Reliable F1FR 300 QREC Bulletin

300 psi (20,7 bar) Rated Concealed Quick Response Extended Coverage Sprinkler to 20’ x 20’ (6.0m x 6.0m)
Features
1. Quick response performance.
2. Push on, thread off, sturdy convenient cover plate.
3. Factory assembled sprinkler and cup, shipped complete with protec­tive cap.
4. Sprinkler assembly and cover plate separately packaged.
5. Two Versions:
• ½” (13mm) Adjustment
5
/
” (8mm) Adjustment
16
6. Rugged damage resistant assembly. No exposed thermal element.
7. Utilizes the Model F1FR-300 QREC Pendent Sprinkler.
8. Aesthetic ceiling profile.
9. Standard finishes in white painted or chrome plated. Other color-painted and specialty finishes available.
For Model F1FR-300 QREC CCP ½” K 5.6 (80) Sprinkler Types refer to Bulletin 030 for technical specifications and approvals.
Product Description
The Reliable Model F1FR-300 QREC Quick Response Ex­tended Coverage Concealed Sprinkler is an attractive, low profile concealed sprinkler assembly. This sprinkler assembly utilizes a Model F1FR-300 QREC pendent sprinkler in a Model CCP cup and push-on thread-off cover plate assembly. The cup is securely factory threaded on the sprinkler’s inlet end. The as­sembly is shipped with a protective cap. The sprinkler and cup are easily installed into the sprinkler fitting using the Model GFR2 Sprinkler Wrench. The cover plate assembly is attached to the sprinkler cup using a flexible tooth threaded engagement. The cover plate is attached to the skirt using 135°F (57°C) ordinary temperature classification solder.
Bulletin 167 March 2019
Model F1FR 300 QREC CCP 300 psi (20,7 bar) Rated Concealed Quick Response Extended Coverage Sprinkler
When the ceiling temperature rises, the solder holding the cover plate melts, allowing the release of this part and thus ex­posing the Model F1FR-300 QREC sprinkler inside to the rising ambient temperature.
The Model F1FR-300 QREC automatic sprinkler utilizes a 3.0 mm frangible glass bulb. This sprinkler has demonstrated re­sponse times in laboratory tests which are five times faster than standard response sprinklers. This quick response enables the Model F1FR-300 QREC sprinkler to apply water to a fire faster than standard sprinklers of the same temperature rating.
Technical Data:
K Factor
Nominal
Orifice
17
32
/
” (20mm) ¾” (R¾) 8.0 115.3 1,2,3 R5942
Thread
Size
¾” NPT
(R¾)
¾” NPT
(R¾)
Flow Rate gpm (L/m)
26 (98.4) 33 (125.0) 40 (151.4)
(1)
135°F (57°C) Only
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Thread
Size
Model
F1FR-300
QREC
F1FR-300
QREC
Pressure
psi (bar)
(Metric 115.3)
10.6 (0,7)
17.0 (1,2)
25.0 (1,7)
Approval
US Metric
Temp. Rating Max.
Sprinkler Cover
135°F
57°C
155°F
68°C
Coverage Area
K=8.0
Organizations
135°F
57°C
135°F
57°C
Max. Enclosure Area Width x
20 x 20
Length
ft. x ft. (m x m)
16 x 16 (4.9 x 4.9)
18 x 18 (5.5 x 5.5)
(1)
Application and Installation
Ceiling
Temp.
100°F
38°C
100°F
38°C
(6.0 x 6.0)
Sprinkler
Ident.
Number
(SIN)
Bulb
Color
Orange
Red
(1)
Bulletin 167 March 2019
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR-300 QREC Concealed Sprinklers use 135°F (57°C) or 155°F (68°C) Model F1FR-300 QREC Pendent Sprin­klers with a threaded Model CCP cup which is factory attached to the sprinkler. The assembly is completed by the installation of the attractive, low profile, 135°F (57°C) rated cover plate assem­bly. The cover plate and sprinkler cup are joined using a flex­ible tooth threaded engagement. A choice of two cover plate assemblies provides either ½” (13mm) or
5
/
” (8mm) of cover
16
adjustment.
Do not install these sprinklers in ceilings which have positive pressure in the space above.
The ¾” NPT (R¾) sprinkler cup is factory attached to the Mod­el F1FR QREC Sprinkler. A Teflon*-based thread sealant should be applied to the sprinkler threads only.
After a 2
5
/
inch (67mm) diameter hole is cut in the ceiling,
8
the sprinkler is easily installed with the Model GFR2 Wrench. When installing a sprinkler, the protective cap is removed and the wrench is positioned into the sprinkler/cup assembly until the two wrench faces engage the wrenching flats on the Model F1FR QREC Sprinkler. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent dam­age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The cover plate assembly is then pressed into the cup. Final adjustment is made by turning the he ceiling surface. Cover plate removal requires turning in the
* DuPont Registered Trademark.
counter clockwise direction.
After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover plate/cup assembly with the Model F1FR-300 QREC Pendent Sprinkler or the use of the Model CCP concealed cover plate assembly on any sprinkler with which it is not specifically listed may prevent good fire protection and will void all guarantees, warranties, listings and approvals.
Maintenance
Model F1FR-300 QREC Concealed Sprinklers should be in­spected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, am­monia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate assembly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation.
Approval Organizations
1. Underwriters Laboratories, Inc.
(UL)
2. Underwriters’ Laboratories of
Canada (ULC)
3. NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic and Open. Quick Response Extended Cover­age Sprinklers.
Ordering Information
Specify:
1. Sprinkler Model:
F1FR-300 QREC Pendent
17
32
/
” (20mm) Orifice, ¾” NPT
(R¾).
2. Sprinkler Temp. Rating:
135°F (57°C)
3. Cover plate Model: CCP
4. Cover plate thread size:
¾” NPT (R¾).
5. Cover plate temp. rating:
135°F (57°C).
6. Cover plate adjustment:
Either ½” (13mm) or (approximate adjustment).
7. Cover plate finish.
(1)
135°F (57°C) required for
20’ x 20’ (6.0m x 6.0m).
(1)
or 155°F (68°C).
5
16
/
” (8mm)
Installation Wrench
Model GFR2 Sprinkler Wrench
Installation Aid
A protective cap is included for use during installation.
Cover Plate Finishes
Standard Finishes
Chrome White
Special Application Finishes
Bright Brass Black Plating Black Paint Off White Satin Chrome
(1)
Other finishes and colors are available on special order. Consult factory for details. Note: Paint or any other coatings applied over the factory finish will void all approvals and warranties.
(1)
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 03/19