Regency S2400M, F2400M User Manual

www.regency-fi re.com
Freestanding Woodstove
Installation Manual
Tested by:
918-154b
MODELS: F2400M S2400M
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
02/18/08
Thank-you for purchasing a
REGENCY FIREPLACE PRODUCT.
The pride of workmanship that goes into each of our products will give you years of trouble-free enjoyment. Should you have any questions about your product that are not covered in this manual, please contact the REGENCY DEALER in your area.
Keep those REGENCY FIRES burning.
SAFETY NOTE: If this woodstove is not properly installed, a house fi re may result. For your safety, follow the instal­lation instructions, contact local building, fi re offi cials, or authority having jurisdiction about restrictions and installation inspection requirements in your area.
The authority having jurisdiction should be consulted before installation to determine the need to obtain a permit.
Modular Parts
2
Regency Freestanding Woodstove
TABLE OF CONTENTS
SAFETY LABEL
Safety Label for F2400 ..................................................4
Safety Label for S2400 ..................................................5
INSTALLATION
Unit Dimensions ............................................................6
Residential Installation ..................................................7
Modular Installation Options ..........................................7
Room Air ....................................................................... 8
Important .......................................................................8
Minimum Clearance to Combustible Materials ..............8
Stove Assembly Prior to Installation ............................10
Step-by-Step Chimney and Connector Installation ..... 11
Masonry Chimney .......................................................12
Masonry Fireplace .......................................................12
Factory Built Chimney .................................................12
Combustible Wall Chimney
Connector Pass-Throughs ..........................................13
Recommended Heights For Woodstove Flue ..............14
Mobile Home Installation ............................................. 15
Listed Components For Mobile Home Installation .......16
Flue Baffl e &Secondary Air Tube Installation .............. 16
Brick Installation ..........................................................17
Door Handle ................................................................17
Glass Installation ......................................................... 17
Step-by-Step Optional Accessories Installation ...........17
Screen Door ................................................................17
MAINTENANCE
Maintenance ................................................................21
Creosote ......................................................................21
Maintenance of Gold-plated Doors ..............................21
Latch Adjustment ......................................................... 21
Door Gasket ................................................................21
Glass Maintenance ......................................................21
Wood Storage ..............................................................21
PARTS LIST
F2400 Stove Main Assembly .......................................22
S2400 Step Stove Main Assembly .............................. 23
Pedestal, Bottom Shield & Leg Options ......................24
Firebrick .......................................................................25
WARRANTY
Warranty ......................................................................27
OPERATING INSTRUCTIONS
Operating Instructions .................................................19
Draft Control ................................................................ 19
First Fire ......................................................................19
Fan Operation .............................................................20
Ash Disposal ...............................................................20
Safety Guidelines and Warnings ................................. 20
Regency Freestanding Woodstove
3
SAFETY LABEL
This is a copy of the label that accompanies each Regency Freestanding Woodstove (F2400M). We have printed a copy of the contents here for your review.
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO SUITABLE FOR MOBILE HOME INSTALLATION
MODEL: REGENCY MEDIUM FREESTANDING STOVE - F2400M
TESTED TO: UL-1482 / ULC-S627-00 / UL-737 REPORT NO:219-S-02-2
THE F2400M MEETS UL737 STANDARD FOR FIREPLACE STOVES WHEN A FIRESCREEN IS PROVIDED.
F2400M WITH
AIRMATE SHIELD
F2400M WITH AIRMATE SHIELD F2400M WITHOUT AIRMATE SHIELD
MEASURE FLUE FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 406 mm / 16 in D 711 mm / 28 in BACKWALL B 280 mm / 11 in E 444 mm / 17.5 in CORNER C 152 mm / 6 in F 444 mm / 17.5 in
INSTALLATION USING LISTED DOUBLE WALL
SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 140 mm / 5.5 in E 304 mm / 12 in CORNER C 102 mm / 4 in F 393 mm / 15.5 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 140 mm / 5.5 in E 304 mm / 12 in CORNER C 102 mm / 4 in F 393 mm / 15.5 in
INSTALLATION USING LISTED DOUBLE WALL
SIDEWALL G 380 mm / 15 in I 685 mm / 27 in BACKWALL H 140 mm / 5.5in J 304 mm / 12 in
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT MAXIMUM ALCOVE DEPTH 915 MM / 36 IN. MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18" THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT COMBUSTION AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. RISK OF SMOKE AND FLAME SPILLAGE, OPERATE ONLY WITH DOORS FULLY OPEN OR FULLY CLOSED. IF INSTALLED IN A MOBILE HOME OPERATE ONLY WITH DOORS FULLY CLOSED - OPEN FEED DOOR TO FEED FIRE ONLY. WHEN OPERATED WITH DOORS OPEN THE MANUFACTURER SUPPLIED SCREEN MUST BE USED. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER OR CHIMNEY CONNECTOR GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH NEOCERAM GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL. OPTIONAL COMPONENT: FAN (846-515), ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS, SCREEN DOOR (846-101) DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE. COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM: SECURITY MODEL S2100, ICC EXCEL 2100, SELKIRK SENTINAL CF. IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA VENT MODEL DVL, GSW SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR METAL-FAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
F2400M WITHOUT AIRMATE SHIELD
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
SINGLE WALL CONNECTOR
CONNECTOR - MOBILE HOME
CONNECTOR - ALCOVE
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
SAFETY LABEL FOR F2400M
244
DO NOT REMOVE THIS LABEL
244
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA. USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK OR 26 MSG BLUED STEEL CONNECTOR WITH LISTED UL103 HT FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUELS OR MASONRY CHIMNEY. SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
MEASURE FLUE FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SIDEWALL A 457 mm / 18 in D 762 mm / 30 in BACKWALL B 305 mm / 12 in E 470 mm / 18.5 in CORNER C 165 mm / 6.5 in F 457 mm / 18 in
SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 165 mm / 6.5 in E 330 mm / 13 in CORNER C 152 mm / 6 in F 444 mm / 17.5in
SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 165 mm / 6.5in E 330 mm / 13 in CORNER C 152 mm / 6 in F 444 mm / 17.5 in
SIDEWALL G 380 mm / 15 in I 685 mm / 27 in BACKWALL H 165 mm / 6.5 in J 330 mm / 13 in
SINGLE WALL CONNECTOR
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
FLOOR
PROTECTION*
K 405 mm / 16 in L 150 mm / 6 in M 150 mm / 6 in
* In Canada, fl oor protection must
extend 18" (450mm) to the front and 8" (200mm) to each side and back of the stove.
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
MANUFACTURED BY: FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 VENTURE ST.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
DELTA, BC V4G 1H4
CERTIFIED TO COMPLY WITH JULY 1990
PARTICULATE EMISSION STANDARDS.
MADE IN CANADA
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
4
918-172c
Regency Freestanding Woodstove
DATE OF MANUFACTURE
2007 20092008
SAFETY LABEL
This is a copy of the label that accompanies each Regency Medium Freestanding Step Stove (S2400M). We have printed a copy of the contents here for your review.
SAFETY LABEL FOR S2400M
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO SUITABLE FOR MOBILE HOME INSTALLATION
MODEL: REGENCY MEDIUM FREESTANDING STEP STOVE - S2400M TESTED TO: UL-1482 / ULC-S627-00 / UL 737 REPORT NO: 219-S-02-2
THE S2400M MEETS UL737 STANDARD FOR FIREPLACE STOVES WHEN A FIRESCREEN IS PROVIDED.
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA. USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK OR 26 MSG BLUED STEEL CONNECTOR WITH LISTED UL103 HT FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUELS OR MASONRY CHIMNEY. SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE
S2400M
MEASURE FLUE FROM HEATER CENTER-LINE
SIDEWALL A 406 mm / 16 in D 711 mm / 28 in BACKWALL B 280 mm / 11 in E 444 mm / 17.5 in CORNER C 152 mm / 6 in F 444 mm / 17.5 in
INSTALLATION USING LISTED DOUBLE WALL
SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 140 mm / 5.5 in E 304 mm / 12 in CORNER C 102 mm / 4 in F 393 mm / 15.5 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
SIDEWALL A 380 mm / 15 in D 685 mm / 27 in BACKWALL B 140 mm / 5.5 in E 304 mm / 12 in CORNER C 102 mm / 4 in F 393 mm / 15.5 in
INSTALLATION USING LISTED DOUBLE WALL
SIDEWALL G 380 mm / 15 in I 685 mm / 27 in BACKWALL H 140 mm / 5.5in J 304 mm / 12 in
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT MAXIMUM ALCOVE DEPTH 915 MM / 36 IN. MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18" THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT COMBUSTION AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. RISK OF SMOKE AND FLAME SPILLAGE, OPERATE ONLY WITH DOORS FULLY OPEN OR FULLY CLOSED.
IF INSTALLED IN A MOBILE HOME OPERATE ONLY WITH DOORS FULLY CLOSED - OPEN FEED DOOR TO FEED FIRE ONLY. WHEN OPERATED WITH DOORS OPEN THE MANUFACTURER SUPPLIED SCREEN MUST BE USED. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER OR CHIMNEY CONNECTOR GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH NEOCERAM GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENT: FAN (846-515), ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS, SCREEN DOOR (846-101) DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE. COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM: SECURITY MODEL
S2100, ICC EXCEL 2100, SELKIRK SENTINAL CF. IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA VENT MODEL DVL, GSW
SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR METAL-FAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
S2400M MINIMUM CLEARANCES
TO COMBUSTIBLE MATERIALS
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
CONNECTOR - MOBILE HOME
CONNECTOR - ALCOVE
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
245
DO NOT REMOVE THIS LABEL
245
FLOOR
PROTECTION*
K 405 mm / 16 in L 150 mm / 6 in M 150 mm / 6 in
*In Canada, fl oor protection must extend
18" (450mm) to the front and 8" (200mm) to each side and back of the stove.
MANUFACTURED BY: FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 VENTURE ST. DELTA, BC V4G 1H4
CERTIFIED TO COMPLY WITH JULY 1990 PARTICULATE EMISSION STANDARDS.
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
MADE IN CANADA
Regency Freestanding Woodstove
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
918-203c
DATE OF MANUFACTURE
2007 20092008
5
INSTALLATION
UNIT DIMENSIONS
27-3/8” (695mm)
24-7/8” (632mm)
6-5/8”
(168mm)
(772mm)
30-3/8"
24” (610mm)
(740mm)
29-1/8"
6
Regency Freestanding Woodstove
INSTALLATION
RESIDENTIAL
INSTALLATION
1) Please read this entire manual before you
install and use your new woodstove. Failure to follow instructions may result in property damage, bodily injury or even death. Be aware that local Codes and Regulations may override some items in this manual. Check with your local inspector.
2) Select a position for your Regency Stove.
Consult the minimum clearance chart for your model and set the stove in place. For close clearance installation use listed double wall connector systems.
3) To insure vertical alignment, suspend a
plumb bob from the ceiling over the exact center of your stove fl ue and mark a spot on the ceiling to indicate the center of the chimney.
4) Check that the area above the ceiling is
clear for cutting. Re-confi rm the clearance from the stove to combustibles to insure that they are within the prescribed limits.
5) This woodstove must be connected to a
UL 103 HT (ULC S629) listed chimney or a code approved masonry chimney with a fl ue liner.
6) Install chimney according to chimney manu-
facturers instructions. The performance of your woodstove is governed to a very large part by the chimney system. Too short a chimney can cause diffi cult start-up, dirty glass, back smoking when door is open, and
even reduced heat output. Too tall a chimney may prompt excessive draft which can result in very short burn times and excessive heat output. The use of an inexpensive fl ue pipe damper may be helpful in reducing excessive draft.
CAUTION: The chimney should be the same
size as the 6" fl ue outlet on the stove. The chimney must be listed as suitable for use with solid fuels. For other types of chimneys check with your local building code offi cials. Do not confuse a chimney with a type “B” Venting System used for gas appliances as suitable for a wood burning appliance. For Mobile Home installations refer to that section within this manual.
7) Mark the location of the pedestal base or legs
on the fl oor, then move the stove aside and mark the position of the fl oor protector.
8) The fl oor protector must be of non-combus-
tible material and must extend 16" (406mm) in front of the door opening and 6" (152mm) to the sides and rear of the unit. Some areas may require a larger size fl oor protector. See your local inspector. For outside air installation refer to Mobile Home installation instructions within this manual.
NOTE: In Canada, fl oor protection must
extend 18" (450mm) to the front and 8" (200mm) to each side and back of the stove.
9) When the fl oor protection is complete, posi-
tion the stove with the fl ue collar centered under the installed chimney.
10) In seismically active areas, Regency rec-
ommends that your unit is secured to the fl oor by using the bolt down holes inside the pedestal (the same ones used in Mobile Home installations).
11) For residential installations using 6" "C"
Vent (single wall) the chimney connector must be at least 24 gauge steel. Do not use galvanized pipe. For Mobile Home instal­lation refer to the Mobile Home installation instructions within this manual.
12) Do not connect this unit to a chimney serving another appliance.
13) A chimney connector cannot pass through
an attic or roof space, closet or similar concealed space, or a fl oor, ceiling, wall or partition of combustible construction. In Canada, if passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365, Installation Code for Solid­Fuel-Burning Appliances and Equipment.
14) Your Regency Woodstove is not to be con­nected to any air distribution duct.
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
The following items are required when assembling your Regency Stove. F2400M unit - the Rear Heat Defl ector is supplied with the stove, but if
MODULAR INSTALLATION OPTIONS
you choose not to use it you must use the Airmate instead.
Modular Part
Clearances are different. See the Minimum Clearance to Combustible Materials chart in the Installation section of this
F2400M
Airmate OR
Rear Heat Defl ector
F2400M, S2400M
Pedestal OR
Legs
manual. Generally you can get closer clearances with the airmate than with the rear heat defl ector.
Convection heat with Airmate vs. Radiant Heat with Rear Heat Defl ector. The airmate pushes heat forward and into the room, the rear heat defl ector defl ects the heat upward. Refer to the Installation section within this manual.
There are no performance differences with either the pedestal or legs. It is primarily a personal preference. Legs can be either painted steel, painted cast, or gold plated cast.
Leg installation requires the bottom shield (refer to Leg and Bottom Shield Assembly, Installation section).
OPTIONS: These can be installed at time of installation or added later:
Modular Option
Blower/Fan
Ash Drawer Kit
Screen Door
Regency Freestanding Woodstove
Adding the blower will increase the area heated by the stove, it can move warm air beyond the room where the stove is installed (refer to Blower/Fan, Installation section).
Adding the Ash Drawer Kit makes cleaning ashes out of the stove easier and cleaner (refer to Bottom Shield Ash Drawer Kit, Installation section).
A simple add-on option that will allow you to enjoy the sound, warmth and view of an open fi re.
Things to consider when choosing options:
Things to consider when choosing options
7
INSTALLATION
ROOM AIR
IMPORTANT
For installation using room air for combustion, remove knockout from the pedestal, and/or from the bottom if using a heat shield.
Mobile home installations require the use of outside air.
On pedestal units there are two locations where outside air may be adapted to the unit. If us­ing the bottom of the pedestal, do not remove knockout from the rear of the pedestal. Only remove rear knockout if outside air will be brought in from the rear.
On leg units outside air can only be brought in from the bottom of the heat shield.
Note: Once the knockout is removed there
are two tabs remaining. Bend both tabs out for ease of installation when attaching outside air.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Please read the section below carefully as clearances depend on whether the airmate or the rear heat defl ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Clearances may only be reduced by means approved by the regulatory authority.
NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.
Residential Installation “C” Vent (Single Wall)
Unit From Unit From Corner From Flue Center-Line
A B C D E F
Medium F2400M with Airmate 16" (406 mm) 11" (279 mm) 6" (152 mm) 28" (710 mm) 17.5" (444 mm) 17.5" (444 mm) with Rear Defl ector 18" (457 mm) 12" (304 mm) 6.5" (165 mm) 30" (762 mm) 18.5" (469 mm) 19.5" (495 mm)
Medium S2400M Step Stove 16" (406 mm) 11" (279 mm) 6" (152 mm) 28" (710 mm) 17.5" (444 mm) 17.5" (444 mm)
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.
Unit From Unit From Corner From Flue Center-Line
A B C D E F
Medium F2400M with Airmate 15" (381 mm) 5.5" (139 mm) 4" (101 mm) 27" (685 mm) 12" (304 mm) 15.5" (393 mm) with Rear Defl ector 15" (381 mm) 6.5" (165 mm) 6" (152 mm) 27" (685 mm) 13" (330 mm) 17.5" (444 mm)
Medium S2400M Step Stove 15" (381 mm) 5.5" (139 mm) 4" (101 mm) 27" (685 mm) 12" (304 mm) 15.5" (393 mm)
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit From Unit From Corner From Flue Center-Line
A B C D E F
Medium F2400M with Airmate 15" (381 mm) 5.5" (139 mm) 4" (101 mm) 27" (685 mm) 12" (304 mm) 15.5" (393 mm) with Rear Defl ector 15" (381 mm) 6.5" (165 mm) 6" (152 mm) 27" (685 mm) 13" (330 mm) 17.5" (444 mm)
Medium S2400M Step Stove 15" (381 mm) 5.5" (139 mm) 4" (101 mm) 27" (685 mm) 12" (304 mm) 15.5" (393 mm)
8
Regency Freestanding Woodstove
INSTALLATION
Minimum Alcove Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84" Maximum depth of alcove - 36"
From From Flue Min. Min.Hearth
Unit Unit Center-line Width to Rear Wall
G H I J K L
Medium F2400M with Airmate 15" (381 mm) 5.5" (139 mm) 27" (685 mm) 12" (304 mm) 54" (1371 mm) 48" (1219 mm) with Rear Defl ector 15" (381 mm) 6.5" (165 mm) 27" (685 mm) 13" (330 mm) 54" (1371 mm) 49" (1244 mm)
Medium S2400M Step Stove 15" (381 mm) 5.5" (139 mm) 27" (685 mm) 12" (304 mm) 54" (1371 mm) 48" (1219 mm)
Floor Protection
A combustible fl oor must be protected by non-combustible material (like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local codes) extending beneath the heater and a minimum of 6" (152mm) from each side and minimum 16" (406mm) from the front face of the stove and minimum 6" (or the rear clearance to combustibles whichever is smaller) from the rear of the stove.
When installed with horizontal venting, non-combustible fl oor protection must beneath the fl ue pipe and extend 2" (51mm) beyond each side.
Minimum Overall Width (X) of Floor Protector for all installations:
Stove F2400M 36" (914 mm)
Step Stove S2400M 36" (914 mm)
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove Unit "C" Vent Close Clearance Close Clearance
Y Z Y Z Y Z Y Z Medium F2400M with Airmate 46" (1168 mm) 6" (152 mm) 45"* (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45"* (1143) 5" (127 mm) with Rear Defl ector 46" (1168 mm) 6" (152 mm) 45" (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45" (1143) 5" (127 mm)
Medium S2400M 46" (1168 mm) 6" (152 mm) 45"* (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45"* (1143) 5" (127 mm)
- Step Stove
NOTE: In Canada, fl oor protection must extend 18" (450mm) to the
front and 8" (200mm) to each side and back of the stove.
*The rear clearance to combustibles is less than 6" (, for corner installations the rear corners may be angled to take advantage of the closer clear­ances.
Regency Freestanding Woodstove
9
Loading...
+ 19 hidden pages