Reliable DDX PrePaK D Instructions For Installation, Operation Care And Maintenance

Bulletin 733 Rev. F
Bulletin 733 Rev. F
Model DDX PrePaK, Type D Preaction System 4”(100mm), 6” (150mm) & 8” (200mm)
Instructions for Installation, Operation, Care and Maintenance
10 PSI (0.7 bar) Pneumatic Supervising Pressure
Single Interlock - Electric Release Double Interlock - Electric/Electric Release
Contents Page
General Description 2
Listings and Approvals 4
Technical Data 4
Installation Requirements 5
System Operation 5-6
System Reset Procedure 6
Inspection, Testing and Maintenance 6-7
Diagrams:
Assembly Dimensions 3
Potter PFC-4410-RC Releasing Control Panel 8
Terminal Box Wiring 9
Factory Installed Electrical Devices 10-11
Detector Circuit Wiring 12-13
Output Device Wiring 14
Component Identification/System Setup 15-16
Potter Panel Programming 17-26
Ordering Information 27-28
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
General Description
The Reliable Model DDX 4” (100 mm), 6” (150mm) & 8” (200mm) PrePaKs are completely self-contained, supervised preaction systems that can be readily installed within a floor space of 5.15ft for the 8” (not including door swing). Installation of the PrePaK (not including exterior devices, i.e., detectors and alarm bells), requires just three piping connections. These connections are the water supply, the sprinkler system, and the drain. Reference locations of these piping connections are shown in Fig.1. Also, two 120 / 220 VAC electrical supply connections are required. Note: The Model DDX PrePak is available with an optional air compressor and an optional Potter Model PFC-4410-RC Re­leasing/Control Panel wired for a 120 VAC / 60Hz or 220 VAC / 50 Hz power supply.
Figures 16, 17, and 18 in this Bulletin identify the standard and optional equipment available in Reliable Model DDX PrePak, Type D, Preaction Systems.
The Reliable Model DDX PrePaK utilizes an optional Potter Model PFC-4410-RC Releasing Control Panel. This fully pro­grammable, microprocessor-based releasing panel is Under­writers Laboratories, Inc. Listed and is in compliance with NFPA 13 and NFPA 72. Because the PFC-4410-RC is totally zone and output programmable, the Reliable Model DDX PrePaK can be utilized in many different preaction applications without having to rewire any of the factory installed devices. Once the previ­ously described connections are completed, the 24 VDC detec­tors, output devices, and relay contacts may be connected to achieve the desired system implementation.
The Model DDX PrePaK can be used in both single and dou­ble interlock applications. Reliable Single and Double Interlock Preaction Systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping.
The major benefits of a single/double interlock preaction Sys­tem, when compared with a wet pipe system, are as follows:
A. A fire alarm sounds prior to the flow of water from a sprin-
kler, which may enable extinguishing the fire by handheld means before the operation of any sprinkler occurs.
B. An annunciator signals whenever the integrity of piping or
sprinklers is accidentally or intentionally disturbed; howev­er, no water flow occurs at that time.
C. Detection and notification of a fire condition are provided
by fire detectors, without the delay associated with water delivery time in the event of a fire. Note that with a wet pipe system, the fire alarm is delayed until after water has begun flowing from an operated sprinkler.
In single interlock applications, one fire detector senses the presence of fire, thereby causing the electrical releasing control panel to activate notification appliances and energize the sole­noid releasing valve in the open position. The use of cross-zoned detectors will require operation of two detectors before the so­lenoid valve can open (Note: Verify that the detection method, including the use of cross-zoned detection, are permitted by all applicable codes and standards, as well as the requirements of all authorities having jurisdiction. Cross-zoned detection may not be permitted in New York City or by Factory Mutual.) The
2
(0.44 m2) for the 4” and 6” and 7.5ft2 (0.70m2)
solenoid valve, when closed, preserves supply water pressure in the Model DDX valve’s push-rod chamber. Actuating the sole­noid valve releases that water pressure which allows the Model DDX valve to open.
To discharge water from sprinklers on a single interlock system with cross-zoned detection, two separate electrical detection systems must activate and a sprinkler must open. During the early stages of a fire, smoke or heat activates the first detector, which causes the control panel to produce a local alarm and an alarm at the fire alarm panel. Electrical relays inside the releasing control panel can be used to shut down air moving equipment or activate security doors and other electrical devices when the panel goes into this first condition. Subsequent activation of a second, nearby or adjacent detector, on a separate detection system, will cause the panel to energize the solenoid valve open and release water into the sprinkler piping. Water flowing into the sprinkler piping will simultaneously produce water pressure that cause the transfer of contacts in the alarm pressure switch mounted in the riser assembly, thereby activating a water flow alarm device. The flow of water into the sprinkler piping effec­tively converts the dry system into a wet-pipe sprinkler system. In the event that the fire subsequently produces sufficient heat to operate a sprinkler, water will flow from that sprinkler.
To flow water into a double interlock preaction system, two events must take place: a fire detection device must operate, and a pressure switch must be operated by the loss of system pressure (sprinkler operation). These two signals, both an elec­tric signal from the detection system and an electrical signal from the pressure (pneumatic) sensor, must coexist at the re­leasing control panel, which only then will energize the solenoid releasing valve, causing water flow into the sprinkler system and out of the open sprinkler(s).
In the event that the system piping is ruptured or a sprinkler is accidentally opened, the system pressure switch will oper­ate and an alarm will sound. The Model DDX, Type D Valve as­sembly, however, will not release water since the solenoid valve remains closed due to only one input into the releasing control panel.
When using the Reliable Model DDX PrePaK, in either single or double interlock applications, the sprinkler system is pressur­ized (supervised) with air provided by the air compressor and is monitored by a system pressure switch. Alternatively, super­visory system pressure may be provided by a nitrogen source.
A Model B Hydraulic Manual Emergency Releasing station is standard equipment in the Model DDX PrePaK. It consists of an aluminum nameplate mechanically attached to a ball valve. The valve handle in its OFF position is guarded against accidental turning to the ON position (and system discharge) by a nylon cable tie provided with the PrePaK assembly. The cable tie is designed to allow, in case of an emergency, forceful turning of the valve handle to the ON position.
2.
Fig. 1
3.
Approvals
1. Underwriters Laboratories, Inc. Listed and Certified for Canada* (cULus) as an assembled unit in the “Special System Water Control Valves Assembled Units” category, (VKYL).
2. Factory Mutual (FM) Approved, as PrePak Single Interlock and Double Interlock Preaction Systems.
* Electrical devices and control panel must be specified
to meet Canadian requirements. This option is avail­able.
3. Approved for use in New York City based on UL Listing.
Note: Although PrePak units are UL Listed, custom built units are sometimes supplied upon request. The components within these special units maintain their individual Listings/Approvals, whereas the assembled units do not.
PrePak units are also available without their door-mounted Pot­ter PFC-4410-RC Releasing/ Control Panel and Air Compressor. These units will still retain their Listings/Approvals, however the installing contractor should make sure that any remote controlled Releasing/Control Panels used with these units are Listed/Ap­proved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system. Any unauthorized modification or addition made on-site to a factory-built Listed/Approved unit will void the Listing/Approval. Such modifications or additions may void the unit’s warranty as well. Consult Reliable’s Technical Services Department before proceeding with any such modifications or additions.
Technical Data
1. The Reliable Model DDX 4” (100 mm), 6” (150 mm) and 8”
(200mm) PrePaKs are rated for a minimum supply pres­sure of 20 psi (1.4 bar) and a maximum supply pressure of 250 psi (17.2 bar). Note: 1 bar = 100 kPa.
2. Friction loss, expressed in equivalent length of Schedule 40
pipe and based on Hazen-Williams Formula with C=120 and a flowing velocity of 15 ft/s (4.6 m/s), is:
System Size Equivalent Length
4” (100 mm) 32.8 ft (17.7 m) 6” (150 mm) 54.7 ft (21.8 m)
8” (200mm) 79.3ft (24.2m)
These values account for the Model DDX valve, supply manifold tee, butterfly control valve, and small pipe/mani­fold located directly above Model DDX valve.
3. Shipping Weight:
System Size Weight
4” (100 mm) 680 lbs (308 kg) 6” (150 mm) 770 lbs (349 kg)
8" (200mm) 1350lbs (531kg)
4. Dimensions:
System Size Cabinet Dimensions
4” (100 mm) & 6” (150 mm)
8” (200mm)
25.7” W x 28.9” D x 68” H
(0.65 m W x 0.73 m D x 1.73 m H)
30” W x 36 D x 74” H
(0.76m W x 0.91m D x 1.88m H)
5. Grooved-End Connections:
Pipe Size
4” (100mm)
6” (150mm)
8” (200 mm)
Pipe Size
2” (50mm)
Groove Dimensions (Inlet & Outlet)
Outlet
Diameter
4.500”
(114mm)
6.625’
(168mm)
8.625”
(219mm)
Groove
Diameter
4.334”
(110mm)
6.455”
(164mm)
8.441”
(214mm)
Groove
Width
3/8”
(10mm)
7/16” (11mm)
Groove Dimensions (Drain Manifold)
Outlet
Diameter
2.375”
(60mm)
Groove
Diameter
2.250”
(57mm)
Groove
Width
5/16”
(8mm)
Outlet Face to Groove
5/8”
(16mm)
3/4”
(19mm)
Outlet Face to Groove
5/8”
(16mm)
6. Flanged-End Connections:
Flange Dimensions (Inlet & Outlet)
System
size:
8”
(200mm)
Flange
Type
ASME B16.5 Class
150
Bolt
Circle
Diameter
11¾”
(298mm)
Bolt
Hole
Diameter
7/8”
(22mm)
Flange
Outside
Diameter
13½”
(343mm)
Flange
thickness
1”
(25.4mm)
Number
of Bolts
8
Flange Dimensions ( Drain)
System
(200mm)
size:
8”
Flange
Type
ASME B16.5 Class
150
Bolt
Circle
Diameter
4¾”
(120mm)
Bolt Hole Diameter
Flange
Outside
Diameter
3/4”
(19mm)6” (150mm)
Flange
thickness
3/4”
” (19mm)
Number of Holes
4
The following is a list of Technical Data Bulletins which de-
scribe the valves and devices which are used in the system:
Device
Model DDX Deluge Valve Reliable Bulletin 519 Type D Double Interlock Preaction Trim Low Air Pressure Switch Potter 5400928 Alarm Pressure switch Potter 5400928 Nitrogen Pressure Switch Potter 5400930 Mechanical Sprinkler Alarm Reliable Bulletins 612/613 Solenoid Valve Reliable Bulletin 718 Releasing Control Panel Potter Manual #5403550 Fire Alarm Devices Reliable Bulletin 700
Desiccant Dryer
Reliable Bulletin #
(unless otherwise noted)
Reliable Bulletin 750
Wilkerson Catalog 9EM-
TK-190-4
The following table provides a quick reference to various pro­grams (found in this bulletin and the Potter Manual #5403550) that may be utilized with a Model DDX PrePaK:
Desired
Applications
Single Interlock
Single Interlock,
Cross-Zoned
(1)
Refer to Potter Manual # 5403550 included with the PrePak, for other
programming options available.
(2)
Factory Program setting.
(1)
Single Hazard, Cross-Zoned, 2
Zone and 2 Supervisory Zones
Description
Single Hazard, 2 Alarm Zones
with 1 Waterflow Zone and 2
Supervisory Zones
Alarm Zones with 1 waterflow
Program
No.
Potter
Program #6
Custom
Program #1
(NYC)
Potter
Program #7
(2)
4.
Installation Requirements
The automatic sprinklers, releasing devices, fire detection devices, manual pull stations, and signaling devices which are utilized with the Reliable Model DDX 4” (100 mm), 6” (150 mm) and 8” (200 mm) PrePaKs must be UL and/or ULC Listed or FM Approved, as applicable.
The steel enclosure and all the interconnecting piping must be located indoors in a readily visible and accessible location and in an area that can be maintained at a minimum tempera­ture of 40°F (4°C). Note: Heat tracing is not permitted. The so­lenoid valve is operated and supervised by the Potter Model PFC-4410-RC Releasing Control Panel. Details on the electrical connections of this system to the Potter Panel can be found in the Potter Manual #5403550, Installation, Operation and Instruc­tion of PFC-4410-RC Releasing Control Panel (this manual is included with other pertinent manuals and shipped inside the enclosure). This panel is fully zone and output programmable and may be adapted to several applications.
System Supervising Pressure Requirements
In accordance with NFPA 13, when using the Reliable Mod­el DDX 4” (100 mm), 6” (150 mm) or 8” (200 mm) PrePaK in double interlock applications, a minimum of 7 psi (0.5 bar) pneumatic pressure is required to supervise the sprinkler sys­tem. When initially filling the system with air, the enclosure’s door should remain open in order to provide maximum intake air flow to the air compressor. The air compressor is connected to an 8 gallon (30.3 liter) ASME rated storage tank. This tank functions as a reservoir, providing make-up air to compensate for small, intermittent leaks in the sprinkler system. It should be noted that significant leaks may overburden this storage tank, thereby causing the air compressor to continuously cycle on and off.
The Pressure Maintenance Device supplied with the system (refer to Fig. 9 or 10), is factory set to maintain system pneu­matic pressure at approximately 10 psi (0.7 bar). Readjusting system pressure to approximately 10 psi (0.7 bar), if necessary, is accomplished by first loosening the locknut on the air pres­sure regulator and turning the adjustment screw (refer to Fig. 9 or 10). The system air pressure gauge that is attached to the vertical pipe/manifold (mounted directly above the Model DDX Deluge Valve) may be used to verify the correct level of pneu­matic pressure.
The system air pressure switch (refer to Fig. 9 or 10) is factory set to operate between 8 psi and 4 psi (0.6 bar and 0.3 bar) with decreasing pressure. Adjustment, if required, should be made according to System Sensor Bulletin A05-0176 included with the switch.
System Electrical Requirements
All releasing, alarm, and detection devices in the Reliable Model DDX 4” (100 mm), 6” (150 mm) and 8” (200 mm) Pre­PaKs are supervised by a Potter Model PFC-4410-RC Releasing Control Panel. To utilize one of the doors of the steel enclosure as a mount for the releasing control panel, all of the terminals are translated to two, water-tight terminal boxes mounted on the interior of the enclosure. Note: The EOL (End of Line) resistors have also been relocated. It is from these terminal boxes that all field wiring is connected. There is one terminal box that contains the 24 VDC connections and one that contains the 120 / 220 VAC connections. The Reliable Model DDX PrePaK is delivered with five factory-installed electrical devices. They consist of the following:
1. A system air pressure switch, which is used to monitor sprinkler piping.
2. An alarm pressure switch, which indicates an actuation of the deluge valve.
3. A normally-closed, releasing solenoid valve, which is used to actuate the deluge valve.
4. A ¾ HP or 1½ HP air compressor with 8 gallon (30.3 liter) tank (1½ HP compressor is optional with 6” (150 mm) sys­tem only).
5. A supervised butterfly water control valve (A System Side butterfly valve is optional).
The factory electrical connections of these devices are illus­trated in Fig. 4. For information on how to install fire detection devices to initiating Zones 1 and 2 of the Potter Model PFC­4410-RC Releasing Control Panel, refer to Fig. 6 or Fig. 7. For information on how to install output devices, i.e., alarm bells or trouble annunciators, to the Potter Model PFC-4410-RC Releas­ing Control Panel, refer to Fig. 8. The power supply, standby emergency power supply, battery charger and rectifier circuitry are all contained within the PFC-4410-RC panel. Batteries that provide 90 hours of standby power are provided with the panel. For additional information and detailed wiring diagrams, refer to Potter Manual #5403550, Installation, Operation and Instruction of PFC-4410-RC Releasing Control Panel.
Note:
In order for the solenoid valve to maintain Reliable’s war­ranty it must remain sealed as it came from the factory. If there are concerns about the valve’s internal components, immediate replacement is recommended.
System Operation (Single Interlock)
To fully activate (water flow) the Reliable Model DDX 4” (100 mm), 6” (150 mm) or 8” (200 mm) PrePaK in a single interlock application, a fire detection device (smoke, heat, etc.) (two de­tectors with cross-zoned detection) must activate. Subsequent­ly, a sprinkler head must open to discharge water on the fire.
When the single interlock preaction system is set for service, the supply pressure acts both on the underside of the deluge valve’s clapper and on the valve’s push rod by means of the pressurized push rod chamber. The pressure force acting on the push rod, when utilized with the mechanical advantage of the deluge valve’s lever, is more than sufficient to hold the clap­per in the closed position against the water supply pressure.
Energizing the releasing solenoid valve allows the deluge valve’s push-rod chamber to be vented to drain through its outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented though the outlet, the push-rod chamber pressure falls rapidly. When the push-rod chamber pressure drops below one-third of the supply pres­sure, the opening force acting beneath the clapper becomes greater than the push-rod force acting on the lever. This causes the clapper to open. Refer to Reliable Bulletins 518 and 519 for further details.
Once the clapper has opened, the lever acts as a latch, pre­venting the clapper from returning to the closed position. Water from the supply flows through the deluge valve into the system piping. Water also flows through the deluge valve alarm outlet to activate any water flow alarm devices. Note that the solenoid valve will be maintained open by the Potter Model PFC-4410­RC Releasing Control Panel’s latching feature until it is reset for operation.
5.
After system shutdown and draining, the Model DDX Deluge Valve is easily reset without special tools (see Fig. 9 or 10). Re­store detection devices by resetting or replacing any operated device. Once detection devices are restored, (the Potter Model PFC-4410-RC Releasing Control Panel reset), and supply pres­sure is re-supplied to the push-rod chamber, the deluge valve is reset.
System Operation (Double Interlock)
To fully activate (water flow) the Reliable Model DDX 4” (100 mm), 6” (150 mm) or 8” (200 mm) PrePaK in a double interlock application, two independent events must coexist. An electrical fire detection device (smoke, heat, etc.) and the system air pres­sure switch must be activated. This pressure switch is activated by a reduction of the system’s pneumatic pressure (as a result of sprinkler operation). Both of these events will cause the control panel to energize the solenoid valve, thereby releasing water through the deluge valve and into the sprinkler system. The ini­tiation of either one of these events will only cause an alarm to annunciate, and will not fill the sprinkler system.
When the double interlock preaction system is set for service, the supply pressure acts both on the underside of the deluge valve’s clapper and on the valve’s push rod by means of the pressurized push rod chamber. The pressure force acting on the push rod, when utilized with the mechanical advantage of the deluge valve’s lever, is more than sufficient to hold the clap­per in the closed position against the water supply pressure.
Energizing the releasing solenoid valve allows the deluge valve’s push-rod chamber to be vented to drain through its outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented though the outlet, the push-rod chamber pressure falls rapidly. When the push-rod chamber pressure drops below one-third of the supply pres­sure, the opening force acting beneath the clapper becomes greater than the push-rod force acting on the lever. This causes the clapper to open. Refer to Reliable Bulletins 518 and 519 for further details.
Once the clapper has opened, the lever acts as a latch, pre­venting the clapper from returning to the closed position. Water from the supply flows through the deluge valve into the system piping. Water also flows through the deluge valve alarm outlet to activate any water flow alarm devices. Note that the solenoid valve will be maintained open by the Potter Model PFC-4410­RC Releasing Control Panel’s latching feature until it is reset for operation.
After system shutdown and draining, the Model DDX Deluge Valve is easily reset without special tools (see Fig. 9 or 10). Re­store detection devices by resetting or replacing any operated device. Once detection devices are restored, (the Potter Model PFC-4410-RC Releasing Control Panel reset), and supply pres­sure is re-supplied to the push-rod chamber, the deluge valve is reset.
Resetting Single And Double Interlock Systems
Refer to Fig. 9 or 10.
1. Close the main valve controlling water supply to the deluge
valve and close the ¼” air shutoff valve, valve J.
2. Close the pushrod chamber supply valve, valve A.
3. Open the main drain valve, valve B, and drain system.
4. Open all drain valves and vents at low points throughout
the system, closing them when flow of water has stopped. Open valve D. Note: The above steps accomplish the relieving of pressure in the pushrod chamber of the deluge valve.
5. Push in the plunger of ball drip valve, valve F, to force the ball from its seat, and drain any water in the alarm line.
6. With the Model B Manual Emergency Station, valve D, open, push in and rotate the deluge valve’s external reset knob clockwise until you hear a distinct clicking noise, indi­cating that the clapper has closed. Note: The reset knob can be rotated only after pressure in the pushrod chamber is reduced to atmospheric conditions (0 psig).
7. Inspect and replace any portion of the sprinkler system subjected to fire conditions.
8. Verify that the following valves are in their respective posi­tions: valve C – open, valve E – closed, valve H – closed, valve K – open, valve M – closed.
9. Open valve A and allow water to fill the deluge valve’s push­rod chamber. Close valve D.
10. Bleed any air from the actuation piping by energizing the solenoid valve. This is done by operating a detector or an electric manual emergency station. While water is flowing through the solenoid valve, cause it to close by pressing the system reset button on the Potter PFC-4410-RC Releasing Control Panel. Note: All detection devices must be reset before the releasing/control panel can be reset.
11. Open the ¼” air shutoff valve, valve J, to restore air pres­sure in the sprinkler system. The rapid air-fill shutoff valve, valve M, may be opened here to expedite the filling of the sprinkler system.
12. Open slightly the main valve controlling water supply to the Model DDX Deluge Valve, closing drain valve B when wa­ter flows. Observe if water leaks through the ball drip valve, valve F, into the drip cup or drain manifold, G. If no leak occurs, the deluge valve’s clapper is sealed. Open slowly, and verify that the main valve controlling water supply is fully opened and properly monitored.
13. Verify that valve A is open.
14. Secure the handle of the Model B Manual Emergency Sta­tion, valve D, in the OFF position with a nylon tie (supplied with the assembly).
15. Press the system reset button on the Potter PFC-4410-RC Panel to place the system in the ready condition. Note: All detection devices must be reset before the panel can be reset.
Maintenance
The Reliable Model DDX PrePaK and associated equipment shall periodically be given a thorough inspection and test. NFPA 25, Standard for the Inspection, Testing and Maintenance of Water Based Fire Protection Systems, provides minimum main­tenance requirements. Systems should be tested, operated, cleaned and inspected at least annually, and parts replaced as required. Periodically open the air/condensate drain valve (refer to Fig. 9 or 10) beneath the air tank to drain any condensate ac­cumulation. Bulletin 518 provides information for maintaining the Model DDX Deluge Valve. Potter Manual #5403550 provides information for maintaining the PFC-4410-RC Releasing Control Panel.
6.
Inspection And Testing Of Single And Double Interlock Systems
Refer to Fig. 9 or 10.
1. Water supply — Verify that the valve controlling wa­ter supply to the deluge valve is opened fully and properly monitored.
2. Alarm line — Verify that valve C is opened and re­mains in this position.
3. Other trimming valves — Verify that valve A is open as well as all of the pressure gauge’s ¼” 3-way valves. Valves D, E, and H should be closed.
4. Ball drip valve F — Push in on the plunger to be sure the ball check is off its seat. If no water appears, the deluge valve’s water seat is tight. Inspect the bleed hole in the front of the Model DDX Deluge Valve for leakage.
5. System pneumatic pressure — Verify that system air pressure is between 7 and 10 psi (0.5 bar 0.7 bar). Check the Pressure Maintenance Device for leakage and proper pressure.
6. Releasing device — Check the outlet of the releas­ing device (i.e., solenoid valve or the Model B Manual Emergency Station, valve D) for leakage. Also verify that tubing drain lines from releasing devices are not pinched or crushed which could prevent proper re­leasing of the deluge valve.
7. Testing alarms — Open valve E permitting water from the supply to flow to the alarm pressure switch and to the mechanical sprinkler alarm (if present). After testing, close this valve completely. Push in on the plunger of ball drip valve F until all of the water has drained from the alarm line.
8. Operational test — Open the Model B Manual Emer­gency Station, valve D only, OR, operate the solenoid valve by electrical actuation. This is done by oper­ating a detector or an electric manual emergency station. Double interlock systems also require that the sprinkler system’s air pressure be discharged, through the inspectors test station or other venting means, below 4 psi (0.3 bar) before total system operation will occur. Note: An operational test will cause the Deluge Valve to open and flow water into the sprinkler system.
9. Secure the Model B Manual Emergency Station, valve D, in the OFF position with a nylon tie (included with the assembly) after the deluge valve is reset.
Testing The Model DDX PrePaK Without Causing Water Flow
Refer to Fig. 9 or 10.
1. Close the main valve controlling water supply to the deluge valve and open drain valve B.
2. Verify that valve A is open, allowing water to enter the push­rod chamber.
3. Operate the detection system - Operate a cross-zoned re­leasing control panel by operating two detectors. For dou­ble interlock applications, close valve J and open valve H. Doing so will discharge the sprinkler system’s air pressure.
4. Step #3 should result in a sudden drop of water pressure in the deluge valve’s push-rod chamber via an energized solenoid valve.
5. Reset the detection system - Reverse the detection system operations performed in Step #3 above. Note: All detec­tion devices must be reset before the Potter PFC-4410-RC Releasing Control Panel can be reset.
6. Proceed according to the directions listed in the “Resetting Single And Double Interlock Systems” section of this bul­letin.
Draining Excess/Condensate Water From The System
Refer to Fig. 9 or 10.
1. Close the main valve controlling water supply to the deluge valve. Also, close valve A and open the main drain valve, valve B.
2. Open the condensate drain valve, valve H, until all of the water (if any) drains completely. Note: Be sure not to keep valve H open for an extended period of time because that will cause enough system air to bleed off, thereby activat­ing the system pressure switch and causing an potentially undesirable alarm condition.
3. Close the main drain valve B. Allow the system’s air pres­sure to return to its previous level. Open valve A first, and then open the main valve controlling the water supply to the deluge valve.
SOLENOID VALVE INSPECTIONS, TESTS AND MAINTENANCE
WARNING: THE OWNER IS RESPONSIBLE FOR MAIN­TAINING THE FIRE PROTECTION SYSTEM IN PROP­ER OPERATING CONDITION. ANY SYSTEM MAINTE­NANCE OR TESTING THAT INVOLVES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES HAVING JURISDICTION. CONSID­ERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA.
WARNING: PRIOR TO OPERATING THE SOLENOID VALVE, BE SURE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE
1. Inspections: It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular basis. The frequency of the inspections may vary due to contami­nated water supplies, corrosive water supplies, or corrosive atmospheres. In addition, the alarm devices, detection sys­tems, or other connected trim may require a more frequent schedule. Refer to the system description and applicable codes for minimum requirements.
2. The valve must be inspected at least monthly for cracks, corrosion, leakage, etc., cleaned and replaced as neces­sary.
3. If leakage is suspected through the solenoid valve, it should be replaced.
7.
RUN
PROGRAM
RED OUTPUT LED STEADY: ABORT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
AC POWER POWER TBL SYSTEM TBL SUP TBL
GROUND FAULT
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
SUP 1/ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE
STEADY: DISCHARGED FLASHING: PRE-DISCHARGE
PROGRAM MODE
SET
SELECT
RUN MODE
SCROLL-UP BUZZER SILENCE
LAMP
}
TEST
SCROLL-DOWN BUZZER SILENCE
SIGNAL SILENCE
VIEWING ANGLE
FUNCTION
SYSTEM RESET
Fig. 2
8.
Fig. 3
9.
Loading...
+ 19 hidden pages