Functional Safety installation guide and safety manual
Contents
Product compliance 1
Denitions2
Information for use 2
Functional Safety data declaration 2
Safety function 3
Certication4
Storage and handling 5
TONiC FS T40x1 readhead installation drawing 6
RESM20 installation drawing (‘A’ section) 7
RESM20 installation drawing (‘B’ section) 8
System connection – DOP interface 14
T40x1 readhead and RESM20 compatibility 15
Readhead mounting and alignment 16
System calibration 17
Diagnostic LEDs 18
Output signals 19
Speed 20
Electrical connections 21
Outputspecications22
Generalspecications23
Select a mounting option 9
Taper mount method 9
Interferencetmethod11
TONiC FS quick-start guide 12
Cable connection 13
System connection – Ti interface 13
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
Ringtechnicalspecications23
TONiC Ti interface drawing 24
TONiC DOP interface drawing 24
Product compliance
This document is an installation guide and safety manual, which details the actions required for the safe
integration of the TONiC FS (Functional Safety) encoder system, as designated by the T4 prex in the part
number, into a functionally safe system; this will be referred to as TONiC FS system in the below document.
SIL2
FUNCTIONAL
SAFETY
PLd
The TONiC FS system as dened below is suitable for use in a Category 3 performance leveld(PLd)
application in compliance with ISO13849 and in a safety integrity level 2 (SIL2) application in compliance
with IEC61508 and IEC61800-5-2 when installed and operated in accordance with the instructions dened.
Failure to follow the correct use instructions or heed the limitations may result in SIL2 and/or PLd
A copy of the TONiC FS certicate is available from our website at www.renishaw.com/productcompliance.
C
Renishaw plc declares that TONiC FS system complies with the applicable standards and regulations.
A copy of the EU declaration of conformity is available from our website at
www.renishaw.com/productcompliance.
For further details of FS compliance see ‘Certication’ on page 4.
FCC compliance
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
The user is cautioned that any changes or modications not expressly approved by Renishaw plc or
authorised representative could void the user’s authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at their own expense.
NOTE: This unit was tested with shielded cables on the peripheral devices. Shielded cables must be used
with the unit to ensure compliance.
Patents
Features of Renishaw’s encoder systems and similar products are the subjects of the following patents and
patent applications:
RENISHAW HAS MADE CONSIDERABLE EFFORTS TO ENSURE THE CONTENT OF THIS DOCUMENT
IS CORRECT AT THE DATE OF PUBLICATION BUT MAKES NO WARRANTIES OR REPRESENTATIONS
REGARDING THE CONTENT. RENISHAW EXCLUDES LIABILITY, HOWSOEVER ARISING, FOR ANY
INACCURACIES IN THIS DOCUMENT.
The packaging of our products contains the following materials and can be recycled.
InsertsLow Density Polyethylene FoamLDPERecyclable
CardboardNot applicableRecyclable
BagsHigh Density Polyethylene BagHDPERecyclable
Metalised PolyethylenePERecyclable
REACH regulation
Information required by Article 33(1) of Regulation (EC) No. 1907/2006 (‘REACH’) relating to products
containing substances of very high concern (SVHCs) is available at www.renishaw.com/REACH
Further information
Further information relating to the TONiC FS encoder range can be found at
www.renishaw.com/safety-encoders and is also available from your local representative. This document
may not be copied or reproduced in whole or in part, or transferred to any other media or language, by any
means without the written prior permission of Renishaw. The publication of material within this document
does not imply freedom from the patent rights of Renishaw plc.
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
The use of this symbol on Renishaw products and/or accompanying documentation indicates that the
product should not be mixed with general household waste upon disposal. It is the responsibility of the end
user to dispose of this product at a designated collection point for waste electrical and electronic equipment
(WEEE) to enable reuse or recycling. Correct disposal of this product will help to save valuable resources
and prevent potential negative effects on the environment. For more information, please contact your local
waste disposal service or Renishaw distributor.
1
Denitions
Functional Safety data declaration
WARNINGA hazard with a medium risk of injury if not avoided
ESD handling
Mechanical safe position
Evaluation unit
System manufacturer
System installer
Information for use
The ESD Susceptibility Symbol consists of a triangle, a reaching hand, and a slash
through the reaching hand. The triangle means ‘Caution’ and the slash through the
reaching hand means ‘Don’t touch’.
The maximum distance the scale might move from its installed position, for example if
the xings work loose.
External item of equipment in which the output signal of the encoder is evaluated,
e.g. machine controller or safety relay.
Personnel with responsibility for selecting the encoder and verifying its capability is
appropriate for the safety related application.
Personnel with responsibility for tting the encoder in the specic application.
WARNINGNot to be used in environments where there is an explosive atmosphere
WARNINGNot to be used by medical devices
The TONiC FS system is designed to be used as part of a safety-related control system as specied by the system
manufacturer. It is the responsibility of the system manufacturer to set the evaluation unit to implement the appropriate
actions when the TONiC FS system reports an error. The decision to use this system for the intended purpose is the
responsibility of the system manufacturer. The TONiC FS system is certied to the SIL and PL levels as shown in the
‘Functional Safety data declaration’, however the system manufacturer must conduct their own assessment of the full
system to determine its safety capability.
Correct use includes:
X Operating the TONiC FS system within the limits dened in this document.X Installing the system as described in this document.X Maintaining the system as described in this document.
System components:
The TONiC FS system comprises the following parts:
X TONiC FS readhead.X TONiC Ti0000A00A or DOP interface.X RESM20 ‘A’ section or ‘B’ section ring.
NOTES:
X Rings retained by interference t only (unbolted) are not approved for use with the TONiC FS encoder system.
X Only the analogue sine and cosine outputs are functionally safe.
If the original termination supplied with the TONiC FS system is altered or an extension cable used, then it is the
responsibility of the system manufacturer to make sure the system is compliant with IEC 61800-5-2 Annex E
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
2
Safety function
The TONiC FS system provides 1 Vpp (nominal) sine and cosine outputs, where the sine and cosine
outputs are 90° phase shifted, in order for the evaluation unit to perform incremental counting and
X The system installer must perform a veried commissioning test during installation.
X The system repairer must perform a veried commissioning test following replacement of a system part.
X When installed correctly, the TONiC FS system shall have mechanical safe position not exceeding 2.5°.
NOTE: Thermal expansion effects of the scale and readhead mounting tolerances are excluded from the
mechanical safe position.
X The TONiC FS system includes no self-diagnostic function.
NOTE:Faults are detected only by the evaluation unit monitoring. When errors are detected it is the
responsibility of the system manufacturer to place the system into a safe state.
Fault exclusions
The following will invalidate the Functional Safety certication of the TONiC FS system (see page 4):
X Faults caused by cutting and reconnecting the readhead cable or extending the readhead cable.
X Incorrect installation of the readhead.
X Incorrect installation of the scale.
X Dismantling of the TONiC readhead or the Ti or DOP interfaces.
X Operating the system outside of the limits specied within this installation guide.
Failure modes
Failure modes are detected by evaluation unit monitoring. See ‘Functional Safety data declaration’ on page 2
for a summary of the FMEDA.
NOTE: For the purposes of the FMEDA calculation, the following conditions have been assumed:
For the safety function to be valid the instructions detailed in this installation guide must be followed.
Commissioning test
The following check must be performed when commissioning the TONiC FS system and after any repair of
the system.
NOTE: Repair is by replacement of system parts only.
Axis movement checkMove the axis over its full travel to verify the following:
X Position output is correct within a tolerance of ±10%.
X Direction of movement is correct.
X The signal amplitude for both sine and cosine signals falls within the limits
dened in ‘Evaluation unit monitoring’.
Evaluation unit monitoring
To achieve full system integrity the evaluation unit must continuously monitor the analogue outputs and,
in the case of fault detection, place the system into a safe state within the process safety time.
Signal amplitude checkNominal signal amplitude value is 1V, indicating full signal strength where
√ (sine2 + cosine2) = 1V. A fault condition must be asserted if the analogue
output is ≤0.7 V and ≥1.35 V.
Sine/cosine cross checkSine and cosine signals must be evaluated separately and the results
compared. A fault condition must be asserted if the phase shift is incorrect
with reference to the safe position limit for the system, see ‘Output
specications’ on page 22.
Following error checkFollowing error is dened as the difference between the expected position
and position feedback. A fault condition must be asserted if the following error
exceeds the safe position limit for the system.
NOTES:
X The evaluation unit must achieve medium diagnostic coverage (≥90%) according to ISO13849.
X Improper setting of the switching thresholds and hysteresis in signal evaluation can result in incorrect
determination of direction of rotation, position or speed.
X A persistent fault condition may indicate a hardware failure of the TONiC FS system or an
installation problem.
Maintenance
The maintenance check intervals will be dened by the system manufacturer according to their risk
assessment. There are no user serviceable parts within the readhead and interface.
The following maintenance actions are advised:
X Check the readhead to bracket screws are correctly tightened.
X Check for worn or damaged cable connecting the readhead to the interface.
X Check that the scale has not been damaged or contaminated. If required, clean the system using
approved solvents (see ‘Storage and handling’ on page 5).
NOTE: Do not retighten the screws securing the encoder ring as this will change the ring settings.
Repair
The replacement parts must have the same part number as the original parts. The new system must be
installed and commissioned in accordance with the ‘Commissioning test’. In the event of failure the affected
parts should be returned to Renishaw for further analysis. Using damaged parts invalidates the Functional
Safety certication.
Proof testing
It is the responsibility of the system manufacturer to dene any proof testing of the system. Due to the
diagnostic coverage (DC) and safe failure fraction (SFF) required to achieve SIL2, the encoder can only
support continuous demand use.
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
3
Certication
EU declaration of conformity
TONiC FS encoder system
FunctionalSafetyCerticateNo.FSC001
SIL2
FUNCTIONAL
SAFETY
PLd
Under the terms of CSA SIRA Functional Safety Certicate SIRA CASS00023/01, for the management and
self-certication of functional safety activities up to SIL3/PLd:
Renishaw plc declares that the products listed by this installation guide meet the requirements of:
BS EN IEC 61508-1:2010, BS EN IEC 61508-2:2010 and BS EN IEC 61508-3:2010
BS EN 61800-5-2:2017 (IEC 61800-5-2:2016)
BS EN ISO 13849-1:2015 and BS EN ISO 13849-2:2012
when used as an element/subsystem in safety related systems performing safety functions requiring up to
and including:
SIL2 with HFT = 0 (1oo1)
Category 3, PLd.
Renishaw plc declares under its sole responsibility that the products identied below are in conformity with
all relevant Union legislation.
NameDescription
Product Name:TONiC FS encoder system
Description:TONiC optical encoder system, that is FS certied
Part no.:T3xxx (Linear); T4xxx (Rotary)
Valid from:Serial number 2AHF37
Serial number 2AHF79
The products comply with EU directives:
2014/30/EUElectromagnetic compatibility (EMC)
2011/65/EUOn the restriction of the use of certain hazardous substances
inelectrical and electronic equipment (recast)
and comply with the following technical standards:
BS EN 12100:2010Safety of machinery. General principles for design.
Risk assessment and risk reduction
BS EN 61010-1:2010Safety requirements for electrical equipment for measurement,
control, and laboratory use
Part 1: General requirements
BS EN 61326-1:2013Electrical equipment for measurement, control and laboratory use.
EMC requirements. General requirements
Immunity to Table 2 - Industrial electromagnetic environment
Emissions to Class A - Industrial electromagnetic environment
BS EN 62471:2008Photobiological safety of lamps and lamp systems
The persons authorised to compile the technical le and issue the declaration of conformity are:
Steve Oakes, Director & General Manager, Encoder Products Division
Martin Curtis, Regulatory Compliance Manager, Encoder Products Division
Renishaw plc, New Mills, Wotton-under-Edge, Gloucestershire, GL12 8JR, United Kingdom
Signed: M. Curtis
Dated: 30/09/2019
Place: Wotton-under-Edge
Reference no. EUD 2019-003
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
BS EN IEC 63000:2018Technical documentation for the assessment of electrical and
electronic products with respect to the restriction of hazardous
substances
4
Storage and handling
TONiC RESM rings are non-contact optical
encoders that provide good immunity against
2 off mounting holes 2.5 through, counterbored Ø3 × 2.3 deep both sides
(Pitch tol. ±1°)
0.6
Rideheight 2.1 ±0.15
Forward direction of ring
(increasing count)
4.25
Alternative
mounting
face
4.15
10
†
* Extent of mounting faces.
NOTE: External magnetic elds greater than 6 mT, in the vicinity of the readhead, may cause false activation of the limit and reference sensors.
†
Minimum thread engagement 5mm (7.5 including counterbore). Tightening torque 0.25 to 0.4 Nm.
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
6
RESM20 installation drawing (‘A’ section)
Dimensions and tolerances in mm
N holes equally spaced on PCD ØDH Ø3.5 through
counterbore top face Ø6 × 3 deep
N holes equally spaced on PCD ØDH M3 × 0.5 through
counterbore top face Ø3.5 × 4 deep
A
10
A
θ
0.5 × 45°
15° ±0.2°
1 × 45°
3
ØDI
Section A–A
ØDH
ØDO
NOTE:θis the angle betweenone tapped hole and the adjacent clearance hole.
The angle between two clearance holes is 2θ.
TONiC RESM20 Functional Safety installation guide and safety manual Original instructions
Nominal
external
diameter
(mm)
52
57
75
100
103
104
115
150
200
206
209
229
255
300
350
413
417
489
550
*
There are no tapped holes on the 489 mm ring.
IMPORTANT: TONiC FS readheads must be used with the correct size RESM.
Ensure matching part numbers when ordering.
Line
count
8 192
9 000
11 840
15 744
16 200
16 384
18 000
23 600
31 488
32 400
32 768
36 000
40 000
47 200
55 040
64 800
65 536
76 800
86 400
DO
(mm)
52.2030.04
52.1030.00
57.3537.04
57.2537.00
75.4055.04
75.3055.00
100.3080.04
100.2080.00
103.2080.04
103.0080.00
104.4080.04
104.2080.00
114.7095.04
114.5095.00
150.40130.04
150.20130.00
200.40180.04
200.20180.00
206.50186.05
206.10186.00
208.80186.05
208.40186.00
229.40209.05
229.00209.00
254.80235.06
254.40235.00
300.40280.06
300.20280.00
350.40330.06
350.20330.00
412.70392.08
412.30392.00
417.40380.10
417.00380.00
489.12451.10
488.72450.90
550.20510.10
549.80510.00
DI
(mm)
Mounting holesReadhead
DH
(mm)
40630°
47630°
65630°
90630°
90630°
90630°
105630°
140920°
1901215°
1961215°
1961215°
2191215°
2451215°
2901611.25°
3401611.25°
4021810°
3901810°
462
520209°
N
20
θ
18° *
model
T4021
T4011
T4001
7
Loading...