Reliable F1 Res 30 LL, F1 RES LL Series, F1 Res 49 LL, F1 Res 58 LL, F1 Res 44 LL User Manual

Bulletin 033 February 2019
Model F1 RES LL Residential Sprinklers
Specifically Listed for use in Multipurpose Systems that serve both domestic water and fire protection.
Types:
1. F1 Res 30 LL Pendent
2. F1 Res 30 LL Recessed Pendent/F2
4. F1 Res 49 LL Pendent
5. F1 Res 49 LL Recessed Pendent/F1
7. F1 Res 58 LL Pendent
8. F1 Res 58 LL Recessed Pendent/F1
10. F1 Res 30 LL CCP Pendent
11. F1 Res 49 LL CCP Pendent
12. F1 Res 58 LL CCP Pendent
13. F1 Res 44 LL HSW
14. F1 Res 44 LL Recessed HSW/F2
15. F1 Res 58 LL HSW
16. F1 Res 58 LL HSW Recessed HSW/F2
17. F1 Res 44 LL SWC
F1 Res 49 LL & 58 LL Recessed
Pendent / F1, F1 R es 3 0 LL
Recessed Pendent/F2
F1 Res 30 LL, 49 LL, & 58
LL Recessed Pendent/FP
Bulletin 033 February 2019
F1 Res 30 LL, 49 LL & 58 LL
Pendent
F1 Res 30 LL, 49 LL & 58 LL
CCP Pendent
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) for Safety to ANSI/ UL1626.
2. Certified by Underwriters Laboratories, Inc. and Under­writers Laboratories of Canada for Health Effects to NSF/ ANSI Standard 61 Annex G (Less than 0.25% Lead Con­tent.)
3. WaterMark certified. WaterMark Certificate Number 23347
F1 Res 44 LL & 58 LL
HSW
Additional Bulletins applicable to all F1RES LL Sprinklers
• Wall Wetting - Bulletin 007
• Design and Installation - Bulletin 140
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49 LL & 58 LL Pendent Sprinklers Other patents pending.
F1 Res 44 LL & 58 LL
Recessed HSW/F2
F1 Res 44 LL
SWC
Product Description
Model F1 Res LL Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast response sprinklers combining excellent durability, high sensitivity glass-bulb and low profile decorative design. The F1 Res LL Horizontal Sidewall sprinklers (Figs. 5, & 6) are equally attractive when above ceiling piping cannot be used.
The 3mm glass-bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in resi­dential fire protection design.
The low flow F1 Res LL sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection application needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire.
Technical Data:
• Thermal Sensor: Nominal 3mm glass-bulb
• Sprinkler Frame : Brass
• Sprinklers’ Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: ½” NPT (R½)
• K-Factor: 3.0 (Actual) - F1 Res 30 LL Pendent Sprinkler
4.9 (Actual) - F1 Res 49 LL Pendent Sprinkler
5.8 (Actual) - F1 Res 58 LL Pendent & HSW Sprinkler
4.4 (Actual) - F1 Res 44 LL HSW Sprinkler
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model F1 Res LL sprinklers are cULus Listed in accor­dance with UL 1626 for installation in accordance with NFPA 13, NFPA 13R, and NFPA 13D. Sprinkler systems using Model F1 Res LL sprinklers must be hydraulically designed to provide at least the flow identified in the Tech­nical Data tables in this bulletin. For NFPA 13 installations, the flow per sprinkler must be the greater of: (1) the flow listed in the applicable Technical Data table and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. For cover­age area dimensions less than those listed in the Technical Data tables, use the minimum required flow for the next larger max. coverage area listed.
Model F1 Res 30 LL, 49 LL & 58 LL Pendent
Installation
Models F1 Res LL sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are the only recessed escutcheons to be used with Model F1 Res LL sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin­kler Wrench; for installing Models F1 Res LL Recessed
Model F1 Res 30 LL Recessed Pendent / F2
Model F1 Res 49 LL & 58 LL Recessed Pendent / F1
Fig. 1
Pendent, CCP & SWC sprinklers use only the Model GFR2 sprinkler wrench; for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench. Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 LL with a ceiling to de­flector distance of 4” - 12”. Flow arrow on deflector must point away from near wall and “Top” marking must face ceiling.
F1 escutcheon, 3/4” (19mm) adjustment
Fig. 2
Escutcheon*, F1 or F2, Data:
Type
F1 3/4 (19.0)
F2 1/2 (12.7)
* Note: Escutcheons F1 or F2 may be used with Model F1 Res 49 LL & 58 LL Recessed Pendent Sprinkler
Adjustment
Inch (mm)
“A”
Inch (mm)
Min.=3/4” (19.1)
Max.=11/2” (38.1)
Min.=15/16” (23.8)
Max.=11/2” (38.1)
Face of fitting
to ceiling
Inch (mm)
3
/16 - 15/
(4.7 - 24.0)
3
/16 - 11/
(4.7 - 17.4)
16
16
2.
Technical Data: F1Res 30 LL Pendent and Recessed Pendent (SIN RA3311)
Thread
Size
½” NPT
(R½)
Max. Coverage area
Ft x Ft (m x m)
12 x 12 (3.6 x 3.6) 12 (3.6) 8 (30.3) 7.0 (0.48) 8 (30.3) 7.0 (0.48)
14 x 14 (4.3 x 4.3) 14 (4.3) 10 (37.8) 11 (0.76) 10 (37.8) 11 (0.76)
16 x 16 (4.9 x 4.9) 16 (4.9) 13 (49) 18.8 (1.3) 13 (49) 18.8 (1.3)
Nominal Orifice
Inch (mm)
21
/64” (8.2) 175 (12)
Max.
Spacing
Ft (m)
Max. Pressure
Sprinkler Temp. Rating Max. Ambient Temp. Actual K
psi (bar)
155 175
Ordinary Temp. Rating
(155°F/68°C)
Flow
GPM (L/min)
Pressure
PSI (bar)
°F °C °F °C
68 79
100 38 3.0 (43.2) 2.25 (57)
Intermediate Temp. Rating
(175°F/79°C)
Flow
GPM (L/min)
Pressure
PSI (bar)
Technical Data: F1Res 49 LL Pendent and Recessed Pendent (SIN RA3316)
Thread
Size
½” NPT
(R½)
Nominal Orifice
Inch (mm)
7
/16” (11) 175 (12)
Max.
Pressure
psi (bar)
Ordinary Temp. Rating
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
(155°F/68°C)
Flow
GPM (L/min)
12 x 12 (3.6 x 3.6) 12 (3.6) 13 (49) 7.0 (0.48) 13 (49) 7.0 (0.48)
Sprinkler
Temp. Rating
Max.
Ambient Temp.
°F °C °F °C
155 175
68 79
100 150
Intermediate Temp. Rating
(175°F/79°C)
Pressure
PSI (bar)
Flow
GPM (L/min)
38 66
Pressure
PSI (bar)
Sprinkler Length
Factor
Inch (mm)
Top of Deflector to Ceiling
Inch (mm)
Smooth Ceilings 1” to 4”
(25mm to 100mm)
Beamed Ceilings per NFPA 13,
13D, or 13R
Actual
K
Factor
4.9 (70.6) 2.25 (57)
Sprinkler
Length
Inch (mm)
Top of Deflector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
8 (2.4)
Minimum
Spacing
Ft (m)
14 x 14 (4.3 x 4.3) 14 (4.3) 13 (49) 7.0 (0.48) 13 (49) 7.0 (0.48)
16 x 16 (4.9 x 4.9) 16 (4.9) 13 (49) 7.0 (0.48) 13 (49) 7.0 (0.48)
18 x 18 (5.5 x 5.5) 18 (5.5) 17 (64.3) 12 (0.83) 17 (64.3) 12 (0.83)
20 x 20 (6.1 x 6.1) 20 (6.1) 20 (75.7) 16.7 (1.14) 20 (75.7) 16.7 (114)
Ordinary Temp. Rating
Max. Coverage area
Ft x Ft (m x m)
12 x 12 (3.6 x 3.6) 12 (3.6) 15 (57) 9.4 (0.65) 15 (57) 9.4 (0.65)
14 x 14 (4.3 x 4.3) 14 (4.3) 16 (60.5) 10.6 (0.73) 16 (60,5) 10.6 (0.73)
16 x 16 (4.9 x 4.9) 16 (4.9) 17 (64.3) 12.0 (0.83) 17 (64.3) 12.0 (0.83)
18 x 18 (5.5 x 5.5) 18 (5.5) 19 (72) 15.0 (1.0) 19 (72) 15.0 (1.0)
20 x 20 (6.1 x 6.1) 20 (6.1) 22 (83.2) 20.2 (1.4) 22 (83.2) 20.2 (1.4)
Max. Spacing
Ft (m)
(155°F/68°C)
Flow
GPM (L/min)
Pressure
PSI (bar)
Intermediate Temp. Rating
(175°F/79°C)
Flow
GPM (L/min)
Pressure
PSI (bar)
Smooth Ceilings 1” to 4”
(25mm to 100mm)
Beamed Ceilings per NFPA
13, 13D, or 13R
Top of Deflector
to Ceiling
Inch (mm)
Smooth Ceilings 4” to 8”
(100mm to 200mm)
8 (2.4)
Minimum
Spacing
Ft (m)
8 (2.4)
3.