associated Zone LED will indication will be given.
On completion of testing, return to the normal Disarmed mode of operation by entering
at the Control Unit keypad.
To test the External Siren, press and hold the and buttons simultaneously on the Control Unit keypad for more than 2 seconds to initiate a Personal Attack
alarm. Enter
to stop the
alarm and clear the ‘Alarm Activated’ light.
MAINTENANCE
Your P500S Intruder Alarm system requires very little maintenance. However, a few simple tasks will ensure its continued reliability and operation.
CONTROL UNIT
The Control Unit requires no maintenance. If cleaning is required, wipe the outside of the casing with a soft damp cloth. Do not use aerosols or sprays or proprietary cleaners. Do not attempt to clean inside the Unit or allow water to enter the Unit.
EXTERNAL SOLAR SIREN
1. At least once a year, preferably in the Autumn, the Solar Panel on the top of the siren housing should be cleaned using a soft, damp cloth. This operation will ensure that the Solar Panel receives all the available light. The cleaning operation can be combined with the general cleaning of the outside of the house, windows etc. to reduce maintenance time.
2. The Solar Siren incorporates tamper protection for system security. Should you, for any reason, have to completely power down the Solar Siren (eg. to move the system to a new premises) remove the holding screw at the base of the Siren and hinge off the front cover.
WARNING - THE SIREN WILL SOUND
Disconnect the rechargeable battery and initial power up battery.
3. The Solar Siren should not be left for long periods with the batteries connected, unless the Unit is able to receive sufficient light to maintain the battery charging circuit. Failure to maintain charge to the Unit will result in the rechargeable battery running unacceptably low. Should this occur, the Unit must be recharged from a 240 Volt AC/7.5 Volt DC mains adaptor (Response order code S100TR). When re-powering the Solar Siren fit a new 9 Volt PP3 leak proof Alkaline Initial Power-Up Battery to ensure that the Unit receives sufficient power until the Solar Panel can recharge the main battery completely.
Access Code
? ???
Access Code
? ???
Access Code
? ???
Page 18
House Code
ON
1 2 3 4 5 6 7 8
Siren Code
ON
1 2 3 4 5 6 7 8
P500S ALARM RECORD
Complete the following information during installation for future reference.
This information is highly confidential and should be kept in a very safe location.
Purchase date
Installation date
Control Unit serial number
Use the diagrams below to record your House Code and Siren Code, eg.,
Detector Type Location
Setting
Instant/Full Arm or
Delay/Part Arm
1
2
3
4
5
ON
16 Protector P500S
RECHARGEABLE BATTERY
The rechargeable battery in the Solar Siren (and the optional Control Unit back-up battery) have a typical life of 3-4 years and need no maintenance during this period providing the batteries are kept charged. The batteries will be damaged if stored in a discharged state.
The rechargeable batteries should be taken to a suitable Recycling Centre at the end of their useful life. DO NOT dispose of with your normal household waste. The rechargeable batteries contain Sulphuric Acid - DO NOT attempt to open the casing.
DETECTORS
The Detectors require no maintenance. Simply replace the batteries once a year or when a low battery is indicated. The specifications of the Detector batteries are as follows:
PIR Detectors: 9 Volt PP3 Alkaline
Magnetic Contact 2 x 3 Volt 230mAhr Lithium Cells Detectors: (Panasonic CR2032 or equivalent)
Please recycle used batteries were Local Authority facilities exist. Keep batteries away from children and do not dispose of in fire.
Pb
Page 19
Protector P500S 17
TROUBLE SHOOTING
Control Unit not working. Mains light is off
1. Check that mains adaptor is plugged into a 13 amp socket and switched on.
2. Control Unit has been turned ‘OFF’ using OFF/ON code (See page 14). Re-enter OFF/ON code to turn ‘ON’.
Full Alarm Occurs when alarm has not been activated by an intruder
1. Ensure mains adaptor is plugged in/connected and switched on.
2. Check that battery covers on all detectors are fitted securely.
3. Ensure that the Control Unit is securely fitted to the wall and that the front cover is firmly closed.
4. Check that the Personal Attack Button or Smoke Detectors (if fitted) have not been operated.
5. Check for Jamming Detection Alarm.
Control Unit ‘Low Battery’ Light flashing
1. Check all PIR Detector(s) for low battery, indicated by detector LED flashing when movement is detected - change battery(s) as required.
2. Check all Magnetic Detectors for low battery indicated by detector LED not illuminating when detector is opened/closed - change batteries as required.
3. Check the battery in all optional Wirefree Smoke Detectors - a low battery will also cause the Smoke Detector to bleep every minute - change battery as required.
Control Unit will not function (Sirens are sounding)
1. Disconnect power (including Control Unit Back-up Battery), for 10 seconds, then re-connect mains power followed by Back up Battery. (Remember, to reset Access Code and timed functions following power-up).
Control Unit not accepting Access Code
1. Pausing too long between pressing keys. Do not pause for more than 5 seconds between keys.
2. Incorrect code entered. Allow 5 seconds to elapse before re-entering correct code.
3. Unit has reset to Access Code 1, 2, 3, 4. Re­programme your Access Code.
Control Unit not responding to detectors
1. Ensure detectors are within radio range of Control Unit. If not, move detector closer.
2. Ensure that the House Code on the Detector is the same as that set in the Control Unit.
3. Replace detector battery.
External Solar Siren sounding but no alarm at Control Unit
1. Siren Anti-tamper activated. Check security of Siren fixing to wall and that Siren anti-tamper switch is fully depressed.
2. Siren has not received ‘Stop’ signal. Press and hold and on Control Unit keypad to initiate
PA alarm. Wait 15 seconds then enter to re-transmit ‘Stop’ signal.
External Solar Siren does not operate when system is activated
1. Incorrect Siren Code dip switch settings in Solar Siren or Siren Code incorrectly set on transmitter module in Control Unit.
2. Siren duration time timed-out before Control Unit Auto stop time.
3. Disconnect rechargeable and power-up batteries. Cover solar panel and leave unit for 3-5 minutes. Re-connect the batteries and then remove the Solar panel cover.
4. Rechargeable battery low. Power down, fit new initial power up battery and re-power up.
No response from Passive Infra Red Detector
1. Check battery connections are good.
2. Ensure that House Code is same as that set in Control Unit.
Passive Infra Red Detector false alarming
1. Ensure that the Detector is not pointing at a source of heat or a moving object.
2. Ensure that the Detector is not mounted above a radiator or heater, or in a draughty area.
3. Ensure that the Detector is not facing a window or in direct sunlight.
Symptom /Recommendation Symptom /Recommendation
Access Code
? ???
Page 20
18 Protector P500S
Continued
TROUBLE SHOOTING
Passive Infra Red Detector not detecting a person’s movement
1. Allow up to one minute for the Detector to settle down and retry.
2. Pulse Count set too high - reset to one Pulse Count Detection.
3. Ensure that Detector is mounted the correct way up (battery compartment at the bottom except for Pet Alley).
4. Ensure that the Detector is mounted at the correct height 1.8 - 2m from floor, (except Pet Alley).
5. Check that the Detector is correctly set-up. (See Setting Up Infra Red Detectors).
6. If Detector is mounted upside down for Pet Alley, check that the mounting height is not greater than 1m from the floor, depending on the size of pet.
Passive Infra Red Detector LED flashes when you walk past it
1. Low battery - replace alkaline battery.
Magnetic Contact Detector not working
1. Ensure House Code is the same as that set in the Control Unit.
Red light on Magnetic Contact Detector not illuminating or is dim when door or window is opened
1. Ensure batteries are connected with correct polarity.
2. Replace batteries with new.
3. Ensure battery connections are good and that connector is fitted correctly to PCB.
Magnetic Contact Detector false alarming
1. Ensure that gap between Magnet and Detector is less than 5mm.
2. Tamper switch below battery cover not depressed. Check battery cover fixing lugs are not broken.
Symptom /Recommendation Symptom /Recommendation
In order to comply with the Code of Practice on Noise from Intruder Alarms 1981 you should carry out the following procedures within 48 hours of the Intruder Alarm installation.
1. Notify your local police station in writing that an Intruder Alarm System has been installed, giving names and contact details of at least two persons who know the System Access Code.
2. Ensure that all users are aware of the operating procedures.
3. Inform the local Environmental Health Authority of the installation and which police station has been informed.
4. Immediately inform your local police station if there is a change to the persons who have access to the system
Important notice following alarm installation
HELPLINE
If you need help, just dial for
expert technical support
01372 450960
(Lines open 9.00am to 6.00pm, Monday to Friday).
Page 21
Protector P500S
19
DUMMY SOLAR SIREN S100YD
The Solar Siren is available as a yellow and blue dummy design and acts as an excellent visual deterrent.
STROBE UPGRADE CA2000STR
Add to your existing Siren Unit to provide full Siren and Strobe protection. The Strobe flash light is activated simultaneously with your Siren which will help to identify the property in alarm condition.
WIREFREE REMOTE CONTROL CA2000R
Allows you to fully Arm and Disarm your system from anywhere in and around your property within range of the Control Unit. The Remote Control also incorporates a built in Personal Attack button, for added peace of mind.
Note: Does not incorporate Part Arm facility.
WIREFREE SMOKE DETECTOR CA2000SD
In the event of fire the battery operated Wirefree Smoke Detector will send a security coded signal to your Control Unit and sound your alarm. The Smoke Detector also has its own alarm siren and when used with the P500S provides an exceptionally high level of safety to your home. There is no limit to the number of Wirefree Smoke Detectors you can use with your Alarm System.
REPEATER UNIT CA2000RU
The signal distance range between a detector and the Control Unit is typically up to 100m in free air space. If you need to increase this range just place the Repeater Unit between the detector and Control Unit to increase the signal range. The Repeater Unit can also be used to extend the range between the Control Unit and the External Solar Siren.
Note: Indoor use only. Requires mains supply.
CONTROL UNIT BACK-UP BATTERY 3001B
Add to your system’s protection to provide battery operation in the event of a mains power failure. The back-up battery is maintenance free; is automatically charged from the system; and fits neatly inside the Control Unit.
ACCESSORIES
S100YD
STROBE UPGRADE
(This part only)
CA2000STR
PANIC
ON OFF
CA2000R
EXTENDING YOUR PROTECTOR P500S WIREFREE INTRUDER ALARM SYSTEM
You may add additional Wirefree Magnetic Contact Detectors and Wirefree PIR Detectors, etc. from the CA2000 range of accessories as required, to give additional protection where needed. The following accessories are also available to extend and enhance your system.
CA2000SD
CA2000RU
WP1.2-12
3001B
For further information contact our SalesLine on 01372 450960 who will be pleased to supply further information on extending your system.
Page 22
20 Protector P500S
GUARANTEE
This product (excluding Detector batteries) is guaranteed for one year from the date of purchase against faulty materials or workmanship. We will repair or replace any faulty product. No liability can be accepted for any problems caused by fair wear and tear, buyers negligence, improper fitting or use, wilful or accidental damage, or any consequential loss or damage howsoever caused. This guarantee does not affect your
statutory rights and is valid in the UK and Eire only.
If an item develops a fault, the product must be returned to the address
below in adequate packaging with:
1. A copy of your original invoice/receipt.
2. A full description of the fault.
3. All relevant batteries.
PLEASE NOTE
If returning a Control Unit, make sure that the optional rechargeable battery
is disconnected and removed. If returning an External Solar Siren, make
sure that the rechargeable battery and initial power up battery are disconnected and secure and that the unit is packaged to
prevent damage in transit.
For security, Recorded or Registered Post is recommended.
17 Church Road, Great Bookham, Surrey KT23 3PG
Telephone: 01372 450960
E-mail: info@wireless-alarms.net
If you need help, just dial the Helpline
for expert technical support:
01372 450960
(Lines open 9.00am to 6.00pm, Monday to Friday).
We can solve most problems quickly over the phone.
www.wireless-alarms.net
Page 23
Control Unit
Internal 110db Siren
Siren tones : Intruder
Tamper/PA
3 zones - Full Arm, Part Arm and 24 Hour Tamper/PA
N/O - N/C Dry Contacts
Semi Silent Delay option
Entry/Exit delay - adjustable 10, 20, 30, 40 or 50 seconds
Siren duration - adjustable 1, 2, 3, 5, or 10 minutes
Built in Dual button Personal Attack Alarm
Front Anti-Tamper
Jamming Detection
Test Mode Facility
Low Battery Indicator for Detectors
12 Volt Auxiliary output (for Automatic Dialler etc)
Keypad Access Code (4 digit - user changeable)
Integral Solar Siren transmitter
Hard-wired Siren connection facility
Facilities for optional back-up battery (Ref. 3001B)
Wirefree
Remote Control
(Optional)
Full Arm/Disarm
Personal attack button
LED confirmation
Alkaline battery supplied
No Part Arm facility
External
Solar Siren
Case material 3mm Polycarbonate
Dual front and rear anti-tamper
Internal receiver and aerial UK frequency 418MHz
Sealed lead acid battery 6 Volt 1.2Ahr
Solar Panel 7.5 Volt - Charge Rate typically 60mA
Time out - switchable 3 or 15 minutes
Quiescent current 850µA (typical)
Piezo Sounder 105dB current 150mA
Operation time in complete darkness - 40 days
Anti-Foam
Also available as visual deterrent Dummy Unit (order code S100YD)
Optional Strobe Upgrade
Wirefree Magnetic
Contact Detector
LED battery confirmation
Anti-tamper
Operating gap up to 10mm
Door or window mounting
Low battery indicator
Lithium batteries supplied
Wirefree Passive
Infra Red Detector
Detection range: up to 6 metres at 110° and 12 metres at 60°
Walk test facility
One or two pulse count detection
RF immunity
Low battery indicator
Anti-tamper
Adjustable wall bracket
Corner or surface mount
Pet mount option
Alkaline battery supplied
Repeater Unit
(Optional)
Increase signal distance range up to a further 100m in free air space
Requires 230 Volt AC mains supply
12 Volt DC adaptor supplied
Optional rechargeable back-up battery (Ref. 3002B)
Telescopic aerial
Indoor use only
225
mm
160
mm
60
mm
Wirefree
Smoke Detector
(Optional)
Ionisation element
Security coded signal
Battery test button
Low Battery audio confirmation
Conforms to British Standard BS 5446 (Part 1 1990)
Internal Siren 85dB
Requires Alkaline battery
45
mm
130
mm
315
mm
225
mm
85
mm
62
mm
141
mm
45
mm
125
mm
26
mm
15
mm
12
mm
10
mm
52
mm
92
mm
62
mm
38
mm
36
mm
78
mm
17
mm
PANIC
ON OFF
HELPLINE:
01372 450960
(Lines open 9.00am to 6.00pm,
Monday to Friday.
If you need help,
just dial the
Helpline for
expert technical
support
PROTECTOR P500S WIREFREE ALARM
SYSTEM SPECIFICATION
RESEARCH &
DEVELOPMENT
Our R & D Department is
constantly developing new
products. We practice a
policy of continued improvement and reserve the right to change specifications
without prior notice.
WA_08/04 P500S
Wireless Alarms. 17 Church Road, Great Bookham, Surrey KT23 3PG
Te lephone: 01372 450960 E-mail: info@wireless-alarms.net www.wireless-alarms.net
Loading...