Reliable NS-ASAM, NS-Pak, Nitrogen Regulator Bulletin

Product Features
NS-ASAM
• Designed for two separate nitrogen or air sources
• Automatically switches between primary and secondary source
• Bypass valve provided for quick fill of system
• Low-pressure switch for primary source
• For use on single or multiple systems
• Keyhole slots provided for easy wall mounting
Bulletin 254 May 2019
Nitrogen Automatic Pressure
Maintenance Devices
NS-Pak
• For bottled nitrogen use on a single system
• Low-pressure switches for nitrogen source and system
• Bypass valve provided for quick fill of system
• Keyhole slots provided for easy wall mounting
Nitrogen Regulator
• For bottled nitrogen use on single or multiple systems
• Low-pressure switch for nitrogen source
General Description
Reliable Nitrogen Automatic Pressure Maintenance Devices are designed to connect nitrogen cylinders to dry pipe and preaction systems. The NS-ASAM is designed to connect a primary and secondary cylinder or bank of cylinders to sin­gle or multiple systems, and provides automatic switchover between sources. The NS-Pak is a self-contained unit for con­nection of a cylinder or bank of cylinders to a single system. The Nitrogen Regulator reduces cylinder pressure and can be connected to the A-2 Pressure Maintenance Device on single or multiple systems. Each device includes a low-pres­sure switch to signal that the nitrogen source is depleting and needs service. High-pressure cylinders (not included) can typically be obtained from a local source.
Model NS-ASAM
Model NS-Pak
Nitrogen Regulator
Model Product Description Listing and Approvals
NS-ASAM Nitrogen maintenance device with automatic switchover
NS-Pak
Nitrogen Regulator
Single system nitrogen maintenance device with high pressure
regulator
maintenance devices
www.reliablesprinkler.com
cULus Listed
FM Approved
cULus Listed
FM Approved
N/A
Model NS-ASAM
Technical Specifications
Threads: 1/2” NPT Min. Inlet Pressure: 100 psi (6.9 bar) Max. Inlet Pressure: 250 psi (17.2 bar) Min. Outlet Pressure: 10 psi (0.7 bar) Max. Outlet Pressure: 70 psi (4.8 bar)
Listings and Approvals
cULus Listed FM Approved
System Operation
Primary and secondary sources of nitrogen or air are con- nected to the primary and secondary inlets, respectively, of the Model NS-ASAM Pressure Maintenance Device. The primary and secondary nitrogen or air sources should sup- ply a recommended pressure of 120 psi (8.3 bar) to the NS-ASAM, although a minimum pressure of 100 psi (6.9 bar) up to a maximum pressure of 250 psi (17.2 bar) are permitted. The NS-ASAM will admit nitrogen or air from the primary source, until the primary source depletes to a pres- sure of approximately 80 psi (5.5 bar). Nitrogen or air from the secondary source is admitted through the NS-ASAM, when the pressure of the nitrogen or air supplied by the primary source is less than approximately 80 psi (5.5 bar). A pressure switch in the NS-ASAM is factory-set to activate at a pressure of 90 psi (6.2 bar) to indicate depletion of the primary source. The pressure switch includes an aux- iliary set of contacts that may be field adjusted to indicate loss of pressure from the secondary source. The system pressure may be set with the system pressure regulator of the NS-ASAM. A bypass valve is provided to rapidly intro- duce nitrogen or air into the system. Individual low-pressure switches (not provided) should be installed in the dry pipe or preaction valve trim to indicate low system pressure.
Model NS-ASAM Dimensions
Figure 1
Bulletin 254 May 2019
www.reliablesprinkler.com
Page 2 of 7
Model NS-ASAM Components
Figure 2
Installation and Adjustment
1. Securely mount the NS-ASAM enclosure to the wall using the keyhole slots.
2. Confirm that all valves are closed.
3. Securely mount and properly pipe the primary and sec- ondary sources of nitrogen or air in accordance with appropriate local, state, or federal standards.
4. Connect the primary source of nitrogen or air to the prima­ ry inlet of the NS-ASAM and connect the secondary source of nitrogen or air to the secondary inlet of the NS-ASAM.
5. Connect the NS-ASAM outlet to the port provided for pneu matic supply to the sprinkler system (see note 1).
6. Before applying pressure to the sprinkler system, turn the adjustment screw on the System Pressure Regulator within the NS-ASAM fully counterclockwise.
7. Adjust the primary and secondary sources of nitrogen or air to a recommended pressure of 120 psi (8.3 bar); the minimum required inlet pressure is 100 psi (6.9 bar) and the maximum rated inlet pressure is 250 psi (7.2 bar).
8. Open the Primary Inlet Valve and the Secondary Inlet Valve.
9. Open the Bypass Valve and the NS-ASAM Outlet Valve to allow nitrogen or air to flow into the system piping.
10. When the system pressure rises to within 2 psi (0.15 bar) of the required system pressure, fully close the Bypass Valve.
11. Slowly turn the adjustment screw of the System Pressure Regulator clockwise to increase pressure to the level required by the system. Tighten the lock-nut on the System Pressure Regulator (see note 2).
12. If desired, supervise the contacts of the Pressure Switch in accordance with NFPA 72 to provide notification that the primary nitrogen or air source is depleted. The auxiliary contacts of the pressure switch may also be supervised to indicate depletion of the secondary source of nitrogen or air. When supervising the auxiliary contacts, the primary contacts of the pressure switch should remain at the factory setting of 90 psi (6.2 bar) to indicate depletion of the primary source and the auxiliary contacts should be adjusted to a pressure setting of approximately 70 psi (4.8 bar).
13. If necessary, adjust the setting of the low-pressure switch for each system.
14. Use a soap solution at all joints to verify leak-tight connec- tions.
Notes:
1. When applying more that one system, each system must have an individual Pressure Maintenance Device.
2. For multiple systems, the NS-ASAM system regulator must be set a minimum of 5 psi above the highest system pres- sure required. Use the regulator on the Pressure Maintenance Device of each system to make final adjustment.
Bulletin 254 May 2019
www.reliablesprinkler.com
Page 3 of 7
Loading...
+ 4 hidden pages