The device complies with the standard type described in the EG
declaration of conformity. It was manufactured and commissioned in
accordance with European directives.
The original of the declaration of compliance is available from the
manufacturer.
9.2Spare parts ..........................................................93
040412 - 7600585-01
5
1. Introduction
1Introduction
1.1Symbols used
Calenta 25s - 28c - 35s - 40c
In these instructions, various danger levels are employed to draw the
user's attention to particular information. In so doing, we wish to
safeguard the user's safety, obviate hazards and guarantee correct
operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical
injury.
WARNING
Risk of a dangerous situation causing slight physical
injury.
1.2Abbreviations
1.3General
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in the
instructions.
4 3CE: Collective conduit for sealed boiler
4 Central heating: Central heating
4 COP: Energy performance
4 DHW: Domestic hot water
4 HRU: Heat Recovery Unit
1.3.1.Manufacturer's liability
Our products are manufactured in compliance with the requirements
of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
6
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
1. Introduction
In the interest of customers, we are continuously endeavouring to
make improvements in product quality. All the specifications stated in
this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following
cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.3.2.Installer's liability
The installer is responsible for the installation and inital start up of the
appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.4Homologations
1.4.1.Certifications
CE identification no
NOx classification
Type of connection
(Flue gas outlet)
Depending on the type of appliance and the gross heat
requirements for domestic water in accordance with NEN
5128, efficiency values up to 0,825 can be applied to
determine EPC.
Approval labels for gas
n
The boiler has been given several approval labels for gas. Stichting
Energie Prestatiekeur grants these independent labels on
performance to gas consumption appliances that meet specific
provisions on a certain number of aspects (efficiency, environmental
friendliness, comfort). The labels have the following meaning:
PIN 0063BT3444
5 (EN 297 pr A3, EN 656)
B23 , B
C
93
, B33 , C13 , C33 , C43 , C53 , C63 , C83 ,
23P
040412 - 7600585-01
7
T001057-A
T001058-A
T001055-A
T001795-A
T001059-A
1. Introduction
Calenta 25s - 28c - 35s - 40c
The labels are not guaranteed if the boiler is adapted to
G20 or G31.
HR 107 gas approval (High efficiency heating)
This means that the efficiency of the boiler when producing heating
water is 107% higher than the Gaskeur HR criterion in relation to
Hi. This means that the boiler is economical and therefore less costly
and more environmentally friendly.
HRww gas approval (High efficiency hot water)
This implies that the hot water/heating boiler produces hot water
economically and efficiently, without wasting energy or water
therefore.
CW 4 gas approval (Hot water comfort)
This means that, for the preparation of hot water, the Calenta 28c
satisfies application class 4. With the application of class 4, the
Calenta 28c is appropriate for:
4 A draw-off flow rate of at least 7,5 l/min at 60°C.
4 A shower function from 6 l/min up to at least 12,5 l/min at 40°C.
4 Filling a bathtub in less than 11 minutes with 120 litres of water at
40°C on average.
The simultaneity of these functions is not a requirement.
Parameters for which the performance of the Calenta 28c boiler
complies with the Hot Water Comfort classification:
4 Rotation speed on start-up 3000 rpm.
4 Maximum DHW rate 6200 rpm.
4 Energy-saving mode: Stop.
CW 5 gas approval (Hot water comfort)
This means that, for the preparation of hot water, the Calenta 40c
satisfies application class 5. With the application of class 5, the
Calenta 40c is appropriate for:
4 Hot water comfort.
4 A shower function from 6 l/min up to at least 12,5 l/min at 40°C.
4 Filling a bathtub in less than 10 minutes with 150 litres of water at
40 °C on average.
The simultaneity of these functions is not a requirement.
Parameters for which the performance of the Calenta 40c boiler
complies with the Hot Water Comfort classification:
4 Rotation speed on start-up 4000 rpm.
4 Maximum DHW rate 6800 rpm.
4 Energy-saving mode: Stop.
SV gas approval (Clean combustion)
8
040412 - 7600585-01
T001779-B
NZ
Calenta 25s - 28c - 35s - 40c
1. Introduction
This means that the boiler complies with the NOx Order and
provisions on clean combustion. The boiler has a gas/air coupling
combined with a fully premixed burner. For this reason, the emission
of NOx and CO is as low as possible.
NZ gas approval (Solar water heater reheating)
This implies that the hot water/heating boiler can operate on reheating
for solar water heaters. The label (solar water heater reheating) is
valid in combination with the connection kit for solar water heaters.
Owing to the possible formation of legionella, the boiler must not be
shut down or the DHW temperature set below 60°C.
1.4.2.Equipment categories
Gas category
II
, I
2L3P
2H
Gas typeConnection pressure (mbar)
G20 (Gas H)20
G25 (Gas L)25
G31 (Propane) 30/50
The boiler is preset in the factory to operate on natural gas G25 (Gas
L).
1.4.3.Additional Directives
Apart from the legal provisions and Directives, the additional
Directives described in these instructions must also be observed.
For all provisions and Directives referred to in these instructions, it is
agreed that all addenda or subsequent provisions will apply at the
time of installation.
1.4.4.Factory test
Before leaving the factory, each boiler is set for optimum performance
and tested to check the following items:
040412 - 7600585-01
4 Electrical safety
4 Adjustment (CO2)
4 Domestic hot water mode (Only on models with domestic hot water
production)
4 Water tightness
4 Gas tightness
4 Parameter settings
9
2. Safety instructions and recommendations
2Safety instructions and
recommendations
2.1Safety instructions
DANGER
If you smell gas:
1.Do not use a naked flame, do not smoke, do not
operate electrical contacts or switches ( doorbell,
light, motor, lift, etc..).
2.Shut off the gas supply.
3.Open the windows.
4.Trace possible leaks and seal them immediately.
5.If the gas leak is before the gas meter, contact the
gas supplier.
Calenta 25s - 28c - 35s - 40c
2.2Recommendations
DANGER
If you smell flue gases:
1.Switch the appliance off.
2.Open the windows.
3.Trace possible leaks and seal them immediately.
WARNING
4Installation and maintenance of the boiler must be
carried out by a qualified professional in compliance
with prevailing local and national regulations.
4When working on the boiler, always disconnect the
boiler from the mains and close the main gas inlet
valve.
4After maintenance or repair work, check all
installations to ensure that there are no leaks.
CAUTION
10
The boiler must be installed in a frost-free environment.
Keep this document close to the place where the boiler is
installed.
Only remove the casing for maintenance and repair operations. Put
the casing back in place after maintenance and repair operations.
Instructions stickers
The instructions and warnings affixed to the appliance must never be
removed or covered and must remain legible during the entire lifespan
of the appliance. Immediately replace damaged or illegible
instructions and warning stickers.
Modifications
Modifications may only be made to the boiler after the written
permission of Remeha to do so.
4 Calenta 25s - 35s: Heating only (Production of domestic hot water
can be ensured by a separate hot water calorifier).
4 Calenta 28c - 40c: Heating and domestic hot water production.
3.2Main parts
Calenta 25s - 28c
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Flue gas outlet
Casing/air box
Outlet for measuring combustion gases
Mixer pipe
Heating flow hose
Air intake silencer
Box for the control PCBs (accessory)
Combined venturi and gas valve unit
Flow end hydroblock
Safety valve outlet pipe
Siphon
Instrument box
Shunt pump
Return end hydroblock
Plate heat exchanger (DHW) (Only on models with
domestic hot water production)
12
16
17
18
19
20
21
3-way valve (Only on models with domestic hot water
production)
Condensate receiver tank
Fan
Heat exchanger (Central heating)
Ignition/ionization electrode
Air intake
040412 - 7600585-01
T002886-C
2
14
16
15
13
17
18
19
20
3
4
5
6
7
8
9
10
11
12
1 21
Calenta 25s - 28c - 35s - 40c
3. Technical description
Calenta 35s - 40c
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Flue gas outlet
Casing/air box
Outlet for measuring combustion gases
Mixer pipe
Heating flow hose
Air intake silencer
Box for the control PCBs (accessory)
Combined venturi and gas valve unit
Flow end hydroblock
Safety valve outlet pipe
Siphon
Instrument box
Shunt pump
Return end hydroblock
Plate heat exchanger (DHW) (Only on models with
domestic hot water production)
3-way valve (Only on models with domestic hot water
production)
3.3Operating principle
17
18
19
20
21
Condensate receiver tank
Fan
Heat exchanger (Central heating)
Ignition/ionization electrode
Air intake
3.3.1.Gas/air setting
The casing fitted to the boiler is also used as an air box. Air is sucked
in by the fan and gas injected into the venturi by the fan intake. The
fan rotation speed is set according to the settings parameters, the
thermal energy requirement and the temperatures measured by the
temperature sensors. The gas and air are mixed in the venturi. The
gas/air ratio ensures that the quantities of gas and air are adjusted to
each other. This provides optimum combustion on the entire output
range. The gas/air mixture is fed into the burner on top of the
exchanger.
040412 - 7600585-01
13
3. Technical description
Calenta 25s - 28c - 35s - 40c
3.3.2.Combustion
The burner heats the heating water circulating in the heat
exchanger. At a return temperature lower than around 55°C, the flue
gases cool down to a temperature lower than the dew point, thus
causing the condensation of the water vapour contained in the flue
gases in the back side of the heat exchanger. The heat released
during this condensation process (the latent heat or condensing heat)
is also transferred to the heating water. The cooled combustion gases
are evacuated via the combustion gas outlet flue. The condensation
water is evacuated via a siphon.
3.3.3.Heating and domestic hot water production
On heating and domestic hot water production type boilers, an
integrated plate exchanger heats the domestic water. A 3-way valve
determines whether the heated water is fed into the heating system
or the plate exchanger. A pick-up sensor signals that a hot water tap
is being opened. This signal is transmitted to the control panel, which
then switches the 3-way valve to the hot water position and trips the
heating pump. The 3-way valve is spring-loaded but only consumes
electricity when it switches to another position.
The heating water reheats the domestic water in the plate
exchanger. In comfort mode, if there is no hot water draw-off, the
boiler handles the periodic reheating of the plate exchanger. Any
limescale particles are kept out of the plate exchanger by a selfcleaning water filter (self-cleans once every 76 hours).
It is possible to connect a 2-wire on/off thermostat to the boiler such
as the Celcia 10 or a power stealing thermostat. The boiler output
can be modulated by an OpenTherm system with an appropriate
modulating thermostat such as the qSense or the iSense.
3.3.6.Regulation of the water temperature
The boiler is fitted with an electronic temperature regulator having an
outlet and return temperature probe. The flow temperature can be set
between 20°C and 90°C. The boiler reduces its power when the set
outlet-temperature is attained. The cutout temperature is the set
heating outlet-temperature + 5 °C.
3.3.7.Protection against a shortage of water
The boiler is fitted with a safety device to prevent the shortage of water
based on temperature measurements. By reducing its output when
the water flow rate is in danger of becoming insufficient, the boiler
continues to operate as long as possible. If the flow rate is too weak
ΔT ≥ 50°C or the heating flow temperature increases too much, the
boiler is locked for 10 minutes, code 5t[09. When there is no
water in the boiler or the pump is not running, the boiler goes into
safety shutdown, code e[10 at ΔT ≥ 70°C.
3.3.8.Maximum temperature protection
The overheating safety device locks the boiler when the water
temperature is too high (110°C), code e[12.
¼ For more detailed information, see chapter: "Error codes",
page 85
The boiler is equipped with a circulating pump. This energy-efficient,
modulating circulating pump is controlled by the control unit based on
ΔT. The graph shows the manometric height at various outputs.
Calenta 25s - 28c
H
Q
Manometric height central heating circuit
Water flow
040412 - 7600585-01
T001748-B
0 250 500 750 1000 1250
0
100
200
300
400
500
700
800
H (mbar)
Q (l/h)
600
20 kW
25 kW
30 kW
35 kW
835 1252 1038
1465
606
418
530
291
T001978-A
0
100
200
300
400
500
600
700
0500
1037437
1500100020002500
∆p [mbar]
Q [l/h]
623 830
∆T = 20K
10 kW
15 kW
20 kW
25 kW
T001749-B
0
100
200
300
400
500
600
0500
1043 1252 1465835
1500100020002500
∆p [mbar]
Q [l/h]
∆T = 20K
20 kW
25 kW
30 kW
35 kW
Calenta 25s - 28c - 35s - 40c
3. Technical description
Calenta 35s - 40c
H
Q
Manometric height central heating circuit
Water flow
Parameters p"8 and p"9 are used to modify the pump settings:
4 If there are audible flowing noises in the system, the maximum
pump speed must be lowered using parameter p"9 (First of all,
vent the heating system).
4 If there is insufficient flow in the radiators or if they do not warm
up completely, the minimum pump speed can be increased using
parameter p"8.
¼ See chapter: "Modification of the installer-level parameters",
page 67.
3.3.11.Water flow rate
The boiler's modulating control system limits the maximum difference
in temperature between the heating flow and return and the maximum
speed at which the flow temperature increases. In this way, the boiler
does not require a minimum water flow rate.
¼ If using thermostatic valves, see chapter: "Hydraulic
connections", page 29.
Heating efficiency under full
load (Hi) (80/60 °C)
Heating efficiency under full
load (Hi) (50/30 °C)
minimummaximum
Factory settingkW24,119,434,023,3
minimummaximum
Factory settingkW25,520,535,924,5
minimummaximum
Factory settingkW-28,6-39,7
minimummaximum
Factory settingkW25,020,135,124,0
minimummaximum
Factory settingkW27,822,339,026,7
minimummaximum
Factory settingkW-28,0-38,8
minimummaximum
Factory settingkW-31,1-43,1
-%96,396,396,996,9
-%102,0102,0102,2102,2
kW5,0 - 24,15,0 - 24,16,3 - 34,06,3 - 34,0
kW5,6 - 25,55,6 - 25,57,0 - 35,97,0 - 35,9
kW-5,0 - 28,6-6,3 - 39,7
kW5,2 - 25,05,2 - 25,06,5 - 35,16,5 - 35,1
kW5,8 - 27,85,8 - 27,87,2 - 39,07,2 - 39,0
kW-5,2 - 28,0-6,5 - 38,8
kW-5,8 - 31,1-7,2 - 43,1
Modulating, Start/Stop, 0 - 10 V
0063BT3444
Heating efficiency under
partial load (Hi) (Return
-%96,196,196,396,3
temperature 60°C)
Heating efficiency under
partial load (EN 92/42)
-%108,0108,0108,2108,2
(Return temperature 30°C)
Data on the gases and combustion gases
Gas categories
Gas inlet pressure G20 (GasH)minimum-
-I
2L3P
and I
mbar17 - 30
2H
maximum
Gas inlet pressure G25 (GasL)minimum-
mbar20 - 30
maximum
Gas inlet pressure G31
(Propane)
Gas consumption G20 (GasH)minimum-
minimummaximum
mbar30 - 50
m3/h
0,55 - 2,650,55 - 2,960,69 - 3,710,69 - 4,11
maximum
Gas consumption G25 (GasL)minimum-
m3/h
0,64 - 3,080,64 - 3,450,80 - 4,320,80 - 4,78
maximum
Gas consumption G31
(Propane)
NOx-Emission per year (n =1)
Mass flue gas flow rateminimum-
minimummaximum
m3/h
mg/kWh3838
0,21 - 1,020,21 - 1,150,27 - 1,440,27 - 1,59
4242
kg/h8,9 - 42,18,9 - 47,111,1 - 57,311,1 - 63,9
maximum
(1) Time needed as of the start of water draw-off to obtain an increase in temperature of 40K at the appliance's water outlet for the purposes of
installation calculation, based on the draw-off flow rate CW.
(2) The specific length of the pipe Ø 10/12 mm is the maximum uninsulated length, on the understanding that, in the most unfavourable summer
situation, the appliance will supply hot water in less than 30 s with a permanent increase in temperature of 35 ºC at the draw-off point in the
kitchen.
(3) Front panel removed
Manometric height central
heating circuit (ΔT = 20K)
Characteristics of the domestic hot water circuit
CW gas approval
Specific hot water flow D
(60 °C)
Specific hot water flow D
(40 °C)
Domestic water resistance
Flow rate thresholdminimuml/min-1,2-1,2
Actual appliance waiting
(1)
time
Specific pipe length
Annual operational efficiency
for domestic water
Water content
Operating pressure (Pmw)maximumbar-8-8
Electrical characteristics
Power supply voltage
Power consumption - Full
load
Power consumption - Part
load
Power consumption Standby
Electrical protection index
Other characteristics
Weight (empty)
Acoustic level at 1 metre
(1) Time needed as of the start of water draw-off to obtain an increase in temperature of 40K at the appliance's water outlet for the purposes of
installation calculation, based on the draw-off flow rate CW.
(2) The specific length of the pipe Ø 10/12 mm is the maximum uninsulated length, on the understanding that, in the most unfavourable summer
situation, the appliance will supply hot water in less than 30 s with a permanent increase in temperature of 35 ºC at the draw-off point in the
kitchen.
(3) Front panel removed
(2)
maximumbar3,0
without iSense%-90,6-92,3
with iSense%-91,4-93,8
maximumW116124129139
Factory settingW72729292
maximumW21212222
maximumW4
Totalkg30313233
Mounting
(3)
°C30 - 8030 - 8530 - 7530 - 80
Pa120130140160
l1,71,72,32,3
mbar295295291291
--4-5
l/min-8,2-11,1
l/min-13,7-19,5
mbar-490-810
s-5,15-5,18
m-23,86-23,83
l-0,33-0,49
VAC230
IPX4D
kg27282930
dB(A)42444547
25s28c35s40c
040412 - 7600585-01
19
4. Installation
4Installation
4.1Regulations governing installation
WARNING
Installation of the appliance must be done by a qualified
engineer in accordance with prevailing local and national
regulations.
Installation must also respect the following points:
4 This instruction manual and any other applicable documentation
4 NEN 1006: The general provisions for drinking water installations
(AVWI)
4 NEN 1010: The provisions on safety for low voltage installations
4 NEN 1078: Gas device with an operating pressure of up to 500
mbar - performance requirements - new construction
4 NPR 3378: Guide on NEN 1078
4 NEN 1087: Ventilation of residential buildings
4 NPR 1088: Explanatory instructions on NEN 1087
4 NEN 2078: Requirements applicable to industrial gas installations
4 NEN 2757: Combustive air supply and flue gas discharge for
combustion appliances
4 NEN 3028: Requirements applicable to incineration installations
4 NEN 3215: Drainage systems inside residences and residential
buildings
4 NEN 8078: Gas device with operating pressure of up to 500 mbar
- performance requirements - existing construction
4 Building Regulations
4 Local provisions from the fire brigade, public service companies
and the municipality
4 In the event of application of domestic hot water supply equipment.
Work data sheet Drinking water installations, VEWIN nr. 4.4 B
Calenta 25s - 28c - 35s - 40c
4.2Package list
20
4.2.1.Standard delivery
The delivery includes:
4 The boiler, fitted with an earthed mains plug
4 Mounting rail and mounting accessories for wall mounting
4 Mounting template
4 Connection kit comprising sleeves and clamping rings
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c4. Installation
4 Run-off collector for siphon and safety valve
4 Installation and Service Manual
4 Sticker: This boiler has been set for...
4 User Guide
4 Warranty card
4 Maintenance log
These installation and maintenance instructions deal only with the
items included in a standard delivery. For the installation or mounting
of any accessories supplied with the boiler, a rail or mounting frame,
for example, refer to the mounting instructions delivered with the
accessories in question.
The boiler is also available with a modular adjustment
device, such as the Combi Comfort system. In this case,
the iSense adjustment device is delivered with the
appliance.
4.2.2.Accessories
Various options are available depending on the configuration of the
installation:
Description
Mounting frame
Mounting frame connection kit, comprising stop valves, safety unit and
pressure gauge
Supporting device for feeding pipes behind the appliance
Pipe kit for connections behind the appliance (in combination with the
supporting device)
Protective cover for the connections
Propane conversion kit
Remeha Celcia 10 on/off thermostat
Remeha qSense basic modulating control system
Remeha iSense extended modulating control system
Remeha iSense integration kit
Outside temperature sensor
Passing through walls Type C1
Combustion air/flue gas adapter 80/125 mm
Combustion air/flue gas adapter 60/100 mm
Kit for connection to the water heater
DHW sensor
Kit for connection to the solar water heater
0-10V (IF-01) control PCB
Extended control PCB (SCU-S02)
Box for the control PCBs
Connection set for coupling to the heat recycling system
Cleaning accessories for the heat exchanger (central heating)
Cleaning kit for the plate heat exchanger (DHW)
Maintenance box
Recom communication kit
Installation kit for the water / gas connection if replacing Remeha Quinta
boilers
040412 - 7600585-01
21
T001539-B
T001531-A
450
min.1000
395
min.
250
min.
250
690
4. InstallationCalenta 25s - 28c - 35s - 40c
4.3Choice of the location
4.3.1.Data plate
The data plate located on top of the boiler provides important
information on the appliance: serial number, model, gas category, etc.
4.3.2.Location of the boiler
4 Before mounting the boiler, decide on the ideal position for
mounting, bearing the Directives and the dimensions of the
appliance in mind.
4 When choosing the position for mounting the boiler, bear in mind
the authorised position of the combustion gas discharge outlets
and the air intake opening.
4 To ensure adequate accessibility to the appliance and facilitate
maintenance, leave enough space around the boiler.
WARNING
4Fix the appliance to a solid wall capable of bearing
the weight of the appliance when full of water and fully
equipped.
4It is forbidden to store inflammable products and
materials in the boiler room or close to the boiler,
even temporarily.
CAUTION
4The boiler must be installed in a frost-free
environment.
4An earthed wall socket must be available close to the
boiler.
4A connection to the mains drainage system for the
discharge of condensate must be available close to
the boiler.
22
040412 - 7600585-01
T000756-A
Z
OZ
1
0
B
23
60
225
240
T001532-A
min. 550
min.495
min. 250
50 (2)
min. 250
100
min. (1)
Calenta 25s - 28c - 35s - 40c4. Installation
Safety rating
n
B
Z
OZ
Bathtub or shower tray
Zones
Breakdown of the exterior zone
For safety rating IP X4D, installation in the bathroom is possible in
zones 2 and 3 and in the breakdown of the exterior zone.
4 In this case, connect the 230V power supply as a fixed connection.
4 Also in this case, connect an air intake pipe.
CAUTION
In the case of a fixed connection to the power cord, you
must always install a main bipolar switch with an opening
gap of at least 3 mm (EN 60335-1).
4.3.3.Ventilation
(1)
(2)
Distance between the front of the boiler and the internal
wall of the casing box.
Distance to allow on either side of the boiler.
If the boiler is installed in a closed casing, respect the minimum
dimensions given in the diagram opposite. Also allow openings to
obviate the following hazards:
4 Accumulation of gas
4 Heating of the box
Minimum cross section of the openings: S1 + S2 = 150 cm
2
040412 - 7600585-01
23
T000754-C
67
195
265
132
199
266
331
690
450
395
225
120
140
140
150
257,5
67
195
265
132
199
266
331
690
450
395
225
120
140
140
150
257,5
4. InstallationCalenta 25s - 28c - 35s - 40c
4.3.4.Main dimensions
i
h
ê
j
z
x
Gas /
Gaz
Connection of the combustion gas exhaust pipe; Ø 80 mm
Connection of the air intake pipe; Ø 80 mm
Safety valve outlet pipe; Ø 25 mm
Condensates discharge; Ø 25 mm
Heating circuit return; Clamping Ø 22 mm
Domestic cold water inlet; Clamping Ø 15 mm
Gas connection; Clamping Ø 15 mm
24
y
{
Domestic hot water outlet; Clamping Ø 15 mm
Heating circuit flow; Clamping Ø 22 mm
040412 - 7600585-01
T001540-A
2
1
5
4
3
Calenta 25s - 28c - 35s - 40c4. Installation
4.4Positioning the boiler
The boiler is delivered with a mounting template.
A suspension clamp situated at the rear of the casing enables the
boiler to be directly suspended on the mounting bracket.
1. Position the mounting template to the wall with adhesive tape.
CAUTION
4Using a spirit level, check that the mounting axis is
perfectly horizontal.
4During mounting, cover up the connection points for
the air supply and the combustion gas exhaust, to
protect the boiler and its connections from dust. Only
remove this protection at the time when these
connections are made.
2. Drill 2 holes with a Ø of 10 mm.
Additional holes are provided in case one or other of the
standard locating holes prevents the correct location of the
plugs.
3. Insert the rawplugs with a Ø of 10 mm.
4. Attach the mounting bracket to the wall with the provided bolts with
a Ø of 10 mm.
5. Hang the boiler on the mounting bracket.
The relevant assembly instruction describes how to hang
the mounting frame (accessory).
040412 - 7600585-01
25
T001535-C
1
2
3
7
5
6
4
T001534-C
1
2
3
4
5
8
6
7
4. InstallationCalenta 25s - 28c - 35s - 40c
4.5Alternatives for hydraulic connections
4.5.1.Connection of the underfloor heating
1
2
3
4
5
6
7
Boiler
Expansion vessel
Stopcock
Regulator valve
Filling/drainage valve
Underfloor heating
Heating by radiators
The boiler can be connected directly to an underfloor heating circuit.
If using plastic ducting (for the underfloor heating for example), the
plastic tubes must be totally oxygen-tight according to standard DIN
4726/4729. If the synthetic ducting used in the installation does not
conform to these standards, it is advisable to hydraulically separate
the boiler circuit from the central heating circuit by installing a plate
heat exchanger.
Parameters p"8 and p"9 are used to modify the
pump settings.
4.5.2.Connection of a solar hot water tank
1
2
3
4
5
6
7
8
Boilers, of the heating and domestic hot water production type, are
Boiler
Tank
Solar collector
Pump
Flow limiter
Safety unit
Mixer valve
Solar DHW sensor SCU-S02
suitable for reheating downstream from solar DHW tanks. A kit
(accessory) is available for the connection.
See the solar domestic hot water tank's technical notes for
more information concerning hydraulic connections.
26
040412 - 7600585-01
T004865-A
1
2
4
6
7
M
3
5
8
Calenta 25s - 28c - 35s - 40c4. Installation
4.5.3.Connection of an independent hot water
tank
The standard version of the heating-only type of boiler is fitted with a
command for regulation of the hot water tank circuit. The command
is adjusted to switch preferentially to the hot water tank circuit. This
gives priority to the hot water tank when simultaneous requests for
heat come from the hot water tank and the central heating. The
indirectly heated calorifier can be connected using an internal or
external three-way valve.
Internal three-way valve
1
2
3
4
5
6
7
8
Boiler
Independent hot water tank
DHW sensor
Air vent kit of the hot water tank
Safety unit
Expansion vessel
Heating-Installation
3-way valve
The boiler connection kit must be used to install the three-way valve
in the boiler (Accessory). The three-way valve (230 V) is controlled
by the boiler control unit of the boiler.
¼ For the installation or mounting of any accessories, refer to the
mounting instructions delivered with the accessories in question.
4
A safety unit is installed at the point where cold water
arrives at the hot water tank to prevent backflow or
overpressure.
4The central heating pipes for the boiler circuit must be
in Ø 22 mm (From Ø 15 mm to Ø 22 mm at the boiler
itself).
040412 - 7600585-01
27
T001537-C
1
2
4
8
6
7
M
3
5
9
T001536-B
1
2
3
4. InstallationCalenta 25s - 28c - 35s - 40c
External three-way valve
1
2
3
4
5
6
7
8
9
Boiler
Independent hot water tank
DHW sensor
Air vent kit of the hot water tank
Safety unit
Expansion vessel
Heating-Installation
3-way valve
SCU-X02 control PCB
Control SCU-X02 must be used to install the three-way valve outside
of the boiler (Accessory). The three-way valve 24 V/230 V is
controlled by control SCU-X02. The control must be installed in the
electronics expansion kit (Accessory).
¼ For the installation or mounting of any accessories, refer to the
mounting instructions delivered with the accessories in question.
4In order to prevent an uncontrolled flow in the heating
circuit, the return channel to the hot water tank must
always be connected directly to the return channel to
the boiler and therefore never directly connected to
the heating installation.
4A safety unit is installed at the point where cold water
arrives at the hot water tank to prevent backflow or
overpressure.
4.5.4.Geyser use
1
2
3
The combi boiler can also be used solely for DHW operation. The
boiler can then function as a geyser. The central heating function has
to be switched off for this purpose, using parameter p3.
Boiler
Filling/drainage valve
Expansion vessel
The flow and return connections of the unit have to be
connected.
28
040412 - 7600585-01
T001958-A
1
2
3
5
4
Calenta 25s - 28c - 35s - 40c4. Installation
4.5.5.Solo use
4.6Hydraulic connections
1
2
3
4
5
Boiler
Expansion vessel
Stopcock
Filling/drainage valve
Heating by radiators
The combi boiler can also be used solely for central heating
operation. The hot water function has to be switched off for this
purpose, using parameter p3.
The sanitary pipes do not have to be connected or capped
off. The dust caps supplied are sufficient.
4.6.1.Flushing the system
Installing the boiler in new installations (installations less than
6 months old)
4 Clean the installation with a universal cleaner to eliminate debris
from the appliance (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
Installing the boiler in existing installations
4 Remove sludge from the installation.
4 Flush the installation.
4 Clean the installation with a universal cleaner to eliminate debris
from the appliance (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
040412 - 7600585-01
29
T001573-C
T001570-B
T001633-B
4. Installation
Calenta 25s - 28c - 35s - 40c
4.6.2.Connection of the heating circuit
1. Remove the anti-dust plug located on the heating outlet
connection { under the boiler.
2. Connect the heating water outlet pipe to the heating flow
connection.
3. Install a filling and drainage valve on the installation for filling and
draining the boiler.
4. Remove the anti-dust plug located on the heating return
connection z under the boiler.
5. Connect the heating water return pipe to the heating return
connection.
4The boiler is factory fitted with a safety valve mounted
on the left hydroblock.
4To facilitate maintenance work, we recommend
mounting a shut off valve on the heating flow and
return pipes.
CAUTION
4The heating pipe must be mounted in accordance
with prevailing provisions.
4If installing shut off valves, position the filling/
drainage valve and the expansion vessel between
the shut off valves and the boiler.
¼ If using thermostatic valves, see chapter: "Connecting the
expansion vessel", page 31
30
040412 - 7600585-01
T001572-B
T001571-C
Calenta 25s - 28c - 35s - 40c4. Installation
4.6.3.Hydraulic connection of the water circuit
for domestic use
1. Remove the anti-dust plug located on the domestic cold water
connection x under the boiler.
2. Remove the anti-dust plug located on the domestic hot water
connection y under the boiler.
3. Connect the cold water inlet pipe to the domestic cold water
connection. Install a safety unit labelled KIWA on this pipe directly
under the boiler.
4. Place a tube, connected to the drains, underneath the safety unit
for water from expansion.
5. Connect the domestic hot water outlet pipe to the domestic hot
water connection.
CAUTION
4The domestic water pipes must be connected in
accordance with prevailing provisions.
4If using synthetic pipes, follow the manufacturer's
(connection) instructions.
4.6.4.Connecting the expansion vessel
Install the expansion vessel on the heating return pipe z.
If using a heating and domestic hot water production type
boiler on an installation in which the flow can be fully
disconnected from the return (e.g. by using thermostatic
valves), you should either fit a bypass or fit an expansion
vessel to the heating flow conduit.
4.6.5.Connecting the condensate discharge pipe
1. Mount a standard drainage pipe, Ø 32 mm or more, leading to the
mains drainage system.
2. Into this, insert the condensate collector hose coming from the
siphon j and the safety valve ê.
3. Mount a trap or a siphon in the discharge pipe.
CAUTION
Do not make a fixed connection owing to maintenance
work on the siphon.
040412 - 7600585-01
4Do not plug the condensate discharge pipe.
4Set the discharge pipe at a gradient of at least 30 mm
per metre, maximum horizontal length 5 metres.
4Do not drain condensation water into a roof gutter at
any time.
4Connect the condensate discharge pipe in
accordance with prevailing standards.
31
T001575-B
4. InstallationCalenta 25s - 28c - 35s - 40c
4.7Gas connection
1. Remove the anti-dust plug located on the gas connection GAS/
GAZ under the boiler.
2. Connect the gas inlet pipe.
3. Mount a gas isolation valve on this pipe, directly under the boiler.
4. Connect the gas pipe to the gas shut off valve.
WARNING
4Close the main gas valve before starting work on the
gas pipes.
4Before mounting, check that the gas meter has
sufficient capacity. To do this, you should keep in
mind the consumption of all domestic appliances.
4If the gas meter has too low a capacity, inform the
energy supply company.
CAUTION
4Ensure that there is no dust in the gas pipe. Blow into
the pipe or shake it before mounting.
4We recommend installing a gas filter on the gas pipe
to prevent clogging of the gas valve unit.
4Connect the gas pipe in accordance with prevailing
standards and regulations.
4.8Connections for the air and exhaust pipes
¼ The boiler is suitable for the following types of flue
gas connections. See chapter: "Certifications", page 7
4.8.1.Classification
The table specifies this classification in detail according to [.
Type
B23
B23P
B33Open
C13Closed
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
ExecutionDescription
Open
(1)
4Without fire-stop approval.
4Exhaust of combustion gases above the roof.
4Air in the installation room.
4Without fire-stop approval.
4Common exhaust of combustion gases above the roof.
4Common exhaust of combustion gases mixed in the air, air in the installation room (special
4Vent in the outside wall.
4The opening for the air-supply inlet is located in the same pressure zone as the vent (For
construction).
example, a common passage through the outside wall).
32
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
TypeExecutionDescription
C33Closed
(2)
C43
C53Closed
C63Closed
C83
C93
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
Closed/Cascade
(3)
Closed
(4)
Closed
4Exhaust of combustion gases above the roof.
4The opening for the air-supply inlet is located in the same pressure zone as the vent (For
example, a concentric passage to the roof).
4Common channelling for the air-supply and exhaust of combustion gases (CLV):
-Concentric.
-Eccentric; Air supply from the shaft.
4This also relates to the overpressure cascades.
4Closed equipment.
4Separate channelling for the air-supply.
4Separate channelling for the combustion gases.
4Terminating on different pressure surfaces.
4The manufacturer delivers this type of equipment without a supply or exhaust system.
4The equipment can be connected on a so-called semi-CLV system (with common combustion
gas exhaust).
4Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
-Concentric.
-Eccentric; Air supply from the shaft.
-Exhaust of combustion gases above the roof.
-The opening for the air-supply inlet is located in the same pressure zone as the vent.
4. Installation
Type Execution DiameterMinimum size of the duct or jacket.
Without air-supplyWith air-supply
∅ Channel Channel∅ Channel Channel
C93Rigid60 mm110 mm110 x 110 mm120 mm110 x 110 mm
80 mm130 mm130 x 130 mm140 mm130 x 130 mm
100 mm160 mm160 x 160 mm170 mm160 x 160 mm
Flexible60 mm110 mm110 x 110 mm120 mm110 x 110 mm
80 mm130 mm130 x 130 mm145 mm130 x 130 mm
100 mm160 mm160 x 160 mm170 mm160 x 160 mm
Concentric60/100 mm120 mm120 x 120 mm120 mm120 x 120 mm
80/125 mm145 mm145 x 145 mm145 mm145 x 145 mm
100/150 mm170 mm170 x 170 mm170 mm170 x 170 mm
4.8.2.Outlets
in general, it is possible to use a standard kit for passage via the roof
or outside wall. In the case of such passage via the outside wall
directly above the boiler, use the Remeha kit for passage via an
outside wall. This is available as an accessory.
For exhausting combustion gases of types C1, C3 and C5, it is
appropriate to use a M&G Skyline / Mugro 3000 or a Coxstand EHR. When exhausting combustion gases of type C6, the material of
the exhaust must conform with Gastec QA and/or be provided with
CE marking.
040412 - 7600585-01
The exhaust vent for combustion gases must conform to EN
1856-1. The flue gas pipes must be calculated conforming to EN
13384 (parts 1 & 2).
33
T000765-B
L
4. InstallationCalenta 25s - 28c - 35s - 40c
For open exhaust of combustion gases above the roof, the
vent must always be provided with a suitable stainless steel
wire grill.
4.8.3.Lengths of the air/flue gas pipes
4To define the maximum final length, you must deduct
the pipe length in accordance with the reduction table.
4The boiler is also suitable for longer chimney lengths
with diameters other than those indicated in the
table. Please contact us for further information.
Open flue (B23, B23P, B33)
n
If using an open flue version, the air supply opening remains open;
only the combustion gas opening is connected. The boiler then takes
in the combustion air required directly from the premises in which it
is installed. For the application of air discharge and combustion gas
discharge piping with a diameter other than 80 mm, a reducer should
be used.
CAUTION
4The air supply opening must remain open.
4The premises in which the appliance is installed must
be fitted with the necessary air supply openings.
They must not be reduced or closed.
Chimney length for the open flue version
SituationDiameter
60 mm19 m16 m11 m10 m
Free vent in zone I
Restricted vent in
zone III
Countryside (ΔP
static = + 25 Pa)
Restricted vent in
zone III Near the
coast (ΔP static =
+ 40 Pa)
70 mm35 m30 m21 m19 m
80 mm40 m40 m40 m40 m
90 mm40 m40 m40 m40 m
60 mm15 m13 m9 m9 m
70 mm28 m24 m17 m16 m
80 mm40 m40 m40 m39 m
90 mm40 m40 m40 m40 m
60 mm12 m11 m8 m8 m
70 mm23 m21 m14 m14 m
80 mm40 m40 m35 m35 m
90 mm40 m40 m40 m40 m
Calenta
25s
Maximum length (L)
Calenta
28c
Calenta
35s
Calenta
40c
34
040412 - 7600585-01
T000766-B
L
T000780-C
L
Calenta 25s - 28c - 35s - 40c4. Installation
Room sealed flue (C13, C33, C43, C63, C93)
n
If using a room sealed version, it is necessary to connect both the
combustion gas exhaust and the air-supply opening (parallel). For the
application of air discharge and combustion gas discharge piping with
a diameter other than 80 mm, a reducer should be used.
Chimney length for room sealed operation
Maximum length (L)
SituationDiameter
Free vent in
zone I or
Restricted vent
in zone III
60-60 mm7 m5 m--
70-70 mm18 m15 m9 m8 m
80-80 mm20 m20 m20 m19 m
90-90 mm20 m20 m20 m20 m
Calenta
25s
Calenta
28c
Calenta
35s
Calenta
40c
Connection in areas of different pressure (C53, C83)
n
Combustion air supply and combustion gas discharge are possible in
various pressure zones, semi-CLV systems. With the exception of
coastal areas. The maximum permissible difference in height
between the combustion air supply and the combustion gas discharge
is 36 m.
Chimney length in the various pressure zones
Maximum length (L)
SituationDiameter
70 mm13 m13 m5 m5 m
Free vent in
zone I
Reduction table
n
Pipe reductions per element used
Diameter
60 mm0,9 m3,1 m
70 mm1,1 m3,5 m
80 mm1,2 m4,0 m
90 mm1,3 m4,5 m
100 mm1,4 m4,9 m
80 mm36 m36 m24 m23 m
90 mm36 m36 m36 m36 m
100 mm30 m36 m36 m36 m
Elbow 45°Elbow 90°
Pipe reduction Pipe reduction
Calenta
25s
Calenta
28c
Calenta
35s
Calenta
40c
040412 - 7600585-01
35
4. Installation
Calenta 25s - 28c - 35s - 40c
4.8.4.Specific air/flue gas applications
If the boiler has been modified, for example:
4high pressure systems
4WTW coupling
4CLV overpressure (combusted gas discharge
systems)
It is necessary to mention on the sticker provided: This
boiler has been set for.... This sticker must be affixed to the
top of the boiler next to the identification plate.
4Please contact us for further information.
high pressure systems
n
Flue gas discharge hoses with smaller diameters are available
commercially for use with the boiler, these hoses are specifically for
renovations where the existing flue gas discharge duct is not suitable
for condensing flue gases.. Some boiler settings must be changed for
this application of the boiler.
This is described in detail in the flue gas discharge systems
practical manual Calenta.
WTW coupling
n
The boiler has been prepared for use in conjunction with a Itho
HRU heat exchanger unit. Some boiler settings must be changed for
this application of the boiler. Full details are provided with the special
connection kit (accessory component).
Always use the heat exchanger connection kit when using
the heat exchanger coupling.
CLV overpressure (combusted gas discharge systems)
n
Under certain conditions, the boiler can be used in a CLV
overpressure system. Some boiler settings must be changed for this
application of the boiler. The setting can be modified using
parameters p19 and p"0.
¼ See chapter: "Changing the settings", page 64
36
4.8.5.Additional Directives
4 Please refer to the manufacturer's instructions for the material in
question when installing the flue gas discharge and air supply
materials. If the flue gas discharge and air supply materials are not
installed according to the instructions (e.g. they are not leakproof,
not clamped in place etc.), this may cause hazardous situations
and/or result in bodily injury. After assembly, check at least all flue
gas and air–carrying parts for tightness.
040412 - 7600585-01
T001972-A
Calenta 25s - 28c - 35s - 40c4. Installation
4 Connection of the combustion gas exhaust directly to the buildings
brick chimneys or flues is forbidden for condensation reasons.
4 If flues or chimneys are to be used, they must have an airtight
construction with thick walls and be made from rigid aluminium or
stainless steel. Flexible supply flue pipes made from plastic or
stainless steel are also permissible. Aluminium is permissible only
if there is no contact between the building supply section and the
combustion gas exhaust pipe.
4 Always clean the ducts thoroughly in cases where lining pipes are
used and/or a connection of the air-supply.
It must be possible to inspect the flue or chimney.
4
4 In cases where condensate coming from the stainless steel or
plastic sections of the flue gas pipe can be driven back towards
the aluminium section, this condensate must be removed using a
collecting device before the aluminium section is reached
(conforming with NPR 3378).
4 For long, aluminium, combustion-gas exhaust pipes it is initially
necessary to consider the relatively high quantity of corrosive
products which are brought together with the condensate from the
exhaust pipe. The siphon on the equipment requires regular
cleaning or, preferably, an additional condensate collector can be
installed above the equipment.
4 The combusted gas discharge pipe must be sufficiently inclined
towards the boiler (at least 50 mm per metre) and an adequate
condensate collection tank and discharge system constructed (at
least 1 m before the boiler opening). The elbows fitted must be at
more than 90° to guarantee the provision of an adequate gradient
and tightness on the lip rings.
Please contact us for further information.
4.8.6.Air/Exhaust adapter
The boiler is factory fitted with a two pipe connection. During
installation, the room ventilated or room sealed version can be
selected. Where needed, the outlet of the combustion gas / air supply
can be turned through 180º. The air supply will then be located to the
left of the combustion gas outlet and not to the right.
040412 - 7600585-01
37
T001512-A
80mm
S
T001513-A
80mm
S
4. InstallationCalenta 25s - 28c - 35s - 40c
4.8.7.Connection of the combustion gas exhaust
pipe
S
Insertion depth 3 cm
Mounting
1. Fit the combustion product discharge conduit.
2. Fit together the combustion gas exhaust pipes, without welding.
4The pipes must allow no leakage of flue gases and be
resistant to corrosion.
4Connect the pipes together without stress between
the sections.
4The horizontal sections need to be constructed with a
gradient of 50 mm per metre: Boiler orientation.
Material
Thick aluminium wallApproval according to EN-1856-1
Stainless steelApproval according to EN-1856-1
A rigid wall
Flexible
(1) The sealing must conform with pressure class 1
(1)
Synthetic material T120 Approval according to Gastec
QA or KOMO
Stainless steelApproval according to EN-1856-1
(1)
Synthetic material T120 Approval according to Gastec
QA or KOMO
4.8.8.Connection of the air intake pipe
S
Mounting
1. Fit the air-intake conduit.
2. Fit the air-intake conduits together without welding.
Material
A rigid wall
Flexible
Insertion depth 3 cm
The pipes must allow no leakage of flue gases and be
4
resistant to corrosion.
4Connect the pipes together without stress between
the sections.
4The horizontal sections need to be constructed with a
gradient: Downwards in the direction of the supply
opening.
aluminium/Stainless steel/Synthetic material
38
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
4.9Electrical connections
4. Installation
4.9.1.Control unit
The boiler is not line- and neutral sensitive. The boiler is fully prewired. All external connections can be made on the connection
connector (low voltage). The main characteristics of the control unit
are described in the table below.
Power supply voltage230 VAC/50Hz
Rating of the main fuse F1 (230 VAC) 6.3 AT
Fuse rating F2 (230 VAC)2 AT
Fan-DC27 VDC
CAUTION
The following boiler components are at a voltage of
230V:
4Electrical connection of the heating pump (Central
heating) (if used).
4Electrical connection of the combined gas valve unit.
4Electrical connection of the 3-way valve (if used).
4The majority of components in the control panel.
4Ignition transformer.
4Connection of the power supply cable.
The boiler is fitted with an earthed plug (cable length 1,5 m) suitable
for a 230VAC/50Hz power supply with live/neutral/earth system. The
power supply cable is connected to the X1 connector. A spare fuse
can be found in the housing of the control system.
CAUTION
4When the power supply cable has to be replaced, it
must be ordered from Remeha.
4The boiler plug must be accessible at all times.
It is possible to connect various control, safety and regulation systems
to the boiler. The standard control PCB (PCU) can be extended with
the following, for example:
4 The 0-10V control PCB (accessory IF-01). For installation behind
the left hand cover on the control panel.
4 The extended control PCB (accessory SCU-S02). For installation
in a box (accessory).
¼ For the optional PCBs, see chapter: "Optional electrical
connections", page 46
040412 - 7600585-01
39
4. InstallationCalenta 25s - 28c - 35s - 40c
4.9.2.Recommendations
WARNING
4Only qualified professionnals may carry out electrical
connections, always with the power off.
4The boiler is entirely pre-wired. Do not modify the
connections inside the control panel.
4Earth the appliance before making any electrical
connections.
Make the electrical connections of the boiler according to:
4 The instructions of the prevailing standards.
4 The instructions on the electrical diagrams provided with the
boiler.
4 The recommendations in the instructions.
CAUTION
Separate the sensor cables from the 230 V cables.
40
040412 - 7600585-01
R000073-A
OT
On/
off
Tout
T
dh
w
BL
RL
X13
X12
7
4
4
33
3
1
90º
1
Calenta 25s - 28c - 35s - 40c4. Installation
4.9.3.Standard control PCB
Various thermostats and controllers can be connected to the standard
control PCB (PCU) (X12 connector block). The possible connections
on the standard control PCB are described in the following
paragraphs.
Access to the connector block:
1. Unscrew the two screws located under the front panel by a quarter
turn and remove the panel.
2. Thread the cables from the regulator or thermostat through the
right-hand grommet(s) on the lower plate of the boiler.
3. Tilt the control box forwards by opening the holding clips located
at the sides.
4. Open the tooling box by opening the clip fastener on the front side.
5. Run the connection cable(s) through the grommet(s) in the control
unit box.
6. Unscrew the necessary cable clamps (to access the connector
block) and introduce the cables.
7. Connect the cables to the appropriate terminals on the connector
block.
8. Firmly retighten the cable clamps and close the control panel.
040412 - 7600585-01
41
T000776-D
On/off
OT BL RL Tou t Tdhw
OT
On/off
Tou
t
Tdhw
BL
RL
OT
T001590-B
Tk
OT
On/off
Tou
t
Tdhw
BL
RL
On/off
OT BL RL Tou t Tdhw
4. InstallationCalenta 25s - 28c - 35s - 40c
4.9.4.Connecting the room thermostat
Connecting modulating controller
n
OT
OpenTherm regulator
The boiler is fitted with a OpenTherm connection as standard.
As a result, modulating OpenTherm room controllers can be
connected without any further adjustments. The boiler is also suitable
for OpenTherm Smart Power.
4 Install the regulator in the reference room (generally the living
room).
4 Connect the two-wire cable to terminals On/off-OT of the
connector.
If the tap water temperature can be set on the
OpenTherm controller, then the boiler supplies this
temperature, with the set value on the boiler as the
maximum.
Connect on/off thermostat
n
Tk
ON/OFF room thermostat
The boiler is suitable for connection to a 2 wire on/off room thermostat.
4 Install the regulator in the reference room (generally the living
room).
4 Connect the 2 wire 24V room thermostat to the On/off-OT
terminals of the connector.
4 Connect the power stealing thermostat to the On/off-OT terminals
of the connector.
If a room thermostat with an anticipation element is used,
this must be converted using parameter p5.
42
040412 - 7600585-01
T001591-B
Ba
OT
On/off
Tout
Tdhw
BL
RL
On/off
OT BL RL Tou t Tdhw
R000038-A
01020
-20
-10
10
30
70
50
90
F
T000778-C
On/off
OTRLBLTou tTdhw
TkTv
Calenta 25s - 28c - 35s - 40c4. Installation
4.9.5.Connecting the outside temperature
sensor
Ba
Outside sensor
An outside sensor can be connected to the Tout terminals of the
connector. Where there is an on/off thermostat controller, the boiler
will control the temperature with the set point of the internal heating
curve.
A OpenTherm controller can also use this outside sensor.
The heating curve required must then be set on the
controller.
Heating curve setting
n
If an outside temperature sensor is connected, it is possible to adapt
the heating curve. The setting can be modified using parameters
p1, p"5, p"6 and p"7.
040412 - 7600585-01
4.9.6.Connect frost protection
Frost protection in combination with on/off thermostat
n
If an on/off thermostat is used, it is advisable to protect any rooms
where there is risk of frost by using a frost thermostat. The radiator
valve in a room where there is a risk of frost must, however, be open.
4 In rooms where there is a risk of frost, a frost thermostat (Tv)
should preferably be installed.
4 Connect the frost thermostat in parallel with an on/off room
thermostat (Tk) to the On/off-OT terminals of the connector.
When using a OpenTherm thermostat, a frost thermostat
cannot be connected in parallel to the On/off-OT
terminals. Implement frost protection for the central heating
system in combination with an external sensor.
43
T000443-B
Ws
OT
On/off
Tou
t
Tdhw
BL
RL
On/off
OT BL RL Tou t Tdhw
4. InstallationCalenta 25s - 28c - 35s - 40c
Frost protection in combination with an outside sensor
n
The central heating system can also be protected against frost in
combination with an outside sensor. The radiator valve in a room
where there is a risk of frost must, however, be open. Connect the
outside sensor to the Tout terminals of the connector.
The frost protection functions as follows where an outside sensor is
used:
4 At an outside temperature lower than -10°C (can be set with
parameter p30): the circulation pump switches on.
4 At an outside temperature higher than -10°C (can be set with
parameter p30): the circulation pump continues to run and then
switches off.
4.9.7.Connecting the calorifier sensor/
thermostat
Ws
DHW sensor
Connect the calorifier sensor or thermostat to the Tdhw terminals of
the connector.
44
040412 - 7600585-01
T000442-A
OT
On/off
Tou
BL
RL
X13
T001917-B
On/off
OTRLBLTou tTdhw
T001917-B
On/off
OTRLBLTou tTdhw
Calenta 25s - 28c - 35s - 40c
4. Installation
4.9.8.PC/Laptop connection
A PC or Laptop can be connected to the telephone connector using
the optional Recom interface. Using the Recom PC/Laptop service
software, you can enter, change and read out various boiler settings.
4.9.9.Shutdown input
The boiler has a shutdown input. This input is on the BL terminals of
the connector.
CAUTION
Only suitable for potential-free contacts.
Remove the bridge before using the input
The behaviour of the input can be changed using parameter
p36.
¼ See chapter: "Parameter descriptions", page 64
4.9.10.Release input
The boiler has a release input. This input is on the RL terminals of the
connector.
CAUTION
Only suitable for potential-free contacts.
040412 - 7600585-01
The behaviour of the input can be changed using parameter
p37.
¼ See chapter: "Parameter descriptions", page 64
45
T000784-A
Status0-10 0-10
Nc NoC
Nc NoOTm 0 + 0 +C
OTm 0 + 0 +
X5
X4
X1
IF-01
%
1
2
T000785-A
1
2
%
2
2
4. InstallationCalenta 25s - 28c - 35s - 40c
4.10Optional electrical connections
4.10.1.Connection options for the 0-10 V control
PCB (IF-01)
The IF-01 control PCB can be built into the instrument box or the
housing for the control PCBs. Refer to the instructions supplied with
the product.
CAUTION
Do not connect a frost thermostat or room thermostat to
the boiler if using the 0-10 V control PCB.
Connection status (Nc)
n
If the boiler locks out, a relay is de-energised and the alarm can be
transmitted via a potential-free contact (maximum 230 V, 1A) on
terminals Nc and C of the connector.
Connection (OTm)
n
The interface communicates with the boiler control via OpenTherm.
The OTm connection must be connected to the OpenTherm input
OT of the boiler control.
Analogue input (0-10 V)
n
This control can be based on temperature or heat output. The two
controls are described briefly below. For analogue control, the 0-10
V signal must be connected to the interface.
n
Analogue temperature-based control (*)
The 0-10 V signal controls the boiler flow temperature between 0°C
and 100°C. This control modulates on the basis of flow temperature,
whereby the heat output varies between the minimum and maximum
values on the basis of the flow temperature set point calculated by
the controller.
46
A jumper (2) on the interface is used to select either temperature
control (*) or heat output control (%).
Jumper 2
*
Input signal (V) Temperature ºC Description
0 - 1,50 - 15Boiler off
1,5 - 1,815 - 18Hysteresis
1,8 - 1018 - 100Temperature required
040412 - 7600585-01
T000800-A
1
2
%
11
T001255-B
Status
CNc No
C
Nc No
Pump
N L
Pump
N L
EgV
N L
EgV
N L
3wV
X3
SCU-SO2
X1
X4X5
N C
3wV
N C
D
D
X2
D3
Tsol Gps
Tsol Gps
Hru
Hru
F 4AT
Calenta 25s - 28c - 35s - 40c4. Installation
Analogue heat output-based control (%)
n
The 0-10V signal controls the boiler output between 0% and 100%.
The minimum and maximum values are limited. The minimum output
is linked to the boiler's modulation depth. The output varies between
the minimum and maximum value on the basis of the value
determined by the controller.
Jumper 2 Input signal (V) Heat output (%) Description
(1)
0 - 2,0
%
2,0 - 2,2
2,0 - 10
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
Analogue output (0-10 V)
n
(1)
(1)
0 - 20Boiler off
20 - 22Hysteresis
20 - 100Heat output requested
The temperature or heat output can be chosen for this feedback
message. The two controls are described briefly below.
A jumper (1) on the interface is used to select either temperature
control (*) or heat output control (%).
Jumper 1
Jumper 1 Output signal (V) Heat output (%) Description
%
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
Output signal (V)
*
Temperature À
Description
0,5-Alarm
1 - 1010 - 100Delivered temperature
00 - 15Boiler off
0,515 - 20Alarm
2,0 - 10
(1)
20 - 100Heat output supplied
4.10.2.Connection possibilities for the PCB (SCU-
S02)
When using the print PCB (SCU-S02), the housing for control PCBs
will first have to be built in. Refer to the instructions supplied with the
product. If the boiler is fitted with the control PCB (SCU-S02), then
this is automatically recognised by the automatic control unit of the
boiler.
040412 - 7600585-01
CAUTION
On removing this PCB, the boiler will show fault code
e[38. To prevent this fault, an auto-detect must be
carried out after removing this PCB.
¼ See chapter: "Carrying out an auto-detect", page
70.
47
4. Installation
Calenta 25s - 28c - 35s - 40c
The status indicator D3 at the top right of the control PCB indicates
the status:
4 Continuous signal: PCB working normally
4 Flashing signal: No connection
4 No signal: No voltage or faulty PCB (Check the wiring)
Control of external central heating pump (Pump)
n
An external central heating pump can be connected to the Pump
terminals of the connector. The maximum input power is 400 VA.
Control of external three-way valve (3wV)
n
The external three-way valve (230 VAC) can be used when
connecting an indirectly heated calorifier. The neutral position of the
three-way valve can be set using parameter p34.
The three-way valve is connected as follows:
4 N = neutral
4 C = central heating
4 D = tank
Control of external sanitary hot water pump (3wV)
n
It is also possible to connect an external DHW pump to the terminals
3wV. Connect the pump as follows:
4 N = N pump
4 D = L pump
4 Q = PE pump
CAUTION
If the neutral position of the three-way valve is adjusted
with parameter p34, the pump should be connected as
follows:
4N = N pump
4C = L pump
4Q = PE pump
48
Control of external gas valve (EgV)
n
If there is a heat demand, an alternating voltage of 230 VAC, 1 A
(maximum) becomes available on the EgV terminals of the connector
to control an external gas valve.
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c4. Installation
Operation signal and failure signal (Status)
n
The alarm or operation signal is selected using parameter p40.
4 If the boiler is operating, the operation signal can be switched via
a potential-free contact (maximum 230 VAC, 1 A) on the No and
C terminals of the connector.
4 If the boiler locks out, the alarm can be transmitted via a potential-
free contact (maximum 230 VAC, 1 A) on the Nc and C terminals
of the connector.
Solar DHW sensor Tsol
n
The solar boiler temperature is controlled using a sensor. Connect
this sensor to the connector terminals Tsol.
Pressure switch minimum Gps
n
The minimum gas pressure switch shuts the boiler down if the inlet
gas pressure becomes too low. Connect the minimum gas pressure
switch to the Gps terminals of the connector. The presence of the gas
pressure switch must be set using parameter p41.
Heat Recovery Unit (Hru)
n
Connect the wires from the heat recovery unit to the Hru terminals of
the connector. The presence of the heat recovery unit must be set
using parameter p4".
040412 - 7600585-01
49
T001047-G
2 31
K1
X1
X14
X13
X12
X3
X2
X4
X5
X6
X7
X8
X9
X10
X11
1
PC
OTOSWS
HLS
1 27 8 9 103 4 5 6
X6
1 2 3
GN/
YW
WH
BL
153
X21
X8
1 2 3
BR
BL
GN/
YW
3 1 2
X41
SCUSCU
1 2 3 4 5 6
WH
GY
OR
RD
GN
YW
X7
1 2 3
WH
BK
RD
1 3 2
X121
X5
2 3 4 1
E
BK
BL
GN/
YW
GY
1 23
X22
PWM
PUMP
12 13
BK
BK
1 2
X116
FTSRTS
9
RD
1
BK
1
22
X115
8
BL
1
22
X114
PS
10 11
BK
BK
3 1
X112
FS
2 3
BK
BK
1 3
X113
4 5 7 6
X111
BK
BK
BK
BK
1 2 3 4
PSU
X9
2 3 4 5
X91
BK
BK
BK
BK
1 2 4 5
1
BK
BK
1
2
X117
P
230V, 50Hz
L N
SCU
X2
132
BL
BR
GN/
YW
X1
123
BR
BL
GN/YW
DIS
1 10
1 10
X3
43 2 15
BR
BL
BR
BL
GN/
YW
3 1
4 2
X51
GBPUMP ADV
ITFAN
S
X13
X12
X11
X10
X14
4. InstallationCalenta 25s - 28c - 35s - 40c
4.11Electrical diagram
P
Power supply
SCU
Extended control PCB
S
On/Off switch
IT
Ignition transformer
E
Ignition power relay
GB
Combined venturi and gas valve unit
DV
3-way valve
50
PSU
OT
OS
WS
PC
DIS
Storage parameter
Thermostat
Outside sensor
DHW sensor
Connecting a computer
Display
PUMP A
HLS
FAN
FS
RTS
FTS
PS
Shunt pump
Safety thermostat
Fan
Flow switch
Return sensor
Flow sensor
Pressure sensor
040412 - 7600585-01
T001523-B
Calenta 25s - 28c - 35s - 40c4. Installation
4.12Filling the system
4.12.1.Water treatment
In most cases, the boiler and the central heating installation can be
filled with normal tap water and no water treatment will be necessary.
WARNING
Do not add chemical products to the central heating water
without consulting Remeha. For example: antifreeze,
water softeners, products to increase or reduce the pH
value, chemical additives and/or inhibitors. These may
cause faults in the boiler and damage the heat exchanger.
4Rinse the central heating installation with at least 3x
the volume of the central heating installation. Flush
the DHW pipes with at least 20 times the volume of
the pipes.
4For untreated water, the pH value of the water in the
installation must be between 7 and 9 and for treated
water between 7 and 8,5.
4The maximum hardness of the water in the installation
must be between 0,5 - 20,0 °dH (Depending on the
total installed heat output).
4For more information, refer to our publication water
quality rules. The rules in the aforementioned
document must be respected.
4.12.2.Filling the siphon
1. Remove the siphon.
2. Fill the siphon with water. This must be filled up to the level
markers.
3. Re-assemble the siphon.
CAUTION
4Fill the water siphon before starting the boiler to avoid
combustion products escaping from the boiler.
4Mount the vent hose above the siphon.
040412 - 7600585-01
51
1
2
3
4
T000181-B
T001574-B
T001507-B
4. InstallationCalenta 25s - 28c - 35s - 40c
4.12.3.Filling the system
CAUTION
Before filling, open the valves on every radiator in the
installation.
In order to be able to read off the water pressure from the
boiler display, the boiler must be switched on.
1. Fill the system with clean tap water (advised water pressure is
between 1,5 and 2 bar).
2. Check the tightness of the water connections.
After switching on the power and if there is adequate water
pressure, the boiler always runs through an automatic
venting program lasting approximately 3 minutes (During
filling, air can escape from the system via the automatic air
vent). If the water pressure is lower than 0,8 bar, the symbol
e will appear. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2 bar).
CAUTION
4The filling must be carried out within 30 minutes,
otherwise the venting program starts and that would
be undesirable if the device is not filled. Switch off the
boiler if the central heating system is not being
topped up immediately.
4When venting, prevent water from getting into the
boiler casing and electrical parts of the boiler
52
040412 - 7600585-01
T001996-A
1
23458
67
Calenta 25s - 28c - 35s - 40c5. Commissioning
5Commissioning
5.1Control panel
5.1.1.Functions of the keys
1
2
3
4
5
6
Display
> [Escape] or J key
D Heating temperature key or [-]
N DHW temperature key or [+]
S [Enter] or cancel d Key lock-out
B [Chimney-sweeping] keys
(press the 2 and 3 keys simultaneously)
7
f [Menu] keys
(press the 4 and 5 keys simultaneously)
8
a On/off switch
The display has several positions and symbols and provides
information on the operating condition of the boiler and any possible
failures. A service message may also appear in the display. Numbers,
dots and/or letters may be displayed. The symbols located above the
function keys indicate their current function.
4 The display content can be changed using parameter p6.
4 The brightness of the display lighting can be changed using
parameter p8.
Information menu:
Reading the various current values.
Q
Chimney-sweeping position:
B
Forced full or part load for CO2 measurement.
User menu:
W
Parameters at user level can be changed.
Heating programme deactivated:
C
The heating function is deactivated.
040412 - 7600585-01
Key lock-out is activated by setting parameter p6 to 3. If no key is
pressed for 3 minutes, the display lighting switches off and only the
current water pressure, the > key and the d symbol are
displayed. Press the S key for about 2 seconds to reactivate the
display and other keys. The d symbol disappears from the display.
5.1.2.Meaning of the symbols on the display
On/Off switch:
After 5 lock-outs, the boiler must be switched off/on
a
again.
Shunt pump:
b
The pump operates.
Central heating function:
D
Access to central heating temperature parameter.
DHW function:
N
Access to sanitary hot water temperature parameter.
53
5. Commissioning
Calenta 25s - 28c - 35s - 40c
Manual mode:
E
Boiler is set to manual operation.
DHW programme deactivated:
T
The DHW mode is deactivated.
Service menu:
?
Parameters at installer level can be changed.
Energy-saving mode:
)
Economic mode activated.
Defect:
Boiler indicates a fault. This can be seen from the e code
c
and red display.
Frost protection:
]
Boiler is running in frost protection mode.
Hour counter menu:
Readout of the operating hours, number of successful
\
starts and hours on mains supply.
K
e
g
[
I
d
5.2Check points before commissioning
5.2.1.Preparing the boiler for commissioning
Yellow display with the symbols:
$ + K + Z (Maintenance message).
Water pressure:
The water pressure is too low.
Battery symbol:
Status of battery of wireless controller.
Signal strength symbol:
Signal strength of the wireless controller.
Burner level:
Boiler is running at full or low load.
Locking the keys:
Key lock-out is activated.
WARNING
Do not put the boiler into operation if the supplied gas is
not in accordance with the approved gas types.
Preparatory procedure for boiler commissioning:
4 Check that the gas type supplied matches the data shown on the
boiler's data plate.
4 Check the gas circuit.
4 Check the hydraulic circuit.
4 Check the water pressure in the heating system.
4 Check the electrical connections to the thermostat and the other
external controls.
4 Check the other connections.
4 Test the boiler at full load. Check the setting of the gas/air ratio
and, if necessary, correct it.
4 Test the boiler at part load. Check the setting of the gas/air ratio
and, if necessary, correct it.
4 Finalizing work.
54
040412 - 7600585-01
T001518-B
C
Calenta 25s - 28c - 35s - 40c
5. Commissioning
5.2.2.Gas circuit
WARNING
Ensure that the boiler is switched off.
1. Open the main gas supply.
2. Unscrew the two screws located under the front panel by a quarter
turn and remove the panel.
3. Tilt the control box forwards by opening the holding clips located
at the sides.
4. Check the gas supply pressure at the pressure outlet C on the gas
valve unit.
WARNING
To ascertain the gas types permitted, see chapter:
¼
"Equipment categories", page 9
5. Check the tightness of the gas connections made after the gas
valve unit in the boiler.
6. Check the tightness of the gas line, including the gas valves. The
test pressure must not exceed 60 mbar.
7. Purge the gas supply pipe within the boiler by unscrewing the
pressure outlet on the gas block. Tighten the measurement point
when the pipe has been sufficiently purged.
8. Check the tightness of the gas connections in the boiler.
5.3Commissioning the boiler
5.2.3.Hydraulic circuit
4 Check the condensate discharge siphon; it must be filled with
clean water up to the mark.
4 Check that there are no leaks on the hydraulic connections.
5.2.4.Electrical connections
4 Check the electrical connections, particularly the earth.
4 Check the electrical connections to the thermostat and the other
external controls.
1. Tilt the control box upwards again and fasten it using the clips
located at the sides.
2. Open the main gas supply.
3. Open the gas valve on the boiler.
4. Insert the boiler plug into an earthing socket.
5. Turn on the boiler using the on/off switch.
040412 - 7600585-01
55
5. CommissioningCalenta 25s - 28c - 35s - 40c
6. Set the controls (thermostats, control system) so that they request
heat.
7. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
A short test where all segments of the display are visible.
fK[xx
pK[xx
: Software version
: Parameter version
The version numbers are displayed alternately.
8. A vent cycle of a duration of around 3 minutes is carried out
automatically.
If a DHW sensor is connected and the anti-legionella
function is activated, the boiler starts to heat the water in
the DHW tank as soon as the vent programme has been
completed.
By pressing the S key for a short time, the current operating status
is shown on the display:
Heat demand 5D
1 : Fan ON1 : Post-ventilation1 : Fan ON1 : Post-ventilation
" : Boiler is igniting 5 : Burner stop" : Boiler is igniting5 : Burner stop
3 : Heating System 0 : Standby4 : Domestic hot water mode 0 : Standby
Heat demand stopped
6 : Post-circulation of the pump
Hot tap water demand N
Heat demand stopped
6 : Post-circulation of the pump
In addition to 0, in STAND-BY the display normally shows the water
pressure and the symbols 5D, 5H and N.
Error during the start-up procedure:
4 No information is shown on the display:
- Check the mains supply voltage
- Check the main fuses
- Check the fuses on the control panel:
(F1 = 6,3 AT, F2 = 2 AT)
- Check the connection of the mains lead to the connector X1 in
the instrument box
4 A fault is indicated on the display by the fault symbol c and a
flashing fault code.
- The meaning of the error codes is given in the error table.
- Press for 3 seconds on key J to restart the boiler.
If the economy setting (eco setting) is on, then, after central
heating operation, the boiler will not start to run for hot tap
water production.
56
040412 - 7600585-01
T001526-A
Calenta 25s - 28c - 35s - 40c5. Commissioning
5.4Gas settings
5.4.1.Adapting to another gas type
WARNING
Only a qualified engineer may carry out the following
operations.
The boiler is preset in the factory to operate on natural gas G25 (Gas
L).
4If the boiler is converted, for example, to:
-G20 (Gas H)
-G31 (Propane)
It is necessary to mention on the sticker provided: This
boiler has been set for.... This sticker must be affixed
to the top of the boiler next to the identification plate.
4If operating on propane, Remeha cannot guarantee
compliance with all aspects of comfort in accordance
with the CW label.
For operation on another group of gases, carry out the following
operations:
4 Regulate the fan speed as indicated in the table (if required). The
setting can be modified using parameters p17, p18,
p19 and p20:
¼ See chapter: "Parameter descriptions", page 64
4 Set the air/gas ratio. For more detailed information:
¼ See chapter: "Setting the air/gas ratio (Full load)", page
57
¼ See chapter: "Setting the air/gas ratio (Part load)", page
59
5.4.2.Setting the air/gas ratio (Full load)
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
WARNING
Ensure that the opening around the sensor is completely
sealed when taking measurements.
040412 - 7600585-01
57
T001586-A
rpm
kWµA
± 30l/min
barPsi
StºC
ºCºFh
A
T000932-A
5. CommissioningCalenta 25s - 28c - 35s - 40c
3. Set the boiler to full load. Press the two B keys simultaneously.
The display shows
. The symbol B appears.
h3
4. Measure the percentage of O2 or CO2 in the flue gases (Front
panel removed).
5. If this rate does not match the required value, correct the gas/air
ratio using the adjustment screw A on the gas valve unit.
6. Check the flame through the flame inspection window.
The flame must not be detached.
O2/CO2 control and setting values at full load for G20 (Gas H)
Boiler typeSetting valueChecking value
O 2 (%)CO 2 (%)O 2 (%)CO 2 (%)
Calenta 25s5,2 ± 0,48,8 ± 0,25,2 ± 0,58,8 ± 0,3
Calenta 28c5,2 ± 0,48,8 ± 0,25,2 ± 0,58,8 ± 0,3
Calenta 35s4,8 ± 0,49,0 ± 0,24,8 ± 0,59,0 ± 0,3
Calenta 40c4,8 ± 0,49,0 ± 0,24,8 ± 0,59,0 ± 0,3
O2/CO2 control and setting values at full load for G25 (Gas L)
Boiler typeSetting valueChecking value
O 2 (%)CO 2 (%)O 2 (%)CO 2 (%)
Calenta 25s5,0 ± 0,48,8 ± 0,25,0 ± 0,58,8 ± 0,3
Calenta 28c5,0 ± 0,48,8 ± 0,25,0 ± 0,58,8 ± 0,3
Calenta 35s4,5 ± 0,49,1 ± 0,24,5 ± 0,59,1 ± 0,3
Calenta 40c4,5 ± 0,49,1 ± 0,24,5 ± 0,59,1 ± 0,3
Diameter of the gas diaphragm (x.xx) O2/CO2 control and setting values at full load for G31 (Propane)
Fit the gas restrictor in the gas blockBoiler typeSetting valueChecking value
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
WARNING
Ensure that the opening around the sensor is completely
sealed when taking measurements.
3. Set the boiler to part load. Press the two B keys
simultaneously. The symbol B appears. Press the [-] key several
times until
4. Measure the percentage of O2 or CO2 in the flue gases (Front
panel removed).
is displayed on the screen.
l3
5. If this rate does not match the required value, correct the gas/air
ratio using the adjustment screw B on the gas valve unit.
4
Turn the screw B anticlockwise to obtain a lower
CO2 value.
4Turn the screw B clockwise to obtain a higher CO
2
value.
6. Check the flame through the flame inspection window.
The flame must be stable and blue in colour with orange
particles around the edge of the burner.
O2/CO2 control and setting values at part load for G20 (Gas H)
Boiler typeSetting valueChecking value
O 2 (%)CO 2 (%)O 2 (%)CO 2 (%)
Calenta 25s5,9 ± 0,48,4 ± 0,25,9 ± 0,48,4 ± 0,2
Calenta 28c5,9 ± 0,48,4 ± 0,25,9 ± 0,48,4 ± 0,2
Calenta 35s5,5 ± 0,48,6 ± 0,25,5 ± 0,48,6 ± 0,2
Calenta 40c5,5 ± 0,48,6 ± 0,25,5 ± 0,48,6 ± 0,2
O2/CO2 control and setting values at part load for G25 (Gas L)
Boiler typeSetting valueChecking value
O 2 (%)CO 2 (%)O 2 (%)CO 2 (%)
Calenta 25s5,7 ± 0,48,4 ± 0,25,7 ± 0,48,4 ± 0,2
Calenta 28c5,7 ± 0,48,4 ± 0,25,7 ± 0,48,4 ± 0,2
Calenta 35s5,2 ± 0,48,7 ± 0,25,2 ± 0,48,7 ± 0,2
Calenta 40c5,2 ± 0,48,7 ± 0,25,2 ± 0,48,7 ± 0,2
040412 - 7600585-01
59
B
T001985-B
A
8
910
T001522-A
5. Commissioning
Calenta 25s - 28c - 35s - 40c
O2/CO2 control and setting values at part load for G31 (Propane)
Boiler typeSetting valueChecking value
O 2 (%)CO 2 (%)O 2 (%)CO 2 (%)
Calenta 25s5,8 ± 0,39,9 ± 0,25,8 ± 0,39,9 ± 0,2
Calenta 28c5,8 ± 0,39,9 ± 0,25,8 ± 0,39,9 ± 0,2
Calenta 35s5,8 ± 0,39,9 ± 0,25,8 ± 0,39,9 ± 0,2
Calenta 40c5,8 ± 0,39,9 ± 0,25,8 ± 0,39,9 ± 0,2
Repeat the high speed test and the low speed test as often
as necessary until the correct values are obtained without
having to make additional adjustments.
5.4.4.Basic setting for the gas/air ratio
If the gas/air ratio is out of adjustment, the gas valve unit has a basic
setting. To do this, proceed as follows:
1. Cut the power supply to the boiler.
2. Close the gas valve on the boiler.
3. Remove the air inlet flue on the venturi.
4. Unscrew the top connection on the gas valve unit.
5. Disconnect the connector located under the fan.
6. Release the 2 clips holding the fan/mixing elbow unit in place on
the heat exchanger.
7. Completely remove the fan/mixing elbow unit.
For steps 3 to 7 inclusive, see chapter: "Checking the burner
¼
and cleaning the heat exchanger", page 78
8. Turn the setting screw A on the gas valve unit to modify the
position of the restrictor.
9. Turn the setting screw B on the gas valve unit anticlockwise until
it matches the front panel.
10.Turn the setting screw B on the gas valve unit by 6 turns clockwise.
11.Follow the procedure in reverse to re-assemble all of the
components.
5.5Checks and adjustments after commissioning
60
5.5.1.Finalizing work
1. Remove the measuring equipment.
2. Put the flue gas sampling plug back in place.
3. Refit the front panel. Tighten the two screws by a quarter turn.
4. Push key
5. Raise the temperature in the heating system to approximately
70°C.
6. Shut down the boiler.
7. After about 10 minutes, vent the air in the heating system.
8. Switch on the boiler.
to return the boiler to normal operating mode.
>
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c5. Commissioning
9. Check the tightness of the flue gases evacuation and air inlet
connections.
10.Checking the hydraulic pressure. If necessary, top up the water
level in the heating system (recommended hydraulic pressure
between 1,5 and 2 bar).
11.Tick the gas category used on the data plate.
12.Complete the checklist in the supplied service book.
13.Explain the operation of the installation, the boiler and the
regulator to the users.
14.Give all the instruction manuals to the user.
15.Together with the end user, fill in the warranty sheet provided.
16.Confirm the commissioning with a signature and a company
stamp.
5.6Reading out measured values
5.6.1.Reading the various current values
The following current values can be read off the information menu
Q:
4 5t = State.
4 5v = Sub-status.
4 t1 = Supply temperature (°C).
4 t" = Return temperature (°C).
4 t3 = Calorifier temperature (°C).
4 t4 = Outside temperature (°C) (Only with an outside
temperature sensor).
4 t5 = Solar boiler temperature (°C).
4 5p = Internal set point (°C).
4 fl = Ionization current (µA).
4 Mf = Fan speed in rpm.
4 pr = Water pressure (bar).
4 p; = Supplied relative heat output (%).
040412 - 7600585-01
61
T000810-F
4x
2x
T000816-G
5x
2x
5. Commissioning
Calenta 25s - 28c - 35s - 40c
The current values can be read as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
is displayed, alternating with the
5t
current status 3 (for example).
3. Press the [+] key.
sub-status
(for example).
30
4. Press the [+] key.
flow temperature
is displayed, alternating with the current
5v
is displayed, alternating with the current
t1
°C (for example).
60
5. Press the [+] key successively to scroll down the various
parameters.
t", t3, t4, t5
6. Press the [+] key.
set point
°C (for example).
88
7. Press the [+] key.
ionization current
8. Press the [+] key.
fan rotation speed
9. Press the [+] key.
water pressure
#0
is displayed, alternating with the internal
5p
is displayed, alternating with the current
fl
µA (for example).
70
is displayed, alternating with the current
Mf
3000
pr
rpm (for example).
is displayed, alternating with the current
bar (for example). If no water pressure sensor
.
is connected, [-.-] appears on the display.
10.Press the [+] key.
modulation percentage
11.Press the [+] key. The readout cycle starts again with
12.Press the
key 2 times to return to the current operating
>
is displayed, alternating with the current
p;
% (for example).
78
5t
mode.
.
5.6.2.Readout from the hour counter and
percentage of successful starts
1. Press the two keys f simultaneously and then key [+] until the
symbol \ flashes on the menu bar.
2. Press the S key.
operation
3600
3. Press the [+] key. The display shows D.
alternating with the number of operating hours in central heating
operation
4. Press the [+] key. The display shows N.
560
alternating with the number of operating hours used for heating
tap water
320
(for example).
5. Press the [+] key. The display shows @.
alternating with the percentage of successful starts
example).
6. Press the
key 2 times to return to the current operating
>
mode.
and the number of hours of boiler
hr
(for example) are displayed alternately.
is displayed,
hr
(for example).
is displayed,
hr
is displayed,
5Z
92
% (for
62
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c5. Commissioning
5.6.3.Status and sub-status
The information menu Q gives the following status and sub-status
numbers:
State 5tSub-status 5v
0
1
2
3 / 4 Burner for central heating operation / DHW System
5
6
8
9
17
Rest
Boiler start (Heat demand)
Burner start
Burner stop
Boiler stop (End of heat demand)
Control stop
Blocking
Bleed
0
Rest
1
Anti-hunting
2
Control three-way valve
3
Start pump
4
Wait for the correct temperatures for burner start
10
Open flue gas damper/external gas valve
11
Increase fan speed
13
Pre-ventilation
14
Wait for release signal
15
Burner on
17
Pre-ignition
18
Main ignition
19
Flame detection
"0
Intermediate ventilation
30
Temperature control
31
Limited temperature control (ΔT safety)
32
Output control
33
Increase protection level 1 (Modulate down)
34
Increase protection level 2 (Part load)
35
Increase protection level 3 (Blockage)
36
Modulate up for flame control
37
Temperature stabilisation time
38
Cold start
40
Burner off
41
Post ventilation
42
Close flue gas damper/external gas valve
43
Recirculation protection
44
Stop fan
60
Pump post circulation
61
Pump off
62
Control three-way valve
63
Start anti-hunting
0
Wait for burner start
1
Anti-hunting
xx
Shutdown code xx
0
Rest
2
Control three-way valve
3
Start pump
61
Pump off
62
Control three-way valve
040412 - 7600585-01
63
5. CommissioningCalenta 25s - 28c - 35s - 40c
5.7Changing the settings
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
5.7.1.Parameter descriptions
Factory setting
Parameter
p1
p2
p3
p4
p5
p6
p7
p8
p17
p18
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
0 = Comfort
1 = Energy-saving mode
2 = Management using a programmable thermostat
0 = No anticipation resistance for the ON/OFF
thermostat
1 = Anticipation resistance for the ON/OFF thermostat
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3 minutes
3 = Automatic switching to simple after 3 minutes; Key
blocking is active
1 to 98 minutes
99 minutes = continuous
0 = Dimmed
1 = Bright
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G31 (Propane)
(x100 rpm)
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G31 (Propane)
(x100 rpm)
(1)
(1)
Calenta
25s 28c 35s 40c
80
60
1
2
0
2
1
1
56466242
56466242
53436242
56626268
56626268
53596268
64
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c5. Commissioning
Factory setting
ParameterDescriptionAdjustment range
Calenta
25s 28c 35s 40c
(1)
18181717
18181717
18181817
p19
Minimum fan speed (Heating
+DHW)
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G31 (Propane)
(x100 rpm)
CLV overpressure (combusted gas discharge
systems)
21212323
(x100 rpm)
G25 (Gas L)
(1)
50507575
G20 (Gas H)50507575
p20
p21
p22
p23
p24
p25
p26
p27
p28
Minimum fan speed (offset)
Start speed
G31 (Propane)50507575
CLV overpressure (combusted gas discharge
systems)
Do not modify
(x100 rpm)
50504040
30304040
Minimum water pressure0 - 3 bar(x 0,1 bar)8
Maximum flow temperature of
0 to 90 °C
system
Anti-hunting differential for central
-15 to 15 °C
heating operation
Heat curve set point
(Maximum outside temperature)
Heat curve set point
(Supply temperature)
Heat curve set point
(Minimum outside temperature)
Setting the pump speed
0 to 30 °C
(Only with an outside temperature sensor)
0 to 90 °C
(Only with an outside temperature sensor)
-30 to 0 °C
(Only with an outside temperature sensor)
2 - 10 (x 10 % )
-15
(Minimum pump speed for central
90
3
20
20
2
heating operation)
p29
Setting the pump speed
(Maximum pump speed for
2 - 10 (x 10 % )
6
central heating operation)
p30
Antifreeze temperaturefrom - 30 to 0°C-10
0 = Stop
1 = Start
p31
Legionella protection
(After commissioning, the boiler will operate once a
1010
week at 65°C for DHW)
2 = Management using a programmable thermostat
p32
p33
p34
p35
Set point increase for calorifier0 to 20 °C15
DHW cut-in temperature DHW
sensor
Control of three-way valve
Boiler type
from 2 to 15°C6
0 = Normal
1 = Reverse
0 = Heating and instant domestic hot water
1 = Heating only
1010
0
0 = Heating activated
p36
Shutdown input function
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
1
3 = Lock-out with frost protection (Pump only)
p37
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
Release function
0 = Hot water on
1 = Release input
1
040412 - 7600585-01
65
T001906-B
1x
2x
5. Commissioning
ParameterDescriptionAdjustment range
p38
p39
p40
p41
p42
p43
p44
p45
p46
Zd
df and dV
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
Release waiting time0 to 255 seconds0
Gas valve switching time0 to 255 seconds0
Fault relay function (Optional)
GpS connected (Optional)
HRU connected (Optional)
Mains detection phase
Maintenance messageDo not modify1
Service operating hoursDo not modify175
Service burning hoursDo not modify30
Detection of connected SCUs
Factory setting
0 = Operation signal
1 = Alarm signal
0 = Not connected
1 = Connected
0 = Not connected
1 = Connected
0 = Stop
1 = Start
0 = No detection
1 = Detection
To restore the factory settings or when replacing the
main PCB, enter the values dF and dU from the type
plate in parameters df and dV
Calenta 25s - 28c - 35s - 40c
Factory setting
Calenta
25s 28c 35s 40c
1
0
0
0
0
X
Y
5.7.2.Modification of the user-level parameters
Parameters p1 to p8 can be modified by the user in order to meet
central heating and DHW comfort needs.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the
symbol W flashes on the menu bar.
2. Select the users menu using the key S.
flashing.
1
3. Press the S key a second time. The value
flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
5. Confirm the value with the S key.
60
°C.
p[1
flashing.
6. Press the
key 2 times to return to the current operating
>
mode.
is displayed with
p[1
°C appears and
80
is displayed with
1
66
040412 - 7600585-01
T000819-E
3x
2x
Calenta 25s - 28c - 35s - 40c5. Commissioning
4The parameters p1 to p8 are changed in the
same way as p1. After step 2, use the [+] key to
move to the required parameter.
4The parameters p1 (the maximum heating water
temperature) and p2 (the maximum drinking water
temperature) can also be modified using the quick
selection menu.
5.7.3.Modification of the installer-level
parameters
Parameters p17 to df must only be modified by a qualified
professional. To prevent unwanted settings, some parameter settings
can only be changed after the special access code 0012 is
entered.
If the boiler has been modified, for example:
4G20 (Gas H) or G31 (Propane)
4high pressure systems
4WTW coupling
4CLV overpressure (combusted gas discharge
systems)
It is necessary to mention on the sticker provided: This
boiler has been set for.... This sticker must be affixed to the
top of the boiler next to the identification plate.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2.
Select the fitter menu using the key.
c0de
appears on the
display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
is displayed with 1 flashing.
p[1
5. Press the S key a second time. The value
0012
80
.
°C appears and
flashes (for example).
6. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
7. Confirm the value with the S key:
60
°C.
is displayed with
p[1
1
flashing.
8. If necessary, set other parameters by selecting them using the
[-] or [+] keys.
9. Press the
key 2 times to return to the current operating
>
mode.
The boiler also returns to operating status if no keys are
pressed for 3 minutes.
040412 - 7600585-01
67
T001848-B
1500
0
5
10
15
20
25
30
2000 2500 3000 3500 4000 4500
5600
5000 5500 6000
F
R
Q
M
T001847-A
1500
0
5
10
15
20
25
30
2000 2500 3000 3500 4000 4500
46005600
5000 5500 6000
F
R
Q
M
T001966-B
200030004000500060007000
0
5
10
15
20
25
30
35
40
6200
F
R
Q
M
T001967-B
200030004000500060007000
0
5
10
15
20
24
30
35
40
6200
R
Q
M
6200
4200
F
5. CommissioningCalenta 25s - 28c - 35s - 40c
5.7.4.Setting the maximum heat input for central
heating operation
Calenta 25s
M
F
Q
R
Calenta 28c
M
F
Q
R
Calenta 35s
M
F
Q
Maximum heat input
Factory setting
Power input (kW)
Fan rotation speed (rpm)
Maximum heat input
Factory setting
Power input (kW)
Fan rotation speed (rpm)
Maximum heat input
Factory setting
Power input (kW)
68
R
Calenta 40c
M
F
Q
R
Fan rotation speed (rpm)
Maximum heat input
Factory setting
Power input (kW)
Fan rotation speed (rpm)
040412 - 7600585-01
T001628-A
3x
...x
...x
2x
T000820-H
3x
...x
Calenta 25s - 28c - 35s - 40c
5. Commissioning
See the graphs for the relationship between heat input and speed for
natural gas. The speed can be changed using parameter p17. To
do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
appears
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key to go to parameter
is displayed with 1 flashing.
p[1
p[17
0012
.
.
6. Confirm using key S.
7. Press the [+] key to increase the speed from
(see the graphs for the associated heat output).
50
to, for example,
46
8. Confirm the value with the S key.
9. Press the
key 2 times to return to the current operating
>
mode.
5.7.5.Return to the factory settings
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key several times.
is displayed with 1 flashing.
p[1
p[df
0012
is displayed with
flashing.
6. Press the S key.
df[x
is displayed with x flashing. This is
the current value of X for dF. Check this against the value of X on
the type plate.
7. Enter the value of X shown on the type plate using the [-] or [+]
key.
8. Confirm the value with the S key,
df[y
is displayed with
flashing. This is the current value of Y for dU. Check this against
the value of Y on the type plate.
9. Enter the value of Y shown on the type plate using the [-] or [+]
key.
10.Confirm the value with the S key. The factory settings are reset.
11.The display returns to the current operating mode.
appears
.
df
y
040412 - 7600585-01
69
T000445-B
3x
...x
T000824-E
2x
2x
bar
5. Commissioning
Calenta 25s - 28c - 35s - 40c
5.7.6.Carrying out an auto-detect
After removing a control PCB, an auto-detect must be carried out. To
do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
appears
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key several times.
is displayed with 1 flashing.
p[1
p[Zd
is displayed with
0012
.
Zd
flashing.
6. Confirm using key S. Auto-detect is carried out.
7. The display returns to the current operating mode.
5.7.7.Setting the manual mode
In some cases it may be necessary to switch the boiler to manual
operation, For example, if the controller has not yet been
connected. The boiler can be switched to automatic or manual
operation under the symbol E. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol E flashes on the menu bar.
2. Press the S key:
or
The text
with the current water pressure (only if an outside
Zv
sensor is connected). The flow temperature is determined by the
internal heating curve.
or
The value of the minimum flow temperature.
3. Press the [-] or [+] key to increase this value temporarily in manual
operation.
4. Confirm the value with the S key. The boiler is now set to manual
operation.
5. Press the
key 2 times to return to the current operating
>
mode.
5.7.8.Setting the legionella protection function
The boiler is supplied with legionella protection as standard. The
setting can be changed using the parameter p31.
70
¼ See chapter: "Parameter descriptions", page 64.
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
6Switching off the boiler
6.1Installation shutdown
If the central heating system is not used for a long period, we
recommend switching the boiler off.
4 Switch the On/Off switch to Off.
4 Cut the power supply to the boiler.
4 Shut off the gas supply.
4 Ensure that the boiler and system are protected against frost
damage.
6.2Frost protection
6. Switching off the boiler
CAUTION
If the home is unoccupied for a long period and there is a
risk of frost, drain the boiler and the heating system.
4 Turn down the temperature of the room thermostat to, for example,
10 °C.
4 Set the boiler to ECO mode using parameter p4, this action will
switch off the standby setting.
¼ See chapter: "Changing the settings", page 64.
The boiler will then only start up to protect itself from frost. To prevent
radiators and the system from freezing in rooms where there is a risk
of frost (e.g. a garage or storage room), a frost thermostat or outside
sensor can be connected to the boiler.
¼ See paragraph: "Connect frost protection", page 43.
CAUTION
4The antifreeze protection does not function if the
boiler is switched off.
4The integrated protection system only protects the
boiler, not the installation.
040412 - 7600585-01
When the heating water temperature in the boiler falls by too much,
the integrated protection system in the boiler starts up. This protection
functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the circulation pump continues to run for a short time.
71
T000836-E
1x
...x
T000837-C
1x
...x
6. Switching off the boilerCalenta 25s - 28c - 35s - 40c
6.3Switching off the central heating
The central heating can be deactivated via the "quick menu". To do
this, proceed as follows:
1. Press the D key 1 times.
2. The symbol D and the current temperature are displayed (the
temperature flashes, e.g.
3. Press the [-] key several times until
80
°C).
0ff
is displayed on the
screen.
4. To confirm, press the S key.
5. The symbol C appears on the display.
6.4Shutting down domestic hot water production
The boiler drinking water mode can be deactivated via the "quick
menu". To do this, proceed as follows:
1. Press the N key 1 times.
2. The symbol N and the current temperature are displayed (the
temperature flashes, e.g.
Boiler maintenance is kept to a minimum. Nevertheless, we
recommend having the boiler inspected and serviced at regular
intervals. To determine the best time for maintenance, the boiler is
fitted with a function that automatically signals any maintenance to be
carried out. The appearance if this service message on the boiler
display is determined by the automatic control unit. Depending on the
use of the boiler, the first maintenance message appears 3 years after
installation of the boiler at the latest.
For more information, refer to the maintenance log
attached to the appliance.
7.2Preventive maintenance with automated service message
When it is time to carry out maintenance on the boiler, the following
instructions are shown on the display:
In a yellow display:
4 The symbol ?
4 The symbol K
4 Maintenance message Z , B or c
Thanks to the automatically transmitted maintenance message, it is
possible to carry out preventive maintenance and therefore use the
maintenance kits defined by Remeha, thus reducing breakdowns to
a minimum. The maintenance message indicates which kit should be
used. These maintenance kits (A, B or C) are available from your
spare parts supplier. If no other faults are noted during the inspection
initiated subsequent to the maintenance message, these
maintenance kits include all of the parts needed for the maintenance
concerned (such as the gaskets, for example).
4
When a maintenance message is displayed, it must
be acted upon within the 2 months following the
appearance of the message.
4If the iSense modulating controller is connected to the
device, then this service message is also passed to
the iSense. In this way, the end user is requested to
contact the installation company. See also the manual
for the iSense controller.
040412 - 7600585-01
CAUTION
Reset the maintenance message to zero after each
inspection.
A service message on the boiler display must be reset by a qualified
installer after the maintenance service has been carried out using the
relevant service set and after this has been entered in the checklist
in the supplied service book. To do this, proceed as follows:
1. When the maintenance message is displayed, press key
time.
c0de
2. Use keys [-] or [+] to input the installer code
appears on the display.
0012
.
J
1
3. Confirm using key S. The maintenance message is reset. The
display returns to the current operating mode.
7.2.2.Dealing with the next maintenance
message and starting the new maintenance
period
For an interim service it is advisable to read out in the boiler service
menu what maintenance service should be carried out. Use the
indicated Remeha service sets (A, B or C). This service message
must be prevented by carrying out a reset. Start the next service
interval. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol \ flashes on the menu bar.
2. Press the S key.
operation
3600
3. Press key [+] several times until
4. Press the S key.
5. Use keys [-] or [+] to input the installer code
6. Confirm using key S.
7. Press key [+] several times until
example) flashing To determine the best time to carry out
maintenance, the boiler is fitted with a single automatic
maintenance indicator.
8. Press the [+] key a second time.
9. Press the S key.
10.Press key [+] to modify the value to 1.
and the number of hours of boiler
hr
(for example) are displayed alternately.
flashes on the menu bar.
K
c0de
cl[0
appears on the display.
0012
5c[B
cl
is displayed with B (for
appears on the display.
.
is displayed with 0 flashing.
11.Confirm using key S. The new maintenance period begins.
12.Press the
key 3 times to return to the current operating
>
mode.
After maintenance operations, fill in the corresponding
checklist in the maintenance log provided. Stick
maintenance sticker A, B or C from the maintenance kit
concerned in the maintenance log and inside the front
panel.
74
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
7.3Standard inspection and maintenance operations
CAUTION
During inspection and maintenance operations, always
replace all gaskets on the parts removed.
Before carrying out any work, check whether the boiler has
been adapted to one of the following situations:
4G20 (Gas H) or G31 (Propane)
4high pressure systems
4WTW coupling
4CLV overpressure (combusted gas discharge
systems)
See the sticker on top of the boiler next to the identification
plate.
7.3.1.Checking the hydraulic pressure
7. Checking and maintenance
The hydraulic pressure must reach a minimum of 0,8 bar. If the water
pressure is lower than 0,8 bar, the symbol e will appear.
If necessary, top up the water level in the heating system
(recommended hydraulic pressure between 1,5 and 2 bar).
7.3.2.Checking the ionization current
Check the ionization current at full load and low load. The value is
stable after 1 minute. If the value lies below 3 µA, replace the ignition
electrode.
¼ See chapter: "Reading the various current values", page 61.
7.3.3.Checking the transfer capacity
If the transfer capacity is noticably low (temperature too low and/or
flow rate less than 6,2 l/min), clean the plate exchanger (domestic hot
water side) and the water filter cartridge.
¼ See chapter: "Cleaning the plate exchanger (domestic hot
water end) and the water filter cartridge", page 79
040412 - 7600585-01
75
T001525-A
T001526-A
T001631-B
...x
7. Checking and maintenance
Calenta 25s - 28c - 35s - 40c
7.3.4.Checking the tightness of the flue gas
evacuation and air inlet connections
Check the tightness of the flue gases evacuation and air inlet
connections.
7.3.5.Checking combustion
The check on combustion is done by measuring the percentage of
O2/CO2 in the flue gas discharge flue. To do this, proceed as follows:
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
CAUTION
Ensure that the opening around the sensor is completely
sealed when taking measurements.
3. Set the boiler to full load. Press the two B keys simultaneously.
The B symbol is visible on the menu bar and
appears in the
h3
display. The boiler is now operating at full load.
4. Measure the percentage of CO2 and compare this value with the
checking values given.
See chapter: "Setting the air/gas
¼
ratio (Full load)", page 57.
5. Set the boiler to part load. Press the [-] key several times until
is displayed on the screen. The boiler is now operating on
l3
part load.
6. Measure the percentage of CO2 and compare this value with the
checking values given.
See chapter: "Setting the air/gas
¼
ratio (Part load)", page 59.
76
040412 - 7600585-01
R000074-B
6
5
5
5
4
90º
4
1
Gas/Gaz
23
Calenta 25s - 28c - 35s - 40c
7. Checking and maintenance
7.3.6.Checking the automatic air vent
1. Cut the power supply to the boiler.
2. Close the gas valve on the boiler.
3. Close the main gas inlet valve.
4. Unscrew the two screws located under the front panel by a quarter
turn and remove the panel.
5. Tilt the control box forwards by opening the holding clips located
at the sides.
6. Check whether there is any water in the small hose on the
automatic air vent.
7. If any leaks are detected, replace the air vent.
7.3.7.Checking the safety valve
1. Take out the flow collector located under the boiler.
2. Check whether there is any water in the end of the flow pipe on
the safety valve.
3. If any leaks are detected, replace the safety valve.
During inspection and maintenance operations, always
replace all gaskets on the parts removed.
1. Remove the air inlet flue on the venturi.
2. Unscrew the top connection on the gas valve unit.
3. Disconnect the connector located under the fan.
4. Release the 2 clips holding the fan/mixing elbow unit in place on
the heat exchanger.
5. Completely remove the fan/mixing elbow unit.
6. Tilt the burner and remove it, along with the heat exchanger
gasket.
7. Use a vacuum cleaner fitted with a special endpiece (accessory)
to clean the top part of the heat exchanger (combustion chamber).
8. Thoroughly clean with the vacuum cleaner again without the top
cleaning brush on the endpiece.
9. Check (using a mirror, for example) whether any dust can still be
seen. If so, hoover it up.
10.The burner does not require any maintenance, it is self-cleaning.
Check that there are no cracks and/or other tears on the surface
of the dismantled burner. If this is not the case, replace the burner.
11.Checking the ignition electrode / ionization sensor.
12.To re-assemble, perform the above actions in reverse order.
13.Open the gas inlet valves and reconnect the plug to the mains.
CAUTION
4Remember to reconnect the connector to the fan.
4Check that the gasket is correctly positioned between
the mixing elbow and the heat exchanger.
(Completely flat in the appropriate groove means it is
leak proof).
78
040412 - 7600585-01
T001528-A
1
2
3
Calenta 25s - 28c - 35s - 40c
7.4Specific maintenance operations
If the standard inspection and maintenance operations have revealed
the necessity to carry out additional maintenance work, proceed as
follows, depending on the nature of the work:
7.4.1.Replacing the ionization/ignition electrode
Replace the ionization/ignition electrode in the following cases:
4 Ionization current <3 µA.
4 Electrode worn.
4 Electrode available in the maintenance kit.
7. Checking and maintenance
CAUTION
After maintenance operations, fill in the corresponding
checklist in the maintenance log provided .
If replacement is necessary, proceed as follows:
1. Remove the cable from the ionization/ignition electrode on the
ignition transformer.
2. Unscrew the 2 screws and remove the ionization/ignition
electrode.
3. Replace the ionization/ignition electrode.
7.4.2.Cleaning the plate exchanger (domestic hot
water end) and the water filter cartridge
Depending on the water quality and the operating mode, limescale
deposits may form in the plate exchanger and the water filter
cartridge. Periodic descaling may therefore be necessary. As a
general rule, a periodic inspection, along with cleaning, if necessary,
is sufficient. The following factors may affect the periodicity:
If descaling of the plate exchanger is necessary, proceed as follows:
1. Close the main water valve.
2. Drain the boiler.
3. Remove the air vent hose above the siphon.
4. Remove the siphon.
5. Remove the clip holding the heating flow hose in place on the left
side of the hydroblock.
6. Dismantle the heating flow hose on the left side of the hydroblock
and not on the heat exchanger side (heating circuit).
7. Unscrew the 2 hexagonal socket screws located to the right and
left of the plate exchanger.
8. Slightly turn the plate exchanger and carefully remove it from the
boiler.
9. Clean the plate exchanger with a descaling product (e.g. citric acid
with a pH of approximately 3). To do this, a specific cleaning
appliance is available as an accessory. After cleaning, rinse
thoroughly under running water.
If cleaning or replacement of the water filter cartridge is necessary,
proceed as follows:
1. Close the main water valve.
2. Drain the boiler.
3. Remove the air vent hose above the siphon.
4. Remove the siphon.
5. Remove the clip holding the water filter cartridge in place. While
doing this, be sure that the silencer is left in place.
6. Remove the domestic water cartridge.
7. Rinse the water filter cartridge with tap water and, if need be, clean
it with a descaling product (e.g. citric acid with a pH of
approximately 3). After cleaning, rinse thoroughly under running
water.
8. Replace the water filter cartridge if faulty or when the maintenance
kit includes one.
fault is detected anywhere in the boiler, the boiler locks out and the
display will show the fault code as follows:
In a red flashing display:
4 The symbol c
4 The symbol J
4 The fault code (for example e[01)
The meaning of the error codes is given in the error table. To do this,
proceed as follows:
Error
code
e[00
e[01
e[02
e[03
4 Note the error code displayed.
The error code is important for rapid and correct tracking
of the type of problem and for any technical assistance from
Remeha.
4 Press the J key for 2 seconds. If the error code continues to
display, search for the cause in the error table and apply the
solution.
If the display does not show J but rather a, the boiler
must be switched off and then switched on again after 10
seconds before the fault can be reset.
DescriptionProbable causesChecking / solution
Storage unit PSU
parameter not found
The safety parameters
are incorrect
Flow temperature sensor
short circuited
Flow temperature sensor
open circuit
4Bad connection4Check the wiring
4Bad connection
4PSU defective
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4Check the wiring
4Replace PSU
4Check the wiring
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Replace the sensor if necessary
4Check the wiring
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Replace the sensor if necessary
040412 - 7600585-01
85
8. TroubleshootingCalenta 25s - 28c - 35s - 40c
Error
code
e[04
e[05
e[06
e[07
e[08
e[09
e[10
e[11
e[12
DescriptionProbable causesChecking / solution
4Check the wiring
4Replace the sensor if necessary
Temperature of heat
exchanger too low
Exchanger temperature
too high
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4No circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Check the cleanliness of the heat exchanger
Return temperature
sensor short circuited
Return temperature
sensor open circuit
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4Check the wiring
4Check that the sensor has been correctly fitted
4Check that the sensors are operating correctly
4Check the wiring
4Check that the sensor has been correctly fitted
4Check that the sensors are operating correctly
4Check the wiring
4Replace the sensor if necessary
Return temperature too
low
Return temperature too
high
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4No circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Check the cleanliness of the heat exchanger
4Replace the sensor if necessary
4Vent the air in the heating system
Difference between the
flow and return
temperatures too great
4Sensor fault
4Sensor not or badly
connected
4No circulation
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Check the cleanliness of the heat exchanger
4Check that the heating pump is operating correctly
4Check the wiring
4Replace the sensor if necessary
Temperature of heat
exchanger above normal
range (high-limit
thermostat STB)
4Bad connection
4Sensor fault
4Sensor not or badly
connected
4No circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
4Check the cleanliness of the heat exchanger
86
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c8. Troubleshooting
Error
code
e[14
e[16
e[17
e[34
e[35
e[36
e[37
DescriptionProbable causesChecking / solution
4Check cabling of ignition transformer
4Check the ionization/ignition electrode
4No ignition
4Check breakdown to earth
4Check the condition of the burner set
4Check the earthing
4Defective control SU PCB
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Check the supply pressure
5 burner start-up failures
4Ignition arc, but no flame
formation
4Check the operation and setting of the gas valve unit
4Check that the air inlet and flue gas discharge flues
are not blocked
4Check the wiring on the gas valve unit
4Defective control SU PCB
4Check that the gas valve is fully opened
4Presence of the flame
but insufficient ionization
(<3 µA)
4Check the supply pressure
4Check the ionization/ignition electrode
4Check the earthing
4Check the wiring on the ionization/ignition electrode
4Ionization current
present when there
False flame signal
should not be a flame
4Ignition transformer
defective
4Gas valve defective
4Check the ionization/ignition electrode
4Check the gas valve and replace if necessary
4Set the CO
2
4The burner remains very
hot: CO2 too high
Problem on the gas
valve SU PCB
Fan fault
4Bad connection
4Defective SU PCB
4Bad connection
4Fan defective
4Check the wiring
4Inspect the SU PCB and replace it if need be
4Check the wiring
4Replace the fan if need be
4Check for adequate draw on the chimney connection
4Bad connection
4Replace the sensor if necessary
4Check the circulation (direction, pump, valves)
4Check that the sensors are operating correctly
4Check that the sensor has been correctly fitted
Flow and return reversed
4Sensor fault
4Sensor not or badly
connected
4Water circulation
direction reversed
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Check the supply pressure
5x Flame loss
4No ionization current
4Check the operation and setting of the gas valve unit
4Check that the air inlet and flue gas discharge flues
are not blocked
4Check that there is no recirculation of flue gases
Communication error
with the SU PCB
4Bad connection
4Check whether the SU PCB has been correctly fitted
in the connector on PCU PCB
040412 - 7600585-01
87
T001632-B
8. TroubleshootingCalenta 25s - 28c - 35s - 40c
Error
code
e[38
e[39
e[40
DescriptionProbable causesChecking / solution
Communication error
with the SCU PCB
Shutdown input in
locked-out mode
HRU/URC unit test error
4Bad connection
4Defective SCU PCB
4Bad connection
4External cause
4Parameter incorrectly
set
4Bad connection
4External cause
4Parameter incorrectly
set
8.2Shutdowns and lock-outs
4Check the wiring
4Replace SCU PCB
4Check the wiring
4Suppress the external cause
4Check the parameters
4Check the wiring
4Suppress the external cause
4Check the parameters
8.2.1.Blockage
If the blocking conditions still exist after several start up attempts, the
boiler will switch into locking mode (fault). The boiler can only start
operating again once the causes of the lock-out have been rectified
and after pressing the > key.
8.2.2.Blocking
A (temporary) blocking mode is a boiler operating function caused by
an unusual situation. In this case, the display gives a code of blocking
(code 5t[9). The boiler control will try to re-start several times.
The boiler will start up again after the blocking conditions have been
eliminated. The shutdown codes can be read out as follows:
1. Press the two f keys simultaneously.
2. Confirm by pressing key S.
the shutdown code 9.
3. Press the [+] key.
appears on the display.
5v
is displayed, alternating with
5t
88
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c8. Troubleshooting
The boiler starts up again automatically when the reason
for the blocking has been removed.
Shutdown
DescriptionProbable causesChecking / solution
code
5v[0
5v[1
5v[2
5v[7
Parameter error
Maximum flow temperature
exceeded
Maximum increase of the
flow temperature has been
exceeded
Maximum difference
between the flow and return
temperature exceeded
4Parameter error on the
4Non-existent or
4Non-existent or
4Sensor error
4Non-existent or
4Sensor error
4External cause
5v[8
No release signal
4Parameter error
4Bad connection
4Mains supply incorrectly
5v[9
Phase and neutral of mains
supply mixed up
4Floating or 2 phase
4External cause
5v[10
Shutdown input is open
4Parameter error
4Bad connection
4External cause
5v[11
Shutdown input active or frost
protection active
4Parameter error
4Bad connection
4Bad connection with BUS
4SCU PCB not installed in
4Water pressure too low
5v[13
5v[14
Communication error with the
SCU PCB
Water pressure too low
4Non-existent or
5v[15
5v[16
5v[17
(1) These lock-outs are not stored in the fault memory
Gas pressure too low
Configuration fault or SU
(1)
PCB not recognised
Configuration fault or default
(1)
parameter table incorrect
4Incorrect setting of the
4Wrong SU PCB for this
4Parameter error on the
PSU PCB
insufficient circulation
insufficient circulation
insufficient circulation
wired
network
the boiler
insufficient circulation
Gps gas pressure switch
on the SCU PCB
boiler
PCU PCB
4Reset df and dV
4Restore parameters with Recom
4Check the circulation (direction, pump,
valves)
4Reasons for the heat demand
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check that the sensors are operating
correctly
4Check that the sensor has been correctly
fitted
4Check the cleanliness of the heat exchanger
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check that the sensors are operating
correctly
4Check that the sensor has been correctly
fitted
4Check the cleanliness of the heat exchanger
4Suppress the external cause
4Check the parameters
4Check the wiring
4Invert phase and neutral
4Set parameter p43 to 0
4Suppress the external cause
4Check the parameters
4Check the wiring
4Suppress the external cause
4Check the parameters
4Check the wiring
4Check the wiring
4Carry out automatic detection
4Check the water pressure
4Fill the boiler and the installation with water
4Check that the gas valve is fully opened
4Check the supply pressure
4Check whether the Gps gas pressure control
system has been correctly fitted
4Replace the Gps gas pressure control
system if need be
4Replace the SU PCB
4Replace the PCU PCB
040412 - 7600585-01
89
8. TroubleshootingCalenta 25s - 28c - 35s - 40c
Shutdown
code
5v[18
5v[19
5v[20
5v[21
5v[22
5v[25
(1) These lock-outs are not stored in the fault memory
DescriptionProbable causesChecking / solution
Configuration fault or PSU
(1)
PCB not recognised
Configuration fault or
(1)
parameters df-dV
unknown
Configuration procedure
(1)
active
Communication error with the
SU PCB
No flame during operation
Internal error on the SU PCB
4Wrong PCU PCB for this
4Active for a short time
4Bad connection
4No ionization current
boiler
after switching on the
boiler
4Replace the PCU PCB
4Reset df and dV
4No action required
4Check whether the PCU PCB has been
correctly fitted in the connector on SU PCB
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Check the supply pressure
4Check the operation and setting of the gas
valve unit
4Check that the air inlet and flue gas discharge
flues are not blocked
4Check that there is no recirculation of flue
gases
4Replace the SU PCB
8.3Error memory
The boiler control is equipped with an error memory. The last 16 errors
encountered are recorded in this memory.
In addition to the error codes, the following data are also saved:
4 Number of times that the error occured: (MK[xx).
4 Boiler operating mode selected (5t[xx).
4 The flow temperature (t1[xx) and the return temperature
(t2[xx) when the error occured.
To view the error memory, you first have to enter access code
0012.
90
040412 - 7600585-01
T001530-B
4x
2x
Calenta 25s - 28c - 35s - 40c
8. Troubleshooting
8.3.1.Error readout memorised
1. Press the two keys f simultaneously and then key [+] until the
symbol c flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Press the S key.
er[xx
appears on the display.
0012
5. The fault list or shutdown list can be displayed by pressing the
[-] or [+] key..
6. Confirm using key S.
er[xx
is displayed with
flashing = Last error which occured, For example
7. Use the [-] or [+] key to scroll through the faults or shutdowns.
8. Press the S key to display the details of the faults or shutdowns.
9. Press the [-] or [+] key to view the following information:
= Number of times that the error occured.
M[1
= The number of operating hours.
hr
= State.
5t
= Sub-status.
5v
= Supply temperature ºF/ºC.
t1
= Return temperature ºF/ºC.
t"
= Calorifier temperature ºF/ºC.
t3
= Outside temperature ºF/ºC (Only with an outside
t4
temperature sensor).
= Solar boiler temperature ºF/ºC.
t5
= Internal set point ºF/ºC.
5p
= Ionization current (µA).
fl
= Fan speed in rpm.
Mf
= Water pressure psig/bar.
pr
= Supplied relative heat output (%).
p;
10.Press the
displayed with
key to interrupt the display cycle.
>
flashing = Last error which occured.
xx
11.Use the [-] or [+] key to scroll through the faults or shutdowns.
12.Press the
13.Press
>
key to show the fault list or shutdown list.
>
times on the key 2 to exit the error memory.
appears
.
xx
.
K2
er[xx
is
040412 - 7600585-01
91
T000831-D
3x
4x
8. TroubleshootingCalenta 25s - 28c - 35s - 40c
8.3.2.Deletion of the error display
1. Press the two keys f simultaneously and then key [+] until the
symbol c flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Press the S key.
er[xx
appears on the display.
0012
5. The fault list or shutdown list can be displayed by pressing the
[-] or [+] key..
6. Confirm using key S.
er[xx
7. Press the [+] key several times until
is displayed with
er[cl
is displayed on the
screen.
8. Press the S key.
cl[0
is displayed with 0 flashing.
9. Press key [+] to modify the value to 1.
10.Press the S key to delete the errors from the error memory.
11.Press
times on the key 3 to exit the error memory.
>
xx
appears
.
flashing.
92
040412 - 7600585-01
Calenta 25s - 28c - 35s - 40c
9Spare parts
9.1General
9. Spare parts
When it is observed subsequent to inspection or maintenance work
that a component in the boiler needs to be replaced, use only original
spare parts or recommended spare parts and equipment.
Send the component to be replaced to the Returned Goods
Department at Remeha when the corresponding part falls under the
warranty terms (see the general terms and conditions of sale and
supply).
Always ensure that your return package is accompanied
by the duly completed return form, see attached
example. In this way, Remeha can more easily and more
effectively expedite its warranty obligations.
Customer
Reference
Name
Address
Town/Postcode
Telephone
Contact person
Order number
Code no.Description
(1) This information can be found on the rating plate.
Serial number
(1)
Date
Type Installation date Reason for the exchange Reference
All technical and technological information contained in these technical instructions,
as well as any drawings and technical descriptions supplied, remain our property
and shall not be multiplied without our prior consent in writing.
040412
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.