Reliable GXLO User Manual

K11.2 (160 metric) (SIN R2921) Upright (SIN R2916) Pendent
Features
1. Upright cULus Listed as a Control Mode Density Area (CMDA) sprinkler for storage & non-storage protection.
2. Upright and Pendent FM Approved as Standard-response, storage and non-storage sprinklers.
3. Standard ¾-inch NPT or ISO 7-R¾ threads; optional ½-inch NPT or ISO 7-R½ threads for upright retrofit applications only.
Listings & Approvals:
The following organizations provide Listings or Approvals for Model GXLO sprinklers. See the Technical Data table for listing and approvals applicable to each sprinkler.
1. Underwriters Laboratories, Inc. and Underwriters Laboratories of Canada (cULus) - Upright only.
2. Approved by Factory Mutual (FM) as a storage and non-storage sprinkler - Upright and Pendent.
UL Guide Number
VNIV
UL Listing Category
Sprinklers, Automatic and Open; Sprinklers for Storage Protection (Control Mode Density Area)
Technical Data
Sprinkler
Type
Upright 0.64
Orifice with
¾” NPT (R¾)
Upright
Retrofit 0.64
Orifice with ½” NPT (R½) Pendent 0.64
Orifice with ¾” NPT (R¾)
Note: This product has been tested and listed for storage applications
Nominal K Factor
US Metric
11.2 160
11.2 160
11.2 160
to qualify its use in lieu of 5.6K or 8.0K Factor sprinklers for the protection of high-piled storage.
Sprinkler
Height
2.71”
(68.8mm)
2.82”
(71.6mm)
2.71”
(68.8mm)
Approvals
cULus, FM R2921
cULus, FM R2921
FM R2916
Sprinkler
Identification
Number (SIN)
Bulletin 129 May 2019
Model GXLO Standard Spray Standard Response
Storage and Non-storage Sprinkler
Model GXLO Upright Model GXLO Pendent
Design Criteria
The Model GXLO sprinkler is intended for use as a standard response standard spray sprinkler in hydraulically designed sprinkler systems with a minimum pressure of 7 psi (0.5 bar) in accordance with the area/density curves of NFPA 13 or in ac­cordance with FM Property Loss Prevention Data Sheets.
The Model GXLO sprinkler is not a “Large Drop” or “ESFR” sprinkler.
Temperature Ratings
Sprinkler
Classification
Ordinary
Intermediate
High
Rating
°F °C °F °C
165 212 286
Optional Guards and Water Shields
Sprinkler Guard or Water Shield
D-6 Guard & Water Shield cULus
GXLO
Upright
D-7 Guard & Water Shield
Water Shield
(factory installed)
GXLO
Pendent
D-9 Guard & Water Shield
D-8 Guard
Maximum Ambient
Temperature
74 100 141
100 150 225
38 66
107
Listings & Approvals
FM
FM
Frame
Color
Uncolored
White
Blue
Bulletin 129 May 2019
Product Description
The Reliable Model GXLO sprinkler is a center strut, solder in compression, extra large orifice sprinkler that has been de­signed for storage and non-storage applications. The Model GXLO sprinkler is available in either an upright or pendent con­figuration. The Model GXLO sprinkler is available with either 3/4-inch NPT or ISO 7-R3/4 threads. The Model GXLO Upright is optionally available with either 1/2-inch NPT or ISO 7-R1/2 threads for retrofit applications only.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Installation
Reliable’s Model GXLO sprinkler must be installed according to NFPA Standards or the appropriate Factory Mutual Loss Pre­vention Data Sheets for all area/density methods of design as well as requirements of the Authority Having Jurisdiction.
Model GXLO sprinklers must be installed with the Reliable Model H sprinkler wrench. Any other type of wrench may dam­age the sprinkler.
A leak tight joint should be obtained with a torque of 14 to 20 lb-ft (19 to 27 N-m) for ¾-inch NPT and ISO 7-R¾ thread sprinklers. For ½-inch NPT and ISO 7-R½ thread sprinklers the recommended installation torque is 8 to 18 lb-ft (11 to 24 N-m). Do not tighten sprinklers over the maximum recommended in­stallation torque, because it may cause leakage or impairment of the sprinklers.
Model H Wrench
Use only the Model H sprinkler wrench for sprinkler removal and installation. Any other type of wrench may damage the sprinkler.
Maintenance
Model GXLO Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Replace any sprinkler which has been painted (other than fac­tory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation.
Ordering Information
Specify:
1. Sprinkler: Model GXLO
2. Orientation: [Upright] [Pendent]
3. Temperature Rating: [Ordinary, 165°F] [Intermediate, 212°F] [High 286°F]
4. Finish: (See Finishes Chart)
5. Threads: [¾-inch NPT] [ISO 7-R¾] [½-inch NPT (Up­right only)] [ISO 7-R½ Upright only]
6. Optional Guard or Water Shield
Finishes
Standard Finishes
Bronze
(1)
Chrome
Special Application Finishes
(1) (2)
(1) (2)
(1)
- 165°F (74°C), 212°F (100°C) and 286°F (141°C) Temp. Ratings
- 165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax
- 165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax
Lead Plated
Wax
Wax/Lead
(1)
cULus, upright (without shield) only.
(2)
212°F (100°C) Brown wax may be used on 286°F (141°C) Sprinklers
when maximum ambient temperatures do not exceed 150°F (66°C).
Fig. 1