Reliable DDX PrePaK Instructions For Installation, Operation Care And Maintenance

Bulletin 747 February 2019
Model DDX PrePaK, Type F Preaction System 2” (50mm), 2
1
/
” (65mm), 3” (80mm), 4”
2
(100mm), 6” (150mm) & 8” (200mm)
Instructions for
Double Interlock Electric/Pneumatic Release
Installation, Operation, Care and Maintenance
10 psi - 26 psi (0.7 bar - 1.8 bar) Recommended Supervisory Pressure
General Description
The Reliable Type F Model DDX PrePaK is a completely self-contained, supervised preaction system that can be readily installed within a floor space of less than 7.5 square feet ( 0.70 square meters) (not including door swing). Refer to Fig. 1 for cabinet dimensions. Installation of the PrePaK (not including exterior devices, i.e., detectors and alarm bells), requires just three piping connections. These con­nections are the water supply, the sprinkler system and the drain. Reference locations of these piping connections are shown in Fig. 1. Two electrical supply connections are re­quired. Note: The Model DDX PrePak is available with an optional 115V VAC (60Hz) air compressor and an optional Potter Model PFC-4410-RC Releasing/Control panel wired for a 120 VAC (50Hz) or 220 VAC (50/60Hz) power supply.
Full assembly drawings for the units are available on the Reliable Automatic Sprinkler Company website (www.reli­ablesprinkler.com)
The Reliable Type F PrePaK utilizes an optional Potter Model PFC-4410-RC Releasing/Control Panel. This fully programmable, microprocessor-based releasing panel is Underwriters Laboratories, Inc. Listed and is in compliance with NFPA 13 and NFPA 72. Because the PFC-4410-RC is totally zone and output programmable, the Reliable Type F PrePaK can be utilized in many different preaction appli­cations without having to rewire any of the factory installed devices. Once the previously described connections are completed, the 24 VDC detectors, output devices, and relay contacts may be connected to achieve the desired system implementation.
The Type F PrePaK is designed specifically for double interlock applications. Reliable double interlock preaction systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler sys­tem piping.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
The major benefits of a double interlock preaction System,
when compared with a wet pipe system, are as follows:
A. A fire alarm sounds prior to the flow of water from
a sprinkler, which may enable extinguishment of the fire by handheld means before the operation of any sprinkler occurs.
B. An annunciator signals whenever the integrity of
piping or sprinklers is accidentally or intentionally disturbed; however, no water flow occurs at that time.
C. Detection and notification of a fire condition are
provided by fire detectors, without the delay as­sociated with water delivery time in the event of a fire. Note that with a wet pipe system, the fire alarm is delayed until after water has begun flow­ing from and operated sprinkler.
To flow water into the system piping of a Type F double
interlock preaction system, two events must take place:
1) A fire detection device must detect heat and/or smoke thereby causing the releasing/control panel to energize the normally-closed solenoid valve.
2) The sprinkler system piping must discharge enough supervisory air for the Model LP Dry Pilot Actuator to operate. This is generally the result of a sprinkler operating due to fire.
In the event that the system piping is ruptured, or a sprin­kler head is accidentally opened, the Model LP Dry Pilot Actuator will open and a low system air pressure alarm will sound. The Model DDX Deluge Valve, however, will not be released to flow water since the solenoid valve still remains closed. Conversely, in the event of a false detection signal, the releasing/control panel will activate an alarm, but the Model DDX Deluge Valve will not flow water due to the fact that the Model LP Dry Pilot Actuator remains closed.
When using the Reliable Type F PrePaK in double inter­lock applications the sprinkler system is pressurized (super­vised) with air provided by the optional factory-installed air compressor (or on-site Nitrogen supply) and is monitored by a system pressure switch. If Nitrogen is used as the supervisory gas, an optional Nitrogen Kit is available. This kit contains a regulator and an additional pressure switch that is used to monitor any low pressure conditions that may arise due to having a limited Nitrogen supply. The optional factory-installed air compressor can be utilized for make-up air until the Nitrogen supply can be replenished.
Note: Compressed air is not to be considered as dry air and may create ice plugs in the sprinkler system piping.
A Model B Hydraulic Manual Emergency Releasing station is standard equipment in the Type F PrePaK. It consists of an aluminum nameplate mechanically attached to a ball valve. The valve handle in its OFF position is guarded against ac­cidental turning to the ON position (and system discharge) by a nylon cable tie provided with the PrePaK assembly. The cable tie is designed to allow, in case of an emergency, forceful turning of the valve handle to the ON position.
Listings and Approvals
1. Underwriters Laboratories, Inc. Listed and Certified for Canada* (cULus) as an assembled unit in the “Special System Water Control Valves Assembled Units” category, (VKYL). *The system’s pressure switches must be specified to meet Canadian requirements. This option is avail­able.
2. Factory Mutual Approved as a Refrigerated Area Sprinkler System for use in refrigerated rooms or buildings. Refrigerated area sprinkler systems are FM Approved as complete systems. Systems are FM approved for use with thermal detectors and Class A detector wiring only.
3. Approved for use in New York City based on UL List­ing.
Note: Although PrePak units are UL Listed, custom built units are sometimes supplied upon request. The compo­nents within these special units maintain their individual Listings/Approvals, whereas the assembled units do not.
PrePak units are also available without their Potter PFC­4410-RC Releasing/Control Panel and Air Compressor. These units will still retain their Listings/Approvals, however the installing contractor should make sure that any remote controlled Releasing/Control Panels used with these units are Listed/Approved and programmed to handle the re­quired sequence of operation necessary to operate the au­tomatic sprinkler system. Any unauthorized modification or addition made on-site to a factory-built Listed/Approved unit will void the Listing/Approval. Such modifications or addi­tions may void the unit’s warranty as well. Consult Reliable’s Technical Services Department before proceeding with any such modifications or additions.
Technical Data
1. The Reliable Type F Model DDX PrePaK is rated for
a minimum water supply pressure of 20 psi (1.4 bar) and a maximum water supply pressure of 250 psi (17.2 bar). Note: 1 bar = 100 kPa.
2. Friction loss, expressed in equivalent length of
Schedule 40 pipe and based on Hazen-Williams Formula is:
System Size:
2” (50mm) 19.4 ft (1.3 m)
2½” (65mm) 24.5 ft (1.8 m)
3” (80mm) 28.9 ft (3.8 m)
4” (100 mm) 32.8 ft (17.7 m)
6” (150 mm) 54.7 ft (21.8 m)
8" (200mm) 79.3ft (24.2m)
These values account for the Model DDX Deluge Valve, supply manifold tee, butterfly control valve, and small pipe/manifold located directly above Model DDX Deluge Valve.
Equivalent Length
2.
Fig. 1
3.
3. Shipping Weight:
System Size Weight
2” (50 mm), 2½” (65 mm)
& 3” (80 mm)
4” (100 mm) 710 lbs (322 kg)
6” (150 mm) 800 lbs (363 kg)
8" (200mm) 1350lbs (531kg)
554 lb. (252 kg)
4. Please reference Figure 1 for dimensions.
The following is a list of Technical Data Bulletins which de-
scribe the valves and devices which are used in the system:
Device
Model DDX Deluge Valve Reliable Bulletin 519 Type F Double Interlock Preaction Trim Reliable Bulletin 751 Low Air Pressure Switch Potter, 5401564 Alarm Pressure switch Potter, 5400928 Nitrogen Pressure Switch Potter, 5400930 Mechanical Sprinkler Alarm Reliable Bulletins 612/613 Releasing Control Panel Potter Manual #5403550 Fire Alarm Devices Reliable Bulletin 700
Desiccant Dryer
Reliable Bulletin #
(unless otherwise noted)
Wilkerson Catalog 9EM-
TK-190-4
The following table provides a quick reference to the vari-
ous programs (found in this bulletin and the Potter Manual
#5403550) that may be utilized with a Type F PrePaK:
Desired Application Program
Single Interlock,
Single Zone
Single Interlock,
Cross-Zoned
Note: The Model DDX Type F PrePak Double Interlock Preaction system utilizes a solenoid controlled by single interlock program­ming in conjunction with a pneumatic (mechanical) actuator.
Potter Program #6
(Factory Setting)
Potter Program #7
Installation Requirements
The automatic sprinklers, releasing devices, fire detection devices, manual pull stations, and signaling devices which are utilized with the Reliable Model DDX Type F PrePaK must be UL and/or ULC Listed or FM Ap­proved, as applicable.
The steel enclosure and all the interconnecting piping must be located indoors in a readily visible and acces­sible location and in an area that can be maintained at a minimum temperature of 40°F (4°C). Note: Heat tracing is not permitted. The solenoid valve is operated and supervised by the Potter Model PFC-4410-RC Releas­ing Control Panel. Details on the electrical connections of this system to the Potter Panel can be found in the Potter Manual #5403550, Installation, Operation and Instruction of PFC-4410-RC Releasing Control Panel (this manual is included with other pertinent manuals and shipped inside the enclosure). This panel is fully zone and output programmable and may be adapted to several applications. Hydrostatic Testing of DDX Valves and DDX Systems.
Hydrostatic Testing of DDX Valves and DDX Systems
As required by NFPA 13, fire sprinkler systems with work­ing pressures up to and including 150 psi are to be hydro­statically tested at a water pressure of 200 psi. Fire sprinkler systems with working pressures above 150 psi are required to be hydrostatically tested at 50 psi above the system working pressure. In addition to the hydrostatic tests described above, dry pipe and double interlock preaction systems require an additional low pressure air test.
In some cases, hydrostatic testing (in accordance with the NFPA 13 requirements noted above) will result in pressures that exceed the working pressure of the valve and trim kit for the two-hour test period. The valve and applicable trim kit have been tested, approved and listed under these conditions and as such, hydrostatic testing in accordance with NFPA 13 is ac­ceptable. In addition, the clapper can remain in the closed po­sition and the trim kit need not be isolated, as each has been designed to withstand hydrostatic testing as required by NFPA
13.
Hydrostatically testing the valve and trim to pressures higher than their rating is limited to the hydrostatic test as referenced by NFPA13. It does not address the occurrence(s) of a “wa­ter hammer” effect, which can indeed damage the valve. A “water hammer” in the water supply piping of the valve can create pressures in excess of the rated pressure and should be avoided by all necessary means. This condition may be created from improper fire pump settings, underground con­struction work, or an improper venting of trapped air in the wa­ter supply piping.
System Air / Nitrogen Pressure Requirements
The Model DDX Type F PrePaK includes gauges indicating the pneumatic and water pressures of Model LP Dry Pilot Ac­tuator. Table A specifies the air or nitrogen pressure level to be applied to the Actuator. The factory installed Pressure Main­tenance Device in the unit automatically provides adequate makeup air or nitrogen flow to maintain supervisory pressure with normal leakage for the system piping, while restricting the flow of makeup air or nitrogen to allow for system operation. Please note that when the optional Model B1 Accelerator is to be utilized to expedite water-delivery time, the pneumatic pressure must be not less than 15 psi (1.0 bar).
Table A
Water Pressure
psi (bar)
Maximum Not Less Than Not More Than
20 (1.4) 10 (0.7) 14 (0.9)
50 (3.4) 12 (0.8) 16 (1.1)
75 (5.2) 13 (0.9) 17 (1.2) 100 (6.9) 15 (1.0) 19 (1.3) 125 (8.6) 16 (1.1) 20 (1.4)
150 (10.3) 17 (1.2) 21 (1.4) 175 (12.1) 18 (1.2) 22 (1.5) 200 (13.8) 19 (1.3) 23 (1.6) 225 (15.5) 21 (1.5) 25 (1.7) 250 (17.2) 22 (1.5) 26 (1.8)
Supervisory Air or Nitrogen Pressure in
Sprinkler System, psi (bar)
4.
Note: During system set-up, a higher pneumatic pres­sure may be required in order to properly set the Model LP Dry Pilot Actuator. The dew point of the air supply must be maintained below the lowest ambient tempera­ture to which the preaction system will be exposed. In­troduction of moisture into the system piping exposed to freezing temperatures can create ice blockage which could prevent proper system operation. As a minimum, the supply of air should be taken from the area of low­est temperature within the protected area. The air supply system must be carefully designed to prevent plugging by frost deposits. Special requirements, such as those in FME&R’s “Installation Guidelines for Refrigerated Stor­age” may need incorporated.
Nitrogen used in refrigerated area systems minimizes a possibility of ice build-up and blockage inside the system piping that could inhibit proper system operation. The dew­point of nitrogen compressed to 20 psig (1.4 bar) pressure is
-46°F (-43.3°C), and -52°F (-46.7°C) when compressed to 10 psig (0.7 bar). High-pressure nitrogen cylinders can typically be rented from a local source, with rental fees varying by supplier and cylinder sizes. The calculated nitrogen supply in lbs (kg) to pressurize various system capacities to 10 psi (0.7 bar) at different freezer temperatures is shown in Table B.
A Nitrogen Kit is available as an option, for installations where nitrogen is used as the supervisory gas. A “low-nitrogen” LED is mounted onto the door of the Potter Model PFC-4410-RC Releasing/Control Panel. It will illuminate when the nitrogen pressure switch detects that the available nitrogen supply falls to 100 psi (6,9 bar). The nitrogen source should be replaced promptly upon operation of the pressure switch. If the nitrogen supply is not replaced, the entire amount of make-up air will come solely from the unit’s air compressor (if installed).
Table B
System
Capacity
Gal. (L)
250
(946)
500
(1891)
750
(2840)
1,000
(3785)
Note: To obtain required nitrogen supply (lbs.) for 15 psi (1.0
* When filled with the Rapid Air – Fill Shutoff Valve open.
20°F
(-6.7°C)
(1.65)
(2.50)
(3.30)
bar) or 22 psi (1.5 bar), multiply the tabulated values by a factor of 1.5 or 2.2 respectively. (1 bar = 100 kPa)
If the air compressor in the Model DDX Type F PrePaK is used to initially fill the sprinkler system with air, the steel enclo­sure door should remain open to provide maximum intake air flow to the air compressor. The air compressor is connected to a storage tank. This tank functions as a reservoir, provid­ing make-up air to compensate for small, intermittent leaks in the sprinkler system. It should be noted that significant leaks may overburden this storage tank, thereby causing the air compressor to continuously cycle on and off.
Freezer Temperature
0°F
(-18°C)
1.90 (.86)
3.64
5.50
7.30
1.90 (.86)
3.80
(1.72)
5.70
(2.60)
7.60
(3.44)
-20°F
(-29°C)
2.00 (.90)
4.00
(1.81)
6.00
(2.72)
8.00
(3.62)
-40°F
(-40°C)
2.10
(.95)
4.20
(1.91)
6.30
(2.86)
8.33
(3.78)
-60°F
(-51°C)
2.20
(1.00)
4.40
(2.00)
6.60
(3.00)
8.80
(4.00)
Approx.
Fill Time
(min.)*
1
2
3
4
The factory-installed system air pressure switch may need on-site adjustment to correspond with the air pressure val­ues found in Table A. Adjustment, if required, should be made according to Potter Bulletin 5401564 included with the switch.
System Electrical Requirements
All releasing, alarm, and detection devices in the Reli­able Model DDX Type F PrePaK are supervised by a Potter Model PFC-4410-RC Releasing Control Panel. All of the ter­minals are translated to a water-tight terminal box mounted on the interior of the enclosure. All field wiring is connected to this terminal box. Note: The EOL (End of Line) resistors have also been relocated.
The Reliable Model DDX PrePaK is delivered with six factory-installed electrical devices. They consist of the fol­lowing:
1. A system air pressure switch, which is used to monitor
sprinkler piping.
2. An alarm pressure switch, which indicates an actuation
of the deluge valve.
3. A normally-closed, releasing solenoid valve, which is
used to actuate the deluge valve.
4. A 1/2 HP (2”, 2-1/2”, & 3” valve), 1 HP (4” valve), or 1-1/2
HP (6” & 8” valve) air compressor with tank.
5. A supervised butterfly (main control) valve (Note: A sys-
tem side butterfly valve is available as an option).
6. A release control disable switch (RCDS) which is used
to disable the solenoid valve for test purposes.
The factory electrical connections of these devices, along with information on the connection of detection devic­es (initiating zones 1 and 2), signaling devices, and super­visory outputs to the Potter PFC4410-RC Releasing Control Panel are included in this bulletin. The power supply, stand­by emergency power supply, battery charger and rectifier circuitry are all contained within the PFC4410 panel. Bat­teries that provide 90 hours of standby power are provided with the panel. For additional information and detailed wiring diagrams, please refer to Potter Manual #5403550 (Instal­lation, Operation and Instruction of PFC4410-RC Releasing Control Panel).
Note: In order for the solenoid valve to maintain a warranty it must remain sealed as it came from the factory. If there are concerns about the valve’s internal components, immediate re­placement is recommended.
System Operation (Double Interlock)
To fully activate (discharge water from) the Reliable Model DDX Type F PrePaK system, a fire detection device must ac­tivate and pneumatic pressure must be lost from the sprin­kler system piping (normally from the activation of one or more fire sprinklers).
When the system is properly set for service, the water sup­ply pressure simultaneously acts on both the underside of the deluge valve’s clapper and on the valve’s push rod by means of the pressurized push rod chamber. The resultant pressure force acting on the push rod, in unison with the me­chanical advantage of the deluge valve lever, is more than sufficient to hold the valve clapper in the closed position against the water supply pressure.
5.
Energizing the releasing solenoid valve is only one of the events required towards opening the deluge valve. Air pres­sure in the sprinkler system must also be reduced to a level low enough to activate the Model LP Dry Pilot Actuator. Both of these events allows the deluge valve’s push-rod chamber to be vented to drain through its outlet. Since the push-rod chamber pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the pressure falls rapidly. When the push-rod chamber pressure drops below one­third of the water supply pressure, the force acting beneath the valve clapper becomes greater than the push-rod force acting on the lever which causes the clapper to open. Refer to Reliable Technical Bulletin 751 for further details.
Once the clapper has opened, the lever acts as a latch, preventing the clapper from returning to the closed position. Water from the supply flows through the deluge valve into the system piping and also through the alarm outlet to acti­vate water flow alarm devices. Note that the solenoid valve will be maintained open by the Potter Model PFC-4410-RC Releasing/Control Panel latching feature until it is reset for operation.
After system shutdown and draining, the Model DDX Del­uge Valve clapper is easily reset without special tools us­ing the external reset feature. Restore detection devices by resetting or replacing any operated device. Once detection devices are restored the system can be reset (see Resetting Model DDX Type F Double Interlock Preaction System).
Resetting Model DDX Type F Double Interlock Preaction System
1. Close the valve controlling water supply to the Del­uge Valve and close the air or nitrogen supply to the sprinkler system.
2. Close the pushrod chamber supply valve.
3. Open main drain valve and drain system.
4. Open all drain valves and vents at low points through­out the system, closing them when flow of water has stopped. Open the Model B Manual Emergency Station to relieve pressure in the pushrod chamber of the Deluge Valve.
5. With the alarm line valve open, push in the plunger of ball drip valve, forcing the ball from its seat, and drain the alarm line.
6. With the Model B Manual Emergency Station open, push in and rotate the Deluge Valve’s external reset knob counterclockwise (when facing the valve), until you hear a distinct noise indicating that the clapper has reset. Note: The reset knob can be rotated only while pressure in the pushrod chamber is vented to atmospheric condi­tions (0 psig).
7. Inspect and replace any portion of the detection sys­tem and/or sprinkler system subjected to fire conditions.
8. Open the pushrod chamber supply valve and allow water to fill the pushrod chamber. Close the Model B Manual Emergency Station.
9. Purge all air from the actuation piping: Open the sole­noid valve by operating a detector or an electric manual emergency station. Note that the Model LP Dry Pilot Ac­tuator should also be open since there is no pneumatic pressure on the system.
10. While water is flowing through the solenoid valve AND the actuator, cause the actuator to close first by ap­plying air or nitrogen pressure to the system.
11. Open the air or nitrogen supply quick fill valve to re­store supervisory pressure in the sprinkler system and close the dry pilot actuator. Allow the pressure to build to the level specified in Table A, then set the pneumatic supply to automatic operation. (Note: To build supervi­sory air pressure in the sprinkler system, it may be nec­essary to temporarily close the main drain valve and the alarm line valve until air pressure has built up to the rec­ommended level.)
12. After the Model LP Dry Pilot Actuator has been set, close the solenoid valve by resetting the release control panel. (All detectors and manual pull stations must be in a normal state before the panel can be reset.) Note: It is important that the piping between the sole­noid valve and the dry pilot actuator is filled with water and not air. This is accomplished by closing the dry pilot actuator FIRST while water is flowing through the device and closing the solenoid valve only AFTER the actuator is completely set.
13. Open the alarm line valve. Verify the main drain valve is open. Slightly open the main valve controlling water supply to the Model DDX Deluge Valve, closing the main drain valve when water flows. Observe if water leaks through the ball drip valve. If no leak occurs, the Deluge Valve clapper is sealed. Slowly open the main valve con­trolling water supply until fully open and verify that it is properly monitored.
14. Verify that the pushrod chamber supply valve and alarm line valve are open. The pushrod chamber supply valve must remain open when the Deluge Valve has been reset, to maintain water pressure in the pushrod cham­ber.
15. Verify that the Model B Manual Emergency Station is secured in the OFF position with the appropriate nylon tie.
Inspection and Testing
1. Water supply — Confirm that valves controlling water supply to the Deluge Valve are opened fully and properly monitored.
2. Alarm line — Confirm that the alarm line valve is open and remains in this position.
3. Other trim valves — Confirm that the pushrod cham­ber supply valve is open, as well as all pressure gauge valves. The main drain valve, condensate drain valve, and alarm test valve should be closed.
4. Ball drip valve — Push in on the plunger to be sure ball check is off its seat. If no water appears, the Deluge Valve water seat is tight. Inspect the bleed hole on the underside of the pushrod chamber for leakage.
6.
Loading...
+ 12 hidden pages