Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
09/24/03
Thank-you for purchasing a
REGENCY FIREPLACE PRODUCT.
The pride of workmanship that goes into each of our products will give you years of trouble-free enjoyment. Should you have
any questions about your product that are not covered in this manual, please contact the REGENCY DEALER in your area.
Keep those REGENCY FIRES burning.
SAFETY NOTE: If this woodstove is not properly installed, a house fire may result. For your safety, follow the installation
instructions, contact local building or fire officials about restrictions and installation inspection requirements in your area.
2
Regency Freestanding Woodstove
TABLE OF CONTENTS
THE REGENCY FREESTANDING STOVE
SAFETY LABEL
Small Freestanding Stove F1100S ..................................... 4
Large Freestanding Stove F3100L ..................................... 5
Large Freestanding Step Stove S3100L ............................. 6
This is a copy of the label that accompanies
each Regency Small Freestanding Woodstove
(F1100S).
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO
SUITABLE FOR MOBILE HOME INSTALLATION
MODEL: REGENCY SMALL FREESTANDING STOVE - F1100S
TESTED TO: CSA B366.2 / ULC S627 / UL 1482 REPORT NO.6621 (MAY 1993)
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND
OPERATING INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS
AND INSTALLATION INSPECTION IN YOUR AREA. USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG
BLACK OR 26 MSG BLUED STEEL CONNECTOR WITH LISTED FACTORY-BUILT CHIMNEY SUITABLE FOR
USE WITH SOLID FUELS OR MASONRY CHIMNEY.
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED
F1100S WITH
AIRMATE SHIELD
F1100S WITHOUT
AIRMATE SHIELD
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
F1100S WITH AIRMATE SHIELDF1100S WITHOUT AIRMATE SHIELD
MEASUREFLUE
FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 330 mm / 13 in D 635 mm / 25 in
BACKWALL B 280 mm / 11 in E 445 mm / 17.5in
CORNERC 205 mm / 8 in F 510 mm / 20 in
SIDEWALL A 280 mm / 11 in D 585 mm / 23 in
BACKWALL B 150 mm / 6 in E 320 mm / 12.5in
CORNERC 150 mm / 6 in F 460 mm / 18 in
SIDEWALL A 230 mm / 9 in D 535 mm / 21 in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNERC 75 mm / 3 in F 380 mm / 15 in
SIDEWALL G 280 mm / 11 in I 585 mm / 23 in
BACKWALL H 180 mm / 7 in J 345 mm / 13.5in
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT MAXIMUM ALCOVE DEPTH 915 MM / 36 IN.
MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18"
THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT
COMBUSTION AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. OPERATE ONLY WITH DOOR CLOSED - OPEN FEED DOOR TO FEED FIRE
ONLY. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER OR CHIMNEY CONNECTOR
GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE CREOSOTE
BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH
NEOCERAM GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO
THE FRONT AND SIDES AS INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENT: FAN, ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM:
SECURITY MODEL S2100, ICC EXCEL 2100 .
IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA
VENT MODEL DVL, GSW SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS
SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR METALFAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
SINGLE WALL CONNECTOR
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY
CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
We have printed a copy of the contents here for
your review.
DO NOT REMOVE THIS LABEL
100
MEASURE FLUE
FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 380 mm /15 in D 685 mm / 27 in
BACKWALL B 265 mm / 10.5in E 430 mm / 17 in
CORNERC 280 mm / 11 in F 585 mm / 23 in
SIDEWALL A 330 mm / 13 in D 635 mm / 25 in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNERC 230 mm / 9 in F 535 mm / 21 in
SIDEWALL A 345 mm / 13.5in D 650 mm / 25.5in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNERC 125 mm / 5 in F 430 mm / 17 in
SIDEWALL G 330 mm / 13 in I 635 mm / 25 in
BACKWALL H 125 mm / 5 in J 290 mm / 11.5in
SINGLE WALL CONNECTOR
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there
is a difference, the label on the unit is the correct
one.
M
FLOOR
PROTECTION*
K 405 mm / 16 in
L 150 mm / 6 in
M 150 mm / 6in
* In Canada, floor protection must
extend 18" to the front and 8" to
each side of the stove.
BACK
SIDE
K
FRONT
L
SIDE
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
MANUFACTURED BY: FIREPLACE PRODUCTS INTERNATIONAL LTD.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
CERTIFIED TO COMPLY WITH JULY 1990,
PARTICULATE EMISSION STANDARDS.
CAUTION
6988 VENTURE ST.
DELTA, BC V4G 1H4
MADE IN CANADA
2004
2003
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
4
CLOTHING AND FURNITURE AW A Y. CONT ACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
908-281 01/03
Regency Freestanding Woodstove
WD
DA TE OF MANUFACTURE
2002
FRONT
BACK
L
K
M
SIDE
SIDE
SAFETY LABEL
This is a copy of the label that accompanies
each Regency Large Freestanding Woodstove
(F3100L).
We have printed a copy of the contents here
for your review.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there
is a difference, the label on the unit is the correct
one.
LISTED SPACE HEATER, SOLID FUEL TYPE, SUITABLE FOR
MOBILE HOME INSTALLATION
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND
INSTALLATION INSPECTION IN YOUR AREA. USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK OR
26 MSG BLUED STEEL CONNECTOR WITH LISTED FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH
SOLID FUELS OR MASONRY CHIMNEY.
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED
F3100L WITH
AIRMATE SHIELD
F3100L WITHOUT
AIRMATE SHIELD
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
F3100L WITH AIRMATE SHIELD
MEASURE FLUE
FROMHEATERCENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 460 mm / 18 in D 810 mm / 32 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5in
CORNERC 215 mm / 8.5in F 560 mm / 22 in
SIDEWALL A 460 mm / 18 in D 810 mm / 32 in
BACKWALL B 240 mm / 9.5in E 405 mm / 16 in
CORNERC 255 mm / 10 in F 595 mm / 23.5in
SIDEWALL A 405 mm / 16 in D 760 mm / 30 in
BACKWALL B 240 mm / 9.5in E 405 mm / 16 in
CORNERC 215 mm / 8.5in F 560 mm / 22 in
SIDEWALL G 405 mm / 16 in I 760 mm / 30 in
BACKWALL H 240 mm / 9.5in J 405 mm / 16 in
MINIMUM CLEARANCE BETWEEN HORIZONTAL CHIMNEY CONNECTOR AND COMBUSTIBLE MATERIALS - 460 MM (18 IN.). CLEARANCE MAY BE
REDUCED BY THE USE OF LISTED PIPE SHIELDS, WALL PROTECTORS OR OTHER MEANS APPROVED BY LOCAL BUILDING OR FIRE OFFICIALS.
COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES
AS INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT
COMBUSTION AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. OPERATE ONLY WITH DOOR CLOSED - OPEN FEED DOOR TO FEED FIRE
ONLY. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER OR CHIMNEY CONNECTOR
GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE CREOSOTE
BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH
NEOCERAM GLASS.
OPTIONAL COMPONENT: FAN, ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM:
SECURITY MODEL S2100, ICC EXCEL 2100.
IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA
VENT MODEL DVL, GSW SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS
SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR METALFAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
SINGLE WALL CONNECTOR
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY
CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE SERVING ANOTHER APPLIANCE.
F3100L WITHOUT AIRMATE SHIELD
MEASURE FLUE
FROMHEATERCENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 355 mm / 14 in E 520 mm / 20.5 in
CORNERC 265 mm / 10.5in F 610 mm / 24 in
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5in
CORNERC 255 mm / 10 in F 595 mm / 23.5in
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5in
CORNERC 215 mm / 8.5in F 560 mm / 22 in
SINGLE WALL CONNECTOR
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
ALCOVE INSTALLATION
REQUIRES AIRMATE SHIELD
DO NOT REMOVE THIS LABEL
102
BACKWALL
B
A
SIDEWALL
D
BACKWALL
HJ
SIDEWALL
G
I
ADJACENT WALL
SIDEWALL
F
FLOOR
PROTECTION*
K 405 mm / 16 in
L 150 mm / 6 in
M 150 mm / 6 in
* In Canada, floor protection must
extend 18" to the front and 8" to
each side of the stove.
E
SIDEWALL
G
C
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
Regency Freestanding Woodstove
MANUFACTURED BY: FIREPLACE PRODUCTS INTERNATIONAL LTD.
6988 VENTURE ST.
DELTA, BC V4G 1H4
MADE IN CANADA
CERTIFIED TO COMPLY WITH JULY 1990,
PARTICULATE EMISSION STANDARDS.
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWA Y. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
WD
908-351
01/03
2003
2002
DA TE OF MANUFACTURE
2001
5
SAFETY LABEL
This is a copy of the label that accompanies
each Regency Large Freestanding Step Woodstove (S3100L).
We have printed a copy of the contents here
for your review.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there
is a difference, the label on the unit is the correct
one.
6
Regency Freestanding Woodstove
INSTALLATION
RESIDENTIAL
INSTALLATION
1) Read all instructions before installing your
Regency Stove. Install and use only in
accordance with these installation and
operating instructions. Be aware that local
Codes and Regulations may override some
items in this manual. Check with your local
inspector.
2) Select a position for your Regency Stove.
Consult the minimum clearance chart for
your model and set the stove in place. For
close clearance installation use listed double wall connector systems (see page 13).
3) To insure vertical alignment, suspend a
plumb bob from the ceiling over the exact
center of your stove flue and mark a spot on
the ceiling to indicate the center of the
chimney.
4) Check that the area above the ceiling is clear
for cutting. Re-confirm the clearance from
the stove to combustibles to insure that they
are within the prescribed limits.
5) Install chimney according to chimney manufacturers instructions. The performance
of your woodstove is governed to a very
large part by the chimney system. Too short
a chimney can cause difficult start-up, dirty
glass, backsmoking when door is open, and
even reduced heat output. Too tall a chimney may prompt excessive draft which can
result in very short burn times and excessive heat output. The use of an inexpensive
flue pipe damper may be helpful in reducing
excessive draft.
CAUTION: The chimney should be the same
size as the flue outlet on the stove. The
chimney must be listed as suitable for use
with solid fuels. For other types of chimneys check with your local building code
officials. Do not confuse a chimney with a
type “B” Venting System used for gas
appliances as suitable for a wood burning
appliance. For Mobile Home installations
refer to that section on page 12.
6) Mark the location of the pedestal base or
legs on the floor, then move the stove aside
and mark the position of the floor protector.
7) The floor protector must be of non-combustible material and must extend 16" in front of
the door opening and 6" to the sides and
rear of the unit. Some areas may require a
larger size floor protector. See your local
inspector. For outside air installation refer
to Mobile Home installation instructions on
page 12.
NOTE: In Canada, floor protection must
extend 18" to the front and 8" to
each side of the stove.
8) When the floor protection is complete, po-
sition the stove with the flue collar centered
under the installed chimney.
9) In seismically active areas, Regency recommends that your unit is secured to the
floor by using the bolt down holes inside the
pedestal (the same ones used in Mobile
Home installations).
10)For residential installations using "C" Vent
(single wall) the chimney connector must
be at least 24 gauge steel. Do not use
galvanized pipe. For Mobile Home installation refer to the Mobile Home installation
instructions on page 12.
11)Do not connect this unit to a chimney serving another appliance unless approved by
your local building authority.
12)A chimney connector cannot pass through
an attic or roof space, closet or similar
concealed space, or a floor, ceiling, wall or
partition of combustible construction. In
Canada, if passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/
CSA-B365, Installation Code for Solid-FuelBurning Appliances and Equipment.
13)Your Regency Woodstove is not to be
connected to any air distribution duct.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
ROOM AIR
IMPORTANT
For installation using room air for combustion,
remove knockout from the pedestal, and/or
from the bottom if using a heat shield.
Mobile home installations require the use of
outside air.
On pedestal units there are two locations where
outside air may be adapted to the unit. If using
the bottom of the pedestal, do not remove
knockout from the rear of the pedestal. Only
remove rear knockout if outside air will be
brought in from the rear.
On leg units outside air can only be brought in
from the bottom of the heat shield.
Note: Once the knockout is removed
there are two tabs remaining. Bend
both tabs out for ease of installation when attaching outside air.
MODULAR INSTALLATION OPTIONS
The following items are required when assembling your Regency Stove. F1100 and F3100 units - the Rear Heat Deflector is supplied with the
stove, but if you choose not to use it you must use the Airmate instead.
Modular Part
Clearances are different. See the chart on pages 8 and 9. Generally you can get closer clearances with the airmate
F1100 & F3100 only:
Airmate OR
Rear Heat Deflector
(all units)
Pedestal OR
Legs
than with the rear heat deflector.
Convection heat with Airmate vs. Radiant Heat with Rear Heat Deflector. The airmate pushes heat forward and into
the room, the rear heat deflector deflects the heat upward. See installation instructions on page 10.
There are no performance differences with either the pedestal or legs. It is primarily a personal preference. Legs
can be either painted steel, painted cast, or gold plated cast.
Leg installation requires the bottom shield. See installation instructions on page 11.
OPTIONS: These can be installed at time of installation or added later:
Modular Option
Blower/Fan
Ash Drawer Kit
Regency Freestanding Woodstove
Adding the blower will increase the area heated by the stove, it can move warm air beyond the room where the stove
is installed. Installation instructions on page 16.
Adding the Ash Drawer Kit makes cleaning ashes out of the stove easier and cleaner. Installation instructions on page
15.
Things to consider when choosing options:
Things to consider when choosing options
7
INSTALLATION
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Please read the section below carefully as clearances depend on whether the airmate or the rear heat deflector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Residential Installation “C” Vent (Single Wall)
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100Swith Airmate13"11"8"25"17.5"20"
with Rear Deflector15"10.5"11"27 "17"23"
Large F3100Lwith Airmate18"12"8.5"32"18.5"22"
Large S3100L Step Stove18"12"8.5"32"18.5"22"
with Rear Deflector20"14"10.5"34"20.5"24"
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove
collar to the ceiling level.
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100Swith Airmate9"5"3"21"11.5"15"
with Rear Deflector13.5"5"5"25.5"11.5"17"
Large F3100Lwith Airmate16"9.5"8.5"30"16"22"
Large S3100L Step Stove16"9.5"8.5"30"16"22"
with Rear Deflector20"12"8.5"3 4"18.5"22"
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100Swith Airmate11"6 "6"23"12.5"18"
with Rear Deflector13"5 "9"25"11.5"21"
Large F3100Lwith Airmate18"9.5"10"32"16"23.5"
with Rear Deflector20"12"10"34"18.5"23.5"
Large S3100L Step Stove18"9.5"10"32"16"23.5"
8
Regency Freestanding Woodstove
INSTALLATION
Minimum Alcove Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
From From FlueMin.Min.Hearth
Unit Unit Center-lineWidthto Rear Wall
GHI JKL
Small F1100Swith Airmate11"7"23"13.5"46"39"
with Rear Deflector13"5"25"11.5"50"37"
Large F3100Lwith Airmate16"9.5"30"16"60"46.5"
Large S3100L Step Stove16"9.5"30"16"6 0"46.5"
with Rear Deflector (not approved for Alcove)
Floor Protection
A combustible floor must be protected by a non-combustible material (like tile,
concrete board, or certified to UL-1618 or as defined by local codes) extending
beneath the heater and a minimum of 6" from each side and minimum 16" from
the front face of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.
Minimum Overall Width (X) of Floor
Protector for all installations:
Small StoveF1100S36"
Large StoveF3100L40"
Large Step StoveS3100L40"
NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove
Unit "C" Vent Close Clearance Close Clearance
YZYZY ZY Z
Small F1100Swith Airmate38"6"37"*5"38"6"38"6"
with Rear Deflector38"6"37"*5"37"*5"37"*5"
Large F3100Lwith Airmate43"6"43"6"43"6"43"6"
Large S3100L Step Stove43"6"43"6"43"6"43"6"
with Rear Deflector43"6"43"6"43"6"n/an/a
*The rear clearance to combustibles is less than 6", for corner installations the rear corners may be angled to take advantage of the closer clearances.
Regency Freestanding Woodstove
9